Professional Documents
Culture Documents
BUILDING
Bonafide record of work done by
KAVIMUGAN B (17C112)
SASWATH S (17C128)
BALASUBRAMANI N (17C205)
GURU M (17C208)
SHRI RAGAV V S (17C222)
APRIL - 2021
DEPARTMENT OF CIVIL ENGINEERING
PSG COLLEGE OF TECHNOLOGY
(Autonomous Institution)
COIMBATORE – 641004
PSG COLLEGE OF TECHNOLOGY
(Autonomous Institution)
COIMBATORE – 641 004
KAVIMUGAN B (17C112)
SASWATH S (17C128)
BALASUBRAMANI N (17C205)
GURU M (17C208)
SHRI RAGAV V S (17C222)
...……………………………. ……….…………..……………….
Mr. C G SIVA KUMAR Dr. M. PALANIKUMAR
Faculty guide Head of the Department
…………………….. …………………………..
(Internal Examiner) (External Examiner)
ACKNOWLEDGEMENT
The final outcome of this project required a lot of guidance and assistance from our
faculties and we are extremely privileged to have this all along the completion of our
project and we would not forget to thank them.
Abstract …………………………………………………………. 03
List of Figures ………………………………………………….. 04
List of Tables …………………………………………………… 06
1.0. Introduction ……………………………………………………………. 07
1.1. Objectives ……………………………………………………… 07
1.2. Outcome ……………………………………………………….. 08
2.0. Requirements …………………………………………………………. 09
2.1. Circulation area ……………………………………………….. 09
2.2. Floor Height …………………………………………………… 09
2.3. Pharmacy ……………………………………………………… 10
2.4. Clinics ………………………………………………………….. 10
2.5. Side laboratory ………………………………………………… 13
2.6. Injection room …………………………………………………. 13
2.7. Diagnostic services …………………………………………… 13
2.8. Dark room ……………………………………………………… 13
2.9. Blood bank ……………………………………………………... 14
2.10. Bleeding room …………………………………………………. 14
2.11. Intensive Care Unit ……………………………………………. 14
2.12. Operation Theatre …………………………………………….. 14
2.13. Hospital Kitchen ……………………………………………….. 15
2.14. Central Sterile and Supply Department …………………….. 15
2.15. Hospital Laundry ………………………………………………. 16
2.16. Medical and General stores ………………………………….. 17
2.17. Ventilation ……………………………………………………… 17
3.0. Planning of hospital building ……………………………………… 19
3.1. Area requirement per bed ……………………………………. 19
3.2. Calculation of area ……………………………………………. 20
3.3. Floor calculation ……………………………………………….. 21
4.0. Visit to ESIC Tirunelveli Hospital ………………………………… 22
5.0. Drawings and Nomenclatures …………………………………….. 24
5.1. Floor plans ……………………………………………………… 24
5.2. Structural elements layout ……………………………………. 32
5.3. Nomenclature …………………………………………………... 40
6.0. Analysis using STAAD.Pro ………………………………………… 42
6.1. Introduction to STAAD.Pro …………………………………… 42
6.2. Importing drawing from AutoCAD to STAAD ………………. 42
6.3. Assigning member properties ………………………………... 43
6.4. Assigning supports ……………………………………………. 43
6.5. Rendering of structure ………………………………………… 43
6.6. Load definitions ………………………………………………… 44
6.7. Analysis results ………………………………………………… 47
1
7.0. Design using STAAD.Pro ………………………………………….. 48
7.1. Material property definition …………………………………… 48
7.2. Design results ………………………………………………….. 48
7.3. Interactive design using STAAD …………………………….. 49
7.4. Foundation design …………………………………………….. 52
8.0. Manual design …………………………………………………………. 54
8.1. Design of one way slab ……………………………………….. 54
8.2. Design of two way slab ……………………………………….. 58
8.3. Design of beam ………………………………………………… 65
8.4. Design of columns …………………………………………….. 68
8.5. Design of footing ………………………………………………. 71
8.6. Design of staircase ……………………………………………. 76
9.0. Sewage treatment plant ……………………………………………. 79
9.1. Population Estimation ………………………………………… 79
9.2. Design of Inlet Chamber ……………………………………… 81
9.3. Design of Screen Chamber …………………………………… 82
9.4. Design of Grit Chamber ……………………………………….. 83
9.5. Design of Aeration tank ……………………………………….. 85
9.6. Design of Secondary Clarifier ………………………………… 88
9.7. Return sludge pump house …………………………………… 89
9.8. Design of sludge drying beds …………………………………. 90
9.9. Filtration pump house and sump ……………………………... 91
9.10. Design of rapid sand filters ……………………………………. 92
9.11. Design of activated carbon filters …………………………….. 95
10.0. Water supply …………………………………………………………. 96
10.1. Tank 1 – Exclusively for people ………………………………. 96
10.2. Tank 2 – Fire Safety …………………………………………… 97
10.3. Tank 3 – Gardening ……………………………………………. 97
11.0. Conclusion …………………………………………………………… 98
12.0. References ……………………………………………………………… 99
2
ABSTRACT
The main objective of this project was to plan, analyse and design a hospital
building by using various software techniques. Nowadays, the software approach
plays a vital role in the construction field to attain quick and better accuracy in
planning, analysis and design of a building, that is of any size or shape. This method
also helps speed-up the execution of the project and hence successfully complete it
in an efficient manner. The planning was done using the Indian standard (IS) codes
in order to achieve a systematic and an efficient structure. In this project, the
structure planned was a multi-speciality hospital building having G+3 floors. The
RCC structure has three blocks consisting of 90 beds overall and a total area of
24,954 sq m. The architectural and structural drawings were done using the
AutoCAD software, followed by analysis and design of the structure in STAAD.Pro
software. Furthermore, the manual design of slabs, beams, columns and footings
were done in MS Excel spreadsheet software. Finally, design and provisions were
made for a Sewage Treatment Plant (STP) and a water supply system which are the
prime requirements a hospital building.
