You are on page 1of 176

INTECONT® Tersus Weighfeeder

Instruction Manual

BV-H2463 GB
PASS - Service you can rely on
Fast, comprehensive, anywhere in the world

Quality and reliability are the cornerstones of our company’s


philosophy. That is why we consider a comprehensive service
concept simply par for the course, from strict quality control,
installation and commissioning through to seamless support
across the entire product life cycle.
With over 30 service stations and over 180 service specialists,
you can count on us to be there whenever – and wherever –
you need us.
It doesn’t matter where you are, our specialists are there to
advise and assist with the best in worldwide, personal, com-
prehensive service.

During office hours, service specialists from all divisions are


on hand to analyze problems and failures. Look at
www.schenckprocess.com for your nearest
Schenck Process Location.

Customized to meet your requirements, our comprehensive


Process Advanced Service System provides you with the best
service. Are you looking for individual, perfect-fit service solu-
tions?
Then our service system PASS is the ticket. It covers the en-
tire service spectrum, from simple inspections through to full
service. Interested?
Then find out more about the individual components at
www.schenckprocess.com/en/service.

© by Schenck Process GmbH


Pallaswiesenstraße 100, 64293 Darmstadt, Germany
Phone: +49 6151 1531-0
www.schenckprocess.com
All rights reserved. Any reproduction of this documentation,
regardless of method, without prior permission by
Schenck Process GmbH in writing, even by excerpt, is prohi-
bited.
Subject to change without prior notice.

Note: Translation of the original German Instruction


Table of Contents

Table of Contents

1 About This Manual ................................................................


................................................................................................
................................................................................................
.................................................................
................................. 1

2 Safety notes................................
notes................................................................
................................................................................................
................................................................................................
...........................................................................
........................................... 3
2.1 Signal Words .......................................................................................................................................... 5
2.1.1 Signal Words for Safety Warnings ................................................................................................. 5
2.1.2 Signal Words for Application Notes ............................................................................................... 5
2.2 Five Safety Rules of Electrical Engineering ........................................................................................... 6
2.3 Damaged / Defective Electrical Components ......................................................................................... 6

3 General Diagram ................................................................


................................................................................................
................................................................................................
...................................................................
................................... 7
3.1 An overview of the INTECONT Tersus .................................................................................................. 7
3.2 The basic diagram of the weighfeeder ................................................................................................... 8
3.3 Method of Function ................................................................................................................................. 9
3.4 Characteristics ......................................................................................................................................10

4 Operation................................................................
................................................................................................
................................................................................................
.............................................................................
............................................. 15
4.1 Quick guide ...........................................................................................................................................15
4.2 Function block.......................................................................................................................................17
4.3 Operating in Normal Operation.............................................................................................................18

5 Service Functions ................................................................


................................................................................................
................................................................................................
................................................................ 21
5.1 Display Test and Version Number ........................................................................................................21

6 Counter functions ................................................................


................................................................................................
................................................................................................
.................................................................
................................. 23

7 Mode functions ................................................................


................................................................................................
................................................................................................
....................................................................
.................................... 25
7.1 Types of operation ................................................................................................................................25
7.2 Keyboard operation ON/OFF................................................................................................................26
7.3 Prefeeder ..............................................................................................................................................26
7.4 Simulation .............................................................................................................................................27

8 Calibration
Calibration functions ................................................................
................................................................................................
............................................................................................
............................................................ 29
8.1 Starting the calibration functions ..........................................................................................................29
8.2 Pulse/Belt circuit LB .............................................................................................................................30
8.3 Tare TW ................................................................................................................................................31
8.4 Weight Check CW ................................................................................................................................33
8.5 Setting the Time ...................................................................................................................................35

9 Parameter functions ................................................................


................................................................................................
.............................................................................................
............................................................. 37
9.1 Read Parameters ................................................................................................................................37

10 Printer functions ................................................................


................................................................................................
................................................................................................
...................................................................
................................... 39
10.1 Status Report ........................................................................................................................................40

11 Batching functions ................................................................


................................................................................................
...............................................................................................
............................................................... 41
11.1 Batching mode ......................................................................................................................................41
11.2 Record the batch ..................................................................................................................................43

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group -i-
Table of Contents

12 Startup operation ................................................................


................................................................................................
................................................................................................
.................................................................
................................. 45
12.1 Weighing Platforms ..............................................................................................................................45
12.1.1 Effective Weighing Platform Length ............................................................................................45
12.1.2 Calibration Weight ........................................................................................................................47
12.1.3 Belt inclination .............................................................................................................................49
12.2 Parameter Input ....................................................................................................................................49
12.3 Function Check .....................................................................................................................................51
12.4 Test With Calibration Weight ................................................................................................................51
12.5 Belt Velocity Check ...............................................................................................................................52
12.6 Test with Material .................................................................................................................................52

13 Parameters ................................................................
................................................................................................
................................................................................................
..........................................................................
.......................................... 53
13.1 Abbreviations ........................................................................................................................................54
13.2 Configuring Event Messages................................................................................................................55
13.3 Parameter Listing ................................................................................................................................55
13.3.1 Parameter Overview ....................................................................................................................55
13.3.2 Parameter Details ........................................................................................................................65
13.3.2.1 Parameter Block 01 - Dialog Behaviour .......................................................................................65
13.3.2.2 Parameter Block 02 - Rated Data ................................................................................................69
13.3.2.3 Parameter Block 03 - Calibration Data ........................................................................................73
13.3.2.4 Parameter Block 04 - Calibrat. Results ........................................................................................74
13.3.2.5 Parameter Block 05 - Analog Outputs .........................................................................................74
13.3.2.6 Parameter Block 06 - Limit Values ...............................................................................................77
13.3.2.7 Parameter Block 07 - Filters.........................................................................................................80
13.3.2.8 Parameter Block 08 - Additional device .......................................................................................81
13.3.2.9 Parameter Block 09 - Batch Mode ...............................................................................................82
13.3.2.1 Parameter Block 10 - Printer Setting ...........................................................................................83
0
13.3.2.1 Parameter Block 11 - Maintenance interval .................................................................................84
1
13.3.2.1 Parameter Block 12 - Belt Monitoring ..........................................................................................85
2
13.3.2.1 Parameter Block 13 - Events .......................................................................................................88
3
13.3.2.1 Parameter Block 14 - Rate controller ...........................................................................................91
4
13.3.2.1 Parameter Block 15 - Linearization ..............................................................................................97
5
13.3.2.1 Parameter Block 16 - Digital Inputs .............................................................................................99
6
13.3.2.1 Parameter Block 17 - Digital Outputs .........................................................................................100
7
13.3.2.1 Parameter Block 18 - Communication EasyServe .....................................................................103
8
13.3.2.1 Parameter Block 19 - Communication Fieldbus.........................................................................104
9
13.3.2.2 Parameter Block 20 - Fixed mode configuration ........................................................................109
0
13.3.2.2 Parameter Block 21 - Ethernet ...................................................................................................111
1
13.3.2.2 Parameter Block 22 - Data Logging ...........................................................................................111
2
13.3.2.2 Parameter Block 23 - Configuration HMI Values .......................................................................114
3
13.3.2.2 Parameter Block 24 - Second Display .......................................................................................116
4
14 Event messages ................................................................
................................................................................................
................................................................................................
................................................................ 119

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- ii - Schenck Process Group
Table of Contents

15 Events ................................................................
................................................................................................
................................................................................................
...............................................................................
............................................... 121
15.1 Events Details .....................................................................................................................................121
15.1.1 Event Group: Calibration ............................................................................................................121
15.1.2 Event Group: Controller .............................................................................................................121
15.1.3 Event Group: Electrical System .................................................................................................122
15.1.4 Event Group: Interlock ...............................................................................................................122
15.1.5 Event Group: Material Flow........................................................................................................122
15.1.6 Event Group: MAX .....................................................................................................................123
15.1.7 Event Group: Mechanic ..............................................................................................................124
15.1.8 Event Group: MIN ......................................................................................................................124
15.1.9 Event Group: Sequence Monitoring ...........................................................................................125
15.1.10 Event Group: System Message .................................................................................................126

16 Hardware and technical data................................................................


................................................................................................
..............................................................................
.............................................. 129
16.1 Technical Data and Replacement Parts .............................................................................................129
16.2 Connection Diagrams .........................................................................................................................131
16.3 Replacing INTECONT PLUS with INTECONT Tersus .......................................................................133
16.4 PROFIBUS module (VPB8020) ..........................................................................................................136
16.5 DeviceNet Module (VCB8020) ..........................................................................................................138
16.6 Modbus Interface VSS8020................................................................................................................140
16.7 LED diagnosis.....................................................................................................................................141

17 Web server functions ................................................................


................................................................................................
.........................................................................................
......................................................... 143
17.1 Web Server .........................................................................................................................................143
17.2 System Information .............................................................................................................................143

18 Appendix ................................................................
................................................................................................
................................................................................................
...........................................................................
........................................... 145
18.1 Service Values ....................................................................................................................................145
18.2 Set option............................................................................................................................................146
18.3 Function Check ...................................................................................................................................147
18.4 Test Connector ...................................................................................................................................148
18.5 Sources of Setpoints and Switch Signals ...........................................................................................149
18.6 Regulation ..........................................................................................................................................151
18.7 Measuring at the Discharge Point VAP ..............................................................................................153
18.8 Belt Monitoring ....................................................................................................................................154
18.9 BIC belt impact compensation ............................................................................................................154
18.10 Linearization .......................................................................................................................................155

Index ................................................................
................................................................................................
................................................................................................
.................................................................................
................................................. 156

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - iii -
About This Manual

1 About This Manual

The operating manual for weighfeeders is intended for the service technician. It describes the functionali-
ty of the VWF 20650-xxx software.

This manual is available in different forms:


▪ A printed version
▪ An electronic document in the platform-independent ADOBE format (file ending: *.PDF)
▪ As online help in the Microsoft Windows HTMLHelp format (file ending: *.CHM)

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group -1-
Safety notes

2 Safety notes
To avoid personal injury and equipment damage, follow the safety regulations stated below.
Additionally, you should observe:
▪ Safety hints given in order-specific documentation
▪ Safety hints relating to mechanical components
▪ Instructions and safety tips for parts manufactured by sub-suppliers or that are not part of
Schenck Process's scope of delivery.
When performing installation, commissioning and service work, observe all applicable local regulations.

Intended Application
The measuring system and its connected mechanical components are exclusively designed for weighing and
controlling tasks. Any use other than originally intended is considered inappropriate.

Sources of Risk
If the measuring system has been correctly installed and commissioned, it does not pose any danger during
weigh operations.
Hazards may arise when the system is used for control operations or for transporting weighed goods. Poten-
tial hazards may then arise from e.g. additional devices through which the weighed goods are passed or
metered. Minor risks may arise in these situations if the measuring system is used or operated by untrained
personnel.
The measuring system can be part of a more complex plant. The system operating company is fully respon-
sible for the operating safety of the system.

Personnel
Preparation, assembly, commissioning, operation, maintenance and servicing may only be carried out by
qualified personnel.
All persons working on the system are required to observe the safety hints and know the parts of the tech-
nical documentation relevant to their work.
The operating company is responsible for instructing his operators to observe all regulations and instructions
given.

Changing Parameters
The measuring system's functionality is determined by parameters. Only personnel familiar with the device's
mode of operation may alter these parameters (e.g. after training by Schenck Process). Incorrectly set para-
meters may cause injury or material damage. Furthermore they may also cause considerable disruption to
weigh operations.

Password
Passwords safeguard the parameters against unauthorized alteration. The measuring system operating
company must ensure that the password is handled safely.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group -3-
Safety notes

Acknowledging Event Messages


Error messages may be acknowledged only after cause of fault has been remedied.
Ensure that any connected peripheral devices are functioning correctly before acknowledging an event. Any
connected control systems in particular must be in safe state.

Service and Maintenance


▪ All warning and instruction signs on the scales must be observed.
▪ The measuring system must be shut down before work is performed on mechanical equipment or peri-
pheral devices (control systems in particular). Take appropriate action to ensure that the measuring sys-
tem cannot be inadvertently restarted.
▪ Before performing work on the electrical equipment, disconnect the power supply.
▪ The devices may be operated only in the provided housings. There is danger of contacting live parts.

Moisture and Humidity


All scales parts, electrical components in particular, must be protected from moisture and humidity when the
housing is opened for e.g. maintenance and service. In other respects the protection classes of the housing
must be observed.

Design Modifications
Unauthorized modifications to the system and/or use of replacement parts not supplied by Schenck Process
voids Schenck Process's liability for any resulting damages. This especially applies to alterations which could
affect the operating safety of the system.

Replacing Components
Spare parts must meet the technical specifications indicated by Schenck Process. To ensure this require-
ment is met, only genuine Schenck Process spare parts should be used. When using other spare parts, the
warranty will be void.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


-4- Schenck Process Group
Safety notes

2.1 Signal Words

2.1.1 Signal Words for Safety Warnings


Warnings
Potential dangers will always exist when working with technical devices. Dangers will arise if the machine
▪ was incorrectly installed
▪ was incorrectly commissioned
▪ is operated by untrained personnel
▪ is repaired by not qualified personnel

The following signal words throughout this manual indicate dangers that may arise when handling this ma-
chine.

DANGER
This signal word indicates a danger that can immediately cause the
most severe injuries up to and including death.
Follow all instructions to prevent this from occurring.

WARNING
This signal word indicates a danger that can cause serious injuries up
to and including death.
Follow all instructions to prevent this from occurring.

CAUTION
This signal word indicates a danger that can cause slight or medium
injuries.
Follow all instructions to prevent this from occurring.

2.1.2 Signal Words for Application Notes

Signal words for information on material damages and on the optimal use of the machine

STRICTLY OBSERVE
Signal word used to identify situations in which material or environ-
mental damage could occur.
Follow all instructions to prevent this from occurring.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group -5-
Safety notes

HINT
Signal word used to identify information on using the product eco-
nomically and at an optimal level of efficiency.

2.2 Five Safety Rules of Electrical Engineering


Engineering

These fives safety rules must be followed in the order shown before commencing work on electrical systems.
Once the work is finished, they are to be applied in reverse order.

DANGER
Electric shock from live components
Danger of life from electric shocks
– Take all possible precautions to ensure safety before commencing work
on live components. Observe, among other things, the following.
1. Disconnect the components.
2. Secure them against inadvertent restart.
3. Ensure that the components have been de-energized.
4. Above 1 KV: Earth the cables and bypass them.
5. Cover or shield adjacent, live components.

2.3 Damaged / Defective Electrical Components

DANGER
Electrified damaged or defective components
There is a danger of life from an electric shock.
– Always have qualified personnel ensure that the components are neither
damaged nor defective.
1. Damaged or defective electrical components must immediately be re-
placed or, if possible, repaired by qualified personnel.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


-6- Schenck Process Group
General Diagram

3 General Diagram

3.1 An overview of the INTECONT Tersus

INTECONT Tersus is an extension of and improvement on the INTECONT system that has proven its worth
for years and has been used in more than 50,000 scales all over the world.

INTECONT Tersus is a measuring and measurement processing system of continuous weighing and feeding
equipment for
▪ weighfeeders
▪ conveyor belt scales
▪ differential feeding scales
▪ Coriolis mass flow equipment and
▪ solids flow equipment.

The basic hardware equipment is aligned to the needs of the application.


The following can be installed as optional equipment:
▪ fieldbus modules
▪ 230 VAC power supply
▪ module with additional analog outputs and analog inputs

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group -7-
General Diagram

3.2 The basic diagram of the weighfeeder

Fig. 1: The basic diagram of the ITE inputs and outputs

1 COUNTER Pulse output for connecting an external totalizing counter


2 ANALOG Analog output
3 SERIAL Serial interfaces for the printer or second display
4 24 V Supply voltage (VEG: 24 V; VKG: 85 - 230 V)
5 MOTOR Control output for belt drive
6 PREFEEDER Control output for a prefeeder
7 FULL "full feed“ relay output for batching
8 DRIBBLE "Dribble feed" relay output
9 MAX Relay output for maximum monitoring
10 MIN Relay output for minimum monitoring
11 FAULT Relay output for alarms
12 ON/OFF Switch-on/off of the scales and the totalizing
13 RELEASE Release signal for recording the total

LC Load cell for ascertaining the belt load


Belt speed Speed pick-up (tachometer)
Belt sensor Sensor for belt drift

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


-8- Schenck Process Group
General Diagram

3.3 Method of Function

A belt weigher or weighfeeder continuously weighs the quantity of material transported by a conveyor belt.
The feed rate is regulated on a weighfeeder according to a setpoint. A belt weigher only measures and it
cannot influence the feed rate.

Definitions

Q Belt load The weight of the material on a meter belt


V Speed The speed of the conveyor belt
I Feed rate The quantity of material transported by the conveyor belt per unit of time
Z Total Amount of material transported = Feed rate x feed time

Belt load Q and speed v are continuously measured and factored together. The result is the feed rate I, from
which the flow rate is determined.

Fig. 2: The belt load of the weighbridge is not legal for trade

The material is transported over a weighing platform located beneath the belt, limited by 2 carrying idlers.
The load on the platform exerts a force on the load cell LC through one or more weighing idlers. The mea-
suring displacement is approximately 0.2 mm. The measuring rolls are linked with the frame construction via
parallel plate springs. The load cell output voltage is proportional to the platform load. It is recorded with a
suitable measuring amplifier.
The load distribution on a single-roll weighbridge is shown by the white triangle. Only half of the force from
the weight of the material is passed into the measuring idler. The following conversion formula applies to the
effective bridge length with single-roll weighbridges:

Leff = Lg / 2 Leff = effective weighing platform length


Lg = total weighing platform length

Weighing platforms with more than one weighing idler will have a different factor than 1/2.
Therefore the belt load in kg/m totals:

QB = total load on the weighbridge.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group -9-
General Diagram

Belt speed
The belt speed is recorded using velocity sensor D and converted into a corresponding pulse frequency.

Feed rate
The readings Q and v are standardized in the unit to the physical quantities kg/m and m/s and multiplied with
one another. The product is feed rate I.

I in kg/s
Q in kg/m
v in m/s
QB in kg
Leff in m

I in kg/h

3.4 Characteristics

Readouts
The display of INTECONT Tersus consists of 4 parts:

1. You can give the technical name at the installation location in the header. A rotating symbol on the left
edge shows whether the weighfeeder is on or off.
2. The second line of the display is reserved for event information.
3. The following two lines show readings that can be selected with the cursor buttons. These lines cor-
respond to the lines of the INTECONT PLUS display.
4. The lower half of the display is used for various visualizations: the large-scale display of an individual
reading, the display of 4 readings in line font size or the display of as many as 9 readings that can be ad-
justed in the parameters block Configuration HMI Values. They adapt their font size over 3 levels.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 10 - Schenck Process Group
General Diagram

Event messages
▪ Events and malfunctions are shown by an alphanumerical shorthand symbol and title.
▪ The appropriate "uncoded text" for all subsequent events can be called up via the operating keyboard.
▪ It distinguishes alarms (red) and warnings that either have to be acknowledged (orange) or do not have
to be acknowledged (yellow). Alarms will shut down the scales, warnings will not. All alarms are also sig-
naled through a relay output.

Fig. 3: Display warning 2

Fig. 4: Display warning 1

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 11 -
General Diagram

Fig. 5: Display alarm

Operating philosophy
▪ Operator guidance through menus on several levels. Important configuration and calibration functions
are secured via a password.

Dialog language for fault messages, operation and service programs


▪ DEUTSCH, ENGLISH, FR-FRANCAIS, ES-ESPANOL, IT-ITALIANO, CN-CHINESE, JP-JAPANESE,
RU-RUSSIAN, HU-HUNGARIAN, NL-NETHERLAND at your choice or a loadable language (OTHER /
XX-NEW).

Dimensions
▪ SI units (Metric): kg, kg/h, t, t/h, m and cm
▪ NON SI units (English): lb, lb/h, t, t/h, f and inches

Turning recording the total or setpoint specification on or off


▪ This can be selected with the P02.06Feeder Start and P02.07Feedrate Setpoint parameters.

Monitoring for minimum and maximum limit values


▪ for feed rate, belt load and belt speed The limit values, relay outputs and event classes are separately
definable for all 6 possibilities.

Mains power failure


▪ Scales data, calibration data, counter readings and quantity pulses not yet issued remain saved for unli-
mited time after a mains power failure, and the time for approx. 5 days.

Belt speed
▪ The belt speed is recorded with a speed pick-up.

Zero setting
▪ The zero point fault of the belt weigher comes from soiling that adheres permanently or from other con-
stant factors. The zero setting records the zero point fault on an empty belt over one or several whole-
number belt circuits. This corrects the regular measurement in normal operation.
▪ Zero setting takes place with an empty belt conveyor with a program which runs automatically.
▪ Zero setting should be started manually at regular intervals if automatic operation is not preselected.
▪ The maximum permitted zero setting correction is monitored.

Zero drop out


▪ Suppression of the totalizing for measurements around zero, so that the counter remains constant during
no-load operation of the belt. The function can be turned off.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 12 - Schenck Process Group
General Diagram

Tare
▪ Taring is a calibration procedure in which the influence of the empty belt on the measuring signal, the
basic tare, is determined. After taring, the total remains unchanged over one belt circuit with the empty
belt. The call-up is protected by a password.

Measuring at dispatch: VAP


▪ For reasons of design, the weighing platform is not located directly at the material dispatch point. This
means that if the belt load changes, the measurement result for the feed rate will not accord precisely
with the current feed rate at the dispatch point. Measurement is relocated to the material dispatch point
using a special velocity-dependent delay element. No special measuring sensors are required to do this.

Batching mode
▪ Batch mode conveys a preset amount of material. The conveying process ends once the batch setpoint
has been reached. The batching process can be controlled via the belt conveyor drive or via the bin
feeder.
▪ The turn-off point and the utilization of "dribble feed" can be automatically adapted.

BIC belt influence compensation and belt drift


▪ This function makes it possible for the belt to record and compensate for dynamic zero point influence
with an additional belt circuit sensor and a metallic marking flag in the belt. This increases the scale's
short-term accuracy.

Display filters
▪ For feed rate, belt load and belt speed

Maintenance guidelines through the appearance of an event in the display


▪ For the voltage supply's operating time, for the scale's operating time and for the next zero setting.

Calibration
▪ Calibration of the pick-up input is not necessary. Certain design data on the load cells, velocity sensor,
inclination of the conveyor belt, etc. must be entered. From this data, the device calculates all required
standardizations for the displays. The control or readjustment can take place using two different me-
thods.
▪ Control with material: the result of a material inspection is entered into the device and serves to correct
the measurement result.
▪ Control with calibration weight: the standardization is controlled or, if the technical data (lever ratio, belt
conveyor inclination etc.) is not precisely known, it can be corrected.
In due course, the program also becomes suitable for the verification of mechanical changes, for exam-
ple twisting of the weighing platform due to movement of the foundations.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 13 -
Operation

4 Operation

4.1 Quick guide


Elements of the graphic display:

line 1: header rotating cross as a progress indicator. The scales are switched on; feed rate and flow
rate are being recorded. It only measures the belt load and belt speed when off (the
cross is stationary).
Ɖ : with activated batching mode
local designation of the feeder. This can be changed with EasyServe via parameters
P01.05.
line 2: event line event information with a code and plain text
upper display zone two lines of the actual value displays These lines correspond to the two lines of
INTECONT PLUS.

lower display zone Actual value displays that can be selected with buttons 0 - 9. The functions of buttons
4 - 7 depend on the application software and parameterization.

--- Totalizer 1 reading as per the parameter block


Configuration HMI Values

Batch Actual ValueLarge SetpointLarge ---


with bars with bars

FeedrateLarge Belt LoadLarge Belt SpeedLarge


with bars with bars with bars

reduce the brightness 4 readings with a bar display increase the brightness

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 15 -
Operation

operating elements:

SCROLL
▪ Preselect the data display of the upper line
▪ Select a group of parameters or one parameter

▪ Preselect the data display of the lower line


▪ Change to the right or left with number inputs

Numerical keys, signs and decimal points for entering parameters


Number buttons in basic position for selecting the actual value displays

DELETE Acknowledge event messages, delete inputs

START/STOP Switch-on/off are preselected

DATA Prepare the input, for instance changing the parame-


ters and inserting the setpoint

FUNCTION Call up the function block, then select the desired


function using the SCROLL keys
If an event is pending, the function "display Events"
has been preselected.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 16 - Schenck Process Group
Operation

ESCAPE Cancel a function or input and return to the actual


value displays.

ENTER Activate a function or confirm an input

4.2 Function block

The function block is the point of entry for everything to be performed on the device. All functions and dialogs
can be called up through it. The function block is two-staged.

Call up the function block


The previously selected function will be displayed if no event is pending.

Select the desired function of the first level. This space has a yellow
background.

Change to the second level. The selected space of the first level has an
orange background.

Select the desired function of the second level. This space has a yellow
background.

Select function. It only shows the functions that can be called up now.

Return to the normal display, or abort a function.

Change back to the first level.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 17 -
Operation

The functions of the 1st stage of the function block:

Setup
Totals
Mode
Calibration
Parameter
Printer Set-
ting
Batch

Configuration and parameter functions are only accessible via password. The password is queried once the
function has been called up.
Access to some functions can be configured in the Dialog Behaviour block. Entries might be missing de-
pending upon this setting.

The appearance on the unit:

Fig. 6: display – function block

4.3 Operating in Normal Operation

Turn on of the total measurement


Specified condition:
The external clearance signal has to be pending (selectable), P02.06 Feeder
Start has to be on OP or the keyboard mode has to be activated.

Turn off of total measurement

The feeder drive can be switched on and off with the keys in this field if the mode of operation and the para-
meterization permit it.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 18 - Schenck Process Group
Operation

WARNING
A start signal will actuate the motors.
There is the danger of injury if persons are in the area of the drives. Bulk
solids can be transported and cover the following equipment.
The turn-off command is not an emergency-off. Instead, it is provided for
operational shutdown.

Reset the totalizing counter


The function has to be activated with the P01.13 or P01.14 parameters.
Call up the function block

Totals
Reset Totalizer 1 or
Reset Totalizer 2

Select the function


Note: Totalizer 3 cannot be deleted.

Call up the zero setting program


Call up the function block

Calibration
>0< Zero Set

Acknowledge event information

Call up other functions such as showing event information, configuration and return from the function
block

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 19 -
Operation

Key in the setpoint

Key in the numerical value.

……
Acknowledge input.

This deletes the last symbol.

This interrupts the input.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 20 - Schenck Process Group
Service Functions

5 Service Functions

Display Events Setup


Display Check
Service Values /
Standard Values
Start Data Logging /
Stop Data Logging
Clear Data Log File

Service functions help get an overview of the status of the unit and the weighing system.

Display Events leads to a list of current upcoming events.

Service Values activates the display of other internal status information in the lower line of the display. This
line has a grey background. The return from this display takes place from Standard Values .

The other functions operate the routines set in the parameter block Data Logging.

5.1 Display Test and Version Number

This function performs a self-test on the display and the signal lamps.

