Professional Documents
Culture Documents
http://www.060.es
NIPO: In process
ROYAL DECREE 997/2002, of September 27, approving the Seismic-resistant
Construction Standard: General part and building (NCSE-02)
I HAVE:
The scope of the standard extends to all construction projects and works related to
building, and, as appropriate, to other types of constructions, as long as they are not
approved for the same standards or provisions. specific with seismic-resistant content
prescriptions.
The projects started prior to the entry into force of this Royal Decree, as well as the
works carried out in their development, and those that were in execution, will be governed by
the Standard until now in force.
3
Transitional provision one-time adaptation period normative.
The projects and constructions of new buildings and other works may be adjusted,
during a period of two years from the entry into force of this Royal Decree, to the content of
the Standard until now in force or to the one approved by this Royal Decree , unless the
competent Public Administration for the approval of the same agrees the obligation of the
latter.
The Minister of Public Works is empowered to issue the necessary provisions for the
development and application of the provisions of this Royal Decree.
This Royal Decree will enter into force the day following its publication in the Official
State Gazette.
JUAN CARLOS R.
4
ANNEXED
1.1. Object
The purpose of this Standard is to provide the criteria to be followed within Spanish
territory for the consideration of seismic action in the project, construction, reform and
conservation of those buildings and works to which it is applicable according to with the
provisions of article 1.2.
The ultimate purpose of these criteria is to avoid the loss of human life and reduce the
damage and economic cost that future earthquakes may cause. The developer may require
benefits greater than those required in this Standard, for example the maintenance of the
functionality of essential services.
The achievement of the objectives of this Standard is conditioned, on the one hand, by
the limiting precepts of land use dictated by the competent Public Administrations, as well as
by the calculation and design specified in the following chapters, and on the other, for the
realization of an adequate execution and conservation.
7
1.2.2. Classification of constructions
For the purposes of this Standard, in accordance with the use to which they are
intended, with the damage that their destruction may cause and regardless of the type of
work in question, constructions are classified as:
1. Of moderate importance
Those with a negligible probability that their destruction by the earthquake could
cause victims, interrupt a primary service, or produce significant economic damage
to third parties.
2. Of normal importance
Those whose destruction by the earthquake can cause victims, interrupt a service
for the community, or produce significant economic losses, without in any case
being an essential service or leading to catastrophic effects.
3. Of special importance
Those whose destruction due to the earthquake could interrupt an essential service
or lead to catastrophic effects. This group includes the constructions that are
considered in this way in urban planning and similar public documents, as well as in
more specific regulations and, at least, the following constructions:
— Hospitals, centers or health facilities of some importance.
— Buildings and basic facilities for communications, radio, television, telephone
and telegraph exchanges.
— Buildings for organization centers and coordination of functions for disasters.
— Buildings for personnel and relief teams, such as fire brigades, police, armed
forces, and machinery and ambulance parks.
— The constructions for basic installations of the towns such as water, gas, fuel
tanks, pumping stations, distribution networks, power plants and transformation
centers.
— Structures belonging to communication routes such as bridges, walls, etc. that
are classified as of special importance in the regulations or specific provisions of
road and rail bridges.
— Vital transportation buildings and facilities at railway stations, airports and ports.
— Buildings and industrial facilities included in the scope of application of Royal
Decree 1254/1999, of July 16, which approves measures to control the risks
inherent to serious accidents involving dangerous substances.
— Large civil engineering constructions such as nuclear or thermal power plants,
large dams and those dams that, depending on the potential risk that may arise
from their possible failure or incorrect operation, are classified in categories A or
B of the Technical Regulations. on Safety of Dams and Reservoirs in force.
— Constructions classified as historical or artistic monuments, or of cultural or
similar interest, by the competent bodies of the Public Administrations.
— Constructions for public performances and large commercial areas, in which a
massive occupation of people is expected.
8
- In constructions of normal importance with frames well braced together in all directions
when the basic seismic acceleration ab (art. 2.1) is less than 0.08g. However, the
Standard will apply to buildings with more than seven floors if the calculation seismic
acceleration, ac, (art. 2.2) is equal to or greater than 0.08g.
If the basic seismic acceleration is equal to or greater than 0.04g, the possible effects of
the earthquake on potentially unstable terrain must be taken into account.
In the cases in which this Standard is applicable, dry masonry, adobe or mud brick
structures will not be used in buildings of normal or special importance.
If the basic seismic acceleration is equal to or greater than 0.08g and less than 0.12g,
the buildings made of brick, mortar blocks, or similar, will have a maximum of four heights,
and if said basic seismic acceleration is equal to or greater than 0.12g, a maximum of two.
In buildings where it is to be applied, this Standard requires:
— Calculate the construction for the seismic action defined in chapter 2, using the
procedures described in chapter 3.
— Comply with the design rules and construction regulations indicated in chapter 4.
If the project manager does not agree with the content of the section on "Seismic
Actions", he will report to the Owner, and where appropriate, will propose the need to carry
out the project modifications that he deems appropriate, which will be developed and, for
approval, they will undergo the same procedure as the original project.
In addition, in important works with delays or very long stops, the project manager must
take into account the seismic actions that may occur and that, in the event of destruction or
damage by earthquake, could lead to serious consequences.
The project manager will check that the prescriptions and structural details shown in the
plans meet the specified ductility levels and that they are respected during the execution of
the work.
9
1.3.3. Compliance with the Standard during the useful life period
Comments
10
the designer - or where appropriate
the developer - can decide to apply
the Standard, especially in the case
of tall buildings situated
11
two on soft or very soft ground, since in these cables; provisions and requirements to which it
cases it is appropriate to follow the isStandard complements.
prescriptions of the Standard, especially those
corresponding to the foundations.
The prohibition of masonry structures in dry, C.1.3.1. Compliance with the Standard in the
made of mud or adobe, for buildings of normal phase of draft
or special importance, when the basic seismic
acceleration is equal to or greater than 0.04g, it C.1.3.2. Compliance with the Standard in the
is due to the high vulnerability of these phase of building
constructions, as has been proven in a large
number of earthquakes, which which prevents C.1.3.3. Compliance with the Standard
the provision of proper security guarantees and during shelf life
this would lead to noncompliance with the
essential purpose of the Standard, which is to Since sometimes seemingly minor flaws or
avoid the loss of human life. damage can be the indication This is why, when
The greater imprecision of the calculation models a high intensity earthquake occurs, all
used lized for The masonry works and their damaged or potentially damaged buildings
fragility make it advisable to generally restrict must be inspected, at least those located in
the height of these buildings in areas of high areas with intensity equal to or greater than VII
seismicity. Furthermore, it is convenient to (EMS-98 scale ), and make a report on each
confine the factory with horizontal and vertical construction, giving a higher priority to those
elements. classified as of special importance, since these
Among the destabilizing effects of the are the most necessary for the community after
earthquake on the ground are permanent a seismic disaster, followed by those classified
ground displacements, slope or slope as of normal importance.
movements, liquefaction (or liquefaction) of The report to be carried out on each damaged or
saturated loose granular soils, etc. potentially damaged construction aims to identify
the damaged elements and parts, as well as the
type and degree of said damage, after an
C.1.2.4. General requirements acknowledgment of the consequences of the
earthquake on said construction, and a first
further of the general prescriptions determined estimate is made- information on the degree of
in the articles, the elastic response spectrum security of the same and the type of preventive
defined in Article 2.3 can be adopted in measures that, where appropriate, should be
general. However, for different constructions of adopted. The objective is to detect
the building, different elastic response spectra constructions (especially those of special and
may be used, which will be included in specific normal importance) with serious structural
standards or provisions, or will be studied and damage that could collapse as a consequence
justified appropriately. of the occurrence of relevant aftershocks of the
main earthquake.
Therefore, local authorities should take care that, in
C.1.3. Compliance with the Standard the aforementioned cases and in the shortest
possible time, the constructions that may have
It is assumed that the project, construction and suffered damage be recognized, estimating the
conservation of the building will be carried out by degree of safety and service of the key
duly qualified and experienced personnel, also facilities, as well as that of the constructions of
complying with all the provisions and requirements special and normal importance .
prescribed in those standards and instructions that The EMS-98 intensity scale (European Macrosismic
by the materials used and by the type, structural Scale) is the updated version of the scale MSK,
disposition or destination of the works are applied cited in the NCSE-94 standard.
11
CHAPTER II
SEISMIC INFORMATION
ac = S ab
where:
ab Basic seismic acceleration defined in 2.1.
Dimensionless risk coefficient, a function of the acceptable probability that
exceeds ac in the life period for which the construction is projected. It takes the
following values:
— constructions of normal importance = 1.0.
— constructions of special importance = 1.3.
S Coefficient of amplification of the terrain. Take the value:
- For ab " 0.1g
S=C
1.25
13
- For 0.4g " · tob
S = 1.0
being:
C Terrain coefficient. It depends on the geotechnical characteristics of the foundation ground
and is detailed in section 2.4.
0.08
1.2
1.1
1.2
1.3
1.3 1.1
1.21.0
1.3
0, 05
ab "
0.16g 0.12g "
0.08
ab <0.16g
0.08g " ab
<0.12g
0.04g " ab
<0.08g
ab <0.04g
Contribution
coefficient K
Figure 2.1 Hazard Map Seismic
14
TA, TB Characteristic periods of the response spectrum, of values:
TTO = KC / 10
TB = KC / 2.5
(
)
2.0
1.0
0
0 TA TB Oscillation period, T
For some structures and modes of vibration with periods longer than 4 seconds, the
designer may use, whenever justified, spectral values lower than those predicted by the
previous expressions.
TABLE 2.1.
Terrain coefficients
I 1.0
II 1.3
III 1.6
IV 2.0
To obtain the value of the calculation coefficient C, the thicknesses e1, e2, e3 and e4 of
land types I, II, III and IV respectively, existing in the first 30 meters below the surface, will
be determined.
The mean value obtained by weighting the Ci coefficients of each stratum with its
thickness ei, in meters, will be adopted as the value of C, using the expression:
C=
Ci ei
30
15
In buildings with basements below the general ground surface level, the thickness of
the different layers to classify the foundation conditions should normally be measured from
the grade.
In those special cases where C> 1.8 results, the response spectrum defined with the
previous rules may not be applicable to constructions with a fundamental period greater than
TB. In this case, for T> TB we will take (T) = 2.5 unless a site-specific response spectrum
is determined, whose ordinates will in no case be less than those obtained with the
procedure described in section 2.3.
The coefficient C does not take into account the possible collapse of the ground under
the structure during the earthquake due to the instability of the ground as in the case of
sensitive clays, soil densification, subsidence of underground cavities, slope movements,
etc. In particular, the possibility of liquefaction (or liquefaction) of soils susceptible to it must
be analyzed.
Comments
C.2.1. Seismic hazard map. Basic The values of the basic seismic acceleration
seismic acceleration correspond to a return period of approximately
500 years. The return period, PR, is not a physical
Basic seismic acceleration has dimensions of time of recurrence, but corresponds to an
acceleration. If you want to obtain its numerical interpretation from the probabilistic point of view
value in m / s2, you can multiply the value that is and is associates with a given probability
deducedfrom the map in units of g times 9.8, fractile in the probability distribution of the
since we have taken g = 9.8 m / s2. maximum potential accelerations (annual). Said
The calculation of the seismic danger has been value corresponds in this case to an annual
carried out in terms of EMS intensity, based on exceedance probability of two per thousand (1 /
updated data in the seismic catalog of the PR) that the seismic acceleration potential
National Geographic Institute. To determine the (annual) is exceeded.
characteristic horizontal acceleration from the The horizontal acceleration corresponding to a
EMS intensity, the correlation was used: period return do PR, can be obtained at each
point of the territory, approximately, multiplying
log10 to = 0.30103I - 0.2321 by (PR/ 500) 0.4 the value that is deduced from
the map in Figure 2.1 for that site.
where a is expressed in gals (10–2 m / s2).
The procedure for calculating the basic seismic
C.2.2. Calculation seismic acceleration
acceleration through intensity leads to “regional”
values of the average acceleration for the The seismic acceleration calculation, at c, has —
different types of seismicity and local conditions same than the basic one— dimensions of
involved in the starting data. It is possible that acceleration.
certain particular earthquakes or certain local The coefficient expresses —for the usual
conditions would have required specific range of probabilities of overcoming the
correlationsto obtain the basic seismic seismic actions to be considered in the
acceleration. earthquake resistant project— values
proportional to the accelerations resulting from
the calculation of the seismic danger.
