ASHIDA Numerical OC/EF Protection Relay
ASHIDA Numerical OC/EF Protection Relay
(ADITYA Series)
Protection Relay (Preliminary)
ASHIDA
Features:
• 4 Element (3 Phase + EF) Over current
IDMT with instant trip.
• Back - lit LCD display for settings.
• Display of fault current. / Load current.
• Selection of Curve: Six selectable curves
(Normal Inverse1 (C1), Normal Inverse2
(C2), Very Inverse (C3), Extremely Inverse
(C4), Long Time Inverse (C5) & Definite
Time (C6).
• Separate curve selection for phase and EF.
• Design using DSP technology.
• Latching of fault current up-to last 5 fault
• Password protection for setting.
• Site selectable CT secondary (in Model
AM00103xxxxx)
• Relay can be made ether IDMT or Define time
• Programmable operating time in instantaneous element
• Breaker Fail Function (in Model AM00104xxxxx)
General:
The ADR141A is member of Ashida Numerical Relay family (Aditya Series) design to meet demand of
low and medium switchgear control. The ADR141A is a 3 OC and 1 EF relay with Instantaneous high set
and programmable output to simplify feeder protection wiring. The ADR141A continuously monitors all 3
phase and earth current, through CT connections. The high-speed micro-controller samples this current
through a 12-bit A/D converter. The micro-controller performs powerful Digital Algorithms to find out
Amplitude of current signal, and then this value is use for protection and metering function. All
measurement is tuned to fundamental frequency. Each input current is also displayed on 16 x 2 LCD
display for metering. The Relay is having main three functions 1) Protection 2) Self-Supervision 3)
Measurement
The Relay can be supplied with different model. It can be either Definite Time or IDMT.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
1. Protection Functions:
The ADR141A give maximum benefit/cost ratio. The ADR141A give all the advantage of numerical
relay at affordable cost. Following is summery of different protection functions provided by relay.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
2. Supervision Function:
2.1 Self-supervision:
The continuously keeping track on its internal hardware and the movement it detect any failure of
any component, it give message on LCD display, This feature is very useful to give pre information
to avoid any mall - operation. In such situation it use some default setting and remain in protection
mode.
3. Measurement Function:
In normal condition this display shows all settings. Via keyboard the display can be program to show
the actual current flowing through the relay. If current excesses set value the relay gives trip
command. The type of fault is displayed on LCD display. During the fault condition the relay
measure the fault current and store in non-volatile memory. The fault current can be read via
keyboard on LCD display Last 5 fault values along with tripping counter can be view via key-
board. All settings are save in Electrically erasable read only memory and remain.
Ordering Information:
The relay is available with nos. of different option. The option is specified by model no. It is user
responsibility to specify correct model no. while ordering.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
AM XXX–XX – X – X – XX – X
Reserved for Future Use
Auxiliary Supply
01 = 18 – 52 V dc 06 = 110 V dc
PT Secondary
0 02 = 77 – 250 V dc 07 = 220 V dc
03 = 24 V dc
04 = 30 V dc
05 = 48 V dc
CT Secondary
1 = 1 Amp.
2 = 5 Amp.
3 = 1 Amp. / 5 Amp. Selectable
AM XXX XX X
3OC + 1EF Relays
001 01 Relay without extra contacts, Fix CT. CSA – 150 1/2
02 Relay with 4 Programmable extra contact, Fix CT. CSA – 150 1/2
03 Relay without extra contact, with Site Selectable CT CSA – 150 3
Sec,
04 Relay with Breaker Fail contact, 2 Ann. contact, with Fix CSA – 150 1/ 2
CT.
05 Relay with Breaker Fail contact, 2 Ann. contact, with CSA – 150 3
Site Selectable CT,
06 Reserved - -
07 Relay Without extra contacts, Fix CT. CSA – 150D Drawout 1/2
08 Relay without extra contact, with Site Selectable CT CSA – 150D Drawout 3
Sec,
09 Reserved - -
10 Relay with 2 Programmable Extra contacts, Fix CT. CSA – 150D Drawout 1/2
Ordering information :
A D R 1 4 1 A - A M - X X X - X X - X - X - X X - X
Example
ADR141A – AM-001-02-2-0-2-0
Type : ADR141A
B a c k T e r m i n a l L a y o u t : With 4 Programmable extra contact, Fix CT.
Cabinet Type : CSA-150 non Drawout
Auxiliary Supply : 77-250Vdc
C T s e c : 5 Amp.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
Technical Specifications:
Sr. No. Specification Particulars
I. For Model AM001xx
[ 3OC + 1EF relay ]
Inputs : Model Fix CT 1A or 5A specify wihile ordering
AM00101xxxxx ,
AM00102xxxxx ,
AM00104xxxxx ,
AM00107xxxxx ,
AM00109xxxxx &
AM00110xxxxx
: Model Suitable for CT secondary 1.0 Amp or 5.0 Amp.