Select function display check

Setup
Display Check
Overlay the software version number
Overlay the Schenck Process Logo
The test ends automatically

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 21 -
Counter functions

6 Counter functions

Reset Totalizer 1
Reset Totalizer 2 Totals
Totalizer Record

Counter 1 and counter 2 can be reset with these functions.


Counter 3 cannot be reset because it documents the total of materials conveyed.

The Totalizer Record function starts the counter print-out on a connected printer.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 23 -
Mode functions

7 Mode functions
There are functions brought together in the Mode menu for switching over into various operating modes.

Functions: Mode

Volumetric Mode
Volumetric Synchronous
Start Keyboard Mode / Mode
Stop Keyboard Mode
Stop Prefeeder /
Particip. Prefeeder
Start Simulation /
Stop Simulation
Gravimetric

7.1 Types of operation

You can change between these types of operation with the GravimetricVolumetric Mode and Volumetric
Synchronous functions.

Display:
V is shown in the header and status line and VOL is shown in the service values in volumetric operation. V is
shown in the header and status line and VOL-S is shown in the service values in volumetric synchronous
operation.
There is no separate status display in gravimetric operation, i.e. normal operation.

Characteristics:
All operation functions can be executed.
All control inputs and outputs work as set.

Gravimetric Operation:
The actual value for the feed rate is regulated to the specified setpoint.
The maximum possible setpoint equals the nominal feed rate. There is the message SC01 Event: Setpoint
Limited with larger inputs.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 25 -
Mode functions

Volumetric Operation:
The drive motor for the conveyor belt or material prefeeder is regulated proportional to the setpoint. The belt
load does not have any impact.
The feed rate approximately equals the specified setpoint under rated conditions. The setpoint is limited to
three times the nominal feed rate.
The calibration functions >0< Zero Set , TW: Tare , CW: Span Calibration and LB: Pulses/Belt can only be
called up in volumetric operation.

Volumetric synchronous operation:


In contrast to volumetric operation, it is not the rated belt load that is used for calculating the current target
belt speed. Instead, it is the current belt load before changing over. That means that changing over is jerk-
free.

7.2 Keyboard operation ON/OFF

The Start Keyboard Mode function can be used to put the preselected operating sources on the keyboard of
INTECONT for turning on/off and specifying the setpoint and target batching values.
Deselecting with Stop Keyboard Mode makes the old sources function again.
When changing from an external source (such as serial) to the keyboard, the on-off status and
the setpoints are retained. The external signals act in the opposite direction. It is still possible to see a prese-
lected external setpoint.

Display:
Keyboard operation is indicated by OP in the status line.

7.3 Prefeeder

The Particip. Prefeeder or Stop Prefeeder functions determine the impact of INTECONT on the prefeeder.
This function is activated in normal operation and INTECONT takes on controlling the prefeeder. The materi-
al flow is interrupted when it is off and the scale can be tared, etc.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 26 - Schenck Process Group
Mode functions

7.4 Simulation

In simulation mode, all functions of the scales without material can be tested during start-up. The scales are
not suited to normal operation during simulation.

Display:
SY14 Event: Simulation active event information
SIM is shown in the status line and service values.
This function can be turned off again with Stop Simulation in the same fashion.

Characteristics:
1. All operating functions can be carried out
2. The actual value for the feed rate is set to the setpoint adjusted.
3. The belt load and velocity measurement are active.
4. All control inputs and outputs work as adjusted.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 27 -
Calibration functions

8 Calibration functions

Functions: Calibration

>0< Zero Set


LB: Pulses/Belt
TW: Tare
CW: Span Calibration Calibration
Set Time

8.1 Starting the calibration functions

The 3 adjustment programs that provide basic and secondary calibration are available in this menu along
with the >0< Zero Set and Set Time functions.

The procedure is the same for all programs.

They have to be used in basic calibration in the order of LB, TW and CW.
All of them are protected from unintentional operation with a password. A total is not recorded during the
running term of a program until acknowledgement. Instead, analog outputs are set to the amount of lift and
event information is not shown.

Call up the function block

Calibration

Select the desired adjustment program LB, TW or CW

Key in password 7353

Afterwards it shows the dialog of the selected adjustment program.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 29 -
Calibration functions

8.2 Pulse/Belt circuit LB

The LB: Pulses/Belt adjustment program only has to be called up.


▪ At initial calibration
▪ when a new belt is mounted or the belt tension was substantially changed
▪ when one of the P02.04 Pulses per length or P02.05 Nominal Speed parameters was changed on scales
with or without speed measurement
The amount of impulses given by the velocity sensor for one belt circuit is calculated. Afterwards, the number
of impulses acts as a belt circuit identifier for the TW: Tare, CW: Span Calibration programs and zero setting.
This program should be called up at initial calibration as the first of all adjustment programs. This also ap-
plies to scales with no speed measurement.

Preconditions:
1. Measure the time for a belt circuit as precisely as possible and key in as theP03.02 Belt Circuit Time
parameters before calling up
2. The conveyor belt has to run
3. Volumetric
4. Switch off batch mode

Note: Belt conveyor drive and prefeeder are not controlled by the set-up program. The setup program will be
interrupted with a corresponding message if one of the preconditions is not met.

Sequence:

Call up the function block

Calibration
LB: Pulses/Belt

Abort possible at any time

While the program is running, the remaining seconds of the program running time and the impulses of the
velocity sensor added up are shown in the display.
LB: Calibration active is shown in the header.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 30 - Schenck Process Group
Calibration functions

After ending the program, the mean of the belt speed is shown in the display over the entire running term
along with the final result of impulses/belt circuit.
There is the request LB: wait for Confirmation in the header.

The results are accepted and filed in P04.06 Belt Circuit No. parameters.

The result is not taken over. Aborted ! is shown in the header.

The procedure is identical for models without velocity measurement.


Specific Messages:
Start ! when the belt is not running,
Volumetric ! when it is gravimetrically active

Note:
The program routine is slightly different if there is a P12.03 Belt Sensor Active belt sensor:
The new reading is shown for impulses/belt circuit after every belt circuit.
If the sensor is not correctly identified, it gives the Error Sensor message and the adjustment program is
cancelled.

8.3 Tare TW

The taring program uses one or several whole-number belt circuits to record the zero point fault of the weigh-
feeders. This value is used to correct the ongoing measuring results in normal operation. Taring and zero
setting must be differentiated.

Tare: Recording of the base tares (weight of mechanics, belt conveyor etc.) during com-
missioning, service and maintenance

Zero: Recording the operational zero deviation such as soiling


The maximum correction stroke of the zero setting program is limited; that of the tare program is not.
After taring, the zeroing program bases the permissible correction deviation on the new reference
value.

Preconditions :
1. Under no circumstances may there be any material on the belt. The prefeeder can be controlled with
Feeder ON/OFF function.
2. The mechanical equipment within the scales area must be cleaned. Deposits may remain that develop
again immediately in normal operation.
3. Switch off batch mode
4. The belt conveyor must be running. Notice is given automatically.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 31 -
Calibration functions

Sequence:

Call up the function block

Calibration
TW: Tare

Abort possible at any time

While the program is running, it shows the remaining running period in % of the entire running period and
the continually meaned tare in % of the rated belt load in the display.
TW: Calibration active is shown in the header

After ending the program, it shows how much tare departs from prior taring in % of the rated belt load and
the mean of the entire tare in % of the rated belt load in the display.
Dev = + : tare has increased
Dev = + : tare has decreased

The message TW: wait for Confirmation in the header reports the end of the program and requests user
input.

The result is accepted and stored in parameters P04.04 Basic Tare. At the same
time, P04.05 Tare Correction is set to zero.

The result is not adopted, the scales will not be tared.

Specific Messages:
Start ! when the belt is not running,
Volumetric ! when it is gravimetrically active

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 32 - Schenck Process Group
Calibration functions

NOTE
The tare may exceed 100 % by using the rated belt load as reference.

CAUTION
If the deviation 'Dev' is significant (>20 %), this may indicate a me-
chanical fault.
The weighing platform must then be checked for jammed material particles.

If BIC is active (P12.05 BIC Active = YES), the tare vectors of BIC are initialized with the taring program.

8.4 Weight Check CW

Using this program, the turndown of the device can be controlled. This is done by loading the weighing plat-
form with a known calibration weight and automatically calculating the average platform load over one or
several whole belt circuits. The result is compared to a predetermined reference value and then displayed.
No automatic correction is performed.
Suitable calibration weights are available as accessories.

Preconditions:
1. Tare or zero
2. Key in the calibration weight in P03.08 parameters. The calibration weight should be between 30 % and
100 % of the rated bridge load Qo.

Qo = qo * Leff qo = Nominal Belt Load, parameters P04.01


Leff = Effective Platform Length, parameters P03.05

1. Attach the calibration weight at the place provided.


2. Switch off batch mode
3. The scale has to run in volumetric operation. Notice is given automatically.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 33 -
Calibration functions

Sequence:

Function block

Calibration
CW: Span Calibration

Abort possible at any time

While program is running, the remaining running period is shown in the display in % of the total running
period along with the continual measuring result Set/Act.
CW: Calibration active is shown in the header.
After ending the program, the fictitiously conveyed quantity of material is shown in the display over the
running period along with the mean of KOR of the Set/Act over the entire running period.

The message TW: wait for Confirmation in the header reports the end of the program and requests user
input.

Exiting the program. Either button may be used AS THE RESULT IS NOT TAKEN
OVER AUTOMATICALLY.

Specific Messages:
Start ! when the belt is not running,
Volumetric ! when it is gravimetrically active
Aborted !

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 34 - Schenck Process Group
Calibration functions

NOTE
If no calibration weight is mounted, the zero point of the scales can be checked with this program.

Evaluating the results


Error < 1 % KOR = 0.99 ... 1.01
The scales condition is fine, no further measures are necessary.
Error < 5 % KOR = 0.95 ... 1.05
Enter the value KOR into parameters D 02. Of course, this is only effective if the
result of a material control has not yet been allowed for in the parameters.
Error > 5 % KOR < 0.95 or KOR > 1.05
Deviations of several percent indicate incorrectly entered technical data (e.g. un-
known exact belt incline, levers, etc.) or mechanical errors (alignment, tension).

The current value of the P04.02 Range Correction parameter is not taken into account in the check.
This is why the control program will show the same KOR fault quotients after correcting with the value input in
P04.02.

8.5 Setting the Time

The date and time are among the Service Values status information for the scale and
they can be changed at any time.

Call up the function block

Calibration
Set Time

Abort possible at any time

Enter the year, month, day, hour, minute and second.


Confirm each entry.
After the seconds have been entered and confirmed, the new time will be
accepted.

Then it shows the new setting for a couple of seconds as Current Time.
The internal clock will run for a further approx. 5 days in case of a mains failure.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 35 -
Parameter functions

9 Parameter functions

Functions: Parameter

Read Parameters
Enter Parameters
Print Parameters
Load Factory Defaults
Load Custom Defaults Parameter
Option activate

9.1 Read Parameters

Parameter are changeable characteristics or data with which the device can be adapted to its special weigh-
ing task.
You can find the meaning of the parameters in the detailed parameter description.
The input of parameters is protected by a password. They can inspected without any hazard with the Read
Parameters function. The parameters are broken down into functional blocks and numbered within a block.
Parameters are composed as follows:

Pxx.yy <Text>, where: xx: block number


yy: Number of the parameters in the block
<Text> Explanatory name of the parameters (language-dependent)

Depending on the situation, individual parameters or groups of parameters may be faded


out to highlight the parameters important to an application. Hidden parameters can only be
shown with the EasyServe service software and they can also be cleared there for the dis-
play on the unit wherever necessary. Fading out may result in breaks in the numbering.
Some parameters can be write protected. The write protection can also be configured using
EasyServe.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 37 -
Parameter functions

Reading parameters:

Call up the function block

Parameter
Read Parameters

Scrolling through parameter blocks 1, 2, …


and select the required block.

Scrolling through the parameters within a block

Return to the blocks

Return to normal display

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 38 - Schenck Process Group
Printer functions

10 Printer functions

Functions: Printer Setting

Totalizer Record
Print Parameters
Print Status Report
Batch Record

Printer Set-
ting

When printing with the Batch Record function, the Totalizer Record function adds the batch setpoint and
actual batch value to the print-out and Totalizer Printout is printed out as the heading.
The batch protocol can only be printed after completing the batch. The counter protocol is available at any
time.

The complete parameter list is printed out with the current readings using the Print Parameters function. All
inputs departing from the default readings are marked with an *. The list of all possible event messages and
the current hardware allocation is printed out as an appendix.
The printing procedure can be cancelled at any time.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 39 -
Printer functions

10.1 Status Report

The Print Status Report can be printed out at any time. It provides information on the events and configura-
tion results that have occurred to date, etc. The Service Values chapter explains the specific data in detail.
The printing procedure can be cancelled at any time.

Software version
Own Address EasyServe address information
IP Address Ethernet address information
OP Mode Status information
Simulation Mode
Feeder On
Volumetric Mode
Summary Alarm
Maintenance Electric Overall duty cycle of mains voltage.
Maintenance Feeder Run Overall duty cycle of the belt conveyor and the device.
Totalizer 1 The readings of the total counter
Totalizer 2
Totalizer 3
The events since Power ON The number and type of events from Power ON or since the last print-out ofPrint
Status Report.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 40 - Schenck Process Group
Batching functions

11 Batching functions

Functions: Batch

Select Batch / Deselect Batch


Batch Record
Abort Batch

Batch

11.1 Batching mode

A preselected quantity of material is dispatched in batching mode. When it reaches the batch setpoint, the
conveyor belt and material prefeeder are turned off and the feeding process is ended.

Display :
If Batch Mode is selected, the summation symbol Ɖ appears in the header.
Relevant data in the middle and lower display zone: Batch Setpoint, Batch Actual Value and Batch Residual
Amount.
Before starting a batch, Batch Actual Value and Batch Residual Amount show the amounts reached by the
previous batch. Deselecting Batch Mode means that the displays are no longer accessible, although they
appear again with the new preselection.
The display format corresponds to Counter 1 Unit.

Preselection batching mode


Preselecting the batching mode makes batching possible, although it does not initiate a batch.
The condition: scale OFF and the function is activated.

Call up the function block

Batch
Select Batch

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 41 -
Batching functions

Input the Batch Setpoint


The Batch Setpoint is queried automatically with preselection or it can be manually initiated after finishing a
batch (scale OFF).
No entry can be made if batch mode is deselected or if a batch is in process.
No input is possible if the Batch Setpoint is specified with the fieldbus (Batch Setpoint Source P09.07 = FB).

If Feedrate Setpoint P02.07 is on OP or keyboard mode is active, it first queries according to the
Setpoint of the Feedrate.

Skip the input.


The old Setpoint of the Feedrate is maintained. Then it automatically asks
for the Batch Setpoint Source.

Input the value


Acknowledge input.

Interrupt entry, continue with previous setpoint

Delete symbols incorrectly keyed in

Starting and interrupting

Start the batch and the conveying process begins

Interrupting a batch
The batch is continued with the next start command.

Deselect Batch
This function deselects batching mode, i.e. it is taken out of the active
scope of functions. The summation symbol disappears from the header and the batching values can no
longer be called up again. However, they will not be cleared.
Conditions: the batch is ended or cancelled via Abort Batch function (scale OFF).

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 42 - Schenck Process Group
Batching functions

Call up the function block

Batch
Deselect Batch

Batching mode can be re-activated with the Select Batch function and you can inspect the old batching val-
ues again.

Abort Batch
This function cancels a current batch and the conveying process is ended immediately.
Operation remains in batch mode
The next start command will begin a new batch; the previous batch will not be resumed.

Call up the function block

Batch
Abort Batch

11.2 Record the batch

Issuing the batching results on a printer.


The batch has to be ended or cancelled. This function is only available in batching mode.

It can be printed out with the Batch Record function or automatically after every finished batch (P09.06 Batch
Automatic Record = YES).

The printing procedure can be cancelled at any time.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 43 -
Startup operation

12 Startup operation

12.1 Weighing Platforms

12.1.1 Effective Weighing Platform Length

The effective weighing platform length "L" is an important value for calibration. It is determined by the design
of the weighing platform and can usually be found in the technical data sheets. However, it is always expe-
dient to measure the length manually and to enter the exact value as a parameter. The hatched area shows
the load distribution on the weighing platform.

Single-Idler Platform
The load on the weighing platform is conducted via a weighing idler into the load cell. This can be done by
means of a lever system or without levers by means of a parallel leaf-spring system.

In this case, L is computed as:

Multiple-Idler Platform
Several weighing idlers are combined into one mechanical unit, the measuring bridge.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 45 -
Startup operation

Buckled Platform
The weighing platform consists of two parts. The force is conducted centrally into the load cell. A split mea-
suring table can also be used in place of the weighing idlers.

Mounting for entire belt on one side only

Lg = Distance to the center of the material cone

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 46 - Schenck Process Group
Startup operation

12.1.2 Calibration Weight


The calibration weight simulates a certain belt load and serves to control the weighing system. It can have a
direct effect on the weighing platform or via a lever system. In parameters C 08, not the actual weight but the
weight affecting the weighing platform must be entered. The effective calibration weight QPRF is the weigh-
ing platform load in kg simulated by the calibration weight.

Single-
Single-Idler Platform

Parallel leaf-spring bearing


The calibration weight can theoretically be mounted at any point on the weighing plat-
form mechanical equipment. The effective load is always the applied weight QP.
QPRF = QP

Pivot joint bearing (e.g. crossed flexure strip)

tan(a)» 0.018 * a

Angle a = 0 : K = 0
Angle a = neg : K = neg

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 47 -
Startup operation

Multiple-
Multiple-Idler Platform

Entire platform supported on load cells


QPRF = QP

Pivot joint bearing


See Single-idler platform

Buckled Platform
The calibration weight usually has an effect in the center.
QPRF = QP

If the entire belt issupported on one side, the following applies

If the belts are inclined, the extension or shortening of the calibration lever corresponding to the single-idler
platform must be taken into account.

Chain Calibration Weights:


If a chain curtain is placed over the weighing platform area, the effective calibration weight then becomes the
total weight of the chain in the weighing area.
QPRF = n * Lg * s
n = Number of chains
Lg = Overall weighing platform length in m
s = Weight of chain per m in kg/m

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 48 - Schenck Process Group
Startup operation

12.1.3 Belt inclination


In certain cases, the belt inclination must be entered as a parameter. The mounting orientation of the load
cell is the decisive factor.

At right angles to the belt conveyor


The angle a must be entered as the parameters. The load acting on the load cell is N = Q - cos a.

Vertical
Vertical to the belt conveyor

0° must be entered as angle a. The full force Q acts on the load cells.

12.2 Parameter Input

A technical data sheet is part of the scope of delivery. It contains all important nominal and calibration data
acc. specification. We will therefore list only a few important pieces of information and some recommenda-
tions at this point. It makes sense to go through all of the parameters and consider the value entered.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 49 -
Startup operation

Parameter block Dialog Behaviour :


Dialog language, display units and availability or security of the function block functions. The parameters
values will be converted automatically if the dimensions are changed.

Parameter block Rated Data :


Pulses per length P02.04 is important to calibration.
The dimension data should be adapted to the Nominal Flow Rate. Flow Rate Units P02.01 resolution should
not be greater than 4 ... 5 decimals for a quiet display.
The output frequency should not be any more than 10 Hz if an external volumeter is connected.

Parameter block Calibration Data :


All calibration and evaluation data are important and must be entered exactly. Most of the details can be
found in the technical data sheets. The effective platform length and the inclination of the belt must be
measured on-site. The inclination of the belt may only be entered for systems in which the load cells are
arranged perpendicular to the belt. On vertically-installed load cells, the effective angle equals 0°.

The inclination of the belt can be determined easily using a spirit level and a measuring tape. It is advanta-
geous to measure multiple times and to take the mean value of these measurements (h1, h2, …) as the val-
ue 'h'.
-1
The Angle P03.07 angle is then a = tan (h/l)
For angle < 20°, a = 55 h/l applies

Parameter block Calibrat. Results :


No input is needed. P04.02 Range Correction should be on 1 at initial calibration. We recommend that once
you have entered the rated data you check whether the load cell becomes overloaded by the rated feed rate.

F = Qo * L * H * cos(a)
Qo Nominal Belt Load P04.01 kg/m
L Effective Platform Length P03.05 m
H Lever Ratio P03.06
a Angle P03.07 Degrees
F Force on the load cell kg

F should be less than or equal to the total of LC Rated Capacity P03.04. Otherwise, the load cells are too
small for the required Nominal Flow Rate.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 50 - Schenck Process Group
Startup operation

12.3 Function Check

1. Switch on the belt conveyor and scales. The switch-on process depends on the preselected Feeder
Start P02.06 source.
2. A rotating cross appears in the header as a progress indicator. If not, there is no clearance or the ON
button was not pressed.
3. Take any event messages which appear into account and remove the error.
4. Check the following:
Tachometer: The output frequency of the tachometer generator has to be less than 3,000 Hz with acti-
vated measurement. The value must approximately correspond to the information in the data sheet.
Load cell: The non-standardized initial value for the load cell amplifier may not be larger than 2.85 mV/V
even at nominal load of the weighing platform. It must change if the weighing platform is placed under
load (e.g. the calibration weight). If the value is too large, the load cell is overloaded. If the value is nega-
tive, the load cell may be wrongly connected.
The load cell load in percent, sourced from the sum of the load cell nominal capacities, should not be
larger than 100 % with nominal belt load.

12.4 Test With Calibration Weight

The test with a calibration weight makes sense because


1. mechanical or electrical faults are possible
2. calibration data can be unreliable (for instance, the leverage is not precisely known) and it is difficult to
measure the belt inclination
3. data may be incorrectly entered

The calibration weight should be between 30 % ... 100 % of the platform nominal load and be accurate.
1. Enter Calibration Weight P03.08.
On beltweighers with parallel leaf-spring guides, the effective calibration weight is the same as the actual
value. In other cases, the effective calibration weight can be taken from the data sheet, or can be calcu-
lated according to the chapter details/data flow images. The inclination of the conveyor belt has no effect
on the effective calibration weight.
2. Call up the CW: Span Calibration program.

Some Possible Causes of Fault:


Warping of the weighing platform, improper alignment, interferences in the load cell cable.
If you suspect any of these faults, repeat the check with a different weight.
Non-linearity is an indication of such faults, linear faults are more likely to be cause by incorrect data.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 51 -
Startup operation

12.5 Belt Velocity Check

The velocity sensor frequency generator can be actuated in a number of different ways.
1. with a frictional wheel on the lower carrying run of the belt or
2. with the shaft of the drive motor
In the first case, the value Pulses per length P02.04 depends on the exact diameter of the frictional wheel; in
the second case, it depends on the gear and looping factor of the belt. So the velocity measurement accura-
cy should be checked.
1. Establish the velocity of the conveyor belt using a stopwatch and a tape measure. Make several mea-
surements to be sure and then calculate the mean.
2. Read the speed display over the same period of time wherever feasible.
3. Compare these readings with one another and correct P02.04 wherever necessary. (new value = prior
value * speed measured/speed read)

This procedure can also be used to determine unknown characteristic values.


Check the space between the recording sensor and crown gear and reduce wherever necessary if there is a
known Pulses per length and large deviations.

12.6 Test with Material

Each test or calibration with calibration weights can only approximate the actual operating conditions. Scales
with highly accurate measurement can only be achieved by several measurements made using material and
a subsequent correction. It is corrected with Range Correction P04.02.
The following items must be observed:
1. The route from the weighing platform to the collecting point for the material must be clean
2. Any available diverters must not divert material.
3. If there are any feed screws or air slides between the weighing platform and the collection point, material
must be conveyed for approx. 1/2 hour before any inspection measurements are made. This will allow
the usual material build-ups to form on the conveying elements.
4. Dedusting must be set to a minimum
5. The containers or vehicles in which the material is transported onto a legal-for-trade scales must be
cleaned and re-weighed (tared) before each filling.

For example:
Old value of P04.02 = 1
A material quantity of 4.9 t is conveyed over a time period of 15 minutes. The count read on the unit is 5.0 t.

P04.02 (new) = 1 * 4.9/5.0 = 0.98

The calculated value should be keyed into P04.02.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 52 - Schenck Process Group
Parameters

13 Parameters
The INTECONT Tersus is adapted to each application by means of parameters. No special programing
knowledge is therefore necessary.

Fig. 7: Parameter sets

Parameter set Purpose Activation Preparation and Alteration


Active parameters set A summary of the effec- Always active via EasyServe or on the unit
tive parameters
Factory settings Complete parameters set Use EasyServe or the unit to Cannot be changed
Non-alterable basic set- copy into the active parame-
ting ter set

Backup set Pre-setting for a group of Use EasyServe or the unit to Only using EasyServe in
applications or a setting copy into the active parame- expert mode
stored during commission- ter set
ing

Tab. 1 : Using parameter sets

Note: Parameters not required for an application can be faded out or declared 'read only' using EasyServe in
expert mode. EasyServe compiles a list of visible parameters that form an integral part of the system docu-
mentation. They, together with this manual, make up the relevant documentation of the control system for an
application. The parameter list in the operating manual contains all of the parameters, regardless of their
actual use in an application.
In addition to the parameter set stored in the scales, we recommend that after commissioning you keep a
copy of the parameter set in a mass storage medium using EasyServe.
The parameters are sorted into blocks for purposes of clarity. The parameter can be explicitly identified by
means of its block and the number in the block in the corresponding version of the scales software:
P01.03: Parameter block 1, 3rd parameter

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 53 -
Parameters

Note: Each parameter also has a unique number (ID) with which it can be addressed over the serial inter-
face. This number can be seen as a Tooltip in EasyServe when passing over the parameter and can be out-
put in the parameter printout.
Gaps can appear between block numbers and parameters within the blocks.
In rare cases, the number of a parameter may change.

13.1 Abbreviations
Source Description

FB Fieldbus
OP Operating panel
DI Digital Input
DO Digital Output
AI Analog Inputs
AO Analog Outputs
Event Event The reaction to an event can be configured.
W1 Warning 1 (requires acknowledgement)
W2 Warning 2 (does not require acknowledgement)
ALARM Alarm
IGNORE Ignore: do not show any event message but switch the corresponding contact outputs
LC Load cell
I Feed rate
v Belt speed
VCU VCU 20100 system unit of DISOCONT Tersus
VHM The operator panel of DISOCONT Tersus
IT INTECONT Tersus

Tab. 2 : List of commonly used parameters-related abbreviations

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 54 - Schenck Process Group
Parameters

13.2 Configuring Event Messages


The system monitors a range of both of its own operation and the peripherals. The reaction to a recognized
deviation, that is to say an event, is set by parameters. The parameters are used to assign to each event a
class that will determine this reaction.
Event class Description Impact on Acknowledgement Color
feeding required

Alarm ALARM Stop feeding, scales are switched Yes Red


off
Cannot be switched on
Warning 1 W1 Feeder will continue to run Yes Orange
Warning 2 W2 Feeder will continue to run No Yellow
Only display as long as
the event is active
Ignore IG Feeder will continue to run - -

Tab. 3 : Event classes

Note: An external binary output channel that may have been assigned to an event is set, independent of the
event class.
A newly pending alarm or warning 1-class event will be shown on the operating panel blinking and in color.
The blinking stops when acknowledged. Acknowledged event messages are cleared from the display for
currently pending events when the event is no longer pending. Each event is stored with a time-stamp in the
internal memory for later analysis.