16
The coefficient S takes into account the influence the shape and ordinates of the response
difference in surface seismic acceleration with spectrum is very complex. A simplified formulation
respect to that of hard soil, depending on the has been adopted in this Standard, the precision
existence of soft surface layers of soil (Table of which, in relation to the available data, is
C.2.1). Furthermore, for low accelerations, the considered sufficient. The spectrum is defined as
acceleration is generally greater on the surface a function of the foundation terrain and the
of soil deposits than in hard soil or rock differentiating characteristics of the seismicity of
outcrops (amplification phenomenon). For high the Azores-Gibraltar area, the influence of which
accelerations (usually for atb " 0.4g) this trend is is introduced through thecoefficients C and K,
not clear and it has even been observed that it respectively.
can be reversed, due to non-linear behavior In the range of periods of interest, for the most
ground (deamplification phenomenon). common constructions, the elastic response
The expressions of the articles propose that for spectrum can be divided into three
one ab " 0.1 g, the seismic acceleration at characteristic sections:
the surface of the softer deposits is twice the
acceleration in rock. However, for a — The segment corresponding to high periods
· tob " 0.4g, it is proposed that the calculation (T> TB), defined by a constant spectral
seismic acceleration is the same in soil as in velocity, whose value, as a function of the
rock. For intermediate values, it is interpolated seismic acceleration, a, of the ground
between the two. surface is:
Because the values of ab are associated with a TB
hard ground (approximately type II), the Sv , m = 2.5a
coefficient S produces a correction in the product 2
· ab, decreasing it when the terrain is good and
increasing-
pain when it is soft or very soft. oscillator T.
Full consideration of all factors that
TABLE C 2.1
S coefficient values
17
— The intermediate section (TTO " T " TB)
defined by a constant spectral acceleration,
conventionally set at 2.5 times the acceleration
of the ground surface, that is:
Sv , m 2.5a
18
GOOD GROUND:
K = 1 C = 1.15
(
NORMAL TERRAIN: K
) = 1 C = 1.30
SOFT SOIL: K = 1
C = 1.70
2.0
1.0
0
0 0.5 1.0 1.5 seconds
OSCILLATION PERIOD, T
real coughs has shown that for periods tall, greater than 2,000 m / s, more than 50 strokes in
spectral velocity is less than Sv, mIn many the SPT test normalized to 60% of the free fall
cases, it can be considered, in a simplified way, energy or a pointed resistance of the static
that the spectral shift is constant or, what is the penetrometer greater than 20 MPa (200 kp /
same, that the spectral acceleration is inversely cm2).
proportional to the square of the period. Type II soils usually have as characteristics:
longitudinal elastic wave velocity greater than
1,000 m / s, the granular ones more than 40
C.2.4. Land classification. Coefficientof strokes in SPT tests normalized to 60% of the
the land energy of free fall or resistance at the tip of the
static penetrometer greater than 15 MPa (150
The terrain is characterized by a numerical kp / cm2). Hard cohesive soils typically have
value, C, based on the characteristics of the simple compressive strengths greater than 500
different layers that compose it. kPa (5 kp / cm2). Type III soils usually have as
For the classification of the different layers of the characteristics: granular ones more than 15
earth no, in the articulated we use the speed of blows in SPT tests normalized to 60% of the
the transverse elastic waves, vS. energy of free fall or resistance at the tip of the
For determining the thickness of each static penetrometer greater than 6 MPa (60 kp /
layer and for its approximate classification, when cm2). Cohesive soils with a firm to very firm
specific determinations of v S, the procedures consistency usually have a single compressive
described in the NTE-CEG, Foundations: strength greater than 200 kPa (2 kp / cm2).
Geotechnical Studies can be used. In granular Any layer of land not classifiable as I, II or III
soils, static or dynamic penetration tests; in must be taken as IV.
cohesive soils, the resistance to simple The response spectrum that is formulated in
compression and in all of them, the speed of section 2.3 is considered sufficiently approximate
propagation of long elastic wavesgitudinal. for the most usual terrain conditions, provided that
In many cases, it will not be necessary for the the soil formations are extensive in plan in relation
reconnaissance of the terrain to reach a depth of to the dimensions of the construction. However,
30 m, being sufficient to determine the thickness there may be some special cases in which the
of the surface layers and the depth of the roof of application of this spectrumIt is not suitable, for
the type I terrain. In general, it will be sufficiently example when there are very soft clay layers or
safe. assume that ground not reached in non-compacted artificial fillings or when the
recognition it will be no worse than the deepest thickness of the type IV soil is high. Normally
one for which information is available. Usually, the representative spectra of these situations
once the type I terrain has been reached, the will have higher values of Sto in the periods
appearance of layers of terrain of the other close to the period of the type IV soil layer. On
types at greater depth is not expected. the contrary, certain types of works, such as
Knowledge of the geology of the area or the some large civil engineering constructions, may
results of other upcoming surveys will be require foundation grounds of a «higher
particularly informative in this regard. hardness» than the types established in this
In case of doubt, and especially with insufficient Standard, which also makes it possible to
data, the corresponding values should be adopt other spectra elastic response, which will
adopted on the safety side. appear, where appropriate, in the
Type I soils usually have the following corresponding specific rules.
characteristics: longitudinal elastic wave speed For the analysis of liquefaction or liquefaction of
soils susceptible to it, the method can be used
detailed in C.4.3.1.
19
C.2.5. Modification of the elastic response C.2.6. Elastic response spectrum for
spectrum as a function of damping vertical movements
Critical damping is understood as the lowest The increase in vertical load due to seismic action
damping value for which a linear oscillator returns can have an impact on horizontal structural
— once displaced — to the equilibrium point elements with a large span, cantilevers or beams
without exceeding it and, therefore, without that support columns. In the case of prestressed
continuing. the swing. horizontal elements, a decrease in vertical load
caused by the earthquake could damage them. In
general, in buildings it is not necessary to take it
into account.
19
CHAPTER III
CALCULATION
3.1. Generalities
The purpose of the earthquake-resistant calculation is to verify the safety of the
constructions against the seismic actions that may act on them during their useful life.
To this end, the Standard provides the criteria for determining:
— the masses of the building to be considered in the calculation,
— the periods and modes of vibration of the structure.
— the response of the structure to seismic actions resulting from the application of
chapter 2
— verification of the safety of the structure.
In general, the calculation methods in this chapter refer to buildings
cios.
21
3.3. Actions that are considered in the calculation
Those that are indicated in the NBE-AE-88: Actions in the Building, or regulation that at
any time replaces it.
The simplified calculation method can be applied in buildings that meet the following
requirements:
1. The number of floors above ground is less than twenty.
2. The height of the building above ground is less than sixty meters.
3. There is geometric regularity in plan and elevation, without significant recesses or
projections.
4. It has continuous supports up to the foundation, uniformly distributed in plan and
without sudden changes in its rigidity.
5. Has of mechanical regularity in the distribution of stiffness, resistance and masses,
so that the centers of gravity and torsion of all the plants are located,
approximately, in the same vertical.
6. The eccentricity of the center of the masses involved in the seismic calculation with
respect to the torsion calculation is less than 10% of the plan dimension of the
building in each of the main directions.
22
Similarly, the simplified calculation method could be applied to apartment buildings of
normal importance (section 1.2.2) with up to four floors in total.
The dynamic study, carried out in the domain of time or frequency, must be made from
accelerograms representative of the movement of the ground. For this, it is necessary to
conveniently scale the chosen accelerograms —in time and amplitudes— so that they are
compatible with the seismic information in chapter 2. Specifically, it must be with the elastic
response spectrum and with the seismic acceleration. calculation.
Both real modulated and artificial accelerograms can be used, justifying in any case
their structure in the time domain, their frequency content and their duration, according to the
characteristics of the calculation earthquake.
The calculations must be made from a representative number of different earthquakes,
which will be at least 5, adopting as calculation request the average of the characteristic
values obtained with each one.
For each earthquake, the spatial response of the structure will be determined by three
independent accelerograms acting in the three main directions of the structure with an
equivalent linear elastic model or with a non-linear model. In both cases, the behavioral laws
adopted for the materials must be duly justified.
This method uses the response spectrum defined in this Standard and requires the
weighted combination of the stresses from each vibration mode of the construction.
For each direction in which the seismic action is considered, the maximum equivalent
displacements uij, max for the vibration mode i, corresponding to each degree of freedom j,
assumed in the equivalent linear model of the structure, are given by :
where:
23
being:
aij, max Component of the acceleration vector associated with the vibration mode i,
corresponding to the degree of freedom j.
Natural frequency of the vibration mode i ( i = 2 / Ti).
Value coefficient:
The maximum displacement, for each mode and each floor, will be calculated by
multiplying the maximum equivalent displacement, calculated by the previous procedure, by
the coefficient of behavior by ductility .
In each case, the number of vibration modes with a significant contribution to the result
will be considered, and at least the following will be considered:
— three modes in the case of flat models of floor structures (Figure 3.1).
— four modes in the case of spatial structure models, two translational and two
rotational.
— all modes of period greater than TTO (section 2.3).
Fk k or2k or3k
or1 H
k
2 hk
24
3.6.2.3.2. Calculation of the modal characteristics of the construction
The characteristics of the construction (proper period and shape coefficient of each
mode of vibration, and damping) will be determined by one of the following procedures, in
order of preference:
The combination of the results obtained in the analysis of the different modes of
vibration must be carried out for every variable associated with each assumed degree of
freedom (displacements, stresses, stresses, etc.). If S represents the variable to be
calculated and If its value in mode i, the combination rule - assuming that the periods of the
modes differ by more than 10% - is:
r
S= Si 2
i =
where r is the number of modes that make a significant contribution to the result.
If there are modes of vibration whose periods differ by less than 10%, the previous rule
can be applied by grouping in a single variable Sj the sum of the absolute values of the
variables Si that differ less than 10% from each other.
The method requires a weighted combination of the stresses from each mode of
vibration of the structure.
The distribution of the stresses —and consequently of the stresses— is obtained from
the variables S, obtained from the combination of modes, according to the discrete model
that translates the real structure.
In particular, in apartment buildings where three degrees of freedom per floor have
been adopted, the overall floor stresses will be assigned to each element in proportion to the
components used to determine the center of rotation.
If two orthogonal plane models have been used, the assignment of the loads will be
made taking into account the torsions caused by the eccentricity of the masses defined in
3.2.
The relevance of the analysis of second order effects should be considered, according
to the importance of the displacements obtained.
The constructions that meet the requirements established in section 3.5.1 may be
assimilated to a one-dimensional model consisting of a multiple oscillator with only one
degree of freedom of movement per floor. Its analysis is carried out, in this simplified
method, from a system of horizontal forces equivalent to that of earthquakes.
25
3.7.2. Vibration modes
For the consideration of the effects of the different modes, the following relationships
between the periods of mode i, Ti, and of the fundamental mode, TF are accepted:
TF
You =
(2i
1)
2
H
LB
TF = 0.06H H / (2L / L
H)
2. Buildings with reinforced concrete frames without the collaboration of stiffening
screens.
TF = 0.09n
TF = 0.07n H / (B
H)
4. Rigid rolled steel frame buildings.
TF = 0.11n
26
5. Rolled steel frame buildings with strong triangulated planes.
TF = 0.085n H / (B
H)
being:
For the rest of the buildings with up to four floors, TF = 0.3 seconds can be taken for
calculation purposes using the simplified method.
The equivalent static seismic force, Fik, corresponding to plant k and mode of vibration i,
is given by
Fik = yes Pk
where:
being:
ac Calculation seismic acceleration determined in section 2.2, expressed in m / s2.
g Acceleration of gravity, also expressed in m / s2.
Response coefficient, defined in section 3.7.3.1.
Distribution factor corresponding to plant k, in mode i, defined in section 3.7.3.2.
Value coefficient (Figure 3.3):
— To Ti " TB = 2.5
— To Ti > TB = 2.5 (TB / Ti )
Ti Period of the considered mode.
TB Characteristic period of the spectrum defined in 2.3.
2.0
1.0
0
0 TB Period of oscillation, Ti
27
3.7.3.1. Response coefficient
It is expressed by
=v
being:
The behavior coefficient for ductility depends on the organization, material and
construction details.
The designer will choose the ductility behavior coefficient for each calculation model
within the limitations established in the following paragraphs based on the structural
organization and the materials used, and will provide the structural details established in
chapter 4 that guarantee the ductility adopted.
Figure 3.4 Examples of structural organizations that allow a value of the coefficient
behavior by ductility = 4
4. The dimensioning and detail must ensure the formation of stable mechanisms
with a very high energy dissipation capacity through hysteresis,
homogeneously distributed throughout the structure. For this, the prescriptions
established in Chapter 4 for this level of ductility must be met.
28
1. Resistance to horizontal actions is mainly achieved (Figure 3.5):
Figure 3.5 Examples of structural organizations that allow a value of the coefficient
behavior by ductility = 3
Also included in this group are structural systems constituted, either by metal
frames that confine to reinforced concrete or reinforced masonry walls, or by load-
bearing concrete or mortar blocks, vertically and horizontally reinforced and with
sufficient stable plastic deformation capacity under cyclical and alternating lateral
actions.
Figure 3.6 Examples of structural organizations that allow a value of the coefficient
behavior by ductility = 2
29
plastic, in particular those made up of masonry, brick or concrete block walls, even
when they include wooden frameworks inside or are reinforced or reinforced only at
critical points, and arcades that resist lateral actions by means of bracing in the
form of « K »(Figure 3.7).
Also included in this group are the structures of industrial buildings with pillars and
trusses, those made with prefabricated elements or containing large-format
prefabricated pieces, in which no special provisions have been adopted to provide
the nodes with ductility.