3
List of Figures
Figure No. Title Pg. No.
4
7.1. Beam results …………………………………………… 48
5
List of Tables
Table No. Title Pg. No.
6
INTRODUCTION CHAPTER !
CHAPTER 1
1.1 INTRODUCTION
i. Cardiac hospitals
v. Psychiatric hospitals
All the above types of exclusive healthcare are found in multi-speciality hospitals.
They are mostly large in size and have a major patient flow daily.
1.2 OBJECTIVE
1.3 OUTCOME
8
REQUIREMENTS CHAPTER 2
CHAPTER 2
The basic requirements and planning of a hospital building was taken from IS
12433-2(2001). This code gave the provisions for a hospital building having up to
100 beds.
Circulation area are the spaces in a hospital building that is used by patients
and people for movement in and around the building. They give access to other parts
of the built environment and also passages leading outdoors. These spaces give a
means of orientation within the building. Visitors, patients and staffs can also find
their way by looking at the well-directed routes overhead that are illuminated using
lights. Circulation spaces include entrances, waiting areas, corridors, stairs, lifts,
landings, foyers etc. According to hospital codes, corridors having breadth less than
8 feet are undesirable. A protective corner beading must be provided in hospital
corridors for impact collisions and to reduce wear and tear on the wall.
Open spaces include atriums, courtyards and in some cases verandahs that
may have several functions. The more the open space area there is in a hospital
building, there can be more accommodation for patients during emergency situations
and severe crises such as breakout of diseases.
The height of floors of every building varies with the client and standard codes
of different countries. According to IS codes, the floor height is generally measured
at any point from the floor surface to the lowest point of the slab or ceiling. It must
not be less than a height of 3 m. This includes the minimum head-room from the
bottom of beams. With the exception of doors, the minimum aggregate areas of
9
REQUIREMENTS CHAPTER 2
openings are kept at a minimum of 20% of the floor area. For rooms with appliances
such as fans and lights, the floor height is measured to be 2.5 m from the floor to the
appliance. HVAC system requirements are also taken into account while fixing the
height of the room.
10 Location: The dispensary must be located in an area that can be easily
accessed by all the clinics in the hospital.
11 Size: The size of the dispensary must be good enough to contain 5% of the
total clinical visits to the OPD in one session at a rate of 0.8 m² per patient.
Generally, for every 200 OPD patients daily, one dispensing counter is
provided. The dispensary and the compounding room have many dispensing
windows, compounding counters and shelves. The patterns of arranging these
shelves and counters depend on the size of the room.
Independent dispensaries are provided for the access of both in-patients and out-
patients in a hospital.
2.4 CLINICS
Clinics are healthcare facilities in a hospital that mainly focuses on the care of
out-patients that are run by multiple practitioners. A Clinic’s aims are to deliver
primary service in health education and also providing health care services.
10
REQUIREMENTS CHAPTER 2
1. Reception
2. Waiting Lobby
4. ECG rooms
5. Toilets
For the purpose of out-patients, the clinic is conveniently placed near the
OPD. Patients in antenatal care have to undergo a small procedure before being
checked by the doctors. For this reason, a clinical laboratory is provided with a toilet-
cum-changing room attached to it.
11
REQUIREMENTS CHAPTER 2
For children aged 12 years and below, a pediatric clinic provides them with
healthcare and medical treatment. The doctor that specializes in pediatrics is known
as a Pediatrician. Due to high risk of infection, this clinic is often placed at a safe
distance from the rest of the clinics in the hospital. A separate treatment room is
provided for immunization in a Pediatric clinic. A children’s play area is also provided
in the clinic.
