You are on page 1of 189

GUJARAT WATER SUPPLY &

SEWERAGE BOARD
Subject: SOR for the Year 2019-20.

Preamble:

- Gujarat Water Supply & Sewerage Board is preparing the SOR for
works of Water Supply & Drainage Projects, this SOR is followed by
GWIL and WASMO also.
- SOR for Electro-Mechanical items for the Year 2012-13 was approved
in 240th Board Meeting held on 07-03- 2012.
- For the year 2013- 14, 2014-15, 2015-16, 2016-17, 2017-18 and
2018-19 same rates of SOR of year 2012 13 are considered and
approved in 271st Board Meeting held on 28-02-2019.
- A committee was constituted for preparation of SOR vide office order
No. 603 dated 21-03 2016 and SOR preparation committee was
formed by letter No. 412 dated 17-02- 2016.
- Consultancy Services for formation of Electro-Mechanical SOR was
awarded to reputed consultants M/s Tata Consulting Engineers Ltd.
Periodically fourteen meetings of SOR committee in the presence of
the representative of M/s TCE were held.
- There after Group meetings of GWSSB senior officers & TCEL team
were held on 16-03-2019, 13-05-2019, 01-06 2019, 13-06 2019 &
15-07-2019 for final presentation to SOR scrutiny committee.
- This SOR 2019-20 for electro-Mechanical items has been approved in
the BOD No.272 of GWSSB held on dated.20/07/2019.
Important Notes:-

1) In Section-A,B,C- Proposed rates are inclusive of GST,


unless otherwise specified in the item covered under annual
Rate Contract.

2) In Section-D-Item No. 1,3 & 4,rates are adopted as per


Electrical SOR of R&B GOG and inclusive of taxes.

3) In Section-D-Item No.2,LED Lighting & Fixtures is new


Item,rates are approved seperately with & without GST.

4) In Section E & F,Approved rates are shown seperately with


and without GST.

5) In Section A,B,C,E & F, WPI Old Series and New Series are
compared and effect of the same is incorporated.
S.O.R. derived on basis of following Prevailing Rates
Sr No Particulars Unit Rate In Rs.
1 Cement Beg 260.00

2 Kapchi Cmt 990.00

3 Sand Cmt 720.00

4 Brick No 4.20

Details For Rate Of Labour Establishment For SOR 2019-20


Sr No Particulars Unit Rate In Rs.
1 Skilled labour No 329.20

2 Semi-Skilled Labour No 320.20

3 Unskilled Labour No. 312.20

Comparision of WPI Index of basic Raw Materials


Sr No Particulars 2012-13 2019-20
1 Pig Iron 96.50 113.80

2 HR Coil 102.80 117.20

3 Copper Wire
104.70 107.70
4 Basic Metal & Alloys
104.60 109.50
Stainless Steel &
5
Alloys 93.90 92.80
6 Aluminium
108.60 112.00
7 Wire Rod
105.30 110.70
8 Fuel & Power
106.70 98.00
9 Electricity (Industry)
101.30 105.40

Comparision of Rates of Fuels


Sr No Particulars 2012-13 2019-20
1 Petrol
64.00 70.00
2 High Speed Diesel
49.69 68.85
Gujarat Water Supply and Sewerage Board
Jalseva Bhavan,Sector-10A,Gandhinagar
SCHEDULE OF RATES : ELECTRO - MECHANICAL
YEAR : 2019-20
INDEX
Section Details Page No.
"A" Section A Drilling of bore Section
1 Drilling of bore hole in Alluvial starta by Direct Rotary rig. 1
2 Drilling of bore hole by DTH rig 2
3 Drilling of bore hole by DTH rig in Rocky formation 4
4 Drilling of 115 mm dia DTH bore by Inwell rig in hilly area of all district . 10
5 Electrologger 10
6 Air Compressor 10
7 Pumping test of Tubewell 11
8 Hydrofracturing 11
9 Geohydrological ground water investigations 12
10 Charges for attending the Bore hole 13
11 Bore Blasting 14
12 Supply of Clay Balls 14
13 Supply of well sorted Sevalia Gravel 14
14 Supply of Cement 14
Annexure - A/A-1
17 Groupwise approved rate for Drilling (Unit Rate) for the year 2018-19. 15
Annexure - B-1/B-2/B-3
18 Approved rate for Drilling 165/200 mm dia DTH bore for SOR for the year 2018-19. 18-20

"B" Section B MATERIAL SECTION


1 M.S. Clamp 21
2 M.S. Bore Plug 21
3 M.S. Reducer 22
4 M.S./ uPVC Bail Plug 22
5 Steel bent Plate suitable to ERW pipe 22
6 Medium/Heavy duty M.S. Coupling 23
7 ISI marked ERW M.S. pipes 23
8 ISI marked Extra Deepwell Handpumps set 24
9 Hand Pump Spares 24
Trapezoidal shape ( ' V ') wire wound low carbon, Galvanized screen pipe and Stainless Steel
10 Screen pipes 26
11 uPVC Pipe Casing 27
12 Mild Steel Cabin 27
13 Pre-fabricated Portable Concrete mini Panel 27
14 H.D.P.E. Pipes 28
15 uPVC Column Pipe, Standard & Heavy Duty 28
16 Fire Hose Pipe 30
17 RO System 30
18 GI Fittings 30
19 RCC Pipes 30
"C" Section C LABOUR SECTION
1 Gas Cutting of M.S./ G.I. Pipes 31
2 Job work of Slotting of M.S. ERW Pipe 31
3 Facing of M.S./G.I. Pipes 31
4 Installation of India mark-II Hand Pump 32
5 Annual Overhauling, Breakdown repairs of Indian Mark-II Hand Pump 33
6 Jacking of Pipes from failed Tube Well 33
7 Loading of Hand Pump assembly/Pipes/Screens 34
8 Hiring of LCV - Medium 36
9 Hiring of LCV - Small 36
10 Hiring of Inspection Vehicle 37
11 Hiring of D.G. Sets 37

"D" Section D ELECTRICAL SECTION (As per Electrical SOR of R&B Department)
1 Wiring
1.1 Point wiring in Copper (TISSINO) 39
1.2 Point wiring in Copper (Modular) 40
1.3 Conduits & Pipes 45
1.4 Mains & Wires 47
1.5 Concealed Boxes & Laminated Sheets 50
1.6 Wiring Accessories 50
1.7 LADDERS 52
2 Lamps & Fittings
2.1 LED Lamp & Tubes 53
2.2 LED Light fixture 53
2.3 Industrial Lighting 54
2.4 Landscape Lighting 54
2.5 Flourocent tubes 54
2.6 Street Lighting & Solar Lighting 54
3 Switchgears & Distribution Boards
3.1 Busbar chambers 54
3.2 Panel mounting busbars 55
3.3 Earth Leakage circuit breaker 55
3.4 Danger Notice Boards 57
3.5 Earthing 57
3.6 Metallic Enclosure 58
4 Substation Equipment & Maintenance
4.1 Substation Equipment & Maintenance 60
4.2 Substation Equipment 60
4.4 Substation Maintenance 61
5 Substation Equipment & Maintenance
5.1 Repairing of Mono Bloc Motors 64
4.2 Repairing of open well Horizontal Mono Pumpsets 64
4.4 Repairing of submersible pumpsets 65
"E" Section E ELECTRO - MECHANICAL SECTION
1 3ph Bore-well Submersible Pumps 67
2 Control Panel Board 68
3 PVC insulated flat / round submersible copper cables 69
4A Supply of monobloc pump 3 phase
Casing: CI-FG260, Impeller : Bronze & Shaft : SS:410 69
4B Monoblock pump 3 phase
Casing: CI-FG260, Impeller : SS-CF8M & Shaft : SS:410 69
5 Monoset sub. pump 3 phase
Casing: CI-FG260, Impeller : Bronze & Shaft : SS:410 70
6 Single phase sub pump motor set
Casing: CI-FG260, Impeller : Bronze & Shaft : SS:410 70
7A Labour Charge for fishing out Sub pump set in tubewell 71
7B Labour Charge for fishing out struck up Sub pump set from bore 71
8 Vaccum Pumpset 72
9 Drain Pumpset 72
10 Portable Diesel Driven Self Priming Horizontal Pump (Dewatering set) 72
11 HSCF Pumps 72
12 End Suction Back Pullout Pump 72
13 V.T Pumps Water Lubricated 73
14 Expansion Bellows 73
15 Sewage Nonclog,End Suction type Horizontal centrifugal Pump 77
16 Sewage Nonclog,End Suction type Vertical centrifugal Pump 77
17 Polder type submersible Pump 77
18 Submersible sewage Non-clog Vertical Pump 78
19 11 KV Double / Four Pole Structure Assembly 78
20 Transformer 79
21 Microprocessor Based LV Variable Frequency Drive 83
22 Microprocessor Based LV Soft Starter 83
23 1.1 kV Grade Cable- Aluminium / Copper Conductor 84
24 11 kV (Earthed / Unearthed) Grade Cable- Aluminium Conductor 87
25 6.6 kV (Earthed/ Unearthed) Grade Cable- Aluminium Conductor 87
26 3.3 kV (Earthed/ Unearthed) Grade Cable- Aluminium Conductor 88
27 Cable Terminals (Lugs) 88
28 Cable Glands 91
29 Cable Terminations / Jointing Kits for 1.1kV grade PVC/ XLPE Cable 92
30 Cable Termina ons / Join ng Kits for 3.3 kV (E/UE) / 6.6 kV (E) XLPE Cable 93
31 Cable Termina ons / Join ng Kits for 6.6 kV (UE) / 11 kV (E) grade XLPE Cable 93
32 Cable Terminations / Jointing Kits for 11 kV (UE) grade XLPE Cable 94
33 415V LV Induction Motor 94
34 LT Power Capacitor 104
35 Cable Trays & Accessories 104
36 Rate per KW for comprehensive work of S.I.T.C 106
37 Single Girder crane (H.O.T & E.O.T. Type) 107
38 Double Girder Crane (H.O.T & E.O.T. Type) 108
39 Chain Pulley Block 108
40 LV APFC Panel 108
41 LV MCC Panel with DOL / Star Delta / ATS / Micro processorbased so starter 109
42 HV VCB Switchgear Panel 112
43 Solar System 114
44 Submerged centrifugal pumpsets 115
45 LV Power Control Centre (PCC) 115
46 HFSR (Harmonic Free Series Reactor) soft starter 124
47 Flux Compensated Magnetic Amplifier (FCMA) Soft Starter 126
48 11kV Ring Main Unit (RMU) 128
49 Servo Controlled Automatic Voltage Stabilizer 129
"F" Section F INSTRUMENTATION SECTION
1 Full Bore Electromagnetic Flow Meter- Inbuilt Battery Power operated 131
2 Full Bore Electromagnetic Flow Meter- Regular Power operated 131
3 Insertion Type Ultrasonic Flow Meter 133
4 Clamp On Ultrasonic Flow Meter- Fixed Type 133
5 Clamp On Ultrasonic Flow Meter- Portable Type 134
6 Acoustic Doppler Type Flow Meter- Regular Power Operated 134
7 Water Meters (Multijet/ Woltman Type) 134
8 Water Meters (Woltman Type) 136
9 Bulk Water Meters (Ultrasonic)/ Full Bore Inline Ultrasonic Flow Meter 137
10 Pressure & Vacuum Gauges with Accessories 138
11 Pressure Transmitter 139
12 Float & Board Type Level Indicator 139
13 Float/ Displacer Type Level Switch 140
14 Ultrasonic Level Transmitter 140
"G" Section G TECHNICAL SUPPORT SECTION 141-163
"H" Section H DRAWINGS 164-166
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Item 1: Drilling of Tubewell by direct rotary rig in alluvial starta

Drilling of Pilot bore hole in


300/250
1.1 Alluvial strata by direct Rotary Mtr. As per attached Annexure-A
mm
rig.
400 mm mtr
Reaming of 250/300 pilot bore
hole including Assembling, 450 mm mtr
1.2 lowering housing casing, strainer 550 mm mtr As per attached Annexure-A
pipes, gravel packing, clay
packing etc. 600 mm mtr

300 mm
Drilling of bore hole by Mini DR 416.15
Zone -I
rig including lowering of pipe
assembly, Gravel packing clay 300 mm
1.3 Mtr. 594.79
packing and development of bore Zone -II
hole by washing. (For installation
of Hand pump/Power pump) 300 mm
594.79
Zone -III

Lowering and removing of 100


mm dia dropline and 32 mm dia
airline for development of each
water bearing Zones come
across up to full depth of Deep
tubewell of size 200 mm/250
1.4 mm/300 mm dia for the tubewell Job Mtr As per attached Annexure-A
having depth 186 Mtr. and above
through suitable air compressor.
The job is for complete period of
development of tubewell.
(Without charges for air
compressor.)

Page 1 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Lowering and removing of 100


mm dia dropline and 32 mm dia
airline for development of each
water bearing Zones come
across up to full depth of Deep
tubewell of size 200 mm/250
mm/300 mm dia for the tubewell
upto 185 Mtr. deep through
1.4.1 suitable air compressor. The job Job Mtr. As per attached Annexure-A
is for complete period of
development. (Where water level
is very deep and 2/3rd
submersion is not achived.) *
All the required accessories,
machineries etc for above job
will have to be provided by
contractors.

Cement sealing if necessary


1.5 without cost of cement by means L.S As per attached Annexure-A
of mud pump.

Item 2: Drill of borehole by DTH Rig.

Zone I - Drilling of bore hole by


DTH Rig As per attached annexure-
2.1 165 mm Mtr.
(a) 0 to 100 mtr B1
(b) 100 to 150 mtr

Zone-II - Drilling of bore hole by As per attached annexure-


2.2 165 mm Mtr.
DTH Rig B2

Page 2 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Drilling of 165 mm dia DTH For Zone-III Rajkot and Zone IV Junagadh

Drilling of 165mm dia by DTH Rig


in Rocky Formation in all
2.3 districts of Zone-III(Except 211.50
Surendranagar District.)
0 to 150 mtr. deep

2.3.1 151 to 225 mtr. deep 261.86

2.3.2 226 to 300 mtr. 283.26

Drilling of 165mm dia by DTH Rig


in Sand Stone Formation in
2.4 Morbi, Tankar & Wakaner Talukas 201.53
of Rajkot District.
0 to 150 mtr. deep

2.4.1 151 to 225 mtr. deep 249.38

Drilling of 165mm dia X 120 Mtr


2.5 deep bore by DTH Rig in Clay 546.00
Formation All Taluka of Zone-III

Drilling of 165mm dia X 120 Mtr


deep bore by DTH Rig in Soft /
Hard Rock Formation in
2.6 Vadhavan, Halvad, Muli, Patdi, 319.00
Dhrangadhra Lakhtar Limdi
Chuda Taluka of Surendranagar
District.

Drilling of 165mm dia X 225 Mtr


deep bore by DTH Rig in Soft /
2.7 Hard Rock Formation in Sayala 232.00
and Chotila Taluka of
Surendranagar District.

Page 3 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Drilling of 200/215MM Dia bore


hole in over burden rocky or
loose collapsible/boulder strata
200/215
& lowering of 175/200mm dia
2.8 mm Mtr. 370.72
UPVC/PVC/ERW casing pipe
above 12mtr upto 40 Mtr depth by
DTH Rig etc. complete.
For Zone-I

Item No. 3

Drilling of bore hole by DTH Rig


As per attached annexure-
3.1 in rocky formation in All Taluka 200 mm Mtr.
B3
of Zone- II

Drilling of bore hole by DTH Rig


in rocky formation in All Taluka
3.2 200 mm Mtr. 435.00
of all district of Zone-3
up to 350 mtr.

Drilling of bore hole by DTH Rig


in Sand Stone formation in All
3.3 200mm Mtr. 353.00
Taluka of Zone-III (Except
Surendranagar Dist)

Drilling of bore hole by DTH Rig


in Soft/Hard rock Area in All
3.4 200mm Mtr. 453.00
Taluka of Surendranagar district
& Halvad taluka of Morbi District

Page 4 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Drilling of min. 250 mm dia. bore


hole in all strata including dual
over burden strata by
combination DR/DTH rig 250/200
3.5 Mtr. 1127.00
including lowering 200 mm dia mm
MS ERW pipes in bore hole as
as suggested by Hydrologist
(Except- Surendranagar Dist)

Drilling of min. 325 mm dia. bore


hole in all strata including dual
over burden strata by
combination DR/DTH rig 325/250
3.6 1327.00
including lowering 250 mm dia mm
MS ERW pipes in bore hole as
as suggested by Hydrologist
(Except- Surendranagar Dist)

Drilling of 450mm dia. bore hole


in alluvial, boulder etc. all strata
including lowering of pipe
assembly, bottom sealing, Gravel
packing, clay packing ,
development of bore hole by
3.7 450/165 MM Mtr. 1433.00
washing and Air compressor &
further drilling of 165 mm dia.
bore hole in rocky strata etc.
complete by D.R. & D.T.H. Rig as
suggested by Hydrologist in
Zone-I & II

Drilling of 250 mm dia. DTH Bore


hole in Soft Rock (Sand Stone
3.8 formation )for all districts & 250mm Mtr. 425.60
talukas of Saurashtra having
sand stone formation.

Page 5 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Drilling of DTH Bore hole in


3.9 Rocky formation for all districts
& talukas of Kutch

3.9.1 Soft Rock 250mm mtr. 554.00

3.9.2 Hard Rock 200 mm mtr. 554.00

3.9.3 Hard Rock 250 mm mtr. 620.48

Drilling of different dia bore by


3.10 DTH/ Combi. Rig in all districts
under Zone-V Junagadh

Drilling of 200/215 mm dia bore


hole in overburden strata by DTH
Rig up to required depth
including fixing of 175/180 dia
ERW/ PVC pipes & further drilling
of 165 mm dia bore hole in hard
3.10(A) rock (trap etc.) strata by DTH
drilling method up to total depth
of 300 mtr inl. measuring the
yield by V notch and flushing of
bore etc. complete in all districts
of Zone-V.
(Casing up to 12 Mts.)

