You are on page 1of 16

HIT-HY 70

Hybrid Adhesive for Masonry

Flexible, strong and reliable.

Hilti. Outperform. Outlast.


Hilti Adhesive Anchor

Applications Flexible, strong and reliable.


• Retrofits of historic masonry HIT-HY 70 Masonry Adhesive
buildings, including seismic
retrofit of multi-wythe walls Anchoring System
• Sign, fence or awning attachment Life just got easier with one adhesive anchoring product to
to masonry wall or façade
solve all your masonry needs. The new Hilti HIT-HY 70 Masonry
• Façade tie-backs to masonry
structural wall Adhesive Anchoring System works in a variety of masonry base
• Scaffolding attachment to materials: grout-filled CMU, hollow CMU, solid brick, hollow
masonry structure brick, multi-wythe solid brick walls. The improved formula and
• Pipe, cable tray, fixture fastening
innovative composite sleeve design provides strong, reliable and
to masonry base material
easy to install fastenings.
Outperform and Outlast

• Cures in ~ 30 minutes at 70° F


providing quick installation times
to finish the job earlier
• Achieve various embedment
depths by combining mesh
sleeves to custom lengths

Technical Data HIT-HY 70


Product Hybrid Urethane Methacrylate
Base material temperature (grout-filled and hollow CMU) 23° F to 104° F (-5° C to 40° C)
Base material temperature 41° F to 104° F (5° C to 40° C)
(hollow brick, solid brick, and multi-wythe solid brick)
Diameter range 1/4" to 3/4"
Listings/Approvals • ICC-ES (International Code Council) - ESR for hollow masonry, grouted masonry and hollow brick (pending)
- ESR for Un-Reinforced Masonry (URM) (pending)
Package volume • Volume of HIT-HY 70 11.1 fl oz/330 ml foil pack is 20.1 in3
• Volume of HIT-HY 70 16.9 fl oz/500 ml foil pack is 30.5 in3

Composite Mesh Sleeves for Hollow Masonry and Brick Material


Actual Length
Description For use with: Qty Dia. (in) (in) Bit Dia. Item No.

Mesh sleeve HIT-SC 12x50 ① 1/4" dia. rods 20 0.47 1.97 1/2" 00375979
Mesh sleeve HIT-SC 12x85 ① 1/4" dia. rods 20 0.47 3.35 1/2" 00375980
Mesh sleeve HIT-SC 16x50 ① 5/16", 3/8" dia. rods and 5/16" HIT-IC rods 20 0.63 1.97 5/8" 00375981 ①
Mesh sleeve HIT-SC 16x85 ① 5/16", 3/8" dia. rods and 5/16" HIT-IC rods 20 0.63 3.35 5/8" 00375982
Mesh sleeve HIT-SC 18x50 ① 1/2" dia. rods 20 0.71 1.97 11/16" 00360485
Mesh sleeve HIT-SC 18x85 ① 1/2" dia. rods 20 0.71 3.35 11/16" 00360486

Mesh sleeve HIT-SC 22x50 ① 5/8” dia. rods, 3/8” and 1/2” HIT-IC rods 20 0.87 1.97 7/8" 00273662
Mesh sleeve HIT-SC 22x85 ① 5/8” dia. rods, 3/8” and 1/2” HIT-IC rods 10 0.87 3.35 7/8" 00284511
Mesh sleeve HIT-SC 26x125 ② 3/4" dia. rods 20 1.02 4.92 1" 00360487
Mesh sleeve HIT-SC 26x200 ② 3/4" dia. rods 20 1.02 7.87 1" 00360488

Internally Threaded Inserts for Hollow Masonry, Grouted Masonry and Brick Material
Bit Dia. Threads ③
Description For use with: Qty (in) per inch Item No.

