You are on page 1of 24

Section 7 - Troubleshooting

7.1 Troubleshooting
The following information is intended as a guide to
WARNING
troubleshooting some common nontechnical equip- Before equipment operation, ALL guards,
ment problems. Many problems can be resolved covers and protective devices MUST BE in
using corrective maintenance, adjustment or minor place and securely fastened. Serious personal
repair. Refer to the Vendor supplied literature, injury could result from contact with exposed or
electrical schematics and mechanical prints for moving components.
additional information.
CAUTION
For engine related issues, refer to Operation and AVOID SERVICING complex components such
Maintenance Manual, Industrial and Power Genera- as: printed circuit boards, and, ECM's, not
tion QSX15 Engines, Bulletin No. 3666423 or specifically authorized by Cummins Inc. Contact
contact the Cummins Customer Assistance Center a Cummins Fire Power Customer Service
at 1-800-DIESELS (1-800-343-7357). Department toll free at 1-800-343-7357 before
performing any extensive maintenance.
It is beyond the scope of this manual to cover all of
the various problems that may affect engine perfor-
mance.
CAUTION
Never climb or stand on the equipment frame,
WARNING guards, or enclosures. Contact with exposed or
The status checks should be performed ONLY moving components can cause personal injury
by a qualified technician. Contact with exposed or equipment damage.
electrical components could cause extreme
personal injury or death.

Fire Power Pump Engine 7-1


Doc. 9779, Rev-10-07
Table of Contents
Problem Page
Fault Code Chart ......................................................................................................................................... 7-3
7.1 Alternator Overcharging with the Engine Running ................................................................................ 7-4
7.2 Neither Battery is Charging with the Engine Running ........................................................................... 7-4
7.3 Only One Battery is Charging with the Engine Running ....................................................................... 7-5
7.4 Voltage Indications Differ ....................................................................................................................... 7-5
7.5 Coolant Contamination .......................................................................................................................... 7-6
7.6 Excessive Coolant Loss ........................................................................................................................ 7-7
7.7 Coolant Temperature Above Normal ..................................................................................................... 7-8
7.8 Coolant Temperature Below Normal (Engine Off) ..............................................................................7-10
7.9 Raw Water Drain Steaming ................................................................................................................. 7-11
7.10 Raw Water Solenoid Valve Fails to Operate .....................................................................................7-11
7.11 Auto Start Failure - Does not Crank on A or B .................................................................................. 7-12
7.12 Auto Start Failure - Cranks but does not Start .................................................................................. 7-12
7.13 Auto Start Failure – Engine Starts but Crank Terminate Does Not Occur ........................................ 7-13
7.14 Manual Start Failure from Solenoid Lever - Does not Crank on A or B ............................................ 7-14
7.15 Manual Start Failure from Control Panel - Does not Crank on A or B .............................................. 7-14
7.16 Engine Cranks Normally But Will Not Start (No Exhaust Smoke) ..................................................... 7-15
7.17 Engine Cranks Slowly But Does Not Start ........................................................................................ 7-17
7.18 Engine Stops During Operation ......................................................................................................... 7-17
7.19 Engine Will Not Reach Rated Speed (RPM) .....................................................................................7-19
7.20 Engine Will Not Shut Off Remotely ................................................................................................... 7-20
7.21 Engine Will Not Shut Off Locally ....................................................................................................... 7-20
7.22 Fuel Consumption Is Excessive ........................................................................................................7-20
7.23 Fuel or Lubricating Oil Leaking From Exhaust Manifold ................................................................... 7-21
7.24 Lubricating Oil is Contaminated ........................................................................................................7-21
7.25 Lubricating Oil Consumption Excessive ............................................................................................ 7-22
7.26 Lubricating Oil in the Coolant ............................................................................................................ 7-23
7.27 Engine Overspeed Trip ...................................................................................................................... 7-23
7.28 Tachometer Does Not Indicate Engine Speed .................................................................................. 7-24
FAULT SID(S)
CODE PID(P) SPN
(LAMP) FMI FMI DESCRIPTION
151 P110 110 Engine Coolant Temperature High – Critical
(Yellow) 0 0
214 P175 175 Engine Oil Temperature High - Critical
(Yellow) 0 0
235 P111 111 Engine Coolant Level Low - Critical
(Yellow) 1 1
259 S017 632 Fuel Shutoff Valve - stuck open
(Red) 7 7
284 S221 1043 Engine Speed/Position Sensor #1 (Crankshaft) Supply Voltage Circuit - shorted low
(Red) 4 4
295 P108 108 Ambient Air Pressure Sensor Circuit - data incorrect
(Yellow) 2 2
341 S253 630 Engine Control Module – data lost
(Red) 2 2
343 S254 629 Engine Control Module - Warning internal hardware failure
(Red) 12 12
378 S018 633 Fueling Actuator #1 Circuit - open circuit
(Red) 5 5
379 S018 633 Fueling Actuator #1 Circuit - grounded circuit
(Red) 6 6
394 S02 0 635 Timing Actuator #1 Circuit - open circuit
(Red) 5 5
399 S084 1245 Timing Actuator #2 Circuit - grounded circuit
(Red) 6 6
415 P100 100 Engine Oil Pressure Low – Critical
(Yellow) 1 1
432 S230 558 Accelerator Pedal Idle Validation Circuit - out of calibration
(Yellow) 13 13
449 P094 94 Fuel Pressure High - Warning
(Red) 0 16
451 P157 157 Injector Metering Rail #1 Pressure Sensor Circuit - shorted high
(Red) 3 3
452 P157 157 Injector Metering Rail #1 Pressure Sensor Circuit - shorted low
(Red) 4 4
482 P094 94 Fuel Pressure Low - Warning
(Red) 1 18
483 P129 1349 Injector Metering Rail #2 Pressure Sensor Circuit - shorted high
(Red) 3 3
484 P129 1349 Injector Metering Rail #2 Pressure Sensor Circuit - shorted low
(Red) 4 4
485 P129 1349 Injector Metering Rail #2 Pressure High - Warning
(Red) 0 16
486 P129 1349 Injector Metering Rail #2 Pressure Low - Warning
(Red) 1 18
496 S221 1043 Engine Speed/Position Sensor #2 (Camshaft) Supply Voltage
(Red) 11 11
546 P094 94 Fuel Delivery Pressure Sensor Circuit - shorted high
(Red) 3 3
547 P094 94 Fuel Delivery Pressure Sensor Circuit- shorted low
(Red) 4 4
553 P157 157 Injector Metering Rail #1 Pressure High - warning level
(Red) 1 18
559 P157 157 “Unexpectedly low rail pressure was detected on the front three cylinders.“
(Red) 1 18
731 S064 723 Engine position signal from the camshaft and crankshaft engine position sensors
(Red) 7 7 do NOT Match up.
753 S064 723 Engine position signal from the camshaft and crankshaft engine position sensors
(Red) 2 2 do NOT match up.
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.1 Alternator Overcharging Batteries have failed. Check the condition of the
with the Engine Running batteries. Replace any defective
batteries.
NOTE: If the batteries are
overcharged while the engine is Voltage regulator malfunction. Test the alternator electrically.
not running, troubleshoot the Contact an Authorized Cummins
customer supplied battery Repair Facility.
charging system.
Replace the alternator as neces-
sary.

