7191101923-EEC14-01
dated 11 Dec 2014
Note: This report is issued subject to the Testing and Certification Regulations of the TÜV SÜD Group and the
General Terms and Conditions of Business of TÜV SÜD PSB Pte Ltd. In addition, this report is governed by the
terms set out within this report.
Subject
Client
20 Nov 2014
Description of Sample
Method of Test
The assessment detailed in this document was carried out by adopting the test methods of the selected
clauses of British Standard 6387 : 1994 as requested by the client.
Results
7.1 Conductor resistance at 20°C ( /km) 9.00 Maximum : 9.18 (see remark
4)
11.1 Resistance to fire alone (Category C) Complied No fuse shall be ruptured nor
Flame temperature : 950 ± 40°C (see remark 5) any lamp extinguished during
Test voltage : 600/1000V the test.
Test duration : 3 hours
11.3 Resistance to fire with mechanical shock Complied No fuse shall be ruptured nor
(Category Z) (see remark 6) any lamp extinguished during
Flame temperature : 950 ± 40°C the test.
Test voltage : 600/1000V
Test duration : 15 minutes
Page 2 of 5
Test Report No. 7191101923-EEC14-01
dated 11 Dec 2014
Remarks:
1) Witness testing was conducted at Phelps Dodge International (Philippines) Inc. Luisita Industrial Park,
San Miguel, Tarlac City, Philippines from 20 Nov 2014 to 21 Nov 2014.
2) The scope of British Standard 6387 : 1994 does not cover cables having one insulated conductor
without metallic element. Tests were conducted by adopting the test methods specified in British
Standard 6387 : 1994.
3) The British Standard 6387 : 1994 is applicable to cables rated at voltages not exceeding 450/750V. The
voltage applied to the tests in this document were based on 600/1000V.
4) For conductor resistance at 20°C, no requirement provided as 2.0 mm 2 is not within the clause 7.1 of
British Standard 6387 : 1994. The requirement is accordance with PNS 1207:2006 as requested by the
client.
5) For resistance to fire alone, 4 metal supporting rings were used instead of 5 metal supporting rings as
stated in the clause D.2.1.2 of British Standard 6387 : 1994.
6) For resistance to fire with mechanical shock, each length of two steel runners is 1.2 m, size of board is
905 mm x 304 mm x 13 mm and the mass of the wall is 16.5 kg were used instead of the parameters
stated in the clause D.4.1.2 of British Standard 6387 : 1994.
7) Except for remarks 2 to 6, the sample tested is deemed to comply with the adopted test methods of
British Standard 6387 : 1994 for those tests conducted.
Page 3 of 5
Test Report No. 7191101923-EEC14-01
dated 11 Dec 2014
Appendix I
Manufactured by Phelps Dodge Phils. 2mm2 LSHF FIRE RATED CABLE 600V 2014
7191101923-EEC14-01
Page 4 of 5
Test Report No. 7191101923-EEC14-01
dated 11 Dec 2014
Please note that this Report is issued under the following terms :
1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.
2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no
responsibility for the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information
supplied.
3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.
4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or results
furnished by TÜV SÜD PSB in any advertisements or sales promotion.
5. Unless otherwise stated, the tests were carried out in TÜV SÜD PSB Pte Ltd, No.1 Science Park Drive Singapore 118221.
July 2011
Page 5 of 5