Page 6 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

3.10.A-1 0 to 150 mtr. deep mtr. 236.88

3.10.A-2 151 to 225 mtr. deep 165mm mtr. 293.28

3.10.A-3 226 to 300 mtr. mtr. 317.25

Drilling of 200/215 mm dia bore


hole in overburden strata by DTH
Rig up to required depth
including fixing of 175/180 dia
ERW/ PVC pipes & further drilling
of 165 mm dia bore hole in hard
rock (trap etc.) strata by DTH
drilling method up to total depth
of 300 mtr inl. measuring the
yield by V notch and flushing of
3.10(B)
bore etc. complete in all districts
of Zone-V.
(Casing up to 12 Mts.) In case of
Lowering of casing more than 12
mtrs. an upto require depth the
rate will be considered as per
item 3.10-B-1 otherwise less than
12 mtr. casing it will be
considered as per item No.
3.10.B-2

3.10.B-1 0 to 60 mtr. deep mtr. 370.72

3.10.B-2 61 to 150 mtr. deep mtr. 236.88


165mm
3.10.B-3 151 to 225 mtr. deep mtr. 293.28

3.10.B-4 226 to 300 mtr. mtr. 317.25

Page 7 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Drilling of 300/315 mm dia bore in


over burden strata including
lowering of 204mm dia uPVC
225/250mm dia PVC/MS casing
pipes up to required depth and
further drilling of 200mm dia
borehole in all types of Rocky
3.10(C) strata, Soft Rock & Hard Rock
Strata formation by DTH Rig
including flushing of bore hole
by air compressor and
measuring of yield of bore by V 200 mm
notch and fixing of bore cap etc.
components.
(Over burden upto 12.0m)

3.10.C-1 0 to 350 mtr. deep mtr. 487.20

3.10.C-2 351 to 400 mtr. deep mtr. 861.91

3.10.C-3 401 to 450 mtr. deep mtr. 1036.46

3.10.C-4 451 to 500 mtr. mtr. 1352.86

Page 8 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Drilling of 300/315 mm dia bore in


all strata including dual over
burden strata by combination
DR/DTH rig including lowering of
204mm dia uPVC 225/250mm dia
PVC/MS casing pipes up to
required depth and further
drilling of 200mm dia borehole in
all types of Alluvial Rocky strata
formation by DTH Rig including
3.10(D) 200 mm
flushing of bore hole by air
compressor and measuring of
yield of bore by V notch and
fixing of bore cap etc.
components. Rates for item No.
3.10-E-1 is applicable mote than
12 mtr. coming only otherwise
less than 12 mtr casing it will be
considered as per item No. 3.10-
E-2

0 to 120 mtr. Deep (alluvial


3.10.D-1 mtr. 1262.24
Strata)

3.10.D-2 121 to 350 mtr. deep mtr. 487.20

Page 9 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Drilling of 215 mm dia bore hole


in overburden strata (alternate
layers of lime stone & yellow
sticky clay formation) by DTH Rig
up to required depth (Approx. up
to 70 mtr) including fixing of
175/180 dia ERW/ PVC pipes
(blank and slotted) & if required
3.11 165 MM Mtr. 611.52
further drilling of 165 mm dia
bore hole in hard rock (trap etc.)
strata by DTH drilling method up
to total depth of 120 mtr
incl.measuring the yield by V
notch and flushing of bore
etc.complete in the Coastal area
of saurastra.

Item No. 4

Drilling of 115 mm dia DTH bore


by Inwell rig in hilly area of all 115 mm Mtr 340.48
district .

Item No. 5

(A)For Dept.work - For


Kachh area- Rs15000/- per
job for other area Rs.12000/-
per job
Electrologger charges (With
_ Hr.
carting) (B) For other dept. and
private work -For Kachh
area- Rs. 21000/- per job for
other area Rs.18000/- per
job

Item No. 6 : Air Compressor

Page 10 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

6.1 400 CFM/100 PSI _ Hr. 2537.50

6.2 600 CFM/150 PSI _ Hr. 3633.70

6.3 900 CFM/200 PSI _ Hr. 7853.75

6.4 1100 CFM/300 PSI _ Hr. 9815.75

Item No. 7 : Pump Test

For first 8 Hours


Pumping test of the tubewell by with Max. upto 20 16500.00
sub. Pump of adequate capacity HP Sub.Pump
A in all districts utilised.
A) 150/200/250 mm DTH bore
pump set.
thereafter Rs./Hr. 720.00

D.R. Bore pump test with D.G.


B _
Set

1st 24hr up to 30 HP _ L.S. 27500.00

There after Rs/Hr _ Hr. 900.00

1st 24hr 31 to 70 HP _ L.S. 34400.00

There after Rs/Hr _ Hr. 1200.00

1st 24hr morethan 70 HP _ L.S. 42775.00

There after Rs/Hr _ Hr. 1515.00

Item No. 8 : Hydro-fracturing

Page 11 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Hydrofracturing of 115mm dia


low discharge existing DTH
BoreHole at different depth as
per geology (Maximum up to
90.00 Mtr.) with single packer
unit by high pressure water
8.1 115mm Job 9500.00
jetting pump for duration of
minimum 15 minutes and
flushing of bore including
measuring the yield by Hand
Pump or single phase sub. pump
set.

Hydrofracturing of 165mm dia


low discharge existing DTH
BoreHole at different depth as
per geology (Maximum up to
120.00 Mtr.) with single packer
8.2 165mm Job 14100.00
unit by high pressure water
jetting pump for duration of
minimum 15 minutes including
Pre and Post fracture, Pump
Testing by sub. pump set.

Item No. 9 : Geo-hydrological Ground Water Investigation

Geohydrological ground water


investigations.(With vehicle
charges)
9.1 i) 100mm/ 165mm / 200mm dia _
DTH Bore Bore 3000.00
ii) 200/250mm dia Deep tubewell
(with water sample) Bore 12000.00

Page 12 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Geophysical & Geohydrological


ground water investigations for
9.2 _ Bore 15000.00
finalisation of one pin point (With
vehicle charges)

Charges for attending the Bore


hole and Taking necessary
measurements & giving opinions
for the depth and kind of filling
10 Materials and Opinion about
cleaning of Bore hole for
cleaning of bore with necessary
tools and tackels.(without lifting
& lowering of pump).

Minimum Charge within 50 KM L.S. 2500.00

From 51 KM to 100 KM L.S. 4000.00

Cleaning of bore hole by sand


barrel system including removing
_ Mtr. 150.00
foreign materials sand, clay,
pebbles etc. with necessory
tools, plants and accessories .

Page 13 of 166
SOR Mech 2019-20
SECTION - "A"
Rate approved for the year
2019-20
Sr. No Description of Item Size Unit
Work to be carried out by
private agency

Bore blasting:-Bore blasting to


the 165 mm dia DTH bore up to
required depth from 15 Mtr to 25
Mtr of required no of bores ( 5 to Job
6 Nos ) by using required ( for
quantity of slurry explossive two
11 _ 17660.00
class -II required blast material Blast)
such as detonetor blasting per
cap,fuse ,wire including well bore
equipement,safety device etc
complete ( for two Blast per bore
)

Supply of Clay ball of size 25mm


to 50mm from Stickly Clay at site
12 _ Cmt
of work. ( As certified by
As per attached annexure-A
Hydrologist).

Supply of Best quality of well


13 sorted Sevaliya gravel of size _ Cmt
4mm to 6mm. As per attached annexure-A

14 Supply of Cement. _ M.Ton


As per attached annexure-A

Page 14 of 166
SOR Mech 2019-20
SECTION - "A"

Annexure - A
Statement showing the details of Approved rate for the Drillng by DR Rig. For the year 2019-2020

Lowering of drop line above 186


Lowering of drop line up to 186

Air Compressor 1100 CFM /300

Sealing of Existing Tubewell by


Air Compressor 600 CFM /150

Air Compressor 900 CFM /200


Pilot 300/250mm drilling

Supply of Clay ball

Supply of Cement
400mm reaming

450mm reaming

Supply of Gravel
550mm reaming

600mm reaming

Cement sealing

Bottom sealing
Schedule No

Sticky Clay
Group

mtr

mtr

PSI

PSI

PSI
District Talukas
Unit Mtr Mtr Mtr Mtr Mtr Cmt Cmt M.Ton Job Job Mtr. Job. LS. LS. LS. Mtr.

1 A Gandhinagar Dehgam up to 300 mtr 671 206 311 413 568 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

Vijapur, Kheralu. Vadnagar,


2 A Mehsana 620 191 288 380 523 701 1894 5882 12388 6217 130 24122 20725 25508 32351 92
Satlasna upto 300 mtr.

Palanpur, Vedgam,
3 A Banaskanth Dhanera, Dantiwada up to 628 193 291 386 531 701 1894 5882 12388 6217 128 23915 20725 25508 32351 92
300 mtr
Alluviun Area Complete up
4 A Kheda 671 206 311 413 568 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr

Alluviun Area Complete up


5 A Anand 671 206 311 413 568 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr

6 A Ahmedabad Dascrol up to 300 mtr 622 190 289 384 527 701 1894 5882 12388 6217 132 24592 20725 25508 32351 92

Dasada,Lakhatar taluka up
7 A Surendranagar 671 206 311 413 568 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr
Mandvi, Naliya, Mundra up
8 A Kutch 713 220 330 440 602 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr
Alluviun Area Complete up
9 B Surat 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr
Alluviun Area Complete up
10 B Bharuch 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr
Alluviun Area Complete up
11 B Navsari 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr

Page 15 of 166
SOR Mech 2019-20
SECTION - "A"
Alluviun Area Complete up
12 B Valsad 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr
Alluviun Area Complete up
13 B Baroda 863 264 397 534 886 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr
Bayad, Talod, Dhansura up
14 B Sabarkantha 863 264 397 534 886 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr

15 B Panchmahal Kalol, Halol up to 300 mtr 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

Coastal area complete up to


16 B Saurashtra 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
300 mtr

17 B Amreli Chalala upto 300 mtr 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

Sihor, Savarkunda upto 300


18 B Bhavnagar 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
mtr

19 B Rajkot Maliya upto 300 mtr 863 264 397 534 886 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

20 B Junagadh Vanthali upto 300 mtr. 768 234 354 475.2 789.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

21 C Sabarkantha Himatnagar up to 300 mtr 1223 0 588 751 1033 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

Halvad,Dhangadhra,Muli,Wa
22 C Surendranagar dhavan,Chotila,Limadi,Sayal 1223 0 588 751 1033 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
a taluka up to 300 mtr

Morbi, Wankaner up to 300


23 C Rajkot 1223 0 588 751 1033 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
mtr
Bhachau, Anjar, Bhuj,
24 C Kutch Nakhatrana, Rapar up to 1117 0 536.4 686.4 945.6 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
300 mtr

25 D Sabarkantha Prantij. up to 300 mtr 539 167 250 330 458 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

City, Bavla, Dholka, Sanand.


26 D Ahmedabad 533 164 246 325 454 701 1894 5882 12388 6217 132 24592 20725 25508 32351 92
up to 300 mtr
Bhabhar,Kankrej,Deodar,De
27 D Banaskantha esa,Lakhani taluka up to 538 164 250 330 456 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
300 mtr

28 D Patan Vagdod up to 300 mtr 509 154 235 310 431 701 1894 5882 12388 6217 130 24122 20725 25508 32351 92

Page 16 of 166
SOR Mech 2019-20
SECTION - "A"
Gandhinagar, Kalol up to
29 D Gandhinagar 509 154 235 310 431 701 1894 5882 12388 6217 130 24122 20725 25508 32351 92
300 mtr

30 D Mehsana Visnagar up to 300 mtr 522 157 241 318 442 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92

Detroj, Mandal, Viramgam


31 E Ahmedabad 533 164 246 325 454 701 1894 5882 12388 6217 132 24592 20725 25508 32351 92
up to 300 mtr

Mehsana,Kadi,Becharaji,Unj
32 E Mehsana ha,Gojarya,Jotana taluka 504 154 234 308 428 701 1894 5882 12388 6217 131 24331 20725 25508 32351 92
up to 300 mtr
Patan,Chanasma,Saraswati,
33 E Patan Siddhapur taluka up to 300 512 156 236 312 434 701 1894 5882 12388 6217 131 24331 20725 25508 32351 92
mtr

34 E Gandhinagar Mansa up to 300 mtr 505 154 233 308 428 701 1894 5882 12388 6217 130 24122 20725 25508 32351 92

Vav, Tharad,& Suigam up


35 E Banaskantha 575 167 265 349 486 701 1894 5882 12388 6217 133 24888 20725 25508 32351 92
to 300 mtr

Sami, Harij, Radhanpur.


36 F Patan Santalpur & Sankheshwar 638 196 292 392 544 701 1894 5882 12388 6217 128 23915 20725 25508 32351 92
up to 300 mtr
Bhabhar,Kankrej,Deodar,De
37 D Banaskantha esa,Lakhani taluka Above 583 179 270 359 496 701 1894 5882 12388 6217 0 26051 0 0 32351 103
300 mtr
Detroj, Mandal, Viramgam
38 E Ahmedabad 586 180 270 359 497 701 1894 5882 12388 6217 0 26051 0 0 32351 103
Above 300 mtr

Mehsana,Kadi,Becharaji,Unj
39 E Mehsana ha,Gojarya,Jotana taluka 559 172 256 342 475 701 1894 5882 12388 6217 0 26051 0 0 32351 103
Above 300 mtr
Patan,Chanasma,Saraswati,
40 E Patan Siddhapur taluka Above 569 173 263 348 484 701 1894 5882 12388 6217 0 26051 0 0 32351 103
300 mtr

Vav, Tharad,Suigam Above


41 E Banaskantha 623 180 288 379 528 701 1894 5882 12388 6217 0 26051 0 0 32351 103
300 mtr

Sami,Harij,Radhanpur,Santa
42 F Patan lpur,Sankheshwar Above 721 222 330 443 613 701 1894 5882 12388 6217 0 26051 0 0 32351 103
300 mtr

Page 17 of 166
SOR Mech 2019-20
SECTION - "A"

Annexure-B1
Approved Drilling of 165mm dia DTH SOR Rate 2019-20 For Zone-1
Approved
Sr. No.

Group

District Taluka Rate for SOR


2019-20
1 A Dahod Devgadhbaria,Dhanpur 274.40
2 B Dahod Limkheda 314.72
3 C Dahod Dahod,Jhalod,Fatepura,Garbada 245.28
4 A P'Mahal Halol,Jambugoda 312.48
5 B P'Mahal Goghamba 282.15
6 C P'Mahal Kalol 299.61
7 D P'Mahal Godhara 268.80
8 E P'Mahal Morva(Hadaf), 280.36
9 F P'Mahal Shahera 271.93
10 A Mahisagar Santarampur,Kadana 225.95
11 B Mahisagar Khanpur Lunavada 342.72
12 C Mahisagar Virpor & Balasinor 306.88
13 A Vadodara All Taluka 268.80
14 A C'Udepur All Taluka Except C'Udepur & Jetpurpavi 268.80
15 B C'Udepur Chhotaudepur & Jetpurpavi 312.48
16 C Surat Mandavi,Mangrol,Umarpada 222.88
17 C1 Surat Mahuva,Bardoli, Kamrej 246.08
18 D Tapi Songadh,Nizaar,Uchchhal 212.93
19 D1 Tapi Vyara,Valod 205.30
20 B Bharuch All Taluka 273.28
21 A Narmada Dediyapada & Sagbara 231.99
22 A1 Narmada Nadod & Tilakvada 328.00
23 B Dang All Taluka 243.26
24 A Navsari All Taluka 194.00
25 B Valsad Dharampur,Kaprada 243.66
26 C Valsad Valsad,Paradi,Vapi 235.83
27 C1 Valsad Umargham 248.94

Page 18 of 166
SOR Mech 2019-20
SECTION - "A"

Annexure-B2
Item No.2.2 for Zone-2
Approved Rate for Drilling of 165mm dia DTH for 2019-20

Rate approved
Sr.No District Taluka Unit for the year
2019-20

PART-I 165 mm dia DTH bore

Ahmedabad All Taluka

Group-I Banaskantha Except Danta,Amirghadh taluka Mtr 357.28

Mehsana Except Vadnagar,Satlasana,Kheralu taluka.


Himmatnagar, Prantij, Talod, Vijaynagar Taluka.
Sabarkantha
Group-II Aravalli - Modasa, Bhiloda, Meghraj, Malpur, Bayad, Dhansura Mtr 299.04
& Aravalli
Taluka
Group-IIISabarkantha Khedbrahma,Vadali ,Idar taluka Mtr 360.64

Banaskantha Danta & Amirgadh taluka


Group-IV Mtr 379.68
Mehsana Vadnagar,Satlasan,Kheralu taluka

Group-V Kheda All Taluka Mtr 309.63

Page 19 of 166
SOR Mech 2019-20
SECTION - "A"

Annexure-B3
Item No.3.1 For Zone-2
Approved Rate for Drilling of 200mm dia DTH for 2019-20

Rate approved
Sr.No District Taluka Unit for the year
2019-20

PART-II 200 mm dia DTH bore


Ahmedabad All Taluka

Sabarkantha Except Khedbrahma,Idar,Vadali & Poshina taluka


Group-I Mtr 507.36
Banaskantha Except Danta,Amirghadh taluka

Mehsana Except Vadnagar,Satlasana,Kheralu taluka.

Group II Sabarkantha Khedbrahma,Poshina,Vadali ,Idar taluka Mtr 585.76

Banaskantha Danta & Amirgadh taluka Mtr


Group-III 536.48
Mehsana Vadnagar,Satlasan,Kheralu taluka Mtr

Page 20 of 166
SOR Mech 2019-20
SECTION- B

SECTION- B (MATERIAL SECTION)

Approved Rate
Sr. No. Description of Item Unit
for 2019-20

Clamp made from M.S. plate with 3 holes on either side with
1
nuts & bolts of Std. Make and suitable size.

450 mm X 50 mm X 10 mm flat suitable to 32 mm


a) per pair 353
dia. Pipe.

450 mm X 65 mm X 10 mm flat suitable to 50 mm


b) per pair 534
dia.Pipe.

450 mm X 65 mm X 10 mm flat suitable to 65/80 mm


c) per pair 542
dia.Pipe.

450 mm X 65 mm X 10 mm flat suitable to 100/125


d) per pair 654
mm dia.Pipe.

750 mm X 75 mm X 10 mm flat suitable to 150 mm


e) per pair 1053
dia.Pipe.

750 mm X 75 mm X 10 mm flat suitable to 175 mm


f) per pair 1065
dia.Pipe for Pipe lowering purpose.

g) 750 mm X 75 mm X 16 mm flat to 200 mm dia.Pipe. per pair 1550

900 mm X 100 mm X 16 mm flat suitable for 250 mm


h) per pair 1922
dia.Pipe.

900 mm X 100 mm X 16 mm flat suitable for 300 mm


I) per pair 2157
dia.Pipe.

Bore plug having 100 mm height made from M.S. plate with 3
holes at equal distance on circumference for nut-bolts type,
2
locking arrangement with nuts-bolts & lock nuts of std. Make
complete.

