DATA TANAH

UNTUK PERENCENAAN BEBAN GEMPA DAN STRUKTUR PONDASI


HANNY KARTIKA / ZALINO SABRIAN
PPG - 3A
4.11.15.0.12 / 4.11.15.0.25

Data Sondir DIY (Projas)

CONE PENETROMETER TEST


SOIL MECHANICS LABORATORY
DUTCH CONE TEST

Manometer Reading
Total
Cone Total Local Friction
Depth Friction (Fr) Fr*20/10 Cumulative Friction Ratio (FR)
Resistance Resistance (LF)
Friction (TCF)
(qc) (TR)
(m) (kg/cm2) (kg/cm2) (kg/cm2) (kg/cm') (kg/cm') (kg/cm2) (%)
A B C D E F G H
0.00 0 0 0 0 0 0.00 0.00
-0.20 0 0 0 0 0 0.00 0.00
-0.40 0 0 0 0 0 0.00 0.00
-0.60 0 0 0 0 0 0.00 0.00
-0.80 3 4 1 2 2 0.10 3.33
-1.00 2 3 1 2 4 0.10 5.00
-1.20 5 7 2 4 8 0.20 4.00
-1.40 6 9 3 6 14 0.30 5.00
-1.60 8 12 4 8 22 0.40 5.00
-1.80 12 16 4 8 30 0.40 3.33
-2.00 16 21 5 10 40 0.50 3.13
-2.20 22 30 8 16 56 0.80 3.64
-2.40 25 33 8 16 72 0.80 3.20
-2.60 16 21 5 10 82 0.50 3.13
-2.80 18 23 5 10 92 0.50 2.78
-3.00 15 20 5 10 102 0.50 3.33
-3.20 17 23 6 12 114 0.60 3.53
-3.40 28 35 7 14 128 0.70 2.50
-3.60 22 30 8 16 144 0.80 3.64
-3.80 20 27 7 14 158 0.70 3.50
DATA TANAH
UNTUK PERENCENAAN BEBAN GEMPA DAN STRUKTUR PONDASI
HANNY KARTIKA / ZALINO SABRIAN
PPG - 3A
4.11.15.0.12 / 4.11.15.0.25

Data Sondir DIY (Projas)

CONE PENETROMETER TEST


SOIL MECHANICS LABORATORY
DUTCH CONE TEST

Manometer Reading
Total
Cone Total Local Friction
Depth Friction (Fr) Fr*20/10 Cumulative Friction Ratio (FR)
Resistance Resistance (LF)
Friction (TCF)
(qc) (TR)
(m) (kg/cm2) (kg/cm2) (kg/cm2) (kg/cm') (kg/cm') (kg/cm2) (%)
A B C D E F G H
-4.00 16 21 5 10 168 0.50 3.13
-4.20 32 44 12 24 192 1.20 3.75
-4.40 29 34 5 10 202 0.50 1.72
-4.60 26 30 4 8 210 0.40 1.54
-4.80 22 25 3 6 216 0.30 1.36
-5.00 15 31 16 32 248 1.60 10.67
-5.20 23 39 16 32 280 1.60 6.96
-5.40 31 47 16 32 312 1.60 5.16
-5.60 35 50 15 30 342 1.50 4.29
-5.80 37 55 18 36 378 1.80 4.86
-6.00 38 55 17 34 412 1.70 4.47
-6.20 32 55 23 46 458 2.30 7.19
-6.40 35 55 20 40 498 2.00 5.71
-6.60 40 55 15 30 528 1.50 3.75
-6.80 35 50 15 30 558 1.50 4.29
-7.00 28 45 17 34 592 1.70 6.07
-7.20 45 47 2 4 596 0.20 0.44
-7.40 50 65 15 30 626 1.50 3.00
-7.60 48 62 14 28 654 1.40 2.92
-7.80 45 60 15 30 684 1.50 3.33
DATA TANAH
UNTUK PERENCENAAN BEBAN GEMPA DAN STRUKTUR PONDASI
HANNY KARTIKA / ZALINO SABRIAN
PPG - 3A
4.11.15.0.12 / 4.11.15.0.25

Data Sondir DIY (Projas)

