You are on page 1of 14

DC SEQUENCER FOR DEDUSTING PLANTS

PLEASE READ THE WHOLE USER MANUAL CAREFULLY BEFORE INSTALLING THE EQUIPMENT

DESCRIPTION
Sequencer for dedusting plant cleaning cycle control with
digital dP control by internal transducer. Device with
microprocessor management and zero-crossing detection
for the outputs activation to give high immunity from
external interference and low field emission.
Max 3 output relays, Max 3 digital voltfree input

DOCUMENTATION INDEX

- Introduction
- Installation rules and technical features
- Enter datas in SET MODE
- RUNNING MODE and Alarms description
- Standard features details
- Option on request
- Electrical Wiring Diagram
- Board layout
- Housing and Dimension
- Problems solution
- CE certificate

STANDARD FEATURES

A1a Out Minimum and maximum dP alarms on one single relay (K2)
A2a Out Relay Voltage ON (K1)
B1b Select Number of outputs
B2x Activation time from 0.05 to 5.00 sec.
B3x Interval time from 1 to 999 sec.
B3c Interval time between ev. during post-cleaning
B8b Short-circuit protection of every single output
B10 Manual activation of every sing output from keyboard
C1 Digital differential pressure control (STOP at cycle end)
C4 Cleaning cycle
C8 dP zero readout regulation
C7c1 Out Minimum dP alarm. Alarmed contact open. Automatic reset.
C7d1 Out Maximum dP alarm. Alarmed contact open. Automatic reset.
C13_10 dP full range 10kPa
D1b1 Additional post-washing cycles from dP readout. Activation at STOP.
D5a In Consent from external compressed air pressure switch
D6a In ON/OFF cleaning cycle from external contact
D14a Operation hour-counter
DPa 6x4 RILSAN air connections
G1 Maximum load power 25W per output
HVB Input and output voltage selection
SL Multi language display

In = Input Signal. Voltfree contact


Out = Output signal. Relay Contact
Code: DC16MU7.1+B9b... ME NHOFERGmbH
ENTSTAUBUNGSANLAGEN UND FILTERELEMENTE
S/N: A-2340 Mödling bei Wien, Südtirolergasse 9
Date: 06 / 05 / 2011 ESACODE Ver. 11.4 Telephone number: 0043 (0) 2236 / 45 355
Telefax number: 0043 (0) 2236 / 45 356
e-mail: MENHOFER.GmbH@vienna.at
INSTALLATION RULES

Protect the device against the direct exposure to the sun.

Avoid arranging the device in the proximity of or in direct contact with any source of heat and electromagnetic field. Connect the
device on supply line other than those used for motor drives or other devices that may cause some noise on the net.

Fix the device on the wall at minimum 60 cm from the floor.

For all input control signals to the Timer (D1a, D5, D6,...) use anti-flame wires with a minimum section of 0.25 mm².
Before acting on the device for any operation, check for safe conditions. For electrical operations never forget to power off, wait
30 seconds for the internal capacitor discharge before opening. At the end of the operations close the device to restore the
protection degree before powering on again.

For the electrical connection of the supply voltage and filter cleaning electrovalves use anti-flame wires with a minimum section
of 0.75 mm². For output relay contacts use anti-flame wires with a minimum section of 1.5 mm2.

For the output signal 4÷20 mA use anti-flame shielded wire with minimum section of 0,25 mm².

For the electrical connections use antiflame shielded cable 3 x 0,75 mm²

ATTENTION: with output voltage 230VAC we advice you to use connectors with RC filter or to insert it on every supply line of
any ev.

TECHNICAL FEATURES

Supply Voltage 230 VAC ± 5 % - 50/60 Hz


Output voltage: 24 VDC
Fuse 250 V / 1 A F (5x20)
Power requirement: 10 VA (Stand-by) - 30 VA ev. ON
Operating temperature: -10 ÷ + 50 °C
No. Outputs 16
dP Control With internal trasducer
Dimensions: / Protection degree ABS IP65 240x185x114 mm.
Terminal Boards 2,5 mm² 250 VAC / 12 A

A wrong supply voltage connection might cause irreparable damages to the device.

