The tender text is split into three sections. Section one covering the total Distributed Pumping solution as
part of the chilled water application. Secondly, (1) Primary side will be covered and finally (2) the
secondary side.
1
Primary side
BMS will take full responsibility for system start-up, synchronization and primary pump
speed modulation. Hence forward this is referred to as “Primary Pump Control”
The primary pump control shall actively be able to prevent deltaT collapse
The primary pump control shall be able to safeguard minimum flow to Chillers
The primary pump control shall be able to cascade minimum 6 pumps
The primary pump control shall be able to control pumps based on both temperature and
flow references
The primary pump controller shall be able to perform pump cut-in/out
Secondary side
The flow modulating device must be including an integrated frequency drive
The flow modulating device shall be completely autonomously controlled
The flow modulating device shall actively be able to reduce or increase pressure in the
load/load zones autonomously or by external setpoint
The flow modulating device shall be including connectivity to BMS/BAS or cloud based
solutions
The flow modulating device shall be able to integrate with analog sensors at the loads. E.g.
differential pressure sensor, supply air temperature sensor.
The flow modulating device shall be able to control flow to branches of a load zone
The flow modulating device shall be able to limit a maximum volume flow to a load
The flow modulating device shall be able to autonomously regulate its flow according to
load demand