Minimum area for a cubicle with at least one wash basin for two beds - 19 to 24
sq m.
Orthopedic clinics mainly focus on the care of the skeletal structure and
system. The doctor who practices this type of medicine is known as an Orthopedist.
The skeletal system is majorly made up of muscles, bones and it also consists of
joints, ligaments and tendons. In this clinic, there are separate rooms for preparation
of plaster for mending fractures. The consultation cum-examination room is where
the doctor checks the patient and gives diagnosis. The X-ray equipments in the clinic
should be in close distance with the radiology department, emergency and accident.
This helps in making maximum use of equipment and decrease the amount of
energy used in travel.
Storage rooms are provided for storing materials like plasters, bandages,
splints and other aids of therapeutic nature. Treatment rooms for mending fractures
and sprains must have good space to accommodate a dressing stand and a mobile
X-ray unit. Finally, a recovery room next to the treatment room is vital so that
patients can rest for a while before being transferred to a ward or leave the hospital.
12
REQUIREMENTS CHAPTER 2
A side laboratory is generally used for fast detection of problems in blood and
urine of patients. The minimum area needed for a side laboratory is 36 sq m. The
test samples of the patients are taken in this room and many laboratory tests are
done on it. The data and test results of the patients are managed by a software.
These laboratories are to be located near the doctor’s room.
The dark room consists of equipment that is used for developing and
processing X-ray results. This comes under the radiography department. Accurate
processing of the X-ray films is vital in radiography to obtain effective results. The
usage of smart and quick methods makes this process less expensive. A skilled staff
is required in the dark room so that using their extensive knowledge, they can notice
pivotal details and eliminate the errors. The dark room should not have light entering
inside it and this is done by installing an airlock. Ventilation is, however required
inside the room which includes provision of exhaust fans. The minimum area
required for the dark room is 2.6m x 2m.
13
REQUIREMENTS CHAPTER 2
The blood bank is a room in a hospital that collects and stores blood of
various donors and patients. They are arranged in terms of blood groups and are
catalogued. The blood bank also issues blood to patients needing the specific blood
group at a specific quantity. They are known as blood transfusions. The storage of
blood is done in refrigerators, which consists of several rows of shelves. The room
has a minimum area of 100 sq m and an extra area of 50 sq m is provided for the
preparation of blood products such as in centrifuges. The blood bank is attached with
a bleeding room that consists of blood groupings, a blood storage room and a
recovery room containing stretchers. A reception area is provided outside the blood
bank.
This room is where the donors donate their blood. They consist of cubicles for
donor privacy. The bleeding room is attached to the blood bank for storing blood
groupings of donors and patients. This room is attached to a resting room exclusively
for donors and also a reception area. Since, the risk of infection is high, free flow of
people in this room is restricted. The appropriate size for the bleeding room is 3.6m x
3.6m. A washroom is provided near the resting room for the use of donors.
An operation theater is a room where all kinds of surgeries and operations are
performed by highly skilled medical professionals. The medical procedures are
usually carried out in a clean or a sterile environment where all the people in the
room wear masks and protective suits to prevent spread of germs. This room usually
does not have a window and it uses air conditioners to maintain a controlled
atmosphere.
14
REQUIREMENTS CHAPTER 2
Various planning and factors are taken into consideration before placing an
operating room in a hospital building. They are generally placed in quiet
surroundings in the hospital and also most importantly the area must be free from
any contaminants. In addition to these considerations, the OT area must have
utmost shielding from sun light. They must be nearby and easy to access from other
units such as ICU, radiology, pathology, blood bank, CSSD and wards.
18 Zone A – This zone is known as the protection zone where the medical
staffs who look after the patient cannot come inside this area.
19 Zone B –This zone is known as the clean zone that consists of rooms for
doctors for changing into medical gear, medical gear and equipment storage and an
induction room for administering anaesthesia to the patient.
20 Zone C – This zone is known as the sterile zone, which covers an area that
includes the operation theatre and the scrub-up room where the doctor cleans up.
21 Zone D – This zone is known as the disposable zone that is a separate area
having direct access to the operating room where all the unclean materials and used
medical equipments are disposed.
An operation theatre has a minimum size of 6.5m x 6.5m, with the corridor
width of minimum 2.85m. The wall corners should be curved to stop dust from
staying on the corner surface. Importantly, the movement of patients and medical
equipment is in one direction. When there are multiple operation theatres present,
the pre-operative, post-operative and a scrub-up room is provided for common use.
The minimum dimensions of the additional rooms largely depend on the number of
operation theatres that makes use of these rooms. In a hospital the number of beds
to be provided should be a minimum of 35-50% of the total bed count.