7.2 Neither Battery is Charging Battery cables or connections are Check the battery cables and
with the Engine Running loose, broken, or corroded connections. Ensure that all
(excessive resistance). connections are free of corrosion
NOTE: If one or both batteries do and that no cables are broken.
not charge with the engine
stopped, troubleshoot the cus- Alternator rotor is not rotating. Test the alternator mechanically.
tomer supplied battery charging If the alternator shaft does not
system. spin freely because of a bad
bearing, replace the alternator.
NOTE: If only one battery is
maintaining charge, go to Only If the alternator does not turn
One Battery is Charging with the because of a bad drive belt,
Engine Running. replace the drive belt. Refer to
Section 6 - Maintenance.

If the alternator does not charge


because of poor drive belt
tension, adjust belt tension. Refer
to Section 6 - Maintenance.

If the alternator pulley spins


freely on the shaft because of a
broken key, replace the alterna-
tor. Contact an Authorized
Cummins Repair Facility.

Battery isolator input has faulted. Test continuity from the alternator
to the battery isolator input.
Repair any open circuit.

Test continuity through the


battery isolator. If an internal
open circuit is detected, replace
the battery isolator.

Alternator excitation is lost. Test the alternator electrically.


Replace the alternator diode as
necessary.

7-4
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.2 Neither Battery is Charging Alternator excitation is lost Locate and repair the open circuit
with the Engine Running. (Cont'd). or short to ground in the alterna-
(Cont'd) tor excitation wiring as neces-
sary.

Alternator internal voltage Test the alternator electrically. If


regulator is malfunctioning. required, replace the alternator.
Contact an Authorized Cummins
Repair Facility.

7.3 Only One Battery is Charg- Battery has failed. Check battery charge.
ing with the Engine Running
Battery cables or connections are Check the battery cables and
NOTE: If one or both batteries do loose, broken, or corroded connections. Ensure connections
not charge with the engine (excessive resistance). clean and that no cables are
stopped, troubleshoot the cus- broken.
tomer supplied battery charging
system. Battery isolator has failed. Remove the battery isolator. Test
the internal diodes for open
NOTE: If neither battery is circuit or short to ground. Re-
maintaining charge, go to Neither place the battery isolator as
Battery is Charging with the necessary.
Engine Running.

7.4 Voltage Indications Differ Voltmeter is providing false See Voltage Indications Differ in
indication. this section.
NOTE: The two voltmeters may
differ slightly due to calibration One battery is discharged or Check battery condition. Replace
differences between the meters. failing. failing battery elements.
Normal differences in battery
condition may also cause differ- Check wiring for corrosion.
ences in indication. These are Ensure good electrical contact.
normal differences and require no
action. Charge discharged batteries by
running the engine or with an
external battery charger. If the
battery does not charge with the
engine running, go to Only One
Battery is Charging with the
Engine Running.

Check for apparent wire damage


or shorts to grounds. Replace the
failed fuse.

