You are on page 1of 13

Configuration

Component Virtual Name: Frigorifico Holon 22 KV


Feeder Name: Feeder 1
Network Topology: WYE
Network Nominal: 12,702kV
Device Type: PQZIP Based Investigation
Report information

Start time: 10/05/2010 12:00:00 a. m. End time: 17/05/2010 12:00:00 a. m.


GMT: -03:00 Report Version: 1.0.0.44
Summary

Compliance Result

Power Frequency Pass

Supply Voltage Variation Pass

Flicker Severity Fail

Supply Voltage Unbalance Pass

Harmonic Voltage Pass

Total Harmonic Distortion Pass

Event type Number of events Result [% within the limits]


Rapid Voltage Changes 14 Pass
Supply Voltage Dip and Interruption 17 Fail
Supply Voltage Swell 8 Fail
Transient Overvoltages 35 Fail
Power Frequency
Under normal operating conditions: the mean value of the fundamental frequency measured over 10s shall be : 50Hz ±1% during 99,5%
of year and 50Hz +4%/-6% during 100% of requested time.For systems with synchronous connection to an interconnected system.
Start time: 10/05/2010 12:00:00 a. m. End time: 17/05/2010 12:00:00 a. m.
Regulation Regulation Result [% within
Time [%] Measured min[Hz] Measured max[Hz]
min[Hz] max[Hz] the limits]
99,5 49,5 49,817 50,5 50,15 Pass (99,97%)
100 47 49,403 52 50,218 Pass (100%)

Page 1 of 13 EN50160 Report


Supply Voltage Variation
Under normal operating conditions, during each period of one week 99% of the 10 min mean r.m.s. values of the supply voltage shall be
within the range of Un ±10% and all 10 min mean r.m.s. values of the supply voltage shall be within the range of Un ±15.
Start time: 10/05/2010 12:00:00 a. m. End time: 17/05/2010 12:00:00 a. m.
Param Result [% within the
Time [%] Regulation min[%] Measured min[%] Regulation max[%] Measured max[%]
eter limits]
V1N 99 No Limit 101,09 110 103,7 Pass (100%)
V2N 99 No Limit 100,07 110 102,72 Pass (100%)
V3N 99 No Limit 100,38 110 102,65 Pass (100%)
V1N 99 90 101,09 No Limit 103,7 Pass (100%)
V2N 99 90 100,07 No Limit 102,72 Pass (100%)
V3N 99 90 100,38 No Limit 102,65 Pass (100%)
V1N 100 85 100,83 115 104 Pass (100%)
V2N 100 85 99,77 115 103,08 Pass (100%)
V3N 100 85 100,15 115 103,05 Pass (100%)

Page 2 of 13 EN50160 Report


Flicker Severity
Under normal operating conditions, during each period of one week the long term flicker severity Plt caused by voltage fluctuation
should be less than or equal to 1 for 95% of the time.
Start time: 10/05/2010 12:00:00 a. m. End time: 17/05/2010 12:00:00 a. m.
Paramete
Time [%] Regulation max Measured max Result [% within the limits]
r
V1N 95 1 1,895 Fail (56,79%)
V2N 95 1 1,806 Fail (60%)
V3N 95 1 1,659 Fail (60,49%)

Page 3 of 13 EN50160 Report


Supply Voltage Unbalance
Under normal operating conditions, during each period of one week, 95% of the 10 min mean r.m.s. values of the negative phase
sequence component (fundamental) of the supply voltage shall be within the range 0% to 2% of the positive phase sequence component
(fundamental).
Start time: 10/05/2010 12:00:00 a. m. End time: 17/05/2010 12:00:00 a. m.
Regulation Result [% within
Parameter Time [%] Measured max[%]
max[%] the limits]
Negative Sequence Unbalance (U2/U1) 95 2 0,24 Pass (100%)

