You are on page 1of 70

PROYECTO 

CENTRAL TERMICA RECKA     
DOCUMENTO: CTR‐01‐YTY‐DMO‐YKG‐00001 
CLIENTE: COBRA 
ORDEN: CTR‐COM‐OC‐CPI‐042 Rev. 0         
     
 

 
26-05-2015
 

MANUAL DE 
MANTENIMIENTO  
 

 
 

457-01-PI20300-0025-0001-A
PROYECTO CENTRAL TERMICA RECKA     
DOCUMENTO: CTR‐01‐YTY‐DMO‐YKG‐00001 
CLIENTE: COBRA 
ORDEN: CTR‐COM‐OC‐CPI‐042 Rev. 0         
     
 

FLUJOMETRO 
ELECTROMAGNETICO 
MODELO AXF 
TAG
01GAC30CF002-B01

 
 

 
 
5. MAINTENANCE

5. MAINTENANCE
WARNING

• Maintenance work must be carried out by the


trained personnel having knowledge of safety
standard and not by operators.
• When opening the cover, wait for more than 10
minutes after turning off the power. Further-
more, opening of the cover must also be
carried out by the trained personnel having
knowledge of safety standard.

CAUTION

• Explosion protected type must be, as a rule,


removed to a non-hazardous area for mainte- F0501.EPS

nance and be disassembled and reassembled (4) Using the hexagonal wrench, loosen the screw in
to the original state. the neck.
• The cover is locked by the special screw. In
(5) Turn the converter or the terminal box in the
case of opening the cover, use the hexagonal
desired direction.
wrench attached.
• Be sure to lock the cover by the special screw
using the hexagonal wrench attached after NOTE
installing the cover.
The converter and the terminal box can be
turned –140 degree to +180 degree from the
arrow mark indicating the flow direction. Do not
5.1 Changing Direction of exceed these angle.

Electrical Connection (6) Using the hexagonal wrench, retighten the neck
screw.

IMPORTANT

The following types can not be changed direction


of electrical connection after delivery.
• Submersible Type.
• Optional code DHC (for district heating and
cooling or condensation-proof).

(1) The following tools are required to change the


direction of the electrical connection:
• Hexagonal wrench (nominal size 1.5): Comes
with the instrument.
• Wrench
(2) Turn off the power to the flowmeter.
(3) Using the wrench, loosen the hexagonal nut at the
F0502.EPS
neck of the instrument.
(7) Using the wrench, retighten the hexagonal nut at
the neck. After that, check that the converter or
terminal box is fixed.

5-1 IM 01E20D01-01E
5. MAINTENANCE

5.2 Removing, Cleaning, (4) Using end A of the tool, open the electrode cover.

and Installing Re-


placeable Electrodes
(General-Purpose
End A
Use Type Only) End B

5.2.1 Removing Replaceable Elec-


trodes
(1) The following tools are required to replace the
electrodes:
• Special tool for removing and installing elec-
trodes (F9807SK): Optional
• Torque wrench or torque driver (nominal size 12)
• Phillips screwdriver F0504.EPS

(5) Hold down the electrode lead wire and terminal


lug and remove the mounting screw using the
Phillips screwdriver.

F9807SK
F0503.EPS

(2) Turn off the power to the flowmeter.


Electrode lead wire:
(3) Drain the fluid from the interior of the flowtube. Red: Electrode A
White: Electrode B

WARNING

• Never fail to drain the fluid from the interior of


the flowtube.
• If the fluid is at a high temperature, the instru- F0505.EPS

ment itself may also be hot. Be careful not to


get burned when removing the electrodes.
• When the process fluid is hazardous to hu-
mans, exercise caution to avoid coming into NOTE
contact with it, and avoid inhaling any residual
Always hold down the lead wire and terminal lug
gas.
when removing the mounting screw.

5-2 IM 01E20D01-01E
5. MAINTENANCE

(6) Move aside the electrode lead wire and avoiding 5.2.2 Cleaning Replaceable Elec-
the screw, insert end A of the tool to the electrode trodes
and loosen the electrode holder using the torque
(1) Clean the electrode surface (wetted part) with
driver.
alcohol or other cleaning agents.

O-ring

Electrode surface

Electrode holde

End A

Torque driver
F0506.EPS

(7) Screw end B of the tool into the screw block of the
electrode, and pull the tool straight out to remove
the electrode holder.
F0508.EPS

NOTE

The screw threads are coated with an anti-


seizing compound. Do not let the compound
come in contact with the electrode.

(2) Clean the surface of the lining seal with an alcohol


moistened swab.
End B
F0507.EPS

Lining seal surface


F0509.EPS

5-3 IM 01E20D01-01E
5. MAINTENANCE

5.2.3 Installing Replaceable Elec- (2) Using end A of the tool, tighten the electrode
trodes holder.

NOTE

It is recommended to replace the O-ring when


reinstalling the replaceable electrode. Use the O-
ring specified by Yokogawa (G9303SE: material
is fluororubber).

NOTE

Precautions for storage of O-rings:


• Keep them in a cool, dark place.
Torque driver F0511.EPS
• Wrap them well.
• Do not use O-rings after one year since their
purchase. NOTE

(1) Push the electrode holder with end B of the tool Using the torque wrench or torque driver, tighten
screwed into it, straight into the flowtube. the electrode holder to the following torque
values:
PFA lining:
8.0 N·m ±1 N·m (80 kgf·cm ±10 kgf·cm)
Polyurethane rubber lining:
3.0 N·m ±0.5 N·m (30 kgf·cm ±5 kgf·cm)
Electrode lead wire:
Red: Electrode A
White: Electrode B
WARNING

If the electrode holder was not tightened to its


specified torque value, fluid leakage from the
Electrode holder: electrode may result. Should fluid spill over the
(Electrode A is engraved with "A" electrode block, wipe it dry and check that the
and electrode B has no markings.)
O-ring has not come off.

F0510.EPS

(3) Fill the interior of the flowtube with the fluid and
check that there is no leakage from the electrode.
NOTE

• Check that the O-ring has not come off. (4) Hold down the lead wire and terminal lug and
• Do not interchange electrodes A and B when screw the mounting screw into the electrode using
installing them. Install electrode A to the the Phillips screwdriver.
electrode boss with the red lead wire and
electrode B to the one with the white lead wire.

Electrode mounting screw


F0512.EPS

5-4 IM 01E20D01-01E
5. MAINTENANCE

2) Installing the butt weld adapter


NOTE
Install a gasket to fit in the groove of the butt weld
Always hold down the lead wire and terminal lug adapter, and tighten in the adapter with the
when adjusting the mounting screw. mounting screws.

(5) Put the lead wire in the electrode boss, and install
the electrode cover to the boss and tighten it using
end A of the tool.

Mini-flange

Gasket

Butt weld adapter

Adapter
mounting screw

Electrode boss
F0316.EPS

Figure 5.3.1 Removing and Installing a Butt Weld


Adapter
Torque driver F0513.EPS

CAUTION
(6) Turn on the power to the flowmeter and start
normal operation. • In case of standard gasket (EPDM rubber),
tighten the adapter mounting screw according
to the torque values in Table 5.3.1.
• In case that optional code GH (Silicon rubber)
5.3 Removing and In- is selected, tighten the adapter mounting screw
according to the torque values in Table 5.3.2.
stalling Adapters for • Tighten the adapter mounting screw in diagonal
Sanitary Types order step by step.
• After tightening of screw, confirm that gaskets
protrude inside adapter. Protruding of gasket is
CAUTION
necessary to keep the sanitary requirements.

• This section describes how to remove and Table 5.3.1 Tightening Torque Values of adapter for
install a butt weld adapter as an example. EPDM rubber gasket
Apply the same procedure to clamp and union Tightening torque values (N-m / {kgf-cm} / [in-lbf])
adapters.
Gasket type EPDM rubber
• Turn off the power of the magnetic flowmeter, Size mm (inch) (standard)
and confirm that there is no fluid inside the pipe 15 (0.5), 25 (1.0), 32 (1.25), 40 (1.5) 3.0 to 3.5 / {30.59 to 35.69} / [26.55 to 30.98]
before removing the instrument from the pipe 50 (2.0), 65 (2.5) 4.5 to 5.0 / {45.89 to 50.99} / [39.83 to 44.25]
line. 80 (3.0) 8.0 to 9.0 / {81.58 to 91.78} / [70.81 to 79.65]
100 (4.0), 125 (5.0) 10 to 11 / {102.0 to 112.2} / [88.50 to 97.35]
• When installation, refer to Subsection 3.3.6. T0502.EPS

Table 5.3.2 Tightening Torque Values of adapter for


1) Removing the butt weld adapter silicon rubber gasket
Tightening torque values (N-m / {kgf-cm} / [in-lbf])
Remove the butt weld adapter by loosening the
Gasket type Silicon rubber
mounting screws. Size mm (inch) (optional code GH)
15 (0.5), 25 (1.0), 32 (1.25), 40 (1.5) 2.0 to 2.5 / {20.39 to 25.49} / [17.70 to 22.13]
50 (2.0), 65 (2.5), 80 (3.0) 4.0 to 4.5 / {40.79 to 45.89} / [35.40 to 39.83]
100 (4.0), 125 (5.0) 6.0 to 6.5 / {61.18 to 66.28} / [53.10 to 57.53]
T0503.EPS

5-5 IM 01E20D01-01E
5. MAINTENANCE

CAUTION

• The lining of sanitary type uses fluorocarbon


PFA. For the property of fluorocarbon PFA, it is
possible that the adapter mounting screws may
loosen as time passes, so retighten them
regularly.
• Be sure to retighten the adapter mounting
screws according to the prescribed torque
values in Table 5.3.1 or Table 5.3.2. Retighten
them diagonally with the same torque values,
step by step up to the prescribed torque value.
• In case of leakage from adapter connection
point, retighten the adapter mounting screws. If
leakage doesn’t stop even if they are retight-
ened, replace the gasket between mini-flange
of flowmeter and adapter.
• It is recommended to replace the gasket
periodically,
• It is necessary to decide the period between
changes with consideration for the frequency of
cleaning cycles, the cleaning temperature and
the fluid temperature.
• Use the gasket specified by Yokogawa in Table
5.3.3

Table 5.3.3 Parts number of gasket


Gasket
type Silicon rubber
EPDM rubber
(optional
(standard)
Size mm code GH)
(inch)
15 (0.5) F9811QA F9811QB
25 (1.0) B1002EG B1010EG
32 (1.25) B1003EG B1011EG
40 (1.5) B1004EG B1012EG
50 (2.0) B1005EG B1013EG
65 (2.5) B1006EG B1014EG
80 (3.0) B1007EG B1015EG
100 (4.0) B1008EG B1016EG
125 (5.0) F9811QC F9811QD
T0504.EPS

5-6 IM 01E20D01-01E
5. MAINTENANCE

5.4 Maintenance for


Converter (Integral
Flowmeter Only)
1 2

WARNING

• Maintenance work must be carried out by the Cover locking screws


trained personnel having knowledge of safety
standard and not by operators.
• When opening the cover, wait for more than 10
minutes after turning off the power. Further- F0516.EPS

more, opening of the cover must also be Figure 5.4.1 Removing the Display Cover
carried out by the trained personnel having
knowledge of safety standard.
(b) Changing the Display Unit Direction 90
Degrees
(1) Hold the display unit with your hand and remove
the two mounting screws.
IMPORTANT
(2) Turn the display unit 90 degrees clockwise and
• As a rule, maintenance of this flowmeter should confirm the assembling position, taking care of the
be implemented in a maintenance service shop connector and wire of the display unit.
where the necessary tools are provided. At this time, do not remove the connector.
• The amplifier assembly contains sensitive parts (3) Secure the display unit using its two mounting
that may be damaged by static electricity. screws.
Exercise care so as not to directly touch the
electronic parts or circuit patterns on the board,
for example, by preventing static electrification
by using grounded wrist straps when handing *1
the assembly.

5.4.1 Fuse Replacement

CAUTION Display unit


mounting
Please contact Yokogawa’s service office for fuse screws
replacement. Also be sure to use the fuse that (two screws)
was supplied by Yokogawa’s sales or service of-
fices.

5.4.2 Changing the Direction of the Clockwise 90 degrees F0518-1.EPS


Display Unit Figure 5.4.2 Changing the Display Unit Direction 90
Degrees
(a) Removing the Cover
(1) Turn off the power.
IMPORTANT
(2) Loosen cover locking screw 1 clockwise using a
hexagonal wrench (nominal size 3) to unlock the *1: To preserve the safety, do not touch the
cover. (Upon shipment from the manufacturing electrical circuit and cable of shaded area.
plant, the cover is locked.) Hold the flowmeter
with your hand and remove the cover by turning it
in the direction of the arrow as shown below.

5-7 IM 01E20D01-01E
5. MAINTENANCE

(c) Installing the Cover Modification of the burnout direction must be carried
(1) Taking care not to entangle the cables, install the out using the setting switch from the amplifier’s CPU
cover to the flowmeter by turning it in the direc- board (i.e., Switch 1) (See Figure 5.5.1).
tion of the arrow as shown below. Table 5.5.1 Output Setting Pins for Burnout
(2) Tighten cover locking screw 1 counterclockwise Position of Burnout Burnout
Remarks
using a hexagonal wrench (nominal size 3) to lock Pin Direction Output
the cover. Low High Set to High before
High 25 mA
shipment
Low High Set to Low for optional
Low 0 mA code C1
T0501.EPS

NOTE
1 2
• On the amplifier’s CPU board, the burnout
setting switch (i.e., Switch 1) and the write
Cover locking protect switch (i.e., Switch 2) are located
screws adjacent to each other. Accordingly, special
care should be taken when making switch
settings.
F0518-2.EPS • In the case of Fieldbus communication type,
Figure 5.4.3 Installing the Display Cover burnout setting switch is not applied.

Low High
5.5 Setting of Switches Switch 1 2 ← Burnout setting switch
Switch 2 1 ← Write protect setting switch
(Integral Flowmeter Enable Protect

Only)

IMPORTANT

• Removing and installing cover are necessary


for setting switches. Perform removing and
installing of the cover as described in Subsec-
tion 5.4.2.
• To preserve the safety, do not touch the
electrical circuit and the cables except setting
F0520.EPS
switches.
Figure 5.5.1 Switch Configuration

5.5.1 Setting of Burnout Switch 5.5.2 Setting of Write Protect Switch


The burnout function sets the direction of current By setting the write protect function to “Protect” it is
output in situations where the CPU has become possible to prevent the overwriting of parameters.
damaged. Upon shipment from the manufacturing Write protection can be carried out using either the
plant, the burnout direction is set to High (i.e., 25 mA); hardware switch on the CPU board (i.e., Switch 2) (See
however, in cases where the optional code C1 has been Figure 5.5.1) or software parameter settings. If either
specified, the output direction will be set to Low (i.e., of these items is set to “Protect,” the overwriting of
0 mA). parameters will be prohibited.

