INTELLIGENT DIGITAL DISPLAY TEMPERATURE CONTROLLER

XMT-1000 INSTRUCTION MANUAL


Before using this product, please carefully read this manual for its correct use. In addition, after reading the manual keep it available easily anytime.

OPERATION PRECAUTIONS

Before cleaning the instrument, check that the power is turned off.

Remove stains on the display unit using a soft cloth or tissue paper.

As the display unit is easily scratched, do not scrub or touch it with a hard object.

Do not operate the front key with a pointed object such as a ballpoint pen or screwdriver, as this may scratch or damage the key.

1.PRODUCT CHECK
XMT□-□□□□□□ □ □—□
① ②③④⑤⑥⑦ ⑧ ⑨

①Panel Dimensions(mm) ⑤ Type of Input

D:96×96 1: Thermocouple signal

E:72×72 2: Thermo-resistance signal (RTD input)

F:96×48(Vertical form) ⑥Type of Output

G:48×48 No: Relay contact (Maximum 3A)

②Type of Display V: Logic output for SSR

1: Double rows display A: Relay contact (Maximum 16A)

③Type of control action G: Relay contact (Maximum 16A)

0: On-off action Relay ⑦Type of power

3: Time proportion action X:20~40v; Y:187~242VAC; Z:85~264VAC

4: On-off PID control with auto tuning ⑧Type of calibration

7: Single phase zero-across pulse PID action with auto-tuning ⑨The range of measurement

<Accessories>

④On-off position Alarm Mounting bracket: 2 pieces

0: No alarm Instruction manual: 1 copy

1: High alarm 2:absolute value of high 3:Low alarm 4:absolute value of Low

2.MOUNTING
2.1Main technique principal
(1) Type of Input: thermocouple E, EA, K; thermo-resistance Pt100, Cu50.

(2) Measure the error:≦±0.5%(F,S)±1dig。

(3)Measure temperature at most: 999℃.

(4)Control method: On-off action Relay ,Time proportion action ,Single phase zero-across pulse PID action with auto-tuning

(5)P I D Choose the range in parameter: Proportional band 1~100%, Integral time 0~999s, Differential time0~999s.

(6) The time of keeping time: ten years.

(7)Control the capacity of outputting:

Contact type:3A/250VAC(Resistance load), Life-span of contact≥10^5times; Level type(Used for driving SSR or controlling the logical circuit):

12VDC/30Ma; SSR(Used for urging SSR to use for driving the two-way silicon controlled rectifier of high-power): 0.5A/250VAC.

(8) Alarm output: Contact type, Capacity of contact:1A/250VAC((Resistance load).

(9) Great power output type: Contact type: 5A/250VAC. Pulse type: 2.5A/250VAC(XMTG TYPE),4A/250VAC.

(10) Voltage of the power: Consulting type table power range.

(11) Consumption: ≤5W.

(12) Environment for use: Temperature 0~50℃, Ambient humidity≤85%,Has not corroded, there is no conductive dust。
3. Configuration of the Instrument Panel
①Measured value (PV)display unit (Red)

Displays measured value (PV).

PV Displays various characters depending on the

instrument.

① ②Set value (SV)display unit (Green)

Displays set value (SV)

SP ② Displays various each parameter set value depending

on the instrument.

③Indication lamps

ALM OUT AT ③ Auto-tuning(AT)lamp [Green]. Flashes during

auto-tuning execution.

Control output lamps [Green](OUT)turned on

when outputs operate

SET AT Alarm output lamp (ALM)[Red] turned on when

output operate

④ Function key

Used for displaying the change and confirm of the

④ ⑤ ⑥ ⑦ parameters

⑤ Shift Key

Used for Adjusting key to change the digital code and/or the key to express entering the auto-

tuning state

⑥,⑦ Adjusting key to change the digital

. Used for adjusting the digital code displayed

4. Dimensions

The appearance and the hole measurement form:


H h type Size of the panel Size of the shell the size of hole
H×B h×b×L h’×b’
XMTD 96×96 92×92×70 (92+1) ×(92+1)
XMTE 72×72 68×68×70 (68+1)×(68+1)
B L
XMTF 96×48 92×44×70 (92+1)×(44+1)
b b’ XMTG 48×48 44×44×70 (44+1)×(44+1)

h’
5. Wiring
5.1 Wiring attention
(1) The electric thermocouple inputting, should use the corresponding compensation wire.