The fuse wire protect only from any short circuit and not necessarily from wrong supply voltage.

We reserve the right to make any change without notice


Pg. 2
ENTER DATA IN SET MODE

When supply voltage switch On the cleaning cycle starts if all the necessary conditions for running are
present.
Press key B to enter in SET MODE.
The upper line of the display shows the code and the description of the selected function and the line
below shows the referement code and the value of the fuction indicated (See table SET DATA).
Press key B to increase the number of the selected function.
Press key D to decrease the number of the selected function.
Press key A to increase the set value.
Press key C to decrease the set value.
Press key E to store the SET UP data and to enter in RUNNING MODE.
If for 5 minutes no key is pressed the device change automatically in RUN MODE.

A / C Increase - Decrease Value


E ESC / Reset
B / D Increase - Decrease Code

DISPLAY DESCRIPTION Range Rif. Default

00 LANGUAGE SEL. Display language selection SL


SL ENGLISH

01 DIGITAL INPUTS Enable / Disable digital inputs CO


C0 ACTIVATED

02 OPERATION Operation Mode selection Manul / Automatic C4a


C4a AUTOMATIC

03 PULSE TIME Activation time from 0.05 to 5.00 sec. 0.01÷5.00 B2x 1.00 sec
B3x 1 sec.

04 INTERVAL TIME Interval time between ev. from 1 to 999 sec. 001÷999 B3x 5 sec
B3x 005 sec.

05 POSTCL INT. Interval time between ev. during post-cleaning 001÷999 B3c 5 sec
B3c 005 sec.

06 POST CYCLES Additional cycles after fan stop 00÷99 D1x 5


D1x 002 cycles

07 ELECTROVAL.N. Selection Number of outputs / solenoid valves B1a


B1a 016 ev.

08 TEST EV. Manual activation of every single output from keyboard B10
B10 001 OFF

09 HOURS COUNTER Operation hour-counter 0÷65535 D14a


D14a 00000 hour

10 REG ZERO dP dP zero readout regulation C8 0.00


C8 0.00 kPa

11 FAN THRESHOLD dP threshold for cycle activation after fan stop 0.01÷0.99 D1bx 0.10
D1bx 0.10 kPa

12 MIN dP ALARM Minimum dP alarm threshold 0.01÷9.99 C7c1 OFF


C7d1 OFF kPa

13 dP STOP CYCLE 1st dP threshold, STOP washing since dP low 0.01÷9.99 C1a 1.00
C1a 1.00 kPa

14 dP START CYCLE 2nd dP threshold, START washing since dP high 0.01÷9.99 C1b 2.00
C1b 2.00 kPa

15 MAX dP ALARM Maximum dP alarm threshold. 0.01÷9.99 C7d1 3.00


C7d1 3.00 kPa

18 EV. VOLTAGE Output voltage setup for ev. (see HVB) (Necessary for right B operating of HV
HV Vout = 24 V B8b)
Pg. 3

40 SUPPL. CYCLE Waiting time for the activation of supplementary cycles 0÷99h59' C2d OFF
C2a 12h34'
INFO MODE

In run mode by pressing key D the device enter in INFO MODE. In this modality is avaliable a
description of keys function in SET UP and RUN MODE.
Press key B to go on in the informations visualization.
Press key E to exit and come back to RUN MODE.
If for 5 minutes no key is pressed the device change automatically in RUN MODE.

NOTE: When the device enter in INFO MODE the cleaning cycle stops. It restart from the beginning
when the device return in RUN MODE.