Figure 3.7 Examples of structural organizations that allow a value of the coefficient
behavior by ductility = 1
In the evaluation of the vertical component of the seismic action, a ductility behavior
coefficient = 1 will be adopted, unless a higher value is justified by the corresponding
analysis.
Table 3.1 provides for the most frequent building cases the values of the response
coefficient , depending on the type of structure, the compartmentalisation of the floors, the
damping, , and the ductility behavior coefficient.
TABLE 3.1.
Response coefficient values
Coefficient of
behavior by
Plant No ductility
Structure type (%) ductility
compartmentalis ( = 1)
ation
=4 =3 =2
The value of the distribution factor, ik, corresponding to plant k in vibration mode i has
the value:
mk ik
ik = ik k =
n
mk
ik
k =
30
where (see figure 3.1):
n Number of plants.
mk Mass of plant k, defined in 3.2.
adopt the following approximate expression:
where:
hk Height above ground of the plant k.
H Total height of the building structure.
3.7.3.3. Displacements
The horizontal displacement, u, in the direction that may imply collision with neighboring
structures will be determined taking into account the post-tellastic behavior by means of the
expression:
or = EU
where:
EU Equivalent linear displacement, calculated in elastic regime.
Coefficient of behavior due to ductility defined in section 3.6.2.2.
The system of equivalent static forces Fk, necessary for the analysis of the structure in
the face of the earthquake in the direction considered, is obtained from the forces Fik, as
follows:
— Obtaining the shear Vik of each plant k in mode i, as the sum of the Fik
existing between the top floor and floor k considered.
— Obtaining the combined shear Vk of plant k for the different modes i considered by
means of the expression:
r
Vk = Vi k2
i =
K
kj j =
being:
Kkj Rigidity of each resistant element j in the direction of the force considered.
31
3.7.5. Consideration of rotation effects
t = 1 + 0.6 x
o You
being:
x The distance of the element considered to be from the center of the building,
measured perpendicular to the direction of the considered seismic action (Figure
3.8).
You The distance between the two most extreme resistant elements, measured in the
same way.
In buildings with flats of up to four floors in which the simplified method is applicable, but
do not meet the regularity conditions of section 3.5.1, a special study of torsion effects will be
required.
F
F
being:
Pk Total gravitational load above the plant, calculated according to section 3.2.
dk Relative displacement between the head and foot of the supports of the plant
considered, calculated according to 3.7.3.3.
Vk Combined shear corresponding to the plant.
hk Height between plants.
32
Comments
C.3.1. Generalities ne the seismic action included in the special
standards current citations are as follows:
C.3.2. Masses involved in the calculation
1. Concrete (EHE, article 13.2)
The fraction of the variable masses considered in
the articles correspond to what is globally
Ultimate limit states, seismic situations:
expected to be simultaneous with the
earthquake. Nor-
badly, the mass considered in the seismic
calculation is less than that produced by the G, j Gk , + G *, jGk*,j + pPk +
vertical load in the static hypotheses. j "1 j j "1
33
3. Brickwork (NBE-FL 90, case III, table 2.3), by the response coefficient (section
5.5) 3.7.3.1) and by the total mass of the building,
including that corresponding to the concomitant
actions (section 3.2), it represents a good
Weighting coefficient with estimate of the total horizontal seismic force.
action effects As a safe approximation, and in the absence of
Share class terrain data, 2.5 can be taken as the spectrum
Unfavorable Favorable value. Regarding the evaluation of local
stresses in buildings, in most cases it is
With loads 1.00 1.00 sufficiently approximate to distribute the total
Use overloads 1.00 0 seismic action, arranging it at each point of
Snow overload 0.50 0 each floor of the building in proportion to its
Ground thrusts 1.25 1.00 mass and height, taking into account it also
Support seats Discretionary 0 takes into account the eccentricities and the
Wind Actions 0.50 0 precautions in respect of sections 3.2 and
Thermal and Discretionary 0 3.7.5.
rheological
Seismic actions 1.00 0
L L
<L / 10
<B /
10
< L / 10 B
B
<B / 10
<B /
10
OUTLETS ENTRY
34
<L/
10
<L / <L /
10 4
<L /
15
>H/
6 <H /
6
LLL
OUTGOING STARTERS LOW BODIES
35
The maximum equivalent displacement corresponds n 2
38
An adequate ductile behavior should allow the e) Storey buildings with steel supports and
dissipation of a good part of the energy that the beams in both directions, with rigid knots,
system It contributes to the structure through a slabs of concrete.
large number of stable and well distributed
hysteresis mechanisms throughout it. — With diagonal triangulations: = 2.
Furthermore, the flexural failure modes must — With triangulations (cross of S. Andrés):
precede the shear failure modes. In this way, it = 3.
is possible to avoid the progressive collapse of — Without triangulations and with rigid
the structure when one of the elements fails. ductile knots two: = 4.
In general, steel provides greater ductility than
concrete and this more than brick or stone. f) ) Floor buildings with metal supports and
Regarding the structural type, ductility is solid slab slabs, alveolated (waffle) or
greater in movable structures such as frames, unidirectional with flat beams, with or
than in wall or triangulated ones, but provided without bracing: = 2.
that at the critical points - the nodes - there is g) Floor buildings with concrete supports and
sufficient capacity to allow significant one-way slab on edge beams:
deformations. constant demand.
It is important to ensure that burnout occurs It — In the direction of the floor: = 2.
occurs earlier in the beam than in the support, — In the direction of the beams: = 3 or 4.
since the ductility or energy dissipation
capacity occurs better in the bent sections than h) Storey buildings with rigid knots, with support
in those that are simultaneously compressed. concrete tees, edge beams in both
Furthermore, in this way, the crushing of the directions and concrete slabs supported on
pillars and the stacking of the floors are their four edges on the beams, with or
avoided. without screens: = 3 or 4.
They are called coupled screens which, belonging i) Floor buildings with concrete supports and
to the same plane, are joined at the level of each solid slab, alveolate (waffle) or
floor by a regular pattern of short ductile beams unidirectional slabs with flat beams, with or
capable of reducing at least the order of 25% the without screens: = 2.
sum of the bending moments of each of the j) Assimilable structures Inverted pendulum,
screens working separately. such as industrial buildings, sports centers,
A beam is considered to be deep when its drop stations, pavilions, supermarkets, canopies,
below the lower plane of the slab or floor is etc., with recessed supports ductilely at the
greater than the depth of the compressed head base: = 2.
(figures 4.4 and 4.5).
The energy dissipation is minimal in vertical If the resistant structure is made up of frames
movements, hence the value = 1 must be —Whether or not they have the complement of
adopted. screens or rigid cores—, in order to consider it as
The following are some of the most common having high or very high ductility, it must be
construction types in Spain and their maximum observed that the floor is not flat, in particular that
values of the ductility behavior coefficient . In order it is not formed by slabs or reticulated or
to use values of " 2 the prescriptions of chapter 4 unidirectional floors of constant depth, but rather
that apply to them must also be observed. put. has drop beams. It is noted that if there are
beams in one directionand slab or slab on the
a) Brick factory bearing wall buildings Ilo or other, the structure may be considered high or
concrete blocks, with loose steel or wood very high ductility in the direction of the beams,
joist floors: = 1. but the slab must necessarily be analyzed as
b) Brick or block factory load-bearing wall low ductility. Alternatively, it may be considered
buildings, with monolithic one-sided floors to have high or very high ductility in all
with a reinforced concrete upper slab. gives: directions, if some drop beams are arranged in
= 1. the slab, but adopting, as elements of the
c) Buildings with reinforced concrete load- structure resistant to the action of the
bearing walls, with solid or lightened slab earthquake, only those beams of that type and
floors: the supports to which they attack.
= 1.
d) Halls for sports halls, supermarkets, fair halls,
stations, terminals, industries, etc., with metal C.3.7.3.2. Distribution factor
supports and covered with metallic structure.
The distribution factor, , will be determined in
— Supports cross braced and covered with accordance with the priorities established in
supported trusses: = 1. section 3.6.2.3.2. However, when the simplified
— Assimilable systems inverted pendulum:
method is applied, the formula of the articles
= 2. may be used.
— Supports and beams forming frames: For buildings of up to eight floors of height and
• with screens: = 3. equal masses, the value of the distribution
• with ductile rigid knots: = 4. factor ik indicated in table C 3.1 can be taken
for the first mode:
39
TABLE C 3.1
Distribution factor for the first mode in buildings with up to 8 equal floors
Floor 8 1.3
7 1.2 1.2
6 1.2 1.2 1.1
5 1.2 1.2 1.1 1.0
4 1.2 1.2 1.1 1.0 0.9
3 1.2 1.1 1.0 0.9 0.8 0.7
2 1.2 1.0 0.8 0.8 0.6 0.5 0.5
1 1.0 0.8 0.6 0.5 0.4 0.3 0.3 0.2
TABLE C 3.2
Requests derived from the combination of modes
C.3.7.5. Consideration of the effects of the torsion center (case, for example, of a
rotation single nucleus of elevators and stairs in the
center of the building) this simplified method is
The simplified method proposed by the not valid, requiring in these cases a special
articulation for symmetrical buildings supposes study of torsion. Likewise, this study must be
increasing the extreme frames with a coefficient carried out in buildings with floors of up to four
a = 1.3, with a = 1.0 the central frame, if any, floors that do not meet the regularity
and with intermediate values the rest. requirements of the section
Consequently when most of the stiffness is 3.5.1 and have been analyzed using this method
concentrated in the vicinity simplified.
39
On the contrary, when most of the stiffness is less than 10% of the first-order ones from
concentrated in structural elements far from the horizontal seismic action.
torsion center, the application of this simplified
method generally leads to an oversize- I swim.
C.3.9. Retaining walls
C.3.8. Second order effects Dynamic overdrives in walls can calculate by any
method sanctioned by practice. For cases
The articulated formula represents the condition where there is no risk of liquefaction, the
that the moments induced by compression are Mononobe-Okabe method can be used.
40
CHAPTER IV
DESIGN RULES AND CONSTRUCTION
PRESCRIPTIONS IN BUILDINGS
4.1. Introduction
This chapter contains a series of design rules and construction prescriptions that must
be complied with in all constructions to which this Standard is applicable.
Some of the rules and prescriptions reflected here have to be applied based on the
ductility behavior coefficients, , adopted in the calculation.
The geometric layout in plan will be as symmetrical and regular as possible, trying to
achieve in the building, in the resistant elements, and in the bracing, a composition with two
orthogonal axes of symmetry (Figure 4.1).
41
In asymmetric buildings, symmetrical structures can be achieved by separating them
into independent regular bodies using vertical joints.
Likewise, a geometric arrangement should be sought in elevation as regular as
possible, avoiding sudden transitions of shape or rigidity between one floor and the next.
DISPLAYS TRIANGULATIONS
42
4.2.4. Non-structural elements
Non-structural elements, such as enclosure walls, partition walls, etc., that can develop
sufficient rigidity and resistance to alter the conditions in the structure, will be taken into
account for the preparation of the structural analysis model and will be checked for the
actions derived from the calculation. Alternatively, constructive solutions may be adopted
that guarantee the resistant non-participation of these elements.
General evacuation routes, especially vertical communication cores such as stairs, will
be endowed with additional strength and ductility to facilitate their use, even in the case of
major earthquakes.
or = 33 1 (ac / g) TF
2
where 1, ac and g are the parameters defined in 3.7.3, and TF is the period of the
fundamental mode in seconds.
The joints between building bodies should preferably be vertical planes and with a width
of at least the sum of the maximum lateral displacements, u, of the two bodies.
In areas with ac “0.16g, support joints should not be designed in free expansion,
unless a special study is carried out.
General conduits will not be installed through joint planes, unless they have adequate
flexible links.
The coexistence, in the same structural unit, of shallow and deep foundation systems,
for example, footings or slabs with those of shafts or piles, should be avoided. The
foundation must be laid on a ground with homogeneous geotechnical characteristics. If the
support ground presents discontinuities or substantial changes in its characteristics, the
entire construction will be divided so that the parts located
The lines on either side of the discontinuity constitute independent units.
When the foundation ground contains in the first 20 m below the ground surface, layers
or seams of loose sand located, totally or partially, below the water table, the possibility of
liquefaction should be analyzed.
If it is concluded that the ground is likely to liquefy in the design earthquake, shallow
foundations should be avoided unless ground improvement measures are taken to prevent
liquefaction. Similarly, in deep foundations, the tips of the piles should be driven deep
enough under the liquefiable layers so that the necessary resistance to subsidence can be
developed there.
Each of the foundation elements that transmits significant vertical loads to the ground
must be linked with the contiguous elements in two directions by means of dis-
43
positive tie-downs located at the footing, pile caps or equivalent, capable of resisting axial
stress, both tensile and compressive, equal to the horizontal seismic load transmitted at
each support (Figure 4.3).
When ac “0.16g, the tie elements must be reinforced concrete beams. When ac
<0.16g, it may be considered that the concrete screed constitutes the
tying unit, provided that it is at the level of the shoes or resting on their upper face, whether
It continues around the pillar in all directions, has a thickness of not less than 15 cm or 1/50
of the span between pillars and is capable of resisting the stress prescribed in the first
paragraph of this section.