Internally Threaded HIT-IC 5/16" x 2" In hollow material use with HIT-SC 16 x 50 10 5/8" 18 00047945
Internally Threaded HIT-IC 5/16" x 3-3/16" ③ In hollow material use with HIT-SC 16 x 85 10 5/8" 18 00047941
Internally Threaded HIT-IC 3/8" x 2" In hollow material use with HIT-SC 22 x 50 10 7/8" 16 00047946
Internally Threaded HIT-IC 3/8" x 3-3/16" ③ In hollow material use with HIT-SC 22 x 85 10 7/8" 16 00047942
Internally Threaded HIT-IC 1/2" x 2" In hollow material use with HIT-SC 22 x 50 10 7/8" 13 00047947
Internally Threaded HIT-IC 1/2" 3-3/16" ③ In hollow material use with HIT-SC 22 x 85 10 7/8" 13 00047943

2 Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12
Hilti Adhesive Anchor

HIT-HY 70 Hybrid Adhesive for Masonry Construction

1.1 Product Description 1.1 Product (for installation only in un-reinforced


Description masonry (URM), hollow CMU, and
1.2 Material Specifications
The Hilti HIT-HY 70 Adhesive Anchor hollow brick walls), and the HIT-HY 70
1.3 Technical Data System is used to anchor building Adhesive.

1.4 Installation Parameters components to light-, medium-, or Anchor elements: Steel all-threaded
normal-weight grout-filled CMU, hollow rods, steel internally threaded inserts,
(ungrouted) CMU, solid brick, hollow and combi inserts manufactured to meet
brick, and multi-wythe un-reinforced
Listings/Approvals the requirements and specifications as
(URM) solid brick masonry*. per Section 1.2.
ICC-ES (International Code Council)
ESR (ICC-ES AC58) Pending HIT-HY 70 is an injectable hybrid Plastic Mesh Screen Tubes: Screen
adhesive mortar consisting of urethane tubes (to be used in URM, hollow
ICC-ES (International Code Council)
methacrylate resin, hardener, cement CMU, or hollow brick masonry) are
ESR (ICC-ES AC60) Pending
and water. The resin and cement are manufactured in a cylindrical shape, with
separated from the hardener and water one end closed to prevent extrusion of
by means of a dual-cylinder foil pack adhesive. The end is closed, but not
attached to a manifold. Properties sealed, to allow the use/combination
of cured HIT-HY 70 Adhesive are of multiple screens for deeper
Independent Code
shown in Section 1.2. An injection embedments (URM). The screen tubes
Evaluation nozzle with an internal mixing element are manufactured with a mesh size,
IBC/IRC 2006, 2009 (ICC-ES AC58)
is attached to the manifold, and the length, and diameter as specified by the
IBC/IRC/IEBC 2006, 2009 (ICC-ES AC60) adhesive components are dispensed adhesive manufacturer.
through the injection nozzle to ensure
UBC/UCBC 1997 (ICC-ES AC60) * For clay tile, terracotta, and masonry outside the scope of
proper mixing of the separate adhesive this document, please contact Hilti Technical Services.
LEED : Credit 4.1-Low Emitting Materials
®
components. The injection nozzle may
be replaced to permit multiple uses of
the cartridges. Only injection tools and
static mixing nozzles as recommended
by the manufacturer’s printed installation
The Leadership in Energy and instructions (MPII) may be used.
Environmental Design (LEED) Green
Building Rating system is the nationally The Hilti HIT-HY 70 Adhesive Anchor
accepted benchmark for the design, Systems consists of steel all-threaded
construction, and operation of high rods, steel internally threaded inserts,
combi inserts, plastic-mesh screen tubes
performance green buildings.

Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12 3
Hilti Adhesive Anchor

1.2 Material Specifications

Material Properties for HIT-HY 70 — Cured Adhesive


Compressive Strength ASTM D 695/DIN 53454 7,252-10,153 psi 50-70 MPa
Modulus of elasticity (Compression test) ASTM D 790/DIN 53452 246,568 psi 1,700 MPa
Water Absorption ASTM D 570/DIN 53495 3-8 % 3-8 %
Electrical Resistance VDE/DIN 0303T3 4.2 · 1011 ohm/in. 1.065 · 1012 ohm/cm

