Huddersfield Mains Lighting
E = F x n x N x MF x UF
A
Where:
E = average illuminance
F = initial lamp lumens
n = number of lamps in each luminaire
N = number of luminaires
MF = maintenance factor
UF = utilisation factor
A = area
of the luminous flux from the lamp that Utilisation factors / TM5
reaches the working plan. This is for the Reflectances Room Index
specific luminaire and allows for surface C W F 0.75 1.0 1.25 1.5 2.0 2.5 3.0 4.0 5.0
70 50 20 N/A 66 72 76 81 85 87 90 92
reflectivity and Room Index. The UF is used 70 30 20 N/A 60 66 71 77 81 84 87 90
in average lumen calculations to calculate 70 10 20 N/A 56 62 67 73 78 81 85 88
the average illumination level for an area 50 50 20 N/A 64 70 73 79 82 84 87 89
50 30 20 N/A 59 65 69 75 78 81 84 86
with a specific luminaire. 50 10 20 N/A 56 61 66 72 76 78 82 85
30 50 20 N/A 63 68 71 76 79 81 83 85
30 30 20 N/A 58 64 68 73 76 78 82 83
30 10 20 N/A 55 61 65 70 74 76 80 82
0 0 0 N/A 53 58 62 67 71 73 76 78
BZ-class 1 2 2 2 2 2 3 3 3
The society of light and lighting produce a number of design guides (LG) for specific
applications which offer useful design advice for best practice approach to illuminating
these areas. A sample of the available guides are: Lighting Guide 02: Hospitals and
Healthcare Buildings, Lighting Guide 04: Sports Lighting, Lighting Guide 05: Light for
Education, Lighting Guide 07: Office Lighting and Lighting Guide 08: Lighting for Museums
and Art Galleries.
Certificate of Conformity
The guide requires that the designer
and installer of the installation complete
and sign a Certificate of Conformity to
demonstrate that all known visual and
ergonomic criteria were fully considered Terzetto
during the design process and installed as
specified.
- Ceilings; 70-90%
- Walls; 50-80%
- Floor; 20-40%
Professional lighting design requires detailed luminaire photometric and product design
data. Eaton’s advanced photometric facility produces accurate performance data for all
product types and light sources, including LEDs.
Eaton provides its customers with this information in partnership with the leading lighting
design software packages to enable accurate and detailed design to be created.
Relux is a simple and intuitive lighting Detailed artificial light simulations can
design software package which enables be created for interior and outdoor
you to produce designs efficiently and projects based on BS EN 12464-1 and -2,
accurately. emergency lighting designs based on EN
1838, roads based on EN 13201, and sports
Construction of rooms, structural elements grounds and daylight based on CIE.
and the positioning of luminaires, objects
and furniture, is done by a simple library Additionally with the Relux energy unit
driven menu system. A comprehensive you are able to calculate the energy
selection of materials and textures can performance of the lighting scheme to
be allocated to your design elements, EN15193 (LENI).
adding a realistic touch to rendered outputs
including the facility to show effective walk A comprehensive results list enables you
through visualisations of your projects. to construct reports exactly to your client’s
For more complex designs the import and needs, from simple basic calculations to
export functions for 2D dxf and dwg files full rendered imagery and results tables.
significantly reduce your design time.
For more information and free download of
the Relux software, visit www.relux.biz
Building Regulations
When specifying luminaires, legislation, as per circuit Watts for office, industrial and
defined by the Building Regulations, must storage areas. Lamp lumens per circuit
be considered to ensure that the installation Watts are used for all other areas. There is
meets with current requirements. The a small allowance for display lighting where
two most relevant pieces of legislation relevant.
contained within the Building Regulations
are: Option 2 is a simplified version of
EN15193 known as LENI (Lighting Energy
• Conservation of fuel and power, which Numeric Indicator). This is based on an
includes limits on the energy efficiency energy consumption model with actual
of lighting in domestic and non-domestic usage targets for a selection of areas and
buildings. operating hours in Kwh/m2 per annum.
• Fire Safety, which includes the The requirements can be met by selecting
requirements for emergency lighting and an efficient lamp, control gear and luminaire
provisions for the use of thermoplastic performance combination, along with
materials, such as luminaire diffusers. lighting controls that make maximum use
Included below is a brief guide to each of of daylight and avoid unnecessary lighting
these documents. during times when spaces are unoccupied.
It should be noted that these documents Solutions include using high frequency
are specific for each part of the UK, dimmable control gear linked to photocells
England, Scotland, Wales and Ireland, and to provide constant illumination and daylight
you should refer to the relevant versions for linking. Intelligent luminaires, such as
the project. Intellect, provide a straightforward solution
to providing lighting control with user
The latest information and requirements selectable functionality.
can be obtained by contacting our technical
support and application department. It is strongly recommended that reference
A list of recommended websites is also be made to the current edition of Approved
included below. Document L, to ensure compliance with
the latest requirements. Full details of Part
Consideration of fuel and power L can be found on
This requires that energy efficient lighting www.communities.gov.uk, or alternatively,
be used in all buildings. The regulations a direct web address would be
currently apply to all new buildings and www.planningportal.gov.uk/
refurbishments of over 100m2 floor area. buildingregulations.
The document provides design information
in non-domestic buildings. Fire safety regulations
Includes the fire safety requirements
The 2014 version now provides two ways for emergency lighting and the use of
to provide the energy information during thermoplastic materials. The impact
the design stage. on emergency lighting of Approved
Documents defines the provisions that
Option 1 is based on the installed load apply to the use of luminaire diffusers,
and uses the metric of luminaire lumens which form part of the ceiling. It should be