B Next
E Exit

DISPLAY DESCRIPTION

INFO B = NEXT Key use in INFO mode


E = EXIT

KEY FUNCTION
IN OPERATING

A=SCROLL ALARMS Key A = Display all active alarms in sequence


B=ENTER SET UP Key B = Enter in setup mode

C = VISUAL dP/TC Key C = Change display between dP and TC readout (OPTION)


D = INFO Key D = Enter in INFO mode

E = ALARMS RESET Key E = Reset alarms

KEYS FUNCTION
IN SETUP

A/C=INC/DEC DATA Keys A / C = Modify set up datas


B/D=INC/DEC CODE Keys B / D = Increment/decrement set up function

E = SET UP EXIT Key E = Exit Setup and store data

Pg. 4
RUNNING MODE

When supply voltage switch On the cleaning cycle starts if all the necessary conditions for running are
present.
The upper line of the display shows the differential pressure reading or TC signal reading depend on
the selection (option) and the type of operating mode (Manual / Automatic).
The line below shows a series of informations of the run status and the alarm situations active (See
table below / alarm description).
If no one key is pressed for 30 seconds the backlight brightness decrease, to ensure upper energy
safe and longer life of the display, up to a key is pressed again.

B Enter in SET UP
D Enter in INFO MODE
A Active alarm Scrolling
C Change visualization dP/TC (option)
E Alarm Reset

DISPLAY DESCRIPTION Rif.

dP = 9.99 kPa MAN Differential pressure readout C3


Manual running mode

TC = 010 mg/m³ AUTO TC Probe readout (Option on request) D11


Automatic running mode

START CONTACT Cycle stop since no remote start D6a


D6a OPEN

Cycle waiting for fan start or dP under set fan threshold D1x
VENTILATOR STOP

Activation output / solenoid valve 003


ACTIVAT. EV. 003

Waiting time before activation of the next ev.


WAITING=005 sec.

CYCLE STOP Cycle stop because differential pressure below 13 C1a


FOR dP LOW

Active cycles after fan stop D1x


POSTCLEANING ACT

Pg. 5
ALARMS DESCRIPTION

In run mode the lower line of the display shows the active alarm situations.
By pressing key A it is possible to scroll all the active alarms.
By pressing key E it is possible to reset the alarms.
The table below shows all the possible alarm situations. Some of these are related to particular
options on request and they are not present in Standard version.
The alarm visualization got the priority on other visualization on the 2nd line of the display.

A Alarms scrolling
E Alarms Reset

DISPLAY DESCRIPTION Rif.

E1 OVERLOAD Overload alarm - Solenoid velves 03 B8b


ELECTROVALVE 003

E2 ACT. FAILED Solenoid valve not activated - Solenoid valves 03 B9x/B6x


ELECTROVALVE 003

E6 COMPR. AIR Cycle stop since no consent from compressed air pressure switch D5a
LACK D5a OPEN

E7 ALARM Maximum dP alarm active. C7d


MAXIMUM dP dP reading over SET 15

E8 ALARM Minimum dP alarm active C7c


MINIMUN dP dP reading under SET 12

Pg. 6
STANDARD FEATURES

A1a MINIMUM AND MAXIMUM DP ALARMS ON ONE SINGLE RELAY (K2)