Mechanical Properties

Material Specifications fy min. fu


ksi (MPa) ksi (MPa)
Standard HAS-E rod material meets the requirements of ISO 898 Class 5.8 58 (400) 72.5 (500)
High Strength or “Super HAS” rod material meets the requirements of ASTM A 193, Grade B7 105 (724) 125 (862)
Stainless HAS rod material meets the requirements of ASTM F 593 (AISI 304/316) Condition CW 65 (448) 100 (689)
3/8" to 5/8"
Stainless HAS rod material meets the requirements of ASTM F 593 (AISI 304/316) Condition CW 3/4" 45 (310) 85 (586)
Carbon Steel HIS-N Insert confirming to DIN 10277-3 54.4 (375) 66.7 (460)
Stainless Steel HIS-RN Insert conforming to DIN 10088-3 50.8 (350) 101.5 (700)
Carbon Steel HIT-IC Insert conforming to DIN 10277-3 54.4 (375) 66.7 (460)
HAS Super and HAS-E Standard Nut Material meets the requirements of SAE J995 Grade 5
HAS Stainless Steel Nut material meets the requirements of ASTM F 594
HAS-E Carbon Steel and Stainless Steel Washers meet dimensional requirements of ANSI B18.22.1 Type A Plain
HAS Stainless Steel Washers meet the requirements of AISI 304 or AISI 316 conforming to ASTM A 240
HAS Super and HAS-E Standard Washers meet the requirements of ASTM F 884, HV
All HAS-E and HAS Super Rods and HAS-E Standard, HIS-N inserts, nuts and washers are zinc plated to
ASTM B 633 SC 1
Note: Special Order steel rod material may vary from standard materials.

1.3 Technical Data

Allowable Tension and Shear Values for Threaded Rods Based on Steel Strength1, 2, 3

Anchor Tension lb (kN) Shear lb (kN)


Diameter ISO 898 ASTM F 593 CW ISO 898 ASTM F 593 CW
ASTM A193 B7 ASTM A193 B7
in. (mm) Class 5.8 (304/316) Class 5.8 (304/316)
1/4 (6.4) 1175 (5.2) 2025 (9.0) 1620 (7.2) 605 (2.7) 1040 (4.6) 835 (3.7)
5/16 (7.9) 1835 (8.2) 3160 (14.1) 2530 (11.3) 945 (4.2) 1630 (7.3) 1300 (5.8)
3/8 (9.5) 2640 (11.7) 4555 (20.3) 3645 (16.2) 1360 (6.1) 2345 (10.4) 1875 (8.3)
1/2 (12.7) 4700 (20.9) 8100 (36.0) 6480 (28.8) 2420 (10.8) 4170 (18.6) 3335 (14.8)
5/8 (15.9) 7340 (32.7) 12655 (56.3) 10125 (45.1) 3780 (16.8) 6520 (29.0) 5215 (23.2)
3/4 (19.1) 10570 (47.0) 18225 (81.1) 12390 (55.1) 5445 (24.2) 9390 (41.8) 6385 (28.4)
1 Allowable load used in the design must be the lesser of bond values and tabulated steel values.
2 The allowable tension and shear values for threaded rods to resist short term loads, such as wind or seismic, must be calculated in accordance with the appropriate IBC Sections.
3 Allowable steel loads are based on allowable tension and allowable shear stresses equal to 0.33 x Fu and 0.17 x Fu , respectively.

4 Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12
Hilti Adhesive Anchor

1.3 Technical Data

Allowable Tension Loads for Threaded Rods in the Face of


Grout-Filled Concrete Masonry Units1, 2, 7, 8, 9, 11, 12
Spacing4 Edge Distance5
Load @ ccr
Anchor Load Load
Embedment, and scr, Critical, Minimum, Critical, Minimum,
Diameter, Reduction Reduction
in. (mm)3 lb (kN) scr, smin, ccr, cmin,
in. (mm) Factor @ Factor @
in. (mm) in. (mm) in. (mm) in. (mm)
smin6 cmin6
3/8 (9.5) 3-3/8 (85.7) 1235 (5.5) 13.5 (342.9) 0.74 12 (304.8) 0.80
1/2 (12.7) 4-1/2 (114.3) 2030 (9.0) 18 (457.2) 0.74 20 (508) 0.76
4 (101.6) 4 (101.6)
5/8 (15.9) 5-5/8 (142.9) 2835 (12.6) 22.5 (571.5) 0.50 20 (508) 0.71
3/4 (19.1) 6-3/4 (171.5) 3805 (16.9) 27 (685.8) 0.50 20 (508) 0.66