15
REQUIREMENTS CHAPTER 2
them. For this purpose, a different entry is provided for the storage room. The
entrance of the kitchen must have a minimum clearance of 1.2m x 1.2m in order to
avoid collision of doors with other rooms next to it.
The Central Sterile and Supply Department has the function of storing and
supplying sterile equipment to departments like the operation theatre, clinics etc.
They sterlize the instruments thoroughly by various effective sterlization methods
and store them in ultra-violet ray cabinets. The CSSD is kept accessible to all the
other departments in the hospital. Since, the operation theatre facility uses sterile
instruments and equipment very often, the CSSD is placed near the operation
theatre. This unit is restricted to the public and only the medical staff is allowed to
access it. Importantly, this facility must be heavily protected from any external
agents. The control of contaminants in this unit is necessary. This unit should have a
floor space of 10 sq m per bed. The CSSD is divided into 3 zones which are the
soiled zone, clean zone and sterile zone. A barrier is provided between the soiled
and the clean zones.
22 Operation theater use – These equipments are only for the use in the
operation theater and no other departments can use this. Surgical equipments such
as gloves, cutting and dissecting instruments, forceps, clamps etc are primarily
supplied to the operating room.
23 Other departments use – These equipments are only for the purpose of
clinical areas in the hospital and are not supplied to the operation theatre. Syringes
and thermometer are such medical equipments.
24 Both OT and other departments use – These equipments are supplied to
both the operation theater and other departments. Oxygen cylinder is one such
equipment.
The hospital laundry is a service provided by the hospital to give clean and
odourless linen to all the patients. The hospital linen consists of all the cloth used in
the hospital. This includes the pillow covers, blankets, mattress, patient clothes
provided by the hospital, bed sheets, towels, table cloth etc. There are two primary
obligations taken by the laundry service, which are cleanliness and disinfection of
cloth. The washing of linen used for the operation theatre is very important as it
should be thoroughly sterilized before use and there must not be any signs
contaminants. For this purpose, a separate laundry is provided only for the OT.
Laundries are run manually or electrically and they are provided with units for
processes like drying, pressing and storage of dirty and cleaned linens. Most
importantly, the change of air in the laundry area is done about 10 times an hour.
Specific methods are used for removing specific stains on the linen. The storage of
Ready To Use (RTU) cleaning chemicals such as abrasives, acids, alkalies,
16
REQUIREMENTS CHAPTER 2
bleaches, detergent and sanitizers are also considered while considering the floor
area.
Requirements:
Designing the laundry space: Space is mainly provided for heavy machines like the
washing machine and squeezer. In addition, there is provision for supply of water and
power. They are designed in such a way that it should help with the main processes
like sorting, washing, hydro-extraction, drying, ironing, folding and packing. There are
separate spaces provided for sewing the linens. A barrier is provided between
sorting, washing and hydro extraction areas and the clean linen processing area.
Floors and Ceiling: The floor should be rust non-slippery, free from rust, easily
washable and have sufficient slope to provide easy flow of water. The ceiling should
be easily washable, non-slippery, moisture proof, and finally, sound proof. The floor to
ceiling height is not less than 3.5 m.
The hospital stores consist of various stores that helps in the effective
functioning of the hospital. The space for each store is used to the maximum by
providing built-in shelves at various heights based on the type of store. Proper
ventilation and security arrangement is provided in every store. Fire extinguishers
and other fire retarding instruments are provided for the stores. For the medical store
or the pharmacy, the layout and the facilities provided are very important, since the
requirement from this store is humongous. The hospital pharmacy deals with
obtaining, storing, compounding, dispensing, testing and distribution of medicines.
They also provide the hospital with medical equipments needed for surgeries and
operations. While designing a medical store one needs to look at the space
requirements of both the the people working there and the customers. The layout of
the drug store must be pleasing to the eye, by having different colours for each
department and easy navigation.
17
REQUIREMENTS CHAPTER 2
2.17 VENTILATION
Bathrooms/toilets 6-12
Wards 8-12
Kitchens 6-9
18
PLANNING CHAPTER 3
CHAPTER 3
ambulatory 9.31
66.01
19
PLANNING CHAPTER 3
Ophthalmology 5
ENT 5
Pediatric 10
Orthopedic 15
ICU 10
20
PLANNING CHAPTER 3
FLOOR DESIGN
Based on trial and error process, the following plan was developed and the size of
each block was fixed to be 37m x 20m
= 8318 / 2220
= 3.75
= 4
Hence the final design proposed is given in Fig 1.Each block is provided with a size
of 37m x 20m. 3 such blocks are provided in each floor and 4 such floors are
provided.
