FEATURES
GENERATOR SET COOLING SYSTEM
● Complete system designed and built at ISO9001 ● Standard ambient temperatures up to 50° C (122° F)
certified facility ● Fan, fan drive and charging alternator fully guarded
● Factory tested to design specifications at full load ● Antifreeze protection coolant
conditions
● Fully engineered with a range of options CIRCUIT BREAKER
and accessories ● 3-pole miniature circuit breaker (mcb) < 160 amps
and 3-pole molded case circuit breaker (mccb)
ENGINE >= 160 amps
● Industrial water cooled diesel engine ● Vibration isolated sheet steel enclosure with
● Governor, mechanical removable cover plate
● Electrical system, 12 VDC ● Outgoing cable stub-up area directly below circuit
● Cartridge type fuel and oil filters breaker
● Air filter AUTOMATIC VOLTAGE REGULATOR
● Battery(s), rack and cables ● Voltage regulation ±0.5 %
GENERATOR ● Provides fast recovery from transient load changes
● Self excited brushless generator EQUIPMENT FINISH
● Insulation system, class H ● All electroplated hardware
● Drip proof generator air intake (IP23) ● Anticorrosive paint protection
● Electrical design in accordance with BS5000 Part 99, ● High gloss polyurethane paint for durability and
IEC34-1, VDE0530, UTE51100
scuff resistance
CONTROL SYSTEM QUALITY STANDARDS
● LCP2 keystart control panel ● BS4999, BS5000, BS5514, IEC34, VDE0530
● Vibration isolated sheet steel enclosure with hinged
lockable door DOCUMENTATION
● Operation and maintenance manuals provided
MOUNTING ARRANGEMENT
● Wiring diagrams included
● Heavy-duty fabricated steel base with lifting points
● Anti-vibration pads to ensure vibration isolation WARRANTY
● Engine coupled to generator with flexible ● 12 months from date of initial start-up or 18 months
disc coupling from shipping, whichever occurs first
● Baseframe incorporates integral plastic fuel tank, 8
hours running capacity
EXHAUST SYSTEM
● Heavy duty industrial capacity exhaust silencer
(approximately 10 dB reduction) supplied loose

W H E R E T H E W O R L D T U R N S F O R P O W E R
5 0 H z S T A N D B Y 1 4 . 0 k V A
1 1 . 2 k W

Exclusively from your Caterpillar® dealer


OPTIONAL EQUIPMENT*
Cooling System Coolant heater
40% Anti-Freeze (Protection to -25°C)
Fuel System Low fuel level alarm
Silencer System — Open Unit Engine mounted level 2 silencer
Overhead mounting kit
Enclosures Sound attenuated canopy
Lockable vandal proof control panel cover in place of window
Handling/Trailers Fixed height drawbar 2 wheel trailer
Adjustable height drawbar 2 wheel trailer
Controls LCP0 Series panel
LCP1 Series panel
Lube oil pressure gauge
Coolant temperature gauge
Battery charger with auxilary controls
Circuit Breaker Upgrades from 3-pole to 4-pole breaker
32A CEE Form socket for generator output up to 32A
63A CEE Form socket for generator output 32A - 63A
Earth Leakage protection for main output 300 mA, CB trip
Certification European CE certification
*Some options may not be available on all models.
Not all options are listed.
5 0 H z S T A N D B Y 1 4 . 0 k V A
1 1 . 2 k W

Exclusively from your Caterpillar® dealer


SPECIFICATIONS
Piston speed — m/sec (ft/sec)
50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8.0 (26.3)
GENERATOR Maximum power at rated rpm — kW (hp)
Make. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Olympian Standby
Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LA1012D 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.8 (19.9)
Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Self-excited, brushless Standby
Voltage regulation . . . . . . . . . . . . . . . ±0.5% at steady state from 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 641 (93.0)
from no load to full load Regenerative power — kW (hp)
Frequency . . . . . . . . . . . . . . . . . . . ±0.04% for constant load from 50 Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TBA
no load to full load Motor starting capability — kW (hp)
50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14.4 (19.3)
Waveform distortion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . THD <4%
Governor
Radio interference . . . . . . . . . . . . . . Compliance with BS800 and Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mechanical
VDE Class G&N Class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ISO 8528 G2
Telephone Interference . . . . . . . . . . . . . . . . . . . . TIF <50, THF <2%
Overspeed limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4500 rpm
Insulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class H
Temperature rise . . . . . . . . . . . . . . . . . . . . . . Within Class H limits
Deration . . . . . . . . . . . . . . . Consult factory for available outputs