13.3 Parameter Listing

13.3.1 Parameter Overview


VWF20650-002 2491

01 - Dialog Behaviour
Number: Name Default Customer Sys ID
P01.01 [➙ 65] Language DEUTSCH 4224

P01.02 [➙ 65] Userdefined Text XX-NEW 5816

P01.03 [➙ 65] Font UMing 30 6244

P01.04 [➙ 65] Units Metric 4225

P01.05 [➙ 65] Scale Name INTECONT Tersus VWF 6238

P01.06 [➙ 65] Password 10000 4292

P01.07 [➙ 65] 2. Password 14389 4321

P01.08 [➙ 65] Feeder ON/OFF active 4280

P01.09 [➙ 65] Switch Grav./Vol. command active 4595

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 55 -
Parameters

P01.10 [➙ 65] Switch Keyboard-/Normal Mode active 4282

P01.11 [➙ 65] Batch control active 4283

P01.12 [➙ 65] >0: Zero ON/OFF active 4284

P01.13 [➙ 65] Reset Counter 1 active 4286

P01.14 [➙ 65] Reset Counter 2 active 4287

P01.15 [➙ 65] Data Log ON/OFF not active 4309

02 - Rated Data
Number: Name Default Customer Sys ID
P02.01 [➙ 69] Flow Rate Units ------ kg/h 4229

P02.02 [➙ 69] Nominal Flow Rate 10 t/h 4226

P02.03 [➙ 69] Speed Measurement DI 6144

P02.04 [➙ 69] Pulses per length 10000 I/m 4256

P02.05 [➙ 69] Nominal Speed 0.1 m/s 4227

P02.06 [➙ 69] Feeder Start OP 4241

P02.07 [➙ 69] Feedrate Setpoint OP 4242

P02.08 [➙ 69] Relative Setpoint NO 4247

P02.09 [➙ 69] WZ Active YES 6158

P02.10 [➙ 69] Counter 1 Unit ------- kg 4230

P02.11 [➙ 69] Pulse Length Total 0 ms 4231

P02.12 [➙ 69] Counter 2 Unit ------- t 4232

P02.13 [➙ 69] Counter 3 Unit ------- t 4233

P02.14 [➙ 69] DO: Pulse Counter n/a 4239

P02.15 [➙ 69] Totalizer Increment 10 kg 4254

P02.16 [➙ 69] Z1-Numberstep Automatic 4255

03 - Calibration Data
Number: Name Default Customer Sys ID
P03.01 [➙ 73] Belt Circuit No. 1 6145

P03.02 [➙ 73] Belt Circuit Time 30 s 4353

P03.03 [➙ 73] LC Characteristic Value 2 mV/V 4257

P03.04 [➙ 73] LC Rated Capacity 60 kg 4258

P03.05 [➙ 73] Effective Platform Length 0.5 m 4259

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 56 - Schenck Process Group
Parameters

P03.06 [➙ 73] Lever Ratio 1 4260

P03.07 [➙ 73] Angle 0 Grad 4261

P03.08 [➙ 73] Calibration Weight 10 kg 4354

04 - Calibrat. Results
Number: Name Default Customer Sys ID
P04.01 [➙ 74] Nominal Belt Load 27.78 kg/m 6146

P04.02 [➙ 74] Range Correction 1 4352

P04.03 [➙ 74] Total Tare 0 kg/m 6147

P04.04 [➙ 74] Basic Tare 0 kg/m 4355

P04.05 [➙ 74] Tare Correction 0 kg/m 4356

P04.06 [➙ 74] Belt Circuit No. 1000000 I/B 4357

05 - Analog Outputs
Number: Name Default Customer Sys ID
P05.01 [➙ 74] AO: Setpoint n/a 4385

P05.02 [➙ 74] Setpoint Offset 4 mA 4386

P05.03 [➙ 74] Setpoint Range 20 mA 4387

P05.04 [➙ 74] AO: Actual Flow Rate n/a 4388

P05.05 [➙ 74] Flow Rate Offset 4 mA 4389

P05.06 [➙ 74] Flow Rate Range 20 mA 4390

P05.07 [➙ 74] AO: Belt Load n/a 4391

P05.08 [➙ 74] Belt Load Offset 4 mA 4392

P05.09 [➙ 74] Belt Load Range 20 mA 4393

P05.10 [➙ 74] AO: Speed n/a 4394

P05.11 [➙ 74] Speed Offset 4 mA 4395

P05.12 [➙ 74] Speed Range 20 mA 4396

P05.13 [➙ 74] AO: Deviation n/a 4397

P05.14 [➙ 74] Deviation Offset 4 mA 4398

P05.15 [➙ 74] Deviation Range 20 mA 4399

P05.16 [➙ 74] AO: Motor Speed Control AO 4400

06 - Limit Values
Number: Name Default Customer Sys ID
P06.01 [➙ 77] Limit: Actual Flow Rate MIN 5 % Io 4337

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 57 -
Parameters

P06.02 [➙ 77] Event: Actual Flow Rate MIN W1 4338

P06.03 [➙ 77] Limit: Actual Flow Rate MAX 120 % Io 4339

P06.04 [➙ 77] Event: Actual Flow Rate MAX W1 4340

P06.05 [➙ 77] Limit: Belt Load MIN 60 % Q 4341

P06.06 [➙ 77] Event: Belt Load MIN W1 4342

P06.07 [➙ 77] Limit: Belt Load MAX 120 % Q 4343

P06.08 [➙ 77] Event: Belt Load MAX W1 4344

P06.09 [➙ 77] Limit: Speed MIN 5%V 4345

P06.10 [➙ 77] Event: Speed MIN W1 4346

P06.11 [➙ 77] Limit: Speed MAX 120 % V 4347

P06.12 [➙ 77] Event: Speed MAX W1 4348

P06.13 [➙ 77] Stand-By Limit Value 0 % Io 4290

P06.14 [➙ 77] Event: Stand-By W2 4289

07 - Filters
Number: Name Default Customer Sys ID
P07.01 [➙ 80] Filter: Actual Flow Rate 3s 4328

P07.02 [➙ 80] Filter: Actual Flow Rate analog 3s 4329

P07.03 [➙ 80] Filter: Belt Load 3s 4331

P07.04 [➙ 80] Filter: Belt Speed 3s 4332

P07.05 [➙ 80] LC Filter 1s 4334

P07.06 [➙ 80] Afterflow Totalizer 3s 4274

08 - Additional device
Number: Name Default Customer Sys ID
P08.01 [➙ 81] Zero Drop-Out Active NO 4679

P08.02 [➙ 81] Zero Drop-Out Limit 1%Q 4680

09 - Batch Mode
Number: Name Default Customer Sys ID
P09.01 [➙ 82] Pre-cut-off Amount 3s 6156

P09.02 [➙ 82] Correction Amount 0 kg 4451

P09.03 [➙ 82] Adaptation Factor 0.5 4452

P09.04 [➙ 82] Batch Tolerance 100000 kg 4458

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 58 - Schenck Process Group
Parameters

P09.05 [➙ 82] Event: Out of Tolerance W1 4459

P09.06 [➙ 82] Batch Automatic Record NO 4453

P09.07 [➙ 82] Batch Setpoint Source OP 4449

10 - Printer Setting
Number: Name Default Customer Sys ID
P10.01 [➙ 83] Baud rate 9600 4512

P10.02 [➙ 83] Print Event YES 6164

P10.03 [➙ 83] Print Page Length 72 4513

11 - Maintenance interval
Number: Name Default Customer Sys ID
P11.01 [➙ 84] Maintenance Electric 3000 h 4465

P11.02 [➙ 84] Event: Maint. Electric W1 4466

P11.03 [➙ 84] Maintenance Feeder Run 3000 h 4467

P11.04 [➙ 84] Event: Maint.Feeder Run W1 4468

12 - Belt Monitoring
Number: Name Default Customer Sys ID
P12.01 [➙ 85] VAP Active NO 4480

P12.02 [➙ 85] Platform Dis.Length 0 % LB 4482

P12.03 [➙ 85] Belt Sensor Active NO 4496

P12.04 [➙ 85] DI: Source Belt Sensor DI 4497

P12.05 [➙ 85] BIC Active NO 4498

P12.06 [➙ 85] Sensor Length 8.2 cm 4500

P12.07 [➙ 85] Sensor Width 12 cm 4501

P12.08 [➙ 85] Sensor Offset 0 cm 4502

P12.09 [➙ 85] Belt Drift 3 cm 4503

P12.10 [➙ 85] Event: Belt Drift W1 4504

P12.11 [➙ 85] Belt Skew 4 cm 4505

P12.12 [➙ 85] Event: Belt Skew A 4506

P12.13 [➙ 85] Slip Value 2 % LB 4507

P12.14 [➙ 85] Event: Slip W1 4508

P12.15 [➙ 85] DO: Belt Drift n/a 4509

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 59 -
Parameters

P12.16 [➙ 85] DO: Belt Skew n/a 4510

P12.17 [➙ 85] DO: Belt Slip n/a 4511

P12.18 [➙ 85] DI: BIC freeze n/a 4499

13 - Events
Number: Name Default Customer Sys ID
P13.01 [➙ 88] Event: Power Failure A 4297

P13.02 [➙ 88] Event: Memory A 4302

P13.03 [➙ 88] Event: Tachometer Input A 4291

P13.04 [➙ 88] Event: Namur Error Tacho A 6199

P13.05 [➙ 88] Event: Namur Error Belt W1 6200

P13.06 [➙ 88] Event: Error LC Input A 4293

P13.07 [➙ 88] Event: Run Disabled W1 4246

P13.08 [➙ 88] Event: LC Input > MAX A 4295

P13.09 [➙ 88] Event: LC Input < MIN A 4294

P13.10 [➙ 88] Event: Simulation active W2 6202

P13.11 [➙ 88] Event: Setpoint Limited W1 4296

P13.12 [➙ 88] Event: External Event 1 A 4417

P13.13 [➙ 88] Event: External Event 2 A 4430

P13.14 [➙ 88] Event: License Violation A 4303

14 - Rate controller
Number: Name Default Customer Sys ID
P14.01 [➙ 91] Optimize Controller STANDARD 4368

P14.02 [➙ 91] P-Component KP 0.04 mA/% 4369

P14.03 [➙ 91] I-Component TN 1s 4370

P14.04 [➙ 91] Filter: Deviation 3s 4333

P14.05 [➙ 91] Time Deviation 20 s 4298

P14.06 [➙ 91] Threshold Deviation 5% 4299

P14.07 [➙ 91] Factor Deviation 1 4320

P14.08 [➙ 91] Deviation abs. max. 100 % 6255

P14.09 [➙ 91] Event: Deviation W1 4300

P14.10 [➙ 91] Event: Controller Limited W1 4301

P14.11 [➙ 91] Lower Limit 0 mA 4371

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 60 - Schenck Process Group
Parameters

P14.12 [➙ 91] Upper Limit 20 mA 4372

P14.13 [➙ 91] Controller Magnitude Offset 0 mA 4373

P14.14 [➙ 91] Position at STOP 0 4374

P14.15 [➙ 91] Volumetric Start-Up 0 Circuits 4272

P14.16 [➙ 91] Volumetric Clearance 0 Circuits 4273

P14.17 [➙ 91] Setpoint Offset 0 mA 4244

P14.18 [➙ 91] Setpoint Range 20 mA 4243

P14.19 [➙ 91] Store NO 4376

P14.20 [➙ 91] Volumetric Mode Qconst 4377

P14.21 [➙ 91] Bypass 0 mA 4375

P14.22 [➙ 91] Setpoint Filter 1st Ord 0s 4378

P14.23 [➙ 91] Setpoint Filter 2nd Ord 0s 4379

P14.24 [➙ 91] Set/Act Sources I 4381

P14.25 [➙ 91] Adaptation 1 NO 4382

15 - Linearization
Number: Name Default Customer Sys ID
P15.01 [➙ 97] Linearization ON NO 4577

P15.02 [➙ 97] Linearization S1 25 % Q 4681

P15.03 [➙ 97] Linearization I1 25 % Q 4579

P15.04 [➙ 97] Linearization S2 50 % Q 4682

P15.05 [➙ 97] Linearization I2 50 % Q 4581

P15.06 [➙ 97] Linearization S3 75 % Q 4683

P15.07 [➙ 97] Linearization I3 75 % Q 4583

P15.08 [➙ 97] Linearization S4 100 % Q 4684

P15.09 [➙ 97] Linearization I4 100 % Q 4585

P15.10 [➙ 97] Event: Linearization Error W2 4586

16 - Digital Inputs
Number: Name Default Customer Sys ID
P16.01 [➙ 99] Source Run Enable DI 4245

P16.02 [➙ 99] DI: Batch Terminate n/a 4454

P16.03 [➙ 99] DI: Acknowledge Events DI 4419

P16.04 [➙ 99] DI: Volumetric Mode n/a 4421

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 61 -
Parameters

P16.05 [➙ 99] DI: Volumetric synchron n/a 4941

P16.06 [➙ 99] DI: Start n/a 6207

P16.07 [➙ 99] DI: External Event 1 n/a 4418

P16.08 [➙ 99] DI: External Event 2 n/a 4431

17 - Digital Outputs
Number: Name Default Customer Sys ID
P17.01 [➙ 100] DO: ALARM DO 4436

P17.02 [➙ 100] DO: Start Prefeeder DO 4435

P17.03 [➙ 100] DO: Scale Start DO 4433

P17.04 [➙ 100] DO: Actual Flow Rate MIN DO 4438

P17.05 [➙ 100] DO: Actual Flow Rate MAX DO 4439

P17.06 [➙ 100] DO: Belt load MIN n/a 4440

P17.07 [➙ 100] DO: Belt Load MAX n/a 4441

P17.08 [➙ 100] DO: Speed MIN n/a 4442

P17.09 [➙ 100] DO: Speed MAX n/a 4443

P17.10 [➙ 100] DO: Batch Running n/a 4455

P17.11 [➙ 100] DO: Full Feed n/a 4457

P17.12 [➙ 100] DO: Dribble Feed n/a 4456

P17.13 [➙ 100] DO: Feeder Started DO 4434

P17.14 [➙ 100] DO: Deviation DO 4437

P17.15 [➙ 100] DO: Volumetric Mode n/a 4444

P17.16 [➙ 100] DO: Keyboard Mode n/a 4462

18 - Communication EasyServe
Number: Name Default Customer Sys ID
P18.01 [➙ 103] Own Address 1 4520

P18.02 [➙ 103] Baud Rate 38400 4521

P18.03 [➙ 103] Format Data 8-N-1 6189

19 - Communication Fieldbus
Number: Name Default Customer Sys ID
P19.01 [➙ 104] Protocol Type NO 4528

P19.02 [➙ 104] Timeout Host 5s 4529

P19.03 [➙ 104] Event: Cyclic Communication A 4530

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 62 - Schenck Process Group
Parameters

P19.04 [➙ 104] Event: Acyclic Communication A 5680

P19.05 [➙ 104] Check in Keyboard Mode YES 6234

P19.06 [➙ 104] Compatibility DISOCONT Master NO 6287

P19.07 [➙ 104] Word Sequence I:std/L:std 6246

P19.08 [➙ 104] Byte Sequence High - Low 6245

P19.09 [➙ 104] Configuration FIXED_8_8 4661

P19.10 [➙ 104] Address 1 4531

P19.11 [➙ 104] Resolution 4096 4533

P19.12 [➙ 104] Baud rate 19200 4535

P19.13 [➙ 104] Data Format 8-O-1 4656

P19.14 [➙ 104] Physics RS232 6186

P19.15 [➙ 104] Address 16 4539

P19.16 [➙ 104] FLOAT-Format IEEE 4540

P19.17 [➙ 104] Compatiblity INTECONT NO 4788

P19.18 [➙ 104] Identifier format BYTE 6190

P19.19 [➙ 104] PA32 compatible NO 4660

P19.20 [➙ 104] Address 63 4541

P19.21 [➙ 104] Baud rate 125K 4542

P19.22 [➙ 104] Access Rights Limitation FB NO 4786

P19.23 [➙ 104] Remote IP Address FB 192.168.240.250 4787

20 - Fixed mode configuration


Number: Name Default Customer Sys ID
P20.01 [➙ 109] ID Preset Value 1 320 6247

P20.02 [➙ 109] ID Preset Value 2 352 6248

P20.03 [➙ 109] ID Preset Value 3 384 6249

P20.04 [➙ 109] ID Preset Value 4 592 6250

P20.05 [➙ 109] ID Preset Value 5 594 6251

P20.06 [➙ 109] ID Preset Value 6 0 6252

P20.07 [➙ 109] ID Preset Value 7 0 6253

P20.08 [➙ 109] ID Preset Value 8 0 6254

P20.09 [➙ 109] ID Read Value 1 752 6256

P20.10 [➙ 109] ID Read Value 2 784 6257

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 63 -
Parameters

P20.11 [➙ 109] ID Read Value 3 1552 6258

P20.12 [➙ 109] ID Read Value 4 1872 6259

P20.13 [➙ 109] ID Read Value 5 1874 6260

P20.14 [➙ 109] ID Read Value 6 1880 6261

P20.15 [➙ 109] ID Read Value 7 1884 6262

P20.16 [➙ 109] ID Read Value 8 1894 6263

21 - Ethernet
Number: Name Default Customer Sys ID
P21.01 [➙ 111] IP Address 192.168.240.1 6235

P21.02 [➙ 111] Net Mask 255.255.255.0 6236

P21.03 [➙ 111] Gateway 0.0.0.0 6237

22 - Data Logging
Number: Name Default Customer Sys ID
P22.01 [➙ 111] Hourly Total Time 0 min 5743

P22.02 [➙ 111] Daily Total Time 0 min 5744

P22.03 [➙ 111] Logger cycle time 1 min 6288

P22.04 [➙ 111] Data Log Value 1 752 6289

P22.05 [➙ 111] Data Log Value 2 755 6290

P22.06 [➙ 111] Data Log Value 3 1872 6291

P22.07 [➙ 111] Data Log Value 4 1874 6292

P22.08 [➙ 111] Data Log Value 5 1876 6293

P22.09 [➙ 111] Data Log Value 6 1880 6294

P22.10 [➙ 111] Data Log Value 7 1884 6295

P22.11 [➙ 111] Data Log Value 8 1894 6296

P22.12 [➙ 111] Data Log Value 9 0 6297

P22.13 [➙ 111] Data Log Value 10 0 6298

23 - Configuration HMI Values


Number: Name Default Customer Sys ID
P23.01 [➙ 114] HMI Value 01 1996 6299

P23.02 [➙ 114] HMI Value 02 1944 6300

P23.03 [➙ 114] HMI Value 03 1942 6301

P23.04 [➙ 114] HMI Value 04 1950 6302

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 64 - Schenck Process Group
Parameters

P23.05 [➙ 114] HMI Value 05 0 6303

P23.06 [➙ 114] HMI Value 06 0 6304

P23.07 [➙ 114] HMI Value 07 0 6305

P23.08 [➙ 114] HMI Value 08 0 6306

P23.09 [➙ 114] HMI Value 09 0 6307

P23.10 [➙ 114] HMI Value 10 0 6308

24 - Second Display
Number: Name Default Customer Sys ID
P24.01 [➙ 116] Second Display active NO 4525

P24.02 [➙ 116] Baud rate 9600 4526

P24.03 [➙ 116] Data Format 8-N-1 4527

P24.04 [➙ 116] Physics RS232 4783

13.3.2 Parameter Details

13.3.2.1 Parameter Block 01 - Dialog Behaviour


The parameters of this group define system behavior towards the operator and set access authorization.

P01.01 Language Default: DEUTSCH


Alternative: DEUTSCH
ENGLISH
OTHER
Device dialog language. User-defined texts can be used if OTHER is selected. Texts can
be written and loaded using EasyServe.

P01.02 Userdefined Text Default: XX-NEW


Alternative: FR-FRANCAIS
ES-ESPANOL
IT-ITALIANO
CN-CHINESE
JP-JAPANESE
RU-RUSSIAN
HU-HUNGARIAN
NL-NETHERLAND
XX-NEW
Direct switching between several built-in languages.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 65 -
Parameters

P01.03 Font Default: UMing 30


Alternative: UMing 30
SAZ 30
Adjustable character representation. The current selection offers the versions of UMing30
for Chinese and SAZ30 for Japanese symbols.

P01.04 Units Default: Metric


Alternative: Metric
English
Switches display and parameter entry units from metric (SI units) to non-metric systems
(English). All values entered will be converted automatically.

P01.05 Scale Name Default: INTECONT Tersus VWF

Letters and characters can be used. The name appears in the upper row of the operating
console and when searching through networks for controllers.

Remark: The characters ";" and "=" are not accepted. During the saving procedure these
characters will automatically be deleted.

P01.06 Password Default: 10000


Min: 1000 Max: 9999
Password 1 for access protection of certain functions on the operator panel as per the fol-
lowing parameters. Usually the 1st password is used for the service personnel and the 2nd
password for operating personnel with particular privileges. The password keyed in is
shown encoded for protection. The password can be reset using EasyServe if it should be
forgotten.
The password set at the factory: 7353

P01.07 2. Password Default: 14389


Min: 1000 Max: 9999
Password 2 for access protection for certain functions on the operator panel as per the
following parameters. Usually the 1st password is used for the service personnel and the
2nd password for operating personnel with particular privileges. The password entered is
shown encoded on the screen. The password can be reset using EasyServe if it should be
forgotten.
The password set at the factory: 2889

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 66 - Schenck Process Group
Parameters

P01.08 Feeder ON/OFF Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

Using this parameters, access to the basic function prefeeder ON/OFF can be controlled.
The following options are available:
active: Access is always permitted.
not active: Access is never allowed. This function is not visible in the block.
Password: Access is available with the standard password.
2nd password: Access is available with the 2nd password.
Confirm: The access must be confirmed for security reasons.

Note: The prefeeder also has to be activated via parameters.

P01.09 Switch Grav./Vol. command Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.10 Switch Keyboard-/Normal Mode Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.11 Batch control Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 67 -
Parameters

P01.12 >0: Zero ON/OFF Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for the function at the operating console.
Definition des Zugriffsschutzes für die Funktion am Bedienteil.

P01.13 Reset Counter 1 Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.14 Reset Counter 2 Default: active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

P01.15 Data Log ON/OFF Default: not active


Alternative: active
not active
Password
2.Password
Confirm
Defines the access protection for using the operating console.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 68 - Schenck Process Group
Parameters

13.3.2.2 Parameter Block 02 - Rated Data

P02.01 Flow Rate Units Default: ------ kg/h


Alternative: ------ kg/h
----.- kg/h
---.-- kg/h
--.--- kg/h
------ t/h
----.- t/h
---.-- t/h
--.--- t/h
----.-- kg/min
Display format for setpoint and actual feed rate values.

P02.02 Nominal Flow Rate Default: 10 t/h


Min: 0.0001 t/h Max: 230000 t/h
The nominal feed rate is a scales' characteristic and serves as a reference value for thre-
shold values and service messages.
The parameter value can be set using an adjustment program or by automatic adaptation.

P02.03 Speed Measurement Default: DI IT.DI5 High


Alternative: DI
n/a
The source for recording the belt speed. A NAMUR transmitter (DI5-N) or velocity transmit-
ter can be used with transistor output (DI5-T).
Belt speed measurement is turned off with n/a. P02.05 Nominal Speed then functions as
the basis for calculation.

P02.04 Pulses per length Default: 10000 I/m


Min: 0.1 I/m Max: 1000000 I/m
Number of speed transducer pulses per belt length meter.
If noch tacho is active don't change characteristic value vs. This would change the timing of
calibration programs.

P02.05 Nominal Speed Default: 0.1 m/s


Min: 0.001 m/s Max: 50 m/s
Serving as reference value for limit value monitoring, nominal speed determines nominal
belt load together with nominal feed rate.

Value should be accurate to some percent.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 69 -
Parameters

P02.06 Feeder Start Default: OP


Alternative: OP
FB
DI
Specifies the device that will turn on the scales.

OP: from the keyboard of INTECONT


FB: through the fieldbus interface
DI: through a digital input

The digital input is flank-controlled, i.e. the ON signal must be removed and then reapplied
if the scales becomes inoperative because of e.g. an alarm.

P02.07 Feedrate Setpoint Default: OP


Alternative: OP
FB
AI
Determining the signal input that specifies the feed rate setpoint.

OP: from the keyboard of INTECONT


FB: through the fieldbus interface
AI: through an analog input

P02.08 Relative Setpoint Default: NO


Alternative: NO
YES
YES: The external absolute setpoints of the fieldbus (FB) or analog output (AI) can be eva-
luated relatively with the keyboard.

The value for the plant can be adapted through P14.17 Setpoint Offset as the starting value
and P14.18 Setpoint Range as the final value.

P02.09 WZ Active Default: YES


Alternative: NO
YES
NO: Belt load measurement is turned off. The Nominal Belt Load calculated from the rated
values functions internally.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 70 - Schenck Process Group
Parameters

P02.10 Counter 1 Unit Default: ------- kg


Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 1.

P02.11 Pulse Length Total Default: 0 ms


Min: 0 ms Max: 10000 ms
Duration of an external totalizing counter output impulse.

The weighting of an impulse is defined by P02.15 Totalizer Increment

If the impulse duration is shorter than 10 ms the impulse output is disabled. All impulses not
issued yet are cleared.

At nominal feed rate the output frequency f is:


f [Hz] = Pnom / 3600 * Zmin

Pnom = Nominal feed rate in kg/h or t/h (see P02.02 Nominal Flow Rate)
Zmin = Smallest display unit of counter 1 in kg or t (see P02.10 Counter 1 Unit)

The output frequency must be ≤ 10 Hz if an external counter is connected.


Refer also to chapter 'Appendices' → 'Impulse Output for External Totalizing Counter'.

P02.12 Counter 2 Unit Default: ------- t


Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 2

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 71 -
Parameters

P02.13 Counter 3 Unit Default: ------- t


Alternative: ------- kg
-----.- kg
----.-- kg
---.--- kg
------- t
-----.- t
----.-- t
---.--- t
Display format for counter 3.

P02.14 DO: Pulse Counter Default: n/a


Alternative: n/a
DO
DO: Selecting the physical output for triggering an external pulse counter for the measured
quantity Bear in mind the limitations on speed and life cycle when selecting a relay output
and set the weight equivalent for an impulse in P02.15 Totalizer Increment. The duration of
the impulse is set by P02.11 Pulse Length Total.

n/a: It is output through contact X3-1.2 where the output frequency may not be in excess of
10 Hz.