SANITARY
WROUGHT IRON SOLERA
SOLERA
TIE BEAM
The shaft resistance of the piles will not be considered in the sections of land likely to
liquefy during the calculation earthquake, nor in those located above those strata.
The piles must be properly bonded to the pile cap or equivalent structural member.
In reinforced concrete piles, the longitudinal reinforcement must extend from the top of
the pile to four diameters below the deepest critical zone, with a minimum of 6 meters.
Critical zones are those in which their structural depletion would first be reached during an
earthquake. The longitudinal reinforcement must be made up of bars with a diameter greater
than or equal to 12 mm, a minimum number of 6 and separated by a maximum of 20 cm.
The minimum amount of steel will be 0.4% of the total section for piles cast in situ and 1%
for precast piles. In sheet-jacketed concrete piles, its section, discounting the anticipation of
corrosion, can partially replace (maximum 50%) the required longitudinal reinforcement.
The transverse reinforcement should extend over the entire length of the longitudinal
reinforcement. It can be made up of fences or spirals, whose diameters must be greater than
or equal to 6 mm and with a volumetric quantity s and a spacing s that meet the following
conditions:
— In critical areas:
" 0.8%
s " 10 cm
" 0.6%
s " 15 cm
44
4.4. From masonry wall structures
4.4.1. General design criteria
To meet the general requirements (article 4.1), resistant walls must be arranged in the
two main directions in plan in the most uniform and symmetrical way possible.
Sudden changes in stiffness caused by changes in materials will be avoided.
When 0.08g "ac" 0.12g, the maximum height of a wall structure will be 4 floors.
each one of them with a height not exceeding 20 times the thickness of the wall. Don't be
They will cause rigidity changes due to variations in thickness greater than half an edge of
the slab in the passage from one floor to another, or due to the arrangement of very different
gaps between successive floors. If ac> 0.12 g the maximum height will be two floors.
In any case, a wall structure will be considered a "non-ductile" solution,
even if the reinforcements prescribed in this chapter are provided.
The minimum thickness for exterior single-sheet walls will be 14 cm and 12 cm for
interiors. Furthermore, for a calculation acceleration ac “0.12g, the minimum thickness of the
exterior walls of a sheet will be 24 cm, if they are made of ceramic brick, and 18 cm if they
are built of blocks. In the case of interior walls, the minimum thickness will be 14 cm.
In the case of exterior walls with two sheets (capuchin) and if ac “0.12g, both sheets will
be built with the same material, with a minimum thickness of each sheet of 14 cm and the
interval between tie reinforcement or anchors will be less 35 cm, in all directions. If only one
of the two sheets is bearing, its thickness will meet the conditions indicated above for the
exterior walls of a single sheet.
For values of ac “0.08g, all the load-bearing elements of the same building will be
made with the same constructive solution.
When ac “0.12g, the openings for passage, doors and windows in the resistant
walls will be distributed on the floor plan as evenly as possible, overlapping those
corresponding to the different floors.
The distance between the gaps shall not be less than 60 cm, nor the distance between
a gap and a corner less than 80 cm. Otherwise, the panels between them will not be
considered resistant and cannot be considered load-bearing.
In load-bearing and bracing walls, only vertical frictions separated from each other by at
least 2 m and whose depth shall not exceed one fifth of their thickness shall be admitted. In
any case, the reduced thickness will not be less than the values specified in the previous
section.
The connection between the floors and the walls and the monolithism between the
various elements that make up the floors are entrusted to the upper slab prescribed by the
EF-96 standard, or the one that replaces it, with the reinforcement sections and the
construction provisions specified therein. The floors will be linked to the walls by means of
the chains prescribed by the NBE-FL-90 standard.
Loose joist floors, made of wood or metal, must be tied along their entire perimeter to
horizontal chains located at the same level, to support the delivery and connection of the
joists with the wall. The tie of the joists that run parallel to the wall will extend to at least the
three closest joists.
When ac “0.12g, in the masonry walls there must be vertical and horizontal
reinforcements at distances less than 5 m. In addition, the diagonal of a panel between
reinforcements must be less than 40 times the thickness of the wall.
45
When the reinforcements are made in concrete, the cross section shall be at least 15
cm high and the total width of the wall, the latter reduced, where appropriate, by the
minimum amount required for the continuity of the visible walls. The reinforcement will be at
least 4 10 longitudinal plus a 6 every 25 cm as transverse reinforcement.
— The end sections of the beams are plasticized before those of the support, which is
fulfilled if the safety coefficient of any stress on any support is always greater than
that of any stress on any beam with which it concurs in a node.
— The extreme sections of beams and supports are exhausted before the exhaustion
of the encounter takes place, which is fulfilled if the safety factor before the
exhaustion of any connecting rod or anchor in any node is slightly higher than that of
any stress. of the sections of beams or supports that attack it.
— The yield to bending in the steel of the longitudinal reinforcement is reached before
the exhaustion of the section by shear, which is fulfilled if the shear safety coefficient
in every section is greater than that of the same section at bending moment. tor.
Short pieces, such as dwarfs, should be checked for the shear resulting from
considering in the extreme sections moments equal to their bending-resistant
capacity and with the opposite sign.
— The checks to be carried out will include those of the pieces, as detailed in the
following sections, and those of the nodes. When the joint between the support and
the beam is made of concrete, the connecting rod must be checked in the diagonal
of the same (Figure 4.7).
To be able to consider that the structure, in the direction of the beams, benefits from the
conditions of high ductility ( = 3), the following requirements must be met (see Figure 4.4):
— The sag under the slab is greater than the design depth of the compressed head in
the cracked section.
— The drop width, b, is at least 0.20 m.
— At least 2 14 are arranged on the upper face and throughout its development.
— On the upper face, the continuity reinforcement in an interior node will have a
section smaller than b · h / 40, where h is the total depth of the beam.
— At least 2 14 and 4 ‰ are arranged on the lower face and throughout its development.
— At least one A / 3 reinforcement will actually be anchored to the end on the bottom
face, A being the maximum amount of the upper tensile reinforcement of that same
end.
— On both the upper and lower faces, a minimum A / 4 reinforcement will be provided
throughout its development, A being the amount of the maximum negative
reinforcement between the two ends. The shear-resistant capacity of the sections
will be 25% higher than that required by the calculation.
— In the extreme areas of the beam, in an amplitude of two edges from the face of the
support, there will be frames of at least 6 mm in diameter and with a separation no
greater than:
• h/4.
• 8 L, where L is the diameter of any compressed longitudinal reinforcement.
• 0.15 m.
• In the rest of the beam, the frames will have a maximum separation of h / 2.
46
0.15 m 0.15 m
h/4 h/4
8ØL 8ØL
A< bh / 40 A/4 T
2Ø14 O'
h
x
A/3 2Ø14 A '/ 3
ØL COMPRESSE
D HEAD h/2 A/4
2h 2h
b
0.20 m
In order to be able to consider that the structure, in the direction of the beams, benefits
from the conditions of very high ductility (momentos = 4), there must be no inversion of
moments, that is, the seismic case must not cause at the ends of the beams moments of
both signs, and in addition to the conditions for = 3 in the previous paragraph, the
following requirements must be met (see Figure 4.5):
— The width of the drop, b, will be at least 0.25 m, but less than that of any of the
supports to which the beam attacks.
— On the lower face, at least one A / 2 reinforcement will actually be anchored to the
end without continuity, A being the amount of the tensile reinforcement at that same
end.
— On both the upper and lower faces, a minimum A / 3 reinforcement will be provided
throughout its development, A being the amount of the maximum negative
reinforcement between the two ends.
— There will be a longitudinal skin armor of at least 2 10, every 0.25 m of edge.
— In the extreme zones of the beam, in an amplitude of two edges from the face of the
support, there will be frames with a diameter of at least 6 mm and with a separation
smaller than:
— 6 L, where L is the diameter of any compressed longitudinal reinforcement.
h/4 h/4
6 øL 6 ØL
0.15 m 0.15 m
A/3
2 Ø 14
T <bh / T
O 40 O'
h
x
Ø 10
A/ 0.25 m
A´ /
orL HEAD 2 2 Ø 14 2
COMPRESSE h/ A/3
D 2
2h 2h
b
0.25 m
Regardless of the value of , when the design seismic acceleration, ac, is equal to or
greater than 0.16g, the longitudinal reinforcement of the main beams will be at least 2 16,
and 0.004bh, extended over its entire development, and the separation of hedges, in an
amplitude of 2h from the face of the support, will not exceed 0.10 m (see Figure 4.6).
0.10 m 0.10 m
2Ø16 2Ø16
47
Furthermore, regardless of the seismic acceleration of the calculation or the degree of
ductility chosen, when the joint between the support and the beam is made of concrete, the
connecting rod must be checked in the diagonal of the same (see Figure 4.7).
LOSS OF EDGE IN
EFFECTIVE TRACTION
SECTION
FLAT
FORGE
D
KNOT
ROD
EDGE IN
TRACTION
TYPE SUPPORT TO PLANT BEAMS CRANKS HIGHLY REQUESTED
KNOT
In general, with concrete supports, the upper reinforcement of the end nodes of beams
that is necessary due to seismic stress must be arranged entirely within the support (Figure
4.8.a), counting its anchorage from the beginning of the area pinched by the links. - those of
support and knot. The favorable effect of pinching between the connecting rods may be
measured as a loss of traction per unit length equal to the guaranteed vertical compression
stress in said area multiplied by the diameter of the reinforcement. The solution of the
anchoring of the upper reinforcement by continuity after the support, in a loop around its
shaft (Figure 4.8.b), is limited to a total traction, between both branches of the loop, not
greater than the guaranteed vertical compression of its interior.
If transverse edge beams are arranged on the edge, the upper reinforcement may be
arranged on the sides of the support in a band with an amplitude not greater than half the
beam depth, (Figure 4.8.c), counting its anchorage from the point at which orthogonal
reinforcement is arranged, or the break, or the welding of the element to which it is crimped.
TO B C
h
PIN
EDGE
BEAM
ARMOR
Ø/ ORTHOGONA
2 L
AREA OF INSIDE
CLAMPING THE LOOP <h / 2
OR
TO B
TO
<h / 2
C
If the support is metallic, with a shaft passing through the slab (Figure 4.9), it must also
be checked that the reinforcing element of the reinforcement, or, in the case of a loop, the
shaft itself, allows balancing the moment between both pieces. In any case, the possibility of
entrusting said equilibrium to torsion in the concrete must be excluded.
In the extreme nodes of the top floor, without superior compression, the anchor check
can be omitted when the reinforcement is continuous with that of the support and has a
similar tension. If independent reinforcements are provided for both pieces, the overlap
length will be the anchor length, with the reduction, where appropriate, of the cross-welded
leg or reinforcement effect (Figure 4.10).
48
h
PIN
ARMOR CRIMPING
TO THE
ORTOGON PROFILE TIE
OR
Ø/2
TIE
OVERLAP 0.06 m
UPPER ARMOR OVERLAPPED UPPER ARMOR CONTINUES WITH
TRACTION
WITH THE BRACKET 0.06 m THE SUPPORT
0.25 m
O OR
R
STEP 15 Ø
M=0
ADDITIONAL LOWER MOUNTING
ARMOR, NON-STRONG COMPRESSION-RESISTANT
LOWER ARMOR
ANCHOR LENGTH CONSIDERING
ANCHOR LENGTH PIN
OVERLAP IN OVERLAP
COMPRESSIO ORTHOGON IN
N AL ARMOR TRACTION
TIE
OR
ADDITIONAL M=0
NON-STRONG MOUNTING 15 Ø
FOOTREST
LOWER FRAME
COMPRESSION-RESISTANT
LOWER ARMOR
To take into account the compression collaboration of the lower reinforcement of the
beam, it must be confirmed that it develops sufficient length for the compression attributed to
it, after the beams of the inner face of the support, being able to count on the improvement
that allows the bending in pin (see Figures 4.4, 4.5 and 4.6).
If said reinforcement is never tensioned, nor is compression taken into account, it will
suffice to check that, from the point of zero tension of the beam, it is prolonged enough to
anchor and that, in any case, it penetrates at least 10 behind the face inside the bracket.
In an internal knot, if the armor penetrates the support, it can be finished with a pin; If
the floor is flat, it can be assumed that compression is tip-relieved in the area that is
compressed in all directions.
49
SUPERIOR
UNDERSTANDING h/
2
OR' OR
ARMOR
ORTHOGONAL
h h
EDGING BEAM
ANCHORIN
G IN
TRACTION h/2
h/2
h/2
PINZADA AREA FLAT BEAM
In an internal knot, to take into account the compression of the reinforcements arranged
outside the support, they must overlap the corresponding anchor length (see Figure 4.12).