CONE PENETROMETER TEST


SOIL MECHANICS LABORATORY
DUTCH CONE TEST

Manometer Reading
Total
Cone Total Local Friction
Depth Friction (Fr) Fr*20/10 Cumulative Friction Ratio (FR)
Resistance Resistance (LF)
Friction (TCF)
(qc) (TR)
(m) (kg/cm2) (kg/cm2) (kg/cm2) (kg/cm') (kg/cm') (kg/cm2) (%)
A B C D E F G H
-8.00 42 58 16 32 716 1.60 3.81
-8.20 50 55 5 10 726 0.50 1.00
-8.40 52 58 6 12 738 0.60 1.15
-8.60 55 58 3 6 744 0.30 0.55
-8.80 50 55 5 10 754 0.50 1.00
-9.00 55 60 5 10 764 0.50 0.91
-9.20 58 62 4 8 772 0.40 0.69
-9.40 55 60 5 10 782 0.50 0.91
-9.60 60 65 5 10 792 0.50 0.83
-9.80 62 68 6 12 804 0.60 0.97
-10.00 65 70 5 10 814 0.50 0.77
-10.20 68 72 4 8 822 0.40 0.59
-10.40 65 70 5 10 832 0.50 0.77
-10.60 72 74 2 4 836 0.20 0.28
-10.80 58 65 7 14 850 0.70 1.21
-11.00 50 68 18 36 886 1.80 3.60
-11.20 55 72 17 34 920 1.70 3.09
-11.40 42 75 33 66 986 3.30 7.86
-11.60 45 70 25 50 1036 2.50 5.56
-11.80 32 72 40 80 1116 4.00 12.50
DATA TANAH
UNTUK PERENCENAAN BEBAN GEMPA DAN STRUKTUR PONDASI
HANNY KARTIKA / ZALINO SABRIAN
PPG - 3A
4.11.15.0.12 / 4.11.15.0.25

Data Sondir DIY (Projas)

CONE PENETROMETER TEST


SOIL MECHANICS LABORATORY
DUTCH CONE TEST

Manometer Reading
Total
Cone Total Local Friction
Depth Friction (Fr) Fr*20/10 Cumulative Friction Ratio (FR)
Resistance Resistance (LF)
Friction (TCF)
(qc) (TR)
(m) (kg/cm2) (kg/cm2) (kg/cm2) (kg/cm') (kg/cm') (kg/cm2) (%)
A B C D E F G H
-12.00 34 68 34 68 1184 3.40 10.00
-12.20 34 70 36 72 1256 3.60 10.59
-12.40 34 72 38 76 1332 3.80 11.18
-12.60 36 75 39 78 1410 3.90 10.83
-12.80 38 78 40 80 1490 4.00 10.53
-13.00 32 80 48 96 1586 4.80 15.00
-13.20 30 82 52 104 1690 5.20 17.33
-13.40 28 80 52 104 1794 5.20 18.57
-13.60 28 88 60 120 1914 6.00 21.43
-13.80 28 75 47 94 2008 4.70 16.79
-14.00 26 72 46 92 2100 4.60 17.69
-14.20 26 70 44 88 2188 4.40 16.92
-14.40 26 68 42 84 2272 4.20 16.15
-14.60 26 14 -12 -24 2248 -1.20 SALAH
-14.80 26 13 -13 -26 2222 -1.30 SALAH
-15.00 24 12 -12 -24 2198 -1.20 SALAH
-15.20 24 12 -12 -24 2174 -1.20 SALAH
-15.40 22 12 -10 -20 2154 -1.00 SALAH
-15.60 26 8 -18 -36 2118 -1.80 SALAH
-15.80 22 7 -15 -30 2088 -1.50 SALAH
DATA TANAH
UNTUK PERENCENAAN BEBAN GEMPA DAN STRUKTUR PONDASI
HANNY KARTIKA / ZALINO SABRIAN
PPG - 3A
4.11.15.0.12 / 4.11.15.0.25

Data Sondir DIY (Projas)