A From 3 mm thick M.S. Plate (For top also.)

i Suitable for 100 mm dia pipe. No. 296

ii Suitable for 125 mm dia pipe. No. 336

iii Suitable for 150 mm dia pipe. No. 434

B From 5 thick M.S. Plate (For Top also)

S.O.R. Mech 2019-20


Page 21 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20

i Suitable for 175 mm dia pipe. No. 624

ii Suitable for 200 mm dia pipe. No. 738

iii Suitable for 250 mm dia pipe. No. 1095

Bore plug having 100mm height made from UPVC of


C
std. make

i Suitable for 125 mm dia pipe. No. 259

ii Suitable for 200 mm dia pipe. No. 525

Reducer made from 6 mm thick plate (M.S.) for ERW pipes


3
of size as below.

i) 150mm dia X 200 mm dia. X 600 mm length No. 1381

ii) 200mm dia X 250 mm dia. X 600 mm length. No. 1777

M.S. Bail plug having length 0.45 mtr from medium class pipe
4-A
as per I.S.S. suitable for

a) 150 mm dia pipe. No. 631

b) 200 mm dia pipe. No. 802

c) 250 mm dia pipe. No. 1004

d) 300 mm dia pipe. No. 1175

4-B Supply of UPVC Bail plug (Bottom Cap) Suitable for

i Suitable for 125 mm dia pipe. No. 282

ii Suitable for 200 mm dia pipe. No. 585

5 Steel bent plate suitable to ERW pipe as detailed below

S.O.R. Mech 2019-20


Page 22 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20

ERW Pipe Size in mm.

a) 150 mm dia 125 X 100 X 5 No. 32

b) 200 mm dia. 150 X 150 X 6 No. 63

c) 250 mm dia 200 X 150 X 6 No. 86

d) 300 mm dia 200 X 150 X 6 No. 86

Medium duty M.S. Coupling as per I.S. specification of


a)
following size.

i) 100 mm dia. No. 432

6
ii) 125 mm dia. No. 522

iii) 300 mm dia. No. 1652

Medium Duty 'B' class G.I. coupling as per I.S. 1239


b) )Part - II)/1990. --- No. 23
32 mm dia

Heavy duty M.S. Coupling (8 mm thickness, 100 mm


c)
length, 8 TPI thread as per IS)

i) 50mm dia 6mm Thick, 100mm Long No. 94

ii) 65mm dia 8mm Thick, 125mm Long No. 197

iii) 80mm dia 8mm Thick, 125mm Long No. 236

iv) 100mm dia 8mm Thick, 150mm Long No. 345

v) 125mm dia 8mm Thick, 150mm Long No. 417

vi) 150mm dia 8mm Thick, 150mm Long No. 502

Manufacture, supply and delivery of ISI marked ERW M.S.


7 pipes conforming to IS: 4270/2001 with latest amendment
Rates are exclusive of GST

a 200 mm dia ( Min 6.00 mm thick). Mtr. 1424

b 250 mm dia (Min.7.10 mm thickness) Mtr. 2112

S.O.R. Mech 2019-20


Page 23 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20
For Item No. 7: Above rates of Pipes are based on WPI Index(98.20) or HRC in month of (Aug-2017)

Manufacturing of ISI marked Deepwell Handpumps set (IS


15500/2004 or any latest ammendment/revision there of) and
supply & Delivery without riser pipes along with 12 Nos of
connecting rods confirming to IS 1573 with latest
amendment/revision.
Rates are exclusive of GST
8
a Normal Stand Assembly No. 5886

b Telescopic Stand Assembly No. 5900

Extra Deepwell Handpumps set with 30 Nos of


c No. 10545
connecting rods.
For Item No. 8 : Rates are taken as per RC Rates, approved in TPC-1 dated 19.12.2018.

Supply of Different Hand Pump Spares


9
Rates are exclusive of GST.

(A) SPARES FOR PUMP HEAD :


A-1 Hexa. Bolts M-12x1.75x40mm long with Hexa.Nut M-12x1.75
No. 4.96
& Washer 4mm thick
A-2
Hex. Bolt M10x1.50x40 mm long No. 2.30

A-3
Nylock Nut M10x1.50 No. 1.54

A-4
Handle Axle(Stainless Steel) No. 66.00

A-5
Washer (4 mm thick) for Handle Axle No. 1.15

A-6
Bearing (No.6204-Z) No. 24.67

A-7
Spacer(for pump Head) No. 3.80

A-8
Chain with Coupling No. 61.00

A-9
Bolt for front cover M-12x20 mm long No. 2.03

A-10
Pump Head Assly.Consi.of Item No.(1) to (7) as per Fig.3.1 No. 1634.00

(B) SPARES FOR CYLINDER

B-1
Pump Bucket No. 4.25

S.O.R. Mech 2019-20


Page 24 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20
B-2
Sealing Ring No. 2.75

B-3 Upper Valve Assly comp. consi.of item as per fig 3.6 A (Part
No. 286.00
no 1 to 4 & 8 to 9)
B-4 Lower Valve Assly comp.consi.of item as per fig 3.6 B (Part
No. 161.00
no 5 to 7 & 10)
(C)
WATER TANK consi.of item as per fig 3.6 B(1 to 6) No. 537.00

(D)
Cylinder With Brass Liner consi.of item (a) & (b) No. 292.00

(E)
REDUCER CAP No. 58.00

(F) SPARES FOR CONECTING RODS

F-1 Hexagonal Coupler M-12 x 1.75 x 50 mm No. 5.90

(G) UPPER VALVE SPARES.

G-1
Upper Valve Seating No. 1.40

G-2
Plunger Yoke Body No. 89.00

G-3
Bucket Spacer No. 69.00

G-4
Follower No. 83.90

G-5
Plunger Rod (S & S) No. 72.98

G-6
Upper Valve (Guide) No. 38.00

(H) LOWER VALVE SPARES

H-1 Check Valve Seat. No. 74.00

H-2 Check Valve. No. 53.00

H-3 Check Valve Seating. No. 2.10

H-4 Rubber Seat Retainer No. 29.30

S.O.R. Mech 2019-20


Page 25 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20

(I) Handle Bar consisting of Item no (1) & (3) as per Fig 4.6 No. 548.00

Cylinder Assly Comp.consisting of Item no (1) to (7) as per


(J) No. 920.00
Fig 3.5

Conn. Rod Electro Galva.consisting of Item no (1) to (3) as


(K) No. 138.00
per Fig 4.21

Special Tool Kit for I. M.-II Handpump consi. Item (1) to (11)
(L) No. 5580.00
as per IS 15500 Part-8 with tool box

Standerd Tool Kit for I. M.-II Handpump consi.Item(1) to (16)


M) No. 6290.00
as per IS 15500 Part-8 with tool box

(N) Third plate consisting of Item (1) & (2) as per fig 4.5 No. 126.60

(O) Spares for deep well Hand pump-Extra Deep

Cylinder Body with Brass Liner consisting of Item no (1) for


O-1 No. 438.00
body fig 5.2 & (2) for brass linear Fig 6.1 B

O-2 Handle Bar consisting of Item no (1) to (3) as per Fig 4.7 No. 1060.00

Upper Valve Assembly complete consisting of Item no (1) to


O-3 No. 475.00
(11) as per Fig 3.12

O-4 Follower as per Fig 6.7 No. 129.00

O-5 Bucket Spacer-Lower as per Fig 6.5 No. 69.00

For Item No. 9: Rates are taken as per RC Rates, approved in TPC-1 dated 10.05.2018.

Manufacture, supply and delivery of cage typeTrapezoidal


shape ( ' V ') wire wound low carbon, Galvanized screen pipe
10
and Stainless Steel Screen pipes, confirming IS: 8110
Rates are exclusive of GST.
Low carbon, Galvanized screen pipe
A) 125 mm dia. LIGHT
1) 1.00 mm Slot size Mtr. 753
2) 1.50 mm Slot size Mtr. 697
B) 200 mm dia. REGULAR

1) 1.00mm Slot size Mtr. 1240


2) 1.50mm Slot size Mtr. 1146
C) 250 mm dia REGULAR
1) 1.00mm Slot size Mtr. 1886
2) 1.50mm Slot size Mtr. 1747
D) 200 mm dia HEAVY
1) 1.00mm Slot size Mtr. 1475
2) 1.50mm Slot size Mtr. 1366
E) 250 mm dia HEAVY
1) 1.00mm Slot size Mtr. 2276
S.O.R. Mech 2019-20
Page 26 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20
2) 1.50mm Slot size Mtr. 2101
F) Stainless Steel Screen pipes.

1) 200 mm Dia 0.5 Slot size Mtr. 4075

2) 400 MM DIA Recharge pit screen 0.75 Slot size Mtr. 7786

3) 550 MM DIA Recharge pit screen 0.75 Slot size. Mtr. 10449

For Item No. 10: Rates are taken as per RC Rates, approved in TPC-1 dated 10.05.2018.

A) Manufacturing supply & delivery of ISI marked (IS 12818


11 with latest amendment ).
Rates are exclusive of GST

UPVC Casing pipe

a 125.00 mm nominal dia " CM " Type Mtr. 355

b 200.00 mm nominal dia " CM " Type Mtr. 891

c 175.00 mm nominal dia " CS " Type Mtr. 559

For Item No. 11: Rates are taken as per RC Rates, approved in TPC-1 dated 31.08.2018.
Above rates of Pipes are based on PVC Resin of RIL, Grade 67ER092
(Rs.90093/MT including GST @ 18%) in month of (March-2018)

Providing dust and vermin proof Mild Steel Cabin having two
compartment one for panel board and other for GEB meter
and fuse unit with required locking arrangement , minimum
degree of protection IP 52 as per IS 2147 fabricated from
CRCA sheer steel minimum thickness for base
frame/channel/gland plates for 3 mm for load bearing
12
members ,1.6 mm for ineternal members including
cutting,bending,drilling,welding, riveting with ineternal
partitions.The sheet steel enclosure shall be powder coated
as per applicable standard with shade as required with finish
thickness of paint film not less than 80 microns.The Cabin
have following dimension.

1 0.6 M X 0.7 M x 0.4 M UNIT 4800

2 1.5 M X 1.0 M x 0.6 M UNIT 19356

3 1.5 M X 1.25 M x 0.6 M UNIT 22292

Providing and fitting readymade prefabricated portable


concrete mini panel having outer size 110x50x190 cm with
13 10670
necessary fitting for electric panel mounting complete as per
detailed specification and drawing.

S.O.R. Mech 2019-20


Page 27 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20

Manufacture, Supply and delivery of following ISI marked


H.D.P.E. Pipes (IS:4984/1985 with latest amendment) having
material Grade PE-80 in approximate 100 mtr. Coil length or
as per GWSSB requirement with SS-316 Nipple at both end
having 11 TPI threading as per specification, press fitted and
bolted having nominal diameter as under as per detailed
Technical Specification. Rates are based on IOCL Resin A
Grade 45 GP 004DP44 as on dated 01.12.2017 Rs. 90284/-
(Without GST)
Rates are Exclusive of GST.

i) DN 32 PN-10 Mtr. 31
14
ii) DN 40 PN-10 Mtr. 48

iii) DN 50 PN-10 Mtr. 73

iv) DN 63 PN-10 Mtr. 113

v) DN 63 PN-12.5 Mtr. 131

vi) DN 63 PN-16 Mtr. 157

vii) DN 90 PN-10 Mtr. 227

viii) DN 90 PN-16 Mtr. 319

ix) DN 110 PN-10 Mtr. 341

For Item No. 14: Rates are taken as per RC Rates, approved in TPC-1 dated 10.05.2018.

15(A) UPVC Colmn Pipe. STANDRAD Duty Grade,175 mtrs,Head

Manufacture, Supply and Delivery of 50 mm Nominal


dia UPVC Column Pipes including PVC Socket
1 (Coupler), Density of Pipe 1.38 to 1.43 Gm per Cm3 Mtr. 157
OD : 59.50 TO 60.10 MM, Wall Thickness End : 6.10
mm to 7.9mm, Berral : 3.9mm to 5.0mm, Length: 3Mtrs.

Manufacture, Supply and Delivery of 50 mm size CI


2 Pipe Adaptor and Pump Adaptor for above 50 mm dia Set 376
column Pippe.

Manufacture, Supply and Delivery of 65 mm Nominal


dia UPVC Column Pipes including PVC Socket
3 (Coupler), Density of Pipe 1.38 to 1.43 Gm per Cm3 Mtr. 221
OD : 74.5 TO 75.2MM, Wall Thickness End : 9.0mm to
10.70mm, Berral : 9.0mm to 10.70mm, Length: 3Mtrs.

Manufacture, Supply and Delivery of 65 mm size CI


4 Pipe Adaptor and Pump Adaptor for UPVC column Set 581
Pipes

S.O.R. Mech 2019-20


Page 28 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20
Manufacture, Supply and Delivery of 80 mm Nominal
dia UPVC Column Pipes including PVC Socket
3
5 (Coupler), Density of Pipe 1.38 to 1.43 Gm per Cm Mtr. 314
OD : 87.5 TO 88.2MM, Wall Thickness End : 9.8mm to
11.9mm, Berral : 7.3mm to 9.0mm, Length:3Mtrs.

Manufacture, Supply and Delivery of 80 mm size CI


6 Pipe Adaptor and Pump Adaptor forUPVC column Set 770
Pipes.

15(B) UPVC Column Pipes HEAVY Duty Grade, 250mtrs. Head

Manufacture, Supply and Delivery of 50 mm Nominal


dia UPVC Column Pipes including PVC Socket
3
1 (Coupler), Density of Pipe 1.38 to 1.43 Gm per Cm , Mtr. 200
OD : 59.50 TO 60.10MM, Wall Thickness End : 6.10 nto
7.9mm, Berral : 3.9 to 5.0mm, Length:3 Mtrs.

Manufacture, Supply and Delivery of 50 mm size CI


2 Pipe Adaptor and Pump Adaptor for UPVC column Set 376
Pippe.

Manufacture, Supply and Delivery of 65 mm Nominal


dia UPVC Column Pipes including PVC Socket
3 (Coupler), Density of Pipe 1.38 to 1.43 Gm per Cm3 Mtr. 301
OD : 74.5 TO 75.2MM, Wall Thickness End : 9.0mm to
10.70mm, Berral : 9.0mm to 10.70mm, Length: 3 Mtrs.

Manufacture, Supply and Delivery of 65 mm size CI


4 Set 581
Pipe Adaptor and Pump Adaptor for UPVCcolumn Pipes

Manufacture, Supply and Delivery of 80 mm Nominal


dia UPVC Column Pipes including PVC Socket
3
5 (Coupler), Density of Pipe 1.38 to 1.43 Gm per Cm , Mtr. 409
OD : 87.5 TO 88.2MM, Wall Thickness End : 9.8mm to
11.9mm, Berral : 7.3mm to 9.0mm, Length: 3 Mtrs.

Manufacture, Supply and Delivery of 80 mm size CI


6 Pipe Adaptor and Pump Adaptor for UPVC column Set 770
Pipes.

S.O.R. Mech 2019-20


Page 29 of 166
SECTION- B

Approved Rate
Sr. No. Description of Item Unit
for 2019-20

Supply and install heavy duty through the weave


polyurethane(PU) covered hoses with coupling made
from 100% high tencity synthetic yarn circular woven
and completely embedded the PU compound,protected
against mechanical damage, forming a single
homogenous construction without the use of anu glues
or adhesives of any type ,resistance to abrasion
,heat,oil,fuel,a wide range of chemicals , weathering and
ozone,working pressure 8 kg/cm2 and burst pressure 20
16 kg/cm2.

A Fire Hose Pipe 100 MM dia Mtr. 1800

B Fire Hose Pipe 200 MM dia Mtr. 3600

C Fire Hose Pipe 300 MM dia Mtr. 5400

RO System

SS Skid mouted RO system as per IS:10500( latest)


including Iron Removing Filter, Chloride & Flouride
Removal Pump,raw water pump sand filter activated
carbon ,dozing pump,micron filters,high pressuer
A pump,low-high presuer switchs,membrane Nos. 134560
housing,membrane,flow metters,pressuer
17 gauges,electrical panal box,inter connection CPVC
pipes,inernal electical wireing etc.
CAPACITY : 500 LPH
As Above.
B Nos. 200000
CAPACITY : 1000 LPH

As Above
C Nos. 265000
CAPACITY : 2000 LPH

GI FITTINGS ( Elbows, Nipple, Step Nipple,Union Plug


Tee, Coupling,Reducer)

18 A) upto 65 MM Kg 72
B) Above 65 MM To 100 MM Kg 73
C) Above 100 MM Kg 74
Supply of 300 mm dia RCC Plain pipes used in drilling of
A) Mtr. 380
RCC Tube wells
19
Supply of 300 mm dia RCC Strainer pipes used in drilling
B) Mtr. 470
of RCC Tube wells

S.O.R. Mech 2019-20


Page 30 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20
"LABOUR ITEM"

Gas cutting of M. S. / G. I. pipes of following


size & facing pipe ends at right angles duly cut
1 including carting of pipes (to & fro from local
With Without
sub division stores to agency's workshop) and Per end
Carting Carting
stacking the same as directed.

a 150 mm dia per end 104.75 36.75

b 175 mm dia per end 108.50 40.50

c 200 mm dia per end 124.00 47.00

d 250 mm dia per end 160.00 54.00

e 300 mm dia per end 174.00 59.00

f 350 mm dia per end 197.30 72.00


Job work of slotting of M S ERW blind pipe of
following size having slot size as 6.75 cm x 6.35
cm x 3.12 mm (including unloading of blind
pipes from truck & reloading slotted pipes into
truck).
2A
a 200 mm dia Per Slot - 0.2271

b 250 mm dia Per Slot - 0.2420

c 300 mm dia Per Slot - 0.4129

As above having slot size as 6.75 cm x 6.35 cm


x 1.59 mm.

a 200 mm dia per slot - 0.2313


2B
b 250 mm dia per slot - 0.2621

c 300 mm dia per slot - 0.4342

Facing of both ends of following size M. S. / G.


I. column pipe & threading (8 TPI) with taper
0
ratio 1.25 & 55 thread angle including fitting of
3 coupling on one end with required
circumferential welding. (including unloading of
pipes from truck & reloading pipes into truck).

a 150 mm dia thread length 65+5 mm per End - 113

S.O.R. Mech 2019-20

Page 31 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20

b 125 mm dia thread length 65+5 mm per End - 89

c 100 mm dia thread length 65+5 mm per End - 70

d 80 mm dia thread length 55+5 mm per End - 53

e 65 mm dia thread length 45+5 mm per End - 44

f 50 mm dia thread length 45+5 mm per End - 32

g 32 mm dia thread length 30+5 mm per End - 29

Installation of India mark II H. P. assembly as


per Unicef specifications complete with carting,
lowering of 32 mm dia. riser pipes as required,
construction of C. C. plateform 1:2:4 etc.
including providing cement, sand & kapachi etc
4(a) - 3635.00
& construction of soak pit as modified Unicef LS Job
design including excavation of (100 cm x 70 cm
x 70 cm deep) with filling of stones, broken
bricks or gravel and laying 29 numbers bricks
vertically on edge of soak pit etc. complete.