5-8 IM 01E20D01-01E
5. MAINTENANCE

(1) Excitation Coil Check (Remote Flowtube


NOTE Only)
• If the hardware switch is set to “Protect,” it will Check that there is continuity between terminals EX1
not be possible to overwrite parameters; and EX2 in the terminal box. If there is no continuity,
furthermore, this condition will be maintained the coils may be broken and replacement or repair of
until the switch is set to “Enable.” the flowtube is necessary. The coil resistance is
• In the case of Fieldbus communication type, designed to be 150  or less. If it is not, this may be
setting of the hardware switch (Enable or an abnormal condition. Consult Yokogawa’s sales or
Protect) is ineffective and write protection can service offices.
be carried out only by software parameter
settings. (2) Insulation Resistance Check (Remote
Flowtube Only)
Check the insulation resistances in the terminal box in
For more details regarding usage of the write protect
accordance with the tables below. If any of them falls
function and the software’s parameter switches, refer
below the values listed in the tables, consult
to “Parameter Description” in the user’s manual of
Yokogawa’s sales or service offices for investigation.
the AXF Integral Flowmeter [Software Edition]
If the insulation resistance cannot be restored, replace-
(IM 01E20C02-01E).
ment or repair of the flowtube is needed. In case of
submersible type flowmeters, undo the wiring connec-
5.6 Regular Inspection tion on the converter side and measure resistance at the
cable terminals.
Items
Coil Circuit
(1) Inspection of moisture-proofing inside the Checking is possible even if the pipe is filled with
terminal box: Once/year fluid.
(2) Retightening of piping joint screws: About
twice/year Test Terminals Test Voltage Specification
Between terminals 500 V DC (Use an insulation
1 M or more
(3) Inspection of electrodes and lining (in EX1 and C tester or the equivalent.)
T050601.EPS
case of adhesive and/or abrasive fluids,
etc.)
Signal Circuit
Determine the period of regular inspection as
necessary. Before testing, be sure to empty and dry the interior of
the pipe, checking that there is no adhesive material.
Also undo the wiring connection on the converter side
5.7 Excitation Coil and before testing.

Insulation Resis- Test Terminals Test Voltage Specification

tance Check (Remote Between terminals


A and C 500 V DC (Use an insulation
tester or the equivalent.)
100 M or
more for each
Between terminals
Flowtube Only) B and C
T050602.EPS

WARNING 5.8 Maintenance of the


• Before checking of the excitation coil and the LCD Display
insulation resistance, be sure that the power
supply for AXFA11 or the AXFA14 converter CAUTION
has been turned off.
• Before checking, be sure to disconnect the The LCD display has certain lifespan and it may
cables from the terminals of the remote deteriorate during operation. Please contact
flowtube. Yokogawa office in this case.

5-9 IM 01E20D01-01E
5. MAINTENANCE

5.9 Troubleshooting
Although magnetic flowmeters rarely require maintenance, failures may occur when the
instrument is not operated correctly. This section describes troubleshooting procedures
where the cause of the breakdown is identified through receiver indication.

5.9.1 No Indication

START

Is an error being displayed? Check the converter display.

Refer to the “Alarm Functions” in


Is an error being YES the AXFA11, AXFA14, and AXF
displayed? Integral Flowmeter [Software
Edition] user manuals.
NO

Is anything else NO
being displayed?

YES

Does the
NO
arrow on the tube match the
flow direction?

YES Perform either of the following:


a. Reinstall the flowtube in
order to make the arrow and
Check whether the flowtube flow direction match.
is filled with fluid. b. Reverse the setting for the
flow direction.

Is the flowtube NO
full of fluid?

YES Change the piping or the


mounting condition so that
Check the resistance between the tube fills with the fluid.
the flowtube’s A, B, and C
terminals using a circuit tester.*1 *1: Follow the warning in Section 5.7
before checking. The integral
flowmeter's resistance cannot be
checked.
Is the NO
resistance between A-C or B-C
100 M or more?

YES

Remove the tube and


inspect the inside of the pipe.

Is foreign NO
matter adhering to
the walls?
YES

Remove the foreign matter. Contact a service center.


F0521.EPS

5-10 IM 01E20D01-01E
5. MAINTENANCE

5.9.2 Unstable Zero

START

Investigate whether or not the flowtube


is filled with fluid and that it is free of
*1: When checking for bubbles, it is
bubbles.
convenient if there is a gas vent hole
on the flowtube’s downstream side.
*1
Particular care must be taken in the case
Is the flowtube NO of horizontal mounting. In order to ensure
completely full of fluid? complete filling of the tube, either adjust
the mounting position or switch to vertical
mounting.
YES

Are there bubbles YES


Install a defoaming device on the
in the fluid? flowtube’s upstream side.
NO

Check for the presence of valve


leakage.

YES
Are valves leaking? Replace the valve(s).

NO

• Confirm the flowmeter grounding.


• Confirm whether or not the
grounding wire is disconnected
from the earth flange.

NO Completely ground the converter and


Is the flowmeter properly flowtube (Refer to the section on
grounded? grounding in the relevant user's manual.)
YES

Recheck the fluid to be measured.

• Ensure that the fluid’s conductivity


changes as little as possible.
• Does the fluid’s • Do not use the meter when fluid
conductivity vary? YES
• Is the fluid conductivity conductivity is out of limits.
within the limits? • Whenever possible, reduce the flow
velocity to being in the vicinity of the
lower conductivity limit.
NO
• Remove dirt and scale of and near
electrodes.
Is the fluid likely to YES • Use a soft brush or cloth to perform
contain deposits? scale removal, and make sure that
the lining is not damaged.
NO

Is the flowmeter YES Provide the meter with sufficient


located near motors, transformers, shielding or move it away from the
or electric equipment?
electrical equipment
NO

Contact a service center.


F0522.EPS

5-11 IM 01E20D01-01E
5. MAINTENANCE

5.9.3 Disagreement Between Indication and Actual Flow

START

Are parameters NO
Set the parameters correctly.
set correctly?
YES

Examine the condition of the fluid in the


flowtube, of bubbles, and of grounding.

Was zero Execute zero adjustment when the


NO
adjustment carried out flowtube is filled completely with fluid and
correctly? when the fluid is not moving.
YES

• Change the mounting position or piping


Is the tube NO so that the flowtube is
filled completely with
fluid? completely filled with fluid.
• Switch to vertical mounting.
YES

Does the fluid YES Install a defoaming device on the


contain bubbles? flowtube’s upstream side.
NO

Is the NO
Completely ground the converter and
flowmeter completely flowtube (Refer to the section on
grounded? grounding in the relevant user's manual.)
YES

Fully terminate the signal cable using


Is the PVC tubing or insulation tape, thus
signal cable terminal NO
treatment of insuring that conductors, inner shields,
complete? and outer shields do not make contact
YES with each other or with the case.

Does the NO
conductivity stay within the Use within the specified conductivity range.
specified range?

YES • Remove scales. Especially clean the


electrodes and their vicinity.
Is the
fluid likely to contain
YES • Use a soft brush or cloth to perform
deposits? scale removal, and make sure that the
lining is not damaged.
NO
Confirm that a valve is located
immediately upstream of the flowtube • If any valve located immediately
(i.e., on the upstream side).
upstream of the flowtube is used in a
half-open condition, the indication may
Is a valve be affected by turbulence in the flow.
YES
located immediately upstream • Relocate the valve to the downstream
of the flowtube? side.
• If the valve must be located on the
NO
upstream side, ensure that the minimum
Remove the flowtube and examine the distance to the flowmeter is 10 times
insulation resistance. the flow-tube diameter; alternatively,
use the valve fully open.

Signal terminals A-C and B-C: NO Dry the tube fully to restore insulation
100 M or more? resistance.
Excitation terminals EX1-C:
1 M or more?*1

YES *1: Refer to Section 5.7 for how to check


the resistance of the remote type
flowtube. The integral flowmeter's
Examine the operation of the converter
resistance cannot be checked.
using an AM012 calibrator in order to
determine whether the fault lies in the
converter or in the flowtube.

Contact a service center.


F0523.EPS

5-12 IM 01E20D01-01E
PROYECTO CENTRAL TERMICA RECKA     
DOCUMENTO: CTR‐01‐YTY‐DMO‐YKG‐00001 
CLIENTE: COBRA 
ORDEN: CTR‐COM‐OC‐CPI‐042 Rev. 0         
     
 

MEDIDOR MASICO TIPO 
CORIOLIS MODELO 
RCCT39/XR 
TAG
01EGA30CF001-B01

 
 

 
 
8. Self-diagnostic and Troubleshooting

8. Self-diagnostic and Trouble-


shooting
8.1 Error descriptions and countermeasure
The self check function displays instrument errors, warnings and alarms.
When an alarm or error occurs, the code (e.g. E-01) and the name (e.g. Frequency fault) appear on the
display during display mode, alternating with measuring value indication. This does not happen in parameter
setting mode.
The alarms, errors and warnings are written into history, see chapter 9.2.
The following table shows the possible alarms, warnings and error with the concerning influences on outputs
and fields variables.
Alarm (A); Flow on Dis- Density/Temp. Totalizer on Analog Frequ./Pulse-
Status outputs *)
Warning play on Display Display outputs outputs
Name
(W)
nc = no change, nd = not defined
Error (E)
A-01 MF 1 criteria nc nc nc nc 6)
Mass flow alm 1 *)
A-02 MF 2 criteria nc nc nc nc 6)
Mass flow alm 2 *)
A-03 VF 1 criteria nc nc nc nc 6)
Vol flow alm 1 *)
A-04 VF 2 criteria nc nc nc nc 6)
Vol flow alm 2 *)
A-05 Dens. 1 criteria nc nc nc nc 6)
Density alm 1 *)
A-06 Dens. 2 criteria nc nc nc nc 6)
Density alm 2 *)
A-07 Temp. 1 criteria nc nc nc nc 6)
Temp alm 1 *)
A-08 Temp. 2 criteria nc nc nc nc 6)
Temp alm 2 *)
A-09 Conc. 1 criteria nc nc nc nc 6)
Conc meas alm 1*)
A-10 Conc. 2 criteria nc nc nc nc 6)
Conc meas alm 2*)
A-11 Netflow 1 crit. nc nc nc nc 6)
Net flow alm 1 *)
A-12 Netflow 2 crit. nc nc nc nc 6)
Net flow alm 2 *)
A-13 Total thr exceed nc nc hold;continue 1) nc 6)
Total switch *)
MFL: meas.; DEN: meas.;
A-14 Slug detection nc nc 6)
Slug alarm *)
hold 4) hold 4)
MFL: meas.;
A-15 Empty pipe det. nc nc nc 6)
Empty pipe alm *)
hold 2)
A-16 Corrosion det. nc nc nc nc 6)
Corrosion alm *)
W-01 Density low nc DEN: 0 kg/l 5) nc nc nc nc
W-02 Fixed dens act. nc DEN: fix value nc nc nc nc
W-03 Fixed temp act. nc TEMP: fix value nc nc nc nc
MFL: fix
W-04 Fixed MF active value nc nc nc nc nc
+ act. zero
W-05 Autozero running nc nc nc nc nc nc
W-06 AZ val error nc nc nc nc nc nc
W-07 AZ fluct error nc nc nc nc nc nc
W-08 Sensor simul. nc nc nc nc nc nc
W-09 Fixed Prim Out nc nc nc 4mA nc nc
W-10 Prim Out sat. nc nc nc nc nc nc
W-11 Sec Out sat. nc nc nc nc nc nc
W-12 Tert Out sat. nc nc nc nc nc nc
W-13 Quart Out sat. nc nc nc nc nc nc
Dens = nd
E-01 Frequency fault nd hold 3,6mA;… 3) 6) 7)
Temp = nc
E-02 Signal fault nd nc hold 3,6mA;… 3) 6) 7)

E-03 EEPROM fault nd nd hold 3,6mA;… 3) 6) 7)

E-04 CPU fault nd nd nd 3,6mA… 8) nd nd


E-05 DSP fault nd nd hold 3,6mA… 8) 6) 7)

Dens = nd
E-06 Sensor 1 fault nd hold 3,6mA;… 3) 6) 7)
Temp = nc
E-07 Sensor 2 fault nd nc hold 3,6mA;… 3) 6) 7)

Density = nd
E-08 Temp sens fault nc hold 3,6mA;… 3) 6) 7)
Temp = 30°C
1)
Choice of “Total at alarm” (Detailed Setup / Totalizer)
2)
Choice of “Output after Empty pipe” (Detailed Setup / Empty pipe detect)
3)
Choice of “Analog 1/2 alarm out” (Detailed Setup / Config Output) and NAMUR/NOT NAMUR (Measuring range)
4)
Choice of “After Slug” (Detailed Setup / Slug detection)
5)
Only if “Liquid” is selected (Detailed Setup / Liquid/gas selection)
6)
Choice of “Pulse 1 at alarm” or “Pulse 2 at alarm” (Detailed Setup / Pulse/Status out 1/2)
7)
Status outputs active if “All Errors” or “All Alarms & Errors” is selected (Detailed Setup / Pulse/Status out 1/2)
8)
Choice of jumper “Burn-out” (See chapter 8.7.9 Setting “Burn-out” Mode)
*) Status outputs acc. SO 1/2 function and SO 1/2 active mode

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-1 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

The following table shows possible countermeasures :