CONE PENETROMETER TEST


SOIL MECHANICS LABORATORY
DUTCH CONE TEST

Manometer Reading
Total
Cone Total Local Friction
Depth Friction (Fr) Fr*20/10 Cumulative Friction Ratio (FR)
Resistance Resistance (LF)
Friction (TCF)
(qc) (TR)
(m) (kg/cm2) (kg/cm2) (kg/cm2) (kg/cm') (kg/cm') (kg/cm2) (%)
A B C D E F G H
-16.00 24 7 -17 -34 2054 -1.70 SALAH
-16.20 24 6 -18 -36 2018 -1.80 SALAH
-16.40 26 6 -20 -40 1978 -2.00 SALAH
-16.60 22 6 -16 -32 1946 -1.60 SALAH
-16.80 26 7 -19 -38 1908 -1.90 SALAH
-17.00 26 7 -19 -38 1870 -1.90 SALAH
-17.20 28 8 -20 -40 1830 -2.00 SALAH
-17.40 20 8 -12 -24 1806 -1.20 SALAH
-17.60 18 7 -11 -22 1784 -1.10 SALAH
-17.80 18 9 -9 -18 1766 -0.90 SALAH
-18.00 18 11 -7 -14 1752 -0.70 SALAH
-18.20 18 13 -5 -10 1742 -0.50 SALAH
-18.40 16 12 -4 -8 1734 -0.40 SALAH
-18.60 18 12 -6 -12 1722 -0.60 SALAH
-18.80 18 10 -8 -16 1706 -0.80 SALAH
-19.00 16 9 -7 -14 1692 -0.70 SALAH
-19.20 16 12 -4 -8 1684 -0.40 SALAH
-19.40 16 12 -4 -8 1676 -0.40 SALAH
-19.60 18 12 -6 -12 1664 -0.60 SALAH
-19.80 12 10 -2 -4 1660 -0.20 SALAH
DATA TANAH
UNTUK PERENCENAAN BEBAN GEMPA DAN STRUKTUR PONDASI
HANNY KARTIKA / ZALINO SABRIAN
PPG - 3A
4.11.15.0.12 / 4.11.15.0.25

Data Sondir DIY (Projas)

CONE PENETROMETER TEST


SOIL MECHANICS LABORATORY
DUTCH CONE TEST

Manometer Reading
Total
Cone Total Local Friction
Depth Friction (Fr) Fr*20/10 Cumulative Friction Ratio (FR)
Resistance Resistance (LF)
Friction (TCF)
(qc) (TR)
(m) (kg/cm2) (kg/cm2) (kg/cm2) (kg/cm') (kg/cm') (kg/cm2) (%)
A B C D E F G H
-20.00 12 9 -3 -6 1654 -0.30 SALAH
TUGAS PONDASI DATA SONDIR
LINTANG DIAN ARTANTI
PPG - 3A
4.11.15.0.14

CONE PENETROMETER TEST / SONDIR


Standart Test : ASTM D 3441 - 94

Local Friction*10 (kg/cm2)

qc (kg/cm2)

TCF / 10 (kg/cm')
Friction Ratio (%)
0 2 4 6 8 10 12 14 16 18 20 0 2 4 6 8 10 12
0.0 0.0

-1.0 -1.0

-2.0 -2.0

-3.0 -3.0

-4.0 -4.0

-5.0 -5.0

-6.0 -6.0

-7.0 -7.0
kedalaman (m)

-8.0 -8.0

-9.0 -9.0

-10.0 -10.0

-11.0 -11.0

-12.0 -12.0

-13.0 -13.0

-14.0 -14.0

-15.0 -15.0

-16.0 -16.0

-17.0 -17.0

-18.0 -18.0

-19.0 -19.0

-20.0 -20.0
P=V Mx My Wx Wy
Max Min Max Min Max Min Max Min Max Min
KN KN KNm KNm KNm KNm KN KN KN KN
1858.718 213.502 1144.418 -1137.953 691.271 -687.782 272.198 -293.264 364.893 -366.441
1858.718 1144.418 691.271 293.264 366.441
ANALISA PERHITUNGAN TIANG PANCANG
BY
LINTANG DIAN ARTANTI
PPG - 3A
4.11.15.0.14
1. Pendimensian Tiang Pancang
A. Ukuran Tiang Pancang

b = 0.3 m
h = 0.3 m

B. Kedalaman Pancang

L = 9.20 m

C. Pengangkatan Pancang Dari Tempat ke Tempat

Tiang Pancang 60 x
60 cm

M1 = M2
1/2 g a² = 1/8 g (L-2a)² – ½ g.a²
1/2 a2 - 1/8 (L – 2a) 2 + 1/2 a2 = 0
4a2– (L – 2a) 2 + 4a2 = 0
4a2– (L2 – 4aL + 4a2) + 4a2 = 0
4a2- L2+ 4aL – 4a2 + 4a2 = 0
4a2+ 4aL - L2 = 0