Installation of India mark II H. P. assembly as


per Unicef specifications complete with carting,
lowering of 32 mm riser pipes as required.
(b) LS Job - 975.00

Construction of C. C. plateform 1:2:4 etc.


including providing cement, sand & kapachi etc
& construction of soak pit as modified Unicef
design including excavation of (100 cm x 70 cm
(c) x 70 cm deep) with filling of stones, broken LS Job - 2660.00
bricks or gravel and laying 29 numbers bricks
vertically on edge of soak pit etc. complete
(Without carting).

S.O.R. Mech 2019-20

Page 32 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20
Construction of soak pit as modified Unicef
design including excavation of (100 cm x 70 cm
x 70 cm deep) with filling of stones, broken
(d) bricks or gravel and laying 29 numbers bricks Job - 384.00
vertically on edge of soak pit etc. complete.

Removal of existing hand pump assembly with


riser pipes from bore well & stacking them
(e) properly by engaging required labour. Job - 197.60

Removal of existing damaged CC platform by


(f) engaging required labour. Job - 296.80

Annual overhauling, break down repairs,


quarterly service of I.M. II H.P. of various
villages of ______ Taluka & district
(A) regular querterly service of each HP, (B)
Breakdown repairing of HP on as and when
required basis and (C) Annual complete
overhauling (inclusive of bottom cylinder) of
5
each HP As per Following Slab For All District
of All Zone.

1 For Zone I Job - 485.00

2 For Zone II to V Job - 485.00

Jacking of pipes from failed tube well from


ground level to 6 Mtr. BGL including by heavy
duty power crane brought to site of work on
6(a) rental basis for following size of pipe & carting
of recovered pipes from site to sub divisional
store as directed.

300 mm dia from GL to 6.0 mtr BGL. Job - 10920.00

250 mm dia from GL to 6.0 mtr BGL. Job - 7800.00

200 mm dia from GL to 6.0 mtr BGL. Job - 5460.00

150 mm dia from GL to 6.0 mtr BGL. Job - 3120.00

125 mm dia from GL to 6.0 mtr BGL. Job - 2340.00

S.O.R. Mech 2019-20

Page 33 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20

100 mm dia from GL to 6.0 mtr BGL. Job - 1092.00

Jacking of pipes from failed tube well futher


6(b)
from 6.00 meters BGL till recovery continues.

i) 300 mm dia RMT - 156.00

ii) 250 mm dia RMT - 125.00

iii) 200 mm dia RMT - 117.00

iv) 150 mm dia RMT - 109.00

v) 125 mm dia RMT - 94.00

vi) 100 mm dia RMT - 86.00


Filling of existing failed tube well or finished
bore hole of any size by sticky clay (With
6(c) required materials) RMT - 83.00

Job work of loading of hand pump assembly


complete into truck And / Or unloading and
7(a) Set - 12.00
stacking the same in sub divisional store as
directed.

Job work of loading of M S / G I column pipes of


3 meters length of following size into truck And /
(b)
Or unloading and stacking the same in sub
divisional store as directed.

i) 32 mm No. - 1.85

ii) 50 mm No. - 2.15

iii) 65 mm No. - 3.10

iv) 80 mm No. - 3.75

v) 100 mm No. - 4.65

vi) 125 mm No. - 6.20

Job work of loading of M S ERW / V Screen


pipes of 4 to 7 meters length of following size
(c)
into truck And / Or unloading and stacking the
same in sub divisional store as directed.

S.O.R. Mech 2019-20

Page 34 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20

i) 150 / 175 mm No. - 18.60

ii) 200 mm No. - 21.00

iii) 250 mm No. - 33.50

iv) 300 mm No. - 37.25

Job work of loading of uPVC pipes of 3 meters


length of following size into truck And / Or
(d)
unloading and stacking the same in sub
divisional store as directed.

i 125 mm No. - 2.75

ii 175 mm No. - 7.00

iii 200 mm No. - 7.00

Job work of loading of HDPE pipe coil of


following size into truck And / Or unloading and
(e)
stacking the same in sub divisional store as
directed.

i 40 mm (100 mt long) No. - 16.75

ii 50 mm (100 mt long) No. - 22.25

iii 63 mm (100 mt long) No. - 22.25

iv 90 mm (100 mt long) No. - 44.75

v 110 mm (100 mt long) No. - 67.00

S.O.R. Mech 2019-20

Page 35 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20

Providing light commercial (medium)


four wheeler diesel vehicle on rental
basis for one day (minimum 12 hours)
(a) 1500.00
(particularly for hand pump repairing
Per Day
works) with Driver & P.O.L. (The vehicle
there after
8 shall be fully insured with fitness
10.00 per
certificate & PUC)
(a) km
Up to first 100 kms per day and extra
km thereafter i. e. beyond 100 kms. Day
(b) 1800.00
Up to first 150 kms per day and extra Km.
(b) Per Day
km thereafter i. e. beyond 150 kms.
there after
9.25 per km

Providing light commercial (small) four


wheeler diesel vehicle (Tata Ace
"Chhota Hathi", Ashok Leyland "Dost",
Mahindra "Utiliti" or equivalent) on rental
basis for one day (minimum 12 hours)
(particularly for hand pump repairing
9A works) with Driver & P.O.L. (The vehicle
shall be fully insured with fitness
certificate & PUC)
Up to first 100 kms per day and extra 900.00 Per
(a) Day
km thereafter i. e. beyond 100 kms. Day there
Km.
after 8.00
per km

Providing three wheeler diesel vehicle


having carrier/ trolly (chhakada or equi.)
on rent basis for entire day hiring
(particular for hand pump repair works)
With Driver, P.O.L., insurance, all RTO
9B & toll tax etc.

Up to first 100 K.M. per Day 750 Per Day


(a) Day
Rate per Extra K.M. for more than 100 there after
(b) Km.
K.M. travelling 6.50 per km

Hiring of vehicles for transportation of


9C
goods
Heavy Commercial Vehicle- Truck
2500 per
day there
i (a) Up to first 100 K.M. per Day Day
after 20.00
(b) Rate per Extra K.M. for more than 100 Km.
per km
K.M. travelling

S.O.R. Mech 2019-20

Page 36 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20
Medium Commercial Vehicle- Eicher or
equiv. Having carrier length not less
2000 per
than 6 meter
day there
ii
after 15.00
(a) Up to first 100 K.M. per Day Day
per km
(b) Rate per Extra K.M. for more than 100 Km.
K.M. travelling
Hiring of Non AC Inspection vehicle
(SUV) not older than 3 years (M & M:
Bolero / Scorpio / Xuv; Tata: Sumo /
Safari, Jeep or Equivalent) With Driver
& P.O.L. (The vehicle shall have taxi
10 (A) passing with comprehensive full
insurance, fitness certificate & PUC). Fix 21700
Up to 2000 Kilometres / Month
and extra km thereafter i. e. beyond Km. 7.75/Km
2000 kms.

Hiring of AC Inspection vehicle (SUV)


not older than 3 years (M & M: Bolero /
Scorpio / Xuv; Tata: Sumo / Safari,
Jeep or Equivalent) With Driver &
P.O.L. (The vehicle shall have taxi
10 (B) passing with comprehensive full
insurance, fitness certificate & PUC) Fix 27999
Up to 2000 Kilometres / Month
and extra km thereafter i. e. beyond Km. 10.48/Km
2000 kms.

Labour charges for hiring of D.G.Sets minimum


for 10 Days with maintainance & fuel charges of
various capacity from 30 KVA to 1000 KVA (440 FUEL-OIL-
Volts) for operating pump & other equipments to Rent of D.G.set LUBRICANT
11
run water supply scheme in different district in Rs./day charges.
Gujarat (the rates are inclusive of providing Rs./ hr
change over switch & standard length cable &
operating crew)

Sr.No Capacity (KVA)

1 30 1156.40 417.72

S.O.R. Mech 2019-20

Page 37 of 166
SECTION - "C"
Approved Rate for
Sr. No Description of Item Unit
2019-20

2 40 1205.10 457.47

3 50 1332.80 580.72

4 62.5 1321.60 870.84

5 75 1345.50 1007.37

6 82.5 1404.20 1260.21

7 100 1593.00 1399.48

8 110 1591.20 1400.49

9 125 1654.10 1460.13

10 140 1947.00 2254.98

11 160 1989.00 2411.37

12 180 2284.80 2507.33

13 200 2324.60 2738.78

14 250 2421.90 3378.96

15 320 2701.30 4168.57

16 380 3150.60 4770.74

17 500 3814.20 5681.52

S.O.R. Mech 2019-20

Page 38 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
1 Wiring

1. For Point wiring above 10 mtr. of length, additional length will be added at rate of mains.

2. For point wiring in bathroom and W/C and washbasin area in residential quarters reduce overall rate by 50% of point wiring
for light.
1.1 Point wiring in Copper (TISSINO)

Point wiring for Light/ Fan/ Bell/ Primary Point with 2-1.5 sq. mm &
earthwire of 1.5 sq. mm (green) both are of ISI marked 1.1kV grade
FRLS PVC insulated multistrand copper wires, in following type of
pipe to be erected concealed in/ flushed on wall /ceiling, complete
1.1.1 with 6A Tissino type ISI marked flush type switch/ bell push and
accessories erected on Metal/ PVC Box covered with 3 mm thick PC
(Polycarbonet)/ Acrylic sheet with necessary Lamp holder/ ceiling
rose/ H.D.Connector as directed.

with medium class Rigid PVC pipe and accessories Pt 270 60 330 -- 330
(a)
with 16 swg(1.6 mm thick) HGS metal conduit pipe and accessories Pt. 370 70 440 -- 440
(b) painted black

(c) with oval conduit/ PVC casing capping double lock type Pt. 240 40 280 -- 280

(d) partial PVC pipe and drops in oval conduit/ PVC casing capping Pt. 255 50 305 -- 305

(e) in existing pipe Pt 200 40 240 -- 240


Point wiring for independent PLUG with following size mains &
earthwire of 1.5 sq.mm (green) both are of ISI marked 1.1kV grade
FRLS PVC insulated multistrand copper wires, in following type of
pipe to be erected concealed in /flushed on wall/ ceiling, complete
1.1.2 with ISI marked 3/5 Pin socket and tissino type switch erected with
earth continuity connection erected on Metal/ PVC box covered with
3 mm thick PC (Polycarbonet)/ Acrylic sheet.

(A) For 2-1.5 sq. mm Cu. Mains

(a) with medium class Rigid PVC pipe and accessories Pt. 240 50 290 -- 290

with 16 swg HGS metal conduit pipe and accessories painted black Pt. 340 60 400 -- 400
(b)

(c) with oval conduit/ PVC casing capping double lock type Pt. 210 40 250 -- 250

(d) partial PVC pipe and drops in oval conduit/ PVC casing capping Pt. 225 45 270 -- 270

(e) in existing pipe Pt. 170 40 210 -- 210

(B) 6/16A Plug with 2-2.5 sq. mm Cu. Mains

(a) with medium class Rigid PVC pipe and accessories Pt. 425 40 465 -- 465

with 16 swg HGS metal conduit pipe and accessories painted black Pt. 505 50 555 -- 555
(b)

(c) with oval conduit/ PVC casing capping double lock type Pt. 340 40 380 -- 380

(d) partial PVC pipe and drops in oval conduit/ PVC casing capping Pt. 405 40 445 -- 445

(e) in existing pipe Pt. 260 40 300 -- 300

(C) 6/16A Plug with 2-4 sq.mm Cu. Mains

(a) with medium class Rigid PVC pipe and accessories Pt. 520 50 570 -- 570

with 16 swg HGS metal conduit pipe and accessories painted black Pt. 610 60 670 -- 670
(b)
with oval conduit/ PVC casing capping double lock type Pt. 460 50 510 -- 510
(c)

(d) partial PVC pipe and drops in oval conduit/ PVC casing capping Pt. 500 50 550 -- 550

(e) in existing pipe Pt. 360 50 410 -- 410

S.O.R. Mech 2019-20


Page 39 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Point wiring for looped PLUG with tissino type single pole ISI marked
Switch and Socket erected with necessary connections erected on
1.1.3 wooden/ Metal/ PVC Box covered with 3 mm thick PC
(Polycarbonet)/ Acrylic sheet for open/ concealed wiring for following
size.

(A) For 6 Amp. Pt. 30 20 50 -- 50

(B) For 16 Amp. Pt. 120 30 150 -- 150

Point wiring for secondary light point with 2-1.5 sq.mm & earthwire of
1.5 sq.mm (green) both are of ISI marked 1.1kV grade FRLS PVC
insulated multistrand copper wires, in following type of pipe to be
erected concealed in/ flushed on wall/ ceiling, complete with earth
continuity and necessary connection with primary light with
1.1.4 accessories erected on Metal/ PVC box covered with 3 mm thick PC
(Polycarbonet)/ Acrylic sheet for open/ concealed wiring with
necessary Lamp holder/ ceiling rose/ H.D.Connector as directed.
Note :- Maximum up to 6 mtrs length, excess will be considered as
Mains for Secondary Point.

(A) with medium class Rigid PVC pipe and accessories Pt. 95 25 120 -- 120

with 16 swg HGS metal conduit pipe and accessories painted black Pt. 150 30 180 -- 180
(B)
with oval conduit/ PVC casing capping double lock type Pt. 75 25 100 -- 100
(C)

(D) partial PVC pipe and drops in oval conduit/ PVC casing capping Pt. 85 25 110 -- 110

(E) in existing pipe Pt. 50 25 75 -- 75

Point wiring for Two way controlled Light Point with 2-1.5 sq.mm &
earthwire of 1.5 sq. mm (green) both are of ISI marked 1.1kV grade
FRLS PVC insulated multistrand copper wires, in following type of
pipe to be erected concealed in/ flushed on wall/ ceiling complete
1.1.5 with 6A Tissino type ISI marked accessories with earth continuity
erected on Metal/ PVC box covered with 3 mm thick PC
(Polycarbonet)/ Acrylic sheet with necessary Lamp holder/ ceiling
rose/ H.D.Connector as directed.

(A) with medium class Rigid PVC pipe and accessories Pt. 290 60 350 -- 350

with 16 swg HGS metal conduit pipe and accessories painted black Pt. 405 70 475 -- 475
(B)

(C) with oval conduit/ PVC casing capping double lock type Pt. 270 40 310 -- 310

(D) partial PVC pipe and drops in oval conduit/ PVC casing capping Pt. 285 50 335 -- 335

(E) in existing pipe Pt. 220 40 260 -- 260

1.2 Point wiring in Copper (Modular)

Point wiring for Light/ Bell with 2-1.5 sq. mm & earthwire of 1.5
sq.mm (Green) both are of ISI marked 1.1kV grade FRLS PVC
insulated multistrand copper wires, in following type of pipe to be
erected concealed in/ on surface on wall/ ceiling complete with 6A
Modular type switch/ bell push & accessories and earth continuity of
1.2.1 following type, erected on PVC/ Metallic box, single mounting base
frame covered with textured/ metallic front plate modules erected on/
in wall/ ceiling as per pipe erected, with necessary Lamp holder/
ceiling rose/ H.D.Connector as directed.

(a) with medium class Rigid PVC pipe and accessories

Cat. I Pt. 290 60 350 -- 350

Cat. II Pt. 340 60 400 -- 400

Cat. III Pt. 360 60 420 -- 420

with 16 swg HGS metal conduit pipe and accessories painted black
(b)
Cat. I Pt. 390 80 470 -- 470

Cat. II Pt. 440 80 520 -- 520

S.O.R. Mech 2019-20


Page 40 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Cat. III Pt. 460 80 540 -- 540

( c) with oval conduit/ PVC casing capping double lock type

Cat. I Pt. 260 50 310 -- 310

Cat. II Pt. 310 50 360 -- 360

Cat. III Pt. 330 50 380 -- 380

partial PVC pipe and drops in oval conduit/ PVC casing capping
(d)
Cat. I Pt. 280 50 330 -- 330

Cat. II Pt. 290 50 340 -- 340

Cat. III Pt. 300 50 350 -- 350

(e) in existing pipe

Cat. I Pt. 220 50 270 -- 270

Cat. II Pt. 270 50 320 -- 320

Cat. III Pt. 300 50 350 -- 350

Point wiring for FAN with 2-1.5 sq.mm & earthwire of 1.5 sq.mm
(Green) both are of ISI marked 1.1kV Grade FRLS PVC insulated
multistrand copper wires, in following type of pipe to be erected
concealed in/ flushed on wall/ ceiling complete with 6A Modular type
switch and hume free EME four or more step type electronic fan
1.2.2 regulator with separately mounted and accessories with earth
continuity of following type erected on PVC/ Metallic box, single
mounting base frame covered with textured/ metallic front plate
modules erected on/ in wall/ ceiling as per pipe erected with
necessary ceiling rose/ H.D.Connector as directed.

(a) with medium class Rigid PVC pipe and accessories

Cat. I Pt. 440 60 500 -- 500

Cat. II Pt. 520 60 580 -- 580

Cat. III Pt. 540 60 600 -- 600

with 16 swg HGS metal conduit pipe and accessories painted black
(b)

Cat. I Pt. 540 80 620 -- 620


Cat. II Pt. 620 80 700 -- 700
Cat. III Pt. 640 80 720 -- 720
( c) with oval conduit/ PVC casing capping double lock type
Cat. I Pt. 400 50 450 -- 450
Cat. II Pt. 490 50 540 -- 540
Cat. III Pt. 510 50 560 -- 560
(d) partial PVC pipe and drops in oval conduit/ PVC casing capping
Cat. I Pt. 420 50 470 -- 470
Cat. II Pt. 470 50 520 -- 520
Cat. III Pt. 490 50 540 -- 540
(e) in existing pipe
Cat. I Pt. 360 50 410 -- 410
Cat. II Pt. 425 50 475 -- 475
Cat. III Pt. 440 50 490 -- 490
Point wiring for Individual Plug with earthwire of 1.5 sq.mm (Green)
both are of ISI marked 1.1kV grade FRLS PVC insulated multistrand
copper wires, in following type of to be erected concealed in/ on
surface of wall/ ceiling complete with Modular type switch & 5 pin
1.2.3
Plug erected on PVC/ Metallic box covered with appropriate front
plate modules erected on/ in wall/ ceiling as per pipe erected with
following type of accessories.

