You are on page 1of 11

Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng...

Page 1 of 11

Power Systems Engineering

Per Unit System – Practice Problem


Solved For Easy Understanding Enter your email address to
subscribe to this blog and
receive notifications of new

posts by email.
Let’s understand the concept of per unit system by solving an example. In the
one-line diagram below, the impedance of various components in a power
Join 429 other subscribers
system, typically derived from their nameplates, are presented. The task now is

to normalize these values using a common base. Email Address

Subscribe

Try Google AdWords™


google.com/AdWords

Get $75 Worth of Advertising


When You Spend $25 With
AdWords

Figure 1: Oneline Diagram Of A Power System

Now that you have carefully examined the system and its parameters, the

equivalent impedance diagram for the above system would look something like Recent Posts Tags

the following.
Choosing Between

Resistor and Reactor

for Neutral Ground

Impedance

Power Cable Neutral

and System Grounding

Substation SCADA

System - Design Guide

Cable and Conduit Installation

in Substations - Best Practices

Substation Sub-

Surface Engineering:

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 2 of 11

An Overview of What a Geotech

Survey Reveals

Per Unit System -


Practice Problem

Solved For Easy

Understanding

Power Circuit Breaker

- Operation and
Control Scheme

What Do Symmetrical,

Asymmetrical,

Momentary,

Figure 2: Impedance Diagram Of A Power System Interrupting, Close &


Latch Ratings Mean?

Resistive impedance for most components have been ignored. Rotating machines
How to Pass the Power
have been replaced with a voltage source behind their internal reactance.
System PE exam
Capacitive effects between lines and to ground are ignored as well.
Power Cable Neutral

To obtain the new normalized per unit impedances, first we need to figure out and System Grounding

the base values (Sbase, Vbase, Zbase) in the power system. Following steps will

lead you through the process.

Step 1: Assume a system base


Assume a system wide of 100MVA. This is a random assumption and chosen
to make calculations easy when calculating the per unit impedances.

So,  = 100MVA

Step 2: Identify the voltage base


Voltage base in the system is determined by the transformer. For example, with
a 22/220kV voltage rating of T1 transformer, the  on the primary side of T1 is
22kV while the secondary side is 220kV. It does not matter what the voltage
rating of the other components are that are encompassed by the  zone.

See figure below for the voltage bases in the system.

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 3 of 11

Figure 3: Voltage Base In The Power System

Step 3: Calculate the base impedance

The base impedance is calculated using the following formula:

Ohms…………………………………………………………………..(1)

For T-Line 1:  = 484 Ohms

For T-Line 2:  = 121 Ohms

For 3-phase load:  = 1.21 Ohms

Step 4: Calculate the per unit impedance


The per unit impedance is calculated using the following formulas:

……………………………………………………………………………..(2)

……………………………….(3)

The voltage ratio in equation (3) is not equivalent to transformers voltage ratio.

It is the ratio of the transformer’s voltage rating on the primary or secondary


side to the system nominal voltage on the same side.

For T-line 1 using equation (2): = 0.1 pu

For T-line 2 using equation (2):  = 0.5 pu

For 3-Phase load:

Power Factor:

Thus,

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 4 of 11

= 1.1495+j1.53267 Ohms

Per unit impedance of 3-phase load using equation (2)= =

0.95+j1.2667 pu

For generator, the new per unit reactance using equation (3)

= 0.2 pu

For transformer T1:  = 0.2 pu

For transformer T2:  = 0.15 pu

For transformer T3:  = 0.16 pu

For transformer T4:  = 0.2 pu

For Motor, = 0.25 pu

The equivalent impedance network with all the impedances normalized to a

common system base and the appropriate voltage base is provided below.

Per Unit Impedance Diagram

Summary:

1. Assume a Sbase for the entire system.


2. The Vbase is defined by the transformer and any off-nominal tap setting it

may have.
3. Zbase is derived from the Sbase and Vbase.

4. The new per unit impedance is obtained by converting the old per unit
impedance on old base values to new ones. See equations (2) and (3).