ENGINE
Manufacturer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lister
Model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LPW2
Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Cycle
Aspiration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Naturally aspirated
Cylinder configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . In-line 2
Displacement — L (cu in) . . . . . . . . . . . . . . . . . . . . . . . . 0.93 (56.8)
Bore/stroke — mm (in) . . . . . . . . . . . . . . . . . . . . . . . 86/80 (3.4/3.2)
Compression ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18.5:1
Engine speed — rpm
50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3000

GENERATOR SET DIMENSIONS AND WEIGHTS

L W

Length Width Height Weight* Note: General configuration not to be


Model mm (in) mm (in) mm (in) kg (lb) used for installation. See general
dimension drawings for detail.
GELH14 1067 (42.0) 576 (22.7) 1198 (47.2) 331 (730)
*Includes oil and coolant

Consult your Olympian representative for more information


5 0 H z S T A N D B Y 1 4 . 0 k V A
1 1 . 2 k W

Exclusively from your Caterpillar® dealer


GELH14 (3-Phase)
50 Hz
Generator Set Technical Data Standby
Package Performance
Power rating kVA (kW) 14 (11.2)
Lubricating System
Type: Oil
Oil filter: Spin-on, full flow
Oil cooler: Coolant
Oil type required: API CD 15W-40
Total lube system capacity L (U.S. Gal) 3.2 (0.85)
Oil pan capacity L (U.S. Gal) 3.0 (0.79)
Fuel System
Fuel Tank Capacity L (U.S. Gal) 44 (11.6)
Generator set fuel consumption**
100% load L/hr (U.S. g/hr) 3.3 (0.87)
75% load L/hr (U.S. g/hr) 2.7 (0.71)
50% load L/hr (U.S. g/hr) 2.1 (0.55)
Engine Electrical System
Voltage/ground: 12 vDC/negative
Battery charging alternator ampere rating amps 35
Cooling System
Water pump type: Centrifugal
Cooling system capacity L (U.S. Gal) 6.4 (1.7)
Maximum coolant static head m H2O (ft H2O) 10.0 (33.1)
Coolant flow rate L/hr (U.S. gal/hr) 3600 (57060)
Minimum temperature to engine °C (°F) 84 (183)
Temperature rise across engine °C (°F) 5 (41)
Heat rejected to coolant at rated power kW (Btu/min) 11.5 (654)
Total heat radiated to room at rated power kW (Btu/min) 7.9 (449)
Radiator fan load kW (hp) 0.48 (0.6)
Air Requirements
Combustion air flow m3/min (cfm) 1.32 (46.61)
Maximum air cleaner restriction kPa (in H2O) 2.5 (10)
Radiator cooling air m3/min (cfm) 55.5 (2076)
Generator cooling air m3/min (cfm) 13.2 (466)
Exhaust System
Maximum allowable backpressure kPa (in Hg) 7.5 (2.21)
Exhaust flow at rated power m3/min (cfm) 3.6 (128)
Exhaust temperature at rated power
(dry exhaust) °C (°F) 572 (1062)
Generator Set Noise Rating*
(without attenuation) at 1 m (3.28 ft) dBA TBA
**dBA levels are for guidance only
**Fuel consumption data at indicated load with diesel fuel with a specific gravity of 0.85 and conforming to BS2869:1998 Class A2.

50 Hz
Generator Technical Data 415/240V 400/230V 380/220V
Motor Starting Capability:
Self Excited (kVA) 21 20 18
Full Load Efficiency
Standby % TBA TBA TBA
Prime % 79.3 79.2 78.2
Reactances (per unit) Xd 3.38 3.63 4.0
Saturated X'd 0.13 0.14 0.16
Reactances X"d 0.065 0.071 0.078
are shown Xq 1.69 1.82 2.0
applicable to the X"q 0.1 0.11 0.12
standby rating X2 0.08 0.09 0.1
X0 0.01 0.01 0.01
t'd t" t'do ta
Time Constants:
37 sec. 4 sec. 976 sec. 6 sec.

Consult your Olympian representative for more information.


5 0 H z S T A N D B Y 1 4 . 0 k V A
1 1 . 2 k W

Exclusively from your Caterpillar® dealer


RATINGS AT AVAILABLE VOLTAGES
50 Hz
Standby
Voltage
Code Voltage kVA kW
V502 415/240 14.0 11.2
V503 400/230 14.0 11.2
V504 380/220 13.9 11.1
Ratings at 27° C (80° F), 152.4 m (500 ft), 60% humidity, 0.8 pf

RATING DEFINITION
STANDBY
These ratings are applicable for supplying
continuous electrical power (at variable load) in
the event of a utility power failure. No overload
is permitted on these ratings.

www.CAT-ElectricPower.com

278-397 © 2001 Caterpillar


All rights reserved.
European sourced Printed in U.S.A.

LEHF1182 Materials and specifications are subject to change without notice.


Replaces OLY/GEL/1299 The International System of Units (SI) is used in this publication.