P02.15 Totalizer Increment Default: 10 kg


Min: 0 kg Max: 100000 kg
Weight equivalent of an impulse at the output for the external counter as per P02.14 DO:
Pulse Counter.
The DO: Pulse Counter is blocked when setting the valence 0.

P02.16 Z1-Numberstep Default: Automatic


Alternative: Automatic
2 kg
5 kg
20 kg
50 kg
200 kg
500 kg
0.02 t
0.05 t
0.2 t
0.5 t
Determines the increment value für counter 1 and all batch values. Parameter P02.10
Counter 1 Unit applies for "Automatic".
The increment value only applies to the local display and for printouts.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 72 - Schenck Process Group
Parameters

13.3.2.3 Parameter Block 03 - Calibration Data

P03.01 Belt Circuit No. Default: 1


Min: 1 Max: 100
Sets the runtime of the programs zero, tare and weight check. Does not apply for the auto-
matic zero setting device.

P03.02 Belt Circuit Time Default: 30 s


Min: 1 s Max: 9999 s
Determines the measurement period for the impulse/belt circuit calibration program.
Usually, the time chosen is the time required for one belt circuit.

P03.03 LC Characteristic Value Default: 2 mV/V


Min: 0.01 mV/V Max: 9.9999 mV/V
Characteristic value (transmission factor) of the load cell.

P03.04 LC Rated Capacity Default: 60 kg


Min: 0.5 kg Max: 220000 kg
The total of the load cell rated loads for recording the weight of the continuous scale.

P03.05 Effective Platform Length Default: 0.5 m


Min: 0.1 m Max: 50 m
Effective weigh bridge length.

P03.06 Lever Ratio Default: 1


Min: 0.01 Max: 2
Lever ratio between force transducing weigh idler and load cell.
Using weighing modules with leaf spring parallel guidance, lever ratio is always 1.

P03.07 Angle Default: 0 Grad


Min: 0 Grad Max: 60 Grad
The inclination of the longitudinal axis of the scale when the load cell is installed vertical to
the belt.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 73 -
Parameters

P03.08 Calibration Weight Default: 10 kg


Min: 0.001 kg Max: 22000 kg
Required for the calibration program CW: Span Calibration.

Also refer to: P04.02 Range Correction

13.3.2.4 Parameter Block 04 - Calibrat. Results

P04.01 Nominal Belt Load Default: 27.78 kg/m


Min: 0.06 kg/m Max: 10000 kg/m
Reference for limit values and zeroing program.
This is calculated from Nominal Flow Rate P02.02 and Nominal Speed P02.05.

P04.02 Range Correction Default: 1


Min: 0.5 Max: 2
The parameter affects the belt-load measurement F proportionally.
Q(corrected) = Q(measured) * P04.02

P04.03 Total Tare Default: 0 kg/m


Min: 0 kg/m Max: 10000 kg/m
Total Tare = Basic Tare + Tare Correction

P04.04 Basic Tare Default: 0 kg/m


Min: 0 kg/m Max: 10000 kg/m
Results of the taring adjustment program.

P04.05 Tare Correction Default: 0 kg/m


Min: -1000 kg/m Max: 1000 kg/m
Results of the >0< Zero Set adjustment program or automatic zero setting.

P04.06 Belt Circuit No. Default: 1000000 I/B


Min: 0 I/B Max: 9000000 I/B
Result of program LB: Pulses/Belt. Defines the cycle of the calibration programs.
Divided by P02.04 Pulses per length results the belt length in m.

13.3.2.5 Parameter Block 05 - Analog Outputs


The parameters in this group select the control source for the analog output channels. On the VCU 20104
controller only one analog channel is available and it is set to feedrate feedback by default.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 74 - Schenck Process Group
Parameters

P05.01 AO: Setpoint Default: n/a


Alternative: n/a
AO
Analog output channel for the setpoint feed rate.

Also refer to: P05.02 Setpoint Offset, P05.03 Setpoint Range

P05.02 Setpoint Offset Default: 4 mA


Min: -200 mA Max: 200 mA
Output current for a feed rate setpoint value of 0 %.

Reference: P02.02 Nominal Flow Rate

See also: P05.01 AO: Setpoint

P05.03 Setpoint Range Default: 20 mA


Min: 0 mA Max: 1000 mA
Output current for a feed rate setpoint value of 100%.

Reference: P02.02 Nominal Flow Rate

Also refer to: P05.01 AO: Setpoint

P05.04 AO: Actual Flow Rate Default: n/a


Alternative: n/a
AO
Analog output channel for the actual feed rate.

Also refer to: P05.05 Flow Rate Offset, P05.06 Flow Rate Range

P05.05 Flow Rate Offset Default: 4 mA


Min: -200 mA Max: 200 mA
Output current for an actual feed rate value of 0%.

Reference: P02.02 Nominal Flow Rate

Also refer to: P05.04 AO: Actual Flow Rate

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 75 -
Parameters

P05.06 Flow Rate Range Default: 20 mA


Min: 0 mA Max: 1000 mA
Output current for the value of an actual feed rate of 100%.

Reference: P02.02 Nominal Flow Rate

Also refer to: P05.04 AO: Actual Flow Rate

P05.07 AO: Belt Load Default: n/a


Alternative: n/a
AO
Analog output source for the belt load.

P05.08 Belt Load Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The output flow for the value of the belt load of 0 %

Reference: P04.01 Nominal Belt Load

Also refer to: P05.07 AO: Belt Load

P05.09 Belt Load Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The output flow for the value of the belt load of 100 %.

Reference: P04.01 Nominal Belt Load

Also refer to: P05.07 AO: Belt Load

P05.10 AO: Speed Default: n/a


Alternative: n/a
AO
The analog output source for belt speed.

P05.11 Speed Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The output flow for the value of the belt speed of 0 %.

Reference: P02.05 Nominal Speed

Also refer to: P05.10 AO: Speed

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 76 - Schenck Process Group
Parameters

P05.12 Speed Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The output flow for the value of the belt speed of 100 %.

Reference: P02.05 Nominal Speed

Also refer to: P05.10 AO: Speed

P05.13 AO: Deviation Default: n/a


Alternative: n/a
AO
Analog output channel for the control deviation.

See also: P05.14 Deviation Offset, P05.15 Deviation Range

P05.14 Deviation Offset Default: 4 mA


Min: -200 mA Max: 200 mA
The value of the control deviation 'zero' lies between the offset and 20 mA.

Also refer to: P05.13 AO: Deviation

P05.15 Deviation Range Default: 20 mA


Min: 0 mA Max: 1000 mA
The output current is calculated according to the following formula:

Current = 10 mA + (P05.14)/2 + (P05.15 - P05.14) × control deviation / 100 %

Reference value: P02.02 Nominal Flow Rate

P05.16 AO: Motor Speed Control Default: AO IT.AO1


Alternative: AO
n/a
Analog output for the actuating variable Y of the feed rate regulator.

Also refer to:


- the parameters in the 'regulator' block
- the regulator diagram in the appendices

13.3.2.6 Parameter Block 06 - Limit Values


The parameters of this group define the limits for process values and specify the event classes of the asso-
ciated events.

Events that can only occur with regular feed operation are only monitored 10 s after beginning feed opera-
tion.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 77 -
Parameters

P06.01 Limit: Actual Flow Rate MIN Default: 5 % Io


Min: -10 % Io Max: 200 % Io
Lower threshold for the actual feed rate.

Reference : P02.02 Nominal Flow Rate

P06.02 Event: Actual Flow Rate MIN Default: W1


Event Group: LO Number: 02

Actual feed rate lower than the minimum value set in Limit: Actual Flow Rate MIN

Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too low

P06.03 Limit: Actual Flow Rate MAX Default: 120 % Io


Min: -10 % Io Max: 200 % Io
Upper threshold for the actual feed rate.

Reference : P02.02 Nominal Flow Rate

P06.04 Event: Actual Flow Rate MAX Default: W1


Event Group: HI Number: 02

Actual feed rate greater than the maximum value set in P06.03 Limit: Actual Flow Rate
MAX

Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too large

P06.05 Limit: Belt Load MIN Default: 60 % Q


Min: -10 % Q Max: 200 % Q
Lower limit for belt load.

Reference: P04.01 Nominal Belt Load

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 78 - Schenck Process Group
Parameters

P06.06 Event: Belt Load MIN Default: W1


Event Group: LO Number: 03

The belt load is less than the minimum value set in Limit: Belt Load MIN

Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment

P06.07 Limit: Belt Load MAX Default: 120 % Q


Min: -10 % Q Max: 200 % Q
Upper limit for the belt load

Reference: P04.01 Nominal Belt Load

P06.08 Event: Belt Load MAX Default: W1


Event Group: HI Number: 03

The belt load is greater than the maximum value set in P06.07 Limit: Belt Load MAX

Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equipment

P06.09 Limit: Speed MIN Default: 5 % V


Min: -10 % V Max: 200 % V
Lower limit for belt speed.

Reference: P02.05 Nominal Speed

P06.10 Event: Speed MIN Default: W1


Event Group: LO Number: 04

The belt speed is less than the minimum value set in Limit: Speed MIN

P06.11 Limit: Speed MAX Default: 120 % V


Min: -10 % V Max: 200 % V
Upper limit for belt speed.

Reference: P02.05 Nominal Speed

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 79 -
Parameters

P06.12 Event: Speed MAX Default: W1


Event Group: HI Number: 04

The belt speed is greater than the maximum value set in Limit: Speed MAX

P06.13 Stand-By Limit Value Default: 0 % Io


Min: 0 % Io Max: 100 % Io
The feeder drive is switched off if the setpoints are lower than the threshold value to protect
the motor from overheating.

Also refer to: P06.14 Event: Stand-By

P06.14 Event: Stand-By Default: W2


Event Group: SC Number: 02

The scale is in stand-by operation. That means that the setpoint is less than the limit set in
P06.13 Stand-By Limit Value. The feeder drive is switched off. The 'running' state will still
be displayed.

This function protects the motor from overheating at very low speeds or when idling.

Steps to take:
Key in the larger setpoint and check P06.13 Stand-By Limit Value.

13.3.2.7 Parameter Block 07 - Filters


The parameters of this group define the time constants of the filters for measurement and display.
All of the filters are 1st order (exponentially). That means that approximately 2/3 of the final value is reached
after the time set with a volatile change in the signal.
Long times result in a smooth but slowly-updating display.

P07.01 Filter: Actual Flow Rate Default: 3 s


Min: 0 s Max: 600 s
Filter time constant for the display and for outputs of the actual feed rate at the operating
console, EasyServe and all fieldbuses. Has no effect on the feeder regulation.

P07.02 Filter: Actual Flow Rate analog Default: 3 s


Min: 0 s Max: 600 s
Filter time constant for the actual feed rate analog output.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 80 - Schenck Process Group
Parameters

P07.03 Filter: Belt Load Default: 3 s


Min: 0 s Max: 600 s
Belt load display

P07.04 Filter: Belt Speed Default: 3 s


Min: 0 s Max: 600 s
Belt speed display

P07.05 LC Filter Default: 1 s


Min: 0 s Max: 600 s
The load cell filters affects all load cell related measuring values. In general this value
should be left at the factory setting.

Note: filtering the load cell signal also effects the regulating action.

P07.06 Afterflow Totalizer Default: 3 s


Min: 0 s Max: 2000 s
Once shut off the scales continue to measure for this duration of time the trickle of material
still flowing.

13.3.2.8 Parameter Block 08 - Additional device

P08.01 Zero Drop-Out Active Default: NO


Alternative: NO
YES
YES: Activating the zero drop-out equipment.

P08.02 Zero Drop-Out Limit Default: 1 % Q


Min: 0 % Q Max: 10 % Q
Recording the total is suppressed with measurements within this limit around the zero point
to ensure that the counter remains constant when the belt is idle.
No feature appears on the display.
Reference: P04.01 Nominal Belt Load

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 81 -
Parameters

13.3.2.9 Parameter
Parameter Block 09 - Batch Mode
The parameters of this group define and optimize behavior in batching mode.

P09.01 Pre-cut-off Amount Default: 3 s


Min: 0 s Max: 3600 s
When Batch Actual Value is reached, the Setpoint is changed to 0 with a ramp function
regardless of the source of the setpoint.

Batch Actual Value = Batch Setpoint - Setpoint/2 * P09.01 - P09.02

P09.02 Correction Amount Default: 0 kg


Min: -1000000 kg Max: 1000000 kg
This can be used for correcting the disconnection in the next batch.
The correction quantity should be set to 0 on commissioning.

P09.03 Adaptation Factor Default: 0.5


Min: 0 Max: 1
The application point of the switch-off function is adapted automatically so that the system
is better adapted to the actual conditions for the next batch.

Adaptation Factor = 0 : no adaptation


Adaptation Factor = 1 : full adaptation

Interim values result in filtered adjustment; this should be used in particular for systems with
poor reproducibility.
The result of the event is stored in P09.02 Correction Amount.

P09.02 NEW = P09.02 OLD - Batch Residual Amount * P09.03

P09.04 Batch Tolerance Default: 100000 kg


Min: 0 kg Max: 2200000 kg
If the batch lies outside of the tolerance range, the maximum alteration of
the correction quantity at adaptation is the entered tolerance value. Also, an event is identi-
fied.

Also refer to: P09.05 Event: Out of Tolerance

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 82 - Schenck Process Group
Parameters

P09.05 Event: Out of Tolerance Default: W1


Event Group: MF Number: 06

The batch result is outside the tolerance range.

Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces

P09.06 Batch Automatic Record Default: NO


Alternative: NO
YES
YES: automatic print after each completed batch.
NO: Printout of the batch can only be made via menu.

The printout can be made only after a batch has ended automatically or manually. The
printout is stored to a file that can be read using the Web-Server.
INTECONT Tersus additionaly may use a printer.

P09.07 Batch Setpoint Source Default: OP


Alternative: OP
FB
Establish the source that will determine the batch.

13.3.2.10 Parameter Block 10 - Printer Setting

P10.01 Baud rate Default: 9600


Alternative: 1200
2400
4800
9600
19200
38400

P10.02 Print Event Default: YES


Alternative: NO
YES
This Parameter lets you determine whether available event messages are printed or not.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 83 -
Parameters

P10.03 Print Page Length Default: 72


Min: 9 Max: 127
The page length must be larger than the number of print data by at least 4. The
The line spacing is always 1/6 inch.

Form feed is not issued at value 128 at the end of the sheet.

13.3.2.11 Parameter Block 11 - Maintenance interval


The parameters of this group define maintenance intervals and the internal accuracy analysis function.

P11.01 Maintenance Electric Default: 3000 h


Min: 1 h Max: 10000 h
Indication of maintenance work that may need to be performed, dependent on the duty
cycle of the power supply. This parameter defines the interval between maintenance work.

Also refer to: P11.02 Event: Maint. Electric

P11.02 Event: Maint. Electric Default: W1


Event Group: SC Number: 04

The sum of the times during which the mains voltage is on is greater than the time 'voltage
ON'.

A message occurs after each expired time interval. The message may indicate service work
required.

See also: P11.01 Maintenance Electric

P11.03 Maintenance Feeder Run Default: 3000 h


Min: 1 h Max: 10000 h
Indication of maintenance work that may need to be performed, dependent on the duty
cycle of the scales (scales ON). This parameter defines the interval between maintenance
work.

Also refer to: P11.04 Event: Maint.Feeder Run

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 84 - Schenck Process Group
Parameters

P11.04 Event: Maint.Feeder Run Default: W1


Event Group: SC Number: 03

The sum of the runtimes of the conveying elements is greater than the time 'Scales ON'
(P11.03 Maintenance Feeder Run).

A message occurs after each expired time interval. The message may indicate service work
required.

13.3.2.12 Parameter Block 12 - Belt Monitoring

P12.01 VAP Active Default: NO


Alternative: NO
YES
If measurement is made at the discharge point VAP, the weighing platform measuring point
is repositioned to the material discharge point by a delay element. The totalized amount of
material discharged is directly recorded.

Note: If VAP is active, we recommend turning on


automatic belt influence compensation (BIC).

The conditions: The length ratio from the middle of the weighbridge to material discharge to
the entire length of the conveyor belt is known.

P12.02 Platform Dis.Length Default: 0 % LB


Min: 0 % LB Max: 50 % LB
The space from the middle of the weighbridge to the material discharge in % of the entire
belt length (refer to P04.06 Belt Circuit No.)

P12.03 Belt Sensor Active Default: NO


Alternative: NO
YES
The belt sensor and sensor surface in the conveyor belt are used for identifying Belt Drift
and Slip Value and synchronizing adaptive belt influence compensation (BIC).

P12.04 DI: Source Belt Sensor Default: DI IT.DI4 High


Alternative: DI
n/a
The digital input for the belt sensor. This function can be checked with the corresponding
service value.

DI: Only DI4 can be used with INTECONT Tersus.


n/a: BIC and the belt monitoring functions are inactive.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 85 -
Parameters

P12.05 BIC Active Default: NO


Alternative: NO
YES
Automatic belt influence compensation (BIC) monitors and corrects the belt influence. It
needs a sensor and sensor surface just like belt monitoring.

Note:
It is started up for the first time without activating BIC.

Characteristics:
After activating belt influence compensation, the influence that the conveyor belt has on the
measurement is compensated after approximately ten belt circuits.

P12.06 Sensor Length Default: 8.2 cm


Min: 0.01 cm Max: 400 cm
Lenght of the conductive mark included in the belt measured in travel direction.

P12.07 Sensor Width Default: 12 cm


Min: 0.01 cm Max: 400 cm
width of the conductive mark included in the belt measured in 90 degrees to the belt travel
direction..

P12.08 Sensor Offset Default: 0 cm


Min: -400 cm Max: 400 cm
The zero point of recording the belt drift can be corrected with the offset. Unfortunately, this
restricts the maximum display zone. This is why greater differences should be calibrated by
mechanically shifting the sensor.
The new display = the old display - the offset

P12.09 Belt Drift Default: 3 cm


Min: 0.01 cm Max: 400 cm
Threshold of the belt drift for detection of event Event: Belt Drift.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 86 - Schenck Process Group
Parameters

P12.10 Event: Belt Drift Default: W1


Event Group: WM Number: 04

Belt out of tolerance.


Action:
1. Clean tail and drive pulleys.
2. Align belt.
Monitoring can be faulty. Watch belt circuit sensor service value; if need be, remedy
fault.
Related threshold: Belt Drift

P12.11 Belt Skew Default: 4 cm


Min: 0.01 cm Max: 400 cm
Threshold of the belt drift for detection of event Event: Belt Skew.

P12.12 Event: Belt Skew Default: A


Event Group: WM Number: 03

Belt has run off-center. Feeder is no longer operable.


Action: See Event: Belt Drift
Related threshold: Belt Skew

P12.13 Slip Value Default: 2 % LB


Min: 0 % LB Max: 10 % LB
The permitted change in length of the conveyor belt in % of the total belt length.

There is a Event: Slip event message if it exceeds the limit


and the P12.17 DO: Belt Slip digital output is set.

P12.14 Event: Slip Default: W1


Event Group: WM Number: 02

P12.15 DO: Belt Drift Default: n/a


Alternative: n/a
DO
The digital output to show the event of drift.
Also refer to: P12.09 Belt Drift and P12.10 Event: Belt Drift

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 87 -
Parameters

P12.16 DO: Belt Skew Default: n/a


Alternative: n/a
DO
Digital output reporting Belt Skew event.
See also: P12.11 Belt Skew and P12.12 Event: Belt Skew

P12.17 DO: Belt Slip Default: n/a


Alternative: n/a
DO
The digital output to show Event: Slip.
Also refer to P12.13 Slip Value .

P12.18 DI: BIC freeze Default: n/a


Alternative: n/a
DI
FB
The BIC values currently running in are frozen when this digital input is set.
This prevents the values already ascertained from being falsified on belt loads that fluctuate
greatly.

13.3.2.13 Parameter Block 13 - Events

P13.01 Event: Power Failure Default: A


Event Group: WE Number: 01

This event is identified once the power supply is restored.

The scales will not switch on automatically, regardless of the event class. The event must
first be acknowledged and the command to start given again before the scales will restart.

P13.02 Event: Memory Default: A


Event Group: SY Number: 01

The program and parameters memory are checked cyclically. An error has occurred during
that. The scales will no longer function correctly.

Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 88 - Schenck Process Group
Parameters

P13.03 Event: Tachometer Input Default: A


Event Group: CA Number: 02

The input frequency is greater than 3,000 Hz.

P13.04 Event: Namur Error Tacho Default: A


Event Group: WE Number: 09

A short-circuit or break in the cable to the velocity sensor.

The internal velocity value is set to 0 if a Namur error occurs.


The frequency display (service value) is still active.

The event message has to be on IG when connecting up other equipment (not Namur).
External Namur adapters and resistance wiring, etc. are not needed.

P13.05 Event: Namur Error Belt Default: W1


Event Group: WE Number: 10

A short-circuit or break in the cable of the belt circuit sensor (BIC).

P13.06 Event: Error LC Input Default: A


Event Group: CA Number: 01

The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.

Steps to take:
- check the cabling and the load cell
- check the load cell

Note:
The power supply must be switched off and on again if the scales still cannot be switched
on even after the error has been rectified.

P13.07 Event: Run Disabled Default: W1


Event Group: IL Number: 01

No release signal from the source determined by P16.01.

If this event is pending then the downstream transport equipment is most likely not switched
on.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 89 -
Parameters

P13.08 Event: LC Input > MAX Default: A


Event Group: HI Number: 01

The load acting on the load cell is greater than 110 % of the sum of the nominal loads of
the load cells.

Measuring range end:


125 % for load cells with 2.85 mV/V
175 % for load cells with 2 mV/V

Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell

P13.09 Event: LC Input < MIN Default: A


Event Group: LO Number: 01

The load cell load is less than 3 % of the sum of the load cell nominal loads.

Possible reasons:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell

P13.10 Event: Simulation active Default: W2


Event Group: SY Number: 14

Simulation operation is on.

P13.11 Event: Setpoint Limited Default: W1


Event Group: SC Number: 01

Cause of the event:


Depending on the respective mode of operation:
a) The setpoint is limited to the nominal feed rate (P02.02 Nominal Flow Rate) in gravime-
tric operation.
b) The setpoint is limited to three times the value of the nominal feed rate (P02.02 Nominal
Flow Rate) in volumetric operation.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 90 - Schenck Process Group
Parameters

P13.12 Event: External Event 1 Default: A


Event Group: SC Number: 05

External interference signal at fault input 1.

Possible cause: depends on the external cabling. Usually: an error in the main drive

P13.13 Event: External Event 2 Default: A


Event Group: SC Number: 06

External interference signal at fault input 2.

Possible cause: depends on the external cabling.

P13.14 Event: License Violation Default: A


Event Group: SY Number: 09

The option selected in the P19.01 Protocol Type parameter is not activated.
It has to be cleared. Refer to the Option activate function

13.3.2.14 Parameter Block 14 - Rate controller

P14.01 Optimize Controller Default: STANDARD


Alternative: STANDARD
UNIVERS
STANDARD: standard controller adjustment for weighfeeder application.
UNIVERS: User-defined controller adjustment for special cases (refer to appendix).

The appendix contains a detailed wiring diagram and applications for special cases.

Caution The parameters from P10.08 are written on the default values again when chang-
ing from UNIVERS to STANDARD.

P14.02 P-Component KP Default: 0.04 mA/%


Min: 0 mA/% Max: 1000 mA/%
Proportional component of the feed rate regulator.

Special case: KP = 0 results in an I-regulator

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 91 -
Parameters

P14.03 I-Component TN Default: 1 s


Min: 0 s Max: 60000 s
Reset time (integral component) for the feed rate regulator.

The reset time TN is the time in which the change to the actuating variable produced by the
I-component is the same as that produced by the P-component (P14.02).
Special cases:
a) KP = 0 : I-regulator
TN is the reciprocal value of the integration constants KI, i.e. a larger value means a slower
regulator.
KI = 1/TN TN in %/(mA/s)
b) TN = 0 : P-regulator
The I-component is cleared.
C) KP = TN = 0 : Regulator output = increase in P14.13 Controller Magnitude Offset

P14.04 Filter: Deviation Default: 3 s


Min: 0 s Max: 600 s
Filter time constant for all displays and printouts of the control deviation.

P14.05 Time Deviation Default: 20 s


Min: 0 s Max: 600 s
Time for which a control deviation above the threshold in P14.06 Threshold Deviation will
be tolerated. The event 'control deviation' is recognized once the time has been exceeded.

Simultaneously, P14.05 Time Deviation functions as a time constant for the filter that con-
tains the value of the control deviation. A 'control deviation' event is also recognized if the
filtered result exceeds the threshold value P14.08 Deviation abs. max..

See also:
P14.06 Threshold Deviation
P14.07 Factor Deviation
P14.08 Deviation abs. max.
P14.09 Event: Deviation

P14.06 Threshold Deviation Default: 5 %


Min: 0 % Max: 100 %
Maximum permissible control deviation.
Reference: P02.02 Nominal Flow Rate.

Also refer to: P14.05 Time Deviation, P14.09 Event: Deviation

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 92 - Schenck Process Group
Parameters

P14.07 Factor Deviation Default: 1


Min: 0 Max: 1
An event message as per P14.09 Event: Deviation will be identified if the absolute value of
the control deviation for the duration P14.05 Time Deviation is greater than the threshold
P14.06 Threshold Deviation.
With a setpoint of 100%, the effective threshold is always determined by the parameter
P14.06 Threshold Deviation. For lower setpoints the threshold can be reduced with para-
meter P14.07 Factor Deviation.
Examples:
P14.07 = 0 : Effective threshold = P14.06 × Setpoint / P02.02
P14.07 = 1 : Effective threshold = P14.06

Also refer to chapter 'Appendices' → 'Feed Rate Regulation'

P14.08 Deviation abs. max. Default: 100 %


Min: 0.1 % Max: 1000 %
The amount of the control deviation will be filtered (filter time constant: P14.05 Time Devia-
tion). If the filter output exceeds the limit set here a 'control deviation' event will be identified
(P14.09 Event: Deviation). The filter is reset when the scales are switched off.

P14.09 Event: Deviation Default: W1


Event Group: HI Number: 05

Maximum control deviation exceeded. The actual feed rate has deviated to far from the
setpoint over too long a period of time.

Possible causes:
- Fault in material handling: the bulk solids flow irregularly or cannot be discharged suffi-
ciently well.

- the controller has at times come against its limits


- error in the electronics
- check the cable to the external output regulator and to the motor. Check the output regu-
lator settings (current limiting, speed range)

- Calibration error: the controller was set at such a critical value during initial calibration that
minor changes in the overall properties of the system lead to unreliable operation.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 93 -
Parameters

P14.10 Event: Controller Limited Default: W1


Event Group: CO Number: 01

The actuating variable of the feed rate regulator has reached the upper response threshold.
After a time the message HI-5 (control deviation) is also sent.
1. No material is flowing or material flow is irregular.
2. The external output regulator has been incorrectly set.

Steps to take: check the material discharge and the actuating variable (service value Y). At
the nominal feed rate, Y should be between about 10...14 mA.