Page 4 of 13 EN50160 Report


Harmonic Voltage
Under normal operating conditions, during each period of one week, 95% of the 10 min mean r.m.s. values of each individual harmonic
voltage shall be less than or equal to the regulation max values shown in the table below (values are given as percentage of the
fundamental harmonic).
Start time: 10/05/2010 12:00:00 a. m. End time: 17/05/2010 12:00:00 a. m.
Time Percent Regulation Measured max [%] Result [% within the
Harmonic V2N V3N limits]
Limit[%] max [%]
V1N V1N V2N V3N
2 95 2 0,02 0,02 0,02 Pass (100%) Pass (100%) Pass (100%)
3 95 5 0,23 0,11 0,09 Pass (100%) Pass (100%) Pass (100%)
4 95 1 0,01 0,01 0,01 Pass (100%) Pass (100%) Pass (100%)
5 95 6 2,19 2,22 2,25 Pass (100%) Pass (100%) Pass (100%)
6 95 0,5 0,01 0,01 0,01 Pass (100%) Pass (100%) Pass (100%)
7 95 5 0,92 0,93 0,93 Pass (100%) Pass (100%) Pass (100%)
8 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
9 95 1,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
10 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)

Page 5 of 13 EN50160 Report


11 95 3,5 0,14 0,18 0,16 Pass (100%) Pass (100%) Pass (100%)
12 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
13 95 3 0,08 0,07 0,07 Pass (100%) Pass (100%) Pass (100%)
14 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
15 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
16 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
17 95 2 0 0 0 Pass (100%) Pass (100%) Pass (100%)
18 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
19 95 1,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
20 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
21 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
22 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
23 95 1,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
24 95 0,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)
25 95 1,5 0 0 0 Pass (100%) Pass (100%) Pass (100%)

Page 6 of 13 EN50160 Report


Total Harmonic Distortion
The THD of the supply voltage (including all harmonics up to the order 40) shall be less than or equal to 8% during 95% of each period
of one week.
Start time: 10/05/2010 12:00:00 a. m. End time: 17/05/2010 12:00:00 a. m.
Paramete
Time [%] Regulation max[%] Measured max[%] Result [% within the limits]
r
V1N 95 8 2,34 Pass (100%)
V2N 95 8 2,37 Pass (100%)
V3N 95 8 2,39 Pass (100%)

Rapid Voltage Changes


Day Allowed Number of events Result
10/05/2010 12:00 a. m. 24 10 Pass
11/05/2010 12:00 a. m. 24 0 Pass
12/05/2010 12:00 a. m. 24 2 Pass
13/05/2010 12:00 a. m. 24 2 Pass
14/05/2010 12:00 a. m. 24 0 Pass
15/05/2010 12:00 a. m. 24 0 Pass

Page 7 of 13 EN50160 Report


16/05/2010 12:00 a. m. 24 0 Pass
Phase Start time Duration Value [% from ref]
V2N 10/05/2010 08:37:17.625012 a. 00:00:00:080047 6,68
m.
V1N 10/05/2010 08:37:17.635018 a. 00:00:00:700409 6
m.
V1N 10/05/2010 08:37:29.503716 a. 00:00:00:109827 6,81
m.
V3N 10/05/2010 08:37:29.503716 a. 00:00:00:089858 5,97
m.
V1N 10/05/2010 08:44:53.234921 a. 00:00:00:109959 7,71
m.
V3N 10/05/2010 08:44:53.254914 a. 00:00:00:099963 6,97
m.
V3N 10/05/2010 08:44:58.828946 a. 00:00:00:129816 9,5
m.
V2N 10/05/2010 08:45:01.394602 a. 00:00:02:084622 10,75
m.
V3N 10/05/2010 08:45:02.122920 a. 00:00:00:039905 5,15
m.
V1N 10/05/2010 08:57:45.940573 a. 00:00:00:620374 9,11
m.
V1N 12/05/2010 11:12:36.178517 a. 00:00:00:529514 5,78
m.
V2N 12/05/2010 11:12:36.258443 a. 00:00:00:829214 11
m.
V2N 13/05/2010 07:37:53.120946 a. 00:00:00:769089 14,56
m.
V1N 13/05/2010 06:15:36.902381 p. 00:00:00:539892 7,24
m.