Alarm (A);
Warning
Name Meaning Description Countermeasure
(W)
Error (E)
A-01 MF 1 criteria Mass flow L Alarm Mass flow below MF 1 criteria Increase mass flow / Change setting
A-02 MF 2 criteria Mass flow H Alarm Mass flow above MF 2 criteria Reduce mass flow / Change setting
A-03 VF 1 criteria Volume flow L Alarm Volume flow below VF 1 criteria Increase volume flow / Change setting
A-04 VF 2 criteria Volume flow H Alarm Volume flow above VF 2 criteria Reduce volume flow / Change setting
A-05 Dens. 1 criteria Density L Alarm Density below Dens. 1 criteria Increase density / Change setting
A-06 Dens. 2 criteria Density H Alarm Density above Dens. 2 criteria Reduce density / Change setting
A-07 Temp. 1 criteria Temperature L Alarm Temperature below Temp. 1 criteria Increase temperature / Change setting
A-08 Temp. 2 criteria Temperature H Alarm Temperature above Temp. 2 criteria Reduce temperature / Change setting
A-09 Conc. 1 criteria Concentration L Alarm Concentration below Conc. 1 criteria Increase concentration / Change setting
A-10 Conc. 2 criteria Concentration H Alarm Concentration above Conc. 2 criteria Reduce concentration / Change setting
A-11 Netflow 1 crit. Net flow L Alarm Net flow below Net flow 1 crit. Increase net flow / Change setting
A-12 Netflow 2 crit. Net flow H Alarm Net flow above Net flow 2 crit. Reduce net flow / Change setting
Totalizer value exceeds total
A-13 Total thr exceed Total threshold exceed Reset totalizer / Change setting
threshold
A-14 Slug detection Slug flow detected Slug criterion is reached Reduce gas bubbles in medium
Empty pipe
A-15 Empty pipe detectd Empty pipe criterion is reached Fill pipe
det.
A-16 Corrosion det. Corrosion detected Corrosion criterion is reached Change detector
W-01 Density low Density lower 0.3 kg/l Density lower than 0.3 kg/l Fill the detector with fluid
Set parameter Dens fix val sel to
W-02 Fixed dens act. Fixed Dens selected Parameter Dens fix val sel is enabled
inhibit
Set parameter Temp fix val sel to
W-03 Fixed temp act. Fixed Temp selected Parameter Temp fix val sel is enabled
inhibit
W-04 Fixed MF active Fixed MF selected Parameter MF fix val sel is enabled Set parameter MF fix val sel to inhibit
Autozero process is performed, Wait until process stops
W-05 Autozero running Autozero is running …
started by user action or status input (30sec or 180sec max)
Autozero value out of Auto zero value is out of the internal Stop flow during auto zero.
W-06 AZ val error
range detector depending range Check detector installation
Stop flow during auto zero. Check
Autozero fluctuation out Auto zero fluctuation is out of the
W-07 AZ fluct error electrical installation, vibrations and
of range internal detector depending range
density.
Fixed frequency or fixed phase dif-
W-08 Sensor simul. Sensor simulation active Set Sensor simulation to inhibit
ference is enabled
Analog output 1 fixed at 4mA for Set HART polling address to 0
W-09 Fixed Prim Out Analog output 1 fixed
multidrop operation (Multidrop operation stops)
Analog output 1 reaches less than Increase or decrease current level of
W-10 Prim Out sat. Analog output 1 saturated
3.8mA or more than 20.5mA output 1
Analog output 2 reaches less than Increase or decrease current level of
W-11 Sec Out sat. Analog output 2 saturated
3.8mA or more than 20.5mA output 2
Relation between pulse width and Decrease length of pulse width or
Pulse/Status output 1
W-12 Tert Out sat. pulse rate of Pulse/Status output 1 increase amount of pulse rate of pulse
saturated
is too high output 1
Relation between pulse width and Decrease length of pulse width or
Pulse/Status output 2
W-13 Quart Out sat. pulse rate of Pulse/Status output 2 increase amount of pulse rate of pulse
saturated
is too high output 2
E-01 Frequency fault Frequency fault detected Driving frequency out of range Check cable (Remote) and detector
E-02 Signal fault Signal fault detected Phase difference out of range Check cable (Remote) and detector
E-03 EEPROM fault EEPROM fault detected CRC-Error Contact Yokogawa service
E-04 CPU fault CPU fault detected Micro processor is not working Contact Yokogawa service
E-05 DSP fault DSP fault detected Micro processor is not working Contact Yokogawa service
Sensor 1 Signal fault
E-06 Sensor 1 fault Sensor 1 signal below 7% for 3 min Check cable (Remote) and detector
detected
Sensor 2 Signal fault
E-07 Sensor 2 fault Sensor 2 signal below 7% for 3 min Check cable (Remote) and detector
detected
Temperature Sensor Check cable (Remote) and detector
E-08 Temp sens fault T<-220°C or T>550°C
Fault detected Check temperature

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-2 All Rights Reserved. Copyright © 2003, Rota Yokogawa
8. Self-diagnostic and Troubleshooting

8.2 Reading Event + Error History (Diag/Service, Self


test/Status)
Event Overview/ Reads the actual errors, alarms and warnings (EAW). In Event
Error Overview the number of the actual EAWs is shown. In Error, Alarm
Alarm or Warning the description of the actual events can be found.
Warning
Hist Overview in Order Shows the latest 10 EAWs. By comparing this with Hist Overview
abs it can be checked if certain EAWs have vanished.
Hist Overview in Order/ Select: Execute, Non execute
Clear History
If Execute is selected the latest 10 EAWs are cleared.
Hist Overview abs/ In Hist Overview abs the number of EAWs after the last clearance
Error can be viewed. In Error, Alarm or Warning the description of the
Alarm events after the last clearance can be found.
Warning
Hist Overview abs/ Select: Execute, Not Execute
Clear History
If Execute is selected the user is asked to fill in a date (mm/dd/yyyy).
If a date is set the errors and warnings are stored in the Error history
with this date.
Error History In Error History the number of EAWs of the last clearance of the
Hist Overview abs can be viewed. In Error or Warning the
description of the events can be found. The last 10 entries can be
selected by date.

8.3 Self test (Diag/Service)


Self test/ Status Select: Self test, Status
If Self test is selected, all error and alarm status are checked.
If Status is selected, the existing errors and alarms are indicated in
succession.

8.4 Signal- and I/O-Test (Diag/Service)


Input/Output test These functions enable you to simulate the I/O signals (loop test).
The outputs can be checked with a multimeter.
Refer to the connecting diagrams in chapter 4.8.6. The test can be
cancelled by pressing any key.
Analog output 1 Setting range: 2 to 22 mA
Analog output 2 Setting range: 2 to 22 mA
Pulse output 1 Setting range: 0 to 10000 Hz
Status output 1 Setting range: On Active or Off Active
Pulse output 2 Setting range: 0 to 2000 Hz
Status output 2 Setting range: On Active or Off Active
Status input Indication range: Open or Short

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-3 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

8.5 Output trim


Output trim With this function the 4 mA and the 20 mA can be adjusted if
required
AO 1 trim 4mA / AO 1 trim 20mA The analog output 1 is set to the 4 mA or 20 mA. Connect a load
resistor between 20 and 600 W and measure the output current.
This current value must be entered on request on display.
The deviation to 4 mA is corrected by the converter itself.

AO 2 trim 4mA / AO 2 trim 20mA The analog output 2 is set to the internal 4 mA or 20 mA value.
Connect a load resistor between 20 and 600 W and measure the
output current.
This current value must be entered on request on display.

8.6 Detector cleaning


CAUTION
For integral type : Ambient temperature may not exceed 55°C !

The equipment can be CIP-cleaned. Steam below 230°C is not a problem. However, you should take care
that the cleaning operation does not last so long that the converter temperature exceed 55°C.
Switch power off during cleaning.

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-4 All Rights Reserved. Copyright © 2003, Rota Yokogawa
8. Self-diagnostic and Troubleshooting

8.7 Troubleshooting
IMPORTANT
If the indicated countermeasures do not remedy the fault or in case of troubles which can not be
remedied by the user, please contact your Yokogawa service centre.

If there is an error, alarm or warning displayed, deal with the error according to 8.1 „Error descriptions and
countermeasure”.
In the following some problems are listed which may not be indicated as error, alarm or warning. First make
sure, that no error, alarm or warning is displayed.

8.7.1 No indication

Is the power supply no Check the power supply


voltage between terminals connections.
L/+ and N/- correct ?

yes

yes
Is display cable connected no Connect the cable in the
correct to CPU board ? correct position.

yes

yes
Contact the nearest
YOKOGAWA office or
service center.
F81.EPS

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-5 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

8.7.2 No key-setting possible

Is parameter Key Status no Set parameter Key


set enable ? Status enable .

yes

Is display cable connected no Connect the cable in the


correct to CPU board ? correct position.

yes

Contact the nearest


YOKOGAWA office or
service center.
F82.EPS

8.7.3 No HART communication

Is HART DD of Rotamass no Store necessary DD in


RCCT3 available in HART HART communicator.
communicator ?

yes

Is HART communicator no Connect HART


connected to Rotamass communicator according
according chapter 4.8.7 ? chapter 4.8.7.

yes

Contact the nearest


YOKOGAWA office or
service center.
F83.EPS

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-6 All Rights Reserved. Copyright © 2003, Rota Yokogawa
8. Self-diagnostic and Troubleshooting

8.7.4 Unstable zero

Is the tube filled with liquid no Fill the detector. May be


completely (check the vertical installation is
density)? indicated.

yes

Are bubbles in the liquid ? yes Check piping and


installation.

no

Is electrical grounding no Make correct grounding.


correct according chapter
4.8.4; 4.8.5; 9 ?

yes

Shield the flowmeter


Is the flowmeter located sufficiently.
near motors, transformers yes
Locate the flowmeter as
or other electric far as possible from
equipments ? these equipments.

no
Loose the process
connections and make
Is the detector installed no sure that they are in line.
free of mechanical stress? Support only one
adjacent pipe, let one
side of the adjacent pipe
be “soft”.
yes

Clean and dry the


Is the connection box free no
connection box. Make
of dirt and humidity? (only
sure that humidity
for remote installation)
cannot penetrate.

yes

Contact the nearest


YOKOGAWA office or
service center. F84.EPS

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-7 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

8.7.5 Disagreement of indication with actual flow rate

Is zero point set correctly? no Run autozero according


chapter 5.6.

yes

Are mass flow unit, URV, no Set correct mass flow


LRV and lowcut set parameters.
correctly ?

yes

Is electrical grounding no Make correct grounding.


correct according chapter
4.8.4; 4.8.5; 9 ?

yes

Is gas penetration in the yes Control the piping. Is


fluid (chek the density)? there a location where
air can be sucked in?

no

For Remote type: Is no Connect remote cable


remote cable connected according chapter 9
according chapter 9 and and 4.8.1.
4.8.1 ?

yes

Is the control Check the control


no
measurement correct and measurement.
reliable?

yes

Contact the nearest


YOKOGAWA office or
service center. F85.EPS

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-8 All Rights Reserved. Copyright © 2003, Rota Yokogawa
8. Self-diagnostic and Troubleshooting

8.7.6 Disagreement of indication with actual density

Are density unit, URV, no Set correct density


LRV and lowcut set parameters.
correctly ?

yes

Is fixed density selected yes Set Density fix val sel =


(Density fix val sel = Inhibit.
Enable) ?

no

Is the tube filled with liquid Change piping . Vertical


completely and without no installation is
bubbles (density low recommended.
reading)? Check installation.

yes

For Remote type: Is Connect remote cable


no
remote cable connected according chapter 9
according chapter 9 and and 4.8.4.
4.8.4 ?

yes

Is temperature no Make troubleshooting


measurement correct ? according chapter 8.7.7.

yes

Has corrosion or errosion Let YOKOGAWA perform


occured (too high yes a new density and mass
density reading)? flow calibration.

no

Is there sediment or yes Clean the tubes by means


clogging in the tubes ? like water, steam or other
solvent.

no

Contact the nearest


YOKOGAWA office or
service center. F86.EPS

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-9 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

8.7.7 Disagreement of indication with actual temperature


Are temperature unit, no Set correct temperature
URV, LRV and lowcut set parameters.
correctly ?

yes

Is fixed temperature no Set Temp fix val sel =


selected (Tempy fix val sel Inhibit.
= Enable) ?

yes

For Remote type: Is Connect remote cable


remote cable connected no according chapter 9
according chapter 9 and and 4.8.4
4.8.4 ?

yes

Compact type: disconnect first the converter housing


Disconnect the temperature sensor cables 7,8,9 from TP1, TP2, TP3 in
detector RCCS3x terminal box.
Measure the resistances of detector temperature sensor terminals TP1,
TP2, TP3.
Resistance between TP1 + TP2 : 50 …200 depending on medium
temperature
Resistance between TP1 + TP3 : 50 …200 depending on medium
temperature
Resistance between TP2 + TP3 : <10

yes
PT 100 fault.
Resistance values are as no Simulate the correct
stored ? temp. by a fixed temp,
value or connect an
external PT100.

yes

For remote type: Check Replace remote cable.


remote cable lines 7, 8, 9. no
Cable OK ?

yes
F87.EPS

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-10 All Rights Reserved. Copyright © 2003, Rota Yokogawa
8. Self-diagnostic and Troubleshooting

Check the electronics:


Connect Pt100 simulator to terminals TP1, TP2, TP3 in converter
RCCF31 terminal box.
TP1 : + power, + sensor
TP2 : - sensor
TP3 : - power

no
Measured temperature Converter fault.
values OK ? Contact the nearest
YOKOGAWA office or
service center.
yes

Check your reference


temperature.
F88.EPS

8.7.8 Discrepancy of output signals to the assigned measurand

Is the setting of the no Make correct parameter


doubtful output signal setting.
correct ?

yes

Check output according no Contact the nearest


chapter 8.4. YOKOGAWA office or
Output OK ? service center

yes

Check measurand.
F89.EPS

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-11 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

8.7.9 Setting "Burn-out" mode


The flowmeter is equipped with a CPU error burn-out function used to set the analog output direction upon
CPU error. When factory-shipment the output of CPU error burn-out is set to HIGH. The setting of the
direction of analog output from burn-out can be changed.
To change the direction of output arising from burn-out, switch the jumper J2 on the CPU Board (see figure
below).

Low : I ≤ 3.6mA

High : I ≥ 21.6mA
CPU Board
JP2 (Burn out)

Cable to display
F810.EPS

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-12 All Rights Reserved. Copyright © 2003, Rota Yokogawa
8. Self-diagnostic and Troubleshooting

8.8 Detection of metering tube failure


The ROTAMASS RCCx34 ... 39/XR was tested and FM- approved according to ANSI/ISA – 12.27.01 – 2003
for Canadian Dual Seal Approval. For units with option /DS this is stated on the name plate.

NOTE
If Rotamass flowmeter is not used in Canada this functionality can also be used without Dual Seal approval.

The primary seal (metering tube) and the secondary seal withstand the maximum test pressures forced for
the maximum flange pressure of 12.41 MPas / 1800 psi (Flange A4, ASME 900). However the enclosure do
not withstand this pressure. For details see GS 01R04B04-00E-E.

When the metering tube fails, the detector enclosure is filled with process medium and the density reading
of ROTAMASS increases rapidly. This can be used for detecting a primary seal failure by the following an-
nunciation methods:

A) Via too high density reading, preferable with liquid application


- Set “Basic setup / Density / Density URV about 0.3 kg/l above the highest possible process density.
- Set an output (current or frequency) to density transmission.
- If the URV is reached (e.g. 20 mA ) the primary seal failed.
- Set Status output to Density alm 1 and status output will be active in case of tube failure.

B) Via Status output and “Empty pipe detection”


Only for liquid (only possible with software version 1.7 or higher):
- Check parameter "Basic Setup / Density / Density URV" (Default value is 1.5 kg/l).
URV should be about 0.3 kg/l higher than any density the process can provide.
- Set parameter "Detailed Setup / Empty pipe detect / Empty pipe alm sel / Apply".
- Set parameter "Detailed Setup / Empty pipe detect / Empty pipe crit / ..." to a value
which is a little bit higher than Density URV.
- For detection with e.g. status output 1:
Set "Detailed Setup / Config Output/Input / Pulse/Status out 1 / Pulse/Stat 1 select / Status out".
Set "Detailed Setup / Config Output/Input / Pulse/Status out 1 / SO1 function / Empty alarm"
- When the metering tube fails, the detector housing is filled with the process medium and the density
increases. Alarm A15 "Empty pipe detection" appears, display is blinking and the status output is set
active.