AM00103xxxxx & (Selectable)
AM00108xxxxx
Protection Relay Setting : Setting For phase 50% - 200 %
Range For EF 5% - 80%
: Operating Time Normal Inverse 1 (C1)
Normal Inverse 2 (C2)
Very Inverse (C3)
Extremely Inverse (C4)
Long Time Inverse (C5)
Definite Tme (C6) 00(Inst) – 99.9Sec
: Inst. Setting For phase 100% - 3000%. or bypass
For EF 100% - 1200% or bypass
: Inst Operating Time 00(Inst) – 1.0Sec
Inst = < 50ms
Output contacts : Model 1) 2 NO Trip duty contact for Alarm and Trip
AM00101xxxxx
: Model 1) 2 NO Trip duty contact for Alarm and Trip
AM00102xxxxx 2) 4 programmable NO contacts for ALARM
: Model 2 NO Trip duty contact for Alarm and Trip
AM00103xxxxx ,
AM00107xxxxx &
AM00108xxxxx
: Model 2 NO Trip duty contact for Alarm, 1NO Alarm
AM00104xxxxx , Contact for Breaker Fail and 2 programmable NO
AM00105xxxxx , contacts for ALARM
AM00106xxxxx &
AM00109xxxxx.
: Model 1) 2 NO Trip duty contact for Alarm and Trip.
AM00110xxxxx 2) 2 NO Ann. Duty Programmable Contacts.
II. Pickup Current : Within 1.1 times of set current value.
III. Resetting Current : 90% of set value.
IV. Time Accuracy : Within class 2.5 As per IS: 3231.
V. Burden on CTs : Less than 0.2VA.
VI. Aux. Supply : 18 – 52VDC or 77 – 250VDC. To be specified while ordering.
VII. Burden on Aux. Supply : Less than 10VA on any supply.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
VIII. Contact Rating Trip Duty : Make and carry for 3sec. – 7500VA with max. 30A & 660VAC/DC
: Make and carry for continuous – 1250VA with max. 5A & 660VAC/DC
: Break AC – 1250 VA DC – 100 W resistive 50W inductive.
IX. Operational Indicators (Flags)
ON : Green LED indicates Relay OK
: In case of following condition led become off
1. Problem in relay Hardware.
2. Auxiliary supply is not sufficient for relay operation.
FAULT : Red LED’s indicates the OC/EF relay trip, Hand Reset (HR) Type.
PKP : Red LED indicates OC/EF relay Pickup.
TRIP : Indicates that Trip pulse is being executed. When BYPASS P.B. is
pressed, actual trip is not executed.
X. Thermal Withstand Capacity : x40 times the normal current for 3sec.
: x2 Continuous
XI. High Voltage Test : IEC 60255-5
: Except DC Voltage – 2.0 kV (RMS), 50Hz
: Only DC voltage - 2.8 kV DC
: Between Open contact of TRIP / CLOSE 1.5kV (RSM) 50Hz
: Between Open contact of ALARM – 1kV (RSM) 50Hz
XII. Impulse Voltage Test (all : IEC60255-5
circuit class – III) : 5kV (peak) 1.2 / 50us, 0.5 J, 3 positive and 3 negative impulse at interval
of 5 sec
XIII. High Frequency test : IEC 60255-22-1, Class III
: 2.5 kV (peak) 1MHz , τ = 15µs 400 surges / s duration 2 s
XIV. Electro static Discharge : IEC 60255-22-2 Class III and IEC 61000-4-2 class III
: 4kV/6kV contact discharge, 8kV air discharge, both polarities 150pF, Ri
330 Ω
XV. Irradiation with radio : IEC 60255-22-3 and IEC 61000-4-2 class III
frequency field, pulse- : 10V/m; 80 to 1000MHz; 80%; 1kHz AM
modulated,
XVI. Fast transient : IEC 60255-22-3 and IEC 61000-4-3, class III
interference/bursts : 4kV; 5/50ns; 5kHz burst duration = 15ms;
: Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.
XVII. Shock Test : IEC 60255-21-2 class 1
: Semi-Sinusoidal
: 5g acceleration, duration 11ms,
: Each 3 shocks in both direction of the 3 axes
XVIII. Vibration Test : IEC 60255-21-1 class 1 / IEC 60068-2-6
: Sinusoidal 10 to 60Hz ±0.035 mm
: Amplitude, 60 to 150Hz, 0.5g acceleration
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.
Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above.