Minimum and maximum dP alarms act on the same relay. The display will specify the type of alarm.
A2a RELAY VOLTAGE ON (K1)
If the timer is supplied, relay K1 is activated and the terminal board contact is closed. In case of power failure, this contact is open.
B1b SELECT NUMBER OF OUTPUTS
Selection of the number of outputs connected by keyboard in set mode. If you set 0 or AUTO in this function the sequencer will automatically select
the connected loads and skip those not connected. If the load is below 5 W, autoselection does not work, set the number of outputs in set up.
B2x ACTIVATION TIME FROM 0.05 TO 5.00 SEC.
B3x INTERVAL TIME FROM 1 TO 999 SEC.
If the pulse time is lower than 1 sec. it is possible to set any interval time value in the range indicated.
If the activation time is higher than 1 sec. the minimum settable interval time is:
Minumum interval time = 5 times pulse time (B2x)
B3c INTERVAL TIME BETWEEN EV. DURING POST-CLEANING
Interval time between two activations settable by keyboard when post-cleaning cycles are active and during the forced cycles of option C2x if
available.
The selection range is the same as the inteval time in standard operation mode (B3x).
B8b SHORT-CIRCUIT PROTECTION OF EVERY SINGLE OUTPUT
In case of short-circuit, the corresponding output is automatically skipped. Relay K2 will signal the alarm condition and display will show the alarm
situation code E1 (See the alarm description).
Press key E to reset the alarm.
B10 MANUAL ACTIVATION OF EVERY SING OUTPUT FROM KEYBOARD
By the keyboard it is possible to manually and individually activate every single output for an operation test.
Press key A to select the output wished to activate. Press key C to activate the output.
C1 DIGITAL DIFFERENTIAL PRESSURE CONTROL (STOP AT CYCLE END)
In automatic running mode (C4a), the washing cycle is activated and deactivated according to the dP readout.
C1a Set the washing STOP threshold: if dP is below this threshold, the washing cycle stops and the display shows 'CYCLE STOP FOR LOW dP'. The
washing cycle stops at the end of the cycle (Set 13).
C1b Set the washing START threshold: if dP is above this threshold, the washing cycle is activated (Set 14)
C4 CLEANING CYCLE
If all the requirements for the start-up of the cleaning cycle are fulfilled when supply is powered on (e.g. fan on, external consents C6 or D5, dP
readout above the start threshold), the sequencer will automatically activate the EV outputs sequencially according to the times set by keyboard.

C4a AUTOMATIC OPERATION MODE


You can select the operation mode by keyboard in SET MODE. In automatic mode, the controls of the fan, the dP, C6 and D5 are active and the
activation of the cleaning cycle will depend on such functions.

C4b MANUAL OPERATION MODE


You can select the operation mode by keyboard in SET MODE. In manual mode, the control of the fan, the dP, C6 and D5 are not active.
C8 DP ZERO READOUT REGULATION
In this set up code it is possible to adjust the zero reading of differential pressure. In this function the display shows the dP reading and, with plant
stops or air pipes not connected if the dP reading is not 0.00 kPa it is possible to adjust it by key A and C.
C7c1 MINIMUM DP ALARM. ALARMED CONTACT OPEN. AUTOMATIC RESET.
If the dP readout is below the threshold in Set up, the minimum dP alarm is activated. The display shows the alarm condition code E8 (see the alarm
description) or the dP readout and letter L alternatively, according to the model.
