Direct CP1L Connection Quick Start

Objective: Connecting CelciuXº to CP1L (serial CompowayF)

Components used:
 EJ1N-TC__-__
 EJ1C-EDU_-NFLK
 24 Volt Supply
 CJ1W-CIF11
 CP1L and USB cable
to program the PLC Port A
 E58-CIFQ1 for
configuration of Port B
CelciuXº

EDU

Procedure:
Assumption: CX-One with drivers for CP1L and EJ1 (CelciuXº) are on the PC

1. Setting the CJ1W-CIF11: Set the dip switches as follows

SW2 Description
1 ON: Terminator connected.
2 ON: 2-wire method
3 ON: 2-wire method
4 Not used.
5 OFF: No RS control of RD
(continual reception)
6 ON: RS control of SD

2. Connect the CJ1W-CIF11 (RS485 port) to the B port of the EDU.

RDB+ __ B+ > EJ1C-EDU terminal 6 (+)


RDA- ___A - > EJ1C-EDU terminal 7 (-)
110Ω to 125 Ω 1/2W terminating resistor EJ1-EDU pin 6+7 (optional)

3. (Optional) Connect EJ1 with PC / CX-Thermo with the E58-CIFQ1 cable


and adjust the “Comm. Port B” settings, defaults are 9K6bps, 7-E-2

3C
Assumption: CP1L is just out of the box and has its default settings.
4. Connect PC to PLC using a USB cable and create the network
a) Start CX-Integrator (new project) and select ‘auto on-line’
b) Select “USB connection” and click
c) Double click CPU port.. in left bottom window, select Port2 and CompowayF

Only in
CP1L-M

d) Click [TRANSFER] select range 0 – 0 and Click [OK]

e) [OK] the “Cannot acquire the Slave node” message


f) Double click the PLC and make these settings: “PLC setup (custom)” and
“serial gateway”, the others should match the CelciuXº settings.

g) Transfer the new settings to the PLC with > [YES]


(PLC must be in Monitor or Stop mode!)
h) Right click “CPU port” and transfer [Network to PC], click [transfer], select a
wider range which include the node numbers of the CelciuXº units.

Network setup and connection complete.

3C
5. Open CX-Thermo to set-up the CelciuXº Temperature Controller
Right click the TC unit, start dedicated tool, start with settings inherited

CX-Thermo starts with the correct TC unit template, don’t forget to upload the TC
parameters from the TC unit first, if the TC unit is already configured!!

6. Example how to read some parameters from the CelciuXº into the PLC

Workflow:
Open CX-Programmer from CX-Integrator and select “off-line” mode.
Insert the desired function blocks from the library (like the _EJ1N202_ReadPV)
Insert the function block in the ladder like in the example above

Note: (read the FB help file for details)


The UnitSelect should be set to #FFFF
When using the CPU-comms In the CJ1/CP1L-M: PortNo = &2
Set TCNo and ChannelNo according to need
PV gives the current measured value in the select TC# and Channel#

Note: Connection with CJ1 works exactly the same.