7-5
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.4 Voltage Indications Differ Breaker 1 or Breaker 2 is tripped. If the breaker trips again, locate
(Cont'd) and correct the overload or repair
the short circuit.

Open circuit or short to ground in Locate and repair the electrical


indicator wiring. fault.

Voltmeter has failed. Remove wiring at the voltmeter


and apply test voltage. Replace
the faulted voltmeter as neces-
sary.

7.5 Coolant Contamination Coolant is rusty and has debris. Drain and flush the cooling
system per the instructions in
Section 6 - Maintenance.

Replace the coolant water filter


per the instructions in Section 6.

Refill with correct mixture of


antifreeze and water per the
instructions in Section 6 - Mainte-
nance.

Drain and flush the cooling


system per the instructions in
Section 6 - Maintenance.

Lubricating oil cooler is leaking oil Check the lubricating oil cooler
into the coolant. Coolant begins for coolant leaks and cracks.
to have the texture and color of
chocolate pudding. Replace the oil cooler gasket or
other parts as necessary.

Refill with correct mixture of


antifreeze and water.

If the problem persists, the


cylinder block may be cracked or
porous. Contact the Cummins
Authorized Repair Facility.

7-6
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.5 Coolant Contamination Coolant Heat Exchanger is Drain and flush the cooling
(Cont'd) leaking raw water into the cool- system per the instructions in
ant. Coolant volume increases Section 6 - Maintenance.
and pressure is relieved when
the unit is operating. Antifreeze Perform a pressure test of the
concentration decreases. raw water side of the heat
exchanger. If the heat exchanger
leaks, it should be replaced.

Check and adjust raw water


pressure regulator set points.

Check and, if required, replace


the zinc plug.

Refill with correct mixture of


antifreeze and water per the
instructions in Section 6 - Mainte-
nance.

Coolant is inadvertently contami- Drain and flush the cooling


nated with unknown liquids. system. Refill with correct mixture
of antifreeze and water per the
instructions in Section 6 - Mainte-
nance.

Contact an Authorized Cummins


Repair Facility.

7.6 Excessive Coolant Loss Adequate coolant was not added Check the coolant level. Add
following previous maintenance coolant as required and check
activities. engine operation. If coolant loss
persists, check for other prob-
lems.

Inadvertent coolant leak is Inspect the engine for coolant


present. leaking from drain cocks or vents.
Close the leaking drain or vent.
Add coolant as required and
check engine operation.

Cooling system hose is leaking. Check the condition of the hoses.


Replace and/or tighten loose
hose clamps. Replace any
damaged hoses as necessary.
Add coolant as required and
check engine operation.

7-7
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.6 Excessive Coolant Loss Pressure cap is malfunctioning or Check that the pressure cap does
(Cont'd) has low-pressure rating. not relieve coolant under normal
operating conditions. Replace a
leaking pressure cap, (Cummins
Fire Power Part No. 11407). Add
coolant as required and check
engine operation.

Mechanical coolant leak. Inspect the engine for coolant


leaking from manifold, expansion
and pipe plugs, fittings, lubricat-
ing oil cooler, water pump seal,
cylinder block, and other compo-
nents that have coolant flow.
Repair leaking components. Add
coolant as required and check
engine operation.

7.7 Coolant Temperature Engine is overheating. Refer to the Coolant Temperature


Above Normal Above Normal in this Section.

NOTE: The thermostat’s normal Raw water flow is improperly Check that the raw water mani-
operating temperature range is aligned. fold is aligned for normal flow
82-95° C (180-203° F) The High through the solenoid valve
Water Temperature lamp on the (preferred) or bypass flow around
local control panel. The lamp only the solenoid valve (alternative).
illuminates if the engine is Align flow if required.
running. If the lamp is illuminated
or if temperature is otherwise Raw water pressure regulator is Check the raw water pressure
excessive, the engine should be improperly adjusted. indication. If pressure is indicated
stopped as soon as practical and but is low, adjust the regulator. If
the problem corrected. NOTE: Pressure should be about pressure is not indicated or is
414 kPa [60 psig] or slightly less. excessively low, go to raw water
solenoid has failed.

Raw water solenoid has failed. If pressure is excessively low


when aligned for normal flow,
open the bypass valves. When
practical, troubleshoot the raw
water solenoid valve. Refer to
Raw Water Solenoid Valve Fails
to Operate in this section. If the
solenoid valve operates, replace
the pressure regulator.

7-8
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.7 Coolant Temperature Raw water solenoid has failed. If pressure is excessively low
Above Normal. (Cont'd) (Cont'd) when aligned for bypass flow,
open the normal valves.

Check the raw water strainer for


blockage per the instructions in
Section 6 - Maintenance. Clean
the strainer if necessary.

Check the raw water piping for


blockage. Clean the piping if
necessary.

Raw water piping or heat ex- Remove any blockage. Check for
changer is plugged. flow through the heat exchanger.
Replace the heat exchanger as
necessary.

Coolant level is below specifica- Check the coolant level. If


tion. coolant level is excessively low,
go to Excessive Coolant Loss in
this section.

Cooling system hose is collapsed Inspect the hoses. Replace any


or restricted. damaged hoses as necessary.