(A) For 6A Plug with 2-1.5 sq.mm Cu. Wire

(a) with medium class Rigid PVC pipe and accessories

Cat. I Pt. 360 50 410 -- 410


Cat. II Pt. 380 50 430 -- 430

S.O.R. Mech 2019-20


Page 41 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Cat. III Pt. 395 50 445 -- 445
with 16 swg HGS metal conduit pipe and accessories painted black
(b)

Cat. I Pt. 460 60 520 -- 520


Cat. II Pt. 480 60 540 -- 540
Cat. III Pt. 495 60 555 -- 555
with oval conduit/ PVC casing capping double lock type
(c)
Cat. I Pt. 330 40 370 -- 370
Cat. II Pt. 350 40 390 -- 390
Cat. III Pt. 365 40 405 -- 405
(d) partial PVC pipe and drops in oval conduit/ PVC casing capping
Cat. I Pt. 345 45 390 -- 390
Cat. II Pt. 365 45 410 -- 410
Cat. III Pt. 38 45 83 -- 83
(e) in existing pipe
Cat. I Pt. 290 40 330 -- 330
Cat. II Pt. 310 40 350 -- 350
Cat. III Pt. 325 40 365 -- 365
(B) For 16A Plug with 2-2.5 sq.mm Cu. Wire
(a) with medium class Rigid PVC pipe and accessories
Cat. I Pt. 560 50 610 -- 610
Cat. II Pt. 595 50 645 -- 645
Cat. III Pt. 620 50 670 -- 670
with 16 swg HGS metal conduit pipe and accessories painted black
(b)
Cat. I Pt. 640 60 700 -- 700
Cat. II Pt. 680 60 740 -- 740
Cat. III Pt. 695 60 755 -- 755
(c) with oval conduit/ PVC casing capping double lock type

Cat. I Pt. 480 40 520 -- 520


Cat. II Pt. 520 40 560 -- 560
Cat. III Pt. 540 40 580 -- 580
partial PVC pipe and drops in oval conduit/ PVC casing capping
(d)
Cat. I Pt. 540 40 580 -- 580
Cat. II Pt. 580 40 620 -- 620
Cat. III Pt. 595 40 635 -- 635
(e) in existing pipe
Cat. I Pt. 395 40 435 -- 435
Cat. II Pt. 435 40 475 -- 475
Cat III Pt. 460 40 500 -- 500
(C) For 16A Plug with 2-4 sq.mm Cu. Wire
(a) with medium class Rigid PVC pipe and accessories
Cat. I Pt. 680 50 730 -- 730
Cat. II Pt. 720 50 770 -- 770
Cat. III Pt. 740 50 790 -- 790
with 16 swg HGS metal conduit pipe and accessories painted black
(b)

Cat. I Pt. 770 60 830 -- 830


Cat. II Pt. 800 60 860 -- 860
Cat. III Pt. 830 60 890 -- 890
(c) with oval conduit/ PVC casing capping double lock type

Cat. I Pt. 620 50 670 -- 670


Cat. II Pt. 660 50 710 -- 710
Cat. III Pt. 680 50 730 -- 730
partial PVC pipe and drops in oval conduit/ PVC casing capping
(d)
Cat. I Pt. 660 50 710 -- 710
Cat. II Pt. 695 50 745 -- 745
Cat. III Pt. 720 50 770 -- 770
(e) in existing pipe
Cat. I Pt. 520 50 570 -- 570
Cat. II Pt. 560 50 610 -- 610
Cat III Pt. 580 50 630 -- 630

S.O.R. Mech 2019-20


Page 42 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Point wiring for looped plug with 6A Modular type switch & 5 pin
socket erected on PVC/ Metallic box, single mounting base frame
1.2.4 covered with textured/ metallic front plate modules erected on/ in
wall/ ceiling with following type accessories.

Cat. I Pt. 160 30 190 -- 190


Cat. II Pt. 190 30 220 -- 220
Cat. III Pt. 210 30 240 -- 240
Point wiring for two way controlled Light Point with 2-1.5 sq.mm &
earthwire of 1.5 sq.mm (green) both are of ISI marked 1.1kV grade
FRLS PVC insulated multistrand copper wires, in following type of
pipe to be erected concealed in/ flushed on wall/ ceiling, complete
with 6A Modular type switches and following type of accessories
1.2.5 erected on PVC/ Metallic box, single mounting base frame covered
with textured/ metallic front plate modules erected on/ in wall/ ceiling
as per pipe erected with necessary batten/ angle holder or ceiling
rose or H.D.Connector as directed.

with medium class Rigid PVC pipe and accessories


(a)
Cat. I Pt. 390 70 460 -- 460
Cat. II Pt. 440 70 510 -- 510
Cat. III Pt. 460 70 530 -- 530
with 16 swg HGS metal conduit pipe and accessories painted black
(b)

Cat. I Pt. 490 80 570 -- 570


Cat. II Pt. 540 80 620 -- 620
Cat. III Pt. 560 80 640 -- 640
with oval conduit/ PVC casing capping double lock type
(c)
Cat. I Pt. 360 50 410 -- 410
Cat. II Pt. 410 50 460 -- 460
Cat. III Pt. 440 50 490 -- 490
(d) partial PVC pipe and drops in oval conduit/ PVC casing capping

Cat. I Pt. 380 50 430 -- 430


Cat. II Pt. 390 50 440 -- 440
Cat. III Pt. 410 50 460 -- 460
(e) in existing pipe
Cat. I Pt. 320 50 370 -- 370
Cat. II Pt. 370 50 420 -- 420
Cat III Pt. 400 50 450 -- 450
Providing following type of Modular type accessories mounted with
PVC/ metallic box, single mounting base frame covered with
1.2.6 textured/ metallic front plate, modules erected with necessary
connection as desired by Engineer In charge
(A) One No. SP 6 A
Cat.I Ea. 80 10 90 -- 90
Cat.II Ea. 115 10 125 -- 125
Cat.III Ea. 140 10 150 -- 150
(B) One No. 5 pin plug
Cat.I Ea. 80 10 90 -- 90
Cat.II Ea. 115 10 125 -- 125
Cat.III Ea. 140 10 150 -- 150
(C) Two Pin/ RJ-11 telephone socket
(a) For One Gang
Cat.I Ea. 90 10 100 -- 100
Cat.II Ea. 120 10 130 -- 130
Cat.III Ea. 150 10 160 -- 160
(b) For Two Gang
Cat.I Ea. 120 10 130 -- 130
Cat.II Ea. 160 10 170 -- 170
Cat.III Ea. 200 10 210 -- 210
(D) TV Co-axial socket outlet
Cat.I Ea. 100 10 110 -- 110
Cat.II Ea. 130 10 140 -- 140
Cat.III Ea. 150 10 160 -- 160
(E) Electronic hume free four or more steps EME fan regulator
Cat.I Ea. 280 10 290 -- 290
S.O.R. Mech 2019-20
Page 43 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Cat.II Ea. 330 10 340 -- 340
Cat.III Ea. 390 10 400 -- 400
(F) Fuse units 10A/ 16A
Cat.I Ea. 90 10 100 -- 100
Cat.II Ea. 110 10 120 -- 120
Cat.III Ea. 170 10 180 -- 180
(G) Blank plate single
Cat.I Ea. 10 0 10 -- 10
Cat.II Ea. 15 0 15 -- 15
Cat.III Ea. 20 0 20 -- 20
(H) Modem jack for computer open RJ-45
Cat.I Ea. 100 10 110 -- 110
Cat.II Ea. 130 10 140 -- 140
Cat.III Ea. 150 10 160 -- 160
(I) 16 Amp. SP one way switch
Cat.I Ea. 90 10 100 -- 100
Cat.II Ea. 120 10 130 -- 130
Cat.III Ea. 170 10 180 -- 180
(J) 6A/ 16A Universal socket
Cat.I Ea. 110 10 120 -- 120
Cat.II Ea. 130 10 140 -- 140
Cat.III Ea. 190 10 200 -- 200
(K) 6 A Bell push
Cat.I Ea. 90 10 100 -- 100
Cat.II Ea. 100 10 110 -- 110
Cat.III Ea. 140 10 150 -- 150
(L) 6A/ 16A two way switch
Cat.I Ea. 110 10 120 -- 120
Cat.II Ea. 120 10 130 -- 130
Cat.III Ea. 160 10 170 -- 170
(M) 6A/ 10A/ 16A/ 20A/ 25A/ 32A single pole modular MCB switch
Cat.I Ea. 220 10 230 -- 230
Cat.II Ea. 260 10 270 -- 270
Cat.III Ea. 300 10 310 -- 310
(N) 6A/ 10A/ 16A/ 20A/ 25A/ 32A double pole modular MCB switch
Cat.I Ea. 300 10 310 -- 310
Cat.II Ea. 320 10 330 -- 330
Cat.III Ea. 400 10 410 -- 410
(O) 32 Amps. DP switch with indicator
Cat.I Ea. 200 10 210 -- 210
Cat.II Ea. 220 10 230 -- 230
Cat.III Ea. 270 10 280 -- 280
(P) 32 Amp. DP main switch operating with energy key ag
Cat.I Ea. 280 10 290 -- 290
Cat.II Ea. 310 10 320 -- 320
Cat.III Ea. 350 10 360 -- 360
(a) For 400W / 450 watt One module electronic dimmer
Cat. II Ea. 250 10 260 -- 260
Cat. III Ea. 310 10 320 -- 320
(b) For 600 / 650 watt two module electronic dimmer
Cat. II Ea. 330 10 340 -- 340
Cat. III Ea. 390 10 400 -- 400
(c) For 1000 watt two module electronic dimmer
Cat. II Ea. 510 10 520 -- 520
Cat. III Ea. 590 10 600 -- 600
(Q) 13 Amp. International modular socket
Cat.I Ea. 150 10 160 -- 160
Cat.II Ea. 170 10 180 -- 180
Cat.III Ea. 230 10 240 -- 240
(R) Modular indicating call bell
Cat.III Ea. 315 15 330 -- 330
(S) Modular buzzer
Cat.II Ea. 115 15 130 -- 130
Cat.III Ea. 310 15 325 -- 325
White Foot Light with concealed box, modular accessories, acrylic
(T) glass cover with suitable CFL 9/11/13 W LED lights
(a) equal of four modules Ea. 450 50 500 -- 500
(b) equal of eight modules Ea. 650 50 700 -- 700

S.O.R. Mech 2019-20


Page 44 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
(U) 16/20/25 Amp. Modular Starter for Motor / A.C. Unit Complete
Cat.II Ea. 370 30 400 -- 400
Cat.III Ea. 470 30 500 -- 500
1.3 Conduits & Pipes
For Laying of pipes on stone wall add to the following item rate per Mtr. 0 10 10 -- 10
1.3.1
meter
Providing and erecting ISI mark Medium class RIGID PVC PIPES of
following size complete to be erected on/ in wall or ceiling erected
1.3.2 with necessary PVC fittings & Junction boxes fixed with adhesive
solution & Clamps with following dia. of pipes in approved manner as
directed.
(a) 20 mm Mtr. 18 5 23 -- 23
(b) 25 mm Mtr. 27 5 32 -- 32
(c) 32 mm Mtr. 46 7 53 -- 53
(d) 40 mm Mtr. 59 8 67 -- 67
Providing & erecting approved make OVAL CONDUIT with
1.3.3 necessary fittings fixed with adhesive solution and suitable clamps
erected on wall/ ceiling of following size.
(a) 20 mm Mtr. 22 3 25 -- 25
(b) 25mm Mtr. 30 5 35 -- 35
Providing & erecting PVC Corrugated Flexible Conduit with required
1.3.4 nos. of coupling, PVC bushes, Check-nuts etc. complete of following
sizes.
(a) 20 mm Mtr. 13 2 15 -- 15
(b) 25 mm Mtr. 18 2 20 -- 20
(c) 32 mm Mtr. 23 2 25 -- 25
(d) 40 mm Mtr. 33 2 35 -- 35
(e) 50 mm Mtr. 43 2 45 -- 45
Supplying & erecting UPVC Mini trunking (PVC Casing-n-Capping)
having double-locking arrangement with grooves, trunking of size not
below 12.5 mm in height as per IS with accessories of PVC/ Resin
1.3.5 polypropylene not below 1.8 mm thick duly sealed in joint & erected
on wall/ ceiling of following size.

(a) 20 mm Mtr. 15 5 20 -- 20
(b) 25 mm Mtr. 25 5 30 -- 30
(c) 32 mm Mtr. 30 5 35 -- 35
(d) 40 mm Mtr. 35 5 40 -- 40
UPVC TRUNKING SYSTEM
(A) Supplying and laying UPVC cable trunking system comprising
unplasticised polyvinyl chloride rigid material with ignition free &
1.3.6 flame proof confirming BS. All necessary accessories and measuring
of following sizes.
(a) 75 mm x 50 mm trunking Mtr. 260 20 280 -- 280
(b) 100 mm x 50 mm trunking Mtr. 400 30 430 -- 430
(B) UPVC COUPLER
(a) For 75 mm x 50 mm trunking Ea 40 5 45 -- 45
(b) For100 mm x 50 mm trunking Ea 60 5 65 -- 65
(C) UPVC ELBOW
(a) For 75 mm x 50 mm trunking Ea 70 5 75 -- 75
(b) For100 mm x 50 mm trunking Ea 130 5 135 -- 135
(D) UPVC TEE
(a) For 75 mm x 50 mm trunking Ea 90 5 95 -- 95
(b) (2) For100 mm x 50 mm trunking Ea 110 5 115 -- 115
(E) UPVC INTERNAL BEND
(a) For 75 mm x 50 mm trunking Ea 70 5 75 -- 75
(b) For100 mm x 50 mm trunking Ea 90 5 95 -- 95
(F) UPVC EXTERNAL BEND
(a) For 75 mm x 50 mm trunking Ea 70 5 75 -- 75
(b) For100 mm x 50 mm trunking Ea 90 5 95 -- 95
(G) UPVC END CAP
(a) For 75 mm x 50 mm trunking Ea 70 5 75 -- 75
(b) For100 mm x 50 mm trunking Ea 80 5 85 -- 85
(H) SOCKET MOUNTING FRAME
(a) For one Gang Ea 60 5 65 -- 65
(b) For two Gang Ea 75 5 80 -- 80
(I) UPVC TRUNKING DIVIDER
(a) For 50 mm (depth) trunking Ea 30 0 30 -- 30

S.O.R. Mech 2019-20


Page 45 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
METAL TRUNKING
Supplying & laying under floor pregalvanised corrosion proof
rectangular sheet steel cable trunking of 1.6 mm thick having with
1.3.7 stand point load up to 1.33 ton & free from seepage of concrete of
screed water having following size of dimensions and No of
compartments (W x D x T)
50mm x 25mm x 1.6 mm with One Compartment Mtr 280 20 300 -- 300
(a)
75mm x 25mm x 1.6 mm with One Compartment Mtr 360 20 380 -- 380
(b)
100mm x 25mm x 1.6 mm with one compartment Mtr 430 30 460 -- 460
(c)
225mm x 25mm x 1.6 mm with Three Compartment Mtr 940 40 980 -- 980
(d)
250mm x 25mm x 1.6 mm with Three Compartments Mtr 1010 40 1050 -- 1050
(e)

(f) 300mm x 25mm x 1.6 mm with Three Compartments Mtr 1180 50 1230 -- 1230

(g) 50mm x 38mm x 1.6 mm with One Compartments Mtr 360 20 380 -- 380

(h) 75mm x 38mm x 1.6 mm with one compartments Mtr 440 20 460 -- 460

(i) 100mm x 38mm x 1.6 mm with One Compartments Mtr 520 30 550 -- 550

(j) 150mm x 38mm x 1.6mm with Three Compartments Mtr 730 40 770 -- 770

(k) 225mm x 38mm x 1.6mm with Three Compartments Mtr 1060 40 1100 -- 1100

(l) 250mm x 38mm x 1.6mm with Three Compartments Mtr 1160 40 1200 -- 1200

(m) 300mm x 38mm x 1.06 mm with Three Compartments Mtr 1300 50 1350 -- 1350

ACCESSOREIS FOR METAL TRUNCKING


under floor metal vertical S.S. unit facilitate accessibility 25/ 38 mm
1.3.8 height duct entry floor to wall & floor to floor.
250mm x 200mm x 50 mm for 2 Nos. compartments Ea 2200 50 2250 -- 2250
(a)

(b) 300mm x 200mm x 50mm for 2 Nos Compartments Ea 2530 70 2600 -- 2600

Floor mounted metal S.S. outlet (under floor service) made of high
quality ABS & polyamide materials with trap frame & screw less
1.3.9 ratchet trap lead with screw less knob reinforced with 2.5mm thick
pregalvanised steel plate of following size.
250mm x 250mm x 60/75 mm one trap three compartment (Metal Ea 4500 100 4600 -- 4600
(a)
lead)
(b) 300mm x 300mm x 60/75 mm (Metal lead) Three Compartments Ea 5300 100 5400 -- 5400
Junction Box
PVC/ GI Junction cross over box for metal/ Al. trunking with duct
entry 25mm x 38mm size having epoxy powder coated trap lead with
1.3.10 corrosion & rust free having load bearing capacity of 3.6 tons with
adjustable levelling screw of following size.
(a) 150mm x 150mm x 60/75 mm depth Ea 950 50 1000 -- 1000
(b) 250mm x 250mm x 60/75 mm depth Ea 1380 70 1450 -- 1450
(c) 300mm x 300mm x 60/75 mm depth Ea 2150 100 2250 -- 2250
(d) 350mm x 350mm x 60/75 mm depth Ea 2400 100 2500 -- 2500
(e) 400mm x 400mm x 60/75 mm depth Ea 2850 150 3000 -- 3000
Supplying under floor trunking accessories joint sleeves for 25mm /
1.3.11 38mm pipe with following dimensions.

