Ecomax 200 W: Boiler Regulator
Systemu Zarządzania
Boiler regulator
ecoMAX 200 W
FOR SOLID FUEL BOILERS WITH A FAN
2010-04-14
TABLE OF CONTENTS
1 Safety ................................................................. 4
12.4 MINIMUM BOILER TEMPERATURE N3 .....................21
12.5 MAXIMUM BOILER TEMPERATURE N4 .....................21
2 General information .......................................... 5
12.6 FUEL SHORTAGE DETECTION TIME N5 .....................22
3 Information about documentation ................... 5 12.7 SCREEN BRIGHTNESS N6.......................................22
4 Storage of documentation ................................ 5 12.8 FAN REVOLUTIONS’ REDUCTION TEMPERATURE N7 ....22
12.9 CENTRAL HEATING PUMP DOWN-TIME BY THERMOSTAT
5 Applied symbols................................................ 5
N8 22
6 Directive WEEE 2002/96/EC .............................. 5 12.10 FUEL SHORTAGE DETECTION METHODS N9 ...........22
12.11 LOWERING THE PRESET BOILER TEMPERATURE R0 .22
REGULATOR INSTRUCTION MANUAL ............. 7 12.12 HOT UTILITY WATER TANK HYSTERESIS R1 ............22
7 Operating the regulator .................................... 8 12.13 BOILER PRESET TEMPERATURE INCREASE R2 .........23
12.14 MAXIMUM HOT UTILITY WATER TEMPERATURE R3 23
7.1 DESCRIPTION OF BUTTONS AND DISPLAY ................... 8
12.15 EXTENDING HOT UTILITY WATER PUMP OPERATION
7.2 FIRST START-UP OF THE REGULATOR ........................ 8
R4 23
7.3 START-UP OF THE REGULATOR ................................ 8
12.16 FUEL SHORTAGE DETECTION – EMISSION
7.4 FIRING UP – ACTIVATION OF AIRFLOW ...................... 9
TEMPERATURE R5 ........................................................... 23
7.5 PRESETTING BOILER TEMPERATURE .......................... 9
12.17 DISABLING THE CH PUMP R6 ............................23
7.6 PRESETTING HOT UTILITY WATER TEMPERATURE ......... 9
12.18 EMISSION TEMPERATURE DURING FIRING UP R7....23
7.7 COMBUSTION REGULATION METHODS ...................... 9
12.19 FIRING UP TIME R8 .........................................23
7.8 SUPERVISION ................................................ 11
12.20 RESTORING SERVICE SETTINGS R9 ......................23
7.9 SETTINGS FOR HOT UTILITY WATER ........................ 11
12.21 METHODS OF DETECTING FUEL SHORTAGE ...........23
7.10 ENABLING THE SUMMER FUNCTION .................... 11
12.22 POWER SUPPLY DECAY .....................................24
7.11 OPERATION WITHOUT AIRFLOW ............................ 12
7.12 MANUAL CONTROL ............................................ 12 13 Firmware ........................................................... 24
7.13 RESTORING DEFAULT SETTINGS ............................. 12 14 Description of alarms ...................................... 24
10 Storage conditions and transport .................. 15 15 Replacement of parts and subassemblies .... 25
4
2 General information significant for safety issues, hence the user
should read both parts of the manual.
The ecoMAX 200 series boiler regulator is an
electronic device intended for solid fuel
We are not responsible for any damages
boilers. It performs the following functions:
caused by failure to observe these
• Automatic stabilization of a given
instructions.
temperature of the boiler cycle,
• Automatic stabilization of a given 4 Storage of documentation
temperature of the hot utility water tank. This assembly and operation manual, as well
as any other applicable documentation,
Combusting regulation is performed using
should be stored diligently, so that it was
three selectable methods:
available at any time. In the case of moving
- by linear reduction of the airflow power
or selling the device, the attached
when the temperature approaches the preset
documentation
boiler temperature (CLASSIC regulation),
should be forwarded to the new user/owner.