Page 8 of 13 EN50160 Report


Type Phase Start time Duration Value [% from ref]
10/05/2010
Transient V2N 00:00:00:000019 -109,52
06:14:34.879405 a. m.
10/05/2010
Transient V3N 00:00:00:000019 -109,25
06:14:34.879405 a. m.
10/05/2010
Dip V3N 00:00:00:039999 88,23
08:37:17.614476 a. m.
10/05/2010
Dip V2N 00:00:00:029999 88,92
08:37:29.493181 a. m.
10/05/2010
Dip V2N 00:00:00:039999 88,43
08:44:53.234280 a. m.
10/05/2010
Dip V1N,V2N 00:00:00:070000 87,01
08:44:58.808353 a. m.
10/05/2010
Dip V1N 00:00:00:019999 89,45
08:45:01.762918 a. m.
10/05/2010
Dip V1N 00:00:00:039999 88,43
08:45:02.092398 a. m.
10/05/2010
Swell V1N 00:00:00:579999 112,01
08:57:45.179860 a. m.
11/05/2010
Transient V2N 00:00:00:000117 -112,82
06:08:52.984090 a. m.
11/05/2010
Transient V3N 00:00:00:000117 -0,21
06:08:52.984090 a. m.

Page 9 of 13 EN50160 Report


11/05/2010
Swell V2N 00:00:00:129999 110,6
02:13:43.797967 p. m.
Supply Voltage Dip and Interruption
Duration [ms]

Value [% from ref] 10 ≤ t ≤ 200 200 < t ≤ 500 500 < t ≤ 1000 1000 < t ≤ 5000 5000 < t ≤ 60000
90 > u ≥ 80 9 0 0 0 0
80 > u ≥ 70 1 0 0 0 0
70 > u ≥ 40 0 1 1 0 0
40 > u ≥ 5 0 1 0 0 0
5>u 3 1 0 0 0
Supply Voltage Swell
Duration [ms]

Value [% from ref] 10 ≤ t ≤ 500 500 < t ≤ 5000 5000 < t ≤ 60000

u ≥ 120 1 3 0

120 > u > 110 3 1 0

Event Summary

Page 10 of 13 EN50160 Report


12/05/2010
Dip V3N 00:00:00:550000 60,35
11:12:35.548063 a. m.
12/05/2010
Swell V1N,V2N 00:00:00:598999 129,15
11:12:35.558980 a. m.
13/05/2010
Transient V1N 00:00:00:000156 -9,6
05:51:25.927960 a. m.
13/05/2010
Transient V3N 00:00:00:000117 -113,13
05:51:25.927979 a. m.
13/05/2010
Swell V1N,V2N,V3N 00:00:03:036999 187,79
07:37:50.143362 a. m.
Supply Voltage 13/05/2010
V2N 00:00:00:180000 1,42
Interruptions 07:37:50.173171 a. m.
13/05/2010
Transient V3N 00:00:00:000507 -131,02
07:37:50.722895 a. m.
13/05/2010
Transient V2N 00:00:00:000390 80,5
07:37:50.723012 a. m.
13/05/2010
Transient V1N 00:00:00:000370 82,06
07:37:50.723031 a. m.
Supply Voltage 13/05/2010
V3N 00:00:00:419999 1,56
Interruptions 07:37:50.732387 a. m.
13/05/2010
Transient V2N 00:00:00:000741 -80,53
07:37:50.836278 a. m.
13/05/2010
Transient V2N 00:00:00:000292 -121,09
07:37:51.162673 a. m.
13/05/2010
Transient V1N 00:00:00:000507 -120,16
07:37:51.682452 a. m.
13/05/2010
Transient V2N 00:00:00:000604 -125,07
07:37:51.682452 a. m.
13/05/2010
Transient V3N 00:00:00:000565 140,57
07:37:51.682452 a. m.
Supply Voltage 13/05/2010
V3N 00:00:00:100000 2,34
Interruptions 07:37:51.731683 a. m.
13/05/2010
Transient V3N 00:00:00:000429 80,16
07:37:51.851294 a. m.
13/05/2010
Transient V1N 00:00:00:000409 -78,46
07:37:51.851314 a. m.
13/05/2010
Transient V2N 00:00:00:000117 -80,43
07:37:51.851587 a. m.
13/05/2010
Transient V3N 00:00:00:000331 -89,18
07:37:51.852270 a. m.
13/05/2010
Transient V3N 00:00:00:001970 -155,13
07:37:52.179926 a. m.
13/05/2010
Transient V1N 00:00:00:001814 141,79
07:37:52.180082 a. m.

