Professional Documents
Culture Documents
Sil MTL4544 - 1
Sil MTL4544 - 1
IEC 61508
Data Declaration
DOCUMENT NO. MTL08FMEA4544 Issue 1
This document is issued as a summary of the hardware failure data affecting the application of the
equipment as a sub-system being part of a Safety Function intended to conform with the
requirements of IEC61508 - Functional Safety of Electrical/Electronic/Programmable Electronic
Safety Systems. The hardware has been subjected to a Failure Modes and Effects Analysis (FMEA)
to determine the specific failure modes and failure rates with the relevant results presented herein.
Product Description
The MTL4544 and MTL5544 provide fully-floating dc supplies for energising two conventional 2-
or 3-wire 4/20mA transmitters located in a hazardous area and repeat the current in other floating
circuits to drive two safe area loads. For smart 2-wire transmitters the units allow bi-directional
communications signals superimposed on the 4/20mA signal current.
It is assumed that the module is powered from a nominal 24Vdc supply and operating with safe side
load resistances of 250 ohms on each channel.
The definitions for product failure of the MTL4544 and MTL5544 were determined as:-
The failure rates apply to either channel 1 or channel 2 used in a safety function. Both channels
should not be used in the same safety function. Failures may effect both channels simultaneously.
FMEA/DD4544/08/08 Page 1 of 2
FMEA
IEC 61508
Example of use in a safety function
In this example, the application context is assumed to be:
In this example, the safe failure fraction is 93.4 % and so the devices meet the hardware architecture
constraints to be used as single devices in Safety Instrumented Functions up to SIL3.
Notes
• FITs means failures per 109 hours or failures per thousand million hours.
• Reliability data for this analysis is taken from IEC TR 62380:2004 Reliability Data
Handbook.
• Failure mode distributions are taken principally from IEC 62061:2005 Safety of Machinery.
• Proof testing must be carried out according to the application requirements, but it is
recommended that this be carried out at least once every three years.
• Consideration should be made of the normal lifetime for a device of this type which would
be in the region of ten years.
• There are no internal diagnostic elements of this product.
• The transmission of HART data is not considered as part of the safety function and is
excluded from this analysis.
• For all other product parameters related to its application (voltage range, environment, etc.)
please refer to the published MTL data sheet for this product, at www.mtl-inst.com.
FMEA/DD4544/08/08 Page 2 of 2