Memakai rumus

Dimana a = 4; b = 4L; c = - L2

(OK)

x1 = a = 1.904 m
g = 216 Kg/m
M1 = M2 = 391.688 Kgm
D. Pengangkatan Pancang Dari Tempat ke Titik Pemancangan

M1 = M1
1/2 g a² = R1 (L-a) – [ g (L-a) x 1/2 (L-a) ]
1/2 g a² = R1 (L-a) – 1/2 g (L-a)²
1/2 g a² = (L-a) (R1 - 1/2 g (L-a))
1/2 g a²
= R1 - 1/2 g (L-a)
(L-a)
R1 = 1/2 g (L-a) - 1/2 g a²
(L-a)
R1 =

R1 =

R1 =

Mx =

Syarat Ekstrim = 0

= 0

Mmax = M2 =

M1 = M2

a² =

a =

2a (L - a) = L² - 2 a L
2aL - 2a² = L² - 2 a L
2a² - 4aL + L² = 0
Dengan menggunakan rumus

Dimana : a = 2 ; b = -4L ; c = L2

= 0.293 L (OK)
= 1.707 L

x1 = a = 2.6956 m
M1 = M2 = 784.7560109 Kgm

Momen Yang Dipakai M = 784.7560109 Kgm

E. Penentuan Tulangan Tiang Pancang

Fe = 3fe

5.0
x

h = 30 cm

Momen M = 784.756 Kgm


Selimut
P = 50 mm
Beton
D = 22 mm
Tulangan
n = 8 bh
Luasan
fe = 3.801 cm²
Tulangan

(x. b . 1/2 x) + (n . Fe . (x - 5)) = n . Fe. (h - x)


(b/2 . x²) + (2n . Fe . x) - ((5n . Fe) + (n . h . Fe)) = 0

(-b±√(b^2+4ac))/2a
Dengan menggunakan rumus X1,2 =

a= b/2 = 15
Dimana : b= 2n . Fe = 182.4637
c = ((5n . Fe) + (n . h . Fe)) = 3193.115
(-b+√(b^2+4ac))/2a
X1 =

= 9.725 cm (Dipakai)
Sehingga :
(-b -√(b^2+4ac))/2a
X2 =

= -21.889 cm
Ix1 = 1/(12 ) b x³ + b x ( 1/(2 )
x²)
= 1/(12 ) b x³ + 1/(4 ) b x³

= 1/(3 ) b x³

= 9197.605 cm4

Momen Inersia Ix2 = n fe ( x - 5 )2

= 678.949 cm4

Ix3 = n fe ( h - x )2

= 12501.00899 cm4

Ixtotal = 22377.562 cm4

Wd = Ix
/
x
= 2301.024252 cm3
Ix/(n(h-
We = x))

= 137.963 cm3

M/
= Wd < 60 Kg/cm2
Beton
= 34.105 ( Oke Aman )
Kekuatan Bahan
M"/
= We < 1400 Kg/cm2
Baja
= 568.816 ( Oke Aman )

2. Kemampuan Tiang Pancang

A. Terhadap Kekuatan Bahan Tiang

1. Luasan Tiang (Atiang)

Abeton = (bxh)
= ( 30 x 30 )
= 900 cm²
Atulangan = ( n x fe )
= ( 8 x 3.801 )
= 30.411 cm²

2. Beban Tiang Sendiri (Ptiang)

Ptiang = (σ izin beton x Abeton) + (σ izin baja x Atulangan)