Page 11 of 13 EN50160 Report


13/05/2010
Transient V2N 00:00:00:001814 -153,73
07:37:52.180082 a. m.
13/05/2010
Transient V1N 00:00:00:000585 -99,71
07:37:52.441638 a. m.

13/05/2010
Transient V2N 00:00:00:000175 -93,98
07:37:52.441657 a. m.
13/05/2010
Transient V3N 00:00:00:000877 99,04
07:37:52.441657 a. m.
13/05/2010
Transient V3N 00:00:00:000819 78,64
07:37:52.449969 a. m.
13/05/2010
Transient V1N 00:00:00:000565 -79,62
07:37:52.450222 a. m.
13/05/2010
Transient V2N 00:00:00:000292 -78,45
07:37:52.450495 a. m.
13/05/2010
Transient V3N 00:00:00:000624 -118,08
07:37:52.451217 a. m.
Supply Voltage 13/05/2010
V3N 00:00:00:129999 1,95
Interruptions 07:37:52.470927 a. m.
13/05/2010
Transient V2N 00:00:00:000429 146,1
07:37:52.601466 a. m.
13/05/2010
Transient V2N 00:00:00:001365 -119,82
07:37:52.941124 a. m.
13/05/2010
Dip V1N,V2N,V3N 00:00:00:469999 27,2
07:39:07.967418 a. m.
13/05/2010
Swell V1N,V2N,V3N 00:00:00:819000 156,1
07:39:07.967880 a. m.
13/05/2010
Transient V3N 00:00:00:000312 -88,91
07:39:07.972321 a. m.
13/05/2010
Dip V1N,V2N 00:00:00:085000 71,44
07:39:08.442271 a. m.
13/05/2010
Dip V3N 00:00:00:039999 81,01
07:39:08.537321 a. m.
13/05/2010
Dip V2N 00:00:00:039999 84,96
07:39:08.587207 a. m.
13/05/2010
Dip V1N 00:00:00:029999 87,74
07:39:08.637186 a. m.
13/05/2010
Swell V2N 00:00:00:039999 112,26
07:39:08.797141 a. m.
13/05/2010
Swell V1N 00:00:00:029999 110,25
07:39:08.847106 a. m.
13/05/2010
Dip V2N 00:00:00:400000 66,36
06:15:36.141649 p. m.
13/05/2010
Swell V1N,V3N 00:00:00:469999 124,9
06:15:36.141747 p. m.

Page 12 of 13 EN50160 Report


14/05/2010
Transient V1N 00:00:00:000136 -2,9
08:42:43.388596 a. m.
14/05/2010
Transient V3N 00:00:00:000136 -141,98
08:42:43.388596 a. m.
16/05/2010
Transient V2N 00:00:00:000136 -123,37
06:19:13.477460 a. m.
16/05/2010
Transient V1N 00:00:00:000117 -2,83
06:19:13.477480 a. m.

Page 13 of 13 EN50160 Report