(a) 50 x 25 x 1.6 mm for one compartments Ea 50 10 60 -- 60


(b) 75 x 25 x 1.6 mm for one compartments Ea 55 10 65 -- 65
(c) 100 x 25 x 1.6mm for one compartments Ea 65 10 75 -- 75
(d) 225 x 25 x 1.6 mm for three compartments Ea 90 20 110 -- 110
(e) 250 x 25 x 1.6 mm for three compartments Ea 105 20 125 -- 125
(f) 300 x 25 x 1.6 mm for three compartments Ea 120 20 140 -- 140
(g) 50 x 38 x 1.6 mm for one compartments Ea 55 10 65 -- 65
(h) 75 x 38 x 1.6 mm for one compartments Ea 60 10 70 -- 70
(i) 100 x 38 x 1.6 mm for one compartments Ea 70 10 80 -- 80
(j) 150 x 38 x 1.6 mm for Two compartments Ea 70 20 90 -- 90
(k) 225 x 38 x 1.6 mm For Three Compartments Ea 105 20 125 -- 125
(l) 250 x 38 x 1.6 mm for Three Compartments Ea 110 20 130 -- 130
(m) 300 x 38 x 1.6 mm for Three Compartments Ea 130 20 150 -- 150

S.O.R. Mech 2019-20


Page 46 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Providing & erecting 16 gauge HGS conduit pipe (as per IS)
painted black of following size complete to be erected on/ in wall or
1.3.12 ceiling with erected with necessary saddles, screws, bends, junction
boxes etc. with following (Nominal Bore) dia of pipes, in approved
manner as directed
(a) 19/20 mm Mtr. 70 20 90 -- 90
(b) 25 mm Mtr. 90 20 110 -- 110
(c) 32 mm Mtr. 120 20 140 -- 140
(d) 38/40 mm Mtr. 200 30 230 -- 230
(e) 50 mm Mtr. 290 30 320 -- 320
1.4 Mains & Wires
Mains with 1.1kV grade FRLS PVC insulated ISI marked stranded
copper conductor wire in following type of pipe to be erected
1.4.1 concealed in /flushed on wall/ ceiling with 1.5 sq. mm copper
conductor FRLS PVC insulated stranded wire of green colour for
earth continuity of following size.
(A) with medium class Rigid PVC pipe and accessories
(a) 2 wire 1.5 sq. mm Mtr. 55 5 60 -- 60
(b) 2 wire 2.5 sq. mm Mtr. 75 5 80 -- 80
(c) 3 wire 1.5 sq. mm Mtr. 75 5 80 -- 80
(d) 3 wire 2.5 sq. mm Mtr. 95 5 100 -- 100
(e) 4 wire 1.5 sq. mm Mtr. 84 6 90 -- 90
(f) 4 wire 2.5 sq. mm Mtr. 119 6 125 -- 125
(g) 6 wire 2.5 sq. mm Mtr. 164 6 170 -- 170
with 16 swg HGS metal conduit pipe and accessories painted black
(B)
(a) 2 wire 1.5 sq. mm Mtr. 105 25 130 -- 130
(b) 2 wire 2.5 sq. mm Mtr. 130 25 155 -- 155
(c) 3 wire 1.5 sq. mm Mtr. 125 25 150 -- 150
(d) 3 wire 2.5 sq. mm Mtr. 150 25 175 -- 175
(e) 4 wire 1.5 sq. mm Mtr. 130 30 160 -- 160
(f) 4 wire 2.5 sq. mm Mtr. 165 30 195 -- 195
(g) 6 wire 2.5 sq. mm Mtr. 220 30 250 -- 250
(C) with oval conduit/ PVC casing capping double lock type
(a) 2 wire 1.5 sq. mm Mtr. 50 5 55 -- 55
(b) 2 wire 2.5 sq. mm Mtr. 75 5 80 -- 80
(c) 3 wire 1.5 sq. mm Mtr. 70 5 75 -- 75
(d) 3 wire 2.5 sq. mm Mtr. 90 5 95 -- 95
(e) 4 wire 1.5 sq. mm Mtr. 80 5 85 -- 85
(f) 4 wire 2.5 sq. mm Mtr. 114 6 120 -- 120
(g) 6 wire 2.5 sq. mm Mtr. 179 6 185 -- 185
partial PVC pipe and drops in oval conduit/ PVC casing capping
(D)

(a) 2 wire 1.5 sq. mm Mtr. 50 5 55 -- 55


(b) 2 wire 2.5 sq. mm Mtr. 75 5 80 -- 80
(c) 3 wire 1.5 sq. mm Mtr. 70 5 75 -- 75
(d) 3 wire 2.5 sq. mm Mtr. 90 5 95 -- 95
(e) 4 wire 1.5 sq. mm Mtr. 80 5 85 -- 85
(f) 4 wire 2.5 sq. mm Mtr. 119 6 125 -- 125
(g) 6 wire 2.5 sq. mm Mtr. 159 6 165 -- 165
(E) in existing pipe
(a) 2 wire 1.5 sq. mm Mtr. 42 3 45 -- 45
(b) 2 wire 2.5 sq. mm Mtr. 57 3 60 -- 60
(c) 3 wire 1.5 sq. mm Mtr. 55 5 60 -- 60
(d) 3 wire 2.5 sq. mm Mtr. 85 5 90 -- 90
(e) 4 wire 1.5 sq. mm Mtr. 74 6 80 -- 80
(f) 4 wire 2.5 sq. mm Mtr. 109 6 115 -- 115
(g) 6 wire 2.5 sq. mm Mtr. 149 6 155 -- 155
Mains with 1.1kV grade FRLS PVC insulated ISI marked stranded
copper conductor wire in following type of pipe to be erected in/ on
1.4.2 wall /ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated
stranded wire of green colour for earth continuity of following size.

S.O.R. Mech 2019-20


Page 47 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
(A) with medium class Rigid PVC pipe and accessories
(a) 2 wire 4 sq. mm Mtr. 105 5 110 -- 110
(b) 2 wire 6 sq. mm Mtr. 140 5 145 -- 145
(c) 2 wire 10 sq. mm Mtr. 228 7 235 -- 235
(d) 3 wire 4 sq. mm Mtr. 135 7 142 -- 142
(e) 3 wire 6 sq. mm Mtr. 193 7 200 -- 200
(f) 3 wire 10 sq. mm Mtr. 318 7 325 -- 325
(g) 4 wire 4 sq. mm Mtr. 170 10 180 -- 180
(h) 4 wire 6 sq. mm Mtr. 250 10 260 -- 260
(i) 4 wire 10 sq. mm 415 10 425 -- 425
with 16 swg HGS metal conduit pipe and accessories painted
(B)
black
(a) 2 wire 4 sq. mm Mtr. 150 25 175 -- 175
(b) 2 wire 6 sq. mm Mtr. 190 25 215 -- 215
(c) 2 wire 10 sq. mm Mtr. 275 25 300 -- 300
(d) 3 wire 4 sq. mm Mtr. 180 25 205 -- 205
(e) 3 wire 6 sq. mm Mtr. 245 25 270 -- 270
(f) 3 wire 10 sq. mm Mtr. 370 25 395 -- 395
(g) 4 wire 4 sq. mm Mtr. 205 30 235 -- 235
(h) 4 wire 6 sq. mm Mtr. 300 30 330 -- 330
(i) 4 wire 10 sq. mm 455 30 485 -- 485
(C) with oval conduit/ PVC casing capping double lock type
(a) 2 wire 4 sq. mm Mtr. 90 5 95 -- 95
(b) 2 wire 6 sq. mm Mtr. 130 5 135 -- 135
(c) 2 wire 10 sq. mm Mtr. 218 7 225 -- 225
(d) 3 wire 4 sq. mm Mtr. 125 7 132 -- 132
(e) 3 wire 6 sq. mm Mtr. 188 7 195 -- 195
(f) 3 wire 10 sq. mm Mtr. 313 7 320 -- 320
(g) 4 wire 4 sq. mm Mtr. 160 10 170 -- 170
(h) 4 wire 6 sq. mm Mtr. 245 10 255 -- 255
(i) 4 wire 10 sq. mm Mtr. 405 10 415 -- 415
partial PVC pipe and drops in oval conduit/ PVC casing capping
(D)

(a) 2 wire 4 sq. mm Mtr. 100 5 105 -- 105


(b) 2 wire 6 sq. mm Mtr. 135 5 140 -- 140
(c) 2 wire 10 sq. mm Mtr. 223 7 230 -- 230
(d) 3 wire 4 sq. mm Mtr. 133 7 140 -- 140
(e) 3 wire 6 sq. mm Mtr. 203 7 210 -- 210
(f) 3 wire 10 sq. mm Mtr. 323 7 330 -- 330
(g) 4 wire 4 sq. mm Mtr. 165 10 175 -- 175
(h) 4 wire 6 sq. mm Mtr. 255 10 265 -- 265
(i) 4 wire 10 sq. mm Mtr. 415 10 425 -- 425
(E) in existing pipe
(a) 2 wire 4 sq. mm Mtr. 80 5 85 -- 85
(b) 2 wire 6 sq. mm Mtr. 115 5 120 -- 120
(c) 2 wire 10 sq. mm Mtr. 203 7 210 -- 210
(d) 3 wire 4 sq. mm Mtr. 113 7 120 -- 120
(e) 3 wire 6 sq. mm Mtr. 173 7 180 -- 180
(f) 3 wire 10 sq. mm Mtr. 298 7 305 -- 305
(g) 4 wire 4 sq. mm Mtr. 145 10 155 -- 155
(h) 4 wire 6 sq. mm Mtr. 230 10 240 -- 240

S.O.R. Mech 2019-20


Page 48 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
(i) 4 wire 10 sq. mm Mtr. 390 10 400 -- 400
Mains with ISI marked electrolyte stranded copper conductor, Non
PVC Zero Halogen free fire retardant insulated copper conductor,
1.4.3 insulated wire (HFFR) conforms to IS-694, erected in existing pipe
with 1.5 sq. mm copper conductor of same specifications for earth
continuity of following size.
(a) 2wire 0.75 sq.mm (w/o ECC) Mtr 17 3 20 20
(b) 2 wire 1.0 sq.mm (w/o ECC) Mtr 24 3 27 -- 27
(c) 2 wire 1.5 sq.mm Mtr 45 5 50 -- 50
(d) 2 wire 2.5 sq.mm Mtr 65 5 70 -- 70
(e) 2 wire 4.0 sq.mm Mtr 95 5 100 -- 100
(f) 2 wire 6.0 sq.mm Mtr 130 10 140 -- 140
(g) 2 wire 10.0 sq.mm Mtr 210 10 220 -- 220
(h) 3 wire 1.0 sq.mm Mtr 45 5 50 -- 50
(i) 3 wire 1.5 sq.mm Mtr 60 5 65 -- 65
(j) 3 wire 2.5 sq.mm Mtr 95 5 100 -- 100
(k) 3 wire 4.0 sq.mm Mtr 130 10 140 -- 140
(l) 4 wire 1.0 sq.mm Mtr 45 5 50 -- 50
(m) 4 wire 1.5 sq.mm Mtr 75 5 80 -- 80
(n) 4 wire 2.5 sq.mm Mtr 120 5 125 -- 125
(o) 4 wire 4.0 sq.mm Mtr 170 10 180 -- 180
Mains with ISI marked, 1.5kV grade electrolyte multi stranded,
annealed copper conductor with heat resistant PVC insulated
conforms to IS 694, IEC-227 erected in existing pipe of following size
1.4.4 (Specifically for control panel, relays, power switchgears, motor
starters & control wiring) with required size of copper lugs, nuts
and bolts if required.
(a) One wire 1.00 sq. mm Mtr. 9 1 10 -- 10
(b) One wire 1.50 sq. mm Mtr. 14 1 15 -- 15
(c) One wire 2.50 sq. mm Mtr. 23 2 25 -- 25
(d) One wire 4.00 sq. mm Mtr. 33 2 35 -- 35
(e) One wire 6.00 sq. mm Mtr. 53 2 55 -- 55
(f) One wire 10.00 sq. mm Mtr. 88 2 90 -- 90
(g) One wire 16.00 sq. mm Mtr. 137 3 140 -- 140
(h) One wire 25.00 sq. mm Mtr. 232 3 235 -- 235
(i) One wire 35.00 sq. mm Mtr. 297 3 300 -- 300
(j) One wire 50.00 sq. mm Mtr. 464 6 470 -- 470
(k) One wire 70.00 sq. mm Mtr. 664 6 670 -- 670
(l) One wire 95.00 sq. mm Mtr. 908 12 920 -- 920
(m) One wire 120.00 sq. mm Mtr. 1168 12 1180 -- 1180
(n) One wire 150.00 sq. mm Mtr. 1450 15 1465 -- 1465
Supplying and erecting Flexible PVC insulated multistrand multicore
1.4.5 1.1kV grade ISI marked copper wires of following size to be erected
as directed.
(a) 0.75 Sq.mm twin twisted Mtr. 11 1 12 -- 12
(b) 1.00 Sq.mm twin twisted Mtr. 13 1 14 -- 14
(c) 1.00 Sq.mm 2 core round/ flat PVC sheathed Mtr. 19 1 20 -- 20
(d) 1.50 Sq.mm 2 core round PVC sheathed Mtr. 29 1 30 -- 30
(e) 1.50 Sq.mm 3 core round PVC sheathed Mtr. 44 1 45 -- 45
(f) 1.50 Sq.mm 4 core round PVC sheathed Mtr. 64 1 65 -- 65
(g) 2.50 Sq.mm 2 core round PVC sheathed Mtr. 54 1 55 -- 55
(h) 2.50 Sq.mm 3 core round PVC sheathed Mtr. 74 1 75 -- 75
(i) 2.50 Sq.mm 4 core round PVC sheathed Mtr. 104 1 105 -- 105
(j) 4.00 Sq.mm 3 core round PVC sheathed Mtr. 123 2 125 -- 125

S.O.R. Mech 2019-20


Page 49 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
(k) 4.00Sq.mm 4 core round PVC sheathed Mtr. 173 2 175 -- 175
Providing & Erecting approved make following size of TV Co-axial
flexible cable comprising inner conductor of solid bare copper
1.4.6 insulated with Foam PE & Secondary conductor made of poly -
Aluminium film bonded Al. Braids @ suitable coverage overall
sheathed with black PVC insulation.
(a) RG 59 Mtr. 16 1 17 -- 17
(b) RG-6 Mtr. 29 1 30 -- 30
(c) RG - 6 CCS Mtr. 14 1 15 -- 15
(d) RG - 11 CCS Mtr 24 1 25 -- 25
(e) RG-11 Mtr. 44 1 45 -- 45
Supplying & erecting Delton or approved make telephone cable
electrolytic copper conductor PE insulation twisted in two pairs, &
wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR
1.4.7 outer Jacket suitable for telephone wiring & confirming to C-DOT
erected in existing pipe of following size of conductors & nos. of pairs
with necessary connections.
Conductor Size 0.5 mm
(A) Unarmoured
(a) One Pair Mtr. 7 2 9 -- 9
(b) Two Pairs Mtr. 12 2 14 -- 14
(c) Three Pairs Mtr. 17 2 19 -- 19
(d) Five Pairs Mtr. 28 2 30 -- 30
(e) Ten Pairs Mtr. 48 2 50 -- 50
(f) Twenty Pairs Mtr. 98 2 100 -- 100
(B) Armoured [Jelly Filled]
(a) Ten Pairs Mtr. 94 6 100 -- 100
(b) Twenty Pairs Mtr. 148 12 160 -- 160
(c) Fifty Pairs Mtr. 370 20 390 -- 390
(d) One Hundred Pairs Mtr. 670 35 705 -- 705
Supplying & erecting approved make LAN cable of following size in
1.4.8 existing pipe as per direction
(a) CAT - 5 Mtr 25 5 30 -- 30
(b) CAT - 5e Mtr 60 5 65 -- 65
(c) CAT - 6 Mtr 35 5 40 -- 40
(d) CAT - 6e Mtr 65 5 70 -- 70
Providing & erecting main Distribution (MDF) indoor type, back
1.4.9
mounted frame.
(a) Suitable for 10 pair Ea. 550 50 600 -- 600
(b) Suitable for 20 pair Ea. 950 50 1000 -- 1000
(c) Suitable for 50 pair Ea. 1450 50 1500 -- 1500
1.5 Concealed Boxes & Laminated Sheets
Supplying & erecting MS Box having 16 Gauge painted with red
oxide or Heavy duty PVC box erected flushed on wall or concealed
1.5.1 in wall with necessary plastering & finishing as directed of following
size.
(a) 100 mm x 100 mm x 75 mm(d) Ea. 35 10 45 -- 45
(b) 175 mm x 100 mm x 75 mm(d) Ea. 65 10 75 -- 75
(c) 200 mm x 250 mm x 75 mm(d) Ea. 75 12 87 -- 87
(d) 250 mm x 300 mm x 75 mm(d) Ea. 95 15 110 -- 110
Providing & Erecting 3mm thick Polycarbonate (PC) sheet with Sq. 1 0.5 1.50 -- 2
1.5.2 grooving as directed Inch
Providing & Erecting 3mm thick acrylic Sheet with grooving as Sq. 1 0.5 1.5 -- 2
1.5.3
directed Inch.
1.6 Wiring Accessories

S.O.R. Mech 2019-20


Page 50 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Providing & Erecting following shockproof tissino type accessories
1.6.1 erected on 3mm thick PC (Polycarbonate) sheet in PVC/ Metal Box
erected on wall/ ceiling.