Coolant thermostat is malfunc- Remove and test the coolant


tioning. thermostat per the instructions in
Section 6 - Maintenance. Re-
place the defective thermostat.

Coolant water pump is malfunc- Remove and inspect the water


tioning. pump. Replace the defective
water pump. Contact an Autho-
rized Cummins Repair Facility.

Lubricating oil is contaminated Check the appearance of the lubri-


with coolant or fuel. cating oil. If the color and texture is
abnormal, refer to the Lubricating
Oil Contaminated in this Section.

Cooling system hose is col- Replace any damaged hoses as


lapsed, restricted, or leaking. necessary.
Inspect the hoses.

7-9
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.7 Coolant Temperature Coolant mixture of antifreeze and Verify the concentration of
Above Normal (Cont'd) water is not correct. antifreeze in the coolant. Add
antifreeze or water to correct the
concentration.

Lubricating oil level is above or Check the oil level per the
below specification. instructions in Section 6.

Coolant temperature sender is Replace the temperature sender


malfunctioning. as necessary.

Coolant temperature gauge is Replace the temperature gauge


malfunctioning. as necessary.

Coolant temperature switch is Remove the temperature switch.


malfunctioning. Test the temperature switch.
Repair or replace the switch, if
necessary.

7.8 Coolant Temperature Below The 120 VAC power supply to the Connect the power supply.
Normal (Engine Off) coolant heater is not connected. Correct any electrical faults in the
supply circuit.

The heater’s overload thermostat Ensure that there is coolant in the


has operated. heater. Allow time for the auto-
matic overload reset to occur.

Coolant temperature sender is Replace the temperature sender.


malfunctioning.

Coolant temperature gauge is Replace the temperature gauge.


malfunctioning.

Coolant is not free to circulate Ensure that the coolant hoses are
through the heater. clear. Repair or replace hoses as
necessary.

The coolant heater has failed Replace the coolant heater.


electrically.

Electronic fault codes are active. Refer to the Vendor supplied


literature or contact an Autho-
rized Cummins Repair Facility for
Fault Codes.

Coolant thermostat has failed Test operation of the thermostat.


open. Replace the thermostat per the
instructions on Section 6 -
Maintenance as necessary.

7-10
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.8 Coolant Temperature Below Coolant temperature sender is Replace the temperature sender.
Normal (Engine Running) malfunctioning.
(Cont'd)
Coolant temperature gauge is Replace the temperature gauge.
malfunctioning. Refer to Section 6 - Maintenance.

7.9 Raw Water Drain Steaming Raw water flow did not start when Check engine coolant tempera-
the engine started. ture. Go to, Coolant Temperature
NOTE: The raw water drain from Above Normal in this section.
the Coolant Heat Exchanger may
steam if raw water flow is inad- Engine coolant is leaking into the Remove the coolant heat ex-
equate when the engine is raw water piping in the coolant changer and perform the pres-
running. It may also steam shortly heat exchanger. sure test. Refer to Section 6 -
after the engine is stopped. If Maintenance. If pressure is not
coolant is leaking into the raw maintained, replace the heat
water drain piping, the steaming exchanger.
may last for some time while the
engine cools. Antifreeze may also
be observed in the raw water
drain.

7.10 Raw Water Solenoid Valve Solenoid valve fails to close Replace the solenoid valve.
Fails to Operate when the engine stops. Clean the raw water strainer
more frequently. Increase the
NOTE: The raw water solenoid frequency of operational testing.
failure may fail to open or to
close. The normally closed valve Solenoid valve fails to energize. Check electrical continuity and
may fail to open when the engine insulation from ground to the
starts. This fault will prevent raw solenoid. Repair any open or
water flow through the normal short circuits in the wiring.
valves. Bypass flow should be
aligned in this event. The valve Solenoid fails to open mechani- Apply temporary voltage to the
may also fail to close because of cally. NOTE: Apply 24 VDC. solenoid. If the solenoid fails to
mechanical blockage. In this operate, replace it. Contact an
event, the raw water flow from Authorized Cummins Repair
the heat exchanger does not stop Facility.
when it should. Depending upon
the fire protection system piping,
the open solenoid valve may
drain all water from the fire
protection system piping that is
higher than the engine’s piping.

7-11
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.11 Auto Start Failure - Does The electrical connection from Test continuity and insulation
not Crank on BATT A or B the fire protection system to from ground between the fire
terminal board has failed. protection system and the engine
control panel. Locate and repair
any electrical fault in the field
wiring or in the fire protection
system panel.

The electrical connection from Test continuity and insulation


terminal board to relay has failed. from ground between the terminal
board and the relay. Locate and
repair any electrical fault.

Relay has failed. Check de-energized continuity at


relay. Replace relay if the circuit
is open. Contact an Authorized
Cummins Repair Facility.

The Fire Protection System fails Locate and correct the common
to produce either redundant start mode fault in the Fire Protection
signal to the fire pump. System.