C) Via rupture disk (option /RD), preferable with gas application


- When the metering tube fails, the installed rupture disk bursts at about 20 bar (290 psi).
- For gas application the result will be a whistle by the gas blowing out.
- Rupture disk is only for annunciation.�

WARNING
If rupture disk bursts, the hazardous process medium is pressed out of the detector housing to the
environment. Take care that no worker gets contact to the medium.

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-13 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

8.9 Customer Maintenance Part List


Converter RCCF31 (RCCT3)

14a

Detector RCCS30 ... 33

Detector
13

14a

Option /PD

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-14 All Rights Reserved. Copyright © 2003, Rota Yokogawa
8. Self-diagnostic and Troubleshooting

Detector RCCS34 ... 39/XR

Detector

All Rights Reserved. Copyright © 2003, Rota Yokogawa 8-15 IM 01R04B04-00E-E 8th edition March 01, 2011 -00
8. Self-diagnostic and Troubleshooting

RCCS34..39/XR
RCCT34..39/XR

RCCS30..33
Item Part-No. Descriptions

RCCF31
1a M3808PA-SP Complete CF-M20 Converter Housing x
M3808PC-SP Complete CF-M20 Converter Housing Epoxy x
M3808PE-SP Complete CF-NPT Converter Housing x
M3808PG-SP Complete CF-NPT Converter Housing Epoxy x
1b M3808NL-SP Complete CT-M20 Converter Housing x
M3808NN-SP Complete CT-M20 Converter Housing Epoxy x
M3808NQ-SP Complete CT-NPT Converter Housing x
M3808NS-SP Complete CT-NPT Converter Housing Epoxy x
2 M3810DD-SP CF/CT Base Board Set Std x x
M3810DE-SP CF/CT Base Board Set /FB Std x x
3 M3810DF-SP CF/CT Cap Assy Std (/HP) x x
4 M3810DS-SP CF/CT Amplifier AC Std x x
M3810DT-SP CF/CT Amplifier AC Std /NM x x
M3810DW-SP CF/CT Amplifier AC Std /XR x x
M3810DX-SP CF/CT Amplifier AC Std /XR /NM x x
M3810DY-SP CF/CT Amplifier DC Std x x
M3810DZ-SP CF/CT Amplifier DC Std /NM x x
M3810EA-SP CF/CT Amplifier DC Std /XR x x
M3810EB-SP CF/CT Amplifier DC Std /XR /NM x x
M3810EC-SP CF/CT_FB Amplifier AC Std x x
M3810ED-SP CF/CT_FB Amplifier AC Std /XR x x
M3810EE-SP CF/CT_FB Amplifier DC Std x x
M3810EF-SP CF/CT_FB Amplifier DC Std /XR x x
5 M3808TC-SP CF/CT Display Set x x
M3808TD-SP CF/CT Display Set /FB x x
6 M3810DJ-SP CF/CT Cover with Window PU (not Ex) x x
M3810DK-SP CF/CT Cover with Window Epoxy (not Ex) x x
7 M3810DL-SP CF/CT Short Cover PU x x
M3810DM-SP CF/CT Short Cover Epoxy x x
8 M3810DN-SP CF/CT Small Cover PU x
M3810DP-SP CF/CT Small Cover Epoxy x
9* M3808TB-SP CF/CT/CS Complete O-Ring Set Conv./Sens. x x x x
9a M3809EF-SP 10pcs O-Ring Set 109,4x3,1 NBR70 N7S33-59 x x
9b M3809EG-SP 10pcs O-Ring Set 89,4x3,3 NBR70 N7S33-59 x
9c M3809EH-SP 10pcs O-Ring Set 84x3 NBR70 N7S33-59 x x x x
9d M3809EJ-SP 10pcs O-Ring Set 81x4 NBR70 N7S33-59 x x
10 M3810EH-SP Cable Gland M20x1,5 Black x x
M3810EK-SP Cable Gland M20x1,5 Nickel-plated Brass x x
M3810FB-SP Cable Gland M20x1,5 Stainless Steel x x
M3810EJ-SP Cable Gland NPT1/2-14 Nickel-plated Brass x x
M3810FC-SP CS Cable Gland SetNPT Nickel-plated Brass x x
M3810FD-SP CS Cable Gland-Set NPT Stainless Steel x x
M3810EM-SP Adapter NPT½-14 => G1/2 x x
11 M3808SZ_SP CS Connection Housing- 316L Set x x
12 M3808TA-SP CS Connection Housing Cover- 316L Set x x
13 M3806JA-SP 2“ Pipe Mounting Set (Option /PD) x
14a M3810DR-SP CF Mounting Bracket+Bracket Mounting Set x
14b M3808TE-SP CF Bracket Mounting Set x
M3810EP-SP CT Wiring Loom x
M3806ZZ-SP CF/CT Connection Part-Set x x
M3810DQ-SP CY Cable Termination Set

IM 01R04B04-00E-E 8th edition March 01, 2011 -00 8-16 All Rights Reserved. Copyright © 2003, Rota Yokogawa
PROYECTO CENTRAL TERMICA RECKA     
DOCUMENTO: CTR‐01‐YTY‐DMO‐YKG‐00001 
CLIENTE: COBRA 
ORDEN: CTR‐COM‐OC‐CPI‐042 Rev. 0         
     
 

TRANSMISOR DE PRESION 
MODELO EJA530E 
TAG
01GAC10CP003-B01
01GHA35CP001-B01
01GHC30CP001-B01
01GHC30CP002-B01
01QFB10CP001-B01
01SCB10CP001-B01

 
 

 
 
<8. Maintenance> 8-1

8. Maintenance
8.1 Overview 8.3 Calibration
Use the procedure below to check instrument
WARNING operation and accuracy during periodic
maintenance or troubleshooting.
Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate care 1) Connect the instruments as shown in figure 8.1
to avoid contact with the body or inhalation of and warm up the instruments for at least ten
vapors when draining condensate or venting gas minutes.
from the transmitter pressure-detector section
and even after dismounting the instrument from IMPORTANT
the process line for maintenance.
• To adjust the transmitter for highest
accuracy, make adjustments with the
Maintenance of the transmitter is easy due to its power supply voltage and load resistance
modular construction. This chapter describes the including leadwire resistances set close to
procedures for calibration, adjustment, and the the conditions under which the transmitter is
disassembly and reassembly procedures required installed.
for component replacement. • If the measurement range 0% point is
Transmitters are precision instruments. Please 0 kPa or shifted in the positive direction
carefully and thoroughly read the following sections (suppressed zero), the reference pressure
for information on how to properly handle them should be applied as shown in the figure.
while performing maintenance. If the measurement range 0% point is shifted
in the negative direction (elevated zero), the
IMPORTANT reference pressure should be applied using
a vacuum pump.
• As a rule, maintenance of this transmitter
should be done in a shop that has all the 2) Apply reference pressures of 0%, 50%,
necessary tools. and 100% of the measurement range to the
• The CPU assembly contains sensitive parts transmitter. Calculate the errors (differences
that can be damaged by static electricity. between digital voltmeter readings and
Take precautions such as using a grounded reference pressures) as the pressure is
wrist strap when handling electronic parts or increased from 0% to 100% and is decreased
touching the board circuit patterns. Also be from 100% to 0%, and confirm that the errors
sure to place the removed CPU assembly are within the required accuracy.
into a bag with an antistatic coating.

8.2 Calibration Instruments


Selection
Table 8.1 lists the instruments that can be used
to calibrate a transmitter. When selecting an
instrument, consider the required accuracy level.
Exercise care when handling these instruments to
ensure they maintain the specified accuracy.

IM 01C25F01-01E
<8. Maintenance> 8-2
Table 8.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital Model MT220 precision digital manometer Select a manometer having
manometer 1) For 10 kPa class a pressure range close to
Accuracy: ±(0.015% of rdg + 0.015% of F.S.) . . . . for 0 to 10 kPa that of the transmitter.
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Pressure Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa Requires air pressure
generator {2500 mmH2O} supply.
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to that
of the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump
source Pressure range: 0 to 133 kPa {1000 mmHg} for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% or higher level, use proper
instruments for required level or contact Yokogawa representatives from which the instrument was purchased or the nearest
Yokogawa office.

If a pressure generator If a pressure source and


is used: a manometer are combined:

Load resistance, Power Load resistance, Power


250Ω supply 250Ω supply
E E
Load Rc R Load Rc R
adjustment adjustment
resistance, V resistance, V
100Ω Digital voltmeter 100Ω Digital voltmeter
Reference pressure Reference pressure
P Model 7674 pneumatic P
pressure standards Model MT220
precision digital manometer

Supply pressure Pressure source


F0801.ai

Figure 8.1 Instrument Connections (4 to 20 mA output)

IM 01C25F01-01E
<8. Maintenance> 8-3
8.4 Disassembly and 8.4.1 Replacing the Integral Indicator
Reassembly
CAUTION
This section describes procedures for disassembly
and reassembly for maintenance and component Cautions for Flameproof Type Transmitters
replacement. Users are prohibited by law from modifying the
Always turn OFF power and shut off and release construction of a flameproof type transmitter.
pressures before disassembly. Use proper tools for This would invalidate the agency approval for the
all operations. Table 8.2 shows the tools required. use of the transmitter in a rated area.
It follows that the user is prohibited from using
Table 8.2 Tools for Disassembly and Reassembly a flameproof type transmitter with its integral
Tool Quantity Remarks indicator removed, or from adding an integral
Phillips 1 JIS B4633, No. 2 indicator to a transmitter. If such modification is
screwdriver absolutely required, contact Yokogawa.
Slotted 1
screwdriver
This subsection describes the procedure for
Allen wrenches 3 JIS B4648
One each, nominal 3, 4 and replacing an integral indicator. (See figure 8.3)
2.5 mm Allen wrenches
Wrench 1 Width across flats, 17 mm ■ Removing the Integral Indicator
Torque wrench 1
1) Remove the cover.
Adjustable 1
wrench 2) While supporting the integral indicator with one
Socket wrench 1 Width across flats, 16 mm hand, loosen its two mounting screws.
Socket driver 1 Width across flats, 5.5 mm 3) Dismount the LCD board assembly from the
Tweezers 1 CPU assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage
CAUTION the connector pins between it and the CPU
assembly.
Precautions for ATEX Flameproof Type
■ Attaching the Integral Indicator
Transmitters
• Flameproof type transmitters must be, as 1) Align both the LCD board assembly and CPU
a rule, removed to a non-hazardous area assembly connectors and engage them.
for maintenance and be disassembled and 2) Insert and tighten the two mounting screws.
reassembled to the original state. 3) Replace the cover.
• On the flameproof type transmitters the two Output terminal cable
covers are locked, each by an Allen head bolt
(shrouding bolt). When a shrouding bolt is
driven clockwise by an Allen wrench, it is going
in and cover lock is released, and then the Press
cover can be opened. forward

When a cover is closed it should be locked Slide


by a shrouding bolt without fail. Tighten the switch

shrouding bolt to a torque of 0.7 N·m. Integral


Boss
indicator Zero-
adjustment
CPU assembly screw
Bracket
(for zero-adjustment
screw pin)
Zero-adjustment
LCD board assembly screw pin
Mounting screw
Amplifier Cover

Shrouding Bolt
F0803.ai

Shrouding Bolt F0802.ai Figure 8.3 Removing and Attaching LCD Board
Figure 8.2 Shrouding Bolts Assembly and CPU Assembly

IM 01C25F01-01E
<8. Maintenance> 8-4
8.4.2 Replacing the CPU Board Assembly
NOTE
This subsection describes the procedure for
replacing the CPU assembly. (See figure 8.3) Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
■ Removing the CPU Assembly to tightening the two bosses. If it is not, the zero-
1) Remove the cover. If an integral indicator is adjustment mechanism will be damaged.
mounted, refer to subsection 8.4.1 and remove
the indicator. 5) Replace the cover.
2) Turn the zero-adjustment screw to the position
8.4.3 Cleaning and Replacing the Capsule
(where the screw head slot is horizontal) as
Assembly
shown in figure 8.3.
3) Disconnect the output terminal cable (cable This subsection describes the procedures for
with brown connector at the end). When doing cleaning and replacing the capsule assembly. (See
this, lightly press the side of the CPU assembly figure 8.4.)
connector and pull the cable connector to
disengage.
4) Use a socket driver (width across flats, 5.5mm) CAUTION
to loosen the two bosses.
Cautions for Flameproof Type Transmitters
5) Carefully pull the CPU assembly straight
Users are prohibited by law from modifying the
forward to remove it.
construction of a flameproof type transmitter. If
6) Disconnect the flat cable (cable with white
you wish to replace the capsule assembly with
connector at the end) that connects the CPU
one of a different measurement range, contact
assembly and the capsule.
Yokogawa.
The user is permitted, however, to replace a
NOTE capsule assembly with another of the same
Be careful not to apply excessive force to the measurement range. When doing so, be sure to
CPU assembly when removing it. observe the following.
• The replacement capsule assembly must
have the same part number as the one being
■ Mounting the CPU Assembly replaced.
1) Connect the flat cable (with white connector) • The section connecting the transmitter and
between the CPU assembly and the capsule. capsule assembly is a critical element in
2) Connect the output terminal cable (with brown preservation of flameproof performance, and
connector). must be checked to verify that it is free of
dents, scratches, and other defects.
NOTE • After completing maintenance, be sure to
securely tighten the setscrews that fasten the
Make certain that the cables do not get pinched transmitter section and pressure-detector
between the case and the edge of the CPU section together.
assembly.

3) Align and engage the zero-adjustment screw


pin with the groove on the bracket on the CPU
assembly. Then insert the CPU board assembly
straight onto the post in the amplifier case.
4) Tighten the two bosses. If the transmitter is
equipped with an integral indicator, refer to
subsection 8.4.1 to mount the indicator.

IM 01C25F01-01E
<8. Maintenance> 8-5
■ Removing the Capsule Assembly Transmitter section

IMPORTANT
Hexagon
Exercise care as follows when cleaning the head screw

capsule assembly. Stopper


• Handle the capsule assembly with care, and
be especially careful not to damage or distort
Setscrew
the diaphragms that contact the process
fluid.
• Do not use a chlorinated or acidic solution for
cleaning.
• Rinse thoroughly with clean water after
cleaning.

1) Remove the CPU assembly as shown in


subsection 8.4.2.
2) Remove the two setscrews that connect the
transmitter section and pressure-detector Capsule assembly
section. F0804.ai

3) Remove the hexagon-head screw and the Figure 8.4 Removing and Mounting the Pressure-
stopper. detector Section
4) Separate the transmitter section and capsule
assembly.
5) Clean the capsule assembly or replace with a 8.5 Troubleshooting
new one.
If any abnormality appears in the measured values,
■ Reassembling the Capsule Assembly use the troubleshooting flow chart below to isolate
and remedy the problem. Since some problems
1) Insert the capsule assembly to the transmitter
have complex causes, these flow charts may
section. Reattach the sopper with the hexagon-
not identify all. If you have difficulty isolating or
head screw.
correcting a problem, contact Yokogawa service
2) Tighten the two setscrews. (Tighten the screws
personnel.
to a torque of 1.5 N·m)
3) Install the CPU assembly according to
subsection 8.4.2.
4) After completing reassembly, adjust the zero
point and recheck the parameters.