21
SITE VISIT CHAPTER 4
CHAPTER 4
22
DRAWINGS & NOMENCLATURE CHAPTER 5
CHAPTER 5
23
DRAWINGS & NOMENCLATURE CHAPTER 5
Rooms Dimensions(mm)
24
DRAWINGS & NOMENCLATURE CHAPTER 5
25
DRAWINGS & NOMENCLATURE CHAPTER 5
Rooms Dimensions(mm)
26
DRAWINGS & NOMENCLATURE CHAPTER 5
27
DRAWINGS & NOMENCLATURE CHAPTER 5
Rooms Dimensions(mm)
28
DRAWINGS & NOMENCLATURE CHAPTER 5
29
DRAWINGS & NOMENCLATURE CHAPTER 5
Rooms Dimensions(mm)
30
DRAWINGS & NOMENCLATURE CHAPTER 5
31
DRAWINGS & NOMENCLATURE CHAPTER 5
32
DRAWINGS & NOMENCLATURE CHAPTER 5
33
DRAWINGS & NOMENCLATURE CHAPTER 5
34
DRAWINGS & NOMENCLATURE CHAPTER 5
35
DRAWINGS & NOMENCLATURE CHAPTER 5
36
DRAWINGS & NOMENCLATURE CHAPTER 5
37
DRAWINGS & NOMENCLATURE CHAPTER 5
38
DRAWINGS & NOMENCLATURE CHAPTER 5
5.3. NOMENCLATURE
BEAMS:-
where,
3 – Floor number
1 - Beam number
SLABS:-
where,
3 – Floor number
1 – Slab number
39
DRAWINGS & NOMENCLATURE CHAPTER 5
Note:-
The numbering should be started from the left top corner of the plan.
Once the numbering of beam is completed in horizontal direction, numbering
should be continued in vertical direction from top to bottom
40
ANALYSIS IN STAAD.Pro CHAPTER 6
Chapter 6
41
ANALYSIS IN STAAD.Pro CHAPTER 6
defined. M30 grade concrete and Fe500 steel are defined as concrete properties.
Moreover, the following section properties were assigned
For slabs, plate thickness is defined as 175mm (1)
For beams, R1 is rectangular beam of dimension 230mm x 345mm (2)
R2 is rectangular beam of dimension 300mm x 450mm (4)
For columns, C1 is rectangular column of dimension 400mm x 400mm(3)
C2 is rectangular column of dimension 400mm x 480mm(5)
42
Earthquake X Earthquake Y DL LL
43
ANALYSIS IN STAAD.Pro CHAPTER 6
Combination 1.5
11
44
ANALYSIS IN STAAD.Pro CHAPTER 6
Once the load combinations are defined, the structure can be analysed. In case of
incorrect details, STAAD issues a error message and it has to corrected. Upon
successful completion of analysis, the shear force, bending moment and deflection
of various structural elements can be viewed.
45
DESIGN IN STAAD.Pro CHAPTER 7
Chapter 7
STAAD also provides design for various structural elements. Though the
design of beam and column can be obtained from STAAD according to Indian
Standards, it doesn’t provide design for slab.
The code for design has to be specified followed by material properties has to
be assigned before carrying out design process. For this structure, IS 456 is defined
as the code and the following were the inputs for material properties
After assigning the above properties, the structure can be analysed again. In case a
member fails in design stage, STAAD will issue a warning message stating the
reason for failure of member. Accordingly, the sectional property of that particular
member can be changed. This process is to be repeated until all the members are
designed and the analysis is completed without warning messages.
Once completed, the design results for beam and column can be viewed by
double clicking on that particular member. In addition to that, information regarding
the steel area required and provided can be viewed.
46
Figure 7.1 Beam results
DESIGN IN STAAD.Pro CHAPTER 7
7.3.1. Inputs
The first step in the interactive design tab involves creation of members by
grouping elements. Any number of colinear elements can be grouped together to
form members. This is followed by grouping of members to form design groups.
They can be broadly classified as beams and columns. In addition to this, the design
code and the material property has to be specified once again in this tab. Once the
above mentioned steps are completed, the structure can be designed again.
47
DESIGN IN STAAD.Pro CHAPTER 7
7.3.2. Results
In the post design tab, the hogging, sagging and also the displacement of the
member can be viewed. In addition to that, the Ast required and provided can also
be viewed. Moreover, by double clicking on any particular member, the detailing of
that member can be seen and the same can be imported to AutoCad. For columns,
the shear force with the main reinforcement detail and shear reinforcement detail can
be viewed. There is a possibility of a member being undesigned and under such
circumstances, the sectional properties of that member has to be changed in the
analytical modelling tab and it will automatically be reflected in interactive design tab.