- by smooth modulation of the airflow power
(PID regulation without an emission sensor),
- by smooth regulation of the airflow power 5 Applied symbols
(PID regulation with an emission sensor)1. In this manual the following graphic symbols
are used:
After equipping the regulator with an
additional emission sensor, it is possible to
- useful information and tips,
quickly detect that the fuel is running out in
any mode of the boiler regulation. This
decreases heat losses related to the fan important information, failure to
operating without any fuel, and extends the observe these can cause damage of
boiler‟s readiness for refuelling. The fuel property, threat for human and
needs not be added quickly, as fast detection household animal heath and life.
of the lack of fuel maintains glow in the
Caution: the symbols indicate important
boiler furnace for a longer time.
information, in order to make the manual more
lucid. Yet, this does not exempt the user from the
The fan start is smooth. This decreases the
obligation to comply with requirements which are
risk of gas explosion in the boiler chamber, not marked with a graphic symbol.
which is of particular significance in fine coal
boilers.
6 Directive WEEE 2002/96/EC
The device is operated in an easy and Act on electrical and electronic
intuitive way. equipment
1
option – the emission sensor is not part of
standard equipment
5
REGULATOR INSTRUCTION MANUAL
ecoMAX 200 W
6. Boiler regulation mode – PID function,
7 Operating the regulator
7. Room thermostat - this symbol lights up
This section briefly describes how the when the temperature inside the room
regulator should be operated. reaches the preset value contacts are
disconnected)
7.1 Description of buttons and display 8. alarm symbol
9. signal of increasing the preset boiler
temperature due to hot utility water
heating,
10. signal decreasing the preset boiler
temperature due to operation of the room
thermostat,
11. service menu symbol
12. hot utility water temperature sensor,
13. central heating pump symbol
14. hot utility water pump symbol
15. boiler temperature sensor,
16. emission temperature sensor,
Drawing 1. Keyboard view, 17. airflow power
18. fan symbol it this is not visible –
Legend: regulation is off, it is visible – regulation
1. menu item change button is on, if it flashes – the regulator is in the
2. STOP button, value decrease SUPERVISION mode
3. START button, value increase 19. hot utility water tank symbol
4. mains switch 20. icons:
5. fuse socket
Temperature settings
After turning the regulator on, the START
and STOP buttons are used to enable and
disable airflow respectively. Blow-off time
10 9 8 7 6 5 4 3
12 Blow-off interval
2
13
Maximum revolutions
14 11
15
1 Minimum revolutions
16
17
Settings for hot utility water
18
19 2
Service menu symbol
Drawing 2. Main display window
7.2 First start-up of the regulator
Legend: Before the first start-up of the regulator, it
1. preset boiler or hot utility water tank should be programmed for the purposes of
temperature, or preset temperature of cooperation with the given boiler and heating
emission, system, in accordance with point 11.9. It is
2. measured temperature of boiler, hot recommended that this performed by a
utility water tank, or emission, person familiar with heating technology.
3. signal arrow
4. SUMMER – hot utility water mode symbol 7.3 Start-up of the regulator
5. PRIORITY - hot utility water mode symbol
8
7.7 Combustion regulation methods
Caution: The combustion regulation
The regulator features three selectable
methods described below will
methods of regulating the combustion
properly regulate the combustion
process.
process, as long as the boiler is
operated in accordance with CLASSIC regulation (regulation mode 1)
recommendations of the boiler In order to enable the CLASSIC mode of
manufacturer. You should pay boiler regulations, set the boiler regulation
special attention to the place of
setting fire during firing up! mode to value 1. In order to do so, press
The regulator is started by pushing the mains the F button in the main window until the
switch (4) Drawing 1. First, an information arrow is in the boiler regulation mode
window with the software version appears, position. Use „+” or „-" buttons to set value
then the regulator displays the main window.
Three modes of combustion control
7.4 Firing up – activation of airflow
are available: 1 - CLASSIC, 2 - PID,
In order to fire the boiler up, you should put
3 – PID SALINES point 7.7.
fire under the fuel, in accordance with the
boiler documentation, close the boiler door
The method is based on the T1 boiler
and activate airflow by pushing the START
indication, and consists in decreasing of the
button. The fan will be activated. Pushing
airflow power from Maximum revolutions
STOP turns the fan and the regulation
to Minimum revolutions while achieving
process off.
the preset boiler temperature. Revolutions
7.5 Presetting boiler temperature start to be reduced at 5°C (service
parameter n7) before the preset boiler
The boiler temperature can be preset by temperature. After achieving the preset
pushing the F button in the main menu. A boiler temperature, the SUPERVISION mode
signalling arrow next to the sign is activated, where blow-offs are performed.