IM 01C25F01-01E
<8. Maintenance> 8-6
8.5.1 Basic Troubleshooting 8.5.2 Troubleshooting Flowcharts
First determine whether the process variable
The following sorts of symptoms indicate that transmitter
is actually abnormal or a problem exists in the may not be operating properly.
Example : • There is no output signal.
measurement system. • Output signal does not change even though
process variable is known to be varying.
If the problem is in the measurement system, • Output value is inconsistent with value
isolate the problem and decide what corrective inferred for process variable.

action to take.
This transmitter is equipped with a self-diagnostic Connect communicator and check self-diagnostics.
function which will be useful in troubleshooting,
and the transmitter equipped with an integral
indicator will show an alarm code as a result of self- Does the self-diagnostic YES
diagnosis. indicate problem location?

See subsection 8.5.3 for the list of alarms.


See also each communication manual. NO Refer to error message summary in
Subsection 8.5.3 or in each
: Areas where self-diagnostic offers support communication manual to take actions.

Abnormalities appear in measurement.


Is power supply NO
polarity correct?

YES Is process variable YES Refer to Section 6.3 to check/correct


itself abnormal? polarity at each terminal from power
supply to the terminal box.

Inspect the NO
Measurement system problem Are power
process system. NO
supply voltage and load
resistance correct?

Isolate problem in
measurement system. YES Refer to Section 6.6 for rated voltage
and load resistance.

Are valves opened or NO


YES Does problem exist in closed correctly?
receiving instrument?

YES Fully close equalizing valve, and fully


NO open high pressure and low pressure
Inspect receiver. valves.

YES
Environmental conditions Transmitter itself Is there any pressure leak?

Check/correct NO Fix pressure leaks, paying particular


Check transmitter.
environmental conditions. attention to connections for impulse
Operating conditions piping,pressure-detector section, etc.

Is there
Check/correct operating continuity through the NO
conditions. transmitter loop wiring?
F0805.ai Do the loop numbers
match?
Figure 8.5 Basic Flow and Self-Diagnostics
Find/correct broken conductor or
YES
wiring error.

Contact Yokogawa service personnel.


F0806.ai

IM 01C25F01-01E
<8. Maintenance> 8-7

Output travels beyond 0% or 100%. Large output error.

Connect a communicator and check self-diagnostics. Connect a communicator and check self-diagnostics.

Does the self- YES Does the self- YES


diagnostic indicate problem diagnostic indicate problem
location? location?

NO Refer to error message summary in NO Refer to error message summary in


each communication manual to take each communication manual to take
actions. actions.

Are valves opened or NO


Is power supply NO
closed correctly?
polarity correct?

YES Fully close equalizing valve, and fully


YES Refer to Section 6.3 to check/correct open high pressure and low pressure
polarity at each terminal from power valves.
supply to the terminal box.

Is impulse piping NO
Are valves opened or NO
connected correctly?
closed correctly?

YES Refer to individual model user manuals


YES Fully close equalizing valve, and fully and connect piping as appropriate for
open high pressure and low pressure the measurement purpose.
valves.

Are power supply NO


YES voltage and load resistance
Is there any pressure leak?
correct?

NO YES Refer to Section 6.6 for rated voltage


Fix pressure leaks, paying particular and load resistance.
attention to connections for impulse
piping, pressure-detector section, etc.

Is transmitter
installed where there is YES
Is impulse piping NO
to high pressure and low marked variation in
pressure side correct? temperature?

Provide lagging and/or cooling, or allow


YES Refer to individual model user manuals NO adequate ventilation.
and connect piping as appropriate for
the measurement purpose.

Were appropriate NO
Is zero point NO instruments used for
adjusted correctly? calibration?

YES Refer to Section 8.2 when selecting


YES Adjust the zero point. instruments for calibration.

NO
Contact Yokogawa service personnel. Is output adjusted correctly?
F0807.ai

YES Adjust the output.

Contact Yokogawa service personnel.


F0808.ai

IM 01C25F01-01E
<8. Maintenance> 8-8
8.5.3 Alarms and Countermeasures
Table 8.3 Alarm Message Summary
Output Operation
Indicator Cause Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error
CAP. ERR Capsule temperature sensor Low) set with parameter. keeps appearing even after
problem. restart.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor Outputs the signal (Hold, High, or Replace amplifier.
AMP. ERR problem. Low) set with parameter.
Amplifier EEPROM problem.
Amplifier problem.
AL. 10 Input is outside measurement Outputs high range limit value or Check input or replace capsule
PRESS range limit of capsule. low range limit value. when necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside Use heat insulation or make
CAP. TMP range (–50 to 130°C). lagging to keep temperature
AL. 13 Amplifier temperature is outside within range.
AMP. TMP range (–50 to 95°C)
AL. 30 Output is outside upper or lower Outputs high range limit value or Check input and range setting,
RANGE range limit value. low range limit value. and change them as needed.
AL. 31 Static pressure exceeds specified Continues to operate and
SP. RNG range. output.
AL. 35 *1 Input pressure exceeds specified Check input.
P. HI threshold.
AL. 36 *1
P. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI specified threshold.
AL. 40 *1
TMP. LO
AL. 50 Specified value is outside of setting Holds output immediately before Check setting and change them
P. LRV range. error occurred. as needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 60 Specified values or settings to Continues to operate and output. Check setting and change
SC. CFG define signal characterizer function them as needed.
do not satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP

*1: These alarms may appear only when process alarm function is activated.

IM 01C25F01-01E
PROYECTO CENTRAL TERMICA RECKA     
DOCUMENTO: CTR‐01‐YTY‐DMO‐YKG‐00001 
CLIENTE: COBRA 
ORDEN: CTR‐COM‐OC‐CPI‐042 Rev. 0         
     
 

TRANSMISOR DE PRESION 
MODELO EJA110E 
TAG
01GHA10CL001AB01
01GHA10CL001BB01
01GHC01CL001AB01
01GHC01CL001BB01
01GHC01CP001-B01
01GAC10CL001AB01
01GAC10CL001BB01
01GAC20CL001AB01
01GAC20CL001BB01
01MBR10CP001-B01
01GMA01CL001-B01
01GMT01CL001-B01

 
 

 
 
<8. Maintenance> 8-1

8. Maintenance
8.1 Overview 8.3 Calibration
Use the procedure below to check instrument
WARNING operation and accuracy during periodic
maintenance or troubleshooting.
Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate care 1) Connect the instruments as shown in figure 8.1
to avoid contact with the body or inhalation of and warm up the instruments for at least five
vapors when draining condensate or venting gas minutes (ten minutes for EJ310.)
from the transmitter pressure-detector section
and even after dismounting the instrument from IMPORTANT
the process line for maintenance.
• To adjust the transmitter for highest
accuracy, make adjustments with the
Maintenance of the transmitter is easy due to its power supply voltage and load resistance
modular construction. This chapter describes the including leadwire resistances set close to
procedures for calibration, adjustment, and the the conditions under which the transmitter is
disassembly and reassembly procedures required installed.
for component replacement. • If the measurement range 0% point is
Transmitters are precision instruments. Please 0 kPa or shifted in the positive direction
carefully and thoroughly read the following sections (suppressed zero), the reference pressure
for information on how to properly handle them should be applied as shown in the figure.
while performing maintenance. If the measurement range 0% point is shifted
in the negative direction (elevated zero), the
IMPORTANT reference pressure should be applied using
a vacuum pump.
• As a rule, maintenance of this transmitter
should be done in a shop that has all the 2) Apply reference pressures of 0%, 50%,
necessary tools. and 100% of the measurement range to the
• The CPU assembly contains sensitive parts transmitter. Calculate the errors (differences
that can be damaged by static electricity. between digital voltmeter readings and
Take precautions such as using a grounded reference pressures) as the pressure is
wrist strap when handling electronic parts or increased from 0% to 100% and is decreased
touching the board circuit patterns. Also be from 100% to 0%, and confirm that the errors
sure to place the removed CPU assembly are within the required accuracy.
into a bag with an antistatic coating.

8.2 Calibration Instruments


Selection
Table 8.1 lists the instruments that can be used
to calibrate a transmitter. When selecting an
instrument, consider the required accuracy level.
Exercise care when handling these instruments to
ensure they maintain the specified accuracy.

IM 01C25B01-01E
<8. Maintenance> 8-2
Table 8.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital Model MT220 precision digital manometer Select a manometer having
manometer 1) For 10 kPa class a pressure range close to
Accuracy: ±(0.015% of rdg + 0.015% of F.S.) . . . . for 0 to 10 kPa that of the transmitter.
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Pressure Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa Requires air pressure
generator {2500 mmH2O} supply.
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to that
of the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump
source Pressure range: 0 to 133 kPa {1000 mmHg} for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa
representatives from which the instrument was purchased or the nearest Yokogawa office.

Supply pressure Pressure source


Using pressure Using pressure
generator source with
manometer Model MT220
P Pressure generator P precision digital manometer
Low pressure side Reference pressure Low pressure side Reference pressure
open to atmosphere open to atmosphere

High pressure side High pressure side

Load resistance, Power Load resistance, Power


250Ω supply 250Ω supply
E E
Rc R Load Rc R
Load
adjusting
adjusting V V
resistance,
resistance,
Digital voltmeter 100Ω Digital voltmeter
100Ω

F0801.ai

Figure 8.1 Instrument Connections (EJX110A)

IM 01C25B01-01E
<8. Maintenance> 8-3
8.4 Disassembly and 8.4.1 Replacing the Integral Indicator
Reassembly
CAUTION
This section describes procedures for disassembly
and reassembly for maintenance and component Cautions for Flameproof Type Transmitters
replacement. Users are prohibited by law from modifying the
Always turn OFF power and shut off and release construction of a flameproof type transmitter.
pressures before disassembly. Use proper tools for This would invalidate the agency approval for the
all operations. Table 8.2 shows the tools required. use of the transmitter in a rated area.
It follows that the user is prohibited from using
Table 8.2 Tools for Disassembly and Reassembly a flameproof type transmitter with its integral
Tool Quantity Remarks indicator removed, or from adding an integral
Phillips 1 JIS B4633, No. 2 indicator to a transmitter. If such modification is
screwdriver absolutely required, contact Yokogawa.
Slotted 1
screwdriver
This subsection describes the procedure for
Allen wrenches 3 JIS B4648
One each, nominal 3, 4 and replacing an integral indicator. (See figure 8.3)
2.5 mm Allen wrenches
Wrench 1 Width across flats, 17 mm ■ Removing the Integral Indicator
Torque wrench 1
1) Remove the cover.
Adjustable 1
wrench 2) While supporting the integral indicator with one
Socket wrench 1 Width across flats, 16 mm hand, loosen its two mounting screws.
Socket driver 1 Width across flats, 5.5 mm 3) Dismount the LCD board assembly from the
Tweezers 1 CPU assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage
CAUTION the connector pins between it and the CPU
assembly.
Precautions for ATEX Flameproof Type
■ Attaching the Integral Indicator
Transmitters
• Flameproof type transmitters must be, as 1) Align both the LCD board assembly and CPU
a rule, removed to a non-hazardous area assembly connectors and engage them.
for maintenance and be disassembled and 2) Insert and tighten the two mounting screws.
reassembled to the original state. 3) Replace the cover.
• On the flameproof type transmitters the two Output terminal cable
covers are locked, each by an Allen head
bolt (shrouding bolt). When a shrouding bolt
is driven clockwise by an Allen wrench, it is
going in and cover lock is released, and then Press
forward
the cover can be opened.
When a cover is closed it should be locked Slide
switch
by a shrouding bolt without fail. Tighten the
shrouding bolt to a torque of 0.7 N·m. Integral Zero-
Boss
indicator adjustment
CPU assembly screw
Bracket
(for zero-adjustment
screw pin)
Zero-adjustment
LCD board assembly screw pin
Mounting screw
Amplifier Cover

Shrouding Bolt
F0803.ai

Shrouding Bolt F0802.ai Figure 8.3 Removing and Attaching LCD Board
Figure 8.2 Shrouding Bolts Assembly and CPU Assembly

IM 01C25B01-01E
<8. Maintenance> 8-4
8.4.2 Replacing the CPU Board Assembly
NOTE
This subsection describes the procedure for
replacing the CPU assembly. (See figure 8.3) Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
■ Removing the CPU Assembly to tightening the two bosses. If it is not, the zero-
1) Remove the cover. If an integral indicator is adjustment mechanism will be damaged.
mounted, refer to subsection 8.4.1 and remove
the indicator. 5) Replace the cover.
2) Turn the zero-adjustment screw to the position
(where the screw head slot is horizontal) as 8.4.3 Cleaning and Replacing the Capsule
shown in figure 8.3. Assembly
3) Disconnect the output terminal cable (cable
This subsection describes the procedures for
with brown connector at the end). When doing
cleaning and replacing the capsule assembly. (See
this, lightly press the side of the CPU assembly
figure 8.4.)
connector and pull the cable connector to
disengage.
4) Use a socket driver (width across flats, 5.5mm) CAUTION
to loosen the two bosses.
Cautions for Flameproof Type Transmitters
5) Carefully pull the CPU assembly straight
Users are prohibited by law from modifying the
forward to remove it.
construction of a flameproof type transmitter. If
6) Disconnect the flat cable (cable with white
you wish to replace the capsule assembly with
connector at the end) that connects the CPU
one of a different measurement range, contact
assembly and the capsule.
Yokogawa.
The user is permitted, however, to replace a
NOTE capsule assembly with another of the same
Be careful not to apply excessive force to the measurement range. When doing so, be sure to
CPU assembly when removing it. observe the following.
• The replacement capsule assembly must
have the same part number as the one being
■ Mounting the CPU Assembly replaced.
1) Connect the flat cable (with white connector) • The section connecting the transmitter and
between the CPU assembly and the capsule. capsule assembly is a critical element in
2) Connect the output terminal cable (with brown preservation of flameproof performance, and
connector). must be checked to verify that it is free of
dents, scratches, and other defects.
NOTE • After completing maintenance, be sure to
securely tighten the setscrews that fasten
Make certain that the cables do not get pinched the transmitter section and pressure-detector
between the case and the edge of the CPU section together.
assembly.

3) Align and engage the zero-adjustment screw


pin with the groove on the bracket on the CPU
assembly. Then insert the CPU board assembly
straight onto the post in the amplifier case.
4) Tighten the two bosses. If the transmitter is
equipped with an integral indicator, refer to
subsection 8.4.1 to mount the indicator.