ØB
TO
COMPRESSI 10 Ø
ON OVERLAP BEAM SINGING FLAT BEAM
A
TO B
In a flat beam end node, only the vertical branches of the existing abutments in the area
defined in Figure 4.13 can be taken into account to resist the seismic stress.
h/
NON-
2 45º BRANCH NOT EFFECTIV
h/2 EFFECTIVE h/2 E h/
BRANCHE 2
S
h/2 h/2 h/
2
When the beam is flat, especially if the support has an elongated section in the direction
of the beam, it is advisable for the stirrup of the latter to cross the node, arranging branches
in the vicinity of the lateral faces of the support.
50
4.5.2.5. Particular conditions in case of inversion of moments
It is said that there is inversion of moments when, due to the horizontal action of the
earthquake, the moment at the end of the beam changes sign and starts to pull the lower
fiber (Figure 4.14).
If there is an inversion in an extreme knot, the same rules apply to the lower
reinforcement as those indicated in the previous section for the upper one.
If inversion occurs in an interior node, that meeting, for the purposes of arranging the
lower and upper reinforcements and the stirrups, behaves as two end-to-end nodes, except
for the anchoring of the beam reinforcement, which in any case, it will be resolved by straight
extension from the opposite face of the support.
In the particular case of metal supports, when an end node is reversed, it is necessary
to have reinforcement crimping devices, both upper and lower.
When the inversion affects the extreme node of the top floor, a specific reinforcement
must be arranged on the diagonal of the node, or the beam and support reinforcements must
be anchored to account for a compressed connecting rod on the opposite diagonal (Figure
4.15).
If the moment inversion is very strong, a reaction inversion can also occur in the beam;
If the support is metallic, in this case the design of the crimping device will have to be altered
so that it allows picking up load in both directions.
4.5.3. Brackets
In concrete supports (Figure 4.16), when the calculation seismic acceleration, ac, is
equal to or greater than 0.12g:
51
— In the extreme areas of the support, in an amplitude measured from the junction with
the slab or beam of at least two edges, and if the beam is also lowered when
passing through the node, frames with a diameter of at least 6 mm will be provided
and with an interval no greater than:
OVERLAP
c/3 c/4
0.15 m (Ø 16) 0.10 m (Ø 16)
2C 0.10 m (Ø 14) 2C 0.07 m (Ø 14)
Ø6
Ø8
15 Ø 15 Ø
OR OR
0.20 m 0.15 m
c 0.25 m c 0.30 m
MINIMUM 8 ARMOR MINIMUM 8 ARMOR
c/3 c/4
0.15 m (Ø 16) 0.10 m (Ø 16)
0.10 m (Ø 14) 0.07 m (Ø 14)
2C
2
C
Furthermore, when the seismic acceleration calculated ac is equal to or greater than 0.16g:
In addition to the general conditions, in all support, whatever the calculation seismic
acceleration, the specific rules detailed below must be respected.
52
If the starting element where the wait is inserted is a footing, beam, slab, shaft or pile
with a section much higher than that of the column, the reinforcement can be finished in a
leg, being advisable to arrange it outwards if its predominant tension is compression. The
part overlapped with the shaft of the support must necessarily be arranged in a straight
extension.
If the starting element is a wall or beam, the waiting reinforcements arranged within that
element must be provided with at least cross-sectional stirrups to the faces of said element
(Figure 4.17).
BOTH EDGES COMPRESSED IN A TRACED EDGE IN SOME A TRACED EDGE IN SOME WALL
ALL LOADING CASES CASE OF LOAD CASE OF LOAD START
C C
FORGED
OR > C> C
LATIGUILLOS
> 0.25
8Ø
TRACTION TRACTION
OVERLAP OVERLAP
In general, the armor of each shaft is prolonged in the upper one. As in the case of
starting, if the seismic action causes the appearance of tractions on one edge, the length of
overlap of both sections must allow the transfer of said stress, finishing the lower one in a
straight extension.
In the case of extreme support, to avoid the effect of expulsion of the compressed
reinforcement from the outer edge, or the one that bursts due to the compression transfer
effect of the reinforcement by tip, it is advisable, in addition to fixing the reinforcement from
the support to the stirrups and while waiting for the lower shaft, arrange the face of the slab
outside the beams of the support (see Figure 4.18).
In the case of extreme support, if the beam reinforcement that causes the breakage of
the connecting rod is arranged recessed with respect to the support, this must be
recalculated taking as the effective section the one resulting from dispensing with the area
located outside the beams. the same.
POINTS
TOWARDS OVERLA
INSIDE P s2
ACCORDI
EFFECTI NG TO
VE VOLTAG
SECTION E
s FORK
TIE CANES
s1
In general, with drop beams, it is convenient that the support stirrups are arranged
within the node. In any case, the end and corner supports will have stirrups or forks as the
node passes, with a cadence no less than that of any of the shafts that attack it, to produce
confinement in the direction perpendicular to the edge or free edges.
In addition to checking the oblique knot rod, mentioned in section 4.5.1, with regard to
the supports, it must be checked that its reinforcement has sufficient development and
adhesion conditions to account for the change in tension when passing through the
encounter with the beam, taking into account the dynamic aspect, coming from the cyclical
change of the sign and direction of the stress, which the classical models do not expressly
take into account.
53
4.5.3.4. Particular conditions of the top node
In interior nodes (Figure 4.19), if both edges of the support are compressed, in all the
load hypotheses considered in the calculation, the solution in pin can be used, provided that
it is towards the outside of the support and prudent distance from the upper face of the slab.
If, in some case of load, tensions are reached in one of the edges, —and, if this
happens due to seismic action, it will be alternately in both—, it is preferable to achieve the
anchor length for said tension by bending inward and overlapping. with the upper armor of
the plant.
If the seismic action produces inversion of moments in an upper node, both the solution
and the anchorage length must be checked, and, in particular, the resistance capacity of the
resulting connecting rod, as well as the variations in the arrangement of stirrups that the knot
demands for it.
TRACTION OVERLAP
> 0.06 m
TRACTION
ANCHOR
4.5.4. Forged
REINFORCED MESH
L / 4L / 4
L
54
4.5.5. Stiffening screens
It is convenient that the screens used as stiffening and resistance elements against
horizontal actions are continuous throughout the entire height of the construction, reaching
the foundation without significant changes in either width or thickness. If there are gaps, they
will be vertically aligned.
When the calculation seismic acceleration ac is equal to or greater than 0.16g or to be
able to consider high or very high ductility in the direction of the screen ( = 3 or = 4), the
following will be fulfilled:
O
R h
H/
b/3 6
10Ø
h/5 Ø8
h / 20
b 0.15 m
h DUCTILE LINTEL
Structures resolved with pieces that are exclusively linear or superficial prefabricated
elements, whatever the material, will be considered, in general, as structures without
ductility, unless the joints are specially designed to provide sufficient rigidity and ductility to
the meeting.
To consider some degree of ductility in floor structures, ductility at the nodes must be
guaranteed, according to the previous articles. For this, the areas closest to the ends of each
structural element will be reinforced and strapped, and the contact surface between the
precast element and the concrete laid out on site will present sufficient roughness and will be
sewn with reinforcement on either side of the said surface.
In the case of one-story buildings, to consider ductility > 1, it must be ensured that all
the columns are ductilely embedded in the base.
The project of metallic structures before seismic actions can be considered in the linear
range, without making use of any plastic dissipation mechanism, or in the non-linear range.
55
neal. In the first case, the structure will be considered without ductility and in the calculation
a unit value will be assigned to the coefficient . In the second, the structure will be
considered, for each of the directions in which it is verified, of high, medium or low ductility
depending on the resistant system (section 3.7.3.1) and the details and materials as
indicated in the sections that follow.
When ductility values equal to or greater than 2 are used in the project of the structure,
all the requirements regarding the material and the section demanded by the project
regulations for metallic structures will be mandatory in the case of using the calculation
plastic.
4.6.2. materials
In the technical specifications and in the project drawings, the quality of the steel to be
used will be specified and the need to check the structure for any modification will be
explicitly indicated, even when this implies the substitution of steels with a higher elastic limit.
or by pieces of greater capacity.
If a high or very high value of ductility has been used in the design of the structure ( =
3 or 4), in the specification of the materials to be used in the systems resistant to earthquake
loads, the limit value will be limited elastic steel, which shall not exceed the nominal by more
than 10%.
In the same sense, the technical specifications will also indicate the need to check the
structure in the event of any modification in the dimensions of the bars, even when this
implies the substitution of bars of greater capacity.
4.6.3. Unions
The project drawings will include specific details of the joints, indicating the location,
dimensions and qualities of the joining means (screws, pins, welding beads), of the cuts,
recesses, grooves in end sections of bars and the possible need for auxiliary means (spill
plates, backrests, deformable washers, etc.). The type of joint will be explicitly declared in
the calculation memory, both in terms of its resistance (total or partial) and its rigidity (rigid,
semi-rigid or articulated).
When values of the ductility behavior coefficient equal to or greater than 2 are used in
the structure design, the joints will be projected as total resistance, assuming an over-
resistance of 1.2 (the joint capacity will be at least 1.2 times that of the joined bars).
When values of the coefficient of behavior by ductility higher than 2 are used in the
design of the structure, partial penetration welds between critical elements belonging to the
earthquake resistant scheme will not be admitted. The screwed joints will be designed, in
this case, in such a way that the failure does not occur due to breakage of the screws.
If the resistant structure is made up of frames with rigid joints, in order to be considered
as having high or very high ductility, it must meet the following conditions:
— The end sections of the beams laminate before those of the support.
— End sections of beams and supports are laminated before joint breakage occurs.
56
4.6.5. Triangulations and bracing
Complete triangulations (the axes of the bars coincide at one point), in which dissipation
occurs by elongation of the tensile bar (San Andrés crosses), will be considered high
ductility. If the collaboration of the compressed bar is included in the calculation, in general,
no ductility will be considered.
Incomplete triangulations (the axes of the diagonals do not go to the girder-column
nodes), in which dissipation occurs due to the formation of hinges in the foreseen areas, will
be considered very high ductility.
Special care will be taken of the symmetry of the section of the bracing elements, as
well as that of the end joints.
One of the objectives of the Standard —according to its purpose, established in section
1.1— is a substantial reduction in the usually large physical and economic losses, and above
all of the victims, especially those who generate the damage. to non-structural elements.
The design values and the earthquake-resistant design —especially the precepts of all
section 4.7— must ensure that small earthquakes, with a return period of the same order as
the life of the construction, do not cause significant damage to the non-structural elements. .
All the panels, interior partitions, false ceilings and other singular elements, such as
façade panels, etc., must be correctly linked to the structural elements to avoid detachment
of the pieces during seismic shocks, especially if they are has assumed that the ductility of
the construction is high or very high.
If 0.16g> ac “0.08g, the enclosing panels or partition walls that exceed 5 m in length
or 20 m2 in area must be subdivided by linking them to intermediate secondary
elements. When ac “0.16g should be made from 3 m in length or 10 m2 of surface.
When the enclosures are made with large format prefabricated elements, and these
have not been considered in the structure model, a ductility behavior coefficient must be
adopted for the construction and calculation of said elements.
= 1. The joints must allow, without breaking, the displacements obtained in the calculation.
In this case, due to its importance, the anchors must be carefully designed.
The elements with the upper free edge, such as parapets, parapets and chimneys, must
be correctly linked to the structure to guarantee its stability, being calculated with the seismic
action corresponding to the plant where they are located, considering, except for special
justification, = 1 Fences will be treated in the same way by anchoring them to their
foundations.
In addition, when the walls or bibs with the upper edge free and with a height of
more than one meter are ac “0.12g, they will be finished off with a crowning chain,
providing vertical reinforcements anchored to the structure or the foundation.
In addition, evacuation routes must comply with the provisions of the Fire Protection
Conditions for Buildings in force, and they must not contain elements that could easily
detach in the event of an earthquake.
57
When ac “0.16g, stairs built on partitioned vaults should not be projected, or those
formed by cantilevered steps embedded in masonry walls.
Comments
C.4.1. Introduction more important the higher the height of the
construction, and are aimed at preventing
Design rules and construction prescriptions that undesirable couplings between rotational and
all constructions to which the Standard applies translational oscillations. To comply with the
are mandatory regardless of the results of the regularity in elevation, it is recommended that the
calculation. These rules have been extracted reduction of dimensions in anyfloor is not greater
from observing the behavior of structural and than 20% of the dimension of the lower floor if
non-structural elements in destructive the center of gravity is maintained and 10% if it
earthquakes and are intended to gather the is not maintained. This reduction can reach
lessons learned from this experience. 50% in the top 15% of the building.
58
If the action of the earthquake is capable of
reversing the sign of the moments in any of the
beams, the stress on the node is greater than on
each of the pieces, being able to arrive at the
break of this before they laminate beams and
supports.
