Rated voltage 72.5 kV 145 kV 170 kV 245 kV 300 kV 420 kV 420 kV 550 kV 800 kV
Rated short-
31.5 kA 40 kA 63 kA 50 kA 63 kA 63 kA 80 kA 63 kA 50 kA
circuit current
Rated current 2500 A 3150 A 4000 A 4000 A 4000 A 4000 A 6300 A 5000 A 5000 A
- Q0
Solution
Rated voltage 72.5 kV 145 kV 170 kV 245 kV 300 kV 420 kV 420 kV 550 kV 800 kV
Rated short-
31.5 kA 40 kA 63 kA 50 kA 63 kA 63 kA 80 kA 63 kA 50 kA
circuit current
Rated current 2500 A 3150 A 4000 A 4000 A 4000 A 4000 A 6300 A 5000 A 5000 A
Technical Data
Voltage 72.5 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 140 kV
Lightning impulse withstand voltage (1.2/50 µs) 325 kV
Busbar Current 2500 A
Feeder Current 2500 A
Short-circuit breaking current 31.5 kA
Short-time withstand current (3 s) 31.5 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width 650 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
7 2
8 10
M 4 M 3
6 7
4
5 M 5
1 8
9
6
3
Technical Data
Voltage 145 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 275 kV
Lightning impulse withstand voltage (1.2/50 µs) 650 kV
Busbar Current 3150 A
Feeder Current 3150 A
Short-circuit breaking current 40 kA
Short-time withstand current (3 s) 40 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width: common drive 800 mm
single drive 1200 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
2 7
M 4 M 3
8 10
7
6
4
5
1 M 5
8
3
6
9
Technical Data
Voltage 145 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 275 kV
Lightning impulse withstand voltage (1.2/50 µs) 650 kV
Busbar Current 3150 A
Feeder Current 3150 A
Short-circuit breaking current 40 kA
Short-time withstand current (3 s) 40 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width n.a.
Driving mechanism of circuit-breaker spring operated
(Single and common drive)
Ambient temperature -25°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
10
1
7
5
Technical Data
Voltage 170 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 325 kV
Lightning impulse withstand voltage (1.2/50 µs) 750 kV
Busbar Current 4000 A
Feeder Current 4000 A
Short-circuit breaking current 63 kA
Short-time withstand current (3 s) 63 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width: common drive 1000 mm
single drive 1200 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE / GOST
other values on request
* type tested
7 2
8 M 4 M 3
10
6 1
5
7
4
1 5
9 M
3 6
- Q0
Solution
Rated voltage 72.5 kV 145 kV 170 kV 245 kV 300 kV 420 kV 420 kV 550 kV 800 kV
Rated short-
31.5 kA 40 kA 63 kA 50 kA 63 kA 63 kA 80 kA 63 kA 50 kA
circuit current
Rated current 2500 A 3150 A 4000 A 4000 A 4000 A 4000 A 6300 A 5000 A 5000 A
Technical Data
Voltage 245 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 460 kV
Lightning impulse withstand voltage (1.2/50 µs) 1050 kV
Busbar Current 4000 A
Feeder Current 4000 A
Short-circuit breaking current 50 kA
Short-time withstand current (3 s) 50 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width 1500 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
M 3 M 5
M 8
1
11
M 9
7M
12 10
13
Technical Data
Voltage 300 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 460 kV
Lightning impulse withstand voltage (1.2/50 µs) 1050 kV
Busbar Current 4000 A
Feeder Current 4000 A
Short-circuit breaking current (2 cycles) 63 kA
Short-time withstand current (3 s) 63 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width 2200 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
3 5 4 6 6 5
4
3
5 5
9
6
7 8
6
10
2 8 5
1 7
9
10
- Q0
Solution
Rated voltage 72.5 kV 145 kV 170 kV 245 kV 300 kV 420 kV 420 kV 550 kV 800 kV
Rated short-
31.5 kA 40 kA 63 kA 50 kA 63 kA 63 kA 80 kA 63 kA 50 kA
circuit current
Rated current 2500 A 3150 A 4000 A 4000 A 4000 A 4000 A 6300 A 5000 A 5000 A
Technical Data
Voltage 420 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 650 kV
Lightning impulse withstand voltage (1.2/50 µs) 1425 kV
Switching impulse withstand voltage (250/2500 µs) 1050 kV
Busbar Current 4500 A
Feeder Current 4000 A
Short-circuit breaking current (2 cycles) 63 kA
Short-time withstand current (3 s) 63 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width 2200 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
3 5 6 4 6 5
4
3
5 5
9
8
7
8 6
2 10 5
1 7
9
10
Technical Data
Voltage 420 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 650 kV
Lightning impulse withstand voltage (1.2/50 µs) 1425 kV
Switching impulse withstand voltage (250/2500 µs) 1050 kV
Busbar Current 6300 A
Feeder Current 5000 A
Short-circuit breaking current (2 cycles) 80 kA
Short-time withstand current (3 s) 80 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width 3600 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
Technical Data
Voltage 550 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 740 kV
Lightning impulse withstand voltage (1.2/50 µs) 1675 kV
Switching impulse withstand voltage (250/2500 µs) 1250 kV
Busbar Current 5000 A
Feeder Current 5000 A
Short-circuit breaking current (2 cycles) 63 kA
Short-time withstand current (3 s) 63 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width 3600 mm
Driving mechanism of circuit-breaker spring operated
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
- Q0
Solution
Rated voltage 72.5 kV 145 kV 170 kV 245 kV 300 kV 420 kV 420 kV 550 kV 800 kV
Rated short-
31.5 kA 40 kA 63 kA 50 kA 63 kA 63 kA 80 kA 63 kA 50 kA
circuit current
Rated current 2500 A 3150 A 4000 A 4000 A 4000 A 4000 A 6300 A 5000 A 5000 A
Technical Data
Voltage 800 kV
Frequency 50 / 60 Hz
Power-frequency withstand voltage (1 min.) 960 kV
Lightning impulse withstand voltage (1.2/50 µs) 2100 kV
Switching impulse withstand voltage (250/2500 µs) 1425 kV
Busbar Current 5000 A
Feeder Current 5000 A
Short-circuit breaking current (2 cycles) 50 kA
Short-time withstand current (3 s) 50 kA
Leakage rate per year and gas compartment < 0.1* %
Bay width 4500 mm
Ambient temperature -30°C up to +40°C
Installation indoor/outdoor
Expected life time > 50 years
Standard IEC / IEEE
other values on request
* type tested
137500
101000
67500
298000
14000
65400
Area 8000 m²
Clean room conditions
Assembly
Locks for material
Routine tests (IEC)
Computerized technology
In-house machining of vessels ensures
high quality of sealing surfaces
Own paint shop
2
3
4
5 1 Contact support
2 Quenching nozzle
3 Main contact
6 4 Arcing contact
5 Contact cylinder
6 Base
1 Closing release
2 Cam plate
3 Coupling linkage
4 Operating rod
5 Closing spring
connection rod
6 Opening spring
connection rod
7 Closing spring
8 Hand-wound mechanism
9 Charging mechanism
10 Charging shaft
11 Roller lever
12 Closing damper
13 Operating shaft
14 Opening damper
15 Opening release
On „off“ position 16 Mechanism housing
17 Opening spring
Off (Closing spring loaded)
© Siemens AG 2011. All rights reserved
Page 42 Oct-11 Energy Sector / Power Transmission / High Voltage Substations
Customer benefits of self-compression circuit-
breakers and spring operated mechanism platforms