= ( 60 x 900 ) + ( 1400 x 30.411 )
= 96574.864 kg
= 96.575 ton

B. Terhadap Kekuatan Tanah

1. Akibat Tanah Ujung

Kedalaman L= 9.2 m
Harga Konus P= 72 Kg/cm²
Luasan Tiang Atiang = 900 cm²

Daya Dukung Tiang = 900 x 72


3
= 21600.000 Kg
= 21.600 Ton
2. Akibat Cleef Friction

a. Perhitungan Clef Rata-Rata

Kedalaman Selisih Kedalaman TCF Selisih TCF C


(m) (cm) (Kg/cm') (Kg/cm') (Kg/cm²)
0.00 0
200 40
2.00 40 0.200
128
4.00 200 168 0.640
200 244
6.00 412 1.220
304
8.00 200 716 1.520
120 120
9.20 - 836 - 1.000 -

b. Daya Dukung Tiang =

= 20064.000 Kg
= 20.064 Ton

Daya Dukung Keseimbangan = 41.664 Ton


= 1987.2 Kg
Berat Sendiri Tiang
= 1.9872 Ton

Beban Netto < Ptiang

39.677 Ton < 96.575 Ton ( Oke Aman )


ANALISA PERHITUNGAN PILE CAP
BY
LINTANG DIAN ARTANTI
PPG - 3A
4.11.15.0.14
1. Pendimensian Pile Cap (P1)

X Y
60.0

Tiang Beton
30 x 30

100.0 100.0 100.0 100.0


50.0 50.0 50.0 50.0
300.0 300.0

50.0

100.0
X 300.0

1200.0

50.0
Tiang Beton
Y
30 x 30

Pile Cap Type P1 (9 tiang ) Arah X ( 3000x3000x600 mm2)


Data - data
fc' 40 Mpa Type P1
P 185872 kg Jumlah 9 tiang
Selimut beton 50 mm Lx 3000 mm
Ht 600 mm Ly 3000 mm
d 550 mm
b1 1
bklm 600 mm
hklm 600 mm
bo = bklm + 2*0.5*Ht 1200 mm
ho = hklm + 2*0.5*Ht 1200 mm

Cek Geser Pons


A = 2*(bo+ho)*d
= 2*(1200+1200)*550 = 2640000 mm2

Vc1 = (1+2/b1) x (fc'0.5 /6) x A


= (1+2/1) x (40^0.5 /6) x 2640000
= 8348413.02 N ~ 834841.3 kg

Vc2 = (fc'0.5 /3) x A


= (40^0.5 /3) x 2640000
= 5565608.68 N ~ 556560.87 kg

Diambil yang terkecil ---> Vc = 556560.87 kg


Cek : Vc > P/f
556560.87 > 309786.67 (ok)
Berarti dimensi pile cap bisa dipakai.

2. Penulangan Pile Cap Arah X


Data-data
fc' (beton) 40 Mpa Ht 600 mm
fy' (baja) 400 Mpa b 3000 mm
d' (1) 50 mm

ALTERNATIVE 1

2P 2P
0.5 m
1.5 m
1.55 m

L1 = 0.50 m 2P = 41304.9 kg
L2 = 1.50 m
L= 1.55 m
220.0

Qpile cap = Ht x B x 2400


= 0.6 x 3 x 2400 = 4320 kg/m

Mu = 1.2 x ( 2P.L1 + 2P.L2 - 1/2.Q.L^2)


= 1.2 x (41304.8888888889x0.5 + 41304.8888888889x1.5 - 1/2x4320x1.55^2)
= 92904.45 kgm

= 929.045 kNm

d = Ht - d'
= 600 - 50
= 550.00 mm

j = 0.80
Rn = Mu
ϕ. b. d2
= (929.04 x 10^6)
(0,8 x 3000 x 550^2)
= 1.280 Mpa

m = Fy
0,85 . Fc'

= 400
0,85 x 40
= 11.765

pmin = 1.4 / fy
= 1.4 / 400
= 0.0035
1/m(1-√(1-
ρ perlu = (2Rn.m)/Fy)

= 1 ( 1 -√ 1 - 2 x 1.28 x 11.76 )
11.76 400

= 0.0033

pb = β1. (0,85.fc′)/fy. 600/(600+fy)