(a) One no single pole 6A switch/ bell push Ea. 25 5 30 -- 30


(b) One no 3/5 pin 6A socket Ea. 25 5 30 -- 30
(c) One no single pole 16A switch Ea. 40 5 45 -- 45
(d) One no 6/16A Universal Socket Ea. 40 5 45 -- 45
One no single pole 16A switch & One no 6/16A Universal Socket Ea. 80 15 95 -- 95
(e) combined
One no single pole 16A switch & One no 6A/16A Universal Socket Ea. 110 15 125 -- 125
(f) combined with indicator & fuse
(g) Bakelite ceiling, rose Ea. 10 5 15 -- 15
(h) Bakelite lamp holder Ea. 15 5 20 -- 20
(i) Telephone Pin, Socket with suitable top Ea. 35 5 40 -- 40
(j) Jack type tissino Telephone outlet Ea. 35 5 40 -- 40
(k) Tissino type Neon ‘Indicator Lamp’ Ea. 15 5 20 -- 20
(l) Tissino type TV antenna socket Ea. 25 5 30 -- 30
(m) Tissino type 10A/16A Kitkat fuse Ea. 25 5 30 -- 30
(n) Electronic hume free EME socket type steps fan regulator Ea. 207 13 220 -- 220
Providing & erecting switch board for computer or electric apparatus
consisting of following items in single board erected on PVC/ Metal
board with 3mm thick PC (Polycarbonate)/ Acrylic sheet erected as
1.6.2 directed 1 no. 6A/16A universal plug-switch combined.
4 nos. 6A switch
4 nos. 6A 5 pin plug

(a) For Tissino Type Accessories Ea. 300 35 335 -- 335


(b) For Modular Type Accessories
Cat. I Ea. 830 60 890 -- 890
Cat. II Ea. 980 60 1040 -- 1040
Cat. III Ea. 1080 60 1140 -- 1140
1.6.3 Bakelite adopter for holder to be erected Ea. 6 2 8 -- 8
1.6.4 Starter for 20 watts/ 40 watts fluorescent tube Ea. 6 0 6 -- 6
Hanging bed switch/ bell push 5A erected on existing flexible wire Ea. 12 3 15 -- 15
1.6.4

1-6-6. 5A, 10 way bakelite connector duly erected on existing board Ea. 22 3 25 -- 25
1.6.7 15A, 10 way bakelite connector duly erected on existing board Ea. 40 5 45 -- 45
1.6.8 Providing & erecting ISI marked 3 pin plug top
(a) for 5/6 A., 240V Ea. 18 2 20 -- 20
(b) for 15/16A, 240V Ea. 28 2 30 -- 30
Supplying & erecting approved make call bell indicator with buzzing Ea. 130 20 150 -- 150
1.6.9 sound and red light indicating lamp with red light button to attend the
call suitable for 240V, 50c/s supply to be erected.
1.6.10 Call bell/ buzzer 250 volts, complete erected Ea. 25 5 30 -- 30
Call bell gong type suitable for 230 volts, 50 c/s AC supply complete Ea. 35 5 40 -- 40
1.6.11 erected

Decorative call bell ting-tong box type 250 volts complete erected Ea. 64 6 70 -- 70
1.6.12

Supplying & erecting electronic type cordless call bell erected on Ea. 250 0 250 -- 250
1.6.13 PVC/ Metal board having portable bell push working on DC & bell on
230V AC supply with cells/ battery.
Providing automatic staircase unit and light control switch with Ea. 650 50 700 -- 700
1.6.14 photocell & solid state circuits with loading capacity up to 1000 Watt

Supplying electrical insulation LT tape role with ISI marked having Ea. 15 0 15 -- 15
1.6.15 nominal width 1.8cms nominal length 9.0mtr nominal thickness
0.125mm and having self adhesive PVC

S.O.R. Mech 2019-20


Page 51 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
1.7 LADDERS
Supply of Fiberglas Step (A Type) Ladder- 4 FT having following Ea. 10800 0 10800 -- 10800
specifications.
It should have nonconductive structural moulded top, with slots to
keep tools close at hand, inside spreader braces, aluminium feet with
1.7.1 thick rubber tread, nonconductive full channel fibreglass and two
pairs of gusset support at the bottom step. All gussets are heavy duty
steel.
Capacity: 300 lbs., Step Size: 3”, Width: 19” Approx. , Spread: 29”
Approx., Wt.:8Kg Approx. , Cube: 4.05’

Supply of Fibreglass Step (A Type) Ladder- 6 FT having following Ea. 14100 0 14100 -- 14100
specifications:
It should have nonconductive structural moulded top with slots to
keep tools close at hand, inside spreader braces, aluminium feet with
1.7.2 thick rubber tread, nonconductive full channel fibreglass and two
pairs of gusset support at the bottom step. All gussets are heavy duty
steel.
Capacity: 300 lbs. , Step Size: 3”, Width: 23” Approx. , Spread: 41”
Approx. , Wt.: 11Kg Approx. , Cube : 6.2’

Supply of Fibreglass Step (A Type) Ladder- 8 FT having following Ea. 18400 0 18400 -- 18400
specifications:
It should have nonconductive structural moulded top with slots to
keep tools close at hand, inside spreader braces, aluminium feet with
1.7.3 thick rubber tread, nonconductive full channel fibreglass and two
pairs of gusset support at the bottom step. All gussets are heavy duty
steel.
Capacity: 300 lbs. , Step Size: 3”, Width: 26” Approx. , Spread: 54”
Approx., Wt.: 15 Kg Approx. , Cube: 9.5
Supply of Fibreglass Step (A Type) Ladder- 10 FT having following Ea. 22600 0 22600 -- 22600
specifications:
It should have nonconductive structural moulded top with slots to
keep tools close at hand, inside spreader braces, aluminium feet with
1.7.4 thick rubber tread, nonconductive full channel fibreglass, two pairs of
gusset support at the bottom step. All gussets are heavy duty steel.
Capacity: 300 lbs, Step Size: 3”, Width: 29” Approx., Spread: 66”
Approx. , Wt.: 19 Kg Approx., Cube: 12.54’

Supply of Fibreglass Step Trestle (A Type) Ladder- 6 FT having Ea. 16500 0 16500 -- 16500
following specifications:
It should have heavy gauge steel hinges suitable for industrial
application, inside spreader braces, aluminium feet with thick rubber
tread, nonconductive full channel fiberglass, two pairs of gusset
1.7.5 support at the bottom step. All gussets are heavy duty steel. It should
have steps on both the sides for climbing. Capacity: 300 lbs.
Step Width: 3”, Bottom Width:23” Approx. , Spread :
52”Approx.Wt.:13 Kg, Approx. Cube : 6.53’

Supply of Fibreglass Step Trestle (A Type) Ladder- 8 FT having Ea. 22000 0 22000 -- 22000
following specifications:
It should have heavy gauge steel hinges suitable for industrial
application, inside spreader braces, aluminium feet with thick rubber
1.7.6 tread, nonconductive full channel fibreglass, two pairs of gusset
support at the bottom step. All gussets are heavy duty steel. It should
have steps on both the sides for climbing. Capacity: 300 lbs., Step
Width: 3”, Bottom Width: 26” Approx.
Spread: 67” Approx. , Wt.: 20 Kg Approx. , Cube: 9.51’
Supply of Fibreglass Step Trestle (A Type) Ladder- 10 FT having Ea. 26000 0 26000 -- 26000
following specifications:
It should have heavy gauge steel hinges suitable for industrial
application, inside spreader braces, aluminium feet with thick rubber
tread, nonconductive full channel fibreglass, two pairs of gusset
1.7.7
support at the bottom step. All
gussets are heavy duty steel. It should have steps on both the sides
for climbing.
Capacity: 300 lbs., Step Width: 4”, Bottom Width: 29” Approx.
Spread: 83” Approx. , Wt.: 27 Kg Approx., Cube: 13.44’

S.O.R. Mech 2019-20


Page 52 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Supply of Fibreglass Platform Step (A Type) Ladder- 6 FT having Ea. 19600 0 19600 -- 19600
following specifications:
It should have large fully serrated
platform 15” wide 20” deep which locks ladder, aluminium feet with
1.7.8 thick rubber tread, top rail guard to serve as a railing, two pairs of
gusset support at the bottom step. All gussets are heavy duty steel.
Capacity: 300 lbs., Step Width: 3’ Approx. , Spread: 50” , Width:
26.5” Approx. , Wt.: 16 Kg Approx. , Cube: 8.15’"
Supply of Fibreglass Platform Step (A Type) Ladder- 8 FT having Ea. 24000 0 24000 -- 24000
following specifications:
It should have large fully serrated
platform 15” wide 20” deep which locks ladder, aluminium feet with
1.7.9 thick rubber tread, top rail guard to serve as a railing, two pairs of
gusset support at the bottom step. All gussets are heavy duty steel.
Capacity: 300 lbs., Step Width: 3’ Approx., Spread: 62” , Width: 29.5”
Approx., Wt.: 22 Kg Approx., Cube: 11.62
Supply of Fibreglass Platform Step (A Type) Ladder- 10 FT having Ea. 28300 0 28300 -- 28300
following specifications:
It should have large fully serrated
platform 15” wide 20” deep which locks ladder, aluminium feet with
1.7.10 thick rubber tread, top rail guard to serve as a railing, two pairs of
gusset support at the bottom step. All gussets are heavy duty steel.
Capacity: 300 lbs. , Step Width: 4’ Approx. , Spread: 75”, Width: 32”
Approx. , Wt.: 29 Kg Approx. , Cube: 15.31
2. Lamps & Fittings
2.1 LED Lamp & Tubes
2.1.1 R&B Approved make LED tube- 9 watt Ea. 433 0 433 12% 485
2.1.2 R&B Approved make LED tube- 18 watt Ea. 577 0 577 12% 646
2.1.3 R&B Approved make LED tube- 21 watt Ea. 613 0 613 12% 687
2.2 LED Light fixture
Supplying and erecting R&B approved make of LED batten for Ea. 217 0 217 18% 256
2.2.1 multipurpose application made from polycarbonate housing with 1 x
9/ 18/ 21W T8 with all accessories

Supplying and erecting R&B approved make of LED batten for Ea. 325 0 325 18% 384
2.2.2 multipurpose application made from polycarbonate housing with 2 x
9/ 18/ 21W T8 with all accessories
Supplying and erecting approved R&B make of LED Downlighter
2.2.3 recessed mounted for Indoor application
(a) With 10 watt LED lamp Ea. 866 0 866 18% 1022
(b) With 18/ 20 watt LED lamp Ea. 945 0 945 18% 1115
Supplying and erecting R&B approved make of LED Downlighter
2.2.4 surface mounted for Indoor application

(a) With 10 watt LED lamp Ea. 758 0 758 18% 894
(b) With 18/ 20 watt LED lamp Ea. 1010 0 1010 18% 1192
Supplying and erecting R&B approved make of LED recessed
2.2.5 mounted luminaire with rear reflector suitable for office and laboratory
applications
(a) With 20 watt LED lamp Ea. 1803 0 1803 12% 2019
(b) With 36 watt LED lamp Ea. 2452 0 2452 12% 2746
(c) With 40 watt LED lamp Ea. 3029 0 3029 12% 3392
Supplying and erecting R&B approved make of LED Suraface
2.2.6 mounted luminaire with rear reflector suitable for office and laboratory
applications
(a) With 20 watt LED lamp Ea. 2019 0 2019 12% 2261
(b) With 36 watt LED lamp Ea. 3245 0 3245 12% 3634
(c) With 40 watt LED lamp Ea. 3389 0 3389 12% 3796
Supplying and erecting R&B approved make of LED Weatherproof
2.2.7
tubelight fixture with tube
With 1 x 18 watt LED lamp Ea. 1190 0 1190 12% 1333
With 1 x 36 watt LED lamp Ea. 2452 0 2452 12% 2746

S.O.R. Mech 2019-20


Page 53 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Supplying and erecting R&B approved make of 10 watt LED Ea. 1154 0 1154 12% 1292
2.2.8
Bulkhead luminaire with diffuser
2.3 Industrial Lighting
Supplying and erecting LED wellglass with die cast alluminium
2.3.1 housing with polycarbonate cover robust construction industrial type
fitting with IP-66 Protection.
(a) With 30 watt LED Lamp Ea. 2740 0 2740 12% 3069
(b) With 40 watt LED Lamp Ea. 3966 0 3966 12% 4442
Supplying and erecting industrial LED high bay luminaire front
2.3.2 toughened glass with discreate high power.
(a) With 90 watt LED Lamp Ea. 9734 0 9734 12% 10902
(b) With 150 watt LED Lamp Ea. 12978 0 12978 12% 14535
Supplying and erecting industrial LED mid bay luminaire front
2.3.3
toughened glass with discreate high power.
(a) With 80 watt LED Lamp Ea. 8292 0 8292 12% 9287
(b) With 100 watt LED Lamp Ea. 9734 0 9734 12% 10902
Providing and erecting heavy duty flood light Luminaire with High
2.3.4
Pressure die Cast Housing with IP 65.
(a) With 80 watt LED lamp Ea. 8292 0 8292 12% 9287
(b) With 150 watt LED lamp Ea. 10815 0 10815 12% 12113
(c) With 200 watt LED lamp Ea. 8292 0 8292 12% 9287
(d) With 240 watt LED lamp Ea. 8292 0 8292 12% 9287
2.4 Landscape Lighting
Supplying and erecting R&B approved make watertight, integral Ea. 3389 0 3389 12% 3796
2.4.1 flying saucer type post top lantern IP 65, suitable for 25 Watt LED
lamp, with other necessary accessories.
Supplying and erecting approved make, 6 Watt LED Wall light tri Ea. 4038 0 4038 12% 4523
2.4.2
ngular down and up-down
2.5 Flourocent tubes
R&B Approved make fluorescent tube (T8) 60 cms. 18/ 20 watt Ea. 44 0 44 12% 49
2.5.1

2.5.2 R&B Approved make fluorescent tube (T8) 60 cms. 36 watt Ea. 57 0 57 12% 64
2.5.3 R&B Approved make 9 watt compact fluorescent lamp Ea. 67 0 67 12% 75
2.5.4 R&B Approved make 11 watt compact fluorescent lamp Ea. 73 0 73 12% 82
2.5.5 R&B Approved make 18 watt compact fluorescent lamp Ea. 124 0 124 12% 139
2.6 Street Lighting & Solar Lighting
R&B Approved make street light luminaire with one no suitable for-
2.6.1 LED lamp complete with alluminium PDC housing toughened glass
with cover IP 66 Protection.
(a) With 70 watt LED lamp Ea. 4687 0 4687 12% 5249
(b) With 90 watt LED lamp Ea. 6850 0 6850 12% 7672
(c) With 120 watt LED lamp Ea. 8652 0 8652 12% 9690
Supplying and erecting R&B approved make, standalone solar LED
2.6.2 street light system with tubular pole, polyacryline PV panel solar
tubular battery. Battery box pole and mechanical hardware
(a) With 15 watt LED lamp Ea. 30138 0 30138 12% 33755
(b) With 30 watt LED lamp Ea. 42395 0 42395 12% 47482
(c) With 60 watt LED lamp Ea. 89116 0 89116 12% 99810
(d) With 70 watt LED lamp Ea. 101157 0 101157 12% 113296
Supplying and erecting R&B approved make, standalone solar LED
2.6.3 mini mast system with tubular pole, polyacryline PV panel solar
tubular battery. Battery box pole and mechanical hardware.
(a) with 3 x 33W Flood light, 8M High Pole Ea. 182413 0 182413 12% 204303
(b) with 3 x 45W Flood light, 10M High Pole Ea. 221347 0 221347 12% 247909
3 SWITCHGEARS & DISTRIBUTION BOARDS
3.1 BUSBAR CHAMBERS

S.O.R. Mech 2019-20


Page 54 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Supply & erection bus bar chamber conforming to IS-375 fabricated
from 16 G.M.S.sheet, dust & vermin proof having hinged door with
rubber gasket and necessary busbar supports with aluminium busbar
having current density not more than 0.8 A/ sq. mm (Rated current/
3.1.1 cross section area) duly wrapped with colour insulation tape for
phase sequence, three phase & neutral each suitable for following
current capacity with necessary painting mounted on wall or pedestal
frame of required size with necessary connections.
(a) Suitable for 63/ 100 A Rmt 2600 160 2760 -- 2760
(b) Suitable for 200 A Rmt 3050 200 3250 -- 3250
(c) Suitable for 300 A Rmt 5210 250 5460 -- 5460
(d) Suitable for 400 A Rmt 5785 325 6110 -- 6110
Supply & erection bus bar chamber confirming to IS-375 fabricated
from 16 G.M.S. sheet, dust & vermin proof having hinged door with
rubber gasket and necessary busbar supports with COPPER busbar
having current density not more than 1.6 A/ sq. mm (Rated current/
3.1.2 cross section area) duly wrapped with colour insulation tape for
phase sequence, three phase & neutral each suitable for following
current capacity with necessary painting mounted on wall or pedestal
frame of required size with necessary connections.

(a) Suitable for 63/100 A Rmt 3990 160 4150 -- 4150


(b) Suitable for 200 A Rmt 5180 200 5380 -- 5380
(c) Suitable for 300 A Rmt 7760 250 8010 -- 8010
(d) Suitable for 400 A Rmt 9375 325 9700 -- 9700
3.2 PANEL MOUNTING BUSBARS
Supplying and erecting triple pole & neutral 440V/ 500V panel
mounting Aluminium Busbars with four equal Nos. of bus having
current density not more than 0.8 A/ sq. mm (Rated current/ cross
section area) duly wrapped with colour insulating tape for phase
3.2.1
sequence of following current carrying capacity, erected with
necessary bus bar supports/ insulators, main cable socket to each
busbar, erected in existing cubicle panel with necessary connections.

(a) Suitable for 100 A Rmt 620 80 700 -- 700


(b) Suitable for 200 A Rmt 1020 80 1100 -- 1100
(c) Suitable for 300 A Rmt 1400 160 1560 -- 1560
(d) Suitable for 400 A Rmt 2180 160 2340 -- 2340
(e) Suitable for 630 A Rmt 3090 160 3250 -- 3250
(f) Suitable for 800 A Rmt 6420 210 6630 -- 6630
(g) Suitable for 1200 A Rmt 8200 250 8450 -- 8450
Supplying and erecting triple pole & neutral 440V / 500V panel
mounting Copper Busbars with four equal Nos. of electrolyte bus
having current density not more than 1.6 Amp. / sq.mm (Rated
current / cross section area) duly wrapped with colour insulating tape
3.2.2
for phase sequence of following current carrying capacity, erected
with necessary bus bar supports /insulators, main cable socket to
each bar, erected in existing cubical panel with necessary
connections.
(a) Suitable for 100 A Rmt 1760 80 1840 -- 1840
(b) Suitable for 200 A Rmt 2920 80 3000 -- 3000
(c) Suitable for 300 A Rmt 4450 160 4610 -- 4610
(d) Suitable for 400 A Rmt 6700 160 6860 -- 6860
(e) Suitable for 630 A Rmt 9730 160 9890 -- 9890
(f) Suitable for 800 A Rmt 12160 200 12360 -- 12360
(g) Suitable for 1200 A Rmt 15200 250 15450 -- 15450
3.3 EARTH LEAKAGE CIRCUIT BREAKERS

S.O.R. Mech 2019-20


Page 55 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Approved make ELCBs/ RCCBs conforming to IS: 12640 and having
sensitivity of 30 mA and Short Circuit withstand capacity of 6 KA and
3.3.1 suitable for operation on single phase 240 V. having characteristic of
quick action & tripping with all advance feature & do not incorporate
any electronic component. for following Max.
(a) 25 A DP
Cat. I Ea. 1730 50 1780 -- 1780
Cat. II Ea. 1850 50 1900 -- 1900
Cat. III Ea. 2250 50 2300 -- 2300
(b) 40 A DP
Cat. I Ea. 1870 50 1920 -- 1920
Cat. II Ea. 1960 50 2010 -- 2010
Cat. III Ea. 2560 50 2610 -- 2610
(c) 63 A DP
Cat. I Ea. 2120 50 2170 -- 2170
Cat. II Ea. 2480 50 2530 -- 2530
Cat. III Ea. 2550 50 2600 -- 2600
R&B Approved make ELCBs / RCCBs conforming to IS: 12640 and
having sensitivity of 30 mA and Short Circuit withstand capacity of 6
KA and suitable for operation on 3 phase and neutral 415V. having
3.3.2 characteristic of quick action & tripping with all advance feature & do
not incorporate any electronic component for following Max. rating
erected as directed.

(a) 25 A FP
Cat. I Ea. 2040 70 2110 -- 2110
Cat. II Ea. 2260 70 2330 -- 2330
Cat. III Ea. 2930 70 3000 -- 3000
(b) 40 A FP
Cat. I Ea. 2180 70 2250 -- 2250
Cat. II Ea. 2350 70 2420 -- 2420
Cat. III Ea. 3010 70 3080 -- 3080
(c) 63 A FP
Cat. I Ea. 2390 70 2460 -- 2460
Cat. II Ea. 2790 70 2860 -- 2860
Cat. III Ea. 3480 70 3550 -- 3550
(d) 100 A FP (100 mA Sensitivity)
Cat. II Ea. 2860 70 2930 -- 2930
Cat. III Ea. 4970 70 5040 -- 5040
Supplying & erecting R&B approved make RCBO (Electro magnetic
type only) working on residual current device having 6 KA short
circuit breaking capacity and 30 mAmp. Sensitivity & 30 mili sec.
3.3.3 tripping time conforming to IS 12640 test knob facility trip free
mechanism operating for rated leakage at nominal ten volt, complete
erected including all materials lugs screws etc. completed.