48
Figure 7.5 Column calculations
DESIGN IN STAAD.Pro CHAPTER 7
Once the design of super structure is completed, the design of sub structure
can be initiated. STAAD provides design of footing in a different software named
STAAD foundation. It offers a variety of footing designs. It includes designing footing
as isolated, combined and mat footings.
For the purpose of footing design, the following inputs were given
49
DESIGN IN STAAD.Pro CHAPTER 7
7.4.2. Result
With the above inputs, it was found that some footings overlapped with one
another. And hence such footings were identified and designed as combined
footings. The results obtained in the STAAD format was exported to AutoCad
drawing.
50
MANUAL DESIGN CHAPTER 8
Chapter 8
lx = 2000 mm
ly = 5115 mm
Iy/Ix = 2.558
fck = 30 N/mm²
fy = 500 N/mm²
Therefore ,
fs = 290 N/mm²
d = 100 mm
Take, d = 155 mm
Diameter of bar = 10 mm
Effective cover = 15 mm
D = 175mm
51
MANUAL DESIGN CHAPTER 8
Effective length
Loads
LL = 3.5 KN/m²
FF = 1 KN/m²
Bending moment
Maximum BM = w*(lex)² / B
= 8.68 kNm
Md = 0.36fck*Xumax*b(d-0.42Xumax)
Solving for d;
drequired = 46.537 mm
52
MANUAL DESIGN CHAPTER 8
dprovided = 155 mm
Safe
Calculation of reinforcement
= 159 mm²
3d = 465mm
300mm = 300mm
= 8 bars
Astmin = 0.12%bD
= 210 mm²
Safe
Distributors
5d = 775 mm
450 mm
= 23 bars
53
MANUAL DESIGN CHAPTER 8
In x direction
Pt% = 0.045%
Safe
= 290 N/mm²
Dprov = 175 mm
Safe
54
MANUAL DESIGN CHAPTER 8
From Cl 26.2.1,
Ld = ɸ(0.87fy) / 4 * ζbd
Ld = 453.125 mm
(M/V)+Lo = 538.80+ Lo mm
Safe
lx = 5115 mm
ly = 5230 mm
ly/lx = 1.022
fck = 30 N/mm²
fy = 500 N/mm²
55
MANUAL DESIGN CHAPTER 8
D = 170.5 mm
Take, D = 175 mm
Effective cover = 15 mm
Diameter of bar = 10 mm
dx = 155 mm
dy = 150 mm
Effective length
Loads
LL = 3.5 kN/m²
FF = 1 kN/m²
56
MANUAL DESIGN CHAPTER 8
Bending moments
Iy/Ix = 1.022
Conditions 4 interpolating,
αx (negative) = 0.0482
αx (positive) = 0.036
αy (negative) = 0.047
αy (positive) = 0.035
Solving for d;
drequired = 70.656 mm
dprovided = 155 mm
Safe
Calculation of reinforcement
57
MANUAL DESIGN CHAPTER 8
3d = 465 mm
300 mm
3d = 450 mm
300 mm
= 1054 mm
= 1076 mm
58
MANUAL DESIGN CHAPTER 8
Astmin = 0.12%bD
= 210 mm²
Safe
In x direction
pt% = 0.09%
Safe
In y direction,
59
MANUAL DESIGN CHAPTER 8
pt% = 0.09%
Safe
Therefore,
fs = 290 N/mm²
In x direction,
Pt% = 0.18%
Dprov = 175 mm
Since, Dprov>Dreq
Safe
In y direction
Pt% = 0.18%
Dprov = 175 mm
60
MANUAL DESIGN CHAPTER 8
Safe
In x direction
From CI 26.2.1
Ld = ɸ(0.87fy)/4*ζbd
Ld = 453.125 mm
(M/V)+Lo = 527.54+Lo mm
Safe
In y direction
Ld = ɸ(0.87fy)/4*ζbd
Ld = 453.125 mm
(M/V)+Lo = 499.13+Lo mm
Safe
61
MANUAL DESIGN CHAPTER 8
fck = 30 N/mm2
fy = 500 N/mm2
Assume, D = 400 mm
b = 350 mm
Bending moment
62
MANUAL DESIGN CHAPTER 8
For support
Pt = 50 * (fck/fy) * (1-(1-4.6Mu/fck*b*d^2)^0.5)
= 0.32%
Xumax / d = 0.46
Mulim/fck*b*d2 = 0.133
63
MANUAL DESIGN CHAPTER 8
%Ptreq = 0.327 %
%Ptprov= 0.264 %
%Pc = 0.264 %
d = 255.75 mm
64
MANUAL DESIGN CHAPTER 8
fck = 30 N/mm²
Breadth, b = 400 mm
fy = 500 N/mm²
Depth, D = 400 mm
Load, Pu = 389.549 KN
Minimum Eccentricity
ex = Mux / Pu = 50.1 mm
ey = Muy / Pu = 49.5 mm
65
MANUAL DESIGN CHAPTER 8