IM 01C25B01-01E
<8. Maintenance> 8-5
■ Removing the Capsule Assembly 3) After the pressure-detector section has been
reassembled, a leak test must be performed to
IMPORTANT verify that there are no pressure leaks.
4) Reattach the transmitter section to the
Exercise care as follows when cleaning the pressure-detector section.
capsule assembly. Reattach the stopper with the hexagon-head
• Handle the capsule assembly with care, and screw.
be especially careful not to damage or distort 5) Tighten the two setscrews. (Tighten the screws
the diaphragms that contact the process to a torque of 1.5 N·m)
fluid. 6) Install the CPU assembly according to
• Do not use a chlorinated or acidic solution for subsection 8.4.2.
cleaning. 7) After completing reassembly, adjust the zero
• Rinse thoroughly with clean water after point and recheck the parameters.
cleaning.
Transmitter section
1) Remove the CPU assembly as shown in
subsection 8.4.2.
2) Remove the two setscrews that connect the
transmitter section and pressure-detector
section.
Setscrew
3) Remove the hexagon-head screw and the
stopper.
4) Separate the transmitter section and pressure- Nut

detector section.
5) Remove the nuts from the four flange bolts. Capsule gasket
6) While supporting the capsule assembly with
Flange bolt
one hand, remove the cover flange.
7) Remove the capsule assembly.
8) Clean the capsule assembly or replace with a
new one.
■ Reassembling the Capsule Assembly
1) Insert the capsule assembly between the flange Pressure-detector section
bolts, paying close attention to the relative Cover flange
F0804.ai
positions of the H (high pressure side) and
Figure 8.4 Removing and Mounting the Pressure-
L (low pressure side) marks on the capsule detector Section
assembly.
Replace the two capsule gaskets with new
gaskets. IMPORTANT
2) Install the cover flange on the high pressure
If you remove the drain/vent plugs when
side, and use a torque wrench to tighten the
disassembling EJ130 and EJ440
four nuts uniformly to a torque shown below.
transmitters, install the plugs again before
EJ110, EJ310, EJ430 reassembling the cover flanges with the capsule
Model Wetted parts material code EJ120 assmbly.
S H,M,T,A,D,B
Torque(N·m) 17* 40 40
{kgf·m} {1.7} {4.1} {4.1}
*: 40 for measurement span code F.

EJ130 EJ440
Model Bolts & nuts material code
G, C J G, C J
Torque(N·m) 90 110 70 100
{kgf·m} {9.2} {11.2} {7.1} {10.2}

IM 01C25B01-01E
<8. Maintenance> 8-6
8.4.4 Replacing the Process Connector 8.5.1 Basic Troubleshooting
Gaskets
First determine whether the process variable
This subsection describes process connector is actually abnormal or a problem exists in the
gasket replacement. (See figure 8.5.) measurement system.
(a) Loosen the two bolts, and remove the process If the problem is in the measurement system,
connectors. isolate the problem and decide what corrective
(b) Replace the process connector gaskets. action to take.
(c) Remount the process connectors. Tighten the
This transmitter is equipped with a self-diagnostic
bolts securely and uniformly to a torque shown
function which will be useful in troubleshooting,
below, and verify that there are no pressure
and the transmitter equipped with an integral
leaks.
indicator will show an alarm code as a result of self-
EJ110 EJ440 diagnosis.
EJ120 See subsection 8.5.3 for the list of alarms.
Model EJ130
EJ310 C capsule D capsule See also each communication manual.
EJ430
: Areas where self-diagnostic offers support
Torque(N·m) 39 to 49 49 to 59
{kgf·m} {4 to 5} {5 to 6} Abnormalities appear in measurement.

Bolt

Process connector YES Is process variable


itself abnormal?

Process connector gasket


Inspect the NO
Measurement system problem
process system.

Isolate problem in
measurement system.

F0805.ai
YES Does problem exist in
Figure 8.5 Removing and Mounting the Process receiving instrument?
Connector
NO
Inspect receiver.

8.5 Troubleshooting
If any abnormality appears in the measured values, Environmental conditions Transmitter itself
use the troubleshooting flow chart below to isolate
and remedy the problem. Since some problems Check/correct
Check transmitter.
have complex causes, these flow charts may environmental conditions.
not identify all. If you have difficulty isolating or Operating conditions
correcting a problem, contact Yokogawa service
personnel. Check/correct operating
conditions.
F0806.ai

Figure 8.6 Basic Flow and Self-Diagnostics

IM 01C25B01-01E
<8. Maintenance> 8-7
8.5.2 Troubleshooting Flowcharts
Output travels beyond 0% or 100%.

The following sorts of symptoms indicate that transmitter


may not be operating properly.
Example : • There is no output signal. Connect a communicator and check self-diagnostics.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
inferred for process variable.
Does the self- YES
diagnostic indicate problem
location?
Connect communicator and check self-diagnostics.
NO Refer to error message summary in
each communication manual to take
actions.

Does the self-diagnostic YES


indicate problem location?
Is power supply NO
polarity correct?
NO Refer to error message summary in
Subsection 8.5.3 or in each
communication manual to take actions. YES Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.

Is power supply NO
polarity correct?
Are valves opened or NO
closed correctly?
YES Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box. YES Fully close equalizing valve, and fully
open high pressure and low pressure
valves.
Are power
NO
supply voltage and load
resistance correct?
YES
Is there any pressure leak?
YES Refer to Section 6.6 for rated voltage
and load resistance.
NO
Fix pressure leaks, paying particular
attention to connections for impulse
piping, pressure-detector section, etc.

Are valves opened or NO


closed correctly?
Is impulse piping NO
to high pressure and low
pressure side correct?
YES Fully close equalizing valve, and fully
open high pressure and low pressure
valves. YES Refer to individual model user manuals
and connect piping as appropriate for
the measurement purpose.
YES
Is there any pressure leak?
Is zero point NO
adjusted correctly?
NO Fix pressure leaks, paying particular
attention to connections for impulse
piping,pressure-detector section, etc. YES Adjust the zero point.

Is there
continuity through the Contact Yokogawa service personnel.
NO
transmitter loop wiring? F0808.ai
Do the loop numbers
match?

Find/correct broken conductor or


YES
wiring error.

Contact Yokogawa service personnel.


F0807.ai

IM 01C25B01-01E
<8. Maintenance> 8-8

Large output error.

Connect a communicator and check self-diagnostics.

Does the self- YES


diagnostic indicate problem
location?

NO Refer to error message summary in


each communication manual to take
actions.

Are valves opened or NO


closed correctly?

YES Fully close equalizing valve, and fully


open high pressure and low pressure
valves.

Is impulse piping NO
connected correctly?

YES Refer to individual model user manuals


and connect piping as appropriate for
the measurement purpose.

Are power supply NO


voltage and load resistance
correct?

YES Refer to Section 6.6 for rated voltage


and load resistance.

Is transmitter
installed where there is YES
marked variation in
temperature?

Provide lagging and/or cooling, or allow


NO adequate ventilation.

Were appropriate NO
instruments used for
calibration?

YES Refer to Section 8.2 when selecting


instruments for calibration.

NO
Is output adjusted correctly?

YES Adjust the output.

Contact Yokogawa service personnel.


F0809.ai

IM 01C25B01-01E
<8. Maintenance> 8-9
8.5.3 Alarms and Countermeasures
Table 8.3 Alarm Message Summary
Output Operation
Indicator Cause Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error
CAP. ERR Capsule temperature sensor Low) set with parameter. keeps appearing even after
problem. restart.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor Outputs the signal (Hold, High, or Replace amplifier.
AMP. ERR problem. Low) set with parameter.
Amplifier EEPROM problem.
Amplifier problem.
AL. 10 Input is outside measurement Outputs high range limit value or Check input or replace capsule
PRESS range limit of capsule. low range limit value. when necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside Use heat insulation or make
CAP. TMP range (–50 to 130°C). lagging to keep temperature
AL. 13 Amplifier temperature is outside within range.
AMP. TMP range (–50 to 95°C)
AL. 30 Output is outside upper or lower Outputs high range limit value or Check input and range setting,
RANGE range limit value. low range limit value. and change them as needed.
AL. 31 Static pressure exceeds specified Holds output immediately before
SP. RNG range. error occurred.
AL. 35 *1 Input pressure exceeds specified Continues to operate and Check input.
P. HI threshold. output.
AL. 36 *1
P. LO
AL. 37 *1 Input static pressure exceeds
SP. HI specified threshold.
AL. 38 *1
SP. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI specified threshold.
AL. 40 *1
TMP. LO
AL. 50 Specified value is outside of setting Holds output immediately before Check setting and change them
P. LRV range. error occurred. as needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 54 Continues to operate and output Check setting and change them
SP. RNG holding static pressure in %. as needed.
AL. 55 Continues to operate and output. Check input.
SP. ADJ
AL. 60 Specified values or settings to Check setting and change
SC. CFG define signal characterizer function them as needed.
do not satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP

*1: These alarms may appear only when process alarm function is activated.

IM 01C25B01-01E
PROYECTO CENTRAL TERMICA RECKA     
DOCUMENTO: CTR‐01‐YTY‐DMO‐YKG‐00001 
CLIENTE: COBRA 
ORDEN: CTR‐COM‐OC‐CPI‐042 Rev. 0         
     
 

TRANSMISOR DE PRESION 
MODELO EJA210E 
TAG
01EGB10CL001AB01
01EGB10CL001B
01EGB20CL001AB01
01EGB20CL001B

 
 

 
 
<8. Maintenance> 8-1

8. Maintenance
8.1 Overview 8.3 Calibration
Use the procedure below to check instrument
WARNING operation and accuracy during periodic
maintenance or troubleshooting.
Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate care 1) Connect the instruments as shown in figure 8.1
to avoid contact with the body or inhalation of and warm up the instruments for at least five
vapors when draining condensate or venting gas minutes.
from the transmitter pressure-detector section
and even after dismounting the instrument from IMPORTANT
the process line for maintenance.
• To adjust the transmitter for highest
accuracy, make adjustments with the
Maintenance of the transmitter is easy due to its power supply voltage and load resistance
modular construction. This chapter describes the including leadwire resistances set close to
procedures for calibration, adjustment, and the the conditions under which the transmitter is
disassembly and reassembly procedures required installed.
for component replacement. • If the measurement range 0% point is
Transmitters are precision instruments. Please 0 kPa or shifted in the positive direction
carefully and thoroughly read the following sections (suppressed zero), the reference pressure
for information on how to properly handle them should be applied as shown in the figure.
while performing maintenance. If the measurement range 0% point is shifted
in the negative direction (elevated zero), the
IMPORTANT reference pressure should be applied using
a vacuum pump.
• As a rule, maintenance of this transmitter
should be done in a shop that has all the 2) Apply reference pressures of 0%, 50%,
necessary tools. and 100% of the measurement range to the
• The CPU assembly contains sensitive parts transmitter. Calculate the errors (differences
that can be damaged by static electricity. between digital voltmeter readings and
Take precautions such as using a grounded reference pressures) as the pressure is
wrist strap when handling electronic parts or increased from 0% to 100% and is decreased
touching the board circuit patterns. Also be from 100% to 0%, and confirm that the errors
sure to place the removed CPU assembly are within the required accuracy.
into a bag with an antistatic coating.

8.2 Calibration Instruments


Selection
Table 8.1 lists the instruments that can be used
to calibrate a transmitter. When selecting an
instrument, consider the required accuracy level.
Exercise care when handling these instruments to
ensure they maintain the specified accuracy.

IM 01C25C01-01E
<8. Maintenance> 8-2
Table 8.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal
Load resistor Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital Model MT220 precision digital manometer Select a manometer having
manometer 1) For 10 kPa class a pressure range close to
Accuracy: ±(0.015% of rdg + 0.015% of F.S.) . . . . for 0 to 10 kPa that of the transmitter.
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs
Pressure Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa Requires air pressure
generator {2500 mmH2O} supply.
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to that
of the transmitter.
Pressure Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump
source Pressure range: 0 to 133 kPa {1000 mmHg} for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa
representatives from which the instrument was purchased or the nearest Yokogawa office.

Terminal box

Power
Load resistance, 250Ω
supply
Rc R E
Load adjusting V
resistance, 100Ω
Digital voltmeter

Model MT220 Mating calibration


Model 7674 pneumatic precision flange (Note)
pressure standards digital manometer
Supply pressure P P
(Note) For a diaphragm-extended type,
prepare a mating calibration flange
Pressure source to match the diaphragm extension
length and outer diameter.

Reference pressure
F0801.ai

Figure 8.1 Instrument Connections (4 to 20 mA output)

IM 01C25C01-01E
<8. Maintenance> 8-3
8.4 Disassembly and 8.4.1 Replacing the Integral Indicator
Reassembly
CAUTION
This section describes procedures for disassembly
and reassembly for maintenance and component Cautions for Flameproof Type Transmitters
replacement. Users are prohibited by law from modifying the
Always turn OFF power and shut off and release construction of a flameproof type transmitter.
pressures before disassembly. Use proper tools for This would invalidate the agency approval for the
all operations. Table 8.2 shows the tools required. use of the transmitter in a rated area.
It follows that the user is prohibited from using
Table 8.2 Tools for Disassembly and Reassembly a flameproof type transmitter with its integral
Tool Quantity Remarks indicator removed, or from adding an integral
Phillips 1 JIS B4633, No. 2 indicator to a transmitter. If such modification is
screwdriver absolutely required, contact Yokogawa.
Slotted 1
screwdriver
This subsection describes the procedure for
Allen wrenches 3 JIS B4648
One each, nominal 3, 4 and replacing an integral indicator. (See figure 8.3)
2.5 mm Allen wrenches
Wrench 1 Width across flats, 17 mm ■ Removing the Integral Indicator
Torque wrench 1
1) Remove the cover.
Adjustable 1
wrench 2) While supporting the integral indicator with one
Socket wrench 1 Width across flats, 16 mm hand, loosen its two mounting screws.
Socket driver 1 Width across flats, 5.5 mm 3) Dismount the LCD board assembly from the
Tweezers 1 CPU assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage
CAUTION the connector pins between it and the CPU
assembly.
Precautions for ATEX Flameproof Type
■ Attaching the Integral Indicator
Transmitters
• Flameproof type transmitters must be, as 1) Align both the LCD board assembly and CPU
a rule, removed to a non-hazardous area assembly connectors and engage them.
for maintenance and be disassembled and 2) Insert and tighten the two mounting screws.
reassembled to the original state. 3) Replace the cover.
• On the flameproof type transmitters the two Output terminal cable
covers are locked, each by an Allen head bolt
(shrouding bolt). When a shrouding bolt is
driven clockwise by an Allen wrench, it is going
in and cover lock is released, and then the Press
cover can be opened. forward

When a cover is closed it should be locked Slide


by a shrouding bolt without fail. Tighten the switch

shrouding bolt to a torque of 0.7 N·m {7 kgf·cm}. Integral


Boss Zero-
indicator adjustment
CPU assembly screw
Bracket
(for zero-adjustment
screw pin)
Zero-adjustment
LCD board assembly screw pin
Mounting screw
Amplifier Cover

Shrouding Bolt
F0803.ai

Shrouding Bolt F0802.ai Figure 8.3 Removing and Attaching LCD Board
Figure 8.2 Shrouding Bolts Assembly and CPU Assembly

IM 01C25C01-01E
<8. Maintenance> 8-4
8.4.2 Replacing the CPU Board Assembly
NOTE
This subsection describes the procedure for
replacing the CPU assembly. (See figure 8.3) Confirm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
■ Removing the CPU Assembly to tightening the two bosses. If it is not, the zero-
1) Remove the cover. If an integral indicator is adjustment mechanism will be damaged.
mounted, refer to subsection 8.4.1 and remove
the indicator. 5) Replace the cover.
2) Turn the zero-adjustment screw to the position
8.4.3 Replacing the Process Connector
(where the screw head slot is horizontal) as
Gasket
shown in figure 8.3.
3) Disconnect the output terminal cable (cable This subsection describes the procedure for
with brown connector at the end). When doing replacing the process connector gasket. (See
this, lightly press the side of the CPU assembly Figure 8.4)
connector and pull the cable connector to
1) Loosen the two bolts and remove the process
disengage.
connector.
4) Use a socket driver (width across flats, 5.5mm)
2) Replace the process connector gasket.
to loosen the two bosses.
3) Mount the process connector. Tighten the bolts
5) Carefully pull the CPU assembly straight
securely and uniformly to a torque of 39 to 49
forward to remove it.
N·m {4 to 5 kgf·m}, and verify that there are no
6) Disconnect the flat cable (cable with white
pressure leaks.
connector at the end) that connects the CPU
assembly and the capsule.

