The Angus Fire Top Pourer Set (TPS) Mk5 Four basic body sizes cover flow ranges
is designed for use in foam systems for from 75 l/min (20 US gal/min) to 3,300 l/
the protection of fixed roof flammable min (870 US gal/min) at inlet pressures
liquid storage tanks and combines foam between 3 bar (45 psi) and 10 bar (150
generation, vapour sealing and foam psi).
pouring in a robust, low-maintenance The discharge is enhanced by a deflector
design. The TPS Mk5 represents over plate fitted to the outlet which disperses
35 years of product development and the finished foam against the tank wall.
operating experience. Modern materials This ensures a rapid spread across the
such as graphite and stainless steel are surface of the fuel, whilst lowering
employed to ensure each unit performs the application velocity, reducing
to the precise pressure and flow standards contamination of the foam by the fuel
laid down by Underwriters Laboratories and minimising splash.
(UL) and NFPA.
Foam Tube Length
Key Features
The standard or minimum length of
z Narrow pressure tolerance bursting the foam dispersal tube projecting into
disc for increased reliability the tank interior is shown in the below
z Impregnated graphite bursting disc for table under “E”. It is designed for pourers
leak free operation mounted (usually using the Angus Fire
z Reusable bursting disc holder mounting kit) directly on to the tank
wall. This positions the deflector plate
z Air/liquid flow controller for optimum
at the optimum position inside the
foam quality
tank to spread the foam evenly around
z Body lid retained by stainless steel the interior. Other lengths of the foam
swing bolts for increased safety dispersal tube can be specified by the
z Captive foam enhancer for ease of customer.
access and maximum foam quality Angus Foam
z Integral one piece construction, With the correct foam concentrate, Top ANSI RF #150 inlet / outlet flange sizes*
including deflector, for quick and
Pourer Sets can be used in applications Inlet outlet
reliable installation
involving either hydrocarbon or water TPS 50 2” 4”
z Heavy duty welded construction to miscible fuels. Angus Tankmaster foam
minimise distortion during operation TPS 80 3” 6”
is recommended for hydrocarbon fuels
Units without a vapour seal are also and Angus Alcoseal or Tridol ATF for polar TPS100 4” 8”
available for total flooding of open roof solvent chemicals. TPS150 6” 10”
tanks. *ISO and DIN flanges also available
GRAPHITE DISC
± 0.05 bar For applications involving water miscible
(± 0.75 psi). Each orifice is specifically designed fuels, Alcoseal at 6% or Tridol ATF produces
to allow the correct amount of foam a 25% drainage time of around 8 – 10
'O' RING
premix into the foam-making tube after minutes at 5 bar inlet pressure to the TPS
taking into account the supply pressure unit. Recommended application rates
DISC HOLDER TOP POURER
BOX WALL
at the inlet flange, the foam type and will vary depending on the specific water
concentration. miscible product(s) involved.
Angus Fire Top Pourer Sets are supplied as standard with a unique yellow
thermoplastic powder paint finish, between 250 and 450 microns thick, suitable for
most operating conditions. Alternative colours are available.
Performance Envelope
3000
400
300 1200
FLOW l.p.m.
FLOW l.p.m.
1000 2000
FLOW l.p.m.
2200
FLOW l.p.m.
200 800
100 400
0 0 0 0
0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10
PRESSURE bar PRESSURE bar PRESSURE bar PRESSURE bar
Foam Top Pourer Set Mk5
Installation Options A hole is cut into the tank side. Then the need for access to the inside of
the Angus mounting kit flange is the tank. The TPS body with its foam
The Angus mounting kit allows the TPS
secured from outside by passing the deflector is then bolted on to the
to be sited without the need for access
stud nuts through the access hole. adapter kit flange in the normal way.
from inside the tank.
They are then tightened on the inside
WARNING: Before any cutting work by reaching through the access hole
is done to the tank wall, which could from outside the tank, removing
cause sparks and hot spots, it must be
ensured that the tank is empty and
purged of any flammable vapour.
Notes:
1. All inlets should be positioned equally around the circumference of the tank, but the
distance between any 2 pourers should not exceed 30m on fixed cone roof tanks.
2. Consideration may have to be given to ensuring the foam application does reach
the centre of large tanks.
Angus Fire is a company assessed to ISO 9001.