= 1 x 0,85 x 40 . 600
400 600 + 400
= 0.0510

pmax = 0.75 x pb
= 0.75 x 0.051
= 0.038

Karena,
pmin > ρ perlu < pmax Tulangan Tunggal
0.0035 > 0.0033 < 0.04 Maka Pakai ρ min
Tulangan Lentur
As = ρ min x b x d
= 0.0035 x 1000 x 550
= 1925.00 mm2

Dia. Tulangan Lentur = 22 mm

Sada = 0,25 x π x 22^2 x 1000


1925
= 197.47 mm

Spakai = 150 mm

Asada = 0,25 x π x 22^2 x 1000


150
= 2534.22 mm2 OK

Maka Digunakan Tulangan Lentur ϕ 22 - 150


Tulangan Arah Lain Dipasang Sama

Tulangan Bagi
As = ( 20 / 100 ) x As Lentur
= ( 20 / 100 ) x 1925
= 385.00 mm2

Dia. Tulangan Lentur = 16 mm

Sada = 0,25 x π x 16^2 x 1000


385
= 522.24 mm

Spakai = 150 mm

Asada = 0,25 x π x 16^2 x 1000


150
= 1340.41 mm2 OK

Maka Digunakan Tulangan Bagi ϕ 16 - 150


Tulangan Arah Lain Dipasang Sama
ANALISA BEBAN TIANG PANCANG & DAYA DUKUNG TANAH
BY
LINTANG DIAN ARTANTI
PPG - 3A
4.11.15.0.14
V = P = 185.872 ton V = P = 185.872 ton

My = 69.127 ton Mx = 114.442 ton


X Y
60.0

Tiang Beton
30 x 30

100.0 100.0 100.0 100.0


50.0 50.0 50.0 50.0
300.0 300.0

50.0

100.0
X 300.0

100.0

50.0
Tiang Beton
30 x 30 Y

1. Data Tiang Pancang

b 0.30 m
Ukuran Tiang Pancang
h 0.30 m
p 3.00 m
Ukuan Poer / Pile Cap l 3.00 m
t 0.60 m
Kedalaman Pancang L 9.2 m
Jarak Tiang s 1.00 m
nx 3 bh
Banyak Tiang ny 3 bh
ntotal 9 bh
Beban Normal Total Σv 185.872 ton
Mx 114.442 t.m
Momen
My 69.127 t.m
Absis Max Xmax 1.500 m
(dari tiang pancang terluar)
Ordinat Max Ymax 1.500 m

2. Perhitungan Beban Tiang Maksimum

ΣX² = (3 x 2 x 2²) + (3 x 2 x 1²)

Σkwadrat Absis Tiang Pancang


= 30.00 m²

ΣY² = (3 x 2 x 2²) + (3 x 2 x 1²)

Σkwadrat Ordinat Tiang Pancang


= 30.00 m²
Pmax = ΣV/ntotal± (My . Xmax)/Σx² ±
(Mx . Ymax)/Σy²

Pmax1 = 185,872/9 + (69,127 x 1,5)/30 +


(114,442x 1,5)/30

= 29.831 ton
Beban Tiang Maksimum
Pmax2 = 185,872/9 - (69,127 x 1,5)/30 -
(114,442x 1,5)/30
= 11.474 ton

Pmax = 29.831 ton

3. Beban Tiang Maksimum Terhadap Daya Dukung Tanah

Beban Tiang Maksimum < Daya Dukung Tanah


Pmax < Daya Dukung Keseimbangan
29.831 ton < 41.664 ton (Oke Aman)
A. PERHITUNGAN KEKUATAN BAHAN

Ukuran Tiang Kedalaman Pengangkatan Pancang dari Pengangkatan Pancang dari Tempat ke
Tempat ke Tempat Titik Pemancangan
B H L X1 = a g M1 = M2 X1=a g
m m m m Kg/m Kgm m Kg/m
0.3 0.3 9.20 1.904 216 391.688 2.696 216

B. PERHITUNGAN KEKUATAN TIANG PANCANG TERHADAP KEKUATAN TANAH

Kekuat
Ukuran Tiang Kekuatan Bahan Tiang
Akibat Tanah Ujung
B H Atiang Ptiang L qc Atiang
m m cm2 Kg Ton m Kg/cm 2
cm2
0.3 0.3 978.540 29356.19 29.356 9.20 72 900