7.12 Auto Start Failure - Cranks The overspeed switch as actu- Press the RESET switch on the
but does not Start ated. The overspeed lamp is local control panel.
illuminated on the local control
NOTE: The fire pump engine will panel.
crank automatically when either
solenoid A or solenoid B is Control power from the Fire Locate and correct the fault in the
selected at the fire protection Protection System is not avail- Fire Protection System or the
system. However, the engine able at local control panel TB-1. field wiring to the local control
does not start. The engine will panel as necessary.
start locally. If local starting
problems are identified, go to the Circuit Breaker CB is open in the Check whether Circuit Breaker
applicable Manual Start Failure local control panel. CB at the local control panel is
troubleshooting table. open.

If open, reset the circuit breaker.


Locate and correct any electrical
faults in the control panel. Press
the RESET Switch on the local
control panel.

The AUTO/MANUAL Rocker Open Circuit Breaker CB at the


Switch fails to select AUTO local control panel and test
mode. switch operation electrically as
necessary.

Replace the switch or repair other


electrical faults as necessary.
When done, close Circuit Breaker
CB at the local control panel.

7-12
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.12 Auto Start Failure - Cranks The overspeed switch has failed. Check power and grounding to
but does not start (Cont'd) the overspeed switch. Repair any
electrical faults.

Test and adjust the overspeed


setting. Refer to Overspeed Set
Point Adjustment and Testing in
Section 6 - Maintenance. Re-
place switch as necessary.

7.13 Auto Start Failure – The overspeed switch not With the engine running, verify
Engine Starts but Crank correctly adjusted or has failed. speed sensor input to the
Terminate Does Not Occur overspeed switch.

If signal is not present, see


Speed Sensor Has Failed. The
tachometer also indicates zero
speed.

Adjust the overspeed switch


crank terminate set point. Re-
place the overspeed switch as
necessary.

Breaker has tripped. The raw Open the raw water bypass
water solenoid valve fails to valves. RESET breaker switch.
open. Locate and repair any local
electrical fault.

The speed sensor has failed. The Locate and repair any electrical
tachometer indicates zero RPM. fault in the speed sensor circuitry.
Replace the speed sensor as
necessary.

An electrical fault is present in Test continuity and insulation


the Fire Protection System. from ground between the fire
protection system and the engine
control panel. Locate and repair
any electrical fault in the field
wiring.

An electrical fault is present Test continuity and insulation


between Control Panel and the from ground between the fire
Fire Protection System. protection system and the engine
control panel. Locate and repair
any electrical fault in the field
wiring.

7-13
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.14 Manual Start Failure from Crank Batter A and B switches Test electrical operation of Crank
Solenoid Lever - Does not failed to make contact. Batt A and B Switches. Replace
Crank on A or B the faulty switches as necessary.

NOTE: The fire pump engine will Relay fails in the local manual Test the electrical operation of
not crank locally when either mode. the relay. Replace the relay if
solenoid lever is actuated. faulted.

Solenoid A or Solenoid B fails to Test continuity and insulation


energize due to electrical fault in from ground between the CRANK
the power or ground circuit. BATT A/B Switches, Relay, and
the Starter Solenoid. Also, check
the solenoid coil connection to
ground. Locate and repair any
electrical fault.

Solenoid A/B failed to operate. Test the electrical operation of


the Solenoid A and Solenoid B.
Replace the faulty solenoids as
necessary.

Starter motor has failed. Replace the starter motor.

An electrical fault is present in Test continuity and insulation


the power or ground circuit for from ground between the battery
the starter motor. splice, the ground connection,
and the starter motor. Locate and
repair any electrical fault.

Engine is seized. Bar the engine over to break the


seizure. Contact an Authorized
Cummins Repair Facility.

7.15 Manual Start Failure from The MANUAL Mode Rocker Test the electrical operation of
Control Panel - Does not Switch contact fails to close. the AUTO/MANUAL Rocker
Crank on A or B Switch. Replace the faulty switch
as necessary.
NOTE: The fire pump engine will
not crank locally from the control An electrical fault exists in the Test continuity and insulation
panel when either CRANK BATT signal power circuit or the ground from ground between the AUTO/
A or CRANK BATT B is selected, to the Relays. MANUAL Rocker Switch and the
however, it does start when a Relays. Check the relay connec-
solenoid lever is actuated. tion to ground. Locate and repair
any electrical fault.

Breaker Switch has tripped. The Open the raw water bypass
raw water solenoid valve also valves. Locate and repair any
fails to open. local electrical fault. RESET the
Breaker Switch.

7-14
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.15 Manual Start Failure from An electrical fault exists in the Test continuity and insulation
Control Panel - Does not signal power circuit or the ground from ground between breaker
Crank on A or B (Cont'd) to the overspeed switch’s crank and the overspeed switch’s crank
circuit. circuit. Check the crank circuit
output to the CRANK BATT
Switches. Locate and repair any
electrical fault.

Overspeed switch crank circuit Test and adjust the crank setting
fails to reset with engine shut- as necessary. Refer to
down. Overspeed Set Point Adjustment
and Testing in Section 6. Replace
the overspeed switch as neces-
sary.

7.16 Engine Cranks Normally Electronic fault codes are active. Refer to the Vendor supplied
But Will Not Start (No literature or contact an Autho-
Exhaust Smoke). rized Cummins Repair Facility for
Fault Codes.