(2) The input signal line should be far away from the instrument cable, motive force cable and load line, in order to avoid producing the miscellaneous

news to interfere. ⑴ ㈠ ⑾

Control output Control level output

⑵ ㈩ ⑿
① ㈠ ⑥ ⑴ ⑻
Alarm output Control output Alarm output Control output ⑶
② ⑦ ⑵ ⑼

③ ㈩ ⑧ ⑶ ⑽ Alarm output

signal input ⑸
④- ⑨ ⑷ ㈠ ⑾
Power input signal input Control level output ⑹

⑤+ ⑩ ⑸ - ㈩ ⑿ Power input


⑹+ ⒀
XMTG-1000 Power input ⑻
⑺ ⒁

signal input ⑼ -

XMTE-1000 ⑽+

XMTD/F-1000

6. Operation
6.1 Have the electricity to show:
Belonging to the display and indicator lamp to light after being set up an electric circuit, then show the type and graduation number , then upper and

lower limit Cheng of showing etc., the first three status display enter routine measurement value after the one second respectively / the establishing value

show that put into and control running.

PV

On power SV

All displays lighting The type of the instrument and calibration The range of measurement Measureing and establishing value display

Caution: The calibration code of the instrument inputing : E: Thermocouple, K: Thermocouple, EA2: Thermocouple
CU50: Thermo-resistance PT100: Thermo-resistance

6.2 Establish temperature value:


Press “ ” or “” “” both can enter the state of establishing, If below row displays " SP " ( establishing value code ); Press “” “” can add and subtract the

temperature of establishing one by one: Press /AT can select figure number revised to want , make it glimmer , press “” “” can make it glimmer location

choose a number value needed from 0 to 9 。After modifying the establishing value , press a key approve and withdraw the setting for value not to set for
the state to revise。

the method of establishing negative temperature:

Establish temperature value first , press “/AT”establish high position most , press “” make it reduce to " 0 " , continue according to appear"

-"Number。

6.3 P I D parameter Auto-tuning


After the machine is set up an electric circuit, establish temperature at first, press “/AT”greater than ten seconds , " AT " indicator lamp show

instrument enter course of auto-turning , after two shake cycle system to glimmer, the auto-turning ends, " AT" light put out, instrument at this moment get

one control parameter that group optimizes and keep for a long time.

CAUTION:
1 When the systematic operating mode changes bigger, should since exactly fix once again , in order to meet the new systematic parameter

2 it will withdraw from the state of auto-turning while losing electrical power,it’s parameter does not change。

Following table lists the function parameters


The first step Press “ ” + “” ≧10s can enter the state of establishing parameter

Initial value setting at


Order Type of Display Represent the content Number value meaning
factory

Dead band for on-off control and Alarm. For on-off


Db : Difference switched
1 controller, On-off control and alarm adopted Same 0.5
over
value.

The time proportion is established again, dispel the

Ub : The time proportion quiet and bad power of maintaining(0~90%).Only


2 5%
is established again used for adjusting the quiet difference of the

proportion controller
The second step:
When “P” is large, the proportional Action is small.
Show each parameter 3 Proportional Band 15.0
Only used for heating Side. P=0,On-off Control
in the order with
(Re-setting time) When “I” is large, the integral action
pressing “ ”。 If revise 4 Integral Time 180
Is small. I=0,PD Control
the shown
(Pre-setting) When “D” is large the derivative Action
parameters,please 5 Differential Time 70
in large. D=0,PI Control
press “/AT”and
1 Contact type : The electric heater of general
select figure number
machinery is fetched for 20-30 seconds, Fetch the 20s
that will be revised , 6 Control Period
large capacity oven heater for 30-120 seconds 4s
and make it glimmer ,
2 Contactless type:fetch for 3-10 seconds
press “” “” can
Ctr=0/4; Routine control; Ctr=1/5; avoid high shoot;
change to glimmer in
7 Control mode Ctr=2/6: have cable avoid overshoot only, later 2
the location . Press “
controlled according to routine PID
” to confirm and keep
Warning value of upper Lower limit of the
after finishing revising
limit , the warning value span/
8 Ctr=0~2 is AH or AL; Ctr=4~6 is AE
of lower limit, the warning Upper limit of the

value of the deviation span

Amplitude limiting of Lower limit of the


9 establishing value≤SA
establishing value span

Revise the error of the sensor, revise the range as 0-


10 The sensor revising 0
12.7 ℃

Lck fetches 123, the parameter can be changed, then


11 Set data Lock 1234
the parameter can't be revised to fetch other value.
The third step Press “ ” and withdraw from the state of establishing parameter