P14.11 Lower Limit Default: 0 mA


Min: 0 mA Max: 20 mA
Lower limit for the regulator actuating variable.

If transfer is made with currents of between 4-20 mA, the parameter must be set to 4 mA at
least. P14.13 Controller Magnitude Offset must be set to a value equal to or greater than
P14.11 Lower Limit.

Also refer to: P14.13 Controller Magnitude Offset

P14.12 Upper Limit Default: 20 mA


Min: 0 mA Max: 20 mA
Upper limit for the regulator actuating variable.

With inputs lower than 20 mA the limit depends on the size of the threshold value.

Also refer to:


- description of the effect of the upper limit can be found in the appendices

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 94 - Schenck Process Group
Parameters

P14.13 Controller Magnitude Offset Default: 0 mA


Min: 0 mA Max: 20 mA
Offset of the actuating variable by a constant value. The offset takes effect before the limi-
tation of the actuating variable.

Generally the same values are chosen for P14.13 Controller Magnitude Offset as for
P14.11 Lower Limit.
Optimization:
- fill the feeder hopper with bulk material
- calculate the actuating variable Y1, the value at which the discharge unit begins to work
- calculate the actuating variable Y2, the value at which reduction of the feed is suspended.
For feeders that are operated with feed rate setpoints of 0:
P14.13 Controller Magnitude Offset = Y2
All other feeders:
P14.13 Controller Magnitude Offset = Y1

Note: P14.13 Controller Magnitude Offset must be equal to or greater than P14.11 Lower
Limit.

P14.14 Position at STOP Default: 0


Alternative: 0
Lower Limit
If the scales are switched off the actuating variable can be set to 0 or to the offset value in
the 'lower limit' parameter.

0: the actuating variable is set to 0 when the scales are switched off.
Lower limit: the actuating variable is set to the lower limit.

P14.15 Volumetric Start-Up Default: 0 Circuits


Min: 0 Circuits Max: 2 Circuits
Length of time it takes to begin volumetric operation once the scales have been switched
on. If selected, feeding will switch to gravimetric operation once the startup time has past.

This function improves the startup with an empty feeder.


The optional DISOCONT speed controller is also active during startup.

P14.16 Volumetric Clearance Default: 0 Circuits


Min: 0 Circuits Max: 2 Circuits
Duration of clearance mode. For clearance mode the flow gate is switched off before the
feeder discharge element. This allows the discharge element to be emptied.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 95 -
Parameters

P14.17 Setpoint Offset Default: 0 mA


Min: 0 mA Max: 200 mA
Input current offset for an analog setpoint of 0 % of the nominal feed rate.

This parameter takes effect only if P02.07 Feedrate Setpoint has been set to AI.

P14.18 Setpoint Range Default: 20 mA


Min: 0 mA Max: 200 mA
Input current for the analog setpoint of 100 % of the nominal feed rate.

The range and offset parameters take effect only if P02.07 Feedrate Setpoint has been set
to AI.

P14.19 Store Default: NO


Alternative: NO
YES
YES-A
Saving the control value after turning off the scale. The next start will begin with this value.

NO: do not save


YES: save
YES-A: only save if the scale has not broken down due to an alarm

P14.20 Volumetric Mode Default: Qconst


Alternative: Qconst
Yconst
Selects Volumetric mode

Qconst : V * Qconst acts as actual value. V is current belt speed and Qconst is the stored
beltload (nominal beltload, or last measurement)
Scale operates speed-controlled.

Yconst : Controller cut off, only P14.21 Bypass is active.

P14.21 Bypass Default: 0 mA


Min: 0 mA Max: 20 mA
Constant for the feed rate setpoint pilot control.

One value is superimposed additively on the actuating variable, proportionally to the preset
setpoint. This parameter gives the bypass value for the nominal setpoint.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 96 - Schenck Process Group
Parameters

P14.22 Setpoint Filter 1st Ord Default: 0 s


Min: 0 s Max: 6000 s
1st-order filter in the setpoint branch. Does not function for the bypass.

P14.23 Setpoint Filter 2nd Ord Default: 0 s


Min: 0 s Max: 6000 s
2nd-order filter in the setpoint branch. Does not function for the bypass.

P14.24 Set/Act Sources Default: I


Alternative: I
Q
Selecting the setpoint.

I: setpoint = target feed rate


Q: setpoint = rated belt load Qo

P14.25 Adaptation 1 Default: NO


Alternative: NO
W
Controlled adaption of the controller input

The adaption means that the controller can be adapted to variable route reinforcements or
the
guidance behavior can be improved.

13.3.2.15 Parameter Block 15 - Linearization


The parameters of this group define the characteristic curve of a non-linear external structural component.

P15.01 Linearization ON Default: NO


Alternative: NO
YES
Belt load measuring can be linearized with this parameters.
The 4 linearization points can be determined by calibration with calibration weights or using
material. Not required or not measured points must be laid either outside the measuring
range or must be interpolated. Detailed calibration instructions are in the appendix.

P15.02 Linearization S1 Default: 25 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 1:
Actual belt load, e.g. determined using calibration weights or by material measurement.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 97 -
Parameters

P15.03 Linearization I1 Default: 25 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 1:
Belt load measured by the weighing electronics.

P15.04 Linearization S2 Default: 50 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 2.
Otherwise as P15.02 Linearization S1

P15.05 Linearization I2 Default: 50 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 2:
Otherwise as P15.03 Linearization I1

P15.06 Linearization S3 Default: 75 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 3.
Otherwise as P15.02 Linearization S1

P15.07 Linearization I3 Default: 75 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 3:
Otherwise as P15.03 Linearization I1

P15.08 Linearization S4 Default: 100 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 4.
Otherwise as P15.02 Linearization S1

P15.09 Linearization I4 Default: 100 % Q


Min: 0.01 % Q Max: 1000 % Q
Linearization point 4:
Otherwise as P15.03 Linearization I1

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 98 - Schenck Process Group
Parameters

P15.10 Event: Linearization Error Default: W2


Event Group: CA Number: 05

Not a monotonically increasing curve.

A monotonically increasing compensation curve is monitored:


- when the linearization is switched on,
- when the parameter is altered

13.3.2.16 Parameter
Parameter Block 16 - Digital Inputs
The parameters in this group are used to associate various controller functions with specific digital input
channels and to associate events with those functions. Most of the functions specified in this group are hard
wired on the controller and cannot be changed.

P16.01 Source Run Enable Default: DI IT.DI3 High


Alternative: DI
FB
n/a
Determines the signal input that gives the scales release signal. This input is generally
used for interlocking with downstream transport equipment.

The setting 'n/a' means that no release is required.

P16.02 DI: Batch Terminate Default: n/a


Alternative: n/a
DI
Digital input signal for stopping a current batch.

P16.03 DI: Acknowledge Events Default: DI IT.DI1 High


Alternative: DI
n/a
Digital input for acknowledging event messages.

Caution: the level is static and may not be on permanently (otherwise continuous acknowl-
edgement).

P16.04 DI: Volumetric Mode Default: n/a


Alternative: n/a
DI
Digital input for switching the scales to volumetric, not with prehistory synchronized opera-
tion.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 99 -
Parameters

P16.05 DI: Volumetric synchron Default: n/a


Alternative: n/a
DI
Switches to volumetric operation while the actuating variable continues itself steadily. The
actuating variable is calculated as an average of the actuating variable obtained during
steady operation. Alterations to the feed rate setpoint automatically adjusts the actuating
variable.

P16.06 DI: Start Default: n/a


Alternative: n/a
DI
If OP is selected as the turn-on source, the digital input that the scale can be started with
using a turn-on impulse can be configured here in parallel to the ON/OFF buttons on the
keyboard.
The scale is turned off by an impulse on the digital input P16.01 Source Run Enable.

P16.07 DI: External Event 1 Default: n/a


Alternative: n/a
DI
Input 1 for an external interference signal.

P16.08 DI: External Event 2 Default: n/a


Alternative: n/a
DI
Input 2 for an external interference signal.

13.3.2.17 Parameter Block 17 - Digital Outputs


The parameters in this group are used to associate various controller functions with specific digital output
channels. Most of the functions specified in this group are hard wired at assembly.

P17.01 DO: ALARM Default: DO IT.DO3 Low


Alternative: DO
n/a
The output becomes active if any alarm is triggered (common alarm). The scales have
failed.

P17.02 DO: Start Prefeeder Default: DO IT.DO6 High


Alternative: DO
n/a
The digital output for turning the prefeeder on or off.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 100 - Schenck Process Group
Parameters

P17.03 DO: Scale Start Default: DO IT.DO7 High


Alternative: DO
n/a
Sends a start command to the feeder's main drive.

P17.04 DO: Actual Flow Rate MIN Default: DO IT.DO4 Low


Alternative: DO
n/a
The output signal becomes active if the feed rate falls below the minimum feed rate (P06.01
Limit: Actual Flow Rate MIN).

The contact output is independent of the event class.

P17.05 DO: Actual Flow Rate MAX Default: DO IT.DO2 Low


Alternative: DO
n/a
The output signal becomes active when the maximum feed rate (P06.03 Limit: Actual Flow
Rate MAX) is exceeded.

The contact output is independent of the event class.

P17.06 DO: Belt load MIN Default: n/a


Alternative: n/a
DO
The output signal becomes active when it falls below the minimum belt load (P06.05 Limit:
Belt Load MIN).

The contact output is independent of the event class.

P17.07 DO: Belt Load MAX Default: n/a


Alternative: n/a
DO
The output signal becomes active when it exceeds the maximum belt load (P06.07 Limit:
Belt Load MAX).

The contact output is independent of the event class.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 101 -
Parameters

P17.08 DO: Speed MIN Default: n/a


Alternative: n/a
DO
The output signal becomes active when it falls below the minimum belt speed (P06.09 Lim-
it: Speed MIN).

The contact output is independent of the event class.

P17.09 DO: Speed MAX Default: n/a


Alternative: n/a
DO
The output signal becomes active when it exceeds the maximum belt speed (P06.11 Limit:
Speed MAX).

The contact output is independent of the event class.

P17.10 DO: Batch Running Default: n/a


Alternative: n/a
DO
The output becomes active if a batch is run.
The signal is activated on the start of the batch and deactivated once the batch has been
completed. It remains active if batch operation is continuous.

P17.11 DO: Full Feed Default: n/a


Alternative: n/a
DO
The output becomes active in the full feed phase.

P17.12 DO: Dribble Feed Default: n/a


Alternative: n/a
DO
The output becomes active in the dribble feed phase.

P17.13 DO: Feeder Started Default: DO IT.DO1 High


Alternative: DO
n/a
Digital output signal used to display the ON or OFF scales states.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 102 - Schenck Process Group
Parameters

P17.14 DO: Deviation Default: DO IT.DO5 Low


Alternative: DO
n/a
The output signal becomes active when the monitoring activates the control deviation
(P14.09 Event: Deviation).

This contact output is independent of the event class.

P17.15 DO: Volumetric Mode Default: n/a


Alternative: n/a
DO
The output becomes active if the scales are switched to a volumetric mode.

P17.16 DO: Keyboard Mode Default: n/a


Alternative: n/a
DO
The output becomes active when keyboard mode is preselected.

(The DISOCONT Tersus is operated using the operating console VHM).

13.3.2.18 Parameter Block 18 - Communication EasyServe


The parameters of this group define the parameters for serial communication with EasyServe via RS 232 or
RS 485. These parameters have no function if EasyServe is connected via Ethernet.

P18.01 Own Address Default: 1


Min: 1 Max: 1
Relevant only for EasyServe connection via RS 232 or RS 485.

This parameter is used for information only. The address cannot be changed.

Also refer to: P18.02 Baud Rate, P18.03 Format Data

P18.02 Baud Rate Default: 38400


Alternative: 38400
Relevant only for EasyServe connection via RS232 or RS485.

Data transfer speed. This parameter is used for information only. The speed cannot be
changed.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 103 -
Parameters

P18.03 Format Data Default: 8-N-1


Alternative: 8-N-1
Relevant only for EasyServe connection via RS232 or RS485.

Formats the serial data.

13.3.2.19 Parameter Block 19 - Communication Fieldbus


The parameters of this group define the communication procedure to be used to a higher-level plant control
system and configure the data link.

P19.01 Protocol Type Default: NO


Alternative: NO
Modbus-RTU
PROFIBUS DP
DeviceNet
Modbus-TCP
Ethernet/IP
Type of communication protocol. Some types of fieldbus need their respective fieldbus
card.
The manual Data Communication BV-H2448 contains further details on the data structures.

NO: It is possible to read via Modbus-TCP, although writing access is not processed.

Modbus: Modbus-RTU protocol; RS232, RS422 or RS485 interface; the VSS 28020 field-
bus interface card has to be installed.

PROFIBUS DP: Fieldbus interface card VPB 28020 must be installed.

DeviceNet: The VCB 28020 fieldbus interface card has to be installed.

Modbus-TCP: communication via Ethernet (RJ45 to X5).

Ethernet/IP: communication via Ethernet (RJ45 to X5). Can be cleared as an option.

P19.02 Timeout Host Default: 5 s


Min: 1 s Max: 600 s
Monitors the interface

A telegram from the host system will be expected within the time set if the timeout value is
greater than zero.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 104 - Schenck Process Group
Parameters

P19.03 Event: Cyclic Communication Default: A


Event Group: SY Number: 08

Cyclical serial communication with the higher-order plant control system has been inter-
rupted for longer than the timeout-period.

To rectify: check cable connections.

P19.04 Event: Acyclic Communication Default: A


Event Group: SY Number: 10

Incorrect data in the noncyclical communication to host computer.

Possible cause: poor programming of the host computer

P19.05 Check in Keyboard Mode Default: YES


Alternative: NO
YES
If the data link fails, this parameter can be used to deactivate fieldbus communication moni-
toring in keyboard mode so that keyboard mode can be
used for emergency operation without needing to sign off the fieldbus link.
This allows the scales to be operated even if the fieldbus link fails.

P19.06 Compatibility DISOCONT Master Default: NO


Alternative: NO
YES
Compatibility setting for the predecessor electronics systems DISOCONT or INTECONT
PLUS.

NO: Not completely compatible


YES: compatible, but with restricted data link compatibility for new functions

P19.07 Word Sequence Default: I:std/L:std


Alternative: I:std/L:std
I:swp/L:std
I:std/L:swp
I:swp/L:swp
The parameter determines the word sequence within a double word.

I denotes IEEE 754 values (floating-point values)


L denotes LONG values (4 byte integer values)
std will not swap the word order
swp will swap the word order

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 105 -
Parameters

P19.08 Byte Sequence Default: High - Low


Alternative: High - Low
Low - High
Determines the byte sequence in a data word.

P19.09 Configuration Default: FIXED_8_8


Alternative: NO_PARA_ID_3_6
PARA_ID_2_4
PARA_ID_3_6
FIXED_8_8
FIXED_4_4
Configuration of the data in the transfer protocol.

See the manual Data Communication (BV-H2220) for details.

'Variable' formats:
NO_PARA_ID_3_6: parameters are not transferred, 3 control values, 6 query values
PARA_ID_2_4: parameters are transferred, 2 control values, 4 query values
PARA_ID_3_6: parameters are transferred, 3 control values, 6 query values

'Fixed' formats:
FIXED_8_8: 8 control values, 8 query values
FIXED_4_4 4 control values, 4 query values

P19.10 Address Default: 1


Min: 1 Max: 254
Address of the device as a slave at the modbus.
Each address may be used at a bus once only.

P19.11 Resolution Default: 4096


Min: 1 Max: 32767
The maximum resolution in analog format or integer format of the measured value trans-
ferred.
The resolution is related to the nominal value on the respective day.

P19.12 Baud rate Default: 19200


Alternative: 2400
4800
9600
19200
38400
Data transfer rate at Modbus-RTU.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 106 - Schenck Process Group
Parameters

P19.13 Data Format Default: 8-O-1


Alternative: 8-O-1
8-E-1
8-N-1
Modbus-RTU always uses an 11-bit character frame.

Example: 8-O-1 means:


1 start bit, 8 data bit, odd parity, 1 stop bit

N = no parity, E = even parity)

P19.14 Physics Default: RS232


Alternative: RS485-2-wire
RS485-4-wire
RS232
Selects the electrical interface type. (Modbus-RTU)

P19.15 Address Default: 16


Min: 0 Max: 126
The address of the slave at the Profibus

P19.16 FLOAT-Format Default: IEEE


Alternative: IEEE
SIEMENS-KG
Information on the formats for all setpoints, measuring values and floating point parame-
ters.

P19.17 Compatiblity INTECONT Default: NO


Alternative: NO
YES
Compatibility to earlier PROFIBUS-Versions of INTECONT PLUS.
Relevant for replacement by INTECONT Tersus.

YES: Ident-No. 0524 is valid and GSD-file of INTECONT PLUS has to be used.

NO: Ident-No. 0C9B is valid and GSD-file of INTECONT Tersus has to be used.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 107 -
Parameters

P19.18 Identifier format Default: BYTE


Alternative: BYTE
WORD

The configuration bytes correspond to INTECONT PLUS if the parameter is on bytes. Oth-
erwise, the data are written in words. Consistency always refers to a data word or double
data word.

This parameter together with P19.19 PA32 compatible guarantees that there is no problem
exchanging with PROFIBUS Master in an existing system without having to adapt Master.

P19.19 PA32 compatible Default: NO


Alternative: NO
YES
YES: It is filled with ZERO bytes to 32 bytes with a defined data scope <32 bytes

P19.20 Address Default: 63


Min: 0 Max: 63
Address of the weighing electronics at the DeviceNet.

P19.21 Baud rate Default: 125K


Alternative: 125K
250K
500K
Data transfer rate of the DeviceNet.

P19.22 Access Rights Limitation FB Default: NO


Alternative: NO
FIRST WRITE
REMOTE IP
Determines for network protocol Modbus-TCP which master system may intervene as a
controller:

NO: No restrictions

FIRST WRITE: The subscriber that transmits the first write access gets the control rights.
The other subscribers may read only.

REMOTE IP: Control commands from the subscriber with the IP address given in P19.23
Remote IP Address FB only will be carried out.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 108 - Schenck Process Group
Parameters

P19.23 Remote IP Address FB Default: 192.168.240.250

IP address of the subscriber with control rights for Modbus-TCP.

Also refer to: P19.22 Access Rights Limitation FB

13.3.2.20 Parameter Block


Block 20 - Fixed mode configuration
Configuration of the data in fieldbus communication 'FIXED' mode.

This is only relevant when P19.09 Configuration = FIXED_8_8

P20.01 ID Preset Value 1 Default: 320

Selecting the first control command with ID 320 (decimal) in the Fieldbus telegram.

The other values can be configured as per the ID list in the Data Communication manual.

P20.02 ID Preset Value 2 Default: 352

Corresponds to P20.01 ID Preset Value 1

P20.03 ID Preset Value 3 Default: 384

Corresponds to P20.01 ID Preset Value 1

P20.04 ID Preset Value 4 Default: 592

Corresponds to P20.01 ID Preset Value 1

P20.05 ID Preset Value 5 Default: 594

Corresponds to P20.01 ID Preset Value 1

P20.06 ID Preset Value 6 Default: 0

Corresponds to P20.01 ID Preset Value 1

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 109 -
Parameters

P20.07 ID Preset Value 7 Default: 0

Corresponds to P20.01 ID Preset Value 1

P20.08 ID Preset Value 8 Default: 0

Corresponds to P20.01 ID Preset Value 1

P20.09 ID Read Value 1 Default: 752

Selecting the first value to be read from weighing electronics in the fieldbus telegram. The
number of the value (ID) can be found in the BV-H2448 Data Communication manual.

P20.10 ID Read Value 2 Default: 784

As P20.09 ID Read Value 1

P20.11 ID Read Value 3 Default: 1552

As P20.09 ID Read Value 1

P20.12 ID Read Value 4 Default: 1872

As P20.09 ID Read Value 1

P20.13 ID Read Value 5 Default: 1874

As P20.09 ID Read Value 1

P20.14 ID Read Value 6 Default: 1880

As P20.09 ID Read Value 1

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 110 - Schenck Process Group
Parameters

P20.15 ID Read Value 7 Default: 1884

As P20.09 ID Read Value 1

P20.16 ID Read Value 8 Default: 1894

As P20.09 ID Read Value 1

13.3.2.21 Parameter Block 21 - Ethernet


The parameters in this group control the Ethernet ports.

P21.01 IP Address Default: 192.168.240.1

IP address of the weighing electronics. If the control system is integrated into an Ethernet
network, the address must be chosen in agreement with the network administrator. In iso-
lated networks we recommend the factory setting 192.168.240.x. "x" allows for selection of
the system on the bus.

P21.02 Net Mask Default: 255.255.255.0

The net mask setting is based on the local network type.


In general the following setting is used: 255.255.255.0

See also: P21.02 Net Mask, system manual BV-H2406

P21.03 Gateway Default: 0.0.0.0

Generally no input is required. Usual value: 0.0.0.0

13.3.2.22 Parameter Block 22 - Data Logging


The parameters in this group are used to specify the time that material total data logging occurs.

P22.01 Hourly Total Time Default: 0 min


Min: -1 min Max: 59 min
Moment at which the totalizing counter begins logging in minutes from the start of a full
hour.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 111 -
Parameters

P22.02 Daily Total Time Default: 0 min


Min: -1 min Max: 1439 min
Moment at which the totalizing counter begins logging in minutes from the start of a day.

P22.03 Logger cycle time Default: 1 min


Min: 1 min Max: 1439 min
Logging cycle time for the Data Log Values selected by P22.04 ... P22.13.

P22.04 Data Log Value 1 Default: 752

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.05 Data Log Value 2 Default: 755

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.06 Data Log Value 3 Default: 1872

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.07 Data Log Value 4 Default: 1874

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 112 - Schenck Process Group
Parameters

P22.08 Data Log Value 5 Default: 1876

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.09 Data Log Value 6 Default: 1880

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.10 Data Log Value 7 Default: 1884

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.11 Data Log Value 8 Default: 1894

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.12 Data Log Value 9 Default: 0

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

P22.13 Data Log Value 10 Default: 0

Selects the process value for logging. The identification number of the values can be found
in the Data Communication manual.

See also: P22.03 Logger cycle time

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 113 -
Parameters

13.3.2.23 Parameter Block 23 - Configuration HMI Values


The parameters in this group define the process variables to be displayed on the 'Values' page of the operat-
ing panel of DISOCONT Tersus.
In INTECONT Tersus the display can be chosen by typing key "9".

EasyServe can be used for easy configuration or the settings can be made with the help of the allocation
map in the data description of the serial interface in the operating panel.

P23.01 HMI Value 01 Default: 1996

Identification number (ID) of the desired process variable.

P23.02 HMI Value 02 Default: 1944

Identification number (ID) of the desired process variable.

P23.03 HMI Value 03 Default: 1942

Identification number (ID) of the desired process variable.

P23.04 HMI Value 04 Default: 1950

Identification number (ID) of the desired process variable.

P23.05 HMI Value 05 Default: 0

Identification number (ID) of the desired process variable.

P23.06 HMI Value 06 Default: 0

Identification number (ID) of the desired process variable.

P23.07 HMI Value 07 Default: 0

Identification number (ID) of the desired process variable.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 114 - Schenck Process Group
Parameters

P23.08 HMI Value 08 Default: 0

Identification number (ID) of the desired process variable.

P23.09 HMI Value 09 Default: 0

Identification number (ID) of the desired process variable.

P23.10 HMI Value 10 Default: 0

Identification number (ID) of the desired process variable.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 115 -
Parameters

13.3.2.24
13.3.2.24 Parameter Block 24 - Second Display

P24.01 Second Display active Default: NO


Alternative: NO
YES
A DLZ055 or DLZ110 model large-scale display can be connected at interface X11.

The display shows the value selected in the upper line of INTECONT Tersus.

The symbols in the display and what they mean:


I : Feedrate
i : Relative Feedrate
Q : Belt Load
q : Relative Belt Load
v : Belt Speed
1 : Totalizer 1
p : Perc. setpoint factor
x : Deviation
2 : Totalizer 2
3 : Totalizer 3
b : Batch Setpoint
d : Batch Residual Amount
N : Batch No.
C : Batch Actual Value
B : Reload Setpoint
D : Reload Amount
P : Setpoint
E : External Setpoint

The large-scale display can only show the dimensions kg or t.

If the letter space is illuminated as a full-surface block, this is an indication that the value
shown is invalid.
Either it is not possible to show the desired format or the unit is in the operator dialog.
Beyond this, the block is also shown to indicate that printing is active.

P24.02 Baud rate Default: 9600


Alternative: 1200
2400
4800
9600
19200
38400

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 116 - Schenck Process Group
Parameters

P24.03 Data Format Default: 8-N-1


Alternative: 7 Bit Even
8-N-1
8-O-1
8-E-1

P24.04 Physics Default: RS232


Alternative: RS485-2-wire
RS485-4-wire
RS232

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 117 -
Event messages

14 Event messages

DANGER
Events register abnormal states, e.g. malfunctions or exceeded thre-
shold values.
A running feeder can be a hazard to people or to property.
The cause of event messages must be corrected before events are ac-
knowledged!

Event messages are grouped together.


Group Identifier Event Domain

SY Internally monitoring the control system


SC Irregularities in operator control or peripheral control
WE Fault in the external power electronics
MF Fault in the bulk material flow
IL Messages from interlocking with system control
CO Internal controller malfunction message
CA Adjustment fault
HI Threshold value exceeded upwards
LO Threshold value exceeded downwards

Tab. 4 : Event groups

Note: In the following list, parameters related to the indicated event are shown in parentheses.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 119 -
Events

15 Events

15.1 Events Details

15.1.1 Event Group: Calibration


CA01 Event: Error LC Input (P13.06)
The load cell cable is improperly connected, not connected or has been interrupted.
The load cell may be faulty.

Steps to take:
- check the cabling and the load cell
- check the load cell

Note:
The power supply must be switched off and on again if the scales still cannot be
switched on even after the error has been rectified.

CA02 Event: Tachometer Input (P13.03)


The input frequency is greater than 3,000 Hz.

CA05 Event: Linearization Error (P15.10)


Not a monotonically increasing curve.

A monotonically increasing compensation curve is monitored:


- when the linearization is switched on,
- when the parameter is altered

15.1.2 Event Group: Controller


CO01 Event: Controller Limited (P14.10)
The actuating variable of the feed rate regulator has reached the upper response
threshold. After a time the message HI-5 (control deviation) is also sent.
1. No material is flowing or material flow is irregular.
2. The external output regulator has been incorrectly set.

Steps to take: check the material discharge and the actuating variable (service value
Y). At the nominal feed rate, Y should be between about 10...14 mA.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 121 -
Events

15.1.3 Event Group: Electrical System


WE01 Event: Power Failure (P13.01)
This event is identified once the power supply is restored.

The scales will not switch on automatically, regardless of the event class. The event
must first be acknowledged and the command to start given again before the scales
will restart.

WE09 Event: Namur Error Tacho (P13.04)


A short-circuit or break in the cable to the velocity sensor.