To find P/fck
P = 100*Asc/bD = 0.85
P/fck = 0.028
Pu/fckbD = 0.08
d'/D = 0.1
Mux1/fckbD² = 0.07
d'/b = 0.1
Muy1/fckbD² = 0.07
To find Pu / Puz
Pt% = 0.8%
fck = 30 N/mm²
fy = 500 N/mm²
66
MANUAL DESIGN CHAPTER 8
Puz/Ag = 17
To find Muy/Muy1
Mux/Mux1 = 0.15
Pu/Puz = 0.14
Muy/Muy1 = 0.85
Muy/Muy1(calc) = 0.14
Safe
Transverse reinforcement
Pitch = 300 mm
16d = 192 mm
Hence, provide 12# of 12-T bars with 8mm ties@ 192 c/c
67
MANUAL DESIGN CHAPTER 8
Design Procedure:
Given data:
Mx = 96.23kN
My = 17.36 kN
Column height = 3m
Along x axis,
Along y axis,
68
MANUAL DESIGN CHAPTER 8
Providing effective depth greater of 2 values considering moment but for safety
against shear failure, the selected depth should be taken 2 to 3 times higher,
69
MANUAL DESIGN CHAPTER 8
Calculation of reinforcement:
70
MANUAL DESIGN CHAPTER 8
Hence Design Shear stress of concrete > maximum shear stress, it is safe against
one way shear. Also for shorter direction, it will safe as the depth is sufficient.
Design Shear stress of concrete > maximum shear stress = 0.3852 N/mm 2
Hence, design Shear stress of concrete > maximum shear stress, it is safe against
one way shear.
71
MANUAL DESIGN CHAPTER 8
The critical distance is at distance d/2 from the face of the column
Τc = 1.369 N/mm2
Ld = 543.75 mm
Hence, the column bars are extended into footing up to Ld rests on the footing
reinforcement.
72
MANUAL DESIGN CHAPTER 8
Given data:
Risers = 0.15m
Treads = 0.3m
Concrete = M30
σcbc = 10
m = 9.33
fy = 500 N/mm2
General Arrangement:
Width of landing = 2m
73
MANUAL DESIGN CHAPTER 8
Design Constraints:
Concrete M30
σcbc = 10
m = 9.33
fy = 500 N/mm2
K = 0.253
J = 0.916
R = 1.16
The landing slab is assumed to span in the same direction as stair and is considered
as acting together to form a single slab.
74
MANUAL DESIGN CHAPTER 8
Reinforcement:
Number of bars = 20
75
SEWAGE TREATMENT PLANT CHAPTER 9
Chapter 9
Staffs = 260
= 73350 lpcd
= 0.07335 MLD
= 85% of 0.07335
= 0.06235 MLD
= ~0.070 MLD
= (70*1000) /1000
= 70 Cum/day
= 3*70
76
SEWAGE TREATMENT PLANT CHAPTER 9
Sewage Characteristic
77
SEWAGE TREATMENT PLANT CHAPTER 9
Inlet chamber
Screen chamber
Grit chamber
Aeration tank for ASP
Secondary clarified
Sludge drying beds.
= {(210) /(24*60*60)}
Assuming:
Length = 2m
B/D = 1.5:1
= 0.0054 sq.m
A = BxD
= 1.5D x D
B = 1.5xD
= 0.45m
78
SEWAGE TREATMENT PLANT CHAPTER 9
= 1.05 m
= 0.129
CHECK:
D/3 = 0.1
A = DxB
= 0.1x0.45
= 0.045 sqm
P = 2D+B
= 0.65 m
R = A/P
= 0.0692
The out flow from the inlet chamber shall be taken to the screen chamber.
ASSUMPTIONS:
79
SEWAGE TREATMENT PLANT CHAPTER 9
= 0.62
Let, 2 numbers of CI penstock gates shall be provided ( one for each channel)
= 0.313
= 87.5
=~ 100 cum/day
To account for turbulence and short circuiting reduce the surface loading rate to 800
m3/sqm/day
80
SEWAGE TREATMENT PLANT CHAPTER 9
= 125 sq.m
Velocity = (100/1x0.555x24x350)
= 0.0017cum
=~ 0.002cum
= 0.785 sq.m
= 0.00255 m
= 0.580
=~ 0.6 m
Outflow from the grit chamber shall be carried to the aeration tank through a 600mm
wide R.C.C. Channel provided with fine bar screen (manually operated). The clear
spacing b/w bars shall be 10 mm.
