FM200 CYLINDERS BATERRY ROOM:

RISK ANALYSIS AND PROTECTION CRITERIA


RISK: ELECTRICAL EQUIPMENT - FIRE CLASS C
TEMPERATURE: 20 ° C
ALTITUDE OF THE ENCLOSURE: 0 MSNM - CORRECTION FACTOR: 1

CARBON STEEL PIPE


PROTECTION CRITERIA: FULL FLOOD BY FM200
VOLUME TO PROTECT: ROOM VOLUMEN - EQUIPMENT VOLUME = 230 m³
AGENT CONCENTRATION; 8%

AGENT VOLUME:

W = (V / S) * ((C / (100-C))
where:
BATERRY ROOM V: FOURTH VOLUME
S: 0.1269 + 0.0005XT; WITH T IN ° C
W: AGENT VOLUME
C: FM 200 CONCENTRATION: 8%

CALCULATION RESULT
AGENT VOLUME = 40 KG WITHOUT HEIGHT CORRECTION
CYLINDERS WILL BE CHARGED WITH THE AMOUNT OF AGENT ACCORDING
TO SUPPLIER SPECIFICATIONS
0,20

AIR AIR
BATERRY ROOM CON CON
CON
AIR

NOT SCALE
1,50 DATA CENTER
Terrestrial

RECTIFIER BSC ROOM PDF LAN/WAN


CABINET BSC ROOM:
1 CABINET
TRM

RISK ANALYSIS AND PROTECTION CRITERIA


RISK: ELECTRICAL EQUIPMENT - FIRE CLASS C

DDF
NE 40 MS TEMPERATURE: 20 ° C
ROUTER ALTITUDE OF THE ENCLOSURE: 0 MSNM - CORRECTION FACTOR: 1
CABINET PROTECTION CRITERIA: FULL FLOOD BY FM200
BSC
VOLUME TO PROTECT: ROOM VOLUMEN - EQUIPMENT VOLUME = 230 m³
CARBON STEEL PIPE UMG CARBON STEEL PIPE AGENT CONCENTRATION; 8%
2,00 8900

CARBON STEEL PIPE


AGENT VOLUME:

UMG W = (V / S) * ((C / (100-C))


UPS 8900 where:
V: FOURTH VOLUME
S: 0.1269 + 0.0005XT; WITH T IN ° C
W: AGENT VOLUME
TRM C: FM 200 CONCENTRATION: 8%
VSAT
CALCULATION RESULT
1,50 AGENT VOLUME = 150 KG WITHOUT HEIGHT CORRECTION
CON

CYLINDERS WILL BE CHARGED WITH THE AMOUNT OF AGENT ACCORDING


AIR

C IR
TO SUPPLIER SPECIFICATIONS

O
A
N
The location of the equipment must be respected as much
as possible. If the installation technician considers that
FM200 CYLINDERS there are conditions that require the relocation of the
equipment, the respective engineer must consult the
respective designer.

OFFICE OFFICE

BSC ROOM
NOT SCALE

FIRE PROTECTION SYSTEM

BATA, EQUATORIAL GUINEA

LEGEND
FIRE EXTINGUISHING
FACP S H
NOZZLE AUTOMATIC ACTUATOR RISER
CA
CLEAN AGENT CYLINDER
FIRE ALARM CONTROL PANEL
P
PHOTOELECTRIC SMOKE DETECTOR
F
FIXED
DETECTOR
TEMPERATURE HEATER AUDIBLE APPLIANCE EMERGENCY LAMP
SYSTEM FM200
UPRIGHT SPRINKLER VALVE CLEAN AGENT EXTINGUISHER
FSCP FIRE SUPRESSION CONTROL PANEL S IONIC SMOKE DETECTOR CA STATION MANUAL CLEAN AGENT STROBOSCOPIC LAMP END OF LINE RESISTOR

XX FM200 I Units: m FPS-BATA-0


S SP RFSACU H CA
PENDENT SPRINKLER SOLENOID VALVE PIPE SUPPORT
CA
CLEAN AGENT CONTROL RELEASE
SERVICE
HEAT DETECTOR
DETECTION
THERMAL ABORT SWITCH CLEAN AGENT AUDIBLE ALARM
STROBOSCOPIC LAMP
WITH
NS EXTINCTION
LIGHTING LABEL
INDICATOR
10/03/2021 S:IND CUSTOMER REVIEW

You might also like