Electronic control module (ECM) Disconnect the battery cables for


is locked up. 30 seconds. Then, reconnect the
battery cables, and start the
engine.

Battery voltage supply to the Check the battery connections,


electronic control module (ECM) the fuses, and the battery supply
is low, interrupted, or open. circuit.

No fuel in supply tank. Check and replenish fuel supply.


Check fittings and hose connec-
tions and hose conditions.

Air is in the fuel system. Check for air in the fuel system.
Tighten or replace the fuel
connections, fuel lines, fuel tank
stand pipe and fuel filters as
necessary. Vent air from the
system.

Fuel drain line is restricted. Check the fuel drain lines for
restriction. Clear or replace the
fuel lines, check valves, or tank
vents as necessary.

Fuel filter is clogged. Replace the fuel filter. Refer to


Change Fuel Filter in Section 6 -
Maintenance.

7-15
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.16 Engine Cranks Normally Fuel grade is not correct for the Operate the engine from a tank of
But Will Not Start (No application or the fuel quality is high-quality no. 2 diesel fuel.
Exhaust Smoke) (Cont'd) poor.

Fuel injection pump is malfunc- Contact an Authorized Cummins


tioning. Pump timing incorrect. Repair Facility.

Fuel tank is empty. Fill the fuel supply tank.

Fuel pump overflow valve is Check the overflow valve.


malfunctioning. Replace if necessary.

Fuel suction line is restricted. Check the fuel suction line for
restriction.

Fuel connections on the suction Tighten all the fuel fittings and
side of the fuel lift pump are connections between the fuel
loose. tanks and fuel lift pump.

Fuel suction stand pipe in the fuel Check and repair the stand pipe,
tank is broken. if necessary.

Fuel supply is not adequate. Locate and correct the restriction


in the customer supplied fuel
lines to the engine.

Fuel tank air breather is blocked. Clean the fuel tank breather.

Fuel lift pump is malfunctioning. Check the fuel lift pump for
correct operation. Check the
pump output pressure. Replace
the fuel lift pump if necessary.

Injection pump drive shaft or Repair or replace the injection


drive shaft key is damaged. pump.

Fuel injectors are plugged. Replace the fuel injectors.

Moisture is in the wiring harness Dry the connectors with Cummins


connectors. electronic cleaner, Part Number
3824510.

Starter motor rotation is not Check the direction of crankshaft


correct or not turning engine. rotation. Replace the starter
motor as necessary. Contact an
Authorized Cummins Repair
Facility.

7-16
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.17 Engine Cranks Slowly But The battery cable connections Check the battery cables and
Does Not Start are loose, broken, or corroded connections. Ensure that connec-
creating excessive resistance. tions are clean and tight.
NOTE: Typical engine cranking
speed is 120 RPM. Engine The battery is not properly Recharge the battery. If the
cranking speed can be checked charged or has failed. battery doers not take the
with a hand-held tachometer, charge, replace it.
stroboscope, or electronic service
tool. Lubricating oil level is too high. Check the oil level per instruc-
tions in Section 6. Drain any
excess oil.

Lubricating oil is the wrong grade Check the grade and type of oil.
or type. Refer to Lubricating Oil Recom-
mendations and Specifications in
Section 6.

If the wrong type or grade of oil is


present, drain and replace it.
Refer to Change Lubricating Oil
and Filters in Section 6.

Engine temperature is too low. Troubleshoot per Coolant Tem-


perature Below Normal (Engine
Off) in this section.

Starter motor is malfunctioning. Replace the starter motor.


Contact an Authorized Cummins
Repair Facility.

7.18 Engine Stops During Normal automatic mode shut- No action required. This is a
Operation down occurs when the fire desirable outcome.
protection systems removes the
signal power feed to the local
control panel.

The selected engine control For instructions on how to read


module (ECM) has detected a active fault codes, refer to
serious fault condition. The Diagnostic Fault Codes in the
ECM’s STOP light is displayed. Vendor supplied literature or
contact a Cummins Authorized
Repair Facility.

7-17
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.18 Engine Stops During In the automatic mode, the signal Locate and correct the electrical
Operation (Cont'd) power feed is lost from the fire fault in the fire protection system
protection system to the control or the field wiring to the engine
panel. control panel.

Circuit breaker on control panel Locate and correct the electrical


tripped. fault in engine control panel.
RESET the tripped breaker.

An overspeed trip has occurred. Remote indications may also be


The overspeed trip lamp illumi- present. Overspeed switch failure
nated on the local control panel. has occurred. The trip indications
may not be present. Go to Engine
Overspeed Trip in this section.

Power supply or grounding fault Locate and correct the electrical


exists at the Electronic Control fault in the power supply or
Module. grounding for the ECM.

The selected ECM has failed. Select the alternate ECM.


Replace the failed ECM. Contact
an Authorized Cummins Repair
Facility.

Fuel tank level is low. Fill the fuel tank. Fill and bleed
the fuel lines to the engine.

Clogged fuel tank air breather Clean the fuel tank breather.
hole.

Fuel piping to engine is clogged. Clean and repair engine fuel


piping.

The fuel filter is clogged. Replace the fuel filter. Refer to


Change Fuel Filter in Section 6.