Figure C.4.2 Very rectangular plant
elongated
C.4.2.4. Non-structural elements
59
Stratification is not horizontal and the pavement mass migón with upper shoe in the areas in that
layer has unevenness -which forces to be laid on the same firm is deeper.
the same stratum at different depths- it is The foundation with isolated footings and runs, nor
permissible to cement with footings in the areas the combination of piles and deep walls (Figure
where the pavement is more superficial and by C.4.4).
filling of wells of hor-
The existence of short columns between the first such, variable with depth z, at which it is com-
floor and the foundation forces to consider try liquefaction.
these in the analysis model of the structure. toc is the calculation seismic acceleration, according to
The existence of a basement perimeter wall, 2.2.
which guarantees that part of the structure a rigid g is the acceleration of gravity.
behavior, allows considering as structure
oscillating the one that exists from the highest and where RL the resistance of the soil to
level slab that connects with the wall. liquefaction, which can be obtained by the
The study of safety against liquefaction can be expression:
done by comparing the horizontal tangential
stress equivalent to the earthquake, E, with the RL = KM R1 v
resistance of the ground to liquefaction, R L, for
which the procedures established in the practice where
of seismic geotechnical engineering or the
following simplified procedure based on the KM = 1.5 - 1.8 (K - 1) 1/2
SPT test, valid for horizontal surface soils and
which will be applied to all liquefiable layers K is the contribution coefficient defined in 2.1. R 1
located in the depth defined in the article. is read in figure C.4.5 as a function of hitting in
Sufficient security against liquefaction is the normalized SPT test, for an energy useful
considered if, at all depths, it is verified that: 60% of nominal and at an effective vertical
pressure of 100 kPa (1 kp / cm2) (N1.60), of
" RL/ 1.5 value:
rd = 1 - 0.015z
C.4.3.2. Tying elements
being
If the first floor is very close to the footings or pile
z the depth in meters. caps, their effect on the foundation tie may be
is the total vertical stress on the horizontal considered.
plane When tying the foundation with the lower concrete
slab, it will be necessary to assemble the hearth
60
with a geometric quantity of 2 ‰,
and links
61
fix it to the edge pillars to resist the stresses sufficiently charged; if necessary, the slabs will be
prescribed in these. arranged counterbalanced, adopting in that case
conservative assumptions about the continuity
ofthe ends of the floors.
C.4.3.3. Specific rules for foundations of piles Yes toc <0.12g it will be enough to comply with
what is specified for Capuchin walls meet the
In cast-in-situ concrete piles, anchoring is NBE FL-90 standard.
achieved by penetrating the longitudinal It is considered inadmissible that in the same
reinforcements into the pile cap, or into the building, and in an area with ac " 0.12g, mortar
structural element with the that link, in a length block walls are mixed with brick masonry work
10 greater than that necessary for anchoring or concrete walls are interposed, unless these
under static stress, where is the diameter of are screen elements with the specific mission
the reinforcement. of resisting the totality of the earthquake efforts,
Anchoring precast piles requires adoption of be it whatever direction it acts.
special measures.
Normally the critical areas are in the head of the
piles, in the embedment with the pile cap and C.4.4.2. Gaps, shelves and chases
in the abrupt transitions between very different
layers, including the ends of the liquefiable The regularity of the articulated refers to the
layers. confrontation vertical opening of the holes, and
at a relatively constant size and interval
0.6 between them in plan (Figure C.4.6).
0.5
123
0.4
R1
0.3
0.2
0.1
BRACING WALLS
The calculation, as well as the design and
execution conditions of brick factory structures,
are included in the NBE-FL-90 standard.
Resistance to horizontal actions in non-reinforced
h c
walls can only occur in its own plane that contains
it, so it is insisted on the articulated that
the walls are arranged in the two main directions >h/4 >h/ >c/
cipales of the plant. If possible, it would be 2 4
preferable
even form rectangular drawers with the walls in Figure C.4.7.Advisable provision of
full height. holes in walls
If a panel is made of reinforced concrete, it must
be of the same material from the foundation.
The shear strength of the walls, necessary to C.4.4.3. Link of the floors to the wall
resist dynamic horizontal stresses, improves the
higher the compression stress. on the walls. The connection of all slabs to the wall tries to
Therefore it is convenient that all of them, the ensure the solidarity between the walls and the
main ones and the bracing ones, elements that make up the slabs by means of
steel bars
61
located in the upper concrete slab, anchored in the jointness, especially in the case of flat floors, with
prescribed perimeter bands. The amount of these little depth, with a very obliquity connecting rod,
reinforcements is specified in the EF-96 standard. which translates into the difficulty of counting
The minimum stirrup for straps will be 5mm on the supports with tensioned reinforcement,
each20 cm. in which case it is possible to choose to resize
In the event of an earthquake, the load-bearing them, increasing their section. In some cases
walls have to withstand high shear stresses in the knot check can provide the critical design
their connection with the bracing ones, for this condition.
reason the link criteria prescribed in the NBE-
FL-90 standard must be strictly met.
If the two-leaf solution is used (as, for example, in C.4.5.2. Concrete beams
the case of a «ventilated façade»), special care
must be taken to ensure that the connecting C.4.5.2.1. General rules for beams
elements between the two panels of the wall have
sufficient strength and ductility so that the outer The general conditions, although they are
sheet cannot be flexed or detached. In principle, expressly written only for beams, it is
and if no special provisions are adopted, a heavy recommended have them into account by
blade can be consideredexterior weakly assimilation to other cases such as waffle slab,
supported it is not a good solution for a façade slab, or even unidirectional slab in the direction
in a seismic zone. of the joists.
ARMOR
COMPRESSED TOO ARMOR
CLOSE COMPRESSED TOO
FROM THE EDGE FIRST STEP TOO FAR CLOSE FIRST STEP TOO FAR
FROM BRACKET FROM THE EDGE FROM BRACKET
LAST STEP TOO
LAST STEP TOO FAR FROM THE
FAR FROM THE BEAM
BEAM
62
Figure C.4.8 Precautions in the encounters of pieces of concrete
63
LAP LAP
LENGTH LENGTH
EDGING BEAM FLAT BEAM
C.4.5.2.4. Particular conditions for Since, in general, the state of upper tension
stirrups and lower compression predominates, in
extreme nodes it is convenient that the
In general, stirrups of two or four are preferable. outermost leg corresponds to the upper
three branches over three, in which, in many reinforcement. Especially when there is
cases, the extreme can be ineffective. investment it is important that the design
foresees a projection of the plant outside the
C.4.5.2.5. Particular conditions in case outer beams of the supports.
investment of moments When There is a reversal of moments in an
extreme node; having pins in all the
If there is inversion of moments in an extreme reinforcements can significantly hinder the
node, the reinforcement of both faces of the beam correct concreting of the node; in that case, ties
will be alternately pulled and compressed. can be used (see figure C.4.10).
The worst effect of the investment is related to the
NORMAL NORMAL
LOOP LOOP
TIE IN
INVESTME
NT
TIE IN
INVESTME
NT
INSIDE INSIDE
THE THE
LOOP LOOP
63
fast change and cyclical from one situation to C.4.5.5. Stiffening screens
another, alternately varying the direction of the
connecting rod and pulling what was Since the behavior of the screen is appro- xima
compressed a few tenths of a second before. to a bracket embedded in the base, the
The dynamic aspect of this phenomenon reinforcements indicated are intended to
advises to be very prudent when applying the provide ductility to the area where a plastic
rules of the articles to the investment case, hinge may be formed.
which, if possible, should be avoided. If coupled screens are arranged, the confinement
When There is an investment in an inner knot, of the concrete and the provision of reinforcement
for the lower reinforcement it is highly amounts in the beam joints must be studied in
recommended to use local, through detail. and screens, to justify the degree of
supplements, with which it is easier to ductility adopted in the calculations.
guarantee position, covering and anchoring.
In many cases, the beam reaction inversion is
usually mitigated or canceled out by the usual C.4.5.6. Precast elements
sense reaction of the orthogonal beam or edge
rib. The special characteristics of the nodes in this
type of structure and the discontinuities that may
exist in the joints, do not generally allow for rigid
C.4.5.3. Brackets node monolithism, especially in In the case of a
prefabricated panel structure, the nodes should
C.4.5.3.1. General rules of supports generally be considered as articulated. In the
latter case, it is recommended that the
C.4.5.3.2. Specific conditions of the node connecting bands between horizontal and
Boot vertical elements satisfy conditions similar to
those established for wall structures.
Usually when eccentricity is reached of the order
of the sixth of the edge, in the opposite edge
the compression is lost. With larger C.4.6. Of steel structures
eccentricities, net pulls can be expected.
C.4.6.1. General criteria
C.4.5.3.3. Particular conditions in knots When the project is based on a ductile structural
intermediate system, it is necessary to ensure that the
resistance of the brittle elements (for example,
If the supports reach traction at their edges and, joints) is higher than the plastic capacity of the
above all, if there is also inversion of moments in ductile elements that are damaged (for example,
beams, it is advisable to study the convenience of ends of the joined bars ). In general, the above
the reinforcement of each shaft being anchored in will require the definition of a ductile failure
squares. dra to the passage of the slab. mechanism characterized by:
Especially in the case of flat floors (flat beams
nas, slabs or waffle floor) and even more so if — The position of the plastic hinges.
there is inversion of moments in beams, the — The value of the global offset.
node check can provide the critical design — The turn produced in each kneecap.
condition.
The failure mechanism thus defined will check:
C.4.5.3.4. Specific conditions of the node — The turning capacity of the sections in which
higher the hinges are formed, for which the effect of
the concomitant forces must be considered
At the extreme node, it is usual for the outer (shear in the case of beams and axial in the
reinforcement to be pulled and the inner one case of columns).
compressed, each having to resort to the — The capacity of the bars to withstand the
appropriate solution for said state. stresses that balance the plastic moments
increased in the appropriate proportion.
64
C.4.6.2. materials of the enclosures in case of earthquake. The
arrangement of the reinforcing elements is aimed
The conditions referred to in the articles in at avoidingassuming the severity of the
relation to the design of structures with some damage.
ductility are normally fulfilled, as regards In the case of panel or prefabricated enclosures
material, by the steels specified in the standard In large format cabinets, it should be tried to
for metallic structures. Those referred to the avoid the detachment of these elements, totally
section are the symmetry and the classification or partially, both because of the risk that their
in type 1 «plastic». The increase in the capacity fall entails and because of the sudden change
of the bars that involves the use of steels with a in local stiffness that it can produce in the
higher elastic limit or sections with a greater resistant structure; It is therefore advisable to
area can induce the brittle failure of the joints design the structure with additional stiffness to
or other bars. The substitution of S 235 steels avoid the mentioned effects. In article 4.2.4. the
for S 275 or S 355 and the usual substitution of need to consider rigid secondary elements in
profiles grouping together higher sections must the calculation is established.
be especially watched in order to reduce the If the enclosures are made with elements
different types of profiles to be used. Naturally, manufactured that have not been considered in
the structure model, the joints must allow,
C.4.6.3. Unions without breakage, the displacements obtained
in the calculation.
The behavior of the joints is of the greatest
importance in the case of structures subjected
to earthquakes and their design obeys basic C.4.7.3. Windowsills, parapets, chimneys
design criteria (chosen resistant system, and fences
assumed ductility, etc.) that must prevail over
possible local conditions ( means available in All these elements, if measures are not taken to
the chosen workshop, means of transport, guarantee their stability, can be very dangerous
etc.). in case of earthquake.
The horizontal calculation force, F, which is
prescribed in the articulation, can be obtained
C.4.6.4. Portal structures
approximately using the expression:
When In the calculation a high or very high
F = p · (toc/ g)· 1 · · 1k
ductility is considered, the condition of total
resistance in the nodes will be checked (their where p is the weight of the element and the rest
capacity is greater than those of the connecting of the variables have the same meaning as in the
bars). article
The definition and verification of the failure 3.7.3 of the Standard.
mechanism will follow the guidelines set out in the
comments. to section 4.6.1.
C.4.7.4. Escape routes
C.4.6.5. Triangulations and bracing
Evacuation routes are critical precincts both
It is always advisable to form each bracing plane by during the seismic movement and for the
triangulating more than one panel, when object to subsequent provision of aid. For this reason,
introduce some degree of redundancy. and given the greater rigidity that they usually
It is advisable to minimize the bending stiffness of exhibit, it is also advisable to provide them with
the bars in the case of bracing in which buckling additional resistance to guarantee their
of the compressed bar is allowed (San Andrés functionality and safety.
crosses) so that such buckling occurs in the
elastic range.
The concern stated in previous articles regarding the C.4.7.5. Exterior carpentry
substitution of project profiles is especially critical in
the case of triangulations. The custom of When the height of the construction is important,
regularizing profiles to the largest section can it is advisable to use security or laminated glass,
concentrate the ductility requirementin the to avoid the risks derived of his fall.
triangulation of a single plant. The prescription of oversizing the gaps, The
chocks and the gaskets try to prevent the
C.4.7. From other construction elements expulsion of the glass in the case of strong
oscillations, which can occur more easily when
C.4.7.1. General considerations the resistant structure is formed by rigid cores
in a centered position.
C.4.7.2. Enclosures, partitions and others
It should be avoided as far as possible that the C.4.7.6. Coatings and cladding
deformations of the structure can cause
detachment The risk that uncontrolled detachment of elements
of facade.
65
It is considered that a suitable fixing is the C.4.7.7. Installations and connections
mechanical type by means of metallic pieces.
Plate fixings that rely exclusively on those The breakdown of gas and electricity
received from them are not considered installations, especially at connection points,
appropriate systems.more to pastes or mortars. pose a serious added problem in the event of
an earthquake.