NOTE
Be careful not to apply excessive force to the
CPU assembly when removing it.
Process connector gasket
■ Mounting the CPU Assembly
Process connector
1) Connect the flat cable (with white connector)
between the CPU assembly and the capsule. Bolt
2) Connect the output terminal cable (with brown
connector).

NOTE
F0804.ai

Figure 8.4 Replacing the Process Connector


Make certain that the cables are free of pinching Gasket
between the case and the CPU assembly edge.

3) Align and engage the zero-adjustment screw 8.5 Troubleshooting


pin with the groove on the bracket on the CPU If any abnormality appears in the measured values,
assembly. Then insert the CPU board assembly use the troubleshooting flow chart below to isolate
straight onto the post in the amplifier case. and remedy the problem. Since some problems
4) Tighten the two bosses. If the transmitter is have complex causes, these flow charts may
equipped with an integral indicator, refer to not identify all. If you have difficulty isolating or
subsection 8.4.1 to mount the indicator. correcting a problem, contact Yokogawa service
personnel.

IM 01C25C01-01E
<8. Maintenance> 8-5
8.5.1 Basic Troubleshooting 8.5.2 Troubleshooting Flowcharts
First determine whether the process variable
The following sorts of symptoms indicate that transmitter
is actually abnormal or a problem exists in the may not be operating properly.
Example : • There is no output signal.
measurement system. • Output signal does not change even though
process variable is known to be varying.
If the problem is in the measurement system, • Output value is inconsistent with value
isolate the problem and decide what corrective inferred for process variable.

action to take.
This transmitter is equipped with a self-diagnostic Connect communicator and check self-diagnostics.

function which will be useful in troubleshooting,


and the transmitter equipped with an integral
indicator will show an alarm code as a result of self- Does the self-diagnostic YES
diagnosis. indicate problem location?

See subsection 8.5.3 for the list of alarms.


See also each communication manual. NO Refer to error message summary in
Subsection 8.5.3 or in each
: Areas where self-diagnostic offers support communication manual to take actions.

Abnormalities appear in measurement.


Is power supply NO
polarity correct?

YES Is process variable YES Refer to Section 6.3 to check/correct


itself abnormal? polarity at each terminal from power
supply to the terminal box.

Inspect the NO
Measurement system problem Are power
process system. NO
supply voltage and load
resistance correct?

Isolate problem in
measurement system. YES Refer to Section 6.6 for rated voltage
and load resistance.

Are valves opened or NO


YES Does problem exist in closed correctly?
receiving instrument?

YES Fully close equalizing valve, and fully


NO open high pressure and low pressure
Inspect receiver. valves.

YES
Environmental conditions Transmitter itself Is there any pressure leak?

Check/correct NO Fix pressure leaks, paying particular


Check transmitter.
environmental conditions. attention to connections for impulse
Operating conditions piping,pressure-detector section, etc.

Is there
Check/correct operating continuity through the NO
conditions. transmitter loop wiring?
F0805.ai Do the loop numbers
match?
Figure 8.5 Basic Flow and Self-Diagnostics
Find/correct broken conductor or
YES
wiring error.

Contact Yokogawa service personnel.


F0806.ai

IM 01C25C01-01E
<8. Maintenance> 8-6

Output travels beyond 0% or 100%. Large output error.

Connect BRAIN TERMINAL and check self-diagnostics. Connect BRAIN TERMINAL and check self-diagnostics.

Does the self- YES Does the self- YES


diagnostic indicate problem diagnostic indicate problem
location? location?

NO Refer to error message summary in each NO Refer to error message summary in each
communication manual to take actions. communication manual to take actions.

Are valves opened or NO


Is power supply NO
closed correctly?
polarity correct?

YES Fully open the low pressure valve.


YES Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.

Is impulse piping NO
Are valves opened or NO
connected correctly?
closed correctly?

YES Refer to individual model user manuals


YES Fully open the low pressure valve. and connect piping as appropriate for
the measurement purpose.

Are power supply NO


YES voltage and load resistance
Is there any pressure leak?
correct?

NO YES Refer to Section 6.6 for rated voltage


Fix pressure leaks, paying particular and load resistance.
attention to connections for impulse
piping, pressure-detector section, etc.

Is transmitter
installed where there is YES
Is zero point NO
marked variation in
adjusted correctly?
temperature?

Provide lagging and/or cooling, or allow


YES Adjust the zero point. NO adequate ventilation.

Contact Yokogawa service personnel.


F0807.ai
Were appropriate NO
instruments used for
calibration?

YES Refer to Section 8.2 when selecting


instruments for calibration.

NO
Is output adjusted correctly?

YES Adjust the output.

Contact Yokogawa service personnel.


F0808.ai

IM 01C25C01-01E
<8. Maintenance> 8-7
8.5.3 Alarms and Countermeasures
Table 8.3 Alarm Message Summary
Output Operation
Indicator Cause Countermeasure
during Error
None
AL. 01 Sensor problem. Outputs the signal (Hold, High, or Replace capsule when error
CAP. ERR Capsule temperature sensor Low) set with parameter. keeps appearing even after
problem. restart.
Capsule EEPROM problem.
AL. 02 Amplifier temperature sensor Outputs the signal (Hold, High, or Replace amplifier.
AMP. ERR problem. Low) set with parameter.
Amplifier EEPROM problem.
Amplifier problem.
AL. 10 Input is outside measurement Outputs high range limit value or Check input or replace capsule
PRESS range limit of capsule. low range limit value. when necessary.
AL. 11 Static pressure exceeds limit. Continues to operate and output.
ST. PRSS
AL. 12 Capsule temperature is outside Use heat insulation or make
CAP. TMP range (–50 to 130°C). lagging to keep temperature
AL. 13 Amplifier temperature is outside within range.
AMP. TMP range (–50 to 95°C)
AL. 30 Output is outside upper or lower Outputs high range limit value or Check input and range setting,
RANGE range limit value. low range limit value. and change them as needed.
AL. 31 Static pressure exceeds specified Continues to operate and
SP. RNG range. output.
AL. 35 *1 Input pressure exceeds specified Check input.
P. HI threshold.
AL. 36 *1
P. LO
AL. 37 *1 Input static pressure exceeds
SP. HI specified threshold.
AL. 38 *1
SP. LO
AL. 39 *1 Detected temperature exceeds
TMP. HI specified threshold.
AL. 40 *1
TMP. LO
AL. 50 Specified value is outside of setting Holds output immediately before Check setting and change them
P. LRV range. error occurred. as needed.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53 Continues to operate and output. Check input.
P. ADJ
AL. 54 Continues to operate and output Check setting and change them
SP. RNG holding static pressure in %. as needed.
AL. 55 Continues to operate and output. Check input.
SP. ADJ
AL. 60 Specified values or settings to Check setting and change
SC. CFG define signal characterizer function them as needed.
do not satisfy the condition.
AL. 79 Displayed value exceeds limit.
OV. DISP

*1: These alarms may appear only when process alarm function is activated.

IM 01C25C01-01E
PROYECTO CENTRAL TERMICA RECKA     
DOCUMENTO: CTR‐01‐YTY‐DMO‐YKG‐00001 
CLIENTE: COBRA 
ORDEN: CTR‐COM‐OC‐CPI‐042 Rev. 0         
     
 

FLUJOMETRO TIPO VORTEX 
MODELO DYA 
TAG
01GHC30CF001-B01

 
 

 
 
10. MAINTENANCE

10. MAINTENANCE

CAUTION

• Disassemble work should be done only for error occurrence.


• Maintenance work must be carried out by expert engineer or skilled personnel and not by operators.
• Before opening the cover, it is important to ensure that at least 10 minutes have passed since the
power was turned off. Furthermore, opening of the cover must also be carried out by expert engineer or
skilled personnel.

CAUTION

• It is prohibited by law for the user to modify flameproof instruments. It is not permitted to add or remove
indicators. If modification is required, contact YOKOGAWA.
• Explosion protected type must be, as a rule, removed to a non-hazardous area for maintenance and be
disassembled and reassembled to the original state.
• For TIIS, ATEX and SAA explosion proof, the display cover is locked by the clamp. In case of opening
the display cover, use the hexagonal wrench attached.
• Be sure to lock the cover by the clamp using the hexagonal wrench attached after installing the cover.

10-1 IM 01F06A00-01EN
10. MAINTENANCE

10.1 Changing the Terminal Box Orientation


The terminal box can be changed in four directions with respect to the flow direction.

Integral Type Vortex Flowmeter Remote Type Vortex Flowmeter

<1> Remove the converter cover. In case of the explosion proof <1> Remove the terminal box cover. In case of the explosion
type cover removal, loosen the clamp (WAF: 3mm). proof type cover removal, loosen the clamp (WAF: 3mm).
<2> For indicator and amplifier unit removal, refer to paragraph <2> Disconnect the vortex shedder assembly lead-wires from
10.2 and 10.4. the terminal box. In case of the explosion proof type,
<3> Disconnect the vortex shedder assembly lead-wires from loosen the lock screw (WAF: 1.5mm).
the converter. In case of the explosion proof type, loosen <3> Remove the bracket mounting bolts and remove the
the lock screw (WAF: 1.5mm). terminal box and bracket from the flowmeter body.
<4> Remove the bracket mounting bolts and remove the The bracket applies to the 1 (25mm) to 4 (100mm) inch
converter and bracket from the flowmeter body. The flowmeters.
bracket applies to the 1 (25mm) to 4 (100mm) inch <4> Remove the hexagon mounting bolts in case of 90-degree
flowmeters. turn.
<5> Remove the hexagon mounting bolts in case of 90-degree <5> Turn the terminal box to the desired orientation. When
turn. reassembling the terminal box, reverse the above
<6> Turn the converter to the desired orientation. When procedure.
reassembling the converter, reverse the above procedure.

Clamp Clamp
For the explosion For the explosion
protected type WAF: protected type
Flameproof (TIIS, 3mm Flameproof (TIIS, WAF:
3mm
ATEX, IECEx) ATEX, IECEx)
Intrinsically safe Intrinsically safe
(SAA) (SAA) Terminal Box
Type n (ATEX) Shielded Cover Type n (ATEX)
Terminal Box Cover Bracket
Amplifier Unit
Bracket
Indicator
Hexagon Bracket Mounting
mounting Bolt
bolt Locking
Lock Screw Hexagon mounting
Screw
Bracket bolt
Mounting Wire*
Wire* Vortex Shedder
Bolt
Converter Cover Assembly
Vortex Shedder
Assembly
*Wire Color Terminal
*Wire Color Terminal
Red A Red A
White B White B
Body
Body

F100101.EPS

10-2 IM 01F06A00-01EN
10. MAINTENANCE

10.2 Indicator Removal and Rota- 10.4 Amplifier Unit Assembling


tion
(1) Turn the power OFF.
IMPORTANT
(2) Remove the cover.
* In case of the Explosion protected type, remove the The amplifier unit must be assembled keeping the
cover after unlock the clamp. procedure as follows. Amplifier may not operate
(3) For the indicator, disconnect the cable connector from normally when the procedure does not keep.
the amplifier unit.
(4) Loosen the two indicator mounting screws using a
Phillips screwdriver. (1) Put two-mounting pins 1 into mounting hole 2 .
(5) Pull out the indicator. (2) Push the head of two mounting screws 4 lightly.
(6) Reinstall the indicator in the reverse order to its removal (3) Push head of two IC 5 and mount the amplifier unit 3 .
(above) and secure the mounting screws. (4) Tighten two mounting screws 4 .

1 Mounting Pins

90° 3 Amplifier Unit

5 IC

2 Mounting Holes

Indicator Indicator Mounting Screws 4 Mounting Screw


(2PCS)
F100201.EPS

Figure 10.1 Removing and Reinstalling the Indicator F100401.EPS

Figure 10.2 Removing and Reinstalling the Amplifier Unit

10.3 Amplifier Unit Removal

IMPORTANT

Do not turn the amplifier unit for removal or assem-


bling. The connector pins may be damaged.

(1) Turn the power OFF.


(2) Remove the converter cover.
* In case of the Explosion protected type, remove the
cover after unlock the clamp.
(3) Remove the indicator according to the procedures
described in paragraph 10.2.
(4) Loosen the terminal screws and remove the amplifier
unit.