„Temperature setting” is lit, and the boiler
Before enabling this mode for the first time,
preset temperature value in the upper part of
it is recommended to program the regulator
the thermometer flashes. START and STOP
in accordance with point 11.9.
buttons are used to increase and decrease
the preset boiler temperature respectively. PID regulation (regulation mode 2)
After setting the parameter boiler regulation
7.6 Presetting hot utility water
mode = 2.
temperature
This method is based on boiler temperature
indications T1, it consists in constant,
If the hot utility water temperature
smooth modulation of the fan revolutions in
sensor is not connected, it is not
order to stabilize the preset boiler
possible to preset the hot utility
temperature. The regulator itself selects the
water temperature.
airflow power in such a way that the boiler
generated minimum amount of heat
The hot utility water temperature can be necessary to satisfy the heat demand of the
preset by pushing the F button in the main building. Transition to the SUPERVISION
menu twice. A signalling arrow next to the mode is rare and it happens during lack of
sign „Temperature setting” is lit, and the hot heat demand.
utility water preset temperature value in the
upper part of the thermometer flashes. Before enabling this mode for the first time,
START and STOP buttons are used to it is recommended to program the regulator
increase and decrease the preset hot utility in accordance with point 11.9.
water temperature respectively. PID EMISSION regulation (regulation
mode 3) – new!
9
After setting the parameter boiler regulation
mode = 3 (emission sensor must be
connected).
This method is based on emission sensor
indications T3. It consists in constant,
smooth modulation of the fan revolutions in
order to stabilize the preset emission
temperature. As opposed to the boiler
Drawing 3. Temporary power increase in the PID
regulation mode = 2, the airflow operation is EMISSION mode
more stable, without excessive increasing of
Moreover, after equipping the regulator with
the airflow power, which makes that method
an emission sensor, it is possible to enable
more economical in respect of fuel saving.
very fast detection of fuel shortage. This
After loading the fuel and pushing the START
provides additional saving of heat energy
button, the fan operates with maximum
resulting from almost instantaneous
revolutions . As the preset emission
deactivation of the fan when the fuel runs
temperature is approached, the revolutions
out. Also, the fuel needs not be added
are automatically reduced. When the
quickly, as fast detection of the lack of fuel
emission temperature reaches the preset
maintains glow in the boiler furnace for a
temperature for the first time, a slight
longer time.
adjustment is made.
In order to preset the emission temperature,
In the PID EMISSION mode, it is possible to
press the “F” button until the following
temporarily increase the emission preset
window appears:
temperature. This facilitates firing the boiler
up. Thanks to this, the temperature in the
heated rooms will increase faster, without
the necessity of going to the boiler room
later on, in order to decrease the boiler
10
If optimal emission temperature causes the boiler furnace chamber. The fan is
excessive heating up of the boiler, it is best enabled for blow-off time at every blow-off
to store the surplus energy in a thermal interval. These times must be selected in
buffer. If the central heating system does not such a way that the boiler furnace did not go
feature a thermal buffer, you such find such out and, at the same time, to prevent the
preset emission temperature at which the boiler temperature from increasing.
temperature of water in the boiler is at the
desired level. If it is too hot in a room, Incorrect selection of blow-off
decrease the preset emission temperature, parameters can cause boiler
and increase it in the opposite case. The overheating.
preset boiler temperature is in this method of
secondary importance, it prevents exceeding 7.9 Settings for hot utility water
undesirable temperature of the boiler. It is The device regulates the temperature of the
recommended to preset the boiler hot utility water tank, provided that a hot
temperature as 10°C higher than the utility water temperature sensor is
expected boiler temperature after the connected. Using the hot utility water mode
emission temperature settles. After the boiler parameter , the user can:
reaches the preset temperature, the set the hot utility water priority (HUW
regulator switches to the SUPERVISION mode =1) – the central heating pump
mode. is disabled to fill the hot utility water
High emission temperature, even if tank faster
the fan rotates slowly, can mean set simultaneous operation of central
that the boiler is contaminated – in heating and hot utility water pump
such case, it should be cleaned. (HUW mode = 2),
enable the SUMMER function (HUW
Before enabling this mode for the first time,
it is recommended to program the regulator mode = 3),
in accordance with point 11.9 disable tank filling (HUW mode =4),
Caution: the regulator will If the hot utility water sensor is
automatically switch from disconnected, the hot utility water
regulation mode 3 to mode 1, if the mode user parameter cannot be
emission sensor is damaged or if changed.
the emission temperature exceeds
7.10 Enabling the SUMMER function
the emission sensor measuring
capacity. Therefore, it is important In order to enable the SUMMER function,
to set proper parameters for the which allows to fill the hot utility water tank
regulator to operate in mode 1, in the summer without the need of warming
without causing any danger. the central heating system, set the
parameter hot utility water mode = 3.