*****

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 5 of 11

base values per unit per unit impedances per unit system per unit value Power
transformers

Please subscribe to this blog to receive informative articles. You may also like:

Book Review: Determine How To Symmetrical Choosing Between Mounting


Protective Relaying Load Two Paralleled Components - Resistor and Provisions for Pole
- Principles and Transformers Demystified Reactor for Neutral Mounted
Application by Two three phase Learning symmetrical Ground Impedance Transformers
Lewis Blackburn transformers with components can be Faults involving Pole mounted
and Thomas ... ratings shown below overwhelming if you ground produce high transformers for
It is hard to miss this are paralleled on consider its fault current station service in
book if you have their secondary mathematical aspect magnitude especially substations or to feed
been in the power side.Transformer No. only. It is time to step when the transformer residential or
industry for a while. 1 - 1000kVA, back and understand (s) neutral is solidly commercial buildings
You will find it on 4160V/480V, Z = this concept from ... grounded. The are fitted with
the ... 5.0%Transformer No. neutral ground circuit mounting lugs that
2 ... in the transformer are sized per ...
provides ...

32 Responses to Per Unit System – Practice Problem Solved


For Easy Understanding

IJAJ says:

what do you mean by….. s*-??

an says:

Can we find the short circuit current at each end?

samuel says:

A load of 50mw at 0.8 power factor lagging is taken from the 33kv.
( taking a base MVA of 100mva), calculate the terminal voltage of

the synchronous machine? (Please help me solve this question)


thanks

Nikhil says:

very useful thanks

alshaia says:

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 6 of 11

How can we determine the voltage on the bus 1

BRian says:

Do you know how to find the voltage at the bus?


Thanks

tahseen says:

Hi
how we can find the voltage in bus1 in PU and in volte

noa says:

tanks alot save me alot of stress

abi says:

. Obtain the per unit impedance(reactance) diagram of the power


system shown in the fig

G1 : 30MVA , 10.5KV, X?=1.6 ?

G2 : 15MVA , 6.6KV, X?=1.2 ?


G3 : 25MVA , 6.6KV, X?=0.56 ?

T1 (3 phase): 15MVA , 33/11KV , X= 15.2 ? per phase on the high

tension side
T2 (3 phase): 15MVA , 33/6.2KV , X= 16 ? per phase on the high

tension side

Transmission line : 20.5 ohm per phase


Load A : 15MW , 11KV , 0.9 p.f lagging

Load B : 40MW , 6.6KV , 0.85 p.f lagging


5

abi says:

how to convert ohms value to per unit value

Lee Taylor says:

Hi, great article – thanks very much! I have a similar problem to

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 7 of 11

solve but I am struggling with the Zact calculation. My inputs are


Vrated = 4.16kV, S = 2MVA <-36.87. Can you help?!

bhanu says:

awesome

kaushik vastarpara says:

its really bcoz by reading this my confusion abut selection of base


nd other is very clear…sommust read it frend /…thank u

Admin says:

@Pavan @Mike: That’s a typo. Correct values are now shown in

the calculations. Since the ratio of Vbase_old/Vbase_new is the

same, the end result, therefore, does not change. Appreciate the
feedback.

Pavan says:

This is really helpful. I didn’t really got it when reading through


this, but when I saw the below comment by Mike, it seems like a

question worth answering. However the content is really clear and

understandable. Keep up the good work!


Thanks,

mike says:

I don’t understand one part: When calculating Xtl2 you are using

(22/22) which is reflected from where? Vbase in T2 is 220 primary


and 11 secondary, so where does 22 come from?

The same for Xtl4.

mark says:

will the impedance or p.u impedance in each line will be like in


series? will the current for the PRIMARY AND SECONDARY of the

transformer now be equal??? how will i find the actual line current
for each line and for the whole system…

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 8 of 11

chris says:

A single phase ,350 kva, 1380v generator has an internal

impedance Zg of j6 ohms. The generator is used to supply a load of


250kva/440v at power factor 0.78 lagging. determine: the turns
ratio of the transfomer, the impedance per km if the line between

the generator and the transformer is 5km, the voltage regulation


of the system.
Using the ratings of the generator as base values determine the

generated per unit voltage that is required to produce a full load


current under short circuit condition.
CAN SOMEONE HELP ME WIT THESE CALCULATION PLZ!!!