Air is trapped in the low pressure Bleed the fuel lines. Refer to Air
fuel lines at the engine. in Fuel in Section 6.

Fuel lift pump has failed. Check the fuel lift pump for
correct operation. Check the
pump output pressure. Replace
the fuel lift pump if necessary.
Contact an Authorized Cummins
Repair Facility.

Fuel injection pump has failed. Replace the fuel injection pump.
Contact an Authorized Cummins
Repair Facility.

7-18
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.18 Engine stops during Electronic fault codes are active. Refer to the Vendor supplied
Operation (Cont'd) literature or contact an Autho-
rized Cummins Repair Facility.

Programmable parameters or Check the programmable param-


selected features are not correct. eters and the selected features
with an electronic service tool.
Set the parameters and features
again if necessary. Refer to a
Cummins Authorized Repair
Facility.

Tachometer is not calibrated. If out of calibration, calibrate the


7.19 Engine Will Not Reach Compare the tachometer reading tachometer as necessary at the
Rated Speed (RPM) with a hand held tachometer or CAL adjustment on the back of
an electronic service tool reading. the gauge. Refer to the Vendor
supplied literature for additional
information. Tachometer is
malfunctioning. Replace the
tachometer. Contact an Autho-
rized Cummins Repair Facility.

Engine power output is low. Refer to the Engine Acceleration


or Response Poor in this section.

Fuel filter requires replacement. Refer to Change Fuel Filter per


the instructions in Section 6.

Fuel grade not correct for the Operate the engine with a good
application, or fuel quality is poor. quality no. 2 diesel fuel.

Fuel suction line is restricted. Check the fuel suction line for
restriction.

Air-fuel tube leaking, waste gate Tighten the fittings, repair plumb-
diaphragm ruptured, or waste ing, replace waste gate dia-
gate plumbing damaged. phragm.

Charge air cooler restricted. Inspect the air cooler for internal
and external restrictions. Replace
the restricted cooler if necessary.

Fuel supply is not adequate. Locate and correct the restriction


in the fuel lines to the engine.

Stop circuit malfunction in the fire In the AUTO mode, the fire pump
pump controller of field wiring. engine stops upon loss of signal
power from the fire pump control-
ler. Check stop circuit in Fire
Pump Controller.

7-19
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.20 Engine Will Not Shut Off Stop circuit malfunction in the fire Correct any faults. Check for
Remotely pump controller of field wiring. short to voltage on the signal
wiring from the fire pump control-
ler to the engine control panel.
Correct any faults. Check opera-
tion of the switch contacts of the
AUTO/MANUAL switch at the
engine control panel. Replace the
switch if the switch contacts fail
to operate properly.

Electronic fault codes are active. Refer to the Vendor supplied


literature or contact a Cummins
Authorized Repair Facility.

Engine running on fumes drawn Identify and isolate the source of


into the air intake. the combustible fumes. Contact
an Authorized Cummins Repair
Facility.

7.21 Engine Will Not Shut Off Inadvertent power source is In the MANUAL Mode, the fire
Locally present from the fire pump pump engine stops when the
controller. AUTO/MANUAL Switch is
returned to the AUTO Mode.

Check for inadvertent voltage on


the wiring to terminal board at the
engine control panel.

Electronic fault codes are active. Refer to the Vendor supplied


literature or contact a Cummins
Authorized Repair Facility.

Engine running on fumes drawn Identify and isolate the source of


into the air intake. the combustible fumes.

7.22 Fuel Consumption Is Fuel is leaking. Check the fuel lines, fuel connec-
Excessive tions, and fuel filters for leaks.
Check the fuel lines to the supply
tanks. Repair any leaks.

Poor-quality fuel is being used. Assure good-quality no. 2 diesel


fuel is being used.

Defective or clogged injection Replace the defective or clogged


nozzle. injection nozzle.

Incorrect injection timing. Adjust injection timing.

7-20
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.22 Fuel Consumption Is Injection pump is adjusted Adjust or replace the injection
Excessive (Cont'd) incorrectly causing excessive pump.
injection.

Air intake or exhaust leaks. Check for loose or damaged


piping connections and missing
pipe plugs. Check the turbo-
charger and exhaust manifold
mounting. Repair any leaks.

Air intake system restriction is Check the air intake system for
above specification. restriction. Refer to Check Air
Cleaner Service Indicator in
Section 6. Replace the air filter
as necessary.

7.23 Fuel or Lubricating Oil Intake air restriction is high. Check the air intake system for
Leaking From Exhaust restriction. Refer to Check Air
Manifold Cleaner Service Indicator in
Section 6. Replace the air filter if
required.

Turbocharger drain line is re- Remove the turbocharger drain


stricted. line and check for restriction. If
required, clean or replace the
drain line.

Turbocharger oil seal is leaking. Check the turbocharger for oil


seals and for leaks. Refer to the
Turbocharger Leaks Engine Oil
or Fuel symptom tree in this
section.

7.24 Lubricating Oil is Con- Bulk oil supply is contaminated. Check the oil supply. Replace it
taminated is necessary. Drain the oil and
replace with non-contaminated
oil. Also, replace the oil filter.
Refer to Change Lubricating Oil
and Filters in Section 6.