10-3 IM 01F06A00-01EN
10. MAINTENANCE

10.5 Vortex Shedder Removal Table 10.1 Torque Value


Torque Value UNIT: N.m
Nominal Size High Temperature (/HT)
Standard,
mm (inch)
/NC, /LT A B
CAUTION
15 (1/2) 16
• Disassemble work should be done only for 25 (1) 12 18 12
error occurrence. 40 (1-1/2) 12 18 12
• Only expert engineer or skilled personnel are 50 (2) 18 27 18
permitted to open the cover. 80 (3) 32 48 32
• When the vortex shedder is disassembled, and 100 (4) 49 74 49
empty the flow tube before the gasket must be Shedder
49 69 49
bar “L”, “X”
replaced with a new one. 150 (6)
Shedder
• Output error may cause when the shedder bar bar “B”
60 90 60
is not restored correctly. 200 (8) 69 98 69
• For Explosion proof type, move vortex flowme- 250 (10) 157 210 140
ter to non-hazardous area firstly, then do the 300 (12) 157 210 140
assemble work. T100501.EPS

(1) For nominal size 15mm to 100mm (1 inch to 4 inch), In case of High Temperature Version (Option code: HT),
remove the converter cover or terminal box according to First time tighten Nuts with a torque wrench, applying the
the following (2) to (5). For nominal size 150mm to 300 torque specified “A”.
(6 inch to 12 inch), this procedure is not necessary. Next time loosen Nuts completely, then again tighten Nuts
(2) For integral type, remove the converter cover. For with a torque wrench, applying the torque specified “B”.
remote type, remove the terminal cover. For integral
type, loosen the hexagonal screw on the Amplifier unit, e. Insert the leadwires (vortex shedder) through the
then remove the amplifier unit. Remove the indicator terminal box bottom hole and lower the terminal box
first, in case the device has it. slowly until the bracket touches the flowmeter
(3) For integral type, remove the Shielded cover back shoulder. Be sure to keep the leadwires vertical
Amplifier unit. In case of following Explosion proof while lowering the terminal box.
type, loosen the locking screw on the converter case or f. After assembling, confirm that there is no leakage
terminal box. from the vortex flowmeter.
Explosion proof type: TIIS Flame proof, ATEX
IMPORTANT
Explosion proof, SAA Flame
proof Please tighten the screws/bolts uniformily and
(4) Remove the Leadwire by loosening a screw on the observing the torque value in Table 10.1.
terminal strip.
(5) Loosen the bracket mounting bolts and remove the
converter case or terminal box together with the bracket.
Be careful not to damage the leadwires of the vortex
shedder assembly.
(6) Loosen the vortex shedder assembly mounting bolts (2
to 6 pcs) and remove the vortex shedder assembly.
(7) When reassembling the vortex shedder assembly, reverse
above procedure. Confirm the following.
a. Replace to a new gasket.
b. The guide pin on the vortex shedder mounting block
meets the guide pin hole. See Figure 10.3.
Nominal size 150mm to 300mm (6inch to 12inch)
has no guide pin.
c. The vortex shedder assembly is installed as illus-
trated in Figure 10.3.
d. Tighten the sensor mounting bolts uniformly and
diagonally in three or four times. See Figure 10.4.

10-4 IM 01F06A00-01EN
10. MAINTENANCE

Vortex shedder
Mounting Bolt *
Converter Case Color Wire

Vortex shedder Red A


Clamp Mounting Block White B
Shielded Cover
Leadwire
Amplifier Unit Bracket
Hexagonal Screw
Indicator

Converter Cover
Locking
Screw
Converter Vortex Shedder
Mounting Bolt Assembly
Bracket
Mounting Gasket
Bolt
Integral Type

Terminal Box
Clamp
Locking
Terminal
Screw Bracket
Box Cover

Bracket
Mounting
Bolt

Allen Bolt
Remote Type

Vortex Shedder Vortex Shedder Leadwire


Assembly Mounting Block

Vortex Shedder Flow direction


Assembly Pin
Guide Pin Hole
Guide Pin Hole
Vortex Shedder
Vortex Shedder Assembly
Direction Assembly
of Flow Flow Direction Arrow

Flow direction
F100501.EPS

Figure 10.3 Disassembling and Reassembling the Vortex Shedder Assembly


① ④ ① ④

① ②
Upstream Upstream Upstream
③ ②

③ ②

Case: two bolts

Case: four bolts


Case: six bolts
F100502.EPS
Figure 10.4 Procedure of tightening bolts
10-5 IM 01F06A00-01EN
10. MAINTENANCE

10.6 Flow Calculation PR: Pulse rate (ex. E+ 3 is 103.)


Tf: Temperature at operating conditions (°C)
(1) Flow Calculation (°F)
The flowrate is calculated with the following equations based FS: Flowrate span
on the N number of generated vortices: TR: Total rate
D: Internal diameter (m) (inch)
(a) Flowrate (in engineering units)
µ: Viscosity (mPa • s(cP))
1 1 ρf: Density at operating conditions (kg/m3) (艎b/
RATE=N × × ε f × εe × εr × × Uk × UTM
t KT ft3)
.... (10.1.1)
(2) Flow Conversion Factor (Uk)
KT=KM × UKT × {1–4.81 × (Tf–15) × 10–5}.... (Metric Units)
Flow conversion factor Uk is obtained by carrying out the
.... (10.1.2)
following computation depending on the selection of the fluid
KT=KM × {1–2.627 × (Tf–59)×10–5} .... (English Units)
.... (10.1.3) to be measured and the flow unit.
(b) Flowrate (%) (a) Steam
1 M (Mass flowrate): Uk=ρf × Uρf × Uk (kg) .... (10.7.1)
RATE(%)=RATE × .... (10.2) Uk=ρf × Uk (艎b) .... (10.7.2)
FS
Qf (Flowrate at operation): Uk=Uk (m3) .... (10.7.3)
(c) Totalized value Uk=Uk (acf) .... (10.7.4)
TOTAL=TOTAL + TOTAL (b) Gas
Qn: (Flowrate at STP):
1 1
TOTAL=RATE × t × × .... (10.3) 1
TR UTM Pf Pf + 273.15
Uk = × × × Uk (Nm )3
.... (10.8)
Pn Pn + 273.15 K
(d) Pulse output frequency
5
1 1 Pf (Tn-32) + 273.15 1
PULSE FREQ=RATE × P × U .... (10.4.1) Uk = × 9
× × Uk (scf)
5
R TM Pn 9 (Tn-32) + 273.15 K
1 1
PULSE FREQ= N × t × P .... (Unscaled pulses) M: (Mass flowrate): Uk=ρf × Uρf × Uk (kg) .... (10.9.1)
R
Uk=ρf × Uρf × Uk (艎b) .... (10.9.2)
.... (10.4.2)
Qf: (Flowrate): Uk=Uk (m3) .... (10.10.1)
(e) Velocity
Uk=Uk (acf) .... (10.10.2)
1 1 4 (c) Liquid
V=N × t × × UKT × .... (10.5)
KT πD
2
Qf: (Flowrate): Uk=Uk (m3) .... (10.11.1)
(f) Reynolds number Uk=Uk (acf) .... (10.11.2)
M (Mass flowrate): Uk=ρf × U (kg) .... (10.12.1)
1
Re=V × D × ρf × × 1000 .... (Metric Units) Uk=7.481 × ρf × U (艎b) .... (10.12.2)
µ
7.481 is a conversion factor of U.S
.... (10.6.1)
gal into acf
1 (d) User’s unit
Re=V × D × ρf × × 124 .... (English Units)
µ Uk=Uk (user) .... (10.13)
.... (10.6.2)
where N: Number of input pulses (pulse) Uρf: Unit conversion factors of density.
∆t: Time corresponding to N (seconds) Uk(kg), Uk(Nm3), Uk(m3)
εf : Instrumental error correction factor Uk(lb), Uk(Btu), Uk(scf) , Uk(acf): Unit conversion factors
εe: Expansion correction factor for compressive
fluid
εr : Reynolds number correction factor
KT: K-factor at operating conditions (pulses/
litre) (pulse/gal)
KM: K-factor at temperature 15°C (59°F)
UKT: Unit conversion factor for K-factor
Uk: Flow unit conversion factor (Refer to item
(2))
Uk(user): Flow unit conversion factor for user’s unit
UTM: Factor corresponding to flow unit time (ex./
m (minute) is 60.)

10-6 IM 01F06A00-01EN
10. MAINTENANCE

(3) Mass Flow calculation Where


a) Steam M : Mass flow
In case of saturated steam, mass flow rate is calculated Qn : Volumetric flow rate at Standard condition
from density values to temperature measured by using Qf : Volumetric flow rate at oprtating condition
saturated steam table. Tn : Temperature at operating condition (°C), (°F)
Tf : Temperature at standard condition (°C), (°F)
In case of superheat steam, mass flow rate is calculated Tft : Measured temperature value (°C), (°F)
from density values to temperature measured by using Pf : Pressure at operating condition (kPa abs), (psi)
steam table. In order to measure superheat steam, it is Pn : Pressure at standard condition (kpa abs), (psi)
necessary to make constant pressure value. A pressure K : Deviation factor
values which is entered in parameter is used. ρft : Density calculated by temperature value
ρn : Density at Standard condition (kg/m3), (lb/cf)
M = ρft × Qf ..................................................................................................... (10.14.1) ρf : Density at operating condition
Uρf: Density unit conversion factor
b) Gas Uk(kg), Uk(Nm3), Uk(m3) : Flow unit conversion factor
In case of gas, Volumetric flow rate at standard a1 : 1st temperature coefficient
condition is calculated, so Pressure-Temperature a2 : 2nd temperature coefficient
correction is carried out. It is necessary to make
constant pressure value. A Pressure values at opera- Example: conversion factor in kg.
tional condition, temperature and pressure value at kg : Ukkg =1
standard condition which is entered in parameter is used. ton : Ukkg =0.001

P Tn + 273.15 1
Qn = Qf × ––f × –––––––––– × –– ........................ (10.14.2)
Pn TfT + 273.15 K

c) Liquid
In case of liquid, mass flow late is calculated from
which used to calculate the secondary function for the
density value to the temperature. A density value which
indicated by the order sheet is used.

M = ρn × Qf × {1 + a1(Tft – Tn) × 10-2 + a2(Tft – Tn)2 × 10-6}


...................................................................... (10.14.3)

[Footnote]
a1 = {(k1 – 1) × ∆T22 – (k2 – 1) × ∆T12}/
{(∆T1 × ∆T22–∆T2 × ∆T12) × 102}
a2 = {(k1 – 1) × ∆T2 – (k2 – 1) × ∆T1}/
{(∆T12 × ∆T2–∆T22 × ∆T1) × 10-6}
∆T = Tf – Tn
k = {(1 + a1× ∆T × 10-2 + a2 × ∆T2 × 10-6}

10-7 IM 01F06A00-01EN
11. TROUBLESHOOTING

11. TROUBLESHOOTING

CAUTION

Please avoid replacing the amplifier unit from the case, and the vortex shedder bar. When these procedures are
needed, please contact the nearest Yokogawa office.

11.1 Flow
● Large flowmeter errors and flowrate reading fluctuates.

• If a built-in indicator is attached,


check the display of the error code.
• Connect a hand-held terminal and
check self-diagnostic.
Is there a snapping Yes Check the cavitation
sound from the flowmeter ? referring to "12.5:Sizing".

No
Was a faulty area Yes
found with selfdiagnosis?

Is digitalYEWFLO No
Refer to the error code list Ground YEWFLO.
properly grounded?
No and check for recovery
measures.
Yes
Are the parameters
No Configure the parameters
configured correctly at
correctly
operating conditions?
Does the value in Yes This case is due to coating
"K34:VORTEX FREQ." of stuff vortex shedder bar.
Yes undergo a lot of Check the piping inner
changes? surfaces.

Ensure the straight lengths


Is straight lengths of No No
of pipeline referring to
pipeline stable? "2:INSTALLATION".

Normal
Yes

Yes
Yes Replace the gaskets
Does gaskets protrudes? referring "2:INSTALLATION".
Check standards.

No
Note 1: This is the temperature and pressure at digitalYEWFLO
mounted place.
Note 2: Contact with our service in case this is not carried out into
the right statement.
F110101.EPS

● After the output showed correctly, the indication


goes down to zero at certain time. How to cope with this problem
When this problem occurred, the cause is suspected of 1) Referring item 10.5 “Vortex Shedder Removal”, take out
deterioration of sensor sensitivity and turbulent of fluid flow the Vortex Shedder bar and clean it.
due to coating on the shedder bar and flowmeter inner tube. 2) If there is the coating on inner tube of the flowmeter,
remove the flowmeter body from adjacent pipes and
clean it.

11-1 IM 01F06A00-01EN
11. TROUBLESHOOTING
● No output is indicated when the fluid is flowing.
• If a built-in indicator is attached,
check the display of the error code.
• Connect a hand-held terminal and
check self-diagnostic.

Was a faulty area Yes


found with selfdiagnosis?

Refer to the error code list and check


No for recovery measures.

Is the output signal current No


present?

Yes
Are the power polarities No Check the
correct? polarities.
Is "6.1.3:Loop test" No Replace the
OK? AMP unit. Yes

Yes

Are there any disconnected Yes Fasten the


power terminals? power terminal.
Are parameters configured No Configure the
correctly at operating
parameters correctly.
conditions?
No

Yes

Yes Replace the


Is the cable broken?
cable.
No
Is "K34:VORTEX FREQ" 0Hz?

No
Yes
Yes Replace the
Is the low cut configured correctly?
AMP unit.

No
Configure the Low
cut value correctly.

Is the TLA value configured No Configure the TLA value referring to


correctly? "9.2.2:Tuning"

Yes

Is the density value configured No Configure the density value correctly


correctly? at operating conditions.

Yes

Is output indicated when


No Yes Replace the
"K25:N.B MODE" is "MANUAL" Is there broken the sensor?
and "K26:NOISE RATIO" is "0" shedder bar

No
Yes

Replace the
This case is due to coating of AMP unit.
vortex shedder bar.
Check the shedder bar piping inner
surfaces.
F110102.EPS

11-2 IM 01F06A00-01EN
11. TROUBLESHOOTING

● Output is indicated at zero flow.


• If a built-in indicator is attached,
check the display of the error code.
• Connect a hand-held terminal and
check self-diagnostic.

Was a faulty area Yes


found with selfdiagnosis?

Refer to the error code list and check


No for recovery measures.

Yes
Is fluid flowing? Stop flow.

No

Are parameters configured No


correctly at operating Configure the parameters correctly.
conditions?

Yes

Are the load resistance No


and supply voltage within Adjust to within the tolerance limits.
the tolerance limits?

Yes

Is digitalYEWFLO No
properly grounded? Ground digitalYEWFLO.

Yes

No
Does low cut adjust? Adjust to low cut.

Yes

No
Does the tuning execute? Execute the tuning referring
"9.2:Adjustment for manual mode"

Yes

Does high vabrations Yes


Eliminate vibration noise using pipe
occurs in pipeline? support.

No

Are pulsation produced?


Check the pipeline conditions
referring "2:INSTALLATION"
F110103.EPS

11-3 IM 01F06A00-01EN
11. TROUBLESHOOTING

11.2 Flow (Only for /MV)


● Start with this flow in case of /MV.

• If a built-in indicator is attached,


check the display of the error
code.
• Connect a hand-held terminal and
check self-diagnostic.

Yes
Was a faulty area
found with self-diagnostic?

Refer to the error code list and check


for recovery measures.
No

Are the power polarities No


Check the polarities.
Correct?

Yes

Are the load resistance No


and supply voltage within Adjust to within the tolerance limits.
the tolerance limits?

Yes

Are the sensor No


Check the sensor.
connected correctly?

Yes

Are the parameters


No
confiured correctly at Configure the parameters correctly.
operational conditions?

Yes

Go to “11.1 Flow”

F110201.EPS

11-4 IM 01F06A00-01EN

You might also like