81
SEWAGE TREATMENT PLANT CHAPTER 9
Number of tanks = 2
ASSUMPTIONS:
F/M = ((Q*Yo)/(V*Xt))
= 33.25/(2 x 5)
= 3.325 m
=~ 4m
t = (V/Q) x 24 (hrs)
= (33.25x24)/35
82
SEWAGE TREATMENT PLANT CHAPTER 9
= (35x350) /40
= 306.25 gm/cum
9.5.3 Check For Return Sludge Ratio (for SVI ranging between 50 - 150 ml/gm)
Xt = 3000 mg/l
Qr/Q = Xt/((106/SVI)-Xt)
= 3000/((10^6/100) -3000)
αy = 1
Ke = 0.06 d-1
Yo = 350 mg/l
Ye = 20 mg/l
V = 40 cum
Xt = 3000 mg/l
Q = 35 cum/day
θc = 25 days
83
SEWAGE TREATMENT PLANT CHAPTER 9
The effluent from the aeration tank will be taken to the final (secondary
clarified. The inflow to the secondary clarified shall be by means of 250 mm dia
C. l pipes, which will give a velocity of 0.78 m/s at peak flow.
= 12.25 kg/day
= 0.510 kg/h
= 0.765 kg/hr
= 0.780hp
=~ 1 hp
84
SEWAGE TREATMENT PLANT CHAPTER 9
= 0.7 kw
= 0.36 HP
= 105 m3/day
= 8.75 m3
= 4.375 m2
= 3.19
=~ 3.5 m.
85
SEWAGE TREATMENT PLANT CHAPTER 9
= 9.62 m2
= 315 kg/day
= 39.4 kg/day/sqm
Sludge will be withdrawn from the clarifier through a C.I pipe. The sludge will be
taken to the return sludge pump house. The treated effluent from the secondary
clarifier can be disposed off in a safe location.
86
SEWAGE TREATMENT PLANT CHAPTER 9
= (35/24x60)
= 0.024 cum/min
= 0.35 cum
Provide 2 numbers of pump of each 0.35 MLD capacity in dry well for returning the
sludge to aeration tank.
Excess sludge shall be taken to sludge drying beds by providing necessary fittings in
the main return sludge header. The sludge feed line to the sludge drying beds shall
be 150mm diameter C.I pipe.
= 1.64 cum/day.
= 11 days
87
SEWAGE TREATMENT PLANT CHAPTER 9
= 18.06 cum
= 60.21 m2
= 23.1kg
= 4.8 kg/day
= 0.47 cum/day
= 0.02 cum/hr
(For 1% concentration)
=0.16 m2
= 0.45 m
88
SEWAGE TREATMENT PLANT CHAPTER 9
Providing 1m diameter wet well for filtrate sump & 1 m liquid depth Below the
incoming pipe line.
This will be covered on top and a 4m high pump room shall be constructed over it. 2
nos of vertical non-clog pumps, each of 0.5 hp capacity , shall be provided in this
pump house. The filtrate from the pump house shall be pumped to distribution
chamber upstream of the aeration tank through 100 mm dia C.I pipe line.
Free board = 60 cm
Q = 1.71xbxh3/2
89
SEWAGE TREATMENT PLANT CHAPTER 9
Allow 0.5%of filtered water for back washing and 30 mins per day for back washing
(10 cum/day)
= 800 sqcm
=~ 13 on either side
90
SEWAGE TREATMENT PLANT CHAPTER 9
Check :
Assume b = 0.2m
Q = 1.71xbxh3/2
h3/2 = 0.2775m
H = 27.75cm =~ 30cm
Free board = 5 cm
Assume depth d = 3m
L/B = 2
91
SEWAGE TREATMENT PLANT CHAPTER 9
Bed Depth = 1 to 3 m
Diameter Calculations:
Expansion = 0.7m
Total height = 3m
Criteria :
Qabe = 12 cum/hr
92
WATER SUPPLY CHAPTER 10
Chapter 10
Assuming,
= 2.953 meter
=~ 3m
Size of tank = 9m x 8m x 3m
93
WATER SUPPLY CHAPTER 10
Length = 5m ,Breath = 5m ,
= 2 meter
Size of tank = 5m x 5m x 2m
= 2 meter
94
CONCLUSION CHAPTER 11
Chapter 11
11.0. CONCLUSION:
The structural aspects of planning, analysis and design of hospital building and
sewage treatment plant has been done and get an ideas for execution of structure by
real example of existing ESIC hospital and regulation under IS codes. By using
software the project of Hospital building (G+3) were analyzed. Here the project was
analyzed by both manual and software for an clear idea of structural basis. Also
some disciplinary planning has been followed for the hospital building for user
friendly reachability of departments based on the requirements of public users,
patients, doctors, and workers etc. The waste water generated from the hospital is
treated and disposed as per the requirements.
95