It is advisable to identify the junction points of the
facilities to the building, to facilitate a possible repair
or supply cut.
66
ANNEX 1
ACCELERATION VALUES
BASIC SEISMIC, ab, AND OF THE
CONTRIBUTION COEFFICIENT, K, OF THE
MUNICIPAL TERMS WITH ab " 0.04g,
ORGANIZED BY AUTONOMOUS
COMMUNITIES
69
Municipality tob / g K Municipality tob / g K
70
Municipality tob / g K Municipality tob / g K
71
Municipality tob / g K Municipality tob / g K
72
Municipality tob / g K Municipality tob / g K
73
Municipality tob / g K Municipality tob / g K
74
Municipality tob / g K Municipality tob / g K
75
Municipality tob / K Municipality tob / g K
g
Yebra de Basa 0.04 (1.0) Alajeró 0.04 (1.0)
Plasterer 0.07 (1.0) Arafo 0.04 (1.0)
Arico 0.04 (1.0)
Arona 0.04 (1.0)
Zaragoza province Windward 0.04 (1.0)
Breña Alta 0.04 (1.0)
Artieda 0.04 (1.0) Breña Baja 0.04 (1.0)
Bagues 0.04 (1.0) Buenavista del Norte 0.04 (1.0)
Mianos 0.04 (1.0) Candelaria 0.04 (1.0)
Navardún 0.04 (1.0) Fasnia 0.04 (1.0)
Paint us, The 0.04 (1.0) Border 0.04 (1.0)
Salvatierra de Esca 0.05 (1.0) Fuencaliente de la Palma 0.04 (1.0)
Are you still 0.04 (1.0) Garachico 0.04 (1.0)
Undues de Lerda 0.04 (1.0) Garafía 0.04 (1.0)
Urriés 0.04 (1.0) Granadilla de Abona 0.04 (1.0)
Guancha, The 0.04 (1.0)
Guide of Isora 0.04 (1.0)
CANARY ISLANDS Güímar 0.04 (1.0)
Hermigua 0.04 (1.0)
Province of Las Palmas Icod de los Vinos 0.04 (1.0)
Llanos de Aridane, Los 0.04 (1.0)
Agaete 0.04 (1.0) Acentejo Massacre, La 0.04 (1.0)
Agüimes 0.04 (1.0) Orotava, The 0.04 (1.0)
Ancient 0.04 (1.0) Step, the 0.04 (1.0)
Reef 0.04 (1.0) Cross port 0.04 (1.0)
Artenara 0.04 (1.0) Fat tip 0.04 (1.0)
Arucas 0.04 (1.0) Puntallana 0.04 (1.0)
Betancuria 0.04 (1.0) Realejos, The 0.04 (1.0)
Firgas 0.04 (1.0) Rosario, The 0.04 (1.0)
Galdar 0.04 (1.0) San Andrés y Sauces 0.04 (1.0)
Would do 0.04 (1.0) San Cristóbal de la Laguna 0.04 (1.0)
Ingenuity 0.04 (1.0) San Juan de la Rambla 0.04 (1.0)
Mogan 0.04 (1.0) San Miguel de Abona 0.04 (1.0)
Moya 0.04 (1.0) San Sebastian de la Gomera 0.04 (1.0)
Olive, The 0.04 (1.0) Santa Cruz de la Palma 0.04 (1.0)
Pajara 0.04 (1.0) Santa Cruz of Tenerife 0.04 (1.0)
Palmas de Gran Canaria, Las 0.04 (1.0) Saint Ursula 0.04 (1.0)
Puerto del Rosario 0.04 (1.0) Santiago del Teide 0.04 (1.0)
San Bartolome 0.04 (1.0) Sauzal, The 0.04 (1.0)
San Bartolomé de Tirajana 0.04 (1.0) Silos, The 0.04 (1.0)
Saint Nicholas of Tolentino 0.04 (1.0) Tacoronte 0.04 (1.0)
Saint Bridget 0.04 (1.0) Tank, The 0.04 (1.0)
Santa Lucia de Tirajana 0.04 (1.0) Tazacorte 0.04 (1.0)
Santa María de Guía Tegueste 0.04 (1.0)
Gran Canaria 0.04 (1.0) Tijarafe 0.04 (1.0)
Teguise 0.04 (1.0) Valle Gran Rey 0.04 (1.0)
Tejeda 0.04 (1.0) Beautiful valley 0.04 (1.0)
Telde 0.04 (1.0) Valverde 0.04 (1.0)
Teror 0.04 (1.0) Victoria de Acentejo, La 0.04 (1.0)
Aunts 0.04 (1.0) Vilaflor 0.04 (1.0)
Tinajo 0.04 (1.0) Villa de Mazo 0.04 (1.0)
Tuineje 0.04 (1.0)
Valleseco 0.04 (1.0)
Valsequillo of Gran Canaria 0.04 (1.0) CASTILLA LA MANCHA
Vega de San Mateo 0.04 (1.0)
Yaiza 0.04 (1.0) Province of Albacete
76
Municipality tob / g K Municipality tob / g K
77
Municipality tob / g K Municipality tob / g K
78
Municipality tob / g K Municipality tob / g K
79
Municipality tob / g K Municipality tob / g K
80
Municipality tob / g K Municipality tob / g K
81
Municipality tob / g K Municipality tob / g K
82
Municipal tob / K Municipality tob / g K
ity g
Vallmoll 0.04 (1.0) Benimantell 0.08 (1.0)
Valls 0.04 (1.0) Benimarfull 0.07 (1.0)
Vandellòs i l'Hospitalet Benimassot 0.07 (1.0)
de l'Infant 0.04 (1.0) Benimeli 0.07 (1.0)
Vendrell, The 0.04 (1.0) Benissa 0.06 (1.0)
Vespella of Gaià 0.04 (1.0) Benitachell / Poble Nou
Vilabella 0.04 (1.0) of Benitatxell, The 0.05 (1.0)
Vilallonga del Camp 0.04 (1.0) Biar 0.07 (1.0)
Vilanova de Prades 0.04 (1.0) Bigastro 0.16 (1.0)
Vilanova d'Escornalbou 0.04 (1.0) Bolulla 0.07 (1.0)
Vilaplana 0.04 (1.0) Busot 0.11 (1.0)
Vila Rodona 0.04 (1.0) Callosa de Segura 0.16 (1.0)
Vila Seca 0.04 (1.0) Callosa d'en Sarrià 0.08 (1.0)
Vilaverd 0.04 (1.0) Calpe / Calp 0.06 (1.0)
Vilella Alta, The 0.04 (1.0) Campello, The 0.13 (1.0)
Vilella Baixa, The 0.04 (1.0) Campo de Mirra / Camp de
Vimbodí 0.04 (1.0) Myrrh, The 0.07 (1.0)
Vinebre 0.04 (1.0) Canada 0.07 (1.0)
Vinyols and els Arcs 0.04 (1.0) Castalla 0.08 (1.0)
Xerta 0.04 (1.0) Castell de Castells 0.07 (1.0)
Catral 0.15 (1.0)
Cocentaina 0.07 (1.0)
VALENCIAN COMMUNITY Confrides 0.08 (1.0)
Cox 0.16 (1.0)
Province of Alicante / Alacant Crevillent 0.15 (1.0)
Daya New 0.16 (1.0)
Adsubia 0.07 (1.0) Daya Vieja 0.16 (1.0)
August 0.11 (1.0) Denia 0.06 (1.0)
Agress 0.07 (1.0) Pains 0.16 (1.0)
Aigües 0.11 (1.0) Elche / Elx 0.15 (1.0)
Albatera 0.15 (1.0) Elda 0.09 (1.0)
Alcalali 0.07 (1.0) Facheca 0.07 (1.0)
Alcocer de Planes 0.07 (1.0) Famorca 0.07 (1.0)
Alcoleja 0.08 (1.0) Finestrat 0.09 (1.0)
Alcoy / Alcoi 0.07 (1.0) Formentera del Segura 0.15 (1.0)
Alfafara 0.07 (1.0) Gaianes 0.07 (1.0)
Alfàs del Pi, L ' 0.08 (1.0) Gorgos cat 0.06 (1.0)
Algorfa 0.16 (1.0) Gorga 0.07 (1.0)
Algueña 0.12 (1.0) Rocamora farm 0.15 (1.0)
Alicante / Alacant 0.14 (1.0) Guadalest 0.07 (1.0)
Almoradí 0.16 (1.0) Guardamar del Segura 0.15 (1.0)
Almudaina 0.07 (1.0) Hondón de las Nieves 0.13 (1.0)
Alqueria d'Asnar, L ' 0.07 (1.0) Hondón de los Frailes 0.14 (1.0)
Altea 0.08 (1.0) Ibi 0.08 (1.0)
Aspe 0.13 (1.0) Jacarilla 0.16 (1.0)
Balls 0.07 (1.0) Jalón / Xaló 0.07 (1.0)
Banyeres de Mariola 0.07 (1.0) Jávea / Xàbia 0.05 (1.0)
Benasau 0.07 (1.0) Jijona / Xixona 0.09 (1.0)
Beneixama 0.07 (1.0) Lorcha / Orxa, L ' 0.07 (1.0)
Benejúzar 0.16 (1.0) Lliber 0.07 (1.0)
Benferri 0.15 (1.0) Millena 0.07 (1.0)
Beniarbeig 0.07 (1.0) Monforte del Cid 0.12 (1.0)
Beniardá 0.07 (1.0) Monóvar / Monòver 0.10 (1.0)
Beniarrés 0.07 (1.0) Montesinos, The 0.15 (1.0)
Benidoleig 0.07 (1.0) Murla 0.07 (1.0)
Benidorm 0.09 (1.0) Wall of Alcoy 0.07 (1.0)
Benifallim 0.08 (1.0) Mutxamel 0.13 (1.0)
Benifato 0.08 (1.0) Novelda 0.12 (1.0)
Benigembla 0.07 (1.0) Nucia, The 0.08 (1.0)
Benijófar 0.15 (1.0) Ondara 0.06 (1.0)
Benilloba 0.07 (1.0) Onil 0.07 (1.0)
Benillup 0.07 (1.0) Orba 0.07 (1.0)
83
Municipal tob / K Municipality tob / g K
ity g
Orihuela 0.16 (1.0) Alborache 0.06 (1.0)
Orxeta 0.09 (1.0) Alboraya 0.06 (1.0)
Parcent 0.07 (1.0) Albuixech 0.06 (1.0)
Pedreguer 0.06 (1.0) Alcàntera de Xúquer 0.07 (1.0)
I hit 0.07 (1.0) Alcàsser 0.07 (1.0)
Penàguila 0.07 (1.0) Alcúdia de Crespins, L ' 0.07 (1.0)
Petrer 0.09 (1.0) Alcúdia, L ' 0.07 (1.0)
Pilar de la Horadada 0.12 (1.0) Aldaia 0.07 (1.0)
Pinoso 0.09 (1.0) Alfafar 0.07 (1.0)
Plans 0.07 (1.0) Alfara of the Patriarch 0.06 (1.0)
Poblets, Els 0.06 (1.0) Alfarp 0.07 (1.0)
Polop 0.08 (1.0) Alfarrasí 0.07 (1.0)
Quatretondeta 0.07 (1.0) Alfauir 0.07 (1.0)
Rafal 0.16 (1.0) Algemesi 0.07 (1.0)
Ràfol d'Almúnia, The 0.07 (1.0) Algimia of Alfara 0.04 (1.0)
Redovan 0.16 (1.0) Alginet 0.07 (1.0)
Relleu 0.08 (1.0) Almàssera 0.06 (1.0)
Rojales 0.15 (1.0) Almiserà 0.07 (1.0)
Romana, The 0.11 (1.0) Almoines 0.07 (1.0)
Sagra 0.07 (1.0) Almussafes 0.07 (1.0)
Salinas 0.08 (1.0) Farmhouse of the Countess /
San Fulgencio 0.16 (1.0) Farmhouse of the Comtessa, 0.07 (1.0)
L'
San Isidro 0.15 (1.0) Alzira 0.07 (1.0)
San Miguel de Salinas 0.15 (1.0) Anna 0.07 (1.0)
San Vicente del Raspeig / Antella 0.07 (1.0)
Sant Vicent del Raspeig 0.13 (1.0) Atzeneta d'Albaida 0.07 (1.0)
Sanet And Negrals 0.07 (1.0) Ayora 0.07 (1.0)
Sant Joan d'Alacant 0.13 (1.0) Barx 0.07 (1.0)
Santa Pola 0.15 (1.0) Barxeta 0.07 (1.0)
Sax 0.08 (1.0) Belgida 0.07 (1.0)
Seal 0.08 (1.0) Bellreguard 0.07 (1.0)
Senija 0.06 (1.0) Bellús 0.07 (1.0)
Tarbena 0.07 (1.0) Benaguasil 0.05 (1.0)
Teulada 0.06 (1.0) Beneixida 0.07 (1.0)
Tibi 0.09 (1.0) Benetússer 0.07 (1.0)
Tollos 0.07 (1.0) Beniarjó 0.07 (1.0)
Tormos 0.07 (1.0) Beniatjar 0.07 (1.0)
Torremanzanas / Torre de les Benicolet 0.07 (1.0)
Maçanes, The 0.08 (1.0) Benifaió 0.07 (1.0)
Torrevieja 0.14 (1.0) Benifairó de la Valldigna 0.07 (1.0)
Vall d'Alcalà, The 0.07 (1.0) Beniflá 0.07 (1.0)
Ebo Valley 0.07 (1.0) Benigánim 0.07 (1.0)
Vall de Gallinera 0.07 (1.0) Benimodo 0.07 (1.0)
Vall de Laguar, La 0.07 (1.0) Benimuslem 0.07 (1.0)
Verger, The 0.06 (1.0) Beniparrell 0.07 (1.0)
Villajoyosa / Vila Joiosa, La 0.11 (1.0) Benirredrà 0.07 (1.0)
Villena 0.07 (1.0) Benisanó 0.05 (1.0)
Benisoda 0.07 (1.0)
Benisuera 0.07 (1.0)