The internal velocity value is set to 0 if a Namur error occurs.


The frequency display (service value) is still active.

The event message has to be on IG when connecting up other equipment (not Na-
mur). External Namur adapters and resistance wiring, etc. are not needed.

WE10 Event: Namur Error Belt (P13.05)


A short-circuit or break in the cable of the belt circuit sensor (BIC).

15.1.4 Event Group: Interlock


IL01 Event: Run Disabled (P13.07)
No release signal from the source determined by P16.01.

If this event is pending then the downstream transport equipment is most likely not
switched on.

15.1.5 Event Group: Material Flow


MF06 Event: Out of Tolerance (P09.05)
The batch result is outside the tolerance range.

Possible causes:
- highly erratic material flow
- altered feeder discharge behavior
- error in weight calculation due to disturbance forces

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 122 - Schenck Process Group
Events

15.1.6 Event Group: MAX


HI01 Event: LC Input > MAX (P13.08)
The load acting on the load cell is greater than 110 % of the sum of the nominal
loads of the load cells.

Measuring range end:


125 % for load cells with 2.85 mV/V
175 % for load cells with 2 mV/V

Possible causes:
- Shunt forces or compression ratios bring about incorrect load cell loading
- incorrect cabling
- faulty load cell

HI02 Event: Actual Flow Rate MAX (P06.04)


Actual feed rate greater than the maximum value set in P06.03 Limit: Actual Flow
Rate MAX

Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too large

HI03 Event: Belt Load MAX (P06.08)


The belt load is greater than the maximum value set in P06.07 Limit: Belt Load MAX

Possible causes:
- bulk material shooting out of the discharge chute
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment

HI04 Event: Speed MAX (P06.12)


The belt speed is greater than the maximum value set in Limit: Speed MAX

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 123 -
Events

HI05 Event: Deviation (P14.09)


Maximum control deviation exceeded. The actual feed rate has deviated to far from
the setpoint over too long a period of time.

Possible causes:
- Fault in material handling: the bulk solids flow irregularly or cannot be discharged
sufficiently well.

- the controller has at times come against its limits


- error in the electronics
- check the cable to the external output regulator and to the motor. Check the output
regulator settings (current limiting, speed range)

- Calibration error: the controller was set at such a critical value during initial calibra-
tion that minor changes in the overall properties of the system lead to unreliable op-
eration.

15.1.7 Event Group: Mechanic


WM02 Event: Slip (P12.14)

WM03 Event: Belt Skew (P12.12)


Belt has run off-center. Feeder is no longer operable.
Action: See Event: Belt Drift
Related threshold: Belt Skew

WM04 Event: Belt Drift (P12.10)


Belt out of tolerance.
Action:
1. Clean tail and drive pulleys.
2. Align belt.
Monitoring can be faulty. Watch belt circuit sensor service value; if need be, remedy
fault.
Related threshold: Belt Drift

15.1.8 Event Group: MIN


LO01 Event: LC Input < MIN (P13.09)
The load cell load is less than 3 % of the sum of the load cell nominal loads.

Possible reasons:
- force shunts or pressure ratios can reduce significantly the load on the load cell
- incorrect cabling
- faulty load cell

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 124 - Schenck Process Group
Events

LO02 Event: Actual Flow Rate MIN (P06.02)


Actual feed rate lower than the minimum value set in Limit: Actual Flow Rate MIN

Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment
- feed rate setpoint too low

LO03 Event: Belt Load MIN (P06.06)


The belt load is less than the minimum value set in Limit: Belt Load MIN

Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equip-
ment

LO04 Event: Speed MIN (P06.10)


The belt speed is less than the minimum value set in Limit: Speed MIN

15.1.9 Event Group: Sequence Monitoring


SC01 Event: Setpoint Limited (P13.11)
Cause of the event:
Depending on the respective mode of operation:
a) The setpoint is limited to the nominal feed rate (P02.02 Nominal Flow Rate) in
gravimetric operation.
b) The setpoint is limited to three times the value of the nominal feed rate (P02.02
Nominal Flow Rate) in volumetric operation.

SC02 Event: Stand-By (P06.14)


The scale is in stand-by operation. That means that the setpoint is less than the limit
set in P06.13 Stand-By Limit Value. The feeder drive is switched off. The 'running'
state will still be displayed.

This function protects the motor from overheating at very low speeds or when idling.

Steps to take:
Key in the larger setpoint and check P06.13 Stand-By Limit Value.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 125 -
Events

SC03 Event: Maint.Feeder Run (P11.04)


The sum of the runtimes of the conveying elements is greater than the time 'Scales
ON' (P11.03 Maintenance Feeder Run).

A message occurs after each expired time interval. The message may indicate ser-
vice work required.

SC04 Event: Maint. Electric (P11.02)


The sum of the times during which the mains voltage is on is greater than the time
'voltage ON'.

A message occurs after each expired time interval. The message may indicate ser-
vice work required.

See also: P11.01 Maintenance Electric

SC05 Event: External Event 1 (P13.12)


External interference signal at fault input 1.

Possible cause: depends on the external cabling. Usually: an error in the main drive

SC06 Event: External Event 2 (P13.13)


External interference signal at fault input 2.

Possible cause: depends on the external cabling.

15.1.10 Event Group: System Message


SY01 Event: Memory (P13.02)
The program and parameters memory are checked cyclically. An error has occurred
during that. The scales will no longer function correctly.

Steps to take:
- load the factory settings
- Normally the hardware has to be replaced.

SY08 Event: Cyclic Communication (P19.03)


Cyclical serial communication with the higher-order plant control system has been
interrupted for longer than the timeout-period.

To rectify: check cable connections.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 126 - Schenck Process Group
Events

SY09 Event: License Violation (P13.14)


The option selected in the P19.01 Protocol Type parameter is not activated.
It has to be cleared. Refer to the Option activate function

SY10 Event: Acyclic Communication (P19.04)


Incorrect data in the noncyclical communication to host computer.

Possible cause: poor programming of the host computer

SY14 Event: Simulation active (P13.10)


Simulation operation is on.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 127 -
Hardware and technical data

16 Hardware and technical data

16.1 Technical Data and


and Replacement Parts

Display LCD graphic display with adjustable brightness


Keyboard 22 buttons
Supply voltage 24 VDC +50 % / -25 %, max. 20 VA
Temperature range Operating temperature: -40 °C to +60 °C
Bearing temperature: -40 °C to +80 °C
Legal for trade operation: -10 °C to +40 °C
Electromagnetic ambient E2 (OIML D11)
conditions
Scales connection Power supply: 6 V alternating voltage
Load cell impedance: R min 80 Ω
Length of cable: max. 1000 m
The housing Built-in IP54 control panel case with optional retainers for IP65
Binary inputs 5 optocouplers 18 - 36 VDC, model 5 mA
1 NAMUR, and 1 NAMUR/voltage 0.04 - 3,000 Hz
Binary outputs 8 relays, max. 230 V, 8 A ohm. / 1 A inductive
Pulse output 1 optocoupler for totalizing counter 24 V, 0.1 A, max. 10 Hz
Analog outputs 2 x 0(4)-20 mA, load max. 500 Ω, galvanically separated
Analog input Current 0(4)-20 mA or voltage 0 - 10 V, input impedance 100 Ω, galvanically
separated
Serial Interfaces: Interface 1: EasyServe
Interface 2: Printer
Interface 3: Large-scale display
VNT0650 power supply 85 – 264 VAC / 24 VDC, 1.1 A
Internal (optional)
fieldbus (optional) Can be selected from: Modbus, PROFIBUS DP, DeviceNet, Ethernet/IP
Analog signal card 2 analog outputs 0(4)-20 mA, load max. 500 Ω,
(optional) VEA 20451 galvanically separated, joint potential reference
2 analog inputs 0(4)-20 mA or voltage 0 - 10 V, input impedance 100 Ω,
galvanically separated, joint potential reference

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 129 -
Hardware and technical data

Wall-Mounted Housing IP65 wall-mounted housing, 380 mm x 300 mm x 236 mm


Power supply 85 - 264 VAC / 24 VDC, 2 A
Power supply, external, desk-top 85 – 264 VAC / 24 VDC, 1.25 A
model
Event printer Printer with serial RS232 interface and system cable
Large-scale displays Can be selected from: VLD 20100 (LED, 100 mm);
VLZ 20045 (LCD, 45 mm); VLZ 20100 (LCD, 100 mm)
Control cubicles and Control cubicles and equipment frames for several
equipment frames INTECONT Tersus units with or without feed

Description Type Material Nummer


Front-of-panel unit with VWF 20650 software for the weighfeeder VEG 20650
Basic Equipment V082001.B01
with Modbus option V082001.B02
with PROFIBUS option V082001.B03
with DeviceNet option V082001.B04
with Ethernet/IP option V082001.B05

Modbus VSS 28020 V081902.B01


PROFIBUS VPB 28020 V081901.B01
DeviceNet VCB 28020 V081903.B01
Ethernet/IP clearance VET 20700 V040035.B01

Further Options
Installed power supply and mounting set V082050.B01
Analog signal card with 2 analog inputs and 2 analog outputs VEA 20451 V054098.B01
IP65 protection type for front-side control panel installation V082039.B01

Software
EasyServe VPC 20150 E144541.01

Large-scale displays
Large-scale 5-digit display, LED, 100 mm digit height VLD 20100 V090252.B01
Large-scale 6-digit display, LCD, 45 mm digit height VLZ 20045 V067304.B01
Large-scale 5-digit display, LCD, 100 mm digit height VLZ 20100 V066611.B01

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 130 - Schenck Process Group
Hardware and technical data

16.2 Connection Diagrams

Fig. 8: Connection diagram for voltage supply

Fig. 9: WZ connection diagram and tachometer

Fig. 10: Connection diagram for inputs and outputs 1

Fig. 11: Connection diagram for ITE inputs and outputs 2

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 131 -
Hardware and technical data

Fig. 12: Serial interface connection diagram

Fig. 13: Modbus connection diagram

Fig. 14: ITE PROFIBUS connection diagram

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 132 - Schenck Process Group
Hardware and technical data

Fig. 15: DeviceNet connection diagram

16.3 Replacing
Replacing INTECONT PLUS with INTECONT Tersus

In the beginning, INTECONT PLUS equipment was produced as the FIP model and then as the VEG 206xx
model starting in 2003.
INTECONT Tersus as the follow-up unit was also kept very similar to its predecessors in terms of its hard-
ware connections.

The EasyServe adjustment program (VPC 20150) can be used for INTECONT Tersus from version 19 which
makes it possible to conveniently change over from VEG to INTECONT Tersus.

The following tables show the connector pin assignment of FIP, VEG and INTECONT Tersus opposite one
another for all physical signals.

Power Supply
Signal FIP and
VEG and
INTECONT Tersus

0V X2 1
24 V in X2 2

0V X2 3
24 V out X2 4

Load cell
Signal FIP VEG INTECONT Tersus

OUT1 X5 3 X7 3 X10 3
REF1 X5 4 X7 4 X10 4
IN2 X5 5 X7 6 X10 6
IN1 X5 6 X7 5 X10 5
REF2 X5 7 X7 7 X10 7
OUT2 X5 8 X7 8 X10 8

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 133 -
Hardware and technical data

Digital Outputs, DO
Signal FIP VEG INTECONT Tersus

DO1 X1 1,2
DO2 X1 3,4
DO3 X1 5,6
DO4 X6 1,2 X8 1,2 X13 9,10
DO5 X6 3,4 X8 3,4 X13 7,8
DO6 X6 5,6 X8 5,6 X13 5,6
DO7 X6 7,8 X8 7,8 X13 3,4
DO8 X6 9,10 X8 9,10 X13 1,2

Digital Inputs, DI
Signal FIP VEG INTECONT Tersus

DI1 X3 1,2 X3 1,2 X4 1,2


DI2 X9 1,2 X3 3,4 X4 3,4
DI3 X9 3,4 X6 6,7 X4 5,6
DI4 X9 1,2
DI5 X9 3,4
Namur sensor DI6 X3 5,6 DI6 X3 5,6 DI4-N X9 1,2 Namur
Namur tachometer 1 DI7 X5 1,2 X7 1,2 DI5-N X10 1,2
Open collector tachometer —- —- DI5-T X9 3,4
1 DI6 X12 3,4
DI7 X12 1,2
X3 3,4
Vol. Synchronous

Analog outputs AO
Signal FIP VEG INTECONT Tersus

A01 X9 9,10 X6 4,5 X8 4,5


A02 X9 11,12 X9 5,6 X12 8,9

AO3 —- —- Optional VEA X30


AO4 —- —- Optional VEA X30

Analog inputs AI
Signal FIP VEG INTECONT Tersus

AI1 X11 1,2,3 X6 1,2,3 X8 1,2,3

AI2 —- —- Optional VEA X30


AI3 —- —- Optional VEA X30

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 134 - Schenck Process Group
Hardware and technical data

Printer
Signal FIP VEG INTECONT Tersus

Shield X8 1 X10 1 X7 1
TX X8 2 X10 2 X7 2
RX X8 3 X10 3 X7 3

Large-scale display
Signal FIP VEG INTECONT Tersus

Shield —- —- X11
TX —- —- Pin assignment
RX —- —- after RSxxx selec-
tion

EasyServe
Signal FIP VEG INTECONT
Tersus

Shield —- X4 5 or X5 1 X6 1
TX —- X4 2 or X5 2 X6 2
RX —- X4 3 or X5 3 X6 3

Pulse output
Signal FIP VEG INTECONT Tersus

24 V X9 5 X6 8 —-
Open collector X9 6 X6 9 X3 1
Open Emitter X9 7 X6 10 —-
0V X9 8 X6 11 X3 2

Fieldbus connection (Modbus, PROFIBUS and DeviceNet)


Signal FIP VEG INTECONT Tersus

Separate field- —- X20 X20


bus card

Modbus is connected to X7 with FIP

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 135 -
Hardware and technical data

16.4 PROFIBUS module (VPB8020)

The module may be attached to the base card of the device to make an interface with the PROFIBUS.

Features of the module:

Isolation: Optocoupler
Power supply: 5 VDC internal
Electricity supply: max. 310 mA
Bus connection plug XP1: 9-pin Sub-D female
XP3: Phönix 5p MSTB 3.5; max. 1.5 mm²

Arrangement of the components:

Fig. 16: VPB8020 PROFIBUS module

Settings:

W100 Determining the power supply:


The platform W100 always remains in position 2-3
W150 Bus termination:
The bus termination resistances must be activated at the first and last station of the bus. This is done
W151 by setting all three jumpers on the board (W150, W151, W152) to position 1-2. By default the
W152 resistances are not activated (position 2-3).
Bus address:
The addresses are set using parameters.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 136 - Schenck Process Group
Hardware and technical data

XP1 XP3
Pin Signal Signal
*
1 - B-line, positive RS485 RxD/TxD
**
2 - A-line, negative RS485 RxD/TxD
*
3 B-line, positive RS485 RxD/TxD GND BUS
4 RTS (Request to Send) +5 V BUS
5 GND BUS Shielding
6 +5 V BUS -
7 - -
**
8 A-line, negative RS485 RxD/TxD -
9 - -
Housing Bus Cable Shield -

Tab. 5 : Bus connection plug

* Wire color red.


** Wire color green.

LEDs H110, H120:


There is one identical-function double-LED (H110, H120) for each bus connection plug (XP1, XP3).
Example H110:

Fig. 17: LEDs - VPB8020 front view

Status Display

Off Not online/no power supply


Green Online, data transfer
Green, flashing Online, clear mode
Red, flashing (1 Hz) Parameterisation fault
Red, blinking (2 Hz) Configuration error

Tab. 6 : LED 'Operating Mode' (below)

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 137 -
Hardware and technical data

Status Display

Off No power supply or not initialized


Green Initialized
Green, flashing Initialized, result of diagnostic test pending
red Exception error

Tab. 7 : LED 'Status' (above)

16.5 DeviceNet Module (VCB8020)

The module can be attached to the mainboard to create an interface to the DeviceNet.
Features of the module:

Isolation: Optocoupler
Power supply: 5 VDC internal
Electricity supply: max. 250 mA
Bus connection plug XC1:Phönix 5p MSTB 5; max. 2.5 mm²
XC3: Phönix 5p MSTB 3.5; max. 1.5 mm²

Arrangement of the components:

Fig. 18: DeviceNet module VCB8020

Settings:

W100 Determining the power supply:


The platform W100 always remains in position 2-3
W160 Bus termination:
The bus termination resistances must be activated at the first and last station of the bus. This is done
by applying the W160 jumper to the position 1-2.
By default the resistances are not activated (position 2-3).
Bus address and Baud rate:
Both values are set using parameters.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 138 - Schenck Process Group
Hardware and technical data

XC1 XC3
Pin Signal Signal

1 V-
2 CAN_L
Ditto:
3 Shielding
4 CAN_H
5 V+

Tab. 8 : Bus connection plug

LEDs H110, H120:


There is one identical-function double-LED (H110, H120) for each bus connection plug (XC1, XC3).
Example H110:

Fig. 19: VCB8020:XC1 DeviceNet module front view

Network status Display


Off Not online/no power supply
Green Online, one or more connections established
Green, flashing Online, no connection
red Critical connection error
Red, flashing (1 Hz) One or more connections have been timed out
Alternating red-green Self-test

Tab. 9 : LED 'Network Status' (above)

Module status Display


Off No power supply
Green Exchange of user data
Green, flashing Incorrect configuration
red Non-repairable error
Red, flashing Repairable error
Alternating red-green Self-test

Tab. 10 : LED 'Module Status' (below)

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 139 -
Hardware and technical data

16.6 Modbus Interface VSS8020

The interface card is an isolated, serial interface. The type of the interface is set using control unit parame-
ters and using jumpers in the plug. Both plugs are electrically parallel.

Features of the module:


Isolation: Optocoupler
Power supply: 5 VDC internal
Current supply Max. 250 mA
Connector to bus XS2: Phoenix 7p max. 1.3 mm²
activation XS3: Phoenix 7p max. 1.3 mm²

Tab. 11 : Modbus module properties

Arrangement of the components:

Fig. 20: VSS8020 Modbus module layout drawing

Pin assignment serial interfaces:


Pin RS232 RS422 RS485

1 GND GND GND


2 TX Tx B RTx A
3 RX Rx B Jumper to pin 2
4 Rx A Jumper to pin 5
5 TX A RTx B
6 Jumper to pin 4 for bus termination
7 Jumper to pin 3 for bus termination

Tab. 12 : Pin assignment modbus serial interface

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 140 - Schenck Process Group
Hardware and technical data

16.7 LED diagnosis

Status LED Color Function

LNK Green Ethernet is connected


FDX Yellow Full Duplex
100 Red 100 MBaud (otherwise 10 MBaud)
ADR Green Measuring hardware is active
IDL Yellow The processor's idling time, flashes during operation
DIA Red Unused
PWR Green Power OK
SYC Yellow System cycle, flashes during operation
ERR Red Fault display, set by the system software

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 141 -
Web server functions

17 Web server functions


functions

17.1 Web Server

The unit is equipped with a web server that provides a homepage for the scale. This homepage is available
in English only.
Equipment needed: The PC has an Ethernet link to the equipment.
Establishing the connection: The IP address of the controller must be entered into the browser address
line.

Various data from the controller can be called up in the left-hand navigation bar.
Navigation entry Function

Events Most recent stored events (alarms, warnings, etc.)


Parameter changes Most recent parameter alterations
Command Log List of certain commands, e.g. start / stop
Totalizer hourly Table of hourly-saved totalizing integrators / counters.
The minute after the full hour at which the saving occurs can be set in P22.01.
Totalizer daily Table of daily-saved totalizing integrators / counters.
The time of saving from 00:00 h is set in P22.02.
Totalizer Table of totalizing integrators / counters saved on the command.
Data logger 1 / 2 Table of recorded measured values. The sampling interval can be set using P22.03.
Up to 10 process variables can be selected to be recorded using P22.04 - P22.13. It
starts recording by activating in the Mode operating zone.

Tab. 13 : Functions available on the controller web page

Memory depth is approx. 1,000 entries. All entries are recorded with the entry time. The table is refreshed
only when it is called up. These readings can be exported by selecting, copying and inserting them into a file
in the PC for evaluating with standard programs.

17.2 System Information

The system data are provided here. You can find files such as the software version, hardware version,
IP address. "Serial No." or "MAC-ID" are the names of the serial number on the CPU board.
Together with the 'mainboard' data, this data also supplies the user with the 'fieldbus' configurations and
settings. In particular the amount of bytes for the read and transmitted data.
This page is still undergoing development and may differ from the image shown here.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 143 -
Appendix

18 Appendix

18.1 Service Values

Detailed information on the system is contained in the service table. The call-up does not interfere with any
weigh functions.

Call up the function block

Setup
Service Values

Scroll through the service values

Exit the service values

Setup
Standard Values

Readouts:

Vxx 2065y-yyy Software version

2011-08-01 08:01:58 Date and time


VOL OP Operating mode when active
(VOL = volumetric, OP = keyboard mode)
DO = 1 1 1 0 0 0 0 0 Relay Outputs Switching State "1" = Contact closed
"0" = Contact open
DI = 1 1 1 1 - 0 1 Inputs Switching State "1" = Contact closed
"0" = Contact open

additional for Namur signals "+" Short circuit


"-" Cable breakage
"1" = Sensor covered
"0" = Sensor clear
Additional for legal for trade "1" = Calibration switch active
belt weighers "0" = Calibration switch inactive
Analog Output 1 4.15 mA Output current of the analog output 1
Time Voltage ON: 22 h Duty cycle of power supply
Monitoring: parameters P11.01

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 145 -
Appendix

Time Feeder ON: 19 h Duty cycle of scales and belt conveyor.


Monitoring: parameters P11.03
Tachometer 1 96.655 Hz velocity sensor input frequency.
The frequency must be within the range 0.04 ... 3000 Hz.
Utilization LC 30.988 % Load on load cells sourced from the sum of the load cell nominal capac-
ities.
The weigh cells are overloaded if the values exceed 100 %.
The message H4: LC Input > MAX occurs upwards of 110 %.
Loadcell 1 0.383257 mV/V Non-standardized output value of the weigh cell amplifier (gross).
The value is recorded before the belt influence compensation function
and before the delay at the dispatch point.
CSUM: Flash 1 Check sum of the scale software
CSUM: Flash calc. 1 Check sum of scales software. recalculated
Controller Magnitude 1.44 mA Controller output as specification for the drive
Actual Tare 27.000 kg/m Currently stored tare value
Temperature 22.5 °C Current temperature in the equipment
Deviation abs. 0.03 % Current value of the controller deviation
ETHERNET/IP: OK OK if ETHERNET/IP option is cleared; otherwise NO

The values listed are exemplary.

18.2 Set option


There is the option of clearing fieldbus coupling ETHERNET/IP by software. This unit issues an unambi-
guous ID (the MAC address). An activation code is generated from this ID that is then keyed into the unit. If
the optional activation is required on devices which have already been delivered, the data is transferred to
the Schenck process, and the generated activation code is reported back.
The Option activate function is only accessible when the fieldbus protocol is on NO or ETHERNET/IP.

Call up the function block

Parameter
Option activate

Key in password


Abort possible at any time

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 146 - Schenck Process Group
Appendix

The MAC-ID (example: 00:15:84:01:03:ee) and selected option


(example:ETHERNET/IP) are shown.

If there is no clearance, memorize the value and report to Schenck Process.


Code: Key in the clearance code from Schenck Process
ETHERNET/IP Message after input of a valid activation code or error message
and abort

18.3 Function Check

Turn on the scale


The switch-on process depends on the preselected P02.06 Feeder Start source.
Analyze any event messages that may appear and rectify the fault.
Call up the function Setup - Service Values

a) tachometer
The output frequency of the tachometer generator has to be less than 3,000 Hz when the measurement is
activated. The value must approximately correspond to the information in the data sheet. If the frequency
fluctuates substantially at a constant belt speed, the Namur sensor of the tachometer generator is probably
too far away.

b) wz
The non-standardized output value of the load cell amplifier may not be greater than 2.85 mV/V even at the
rated load of the weighbridge. It must change if the weighing platform is placed under load (e.g. the calibra-
tion weight).

Value too large:


– load cell overloaded
– tare equalization weight incorrectly set (if available)

Negative Value:
– load cell connected incorrectly
– tare equalization weight incorrectly set

c) aw
Load of the load cell in percents with reference to the total of the rated loads of the load cell.
The value can be analyzed as per item b). aw should not be greater
than 100 % at the rated belt load.

If it is not possible to bring about a reasonable operational state in spite of all efforts, the test plug chapter
might help.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 147 -
Appendix

18.4 Test Connector

A basic function control of the INTECONT can be carried out using a simple test connector. In this way an
error can be limited between the load cell with wiring and electrical equipment.
1. Connect the connector as shown in the diagram
2. Disconnect load cell connector X7 and plug in the test connector instead

The dimensioned resistances given result in the following service values:


1. Load cell signal (lc) approx.1.1 mV/V
2. Load cell usage factor (aw) approx. 55 % if C03 = 2 mV/V and approx. 39 % if C03 = 2.85 mV/V
If lc is in the listed areas, the pick-up input is free of errors.

Note:
With other resistances R1 and R2, the LC Raw is calculated to 500 * R2 / R1 [mV/V].
The test plug is available as an accessory.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 148 - Schenck Process Group
Appendix

18.5 Sources of Setpoints and Switch Signals


Setpoint can be set and feed on and off commands can come from different sources.

Fig. 21: Setpoint and switching-in source changeover VWF

The sources are preselected with parameters in the Control Sources group.
You can use the Keyboard mode function to change over between the preselected sources and the key-
board (Keyboard Mode ON/OFF).
Parameters Function Range

P02.06 Switch-on source Keyboard (OP)


Serial (FB)
Contact (DI)
P02.07 Setpoint source Keyboard (OP)
Serial (FB)
Analog input (AI)
FALSE Setpoint with a percentage quantifi- Switched off (n/a)
er Keyboard (OP)
Analog input (AI)

The effective setpoint is displayed on the operating panel. The setpoint entry field will only be active if the
parameters permit entry with the operating panel.
A new window for entering the relative portion will open when the setpoint field is touched if the relative set-
point qualifier was preselected using the operating panel.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 149 -
Appendix

Setpoint Synchronization:
The external setpoint will be taken if the source is switched from an external source to the keyboard (OP).
The external source will take effect in the opposite direction.
On / Off Synchronization:
The on/off switch status is preserved if switching from an external source to the keyboard (OP). The external
source will take effect in the opposite direction.
Mains Power OFF:
The keyboard setpoints are stored.

Fig. 22: VWF switch-on sequence

Time Condition

1 Feeding does not begin with the on command as the all-clear signal has not been given.
2 To start, the scales requires the increasing slope of a start command.
3 Feeding is started with the increasing slope.
4 Feed rate control will operate in volumetric mode during the startup time defined in P14.15 (also refer
to: Volumetric / (Volumetric Synchronous) / Gravimetric Modes of Regulator Operation).
5 Changing over to normal gravimetrically controlled feeding operation (assuming gravimetric mode was
selected before). Regulation stays in volumetric mode (assuming the operator selected this ahead of
time).
6 Feeding will be switched off if no all-clear signal is received (or if the switch on command was re-
moved).
7 The feed rate will continue being calculated for the time set in P07.06 in order to capture the last trick-
ling material. Calculation will then stop; the counter will retain the value previously reached even if the
fill level in the hopper changes.