7.8 SUPERVISION
The regulator switches to the SUPERVISION Do not enable the SUMMER function if
mode in the following circumstances: the hot utility water pump is
a) In the case of CLASSIC and PID disconnected.
EMISSION modes of regulation – if the
The SUMMER function cannot be
boiler temperature exceeds the preset
enabled if the hot utility water sensor is
boiler temperature,
disconnected.
b) In the case of PID mode of regulation – if
The SUMMER function can be enabled
the boiler temperature exceeds the
only after making sure that the boiler will
preset boiler temperature by +10°C.
not overheat. If the SUMMER function is
enabled, the heat consumption is much
In the SUPERVISION mode the fan is enabled
lower, because the central heating pump
cyclically for short periods, in order to
is inactive. The method of decreasing the
prevent the fire from going out and to
boiler overheating is described in point
remove accumulated combustible gases from
11
12.15
Do not enable the SUMMER function
in a hydraulic system with a thermal
buffer
12
REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL
ecoMAX 200 W
8 Technical data 9 Hydraulic diagram
Screw terminal on
the mains voltage Drawing 6. Hydraulic diagram supported by the
side 2,5mm2 regulator, where: 1 – ecoMAX 200 regulator, 2 –central
Terminals
Screw terminals on heating pump, 3 – hot utility water pump, 4 – fan, 5 –
the control side room thermostat 6 – hot utility water tank, 7 – central
1,5mm2 heating system, 8 – chimney duct, 9 –boiler, T1 – boiler
temperature sensor, T2 – hot utility water temperature
sensor, T3 – emission temperature sensor (optional, not
Display Backlit LCD
required for normal operation).
11 Regulator installation
15
Drawing 8. Fitting the regulator in a mounting plate,
where: 1 - regulator, 2 – sheet metal screw 2.9x9, 3 – Drawing 10. Conditions of enclosing the regulator
hole plug.
The regulator enclosure must provide degree
of protection appropriate for the
environmental conditions in which the
regulator will be used. Moreover, it must
prevent the user from accessing dangerous
live parts, e.g. the terminals. The regulator
enclosure does not provide resistance to dust
and water. In order to secure the device
against these factors, the module must be
equipped with appropriate body.
Due to thermal conditions and safety issues,
a safe distance between active parts of the
terminals and the conductive (metal)
elements of the enclosure must be kept –
Drawing 10. Metal elements of the regulator
Drawing 9. Recommended display viewing angle
enclosure must be connected with the
protective wire of the feeding cable Drawing
It is recommended to fit the regulator on the
12.
boiler in such a way, that the user viewed
Connecting wires must be protected against
the regulator at the angle shown in Drawing
being torn out, loosened, or they must be
9. Green shows optimal viewing angle for the
enclosed in a way which prevents any
display.
tensions in relation to the wires.
16
three core (with protective wire),
in accordance with applicable
regulations.
17
11.6 Connecting emission sensor 11.7 Connecting temperature sensors
The temperature limiter must The fan starts smoothly from Minimum
have nominal operating voltage of revolutions to power resulting from the
at least ~230V, and it should have algorithm within the P5 time (manufacturer‟s
the applicable permits. parameter – fan starting time).
20
its being cooled down by hot water returning
12 Service settings
from the system.
Enter the service settings by holding the „F”
button in the main window for 8 seconds. Disabling the central heating pump
Exit from service settings is made on its own does not guarantee
automatically after a period of idleness, or protecting the boiler against retting,
after holding the F button. and resulting corrosion of the boiler.
name sym range unit typical Additional automatics should be
bol value
applied, e.g. four-way valve, or
Pump activation n0 0…80 C 40
temperature thermostatic three-way valve.