Province of Valencia / València Betera 0.06 (1.0)
Bicorp 0.07 (1.0)
Adore 0.07 (1.0) Bocairent 0.07 (1.0)
Agullent 0.07 (1.0) Bolbaite 0.07 (1.0)
Aielo of Malferit 0.07 (1.0) Bonrepòs i Mirambell 0.06 (1.0)
Aielo de Rugat 0.07 (1.0) Bufali 0.07 (1.0)
Alaquàs 0.07 (1.0) Bunol 0.06 (1.0)
Albaida 0.07 (1.0) Burjassot 0.06 (1.0)
Albal 0.07 (1.0) Canals 0.07 (1.0)
Albalat of La Ribera 0.07 (1.0) Canet D'en Berenguer 0.04 (1.0)
Albalat dels Sorells 0.06 (1.0) Carcaixent 0.07 (1.0)
Albalat dels Tarongers 0.04 (1.0) Càrcer 0.07 (1.0)
Alberic 0.07 (1.0) Carlet 0.07 (1.0)
84
Municipality tob / g K Municipality tob / g K
85
Municipality tob / g K Municipality tob / g K
86
Municipality tob / g K Municipality tob / g K
87
Municipal tob / K Municipality tob / g K
ity g
Ramirás 0.04 (1.0) Campanet 0.04 (1.0)
Ribadavia 0.04 (1.0) Fields 0.04 (1.0)
Rúa, A 0.04 (1.0) Capdepera 0.04 (1.0)
San Amaro 0.04 (1.0) Castell, Is 0.04 (1.0)
San Cibrao das Viñas 0.04 (1.0) Ciutadella de Menorca 0.04 (1.0)
Saint Christ of Cea 0.04 (1.0) Consell 0.04 (1.0)
San Xoán de Rio 0.04 (1.0) Costitx 0.04 (1.0)
Sandias 0.04 (1.0) Deyá 0.04 (1.0)
Sarreaus 0.04 (1.0) Ibiza 0.04 (1.0)
Taboadela 0.04 (1.0) Escorca 0.04 (1.0)
Teixeira, A 0.04 (1.0) Esporles 0.04 (1.0)
Toen 0.04 (1.0) Estellencs 0.04 (1.0)
You transmit 0.04 (1.0) Felanitx 0.04 (1.0)
Verea 0.04 (1.0) Ferreries 0.04 (1.0)
Verin 0.04 (1.0) Formentera 0.04 (1.0)
Viana do Bolo 0.04 (1.0) Fornalutx 0.04 (1.0)
Vilamarin 0.04 (1.0) Inca 0.04 (1.0)
Vilamartín de Valdeorras 0.04 (1.0) Lloret de Vistaalegre 0.04 (1.0)
Vilar de Barrio 0.04 (1.0) Lloseta 0.04 (1.0)
Vilar de Santos 0.04 (1.0) Llubí 0.04 (1.0)
Vilariño de Conso 0.04 (1.0) Llucmajor 0.04 (1.0)
Xinzo de Limia 0.04 (1.0) Mahon 0.04 (1.0)
Xunqueira de Ambía 0.04 (1.0) Manacor 0.04 (1.0)
Xunqueira de Espadanedo 0.04 (1.0) Mancor de la Vall 0.04 (1.0)
Maria de la Salut 0.04 (1.0)
Marratxí 0.04 (1.0)
Pontevedra Province Mercadal, Is 0.04 (1.0)
Migjorn Gran, Is 0.04 (1.0)
Beleaguered 0.04 (1.0) Montuïri 0.04 (1.0)
Tree 0.04 (1.0) Wall 0.04 (1.0)
Cañiza, A 0.04 (1.0) Palma de Mallorca 0.04 (1.0)
Covelo 0.04 (1.0) Petra 0.04 (1.0)
Growing 0.04 (1.0) Pobla, Sa 0.04 (1.0)
Dozon 0.04 (1.0) Pollença 0.04 (1.0)
Forcarei 0.04 (1.0) Porreres 0.04 (1.0)
Igrexa, A 0.04 (1.0) Puigpunyent 0.04 (1.0)
Lalin 0.04 (1.0) Salines, Ses 0.04 (1.0)
Mondariz 0.04 (1.0) Saint Joseph 0.04 (1.0)
Mondariz Spa or Troncoso 0.04 (1.0) Sant Antoni de Portmany 0.04 (1.0)
Neves, As 0.04 (1.0) Sant Joan 0.04 (1.0)
Pedreira, A 0.04 (1.0) Sant Joan de Labritja 0.04 (1.0)
Rodeiro 0.04 (1.0) Sant Llorenç des Cardassar 0.04 (1.0)
Silleda 0.04 (1.0) Sant Lluís 0.04 (1.0)
Vila de Cruces 0.04 (1.0) Saint Eugene 0.04 (1.0)
Santa Eulalia del Rio 0.04 (1.0)
Santa Margalida 0.04 (1.0)
ILLES BALEARS Santa Maria del Camí 0.04 (1.0)
Santanyí 0.04 (1.0)
Illes Balears Province Jungle 0.04 (1.0)
Sencelles 0.04 (1.0)
Alaior 0.04 (1.0) Sineu 0.04 (1.0)
Alaró 0.04 (1.0) Soller 0.04 (1.0)
Alcúdia 0.04 (1.0) They are Servera 0.04 (1.0)
Algaida 0.04 (1.0) Valldemosa 0.04 (1.0)
Andratx 0.04 (1.0) Vilafranca de Bonany 0.04 (1.0)
Ariany 0.04 (1.0)
Artà 0.04 (1.0)
Banyalbufar 0.04 (1.0) MURCIA REGION
Binissalem 0.04 (1.0)
Buger 0.04 (1.0) Murcia province
Bunyola 0.04 (1.0)
Calvià 0.04 (1.0) Abanilla 0.15 (1.0)
88
Municipality tob /gK Municipality tob /gK
89
Municipal tob / K Municipality tob / g K
ity g
Etxauri 0.04 (1.0) Nazar 0.04 (1.0)
Eulate 0.04 (1.0) Noáin (Valley of Elorz) / Noain
Ezcabarte 0.04 (1.0) (Elortzibar) 0.04 (1.0)
Ezcároz / Ezkaroze 0.06 (1.0) Obanos 0.04 (1.0)
Ezkurra 0.04 (1.0) Ochagavía 0.06 (1.0)
Ezprogui 0.04 (1.0) Oco 0.04 (1.0)
Galar 0.04 (1.0) Odieta 0.04 (1.0)
Gallués / Galoze 0.05 (1.0) Oitz 0.04 (1.0)
Garaioa 0.05 (1.0) Olaibar 0.04 (1.0)
Garde 0.06 (1.0) Olazti / Olazagutía 0.04 (1.0)
Garinoain 0.04 (1.0) Olejua 0.04 (1.0)
Garralda 0.05 (1.0) Ollo 0.04 (1.0)
Goizueta 0.04 (1.0) Olóriz 0.04 (1.0)
Goñi 0.04 (1.0) Olza 0.04 (1.0)
Güesa / Gorza 0.05 (1.0) Orbaitzeta 0.05 (1.0)
Guesálaz 0.04 (1.0) Orbara 0.05 (1.0)
Guirguillano 0.04 (1.0) Orcoyen 0.04 (1.0)
Hiriberri / Villanueva de Aezkoa 0.05 (1.0) Orisoain 0.04 (1.0)
Huarte / Uharte 0.04 (1.0) Oronz 0.06 (1.0)
Ibargoiti 0.04 (1.0) Oroz Betelu 0.05 (1.0)
Igantzi 0.04 (1.0) Orreaga / Roncesvalles 0.05 (1.0)
Iguzquiza 0.04 (1.0) Oteiza 0.04 (1.0)
Imotz 0.04 (1.0) Pamplona / Iruña 0.04 (1.0)
Irañeta 0.04 (1.0) Piedramillera 0.04 (1.0)
Irurtzun 0.04 (1.0) Puente La Reina / Gares 0.04 (1.0)
Isaba / Izaba 0.07 (1.0) Pueyo 0.04 (1.0)
Ituren 0.04 (1.0) Romanced 0.04 (1.0)
Iturmendi 0.04 (1.0) Roncal / Erronkari 0.06 (1.0)
Iza 0.04 (1.0) Sada 0.04 (1.0)
Izagaondoa 0.04 (1.0) You went out 0.04 (1.0)
Izalzu / Itzaltzu 0.06 (1.0) Salinas de Oro 0.04 (1.0)
Jaurrieta 0.06 (1.0) Sangüesa / Zangoza 0.04 (1.0)
Javier 0.04 (1.0) Sarriés / Sartze 0.05 (1.0)
Juslapeña 0.04 (1.0) Sorlada 0.04 (1.0)
Lakuntza 0.04 (1.0) Sunbilla 0.04 (1.0)
Wool 0.04 (1.0) Tiebas Muruarte de Reta 0.04 (1.0)
Lantz 0.04 (1.0) Tirapu 0.04 (1.0)
Larraona 0.04 (1.0) Ucar 0.04 (1.0)
Larraun 0.04 (1.0) Uharte Arakil 0.04 (1.0)
Leache 0.04 (1.0) Ultzama 0.04 (1.0)
Legarda 0.04 (1.0) Unciti 0.04 (1.0)
Legaria 0.04 (1.0) Unzué 0.04 (1.0)
Leitza 0.04 (1.0) Urdazubi / Urdax 0.05 (1.0)
Leoz 0.04 (1.0) Urdiain 0.04 (1.0)
Lerga 0.04 (1.0) Urraul Alto 0.05 (1.0)
Lesaka 0.04 (1.0) Urraul Low 0.04 (1.0)
Lezáun 0.04 (1.0) Urrotz 0.04 (1.0)
Liedena 0.04 (1.0) Urroz 0.04 (1.0)
Lizoáin 0.04 (1.0) Urzainqui 0.06 (1.0)
Long / Long 0.04 (1.0) Uterga 0.04 (1.0)
Lumbier 0.04 (1.0) Uztárroz / Uztarroze 0.07 (1.0)
Luquin 0.04 (1.0) Vidángoz / Bidankoze 0.05 (1.0)
Luzaide / Valcarlos 0.05 (1.0) Villamayor de Monjardín 0.04 (1.0)
Maneru 0.04 (1.0) Villatuerta 0.04 (1.0)
Mendaza 0.04 (1.0) Villava / Atarrabia 0.04 (1.0)
Beggar 0.04 (1.0) Yerri 0.04 (1.0)
Metauten 0.04 (1.0) Yesa 0.04 (1.0)
Monreal 0.04 (1.0) Zabalza 0.04 (1.0)
Morentin 0.04 (1.0) Ziordia 0.04 (1.0)
Murieta 0.04 (1.0) Zubieta 0.04 (1.0)
Muruzábal 0.04 (1.0) Zugarramurdi 0.05 (1.0)
Navascués 0.05 (1.0) Zuniga 0.04 (1.0)
90
Municipality tob / g K Municipality tob / g K
91
Index
ANNEXED.
ARTICULATED AND COMMENTS
CHAPTER I. GENERAL
CHAPTER III.CALCULATION
93
3.6.2.4. Combination of the results obtained for the different modes .......................................... 25
3.6.2.5. Calculation of solicitations .............................................................................................. 25
3.7. Simplified calculation method for the most common cases of edification .................................. 25
3.7.1. Model of the structure25 ....................................................................................................
3.7.2. Modes of vibration26..........................................................................................................
3.7.2.1. Number of modes a to consider ..................................................................................... 26
3.7.2.2. Calculation of the fundamental period of the buildings ................................................... 26
3.7.3. Calculation of forces seismic27 .........................................................................................
3.7.3.1. Response coefficient ............................................................................................................. 28
3.7.3.2. Distribution factor ................................................................................................................... 30
3.7.3.3. Displacements ............................................................................................................... 31
3.7.4. Static forces system equivalents31 ....................................................................................
3.7.5. Consideration of the effects of rotation32 ..........................................................................
3.8. Second effects order.................................................................................................................. 32
3.9. Walls of containment ................................................................................................................. 32
Old 1...................................................................................................................................................... 67
94