The corresponding alarm relay will signal its condition. The alarm is automatically reset when the dP readout is above the threshold again.
If set to 'OFF' or 'E' (according to the model), the function is excluded.
NOTE: the minimum dP alarm is delayed by 60 seconds by default after the activation of the first washing cycle.
C7d1 MAXIMUM DP ALARM. ALARMED CONTACT OPEN. AUTOMATIC RESET.
If the dP readout is above the threshold in Set up, the maximum dP alarm is activated. The display shows the alarm condition code E7 (see the alarm
description) or the dP readout and letter H alternatively, according to the model.
The corresponding alarm relay will signal its condition. The alarm is automatically reset when the dP readout is below the alarm threshold again.
The activation of this alarm is delayed by 20 seconds by default.
C13_10 DP FULL RANGE 10KPA
Maximum differential pressure value measurable by the device 10.00 kPa = 100.0 mbar = 1012 mmH2O.
With dP reading over 10 kPa the display shows 'E' instead of the numeric value of dP.
D1b1 ADDITIONAL POST-WASHING CYCLES FROM DP READOUT. ACTIVATION AT STOP.
In automatic operation mode, you can add a pre-set number of cleaning cycles after the fan stop. Their number can be set from 0 to 99 by keyboard.
The sequencer will automatically recognise the fan state by comparing the dP readout with the threshold in set code 11: dP > set 11 = fan on, dP <
set 11 = fan off.
Post-cleaning cycles are activated even if dP = 0.
When the fan is off or dP < set 11, the display shows 'FAN STOP'.
The display shows 'POST-CLEANING ACT' during additional cycles and if there is no alarm.
Post-cleaning cycles are activated only if the dP readout should reach the threshold value of cycle STOP in normal operation mode.
D5a CONSENT FROM EXTERNAL COMPRESSED AIR PRESSURE SWITCH
If the operation mode is automatic and contact D5a is open, the cleaning cycle stops, relay K2 indicates the alarm situation. Close D5a to restart the
washing cycle from the point where it had stopped. If contact D5a is open, the display shows alarm code E6.
NOTE: Jump D5a if it is not used with active digital inputs.
D6a ON/OFF CLEANING CYCLE FROM EXTERNAL CONTACT
If contact D6a is open, the cleaning cycle is not enabled and the display shows 'START CONTACT D6a OPEN'.
Close D6a to start cleaning cycle from the first electrovalve.
NOTE D6a: Jump D6a if it is not used with inputs on.
D14a OPERATION HOUR-COUNTER
In SET MODE it is possible to visualize an hours counter. This counter is active when the cleaning cycle in On. In case of fan stop, consent D6 not
Pg. 7
present or with the device in SET MODE the counter stops.
DPa 6X4 RILSAN AIR CONNECTIONS
G1 MAXIMUM LOAD POWER 25W PER OUTPUT
HVB INPUT AND OUTPUT VOLTAGE SELECTION
Use the jumpers on the board to select the supply voltage and the output voltage for the electrovalves. (See the drawing of the printed circuit layout).
JP1: Select the supply voltage between 115VAC and 230VAC.
JP2: Select the output voltage between 24, 115, 230 V (Only when the power supply is 115VAC or 230VAC).
JP3: Select the output voltage between AC and DC only when JP2 is set to 24V.
ATTENTION: set the same output voltage you have selected by means of the jumpers to adjust the trip threshold of the short-circuit. Otherwise, the
sequencer might malfunction or be damaged.
SL MULTI LANGUAGE DISPLAY
In Set up it is possible to select the language of all the descriptions showed by the display.