Tab. 14 : States and points in time in the flow chart

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 150 - Schenck Process Group
Appendix

Parameters Function

P14.15 Duration of volumetric startup time


P07.06 Duration of continuing feed rate calculation once feeding has been switched off (stopping
time counter)
P02.06 Source of on signal
P16.01 Source of all-clear signal
P17.13 Scales signal output switched on

Tab. 15 : Relevant parameters

Behavior if alarm Triggered:


The feeder drive is switched off immediately if an alarm is triggered. The feed rate will continue being calcu-
lated for the time set in P07.06.
Measurement and display:
The measuring load will always be calculated and displayed. The feed rate will only be calculated with the
feeder switched on and during the stopping time (P07.06).

18.6 Regulation

Weighfeeder
A weighfeeder draws material from a storage hopper. The set and actual feed rates are compared and the
difference conducted to the controller. This changes the speed of the conveyor belt until the actual value is
equal to the setpoint.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 151 -
Appendix

Belt weigher with controlled material prefeeder


The feed rate is set to the setpoint by changing the belt load. The belt speed is normally constant. An exter-
nal three-point step controller is needed with position-regulated prefeeders.

Belt weigher with a constant load


A non-regulated material prefeeder charges a conveyor belt. The belt speed is adapted by the controller so
that the belt load always equals the rated value. The fact that the weighing system always has the same
working point means it can achieve a high level of measuring accuracy. The feed rate at the discharge is
equal to the feed rate of the prefeeder.

An external performance level with anchor tension or speed regulation is needed for the drive in all cases.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 152 - Schenck Process Group
Appendix

Modes:

Gravimetric
Controlled operation as described above

Volumetric
Uncontrolled operation, i.e. the belt speed or prefeeder is controlled proportional to the setpoint. The meas-
ured feed rate or actual belt load value is not taken into consideration.

Volumetric Synchronous
In contrast to volumetric operation, it is not the rated belt load that is used for calculating the set belt speed.
Instead, the measured belt load is used before changing over. That means that changing over is jerk-free.

The operating modes can be selected with a dialog function. Special start-up and empty running functions
can also be activated.

Operating sources:
Some operating functions can be triggered by various sources. For example, setpoint specification, turning
on and off, resetting the counter and acknowledging events.

18.7 Measuring at the Discharge Point VAP

Measuring on the VAP discharge point shifts the measuring point of the weighbridge to the discharge point of
the material by means of a time-lag device. The totalized amount of material dispatched is directly recorded.

Measuring at dispatch: VAP

Preconditions:
▪ The length ratio from the centerline of the weighing platform to the material dispatch to the overall belt
conveyor length is known.
▪ Key in the length ratio in percent in parameters Platform Dis.Length P12.02.
▪ Activate VAP via VAP Active P12.01 parameters.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 153 -
Appendix

18.8 Belt Monitoring

Drift and slippage monitoring is built into the functions. Monitoring is activated with the P12.03 Belt Sensor
Active parameter.

The programs can only be used for belt monitoring if there is a belt circuit sensor (Namur transmitter) and a
triangular metallic sensor surface in the conveyor belt. Otherwise, the aforementioned parameter and
P12.05 BIC Active parameters have to be on NO.

Procedure for activating belt monitoring


1. Set the parameters P12.03 Belt Sensor Active to YES
2. Key in the sensor length in P12.06 Sensor Length parameters
3. Key in the sensor width in P12.07 Sensor Width parameters
4. Set P12.08 Sensor Offset parameters to 0
5. Call up the calibration function LB: Pulses/Belt

18.9 BIC belt impact compensation

Even excellent conveyor belts are never completely even and they become heavier and stiffer especially on
the seams. This is why it is normally only possible to guarantee a high level of accuracy over entire belt cir-
cuits (i.e. over the mean).
An additional belt circuit sensor and metallic marking flag in the belt enable the unit to record this impact and
constantly correct it.
That substantially boosts the short-term accuracy of the scale.
Belt impact measurement is constant to take changes in regular operation into account. Compensation
adapts itself whenever material is conveyed.
Relevant parameters P12.05 BIC Active, P12.03 Belt Sensor Active, P12.04 DI: Source Belt Sensor.

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 154 - Schenck Process Group
Appendix

18.10 Linearization

The belt loading does not usually need to be linearized. It only makes sense with major belt load fluctuations
and simple weighing mechanisms.

Calibration with calibration weights:


Apply calibration weight Q1, start the scales and call up the zeroing program.
Key in the final result of zero setting program and key in later in Linearization I1 parameters.
Cancel the program and do not exceed the result.

Key in the result of the formula q1 = Q1 / L * 100 % / q0 in Linearization S1 parameters.


Where
Q1: calibration weight in kg
L: P03.05 Effective Platform Length
q0: P04.01 Nominal Belt Load

Repeat work processes 1 - 3 with increasingly large calibration weights for the other linearization points.

Calibration using material:


Perform a material check with a belt load q1.
Read the mean of the belt load q1(a) on the equipment and key it into the Linearization I1 parameters.
Key in the result of the formula q1(s) = q1(a) * Ms / Ma into the Linearization S1 parameters.
Where
Ms: conveyed quantity of material in kg
Ma: quantity of material read on the equipment in kg

Repeat work processes 1 - 3 with increasingly large calibration weights for the other linearization points.

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 155 -
Index

Index
>0 Zero ON/OFF .............................................................................................................................................................. 68
2. Password ...................................................................................................................................................................... 66
Abbreviations .................................................................................................................................................................... 54
About This Manual .............................................................................................................................................................. 1
Access Rights Limitation FB............................................................................................................................................ 108
acknowledge event information ......................................................................................................................................... 19
Activation code ................................................................................................................................................................ 146
Adaptation 1 ...................................................................................................................................................................... 97
Adaptation Factor .............................................................................................................................................................. 82
Additional device ............................................................................................................................................................... 81
Address ........................................................................................................................................................... 106, 107, 108
Afterflow Totalizer ............................................................................................................................................................. 81
An overview of the INTECONT Tersus................................................................................................................................ 7
Analog Outputs ................................................................................................................................................................. 74
Angle ................................................................................................................................................................................. 73
AO Actual Flow Rate ........................................................................................................................................................ 75
AO Belt Load .................................................................................................................................................................... 76
AO Deviation .................................................................................................................................................................... 77
AO Motor Speed Control .................................................................................................................................................. 77
AO Setpoint ...................................................................................................................................................................... 75
AO Speed......................................................................................................................................................................... 76
Appendix ......................................................................................................................................................................... 145
Basic Tare ......................................................................................................................................................................... 74
Batch Automatic Record.................................................................................................................................................... 83
Batch control ..................................................................................................................................................................... 67
Batch Mode ....................................................................................................................................................................... 82
Batch Setpoint Source....................................................................................................................................................... 83
Batch Tolerance ................................................................................................................................................................ 82
Batching functions ............................................................................................................................................................. 41
Batching mode .................................................................................................................................................................. 41
Baud rate................................................................................................................................................... 83, 106, 108, 116
Baud Rate ....................................................................................................................................................................... 103
Belt Circuit No. ............................................................................................................................................................ 73, 74
Belt Circuit Time ................................................................................................................................................................ 73
Belt Drift ............................................................................................................................................................................ 86
Belt inclination ................................................................................................................................................................... 49
belt load............................................................................................................................................................................... 9
Belt Load Offset ................................................................................................................................................................ 76
Belt Load Range ............................................................................................................................................................... 76
Belt Monitoring ................................................................................................................................................................ 154
Belt Monitoring ................................................................................................................................................ 85, 86, 87, 88
Belt Sensor Active ............................................................................................................................................................. 85
Belt Skew .......................................................................................................................................................................... 87
Belt Velocity Check ........................................................................................................................................................... 52
BIC Active ......................................................................................................................................................................... 86
BIC belt impact compensation......................................................................................................................................... 154
Bypass .............................................................................................................................................................................. 96
Byte Sequence ................................................................................................................................................................ 106
CA01 Event Error LC Input............................................................................................................................................ 121
CA02 Event Tachometer Input ...................................................................................................................................... 121
CA05 Event Linearization Error ..................................................................................................................................... 121
Calibrat. Results ................................................................................................................................................................ 74
Calibration ....................................................................................................................................................................... 121
Calibration Data .......................................................................................................................................................... 73, 74
Calibration functions .......................................................................................................................................................... 29
calibration switch ............................................................................................................................................................. 145
Calibration Switch ........................................................................................................................................................... 145
Calibration Weight ....................................................................................................................................................... 47, 74
call up the zero setting program ........................................................................................................................................ 19
Characteristics .................................................................................................................................................................. 10
Check in Keyboard Mode ................................................................................................................................................ 105
CO01 Event Controller Limited ...................................................................................................................................... 121
Communication EasyServe ............................................................................................................................................. 103

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 156 - Schenck Process Group
Index

Communication Fieldbus ................................................................................................................................................. 104


Compatibility DISOCONT Master .................................................................................................................................... 105
Compatiblity INTECONT ................................................................................................................................................. 107
Configuration ................................................................................................................................................................... 106
Configuration HMI Values ............................................................................................................................................... 114
Configuring Event Messages ............................................................................................................................................ 55
Connection Diagrams ...................................................................................................................................................... 131
Controller......................................................................................................................................................................... 121
Controller Magnitude Offset .............................................................................................................................................. 95
Correction Amount ............................................................................................................................................................ 82
Counter 1 Unit ................................................................................................................................................................... 71
Counter 2 Unit ................................................................................................................................................................... 71
Counter 3 Unit ................................................................................................................................................................... 72
Counter functions .............................................................................................................................................................. 23
Daily Total Time .............................................................................................................................................................. 112
Damaged / Defective Electrical Components ...................................................................................................................... 6
DATA................................................................................................................................................................................. 16
Data Format ............................................................................................................................................................ 107, 117
Data Log ON/OFF ............................................................................................................................................................. 68
Data Log Value 1 ............................................................................................................................................................ 112
Data Log Value 10 .......................................................................................................................................................... 113
Data Log Value 2 ............................................................................................................................................................ 112
Data Log Value 3 ............................................................................................................................................................ 112
Data Log Value 4 ............................................................................................................................................................ 112
Data Log Value 5 ............................................................................................................................................................ 113
Data Log Value 6 ............................................................................................................................................................ 113
Data Log Value 7 ............................................................................................................................................................ 113
Data Log Value 8 ............................................................................................................................................................ 113
Data Log Value 9 ............................................................................................................................................................ 113
Data Logging ................................................................................................................................................................... 111
DELETE ............................................................................................................................................................................ 16
Deviation abs. max............................................................................................................................................................ 93
Deviation Offset................................................................................................................................................................. 77
Deviation Range................................................................................................................................................................ 77
DeviceNet Module (VCB8020) ........................................................................................................................................ 138
DI Acknowledge Events ................................................................................................................................................... 99
DI Batch Terminate .......................................................................................................................................................... 99
DI BIC freeze.................................................................................................................................................................... 88
DI External Event 1 ........................................................................................................................................................ 100
DI External Event 2 ........................................................................................................................................................ 100
DI Source Belt Sensor ...................................................................................................................................................... 85
DI Start ........................................................................................................................................................................... 100
DI Volumetric Mode .......................................................................................................................................................... 99
DI Volumetric synchron .................................................................................................................................................. 100
Dialog Behaviour ............................................................................................................................................................... 65
Digital Inputs ..................................................................................................................................................................... 99
Digital Outputs................................................................................................................................................................. 100
Display Test and Version Number..................................................................................................................................... 21
DO Actual Flow Rate MAX ............................................................................................................................................. 101
DO Actual Flow Rate MIN .............................................................................................................................................. 101
DO ALARM .................................................................................................................................................................... 100
DO Batch Running ......................................................................................................................................................... 102
DO Belt Drift ..................................................................................................................................................................... 87
DO Belt Load MAX ......................................................................................................................................................... 101
DO Belt load MIN ........................................................................................................................................................... 101
DO Belt Skew ................................................................................................................................................................... 88
DO Belt Slip...................................................................................................................................................................... 88
DO Deviation .................................................................................................................................................................. 103
DO Dribble Feed ............................................................................................................................................................ 102
DO Feeder Started ......................................................................................................................................................... 102
DO Full Feed .................................................................................................................................................................. 102
DO Keyboard Mode ....................................................................................................................................................... 103
DO Pulse Counter ............................................................................................................................................................ 72
DO Scale Start ............................................................................................................................................................... 101
DO Speed MAX.............................................................................................................................................................. 102
DO Speed MIN ............................................................................................................................................................... 102

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 157 -
Index

DO Start Prefeeder ........................................................................................................................................................ 100


DO Volumetric Mode ...................................................................................................................................................... 103
dribble feed ......................................................................................................................................................................... 8
duty cycle ........................................................................................................................................................................ 145
Effective Platform Length .................................................................................................................................................. 73
Effective weighing platform length ....................................................................................................................................... 9
Effective Weighing Platform Length .................................................................................................................................. 45
Electrical System............................................................................................................................................................. 122
ENTER .............................................................................................................................................................................. 17
ESCAPE............................................................................................................................................................................ 17
Ethernet........................................................................................................................................................................... 111
Ethernet/IP ...................................................................................................................................................................... 146
Event Actual Flow Rate MAX ................................................................................................................................... 78, 123
Event Actual Flow Rate MIN .................................................................................................................................... 78, 125
Event Acyclic Communication ................................................................................................................................ 105, 127
Event Belt Drift ......................................................................................................................................................... 87, 124
Event Belt Load MAX ............................................................................................................................................... 79, 123
Event Belt Load MIN ................................................................................................................................................ 79, 125
Event Belt Skew ....................................................................................................................................................... 87, 124
Event Controller Limited ........................................................................................................................................... 94, 121
Event Cyclic Communication.................................................................................................................................. 105, 126
Event Deviation ........................................................................................................................................................ 93, 124
Event Error LC Input ................................................................................................................................................ 89, 121
Event External Event 1 ............................................................................................................................................. 91, 126
Event External Event 2 ............................................................................................................................................. 91, 126
Event LC Input < MIN ............................................................................................................................................... 90, 124
Event LC Input > MAX.............................................................................................................................................. 90, 123
Event License Violation ............................................................................................................................................ 91, 127
Event Linearization Error .......................................................................................................................................... 99, 121
Event Maint. Electric................................................................................................................................................. 84, 126
Event Maint.Feeder Run .......................................................................................................................................... 85, 126
Event Memory .......................................................................................................................................................... 88, 126
Event Namur Error Belt ............................................................................................................................................ 89, 122
Event Namur Error Tacho ........................................................................................................................................ 89, 122
Event Out of Tolerance ............................................................................................................................................ 83, 122
Event Power Failure ................................................................................................................................................. 88, 122
Event Run Disabled ................................................................................................................................................. 89, 122
Event Setpoint Limited ............................................................................................................................................. 90, 125
Event Simulation active ............................................................................................................................................ 90, 127
Event Slip ................................................................................................................................................................. 87, 124
Event Speed MAX .................................................................................................................................................... 80, 123
Event Speed MIN ..................................................................................................................................................... 79, 125
Event Stand-By ........................................................................................................................................................ 80, 125
Event Tachometer Input ........................................................................................................................................... 89, 121
Event Group: Calibration ................................................................................................................................................. 121
Event Group: Controller................................................................................................................................................... 121
Event Group: Electrical System ....................................................................................................................................... 122
Event Group: Interlock..................................................................................................................................................... 122
Event Group: Material Flow ............................................................................................................................................. 122
Event Group: MAX .......................................................................................................................................................... 123
Event Group: Mechanic ................................................................................................................................................... 124
Event Group: MIN ........................................................................................................................................................... 124
Event Group: Sequence Monitoring ................................................................................................................................ 125
Event Group: System Message ....................................................................................................................................... 126
Event messages .............................................................................................................................................................. 119
Events ............................................................................................................................................................................. 121
Events ............................................................................................................................................................. 88, 89, 90, 91
Events Details ................................................................................................................................................................. 121
Factor Deviation ................................................................................................................................................................ 93
feed rate .............................................................................................................................................................................. 9
Feeder ON/OFF ................................................................................................................................................................ 67
Feeder Start ...................................................................................................................................................................... 70
Feedrate Setpoint.............................................................................................................................................................. 70
Fig. 1: The basic diagram of the ITE inputs and outputs ..................................................................................................... 8
Fig. 10: Connection diagram for inputs and outputs 1 ..................................................................................................... 131
Fig. 11: Connection diagram for ITE inputs and outputs 2 .............................................................................................. 131

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 158 - Schenck Process Group
Index

Fig. 12: Serial interface connection diagram ................................................................................................................... 132


Fig. 13: Modbus connection diagram .............................................................................................................................. 132
Fig. 14: ITE PROFIBUS connection diagram .................................................................................................................. 132
Fig. 15: DeviceNet connection diagram........................................................................................................................... 133
Fig. 16: VPB8020 PROFIBUS module ............................................................................................................................ 136
Fig. 17: LEDs - VPB8020 front view ................................................................................................................................ 137
Fig. 18: DeviceNet module VCB8020 .............................................................................................................................. 138
Fig. 19: VCB8020:XC1 DeviceNet module front view ..................................................................................................... 139
Fig. 2: The belt load of the weighbridge is not legal for trade .............................................................................................. 9
Fig. 20: VSS8020 Modbus module layout drawing.......................................................................................................... 140
Fig. 21: Setpoint and switching-in source changeover VWF ........................................................................................... 149
Fig. 22: VWF switch-on sequence ................................................................................................................................... 150
Fig. 3: Display warning 2 ................................................................................................................................................... 11
Fig. 4: Display warning 1 ................................................................................................................................................... 11
Fig. 5: Display alarm ......................................................................................................................................................... 12
Fig. 6: display – function block .......................................................................................................................................... 18
Fig. 7: Parameter sets ....................................................................................................................................................... 53
Fig. 8: Connection diagram for voltage supply ................................................................................................................ 131
Fig. 9: WZ connection diagram and tachometer.............................................................................................................. 131
Filter Actual Flow Rate ..................................................................................................................................................... 80
Filter Actual Flow Rate analog ......................................................................................................................................... 80
Filter Belt Load ................................................................................................................................................................. 81
Filter Belt Speed ............................................................................................................................................................... 81
Filter Deviation ................................................................................................................................................................. 92
Filters ................................................................................................................................................................................ 80
Five Safety Rules of Electrical Engineering......................................................................................................................... 6
Fixed mode configuration ................................................................................................................................................ 109
FLOAT-Format ................................................................................................................................................................ 107
Flow Rate Offset ............................................................................................................................................................... 75
Flow Rate Range .............................................................................................................................................................. 76
Flow Rate Units ................................................................................................................................................................. 69
Font ................................................................................................................................................................................... 66
Format Data .................................................................................................................................................................... 104
full feed................................................................................................................................................................................ 8
FUNCTION........................................................................................................................................................................ 16
function block .................................................................................................................................................................... 19
Function block ................................................................................................................................................................... 17
Function Check ......................................................................................................................................................... 51, 147
Gateway .......................................................................................................................................................................... 111
General Diagram ................................................................................................................................................................. 7
Hardware and technical data........................................................................................................................................... 129
HI01 Event LC Input > MAX .......................................................................................................................................... 123
HI02 Event Actual Flow Rate MAX ................................................................................................................................ 123
HI03 Event Belt Load MAX............................................................................................................................................ 123
HI04 Event Speed MAX ................................................................................................................................................ 123
HI05 Event Deviation..................................................................................................................................................... 124
HMI Value 01 .................................................................................................................................................................. 114
HMI Value 02 .................................................................................................................................................................. 114
HMI Value 03 .................................................................................................................................................................. 114
HMI Value 04 .................................................................................................................................................................. 114
HMI Value 05 .................................................................................................................................................................. 114
HMI Value 06 .................................................................................................................................................................. 114
HMI Value 07 .................................................................................................................................................................. 114
HMI Value 08 .................................................................................................................................................................. 115
HMI Value 09 .................................................................................................................................................................. 115
HMI Value 10 .................................................................................................................................................................. 115
Hourly Total Time ............................................................................................................................................................ 111
I-Component TN................................................................................................................................................................ 92
ID Preset Value 1 ............................................................................................................................................................ 109
ID Preset Value 2 ............................................................................................................................................................ 109
ID Preset Value 3 ............................................................................................................................................................ 109
ID Preset Value 4 ............................................................................................................................................................ 109
ID Preset Value 5 ............................................................................................................................................................ 109
ID Preset Value 6 ............................................................................................................................................................ 109
ID Preset Value 7 ............................................................................................................................................................ 110
ID Preset Value 8 ............................................................................................................................................................ 110

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 159 -
Index

ID Read Value 1 .............................................................................................................................................................. 110


ID Read Value 2 .............................................................................................................................................................. 110
ID Read Value 3 .............................................................................................................................................................. 110
ID Read Value 4 .............................................................................................................................................................. 110
ID Read Value 5 .............................................................................................................................................................. 110
ID Read Value 6 .............................................................................................................................................................. 110
ID Read Value 7 .............................................................................................................................................................. 111
ID Read Value 8 .............................................................................................................................................................. 111
Identifier format ............................................................................................................................................................... 108
IL01 Event Run Disabled............................................................................................................................................... 122
Interlock........................................................................................................................................................................... 122
IP Address....................................................................................................................................................................... 111
key in the setpoint ............................................................................................................................................................. 20
Keyboard operation ON/OFF ............................................................................................................................................ 26
Language .......................................................................................................................................................................... 65
LC Characteristic Value..................................................................................................................................................... 73
LC Filter............................................................................................................................................................................. 81
LC Rated Capacity ............................................................................................................................................................ 73
LED diagnosis ................................................................................................................................................................. 141
Lever Ratio ........................................................................................................................................................................ 73
Limit Actual Flow Rate MAX ............................................................................................................................................. 78
Limit Actual Flow Rate MIN .............................................................................................................................................. 78
Limit Belt Load MAX ......................................................................................................................................................... 79
Limit Belt Load MIN .......................................................................................................................................................... 78
Limit Speed MAX ............................................................................................................................................................. 79
Limit Speed MIN............................................................................................................................................................... 79
Limit Values....................................................................................................................................................................... 77
Linearization .................................................................................................................................................................... 155
Linearization ...................................................................................................................................................................... 97
Linearization I1 .................................................................................................................................................................. 98
Linearization I2 .................................................................................................................................................................. 98
Linearization I3 .................................................................................................................................................................. 98
Linearization I4 .................................................................................................................................................................. 98
Linearization ON ............................................................................................................................................................... 97
Linearization S1 ................................................................................................................................................................ 97
Linearization S2 ................................................................................................................................................................ 98
Linearization S3 ................................................................................................................................................................ 98
Linearization S4 ................................................................................................................................................................ 98
LO01 Event LC Input < MIN .......................................................................................................................................... 124
LO02 Event Actual Flow Rate MIN ................................................................................................................................ 125
LO03 Event Belt Load MIN............................................................................................................................................ 125
LO04 Event Speed MIN ................................................................................................................................................ 125
Logger cycle time ............................................................................................................................................................ 112
Lower Limit ........................................................................................................................................................................ 94
Maintenance Electric ......................................................................................................................................................... 84
Maintenance Feeder Run .................................................................................................................................................. 84
Maintenance interval ......................................................................................................................................................... 84
Material Flow ................................................................................................................................................................... 122
MAX ................................................................................................................................................................................ 123
Measuring at the Discharge Point VAP ........................................................................................................................... 153
Mechanic ......................................................................................................................................................................... 124
Method of Function ............................................................................................................................................................. 9
MF06 Event Out of Tolerance ....................................................................................................................................... 122
MIN.................................................................................................................................................................................. 124
Modbus Interface VSS8020 ............................................................................................................................................ 140
Mode functions .................................................................................................................................................................. 25
Net Mask ......................................................................................................................................................................... 111
Nominal Belt Load ............................................................................................................................................................. 74
Nominal Flow Rate ............................................................................................................................................................ 69
Nominal Speed.................................................................................................................................................................. 69
Operating in Normal Operation ......................................................................................................................................... 18
operating sources .............................................................................................................................................................. 26
Operation .......................................................................................................................................................................... 15
Optimize Controller ........................................................................................................................................................... 91
Output current ................................................................................................................................................................. 145
Own Address................................................................................................................................................................... 103

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 160 - Schenck Process Group
Index

P01 - Dialog Behaviour ..................................................................................................................................................... 65


P01.01 - Language ............................................................................................................................................................ 65
P01.02 - Userdefined Text ................................................................................................................................................ 65
P01.03 - Font .................................................................................................................................................................... 66
P01.04 - Units ................................................................................................................................................................... 66
P01.05 - Scale Name ........................................................................................................................................................ 66
P01.06 - Password ............................................................................................................................................................ 66
P01.07 - 2. Password ........................................................................................................................................................ 66
P01.08 - Feeder ON/OFF .................................................................................................................................................. 67
P01.09 - Switch Grav./Vol. command ............................................................................................................................... 67
P01.10 - Switch Keyboard-/Normal Mode ......................................................................................................................... 67
P01.11 - Batch control ....................................................................................................................................................... 67
P01.12 - >0 Zero ON/OFF................................................................................................................................................ 68
P01.13 - Reset Counter 1.................................................................................................................................................. 68
P01.14 - Reset Counter 2.................................................................................................................................................. 68
P01.15 - Data Log ON/OFF............................................................................................................................................... 68
P02 - Rated Data ............................................................................................................................................ 69, 70, 71, 72
P02.01 - Flow Rate Units .................................................................................................................................................. 69
P02.02 - Nominal Flow Rate ............................................................................................................................................. 69
P02.03 - Speed Measurement .......................................................................................................................................... 69
P02.04 - Pulses per length ................................................................................................................................................ 69
P02.05 - Nominal Speed ................................................................................................................................................... 69
P02.06 - Feeder Start ........................................................................................................................................................ 70
P02.07 - Feedrate Setpoint ............................................................................................................................................... 70
P02.08 - Relative Setpoint................................................................................................................................................. 70
P02.09 - WZ Active ........................................................................................................................................................... 70
P02.10 - Counter 1 Unit..................................................................................................................................................... 71
P02.11 - Pulse Length Total .............................................................................................................................................. 71
P02.12 - Counter 2 Unit..................................................................................................................................................... 71
P02.13 - Counter 3 Unit..................................................................................................................................................... 72
P02.14 - DO Pulse Counter.............................................................................................................................................. 72
P02.15 - Totalizer Increment ............................................................................................................................................. 72
P02.16 - Z1-Numberstep ................................................................................................................................................... 72
P03 - Calibration Data ................................................................................................................................................. 73, 74
P03.01 - Belt Circuit No. .................................................................................................................................................... 73
P03.02 - Belt Circuit Time ................................................................................................................................................. 73
P03.03 - LC Characteristic Value ...................................................................................................................................... 73
P03.04 - LC Rated Capacity.............................................................................................................................................. 73
P03.05 - Effective Platform Length .................................................................................................................................... 73
P03.06 - Lever Ratio ......................................................................................................................................................... 73
P03.07 - Angle .................................................................................................................................................................. 73
P03.08 - Calibration Weight .............................................................................................................................................. 74
P04 - Calibrat. Results ...................................................................................................................................................... 74
P04.01 - Nominal Belt Load .............................................................................................................................................. 74
P04.02 - Range Correction................................................................................................................................................ 74
P04.03 - Total Tare ........................................................................................................................................................... 74
P04.04 - Basic Tare .......................................................................................................................................................... 74
P04.05 - Tare Correction ................................................................................................................................................... 74
P04.06 - Belt Circuit No. .................................................................................................................................................... 74
P05 - Analog Outputs ........................................................................................................................................................ 74
P05.01 - AO Setpoint ....................................................................................................................................................... 75
P05.02 - Setpoint Offset .................................................................................................................................................... 75
P05.03 - Setpoint Range ................................................................................................................................................... 75
P05.04 - AO Actual Flow Rate ......................................................................................................................................... 75
P05.05 - Flow Rate Offset ................................................................................................................................................. 75
P05.06 - Flow Rate Range ................................................................................................................................................ 76
P05.07 - AO Belt Load ..................................................................................................................................................... 76
P05.08 - Belt Load Offset .................................................................................................................................................. 76
P05.09 - Belt Load Range ................................................................................................................................................. 76
P05.10 - AO Speed .......................................................................................................................................................... 76
P05.11 - Speed Offset ....................................................................................................................................................... 76
P05.12 - Speed Range ...................................................................................................................................................... 77
P05.13 - AO Deviation...................................................................................................................................................... 77
P05.14 - Deviation Offset .................................................................................................................................................. 77
P05.15 - Deviation Range ................................................................................................................................................. 77
P05.16 - AO Motor Speed Control ................................................................................................................................... 77