Boiler temperature n1 1…5 C 2
hysteresis 12.2 Boiler hysteresis n1
Min. airflow power n2 10…99 % 14
Min. boiler temperature 40…55 C 50
The (n1) parameter determined the
n3
Max. boiler 70…90 C 85
temperature at which the boiler returns from
n4
temperature the SUPERVISION mode to the OPERATION
Fuel shortage detection n5 2…250 Min 20 mode. The regulator returns to the
time . OPERATION mode at the temperature preset
Screen brightness n6 0…100 % 80
boiler temperature – boiler hysteresis.
Fan revolutions‟ n7 C 5
reduction temperature
Central heating pump 0…99 min 0
12.3 Minimum airflow power n2
n8
down-time by .
When the regulator is turned on for the first
thermostat
Extinguishment 1,2 1
time, it is necessary to set the user-defined
n9
detection method parameter Minimum airflow power. After
Boiler preset r0 0,1…20 C 0 setting a value of e.g. 14%, the user will be
temperature decrease able to set airflow power of at least 14%.
by thermostat
C
The minimum airflow power should be
Hot utility water r1 1…20 5
temperature hysteresis determined after observing the fan
Boiler preset r2 0…20 C 5 behaviour. You must determine minimum
temperature increase value of revolutions at which the fan can
by hot utility water
rotate properly, i.e. freely, without rattling.
Max. hot utility water r3 20…85 C 65
temp.
Extending hot utility r4 0,1…30 min 0 Set boiler regulation mode = 1 Maximum
water pump operation . revolutions and Minimum revolutions to the
Fuel shortage detection r5 20…250 C 90 value of revolutions you want to test. For
– emission temperature
most fans, this will be 12 – 15%.
Disabling the CH pump r6 0…1 0
-operation with a buffer
Emission temperature - r7 10…40 C 30 12.4 Minimum boiler temperature n3
firing up mode 3 (x10) (300)
This parameter can be used to prevent the
Firing up time mode3 r8 0, 250 min 30
user from setting too low preset boiler
Restoring service r9 1,0 - 0
parameters temperature. If the boiler operates at too low
a temperature, it can cause its rapid
12.1 Central heating pump activation damage, corrosion, soiling, etc.
temperature n0
Set the value in accordance with the
The (n0) parameter specifies the boiler manufacturer‟s
temperature at which the central heating recommendations
pump is activated. After reaching the
temperature equal to the Central heating
12.5 Maximum boiler temperature n4
pump activation temperature parameter, the
central heating pump is activated. This This parameter can be used to prevent the
protects the boiler against retting caused by user from setting too high preset boiler
temperature.
21
temperature (point 11.10). As a result of
Set the value in accordance with the blocking the central heating pump, the
boiler manufacturer‟s temperature in the heated rooms will drop,
recommendations and the boiler will reach the preset
temperature faster and switch to the
SUPERVISION mode. Yet, too long a
12.6 Fuel shortage detection time n5
blockade of the central heating pump will
This is the time after which the regulator will cause the system to cool down, which is
produce the fuel shortage alarm. disadvantageous for maintaining the room
If the regulator produces the “No temperature at constant level. The heating
fuel” alarm too fast, increase the medium accumulated in the system has high
value of this parameter. thermal inertia, and heating it after the
Recommended settings of the n5 parameter thermostat contacts are shorted can take too
depending on the method of detecting fuel long. Thus, it is not recommended to set
shortage: excessively long central heating pump down-
times. After the central heating pump down-
Detection method n5 value
time by thermostat (service parameter n8),
1 – boiler sensor 20min the regulator will enable it for a constant,
2 – emission 10min pre-programmed time of 30 s.
sensor
12.10 Fuel shortage detection methods
Methods of detection are specified in point
n9
12.21.
This parameter determines the method of
12.7 Screen brightness n6
detecting fuel shortage. If:
Increases or decreases the brightness of
display backlight. n9 = 1, fuel shortage is detected on the
basis of the boiler temperature readings T1,
12.8 Fan revolutions’ reduction point 14.1,
temperature n7 n9 = 2, fuel shortage is detected on the
This parameter is applicable only if the boiler basis of emission sensor T3 readings. Do not
regulation mode = 1 – CLASSIC is set n9=2 if emission sensor is disconnected.