Allowable Shear Loads for Threaded Rods in the Face of


Grout-Filled Concrete Masonry Units1, 2, 7, 8, 9, 10, 11, 12

Spacing4 Edge Distance5


Load Reduction Factor
Anchor Load @ ccr Load
Embedment, Critical, Minimum, Critical, Minimum, @ cmin6
Diameter, and scr, Reduction
in. (mm)3 scr, smin, ccr, cmin, Load Load
in. (mm) lb (kN)10 Factor @
in. (mm) in. (mm) in. (mm) in. (mm) Perpendicular Parallel
smin6
to Edge to Edge
3/8 (9.5) 3-3/8 (85.7) 850 (3.8) 13.5 (342.9) 1.00 12 (304.8) 0.88 1.00
1/2 (12.7) 4-1/2 (114.3) 1495 (6.7) 18 (457.2) 1.00 12 (304.8) 0.49 1.00
4 (101.6) 4 (101.6)
5/8 (15.9) 5-5/8 (142.9) 2613 (11.6) 22.5 (571.5) 0.50 20 (508) 0.40 0.78
3/4 (19.1) 6-3/4 (171.5) 4090 (18.2) 27 (685.8) 0.50 20 (508) 0.26 0.60
1 A  ll values are for anchors installed in fully grouted concrete masonry with minimum masonry prism strength of 1500 psi. Concrete masonry units shall be light-, medium-, or normal-weight
conforming to ASTM C 90. Allowable loads are computed using a safety factor of 5.
2 Anchors may be installed in any location in the face of the masonry wall (cell, web, joints). Anchors are limited to one per masonry cell.
3 Embedment depth is measured from the outside face of the concrete masonry unit.
4 The critical spacing, scr, is the anchor spacing where full load values in the Table may be used. The minimum spacing, smin, is the minimum anchor spacing for which values are available and
installation is recommended. Spacing is measured from the center of one anchor to the center of an adjacent anchor.
5 The critical edge distance, ccr, is the edge distance where full load values in the Table may be used. The minimum edge distance, cmin, is the minimum edge distance for which values are
available and installation is recommended. Edge distance is measured from the center of the anchor to the closest edge (figure 2).
6 Load reduction factors are multiplicative, both spacing and edge distance load reduction factors must be considered.
Load values for anchors installed at less than scr and ccr must be multiplied by the appropriate load reduction factor based on actual edge distance (c) or spacing (s).
7 Linear interpolation of load values between minimum spacing (smin) and critical spacing (scr) and between minimum edge distance (cmin) and critical edge distance (ccr) is permitted.
8 Concrete masonry thickness must be equal to or greater than 1.5 times the anchor embedment depth. EXCEPTION: the 5/8-inch- and the 3/4-inch-diameter anchors may be installed in
minimum nominally 8-inch-thick concrete masonry.
9 W  hen using the basic load combinations in accordance with IBC Section 1605.3.1, tabulated allowable loads must not be increased for seismic or wind loading. When using the alternative
basic load combinations in IBC Section 1605.3.2 that include seismic or wind loads, tabulated allowable loads may be increased by 33-1/3 percent, or the alternative basic load combinations
may be reduced by a factor of 0.75.
10 Allowable shear loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in Section 1.3.
11 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.
12 For combined loading: (Tapplied/Tallowable)n+(Vapplied/Vallowable)n ≤ 1
where n=5/3 for 3/8- and 1/2-inch diameters, and n=1 for 5/8- and 3/4-inch diameters.

Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12 5
Hilti Adhesive Anchor

1.3 Technical Data

Allowable Tension and Shear Loads for Threaded Rods in the Top of
Grout-Filled Concrete Masonry Units1, 2, 3, 4, 8

Shear Load, lb (kN) 7


Anchor Edge Minimum End Load
Embedment, Tension Load, Load Parallel
Diameter, Distance, Distance, Perpendicular
in. (mm) lb (kN) to Edge of
in. (mm) in. (mm)5, 6 in. (mm) to Edge of
Masonry Wall
Masonry Wall
1-3/4 (44.5) 1165 (5.2) 816 (3.6) 344 (1.5)
1/2 (12.7) 4-1/2 (114.3)
4 (101.6) 1625 (7.2) 1444 (6.4) 506 (2.3)
8 (203.2)
1-3/4 (44.5) 1165 (5.2) 1190 (5.3) 382 (1.7)
5/8 (15.9) 5-5/8 (142.9)
4 (101.6) 1745 (7.8) 1824 (8.1) 654 (2.9)
1 A  ll values are for anchors installed in fully grouted concrete masonry with minimum masonry prism strength of 1500 psi. Concrete masonry units shall be light-, medium-, or normal-weight
conforming to ASTM C 90. Allowable loads are computed using a safety factor of 5.
2 When using the basic load combinations in accordance with IBC Section 1605.3.1, tabulated allowable loads must not be increased for seismic or wind loading. When using the alternative
basic load combinations in IBC Section 1605.3.2 that include seismic or wind loads, tabulated allowable loads may be increased by 33-1/3 percent, or the alternative basic load combinations
may be reduced by a factor of 0.75.
3 One anchor shall be permitted to be installed in each CMU block.
4 Anchors are not permitted to be installed in a head joint, flange or web of the concrete masonry unit.
5 The tabulated edge distance is measured from the anchor centerline to the edge of the CMU block. (See Figure 3).
6 Linear interpolation of load values between the two tabulated edge distances is permitted.
7 Allowable shear loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in Section 1.3.
8 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.

6 Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12
Hilti Adhesive Anchor

1.3 Technical Data

Allowable Tension Loads for HIS-N inserts in the Face of


Grout-Filled Concrete Masonry Units1, 2, 7, 8, 9, 11,12

Spacing4 Edge Distance5


Anchor Load @ ccr Load Load
Embedment, Critical, Minimum, Minimum,
Diameter, and scr, Reduction Critical, ccr, Reduction
in. (mm)3 scr, smin, cmin,
in. (mm) lb (kN) Factor @ in. (mm) Factor @
in. (mm) in. (mm) in. (mm)
smin6 cmin6
3/8 (9.5) 4-3/8 (111) 2072 (9.2) 17 (431.8) 0.74 12 (304.8) 0.82
4 (101.6) 4 (101.6)
1/2 (12.7) 5 (127) 2708 (12.1) 20 (508) 0.74 20 (508) 0.63

Allowable Shear Loads for HIS-N inserts in the Face of


Grout-Filled Concrete Masonry Units1, 2, 7, 8, 9, 10, 11,12

Spacing4 Edge Distance5


Load Reduction Factor
Anchor Load @ ccr Load
Embedment, Critical, Minimum, Critical, Minimum, @ cmin6
Diameter, and scr, Reduction
in. (mm)3 scr, smin, ccr, cmin, Load Load
in. (mm) lb (kN)10 Factor @
in. (mm) in. (mm) in. (mm) in. (mm) Perpendicular Parallel
smin6
to Edge to Edge
3/8 (9.5) 4-3/8 (111) 1097 (4.9) 17 (431.8) 1.00 12 (304.8) 0.72 1.00
4 (101.6) 4 (101.6)
1/2 (12.7) 5 (127) 2063 (9.2) 20 (508) 1.00 20 (508) 0.40 0.87
1 A  ll values are for anchors installed in fully grouted concrete masonry with minimum masonry prism strength of 1500 psi. Concrete masonry units shall be light-, medium-, or normal-weight
conforming to ASTM C 90. Allowable loads are computed using a safety factor of 5.
2 Anchors may be installed in any location in the face of the masonry wall (cell, web, joints). Anchors are limited to one per masonry cell.
3 Embedment depth is measured from the outside face of the concrete masonry unit.
4 The critical spacing, scr, is the anchor spacing where full load values in the Table may be used. The minimum spacing, smin, is the minimum anchor spacing for which values are available and
installation is recommended. Spacing is measured from the center of one anchor to the center of an adjacent anchor.
5 The critical edge distance, ccr, is the edge distance where full load values in the Table may be used. The minimum edge distance, cmin, is the minimum edge distance for which values are
available and installation is recommended. Edge distance is measured from the center of the anchor to the closest edge (figure 2).
6 Load reduction factors are multiplicative, both spacing and edge distance load reduction factors must be considered.
Load values for anchors installed at less than scr and ccr must be multiplied by the appropriate load reduction factor based on actual edge distance (c) or spacing (s).
7 Linear interpolation of load values between minimum spacing (smin) and critical spacing (scr) and between minimum edge distance (cmin) and critical edge distance (ccr) is permitted.
8 C  oncrete masonry thickness must be equal to or greater than 1.5 times the anchor embedment depth.
9 W  hen using the basic load combinations in accordance with IBC Section 1605.3.1, tabulated allowable loads must not be increased for seismic or wind loading. When using the alternative
basic load combinations in IBC Section 1605.3.2 that include seismic or wind loads, tabulated allowable loads may be increased by 33-1/3 percent, or the alternative basic load combinations
may be reduced by a factor of 0.75.
10 Allowable shear loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in Section 1.3.
11 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.
12 For combined loading: (Tapplied/Tallowable)5/3+(Vapplied/Vallowable)5/3 ≤ 1

Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12 7
Hilti Adhesive Anchor

1.3 Technical Data

Allowable Tension and Shear Loads for Threaded Rods in the


Face of Hollow Concrete Masonry Units1, 3, 7, 9

Anchor Tension Minimum Edge Shear Load Edge Distance6


Embedment,
Diameter, Load, Distance, cmin, @ ccr, Critical, ccr, Minimum, cmin, Load Reduction
in. (mm)2
in. (mm) lb (kN)4, 5 in. (mm)6 lb (kN)4, 5, 8 in. (mm) in. (mm) Factor @ cmin
1/4 (6.4) 215 (1.0) 355 (1.6) 4 (101.6) 1.00
5/16 (7.9) 390 (1.7) 630 (2.8) 12 (304.8) 0.73
2 (50.8) 4 (101.6) 4 (101.6)
3/8 (9.5) 390 (1.7) 640 (2.8) 12 (304.8) 0.73
1/2 (12.7) 390 (1.7) 670 (3.0) 12 (304.8) 0.73

Allowable Tension and Shear Loads for HIT-IC Inserts in the


Face of Hollow Concrete Masonry Units1, 3, 7, 9

Shear Edge Distance6


Tension Minimum Edge
Anchor Diameter, Embedment, Load @
Load, Distance, cmin, Critical, ccr, Minimum, cmin, Load Reduction
in. (mm) in. (mm)2 ccr,
lb (kN)4, 5 in. (mm)6 in. (mm) in. (mm) Factor @ cmin
lb (kN) 4, 5, 8
#14 Screw (6.4) 190 (0.8) 235 (1.0) 4 (101.6) 1.00
5/16 (7.9) 415 (1.8) 600 (2.7) 12 (304.8) 0.80
2 (50.8) 4 (101.6) 4 (101.6)
3/8 (9.5) 480 (2.1) 620 (2.8) 12 (304.8) 0.78
1/2 (12.7) 495 (2.2) 620 (2.8) 12 (304.8) 0.75
1 A ll values are for anchors installed in hollow concrete masonry with minimum masonry prism strength of 1500 psi. Concrete masonry units shall be light-, medium-, normal-weight conforming to ASTM
C 90. Allowable loads are computed using a safety factor of 5.
2 Tabulated embedment depth is the length of the plastic HIT-SC screens.
3 Anchors shall be installed in the face of the hollow CMU masonry wall. A maximum of two anchors for each cell of the hollow CMU block is allowed.
4 Tabulated values are for one anchor installed in the center of the cell of the hollow CMU. Installation in other locations of the hollow CMU (mortar joints, flange or cell web) is not permitted.
5 Two anchors installed in the same cell or adjacent cells may be spaced as close as 4 inches apart without any load reduction.
6 T he critical edge distance, ccr, is the edge distance where full load values in the Table may be used. The minimum edge distance, cmin, is the minimum edge distance for which values are available and
installation is recommended. Edge distance is measured from the center of the anchor to the closest edge.
7 Anchors are not recognized for resisting earthquake forces. For short-term loading due to wind forces, the allowable loads shall not be increased.
8 Allowable shear loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in Section 1.3.
9 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.