Fuel is present in the lubricating Refer to the Fuel in Lubricating


oil. Oil in this section.

Coolant is present in the lubricat- Refer to the Coolant in Lubricat-


ing oil. ing Oil symptom tree in this
section.

Metal is present in the lubricating Contact an Authorized Cummins


oil. Repair Facility.

7-21
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.25 Lubricating Oil Consump- Verify the oil consumption rate. Check the amount of oil added
tion Excessive versus the operating hours.

External engine leak is present. Inspect the engine and its


components for seal, gasket,
tappet cover, oil cooler, or drain
cocks leaks. Repair or correct
any leaks.

Crankcase ventilation system is Check and clean the crank case


plugged. breather and vent tube per the
instructions in Section 6.

Turbocharger oil seal is leaking. Check the turbocharger compres-


sor and turbine seals. Contact an
Authorized Cummins Repair
Facility.

Lubricating oil cooler is leaking. Check for lubricating oil in the


coolant. Refer to the Lubricating
Oil in the Coolant in this section.
Contact an Authorized Cummins
Repair Facility.

Lubricating oil does not meet Change the oil and filters per the
specifications for operating instructions in Section 6.
conditions.

Lubricating oil drain interval is Verify the correct lubricating oil


excessive. drain interval. Refer to Change
Lubricating Oil and Filters in
Section 6.

Piston, cylinder liner, or piston Check for air intake system leaks.
rings are worn or damaged. Contact an Authorized Cummins
Repair Facility.

Piston rings are not seated Check blowby. If blowby is


correctly (after an engine rebuild excessive, check the piston rings
or piston installation). for correct seating. Contact an
Authorized Cummins Repair
Facility.

7-22
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.26 Lubricating Oil in the Bulk coolant supply is contami- Check the coolant expansion
Coolant nated. tank per the instructions in
Section 6. Drain the coolant and
replace with non-contaminated
coolant. Refer to Drain and Flush
Cooling System in Section 6.
Replace the coolant filter. Refer
to Change Coolant Filter in
Section 6.

Lubricating oil cooler is malfunc- Check the oil cooler. Contact an


tioning. Authorized Cummins Repair
Facility.

Cylinder head gasket damaged Contact an Authorized Cummins


or leaking. Repair Facility.

Remove intake manifold. Re-


Cylinder head is cracked or move exhaust manifold. Check
porous. for evidence of coolant leak. If
necessary, operate engine at
idle. Pressure-test the cylinder
head. Contact an Authorized
Cummins Repair Facility.

Remove the oil pan. Pressure-


Cylinder block is cracked or test the cooling system to check
porous. for leaks. Contact an Authorized
Cummins Repair Facility.

7.27 Engine Overspeed Trip Engine operated at too great a Correct the cause of the load
speed due to catastrophic load failure. Contact a Cummins
NOTE: An engine overspeed trip failure such as pipe break, pump Authorized Repair Facility.
occurs when the engine’s speed mechanical failure, or loss of
exceeds the value specified on suction.
the Factory Setting Tag de-
scribed in Section 2. The trip Engine actually operated at too Check rated speed setting as
isolates the fuel supply to the great a speed due to configura- specified on the Factory Setting
engine and it stops immediately. tion error. Tag. Refer to Rated Speed Set
The trip is indicated on the local Point Adjustment and Testing in
control panel and inside the local Section 6.
control panel on the speed
switch. Additionally, a trip output Overspeed switch is set at too Check overspeed speed setting
is supplied to the fire protection low a set point. as specified on the Factory
system for remote display. Setting Tag. Refer to Overspeed
Set Point Adjustment and Testing
in Section 6.

7-23
Section 7 - Troubleshooting

Problem Possible Cause Solution

7.27 Engine Overspeed Trip Speed switch wiring failure has Check continuity and insulation
(Cont'd) occurred. from ground for the signal power
wiring and ground wiring to the
speed switch. Replace defective
components and repair electrical
faults.

Speed switch failure has oc- If the speed switch fails to


curred. operate as per Overspeed Set
Point Adjustment and Testing in
Section 6, replace the speed
switch. Contact an Authorized
Cummins Repair Facility.

7.28 Tachometer Does Not An electrical fault exists in the Check continuity and insulation
Indicate Engine Speed tachometer power and grounding from ground for the power wiring
circuits. and ground wiring to the tachom-
eter. Contact an Authorized
Cummins Repair Facility. Re-
place defective components and
repair electrical faults.

An electrical fault exists in the This fault may also cause a


speed sensor input circuit. failure in the crank terminate
signal to the fire protection
system. Check continuity and
insulation from ground for the
speed sensor circuit. Contact an
Authorized Cummins Repair
Facility. Replace defective
components and repair electrical
faults.

The speed sensor has failed. With the engine running, check
the signal from the speed sensor
with an oscilloscope or pulse
counter. Replace the speed
sensor is it has failed. Contact an
Authorized Cummins Repair
Facility.

The tachometer has failed. Check the operation of the


tachometer with a pulse genera-
tor. Replace the tachometer is it
has failed. Contact an Authorized
Cummins Repair Facility.

7-24

You might also like