enabled. After the boiler reaches the boiler
preset temperature – n7, the fan starts 12.11 Lowering the preset boiler
reducing its revolutions until the boiler preset
temperature is reached. By default n7 = 5C. temperature r0
23
Fast detection of fuel shortage decreases 13 Firmware
losses of heat caused by the fan operating
WARNING!!! Values of the following
with no fuel, and it allows to sustain fire for a
parameters can be modified only by
longer time, during which the boiler can be
qualified staff of the boiler manufacturer
refuelled without the need of firing it up
There is a menu of factory parameters in the
again.
regulator. These are advanced settings. After
restoring default settings, the following
1-first method – based on the boiler
parameter values are not restored!
temperature sensor readings T1 (factory
Therefore, before changing any parameter it
parameter S9=1). After the boiler
is recommended to write down its default
temperature drops below the n0 parameter
value, in order to be able to restore it.
Pump activation time, the fuel shortage
The manufacturer‟s menu can be accessed
detection time n5 is counted out (see point
by activating the regulator via the mains
12.6). If after that time the boiler
switch while pressing the F button, and
temperature does not rise, the AL1 alarm is
holding it for 12 seconds.
produced and the fan is disabled.
Name sy range typica
mb l
2-second method (recommended) – based ol value
on emission temperature sensor readings Boiler overheating alarm P0 50…99 C 90
(factory parameter S9=2). This method temperature
Central heating pump P1 1…250 s 30
allows very fast detection of the fuel
operation time with
shortage. It can be used only if an emission blockade by room
sensor T3, placed in the boiler flue, is thermostat
connected. After the emission temperature Central heating and hot P2 1…10 C 2
drops below the factory parameter P8 (Fuel utility water pump
hysteresis
shortage detection – emission temperature), Central heating and hot P3 1…30 C 15
the fuel shortage detection time n5 is utility water pump
counted out (see point 12.6). If after this hysteresis – AL3 alarm
time the temperature does not increase, AL1 end
Central heating pump P4 1…250 min 0
alarm is produced.
down-time by priority
Fan start time P5 0…60 s 2
The AL1 alarm will be cancelled after: Temperature 1 of P6 - C 10
- pushing the START button, or after extending blow-off
- disabling and enabling the regulator via interval
Temperature 2 of P7 - C 15
mains switch.
extending blow-off
interval
Recommended settings of the n5 parameter Amplification factor – P8 1...999 - 180
(fuel shortage detection time) depending on regulation mode 2
the method of detecting: Integration time – P9 1…999 - 350
regulation mode 2
Differentiation time – S0 1…999 - 25
Detection n5 value
regulation mode 2
method Amplification factor – S1 1...999 - 11
1 – boiler sensor 20min regulation mode 3
2 – emission 10min Integration time – S2 1…999 - 120
regulation mode 3
sensor
Differentiation time – S3 1…999 - 5
regulation mode 3
12.22 Power supply decay
14 Description of alarms
In the cases of power supply failure, the
regulator will resume the operation mode in 14.1 No fuel AL1
which it was before the failure. After detecting fuel shortage, the following
message will appear on the display
24
cause stoppage of the boiler.
This alarm will occur after the boiler exceeds When ordering parts and subassemblies,
temperature determined by the factory please specify necessary information read off
parameter Boiler overheating alarm the rating plate. It is best to give the
temperature P0. By default, this parameter is regulator serial number. If the serial number
set to 90C. In such case, the fan is turned is not known, please specify the model and
off, and the central heating and hot utility type of the regulation, as well as the year of
water pumps are activated. A sound signal is its production.
also activated. The hot utility water pump
works only until the hot utility water tank 15.1 Replacing mains fuse
exceeds the maximum temperature r3
The mains fuse can be found in the regulator
(service parameter). This protects the users
front panel. It protects the regulator and the
against possible scalding.
devices fed by it. Please use time-delay
After the boiler temperature drops, the
fuses, porcelain, 5x20mm, of nominal
regulator resumes normal operation.
burnout current 3,15A, e.g. 02153.15P made
It is suggested to set the P0 value
by LittelFuse.
below the safety temperature
In order to remove the fuse, push in its
limiter actuation threshold. Thanks
socket with a flat-tip screwdriver and turn it
to this, a momentary exceeding of
counter clockwise.
the boiler temperature will not
25
16 Description of possible faults
26
sp. z o.o.
Ignatki 27a 16-001 Kleosin
tel. +48 85 749-70-00
fax +48 85 749-70-14
plum@plum.pl, www.plum.pl
POLAND