C. PERHITUNGAN BEBAN TIANG MAKSIMUM TERHADAP DAYA DUKUNG TANAH

Data Tiang Pancang


Ukuran Tiang Pancang Ukuran Poer/Pile Cap Kedalaman Jarak Antar Tiang Banyak Tian
B H p l t L s nx
m m m m m m m bh
0.3 0.3 3.00 3.00 0.60 9.20 1.00 3

D. PERHITUNGAN CEK DIMENSI PILE CAP

fc' = 25 Mpa
fy = 400 Mpa
βc = 1

Data Kolom Data Tiang Pancang Data Pile Cap


B H B H n p l t
m m m m bh m m m
0.7 0.7 0.3 0.3 9 3.00 3.00 0.60

D. PERHITUNGAN TULANGAN PILE CAP

fc' = 25 Mpa
fy = 400 Mpa

Ukuran Tiang Ukuran Pile Cap


B H p l t A L ts
m m m m m m2 m mm
0.70 0.70 3.00 3.00 0.60 9.00 9.20 50
ncang dari Tempat ke Momen
Selimut Beton Tulangan
mancangan Pakai
M1=M2 Mpakai p n Dia. fe a
Kgm Kgm mm bh mm cm2 cm
784.756 784.756 50 16 25 4.909 15.0

Kekuatan Tanah
anah Ujung Akibat Cleef Friction Daya Dukung
Berat Sendiri Tiang
Keseimbangan
Daya Dukung Tiang cleef Rata Daya Dukung Tiang
Kg Ton Kg/cm Kg Ton Ton Kg
21600.000 21.600 #REF! #REF! #REF! #REF! 1987.2

Data Tiang Pancang


Banyak Tiang Beban Nominal Total Momen Absis Max Ordinat Max
ny ntotal ΣV atau ΣP Mx My Xmax Ymax
bh bh Ton T.m T.m m m
3 9 185.872 114.442 69.127 1.50 1.50

Dia. Tul p d bo ho A Vcl


mm mm mm mm mm mm2
25 50 237.5 1000 1000 950000 2375000
d Dulir Pu Wx Wy Mx My
mm mm KN KN KN KNm KNm
641 19 1858.718 293.264 366.441 2698.029 3371.257
Rumus abc Momen Ine
b c X1 X2 Xpakai Ix1
cm cm cm cm cm cm4
785.398 13744.468 13.841 -66.20102137 13.841 26516.484

Beban Akibat
Beban Akibat
Berat Sendiri Tiang Tiang
Tanah Keterangan
Pancang
Ton Ton Ton
1.9872 #REF! 29.356 #REF!

Beban Tiang Maksimum Daya


Σkwadrat Absis Σkwadrat Ordinat Beban Tiang Maksimum Dukung
ΣX2 ΣY2 Pmaks1 Pmaks2 Pmaks Pakai Tanah
m2 m 2
Ton Ton Ton Ton
30.00 15.00 35.553 5.752 35.553 29.356
ex ey σu max σu min σu pakai Mu
KN/m² KN/m² KN/m² KNm
1.4516 1.8138 1555.254 1142.206 1555.254 1028.412

Fy
0,85 . Fc'
Momen Inersia Kekuatan Bah
Ix2 Ix3 Ixtotal Wd We σbeton hitung σbeton izin
cm4
cm4
cm4
cm3
cm3
Kg/cm 2
Kg/cm2
6139.129 20507.424 53163.038 3840.943 205.627 20.431 60

Keterangan

Desain Ulang
Rn
Ø Ø m ρ min ρ perlu ß
Mpa
0.8 3.134 0.85 18.824 0.0018 0.0085 0.65

1/m(1-√(1-(2Rn.m)/Fy)
Kekuatan Bahan
σbaja hitung σbaja izin
Keterangan Keterangan
Kg/cm 2
Kg/cm2
OKE AMAN 381.641 1400 OKE AMAN
As perlu Sperlu Spakai As pakai
ρb ρmax ρ pakai
mm2 mm mm mm2
#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! Err:520 Err:520
Cek Hasil

Err:520 Err:520 Tulangan Arah Lain dipasang Sama