Admin says:

Kam,

Once you have the impedance network, use the current division

rule to determine the current flowing each line. I am not sure I


understand “voltage at 3″, if bus 3 is faulted (3ph) then it is zero

otherwise it should be the same as nominal voltage as seen on the

secondary side of the transformer.


I will solve one for the currents in the future but for now, you will

have to learn how to reduce a circuit (using KVL and KCL) to

determine the currents.

kam says:

sorry but i didnt get my reply yet, so could you pls help me
out???????? thanks a lot

karthik says:

very well explained but could you pls show me how to calculate
voltage and current in both lines, will be very greatful , thanks a
lot……….

kam says:

It is really well explained but could you pls show me how to


calculate voltage at but 3 and current in both lines, will be very

greatful , thanks a lot

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems Eng... Page 9 of 11

manish says:

what if transformers are connected in star and delta connection?

Anayat says:

i am very new to Power side , so i really dont know abt all these

concepts , what we only have T1 and T2 , and all the rating given
are three phase line to line ? how we ll solve it then?

richa says:

very nicely explained….to the point and complete..thanks a lot

Sanket says:

VERY NICELY EXPLAINED THANK-YOU ………

I WILL VISIT WEBSITE AGAIN FOR FURTHER REFERENCES.

BABULS RAJ says:

Thank u so much…..after searching for a proper explanation for

the same in so many sites, i got it finally from your site. Clear

explanation with proper diagrams with multi colour…….very nice


…..

Admin says:

Nice catch. Fixed it. Thanks.

Renjith M says:

Commendable work. But there is a small error. The per-unit

system is the ratio of two quantities of the same units. Therefore


it is unitless. Well that is what I know. So accordingly we specify

the per-unit quatities as just ‘P.U’. So you need to remove the


‘Ohms’ from the text and insert ‘p.u’

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems E... Page 10 of 11

Alfredo says:

It was very useful, but it is short because is necessary to get the

complete solution, any way I liked.

Abdul Rauff says:

Very Good Info About PSA.Thanks Alot

Hilary says:

Protection engieering, i have been give the reactance as Xd’ to


calculate faults on a system do i convert to Xd” how do i do this

Leave a Reply

A R CH I V ES TA G C LO U D B O O K S O N MY SH ELF W ELCO M E T O P E G U RU

January 2013 AC system arc flash study arc Protective Relaying


base
flash test asymmetrical current
December 2012
values cable shield
September 2012 grounding direct buried conduits
direct transfer trip FACT
June 2012 NEC 2011 Handbook
generator swing Ground grid
May 2012 HVDC IEEE 1584 John Camara Juan

March 2012 L. Bala Lewis Blackburn Power System Analysis and


lockout relays modern power system
January 2012 Design
momentary rating NCEES Professional

November 2011 neutral


Engineering

grounding NFPA 70E


August 2011
OSHA 1910 Pass PE Exam
July 2011 permissive over reaching
June 2011 transfer trip per unit
system PE Sample Problems
May 2011
pilot relaying
April 2011 power blackout power flow power

March 2011 system Power


transformers PPE
September 2010
protective relaying
July 2010 short
reactive power support

circuit rating steady state


June 2010
stability substation conduit details

symmetrical
components symmetrical current
system frequency thermal limitation

transformers voltage drop


limitation Zia A. Yamayee

AB O UT CO N T ACT TE R MS & C O ND IT I O NS PR IV ACY PO L IC Y SI T E M A P

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014
Per Unit System - Practice Problem Solved For Easy Understanding | Power Systems E... Page 11 of 11

http://peguru.com/2011/06/per-unit-system-practice-problem-solved-for-easy-understandi... 10/10/2014

You might also like