OPERATION PRECAUTIONS
Before cleaning the instrument, check that the power is turned off.
Remove stains on the display unit using a soft cloth or tissue paper.
As the display unit is easily scratched, do not scrub or touch it with a hard object.
Do not operate the front key with a pointed object such as a ballpoint pen or screwdriver, as this may scratch or damage the key.
1.PRODUCT CHECK
XMT□-□□□□□□ □ □—□
① ②③④⑤⑥⑦ ⑧ ⑨
7: Single phase zero-across pulse PID action with auto-tuning ⑨The range of measurement
<Accessories>
1: High alarm 2:absolute value of high 3:Low alarm 4:absolute value of Low
2.MOUNTING
2.1Main technique principal
(1) Type of Input: thermocouple E, EA, K; thermo-resistance Pt100, Cu50.
(4)Control method: On-off action Relay ,Time proportion action ,Single phase zero-across pulse PID action with auto-tuning
(5)P I D Choose the range in parameter: Proportional band 1~100%, Integral time 0~999s, Differential time0~999s.
Contact type:3A/250VAC(Resistance load), Life-span of contact≥10^5times; Level type(Used for driving SSR or controlling the logical circuit):
12VDC/30Ma; SSR(Used for urging SSR to use for driving the two-way silicon controlled rectifier of high-power): 0.5A/250VAC.
(9) Great power output type: Contact type: 5A/250VAC. Pulse type: 2.5A/250VAC(XMTG TYPE),4A/250VAC.
(12) Environment for use: Temperature 0~50℃, Ambient humidity≤85%,Has not corroded, there is no conductive dust。
3. Configuration of the Instrument Panel
①Measured value (PV)display unit (Red)
instrument.
on the instrument.
③Indication lamps
auto-tuning execution.
output operate
④ Function key
④ ⑤ ⑥ ⑦ parameters
⑤ Shift Key
Used for Adjusting key to change the digital code and/or the key to express entering the auto-
tuning state
4. Dimensions
h’
5. Wiring
5.1 Wiring attention
(1) The electric thermocouple inputting, should use the corresponding compensation wire.
(2) The input signal line should be far away from the instrument cable, motive force cable and load line, in order to avoid producing the miscellaneous
news to interfere. ⑴ ㈠ ⑾
⑵ ㈩ ⑿
① ㈠ ⑥ ⑴ ⑻
Alarm output Control output Alarm output Control output ⑶
② ⑦ ⑵ ⑼
⑷
③ ㈩ ⑧ ⑶ ⑽ Alarm output
signal input ⑸
④- ⑨ ⑷ ㈠ ⑾
Power input signal input Control level output ⑹
⑤+ ⑩ ⑸ - ㈩ ⑿ Power input
⑺
⑹+ ⒀
XMTG-1000 Power input ⑻
⑺ ⒁
signal input ⑼ -
XMTE-1000 ⑽+
XMTD/F-1000
6. Operation
6.1 Have the electricity to show:
Belonging to the display and indicator lamp to light after being set up an electric circuit, then show the type and graduation number , then upper and
lower limit Cheng of showing etc., the first three status display enter routine measurement value after the one second respectively / the establishing value
PV
On power SV
All displays lighting The type of the instrument and calibration The range of measurement Measureing and establishing value display
Caution: The calibration code of the instrument inputing : E: Thermocouple, K: Thermocouple, EA2: Thermocouple
CU50: Thermo-resistance PT100: Thermo-resistance
temperature of establishing one by one: Press /AT can select figure number revised to want , make it glimmer , press “” “” can make it glimmer location
choose a number value needed from 0 to 9 。After modifying the establishing value , press a key approve and withdraw the setting for value not to set for
the state to revise。
Establish temperature value first , press “/AT”establish high position most , press “” make it reduce to " 0 " , continue according to appear"
-"Number。
instrument enter course of auto-turning , after two shake cycle system to glimmer, the auto-turning ends, " AT" light put out, instrument at this moment get
one control parameter that group optimizes and keep for a long time.
CAUTION:
1 When the systematic operating mode changes bigger, should since exactly fix once again , in order to meet the new systematic parameter
2 it will withdraw from the state of auto-turning while losing electrical power,it’s parameter does not change。
proportion controller
The second step:
When “P” is large, the proportional Action is small.
Show each parameter 3 Proportional Band 15.0
Only used for heating Side. P=0,On-off Control
in the order with
(Re-setting time) When “I” is large, the integral action
pressing “ ”。 If revise 4 Integral Time 180
Is small. I=0,PD Control
the shown
(Pre-setting) When “D” is large the derivative Action
parameters,please 5 Differential Time 70
in large. D=0,PI Control
press “/AT”and
1 Contact type : The electric heater of general
select figure number
machinery is fetched for 20-30 seconds, Fetch the 20s
that will be revised , 6 Control Period
large capacity oven heater for 30-120 seconds 4s
and make it glimmer ,
2 Contactless type:fetch for 3-10 seconds
press “” “” can
Ctr=0/4; Routine control; Ctr=1/5; avoid high shoot;
change to glimmer in
7 Control mode Ctr=2/6: have cable avoid overshoot only, later 2
the location . Press “
controlled according to routine PID
” to confirm and keep
Warning value of upper Lower limit of the
after finishing revising
limit , the warning value span/
8 Ctr=0~2 is AH or AL; Ctr=4~6 is AE
of lower limit, the warning Upper limit of the