Professional Documents
Culture Documents
G E N E R A T O R S E T
GELH14 (3-Phase)
50 HZ
STANDBY 14.0 kVA
11.2 kW
FEATURES
GENERATOR SET COOLING SYSTEM
● Complete system designed and built at ISO9001 ● Standard ambient temperatures up to 50° C (122° F)
certified facility ● Fan, fan drive and charging alternator fully guarded
● Factory tested to design specifications at full load ● Antifreeze protection coolant
conditions
● Fully engineered with a range of options CIRCUIT BREAKER
and accessories ● 3-pole miniature circuit breaker (mcb) < 160 amps
and 3-pole molded case circuit breaker (mccb)
ENGINE >= 160 amps
● Industrial water cooled diesel engine ● Vibration isolated sheet steel enclosure with
● Governor, mechanical removable cover plate
● Electrical system, 12 VDC ● Outgoing cable stub-up area directly below circuit
● Cartridge type fuel and oil filters breaker
● Air filter AUTOMATIC VOLTAGE REGULATOR
● Battery(s), rack and cables ● Voltage regulation ±0.5 %
GENERATOR ● Provides fast recovery from transient load changes
● Self excited brushless generator EQUIPMENT FINISH
● Insulation system, class H ● All electroplated hardware
● Drip proof generator air intake (IP23) ● Anticorrosive paint protection
● Electrical design in accordance with BS5000 Part 99, ● High gloss polyurethane paint for durability and
IEC34-1, VDE0530, UTE51100
scuff resistance
CONTROL SYSTEM QUALITY STANDARDS
● LCP2 keystart control panel ● BS4999, BS5000, BS5514, IEC34, VDE0530
● Vibration isolated sheet steel enclosure with hinged
lockable door DOCUMENTATION
● Operation and maintenance manuals provided
MOUNTING ARRANGEMENT
● Wiring diagrams included
● Heavy-duty fabricated steel base with lifting points
● Anti-vibration pads to ensure vibration isolation WARRANTY
● Engine coupled to generator with flexible ● 12 months from date of initial start-up or 18 months
disc coupling from shipping, whichever occurs first
● Baseframe incorporates integral plastic fuel tank, 8
hours running capacity
EXHAUST SYSTEM
● Heavy duty industrial capacity exhaust silencer
(approximately 10 dB reduction) supplied loose
W H E R E T H E W O R L D T U R N S F O R P O W E R
5 0 H z S T A N D B Y 1 4 . 0 k V A
1 1 . 2 k W
ENGINE
Manufacturer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lister
Model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LPW2
Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Cycle
Aspiration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Naturally aspirated
Cylinder configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . In-line 2
Displacement — L (cu in) . . . . . . . . . . . . . . . . . . . . . . . . 0.93 (56.8)
Bore/stroke — mm (in) . . . . . . . . . . . . . . . . . . . . . . . 86/80 (3.4/3.2)
Compression ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18.5:1
Engine speed — rpm
50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3000
L W
50 Hz
Generator Technical Data 415/240V 400/230V 380/220V
Motor Starting Capability:
Self Excited (kVA) 21 20 18
Full Load Efficiency
Standby % TBA TBA TBA
Prime % 79.3 79.2 78.2
Reactances (per unit) Xd 3.38 3.63 4.0
Saturated X'd 0.13 0.14 0.16
Reactances X"d 0.065 0.071 0.078
are shown Xq 1.69 1.82 2.0
applicable to the X"q 0.1 0.11 0.12
standby rating X2 0.08 0.09 0.1
X0 0.01 0.01 0.01
t'd t" t'do ta
Time Constants:
37 sec. 4 sec. 976 sec. 6 sec.
RATING DEFINITION
STANDBY
These ratings are applicable for supplying
continuous electrical power (at variable load) in
the event of a utility power failure. No overload
is permitted on these ratings.
www.CAT-ElectricPower.com