8 Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12
Hilti Adhesive Anchor

1.3 Technical Data

Allowable Tension and Shear Loads for Threaded Rods in the


Face of Hollow Brick1, 3, 4, 7, 9

Minimum Edge Distance6


Anchor Shear Load
Embedment, Tension Load, Edge Load
Diameter, @ ccr, Minimum, Minimum,
in. (mm)2 lb (kN)5 Distance, cmin, Reduction
in. (mm) lb (kN)5, 8 ccr, in. (mm) cmin, in. (mm)
in. (mm) Factor
1/4 (6.4) 535 (2.4) 440 (2.0) 1.00
5/16 (7.9) 740 (3.3) 710 (3.2) 1.00
3-1/8 (79.4) 6-3/8 (162) 12 (304.8) 6-3/8 (162)
3/8 (9.5) 915 (4.1) 1080 (4.8) 0.88
1/2 (12.7) 915 (4.1) 1740 (7.7) 0.60

Allowable Tension and Shear Loads for HIT-IC Inserts in the


Face of Hollow Brick1, 3, 4, 7, 9

Minimum Edge Distance6


Anchor Shear Load
Embedment, Tension Load, Edge Load
Diameter, @ ccr, Minimum, Minimum,
in. (mm)2 lb (kN)5 Distance, cmin, Reduction
in. (mm) lb (kN)5, 8 ccr, in. (mm) cmin, in. (mm)
in. (mm) Factor
#14 Screw (6.4) 2 (50.8) 170 (0.8) 265 (1.2) 1.00
5/16 (7.9) 890 (4.0) 780 (3.5) 1.00
6-3/8 (162) 12 (304.8) 6-3/8 (162)
3/8 (9.5) 3-1/8 (79.4) 890 (4.0) 1330 (5.9) 0.73
1/2 (12.7) 1000 (4.4) 1840 (8.2) 0.54
1 A ll values are for anchors installed in hollow brick masonry with minimum masonry prism strength of 3,000 psi. Hollow brick units shall be conforming to ASTM C 652. Allowable loads are computed
using a safety factor of 5.
2 Tabulated embedment depth is limited by the length of the plastic HIT-SC screens.
3 Anchors shall be installed in the face of the hollow brick masonry wall.
4 Tabulated values are for one anchor installed in the center of the hollow brick. Installation in other locations of the hollow brick (mortar joints, flanges, or cell web) is not permitted.
5 One anchor shall be permitted to be installed in each brick. Two anchors may be spaced as close as the lesser of 2 bricks or 8 in. (203.2 mm) apart without any load reduction.
6 T he critical edge distance, ccr, is the edge distance where full load values in the table may be used. The minimum edge distance, cmin, is the minimum edge distance for which values are available and
installation is recommended. Edge distance is measured from the center of the anchor to the closest edge.
7 Anchors are not recognized for resisting earthquake forces. For short-term loading due to wind forces, the allowable loads shall not be increased.
8 Allowable shear loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in Section 1.3.
9 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.

Allowable Tension and Shear Loads for Threaded Rods in


Multi-Wythe Solid Brick Walls1, 3, 4, 5, 6

Anchor
Embedment, Tension Load, Shear Load, Minimum Edge Distance,
Diameter, Minimum Spacing, smin
in. (mm)2 lb (kN) lb (kN) cmin, in. (mm)
in. (mm)
6 (152.4) 895 (4.0) 680 (3.0)
3/8 (9.5)
10 (254) 1325 (5.9) 795 (3.5)
6 (152.4) 895 (4.0) 1075 (4.8)
1/2 (12.7) 16 (406.4)
10 (254) 1455 (6.5) 1115 (5.0)
or 2 complete bricks in any direction
6 (152.4) 1025 (4.6) 1405 (6.3)
5/8 (15.9) (whichever is greater)
10 (254) 1955 (8.7) 1445 (6.4)
8 (203.2) 1575 (7.0) 1985 (8.8)
3/4 (19.1)
13 (330.2) 2135 (9.5) 1985 (8.8)
1 All values are based on mortar shear strength of 45 psi or greater. Allowable loads are computed using a safety factor of 5.
2 Tabulated embedment depth is limited by the length of the plastic HIT-SC screens.
3 Anchors must be installed in the face of the multi-wythe URM wall. The wall must have a minimum thickness of 13 inches (3 wythes).
4 Tabulated values are for one anchor installed in the center of the brick of the multi-wythe URM wall.
5 T he minimum edge distance, cmin, and the minimum spacing, smin, are the minimum distances for which values are available and installation is recommended. Edge distance is measured from the center
of the anchor to the closest edge. Spacing is measured from the center of one anchor to the center of an adjacent anchor
6 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with Figure 1, as applicable.

Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12 9
Hilti Adhesive Anchor

1.3 Technical Data


23 – 32 -5 ... 0 10 min 6 h
Influence of base material temperature on work time, cure time, and
33on
– 41bond strength
1 ... 5 of Hilti HIT-HY
10 min 70 4 h
42 – 50 6 ... 10 7 min 2.5 h
51 – 68 11 ... 20 4 min 1.5 h
69 – 86 21 ... 30 2 min 30 min
Work and Cure Time Table (Approximate) Work
87and
– 104Cure Time
31 ... Table
40 (Approximate)
1 min 20 min

23 – 32 -5 ... 0 10 min 6 h 41 5 10 min 4 h


33 – 41 1 ... 5 10 min 4 h 42 – 50 6 ... 10 7 min 2.5 h
42 – 50 6 ... 10 7 min 2.5 h 51 – 68 11 ... 20 4 min 1.5 h
51 – 68 11 ... 20 4 min 1.5 h 69 – 86 21 ... 30 2 min 30 min
69 – 86 21 ... 30 2 min 30 min 87 – 104 31 ... 40 1 min 20 min
87 – 104 31 ... 40 1 min 20 min

41 5 10 min 4 h
42 – 50 6 ... 10 7 min 2.5 h
51 – 68 11 ... 20 4 min 1.5 h
69 – 86 21 ... 30 2 min 30 min
87 – 104 31 ... 40 1Figure
min 1 — Influence
20 min of Temperature on Bond Strength

10 Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12
Hilti Adhesive Anchor

1.3 Technical Data

Figure 2 — Allowable Anchor Installation Locations in the Face of Grout-Filled CMU (ASTM C 90)

Figure 3 — Edge and End Distances for Threaded Rods Installed in the Top of Grout-Filled CMU (ASTM C 90)

Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12 11
Hilti Adhesive Anchor

1.4 Installation Parameters

Hollow CMU and Clay Brick with Holes

Approximate number of trigger pulls Approximate number of trigger pulls

12 Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12
Hilti Adhesive Anchor

1.4 Installation Parameters

Grout-Filled CMU

Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12 13
Hilti Adhesive Anchor

1.4 Installation Parameters

Solid Brick

14 Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12
Hilti Adhesive Anchor

1.4 Installation Parameters

Multi-Wythe Wall

Hilti HIT-HY 70
Rebar

Rebar HIT-SC d0 [inch] h0 hef HIT-RB


[inch] [inch]
#4
#5 26x200 1 81⁄4 8 1
#6
Rebar HIT-SC d0 [mm] h0 hef HIT-RB
[mm] [mm]
Ø 12
Ø 16 26x200 26 210 20 28
Ø 20

16

Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca I HIT-HY 70 Submittal Information 01/12 15
Hilti. Outperform. Outlast.
P.O. Box 21148, Tulsa, OK 74121 • Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti
(Canada) Corp. 1-800-363-4458 www.hilti.ca • Hilti is an equal opportunity employer • Hilti is a registered trademark of Hilti, Corp.
©Copyright 2012 by Hilti, Inc. (U.S.) • H462 • 34889940 • 04/12 • DBS

The data contained in this literature was current as of the date of publication. Updates and changes may be made
based on later testing. If verification is needed that the data is still current, please contact the Hilti Technical
Support Specialists at 1-800-363-4458. All published load values contained in this literature represent the results
of testing by Hilti or test organizations. Local base materials were used. Because of variations in materials, on-site
*14001 US only
testing is necessary to determine performance at any specific site. Laser beams represented by red lines in this
publication. Printed in the United States