Pg. 8
OPTIONS ON REQUEST

B9b ELECTRIC CONTROL OF OUTPUT ACTIVATION (TIMER WITH 16X2 LCD DISPLAY)
If a solenoid valve is not activated, the relay K2 indicate the alarm condition and the display shows the alarm condition code E2 (See alarm
description).
Press key 'E' to reset alarm condition.
ATTENTION: this function will be active only if the automatic selection of the load in set up is not selected.
The alarm switch on after 5 consecutive fails on the same output.
C1c DIGITAL DIFFERENTIAL PRESSURE CONTROL (INSTANTANEOUS STOP)
In automatic running mode (C4a), the cleaning cycle is activated and deactivated according to the dP readout.
C1c Set the cleaning STOP threshold: if dP is below this threshold, the cleaning cycle stops and the display shows 'CYCLE STOP FOR LOW dP'. The
cleaning cycle stops immediately and as soon as the start threshold is reached. The cycle will restart from the point of stop (Set 13).
C1b Set the cleaning START threshold: if dP is above this threshold, the cleaning cycle is activated (Set 14).
C2a ADDITIONAL CLEANING CYCLES AFTER A PRESET TIME
By keyboard it is possible to set a well-defined interval time (from 1 minute to 99 hours and 59 minutes), at the expiry of which a well-defined number
of set cleaning cycles are automatically activated.
Activation occurs if the sequencer stops because of low dP for the set time interval.
The display shows 'POST-CLEANING ACT' during these additional cycles.
This function is active only when the sequencer is in automatic operation mode.
By setting OFF in set up, option C2a is excluded.
C11a 4÷20 MA SIGNAL AT THE OUTPUT OF DP READOUT
4÷20 mA output signal corresponding to the dP reading.
The signal is active, supplied at 12VDC by the device, the maximun drived load is 450 Ohm. 4mA = dP reading 0.00 kPa, 20 mA = dP reading equal to
the full range requested.
If an external voltage is applied to C11a clamps the device will be damaged.
C7a2 MINIMUM DP ALARM. ALARMED CONTACT CLOSED. EVENT MEMORY
If the dP readout is below the threshold in Set Up, the minimum dP alarm is activated. The display shows the alarm condition code E8 (see the alarm
description) or the dP readout and letter L alternatively, according to the model.
The corresponding alarm relay will signal its condition. Press the alarm reset key to reset it.
If set to 'OFF' or 'E' (according to the model), the function is excluded.
NOTE: the minimum dP alarm is delayed by 60 seconds by default after the activation of the first washing cycle.
C7b2 MAXIMUM DP ALARM. ALARMED CONTACT CLOSED. EVENT MEMORY
If the dP readout is above the threshold in Set up, the maximum dP alarm is activated. The display shows the alarm condition code E7 (see the alarm
description) or the dP readout and letter H alternatively, according to the model.
The corresponding alarm relay will signal its condition. Press the alarm reset key to reset it.
The activation of this alarm is delayed by 20 seconds by default.
C13_5 DP FULL RANGE 5 KPA
Maximum differential pressure value measurable by the device 5.00 kPa = 50.0 mbar = 506 mmH2O. With dP reading over 5 kPa the display shows 'E'.
D1a3 ADDITIONAL CYCLES FROM VOLTFREE CONTACT. ALWAYS ENABLED.
By connecting an NO auxiliary contact of the circuit intended to drive the fan with the sequencer, it is possible to add a pre-set number of cleaning
cycles after the fan stop. Their number can be set from 0 to 99 by keyboard.
Post-cleaning cycles are activated even if dP = 0 or C6x open.
If contact D1a3 is open, the DS2 display shows 'FAN STOP'.
The display shows 'POST-CLEANING ACT' during additional cycles.
NOTE. Jump D1a3 clamps if it is not used with inputs enabled.
Kb3 PROTECTED MENU ACCESS
In set up function 50, by insert the right password, it is possible to enter in a protected set up to manage particoular parameters.
Contact the supplier to access to these parameters.

Pg. 9
Pg. 10
Pg. 11
ENCLOSURE TECHNICAL DATAS [7.1]

Material: ABS, polycarbonate Temperature: -20°C ÷ 60°C


Protection degree: IP 65 Colour: Light grey similar to RAL 7035
Inflammability: UL 94 HB

Pg. 12
PROBLEMS SOLUTION

DEFECT POSSIBLE CAUSE SOLUTION

Display OFF Protection fuse broken. Check the protection fuse on supply line.
Supply voltage. Verify that supply voltage is present and it agree with
supply volateg request for the device (clamps 1 and 2).

No output activation Output voltage. Verify that the output voltage of the Timer and the
Connection to the electrovalves. voltage of the electrovalves are the same. Check the
connection between Timer and electrovalves.

Wrong differential pressure reading. Pneumatic connection not free. Disconnect the 2 pipe to the Timer and verify that dP
Pipe damaged reading is 0.00 kPa. If it is OK check the pipe for air
connection from the device to the filter.

The cleaning cycle do not run in The memory of the microprocessor could be Switch off the supply voltage to the Timer. With key A
according to the set value. modified by external factor. hold down switch on supply voltage. With this operation
the default data are loaded in set up. Adjust the zero dP
reading and the other parameters as request.

WARRANTY

The warranty lasts 4 years. The company will replace any defective electronic component, exclusively at our laboratory,
unless otherwise agreed, upon the Company's prior consent.

WARRANTY EXCLUSION

The warranty is not valid in case of:


1) Tampering or unauthorized repairs.
2) Wrong use of the device, not in compliance with technical data.
3) Wrong electrical wiring.
4) Inobservance of the installation rules.
5) Use of the device, not in compliance with CE rules.
6) Atmospheric events (Lightning, electrostatic discharge), Overvoltage.

Pg. 13

You might also like