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 161 -
Index

P06 - Limit Values ............................................................................................................................................................. 77


P06.01 - Limit Actual Flow Rate MIN ............................................................................................................................... 78
P06.02 - Event Actual Flow Rate MIN .............................................................................................................................. 78
P06.03 - Limit Actual Flow Rate MAX .............................................................................................................................. 78
P06.04 - Event Actual Flow Rate MAX ............................................................................................................................. 78
P06.05 - Limit Belt Load MIN ........................................................................................................................................... 78
P06.06 - Event Belt Load MIN .......................................................................................................................................... 79
P06.07 - Limit Belt Load MAX .......................................................................................................................................... 79
P06.08 - Event Belt Load MAX......................................................................................................................................... 79
P06.09 - Limit Speed MIN ................................................................................................................................................ 79
P06.10 - Event Speed MIN............................................................................................................................................... 79
P06.11 - Limit Speed MAX ............................................................................................................................................... 79
P06.12 - Event Speed MAX ............................................................................................................................................. 80
P06.13 - Stand-By Limit Value .......................................................................................................................................... 80
P06.14 - Event Stand-By .................................................................................................................................................. 80
P07 - Filters ....................................................................................................................................................................... 80
P07.01 - Filter Actual Flow Rate ....................................................................................................................................... 80
P07.02 - Filter Actual Flow Rate analog ........................................................................................................................... 80
P07.03 - Filter Belt Load................................................................................................................................................... 81
P07.04 - Filter Belt Speed ................................................................................................................................................ 81
P07.05 - LC Filter .............................................................................................................................................................. 81
P07.06 - Afterflow Totalizer ............................................................................................................................................... 81
P08 - Additional device...................................................................................................................................................... 81
P08.01 - Zero Drop-Out Active .......................................................................................................................................... 81
P08.02 - Zero Drop-Out Limit ............................................................................................................................................ 81
P09 - Batch Mode ............................................................................................................................................................. 82
P09.01 - Pre-cut-off Amount.............................................................................................................................................. 82
P09.02 - Correction Amount .............................................................................................................................................. 82
P09.03 - Adaptation Factor ............................................................................................................................................... 82
P09.04 - Batch Tolerance.................................................................................................................................................. 82
P09.05 - Event Out of Tolerance ...................................................................................................................................... 83
P09.06 - Batch Automatic Record ..................................................................................................................................... 83
P09.07 - Batch Setpoint Source ........................................................................................................................................ 83
P10 - Printer Setting .................................................................................................................................................... 83, 84
P10.01 - Baud rate ............................................................................................................................................................ 83
P10.02 - Print Event .......................................................................................................................................................... 83
P10.03 - Print Page Length ............................................................................................................................................... 84
P11 - Maintenance interval................................................................................................................................................ 84
P11.01 - Maintenance Electric .......................................................................................................................................... 84
P11.02 - Event Maint. Electric .......................................................................................................................................... 84
P11.03 - Maintenance Feeder Run ................................................................................................................................... 84
P11.04 - Event Maint.Feeder Run .................................................................................................................................... 85
P12 - Belt Monitoring ....................................................................................................................................... 85, 86, 87, 88
P12.01 - VAP Active .......................................................................................................................................................... 85
P12.02 - Platform Dis.Length ............................................................................................................................................ 85
P12.03 - Belt Sensor Active .............................................................................................................................................. 85
P12.04 - DI Source Belt Sensor ....................................................................................................................................... 85
P12.05 - BIC Active ........................................................................................................................................................... 86
P12.06 - Sensor Length .................................................................................................................................................... 86
P12.07 - Sensor Width ...................................................................................................................................................... 86
P12.08 - Sensor Offset ...................................................................................................................................................... 86
P12.09 - Belt Drift .............................................................................................................................................................. 86
P12.10 - Event Belt Drift ................................................................................................................................................... 87
P12.11 - Belt Skew............................................................................................................................................................ 87
P12.12 - Event Belt Skew................................................................................................................................................. 87
P12.13 - Slip Value ........................................................................................................................................................... 87
P12.14 - Event Slip .......................................................................................................................................................... 87
P12.15 - DO Belt Drift....................................................................................................................................................... 87
P12.16 - DO Belt Skew .................................................................................................................................................... 88
P12.17 - DO Belt Slip ....................................................................................................................................................... 88
P12.18 - DI BIC freeze ..................................................................................................................................................... 88
P13 - Events.................................................................................................................................................... 88, 89, 90, 91
P13.01 - Event Power Failure .......................................................................................................................................... 88
P13.02 - Event Memory.................................................................................................................................................... 88
P13.03 - Event Tachometer Input .................................................................................................................................... 89
P13.04 - Event Namur Error Tacho .................................................................................................................................. 89

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 162 - Schenck Process Group
Index

P13.05 - Event Namur Error Belt...................................................................................................................................... 89


P13.06 - Event Error LC Input .......................................................................................................................................... 89
P13.07 - Event Run Disabled ........................................................................................................................................... 89
P13.08 - Event LC Input > MAX ....................................................................................................................................... 90
P13.09 - Event LC Input < MIN ........................................................................................................................................ 90
P13.10 - Event Simulation active ..................................................................................................................................... 90
P13.11 - Event Setpoint Limited ....................................................................................................................................... 90
P13.12 - Event External Event 1 ...................................................................................................................................... 91
P13.13 - Event External Event 2 ...................................................................................................................................... 91
P13.14 - Event License Violation ..................................................................................................................................... 91
P14 - Rate controller ..................................................................................................................... 91, 92, 93, 94, 95, 96, 97
P14.01 - Optimize Controller ............................................................................................................................................. 91
P14.02 - P-Component KP ................................................................................................................................................ 91
P14.03 - I-Component TN ................................................................................................................................................. 92
P14.04 - Filter Deviation ................................................................................................................................................... 92
P14.05 - Time Deviation .................................................................................................................................................... 92
P14.06 - Threshold Deviation ............................................................................................................................................ 92
P14.07 - Factor Deviation.................................................................................................................................................. 93
P14.08 - Deviation abs. max. ............................................................................................................................................ 93
P14.09 - Event Deviation.................................................................................................................................................. 93
P14.10 - Event Controller Limited .................................................................................................................................... 94
P14.11 - Lower Limit ......................................................................................................................................................... 94
P14.12 - Upper Limit ......................................................................................................................................................... 94
P14.13 - Controller Magnitude Offset ................................................................................................................................ 95
P14.14 - Position at STOP ................................................................................................................................................ 95
P14.15 - Volumetric Start-Up ............................................................................................................................................ 95
P14.16 - Volumetric Clearance ......................................................................................................................................... 95
P14.17 - Setpoint Offset .................................................................................................................................................... 96
P14.18 - Setpoint Range ................................................................................................................................................... 96
P14.19 - Store ................................................................................................................................................................... 96
P14.20 - Volumetric Mode ................................................................................................................................................. 96
P14.21 - Bypass ................................................................................................................................................................ 96
P14.22 - Setpoint Filter 1st Ord ......................................................................................................................................... 97
P14.23 - Setpoint Filter 2nd Ord ........................................................................................................................................ 97
P14.24 - Set/Act Sources .................................................................................................................................................. 97
P14.25 - Adaptation 1 ....................................................................................................................................................... 97
P15 - Linearization ............................................................................................................................................................ 97
P15.01 - Linearization ON ................................................................................................................................................. 97
P15.02 - Linearization S1 .................................................................................................................................................. 97
P15.03 - Linearization I1 ................................................................................................................................................... 98
P15.04 - Linearization S2 .................................................................................................................................................. 98
P15.05 - Linearization I2 ................................................................................................................................................... 98
P15.06 - Linearization S3 .................................................................................................................................................. 98
P15.07 - Linearization I3 ................................................................................................................................................... 98
P15.08 - Linearization S4 .................................................................................................................................................. 98
P15.09 - Linearization I4 ................................................................................................................................................... 98
P15.10 - Event Linearization Error ................................................................................................................................... 99
P16 - Digital Inputs ............................................................................................................................................................ 99
P16.01 - Source Run Enable............................................................................................................................................. 99
P16.02 - DI Batch Terminate ............................................................................................................................................ 99
P16.03 - DI Acknowledge Events ..................................................................................................................................... 99
P16.04 - DI Volumetric Mode ........................................................................................................................................... 99
P16.05 - DI Volumetric synchron .................................................................................................................................... 100
P16.06 - DI Start ............................................................................................................................................................ 100
P16.07 - DI External Event 1 .......................................................................................................................................... 100
P16.08 - DI External Event 2 .......................................................................................................................................... 100
P17 - Digital Outputs ....................................................................................................................................................... 100
P17.01 - DO ALARM ...................................................................................................................................................... 100
P17.02 - DO Start Prefeeder .......................................................................................................................................... 100
P17.03 - DO Scale Start ................................................................................................................................................. 101
P17.04 - DO Actual Flow Rate MIN ................................................................................................................................ 101
P17.05 - DO Actual Flow Rate MAX .............................................................................................................................. 101
P17.06 - DO Belt load MIN ............................................................................................................................................. 101
P17.07 - DO Belt Load MAX .......................................................................................................................................... 101
P17.08 - DO Speed MIN ................................................................................................................................................ 102
P17.09 - DO Speed MAX ............................................................................................................................................... 102

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 163 -
Index

P17.10 - DO Batch Running ........................................................................................................................................... 102


P17.11 - DO Full Feed ................................................................................................................................................... 102
P17.12 - DO Dribble Feed .............................................................................................................................................. 102
P17.13 - DO Feeder Started .......................................................................................................................................... 102
P17.14 - DO Deviation ................................................................................................................................................... 103
P17.15 - DO Volumetric Mode ....................................................................................................................................... 103
P17.16 - DO Keyboard Mode ......................................................................................................................................... 103
P18 - Communication EasyServe ................................................................................................................................... 103
P18.01 - Own Address .................................................................................................................................................... 103
P18.02 - Baud Rate ......................................................................................................................................................... 103
P18.03 - Format Data ...................................................................................................................................................... 104
P19 - Communication Fieldbus ....................................................................................................................................... 104
P19.01 - Protocol Type.................................................................................................................................................... 104
P19.02 - Timeout Host .................................................................................................................................................... 104
P19.03 - Event Cyclic Communication ........................................................................................................................... 105
P19.04 - Event Acyclic Communication.......................................................................................................................... 105
P19.05 - Check in Keyboard Mode ................................................................................................................................. 105
P19.06 - Compatibility DISOCONT Master ..................................................................................................................... 105
P19.07 - Word Sequence ................................................................................................................................................ 105
P19.08 - Byte Sequence ................................................................................................................................................. 106
P19.09 - Configuration .................................................................................................................................................... 106
P19.10 - Address ............................................................................................................................................................ 106
P19.11 - Resolution ......................................................................................................................................................... 106
P19.12 - Baud rate .......................................................................................................................................................... 106
P19.13 - Data Format ...................................................................................................................................................... 107
P19.14 - Physics ............................................................................................................................................................. 107
P19.15 - Address ............................................................................................................................................................ 107
P19.16 - FLOAT-Format.................................................................................................................................................. 107
P19.17 - Compatiblity INTECONT ................................................................................................................................... 107
P19.18 - Identifier format ................................................................................................................................................. 108
P19.19 - PA32 compatible............................................................................................................................................... 108
P19.20 - Address ............................................................................................................................................................ 108
P19.21 - Baud rate .......................................................................................................................................................... 108
P19.22 - Access Rights Limitation FB ............................................................................................................................. 108
P19.23 - Remote IP Address FB ..................................................................................................................................... 109
P20 - Fixed mode configuration ...................................................................................................................................... 109
P20.01 - ID Preset Value 1.............................................................................................................................................. 109
P20.02 - ID Preset Value 2.............................................................................................................................................. 109
P20.03 - ID Preset Value 3.............................................................................................................................................. 109
P20.04 - ID Preset Value 4.............................................................................................................................................. 109
P20.05 - ID Preset Value 5.............................................................................................................................................. 109
P20.06 - ID Preset Value 6.............................................................................................................................................. 109
P20.07 - ID Preset Value 7.............................................................................................................................................. 110
P20.08 - ID Preset Value 8.............................................................................................................................................. 110
P20.09 - ID Read Value 1 ............................................................................................................................................... 110
P20.10 - ID Read Value 2 ............................................................................................................................................... 110
P20.11 - ID Read Value 3 ............................................................................................................................................... 110
P20.12 - ID Read Value 4 ............................................................................................................................................... 110
P20.13 - ID Read Value 5 ............................................................................................................................................... 110
P20.14 - ID Read Value 6 ............................................................................................................................................... 110
P20.15 - ID Read Value 7 ............................................................................................................................................... 111
P20.16 - ID Read Value 8 ............................................................................................................................................... 111
P21 - Ethernet ................................................................................................................................................................. 111
P21.01 - IP Address ........................................................................................................................................................ 111
P21.02 - Net Mask .......................................................................................................................................................... 111
P21.03 - Gateway ........................................................................................................................................................... 111
P22 - Data Logging ......................................................................................................................................................... 111
P22.01 - Hourly Total Time ............................................................................................................................................. 111
P22.02 - Daily Total Time ................................................................................................................................................ 112
P22.03 - Logger cycle time.............................................................................................................................................. 112
P22.04 - Data Log Value 1 .............................................................................................................................................. 112
P22.05 - Data Log Value 2 .............................................................................................................................................. 112
P22.06 - Data Log Value 3 .............................................................................................................................................. 112
P22.07 - Data Log Value 4 .............................................................................................................................................. 112
P22.08 - Data Log Value 5 .............................................................................................................................................. 113
P22.09 - Data Log Value 6 .............................................................................................................................................. 113

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 164 - Schenck Process Group
Index

P22.10 - Data Log Value 7 .............................................................................................................................................. 113


P22.11 - Data Log Value 8 .............................................................................................................................................. 113
P22.12 - Data Log Value 9 .............................................................................................................................................. 113
P22.13 - Data Log Value 10 ............................................................................................................................................ 113
P23 - Configuration HMI Values ...................................................................................................................................... 114
P23.01 - HMI Value 01 .................................................................................................................................................... 114
P23.02 - HMI Value 02 .................................................................................................................................................... 114
P23.03 - HMI Value 03 .................................................................................................................................................... 114
P23.04 - HMI Value 04 .................................................................................................................................................... 114
P23.05 - HMI Value 05 .................................................................................................................................................... 114
P23.06 - HMI Value 06 .................................................................................................................................................... 114
P23.07 - HMI Value 07 .................................................................................................................................................... 114
P23.08 - HMI Value 08 .................................................................................................................................................... 115
P23.09 - HMI Value 09 .................................................................................................................................................... 115
P23.10 - HMI Value 10 .................................................................................................................................................... 115
P24 - Second Display .............................................................................................................................................. 116, 117
P24.01 - Second Display active ...................................................................................................................................... 116
P24.02 - Baud rate .......................................................................................................................................................... 116
P24.03 - Data Format ...................................................................................................................................................... 117
P24.04 - Physics ............................................................................................................................................................. 117
PA32 compatible ............................................................................................................................................................. 108
Parameter Block 01 - Dialog Behaviour ............................................................................................................................ 65
Parameter Block 02 - Rated Data ..................................................................................................................................... 69
Parameter Block 03 - Calibration Data .............................................................................................................................. 73
Parameter Block 04 - Calibrat. Results ............................................................................................................................. 74
Parameter Block 05 - Analog Outputs ............................................................................................................................... 74
Parameter Block 06 - Limit Values .................................................................................................................................... 77
Parameter Block 07 - Filters .............................................................................................................................................. 80
Parameter Block 08 - Additional device............................................................................................................................. 81
Parameter Block 09 - Batch Mode .................................................................................................................................... 82
Parameter Block 10 - Printer Setting ................................................................................................................................. 83
Parameter Block 11 - Maintenance interval....................................................................................................................... 84
Parameter Block 12 - Belt Monitoring ................................................................................................................................ 85
Parameter Block 13 - Events............................................................................................................................................. 88
Parameter Block 14 - Rate controller ................................................................................................................................ 91
Parameter Block 15 - Linearization ................................................................................................................................... 97
Parameter Block 16 - Digital Inputs ................................................................................................................................... 99
Parameter Block 17 - Digital Outputs .............................................................................................................................. 100
Parameter Block 18 - Communication EasyServe .......................................................................................................... 103
Parameter Block 19 - Communication Fieldbus .............................................................................................................. 104
Parameter Block 20 - Fixed mode configuration ............................................................................................................. 109
Parameter Block 21 - Ethernet ........................................................................................................................................ 111
Parameter Block 22 - Data Logging ................................................................................................................................ 111
Parameter Block 23 - Configuration HMI Values ............................................................................................................. 114
Parameter Block 24 - Second Display ............................................................................................................................. 116
Parameter Details ............................................................................................................................................................. 65
Parameter functions .......................................................................................................................................................... 37
Parameter Input ................................................................................................................................................................ 49
Parameter Listing .............................................................................................................................................................. 55
Parameter Overview ......................................................................................................................................................... 55
Parameters........................................................................................................................................................................ 53
Password .......................................................................................................................................................................... 66
P-Component KP .............................................................................................................................................................. 91
Physics .................................................................................................................................................................... 107, 117
Platform Dis.Length ........................................................................................................................................................... 85
Position at STOP............................................................................................................................................................... 95
Pre-cut-off Amount ............................................................................................................................................................ 82
Prefeeder .......................................................................................................................................................................... 26
Print Event......................................................................................................................................................................... 83
Print Page Length ............................................................................................................................................................. 84
Printer functions ................................................................................................................................................................ 39
Printer Setting ............................................................................................................................................................. 83, 84
PROFIBUS module (VPB8020)....................................................................................................................................... 136
Protocol Type .................................................................................................................................................................. 104
Pulse Length Total ............................................................................................................................................................ 71
Pulse/Belt circuit LB .......................................................................................................................................................... 30

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 165 -
Index

Pulses per length .............................................................................................................................................................. 69


Quick guide ....................................................................................................................................................................... 15
Range Correction .............................................................................................................................................................. 74
Rate controller ............................................................................................................................... 91, 92, 93, 94, 95, 96, 97
Rated Data ...................................................................................................................................................... 69, 70, 71, 72
Read Parameters .............................................................................................................................................................. 37
Record the batch ............................................................................................................................................................... 43
Regulation ....................................................................................................................................................................... 151
Relative Setpoint ............................................................................................................................................................... 70
Remote IP Address FB.................................................................................................................................................... 109
Replacing INTECONT PLUS with INTECONT Tersus .................................................................................................... 133
Reset Counter 1 ................................................................................................................................................................ 68
Reset Counter 2 ................................................................................................................................................................ 68
reset the totalizing counter ................................................................................................................................................ 19
Resolution ....................................................................................................................................................................... 106
Safety notes ........................................................................................................................................................................ 3
SC01 Event Setpoint Limited ........................................................................................................................................ 125
SC02 Event Stand-By ................................................................................................................................................... 125
SC03 Event Maint.Feeder Run ..................................................................................................................................... 126
SC04 Event Maint. Electric............................................................................................................................................ 126
SC05 Event External Event 1 ........................................................................................................................................ 126
SC06 Event External Event 2 ........................................................................................................................................ 126
Scale Name....................................................................................................................................................................... 66
SCROLL ............................................................................................................................................................................ 16
Second Display ....................................................................................................................................................... 116, 117
Second Display active ..................................................................................................................................................... 116
Sensor Length ................................................................................................................................................................... 86
Sensor Offset .................................................................................................................................................................... 86
Sensor Width..................................................................................................................................................................... 86
Sequence Monitoring ...................................................................................................................................................... 125
Serial number of the CPU board ..................................................................................................................................... 143
Service Functions .............................................................................................................................................................. 21
Service Values ................................................................................................................................................................ 145
Set option ........................................................................................................................................................................ 146
Set/Act Sources ................................................................................................................................................................ 97
Setpoint Filter 1st Ord ....................................................................................................................................................... 97
Setpoint Filter 2nd Ord ...................................................................................................................................................... 97
Setpoint Offset ............................................................................................................................................................ 75, 96
Setpoint Range ........................................................................................................................................................... 75, 96
Setting the Time ................................................................................................................................................................ 35
Signal Words ....................................................................................................................................................................... 5
Signal Words for Application Notes ..................................................................................................................................... 5
Signal Words for Safety Warnings ...................................................................................................................................... 5
Simulation ......................................................................................................................................................................... 27
Slip Value .......................................................................................................................................................................... 87
software identification ...................................................................................................................................................... 145
Software version ..................................................................................................................................................... 143, 145
Source Run Enable ........................................................................................................................................................... 99
Sources of Setpoints and Switch Signals ........................................................................................................................ 149
speed .................................................................................................................................................................................. 9
Speed Measurement ......................................................................................................................................................... 69
Speed Offset ..................................................................................................................................................................... 76
Speed Range .................................................................................................................................................................... 77
Stand-By Limit Value ......................................................................................................................................................... 80
START/STOP.................................................................................................................................................................... 16
Starting the calibration functions ....................................................................................................................................... 29
Startup operation ............................................................................................................................................................... 45
Status Report .................................................................................................................................................................... 40
Store.................................................................................................................................................................................. 96
Switch Grav./Vol. command .............................................................................................................................................. 67
Switch Keyboard-/Normal Mode ........................................................................................................................................ 67
SY01 Event Memory ..................................................................................................................................................... 126
SY08 Event Cyclic Communication ............................................................................................................................... 126
SY09 Event License Violation ....................................................................................................................................... 127
SY10 Event Acyclic Communication ............................................................................................................................. 127
SY14 Event Simulation active ....................................................................................................................................... 127

BV-H2463GB, 1149 INTECONT® Tersus Weighfeeder, Instruction Manual


- 166 - Schenck Process Group
Index

System Information ......................................................................................................................................................... 143


System Message ............................................................................................................................................................. 126
Tab.1: Using parameter sets ............................................................................................................................................. 53
Tab.10: LED 'Module Status' (below) .............................................................................................................................. 139
Tab.11: Modbus module properties................................................................................................................................. 140
Tab.12: Pin assignment modbus serial interface............................................................................................................. 140
Tab.13: Functions available on the controller web page ................................................................................................. 143
Tab.14: States and points in time in the flow chart .......................................................................................................... 150
Tab.15: Relevant parameters .......................................................................................................................................... 151
Tab.2: List of commonly used parameters-related abbreviations ...................................................................................... 54
Tab.3: Event classes ......................................................................................................................................................... 55
Tab.4: Event groups ........................................................................................................................................................ 119
Tab.5: Bus connection plug ............................................................................................................................................. 137
Tab.6: LED 'Operating Mode' (below) ............................................................................................................................. 137
Tab.7: LED 'Status' (above) ............................................................................................................................................ 138
Tab.8: Bus connection plug ............................................................................................................................................. 139
Tab.9: LED 'Network Status' (above) .............................................................................................................................. 139
Tare Correction ................................................................................................................................................................. 74
Tare TW ............................................................................................................................................................................ 31
Technical Data and Replacement Parts .......................................................................................................................... 129
Test Connector................................................................................................................................................................ 148
Test With Calibration Weight ............................................................................................................................................. 51
Test with Material .............................................................................................................................................................. 52
The basic diagram of the weighfeeder ................................................................................................................................ 8
Threshold Deviation .......................................................................................................................................................... 92
Time Deviation .................................................................................................................................................................. 92
Timeout Host ................................................................................................................................................................... 104
total ..................................................................................................................................................................................... 9
Total Tare .......................................................................................................................................................................... 74
Totalizer Increment ........................................................................................................................................................... 72
Turn off .............................................................................................................................................................................. 18
turn on ............................................................................................................................................................................... 18
Types of operation ............................................................................................................................................................ 25
Units .................................................................................................................................................................................. 66
Upper Limit ........................................................................................................................................................................ 94
Userdefined Text ............................................................................................................................................................... 65
VAP Active ........................................................................................................................................................................ 85
Volumetric Clearance ........................................................................................................................................................ 95
Volumetric Mode ............................................................................................................................................................... 96
Volumetric Start-Up ........................................................................................................................................................... 95
WE01 Event Power Failure ........................................................................................................................................... 122
WE09 Event Namur Error Tacho ................................................................................................................................... 122
WE10 Event Namur Error Belt ...................................................................................................................................... 122
Web Server ..................................................................................................................................................................... 143
Web server functions....................................................................................................................................................... 143
Weighing Platforms ........................................................................................................................................................... 45
Weight Check CW ............................................................................................................................................................. 33
WM02 Event Slip ........................................................................................................................................................... 124
WM03 Event Belt Skew ................................................................................................................................................. 124
WM04 Event Belt Drift ................................................................................................................................................... 124
Word Sequence .............................................................................................................................................................. 105
WZ Active .......................................................................................................................................................................... 70
Z1-Numberstep ................................................................................................................................................................. 72
Zero Drop-Out Active ........................................................................................................................................................ 81
Zero Drop-Out Limit .......................................................................................................................................................... 81

INTECONT® Tersus Weighfeeder, Instruction Manual BV-H2463GB, 1149


Schenck Process Group - 167 -

You might also like