(a) 6A / 10A / 16A / 20A / 25A 2 pole single phase Cat. II Ea. 2050 70 2120 -- 2120
(b) 32A / 40A, 2 pole Single Phase Cat. II Ea. 2200 70 2270 -- 2270
(c) 63 A, 2 pole Single Phase Cat. II Ea. 2660 70 2730 -- 2730
(d) 6A to 25 A, 4 Pole Three Phase Cat. II Ea. 2330 70 2400 -- 2400
(e) 32A to 40 A, 4 Pole Three Phase Cat. II Ea. 2460 70 2530 -- 2530
(f) 63A, 4 pole Three Phase Cat. II Ea. 3240 70 3310 -- 3310
Supplying & fixing box for housing ELCB / ELCB + MCB combination
made of 18 SWG sheet steel duly powder coated with gasket, dust &
3.3.4
vermin proof bakelite shield two earthing terminals for following type
of RCCB, ELCB, ELCB + MCB
(a) For 2 pole Ea. 270 50 320 -- 320

S.O.R. Mech 2019-20


Page 56 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
(b) For 4 Pole Ea. 470 50 520 -- 520
3.4 DANGER NOTICE BOARDS
Supply & erectionmetallic vitrified danger notice board for Medium Ea. 65 15 80 -- 80
3.4.1 Voltage installation to be erected as per IS.
Supply & erectionmetallic vitrified danger notice board for High Ea. 80 15 95 -- 95
3.4.2 Voltage installation to be erected as per IS.
Providing & erecting Medium Voltage Danger Notice Board sticker of Ea 20 10 30 -- 30
3.4.3
standard size
Providing & erecting High Voltage Danger Notice Board sticker of Ea 30 10 40 -- 40
3.4.4
standard size
3.5 EARTHING
Supply & erectionrequired size Aluminium strip for earthing of H.T. Kg. 200 20 220 -- 220
3.5.1 OCB / ACB / Transformer, LT panel board, Motors etc. using copper
clamp.
Supply & erectionrequired size HOT deep Galvanised iron strip for Kg. 70 20 90 -- 90
3.5.2 earthing of H.T. , OCB/ ACB/ Transformer LT panel board, Motors
etc. using proper clamp.
Supply & erectionrequired size Copper strip for earthing of H.T. OCB Kg. 670 40 710 -- 710
3.5.3 / ACB/ Transformer, LT panel board, Motors etc. using copper clamp.

3.5.4 Supply & erectionAnnealed bare Copper wire 8 to 16 SWG. Kg. 670 40 710 -- 710
Supply & erection HOT deep Galvanised iron strip wire 8 to 16 SWG. Kg. 70 20 90 -- 90
3.5.5
Pipe type earthing having 150 cms.long and 2.5 cms. dia. galvanised Ea. 350 80 430 -- 430
3.5.6(a) iron pipe with coupling and buch buried in specially prepared earth pit
complete with necessary 8 SWG earth wire.

Pipe type earthing with 40 mm dia 2.5 mtr long 'B' grade G.I. pipe Ea. 810 150 960 -- 960
with necessary coupling buch buried in specially prepared earth pit &
3.5.6(b)
G.I. earth wire of 8 SWG erected & connected as directed (For panel)

For using salt and charcoal / coke as required for pipe type earthing. Ea. 180 20 200 -- 200
3.5.6(c)

Add Extra for excavation in Semi hard rock (Murrum) by dry and wet Ea. 0 130 130 -- 130
3.5.7
blasting and chiselling for pipe type earthing
Add Extra for excavation in Hard rock by dry and wet blasting and Ea. 0 325 325 -- 325
3.5.8 chiselling for pipe type earthing.
Supplying & erecting earth pit of minimum bore dia.150mm size
approved make Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS 3043-1987 made of corrosion free G.I.Pipes
having Outer pipe dia of 50mm having 80-200 Micron galvanising,
3.5.9
Inner pipe dia of 25 mm having 200-250 Micron galvanising,
connection terminal dia of 12mm with constant ohmic value
surrounded by highly conductive compound with high charge
dissipation suitable for following type of applications.
For Electrical Installation up to 440V in normal soil Ea. 6630 520 7150 -- 7150
(a) Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg.
For Electrical installation up to 11 KV in normal soil. Ea. 8370 600 8970 -- 8970
(b) Length of Pipe : 2.00 mtrs
Back filling Compound :1 no. Bag of 25 Kg.
For Electrical Installation covering Transformer Neutrals, Lightning Ea. 12550 900 13450 -- 13450
arrester Earthing, A.C.Plant & Sensitive Computer System(like
(c) Automation, SCADA) i.e independent Earthing in normal soil.
Length of Pipe : 3.00 mtrs
Back filling Compound :2 nos Bags of 25 Kg.
Supplying & erecting in earthpit of minimum bore dia. 225mm size
ASH or approved make Safe Earthing Electrode consisting Pipe-
in-Pipe Technology as per IS 3043-1987 made of corrosion free
G.I.Pipes having Outer pipe dia of 80 mm having 80-200 Micron
galvanising, Inner pipe dia of 40 mm having 200-250 Micron
3.5.10
galvanising, connection terminal dia of 14 mm with constant ohmic
value surrounded by highly conductive compound with high charge
dissipation suitable for following type of applications.

S.O.R. Mech 2019-20


Page 57 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
For electrical installation up to 440 V Ea. 8580 520 9100 -- 9100
(a) Length of Pipe - 1 Mtr
Back filling compound - 1 Nos. of Bag of 15 Kgs.
For Electrical installation up to 11 KV located in other than normal Ea. 10450 600 11050 -- 11050
soil i.e. Soft Rock, Marshy Soil etc.
(b) -Length of Pipe : 2 mtr
-Back filling Compound :1 no. Bag of 25 Kg.
For Electrical Installation covering Transformer Neutrals, Lightning Ea. 15600 900 16500 -- 16500
arrester Earthing, Instrumentation (like PLC Panel, SCADA)i.e.
independent Earthing located in other than normal soil i.e.Soft Rock,
(c) Marshy Soil etc..
-Length of Pipe : 3 Mtrs.
-Back filling Compound :2 nos Bags of 25 Kg.
Providing one bag of 25 Kg. Additional Back Filling Compound Ea. 1100 0 1100 -- 1100
3.5.11
suitable for safe earthing device.
Supplying & erecting funnel type earthing having earth plate of
following size burred in specifically prepared earth pit 3 mtr. below
ground with 40 kg. charcoal and salt with alternate layers of charcoal
& salt, 20mm.dia. G.I. pipe with Funnel with a wire mesh for watering
& bricks masonry block, C.I. Cover complete as per para 7.3 of IS
3.5.12 3043 with necessary length of double Galvanised Iron / copper earth
wire No 6 SWG bolted with lug to the plate and covered in 12 mm
dia. G.I. pipe 2.5 mtr long complete connected to the nearest switch
gear with end socket as per direction & duly tested by earth tester
confirming to IS (As per drawing) with following specification

(A) With 30 x 30 x 0.35 cms: C.I. earth plate Ea. 1900 800 2700 -- 2700
(B) With 45 x 45 x 0.35 cms. C.I. earth plate Ea. 2200 800 3000 -- 3000
(C) with 60 x 60x 0.315 cms. Copper earth Plate Ea. 8400 800 9200 -- 9200
ADD Extra for excavation in Semi hard rock (Murrum) by dry and wet Ea. 10 250 260 -- 260
3.5.13 blasting and chiselling for funnel type earthing of above

ADD Extra for excavation in Hard rock by dry and wet blasting and Ea. 0 380 380 -- 380
3.5.14 chiselling for funnel type earthing of above .

Cast iron earth plate size 30 X 30 X 0.35 cms. buried in specially Ea. 600 200 800 -- 800
prepared 2.5 Mtr. deep earth pit complete with necessary G.I. strip in
3.5.15 G.I. pipe 2 Mtr. long with coupling and G.I. plug for earthing of switch
gear, conduit run or power plug etc.
Cast iron earth plate size 45 X 45 X 0.35 cms. buried in Ea. 800 200 1000 -- 1000
specially prepared 2.5 Mtr. Deep earth Pit complete with necessary
3.5.16 G.I. strip in G.I. pipe 2 Mtr. long with coupling and G.I. plug for
earthing of switch gear, conduit run or power plug etc.
Maintenance free Chemical Earthing Ea. 5356 0 5356 -- 5356
Supply of UL Listed Maintenance Free Earthing System made of
copper bonded rod of 10 feet (3 mtr approx.)
length, 17.2 mm dia. (Minimum copper bonding shall be 0.25mm,
3.5.12 suitable for 25 kA fault current) along with Rod-to-Conductor
connectors, 95% pure Carbon-Based
Earth enhancement material of 30kg, Pit Cover as required and as
per specification.
Supply of UL complying Maintenance Free Earthing System made of Ea. 2266 0 2266 -- 2266
copper bonded rod of 4 feet (1.2 mtr approx.) length, 17.2 mm dia.
(Minimum copper bonding shall be 0.25mm) along with Rod-to-
3.5.13
Conductor connectors, 95% pure Carbon-Based Earth enhancement
material of 5kg, Pit Cover as required and as per
specification.
3.6 METALLIC ENCLOSURE

S.O.R. Mech 2019-20


Page 58 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Providing & erecting weather proof, dust & vermin proof, floor
mounted front operated indoor type cubical switchgear enclosure
having IP-64 protection made from 14 SWG thick CRC M.S. sheet
for outer body & doors, 16 SWG thick CRC M.S.sheet for internal
partitions with necessary supporting angles, flats including cutting,
bending, drilling, welding, riveting with internal partitions & cable alley
as per requirements & instruction of engineer-in-charge with erection
of supplied switch gears, BUSBARS, with suitable size of inter
connecting PVC copper wire / copper-aluminium strips, rubber
grommets, rib, bakelite control fuses for measuring instruments,
3.6.1 earth bus & earth bolts, foundation flange - bolts-base Plates,
sufficient nos. of hinged doors, handles with locking arrangement and
rubber gasket complete. The Panel shall be painted with epoxy
powder coating. (The rates excludes the cost of switchgears, bus
bars, inter connecting mains & Copper Aluminium strips, meters,
Fuses etc. The dimension shall be measured excluding base beams)
The panel shall be supplied with following approved manufacturers
with following size.

The standard companies switch gear shall be used and only


manufacturers at CPRI approved factory and shall be certified by that
(A) company whose switch gears are used after fabrication for beneficial
use
(a) (i) with 350mm depth Smt 16600 810 17410 -- 17410
(b) (ii) with 550 mm. Depth Smt 21840 810 22650 -- 22650
(c) (iii)with 750 mm. Depth Smt 33280 810 34090 -- 34090
(d) (iv) with 1000 mm. depth Smt 44270 810 45080 -- 45080
(B) locally fabricated panel board
(a) (i) with 350 mm depth Smt 11650 580 12230 -- 12230
(b) (ii) With 550 mm. Depth Smt 15280 580 15860 -- 15860
(c) (iii) with 750 mm. Depth Smt 23290 580 23870 -- 23870
(d) (iv) with 1000 mm. depth Smt 31300 580 31880 -- 31880
Steel cover as per drawing using 16 SWG M.S.sheet of following
depth, to house the switch gear etc. complete with locking
3.6.2 arrangement and lock with duplicate keys per cupboard and door
handles erected with necessary support and painting. [One coat red
oxide and two coat enamel paint]
(A) with angle iron frame
(a) For 25 cms. Depth Smt 3770 390 4160 -- 4160
(b) For 40 cms. Depth Smt 4550 390 4940 -- 4940
(B) without angle iron frame
(a) For 25 cms. Depth Smt 2600 390 2990 -- 2990
(b) For 40 cms. depth Smt 3120 390 3510 -- 3510
Meter cover made from multi chamber hollow PVC sections of 20 Smt 3650 250 3900 -- 3900
mm thick having all the corner joints with PVC solution angles
without using any screws, nails shutters having required size of eye
3.6.3
glass and with necessary locking arrangement hinged with box. The
back of meter box should be fixed with timber. Hold fast for holding
screws or nut bolts.
Providing , erecting , fabricating the M.S. structure as per Kg. 67 23 90 -- 90
requirement on site incorporating proper size of M.S. angles, flats,
bars, channels, sections complete with cutting, welding, grinding &
3.6.4(a)
finishing duly painted with one coat of red oxide with erection on site
as per direction of engineer in charge with necessary grouting,
cementing, plastering & finishing complete.
Fabricating the box type items made from M.S. Sheet with A.I. Kg. 170 40 210 -- 210
supports, wings, doors, handles other hardware materials as per
3.6.4(b) requirement design with finishing by three tank powder coating
processed inside and outside painted, erected as directed including
minor civil work.

S.O.R. Mech 2019-20


Page 59 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Add for specialised type of fabrication work on height by using Kg. 7 23 30 -- 30
3.6.5 scaffolding or tower stair or rope as well as for lift machine room &
siren works.
Painting by cleaning, the surface and applying one coat of primer and Smt 120 50 170 -- 170
3.6.6 two coats of enamel paint for meter cup-board or base plate suitable
to match the wall finish
Painting the number and words for inventory Identification on erected
fittings / equipment’s or Such accessories as may required with good
3.6.7
quality of enamelled paint as directed by engineer in charge.

(a) up to 20 characters, up to 50 mm height. Ea. 15 10 25 -- 25


(b) Add. for additional character. Ea. 2 0 2 -- 2
(c) Add for additional each 25mm. height Ea. 4 2 6 -- 6
Supplying and erecting nuwood 12mm thick on existing angle iron Smt 370 80 450 -- 450
3.6.8
frame or wooden patti
4.1 SUBSTATION EQUIPMENT & MAINTAINANCE
Providing & erecting dust & vermin proof busduct fabricated from
cold rolled 14 SWG CRCA sheet steel completed with required
size of electrolytic grade copper / high grade aluminium. 63401 WP
confirming to IS: 5082 for three phase & neutral of following
capacities erected on SMC / DMC supporters designed & placed
considering the most destructive fault conditions. The sheet metal
work shall be dephosphated and given alkaline treatment and subject
4.1.1
to seven tank process for cleaning oil, grease, dirt etc. Epoxy paint
should be applied after application of two coats of primer. All
BUSBARS should be insulated with close fitting sleeve of hard,
smooth, dust & dirt free heat , shrunk PVC insulation of high
dielectric strength. Busbar should be thoroughly cleaned at joint
locations and a suitable contact grease and spring washers shall be
used at joints.
(A) Aluminium Bus
(a) 800 A Mtr. 10620 1265 11885 -- 11885
(b) 1200 A Mtr. 14220 1265 15485 -- 15485
(c) 1600 A Mtr. 17220 1265 18485 -- 18485
(B) Copper Bus
(a) 800 A Mtr. 17315 1265 18580 -- 18580
(b) 1200 A Mtr. 22900 1265 24165 -- 24165
(c) 1600 A Mtr. 29800 1265 31065 -- 31065
4.2 SUBSTATION EQUIPMENT
Providing printed instruction chart both in English and Gujarati and . 144 6 150 -- 150
4.2.1 duly framed with front glasses for treatment of person suffering from
Electric shock.
Providing pair of rubber hand gloves suitable for working on 11kV/ Ea. 250 5 255 -- 255
4.2.2 22kV supply.
Supplying rubber matting of 6 mm thickness as per IS 5424 and of Sq.M 990 0 990 -- 990
4.2.3 required length and breadth with good insulation property for 22 KV tr
Supplying rubber matting of 12 mm thickness as per IS 5424 and of Sq.M 2000 0 2000 -- 2000
4.2.4
required length and breadth with good insulation property for 22 KV tr
Supplying stand first AID box with antiseptic cream, medicine for use Ea. 350 0 350 -- 350
on wounds due burn, crepe bandage, gauge bandage, medicated
4.2.5 ready to use bandage (Band-aid) adhesive tape for medicinal user,
Scissors, anti-septic solution (savlon or similar) etc. (All above
contents shall be of standard makes)
Supplying FIRE bucket round bottom of 9 litres capacity made out Ea. 250 0 250 -- 250
of 24 gauge G.I. sheet with extra handle at bottom duly painted white
4.2.6
inside and Red out side with FIRE mark, filled with dry-sand and
kept on existing stand provided or hung on wall hook.
Supplying and erecting floor mounting stand for keeping four nos. of Ea. 1050 50 1100 -- 1100
FIRE buckets comprising 1500 mm in length, 900 mm height frame
4.2.7 made out of 30mm X 30 mm X 4 mm angle iron with cross supports
for legs, welded with 4 hooks and duly painted with one coat of red
lead and two coats of approved enamelled silver paint.

S.O.R. Mech 2019-20


Page 60 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
Wall hook 22 to 25 cms. projection for keeping fire buckets made out Ea. 47 23 70 -- 70
4.2.8 of 15 mm dia. M.S rod grouted in wall to a depth of minimum 15 cms.

Transformer oil having good resistance to high electrical stress, high Ltr. 85 0 85 -- 85
di-electric strength (50kV) low viscosity, low pour point, high flash
4.2.9
point and excellent thermal properties for efficient heat transfer and
cooling as per I.S.335 -1972.
Filtration of transformer oil as per I.S.S. for removal of moisture,
carbon, slurry etc. by means of circulating oil through vacuum pump
4.2.10 from heating elements and filters to with stand the breaking strength
of the oil above 40kV beyond one minute tested in oil testing Kit.
(a) on site Ltr. 0 9 9 -- 9
(b) at factory Ltr. 0 7 7 -- 7
4.3 SUBSTATION MAINTENANCE
Carryout routine maintenance, servicing and testing of HT VCB Job 0 2500 2500 -- 2500
(rating upto 1250 A) including cleaning of Breaker mechanism,
4.3.1 auxiliary male-female contacts, time leg fuse contact coil contacts,
overload and earth fault trip device control wiring contacts, lowering
and lifting mechanism on trolley drawout mechanism etc.
Carry out routine maintenance and servicing and testing of LT ACB Job 0 1950 1950 -- 1950
(rating upto 2000 Amp) by cleaning fix contacts, moving contacts and
4.3.2 arc chutes including servicing and putting the ACB in perfect
working order after setting all relays and ON/ OFF mechanism.

Carry out routine maintenance and servicing of LT cubicle panel Job 0 2500 2500 -- 2500
board having approximately 15 to 22 Nos. of switches cleaning and
servicing the contacts tightning the connections of incoming and
4.3.3 outgoing cables. and checking the operating mechanism for smooth
functioning of switches. and putting them in smooth working order.

Carrying out the testing of earth fault and overload relay on LT side. Job 0 1950 1950 -- 1950
4.3.4 Removing the fault of relay by checking the trip devices, control
wiring and putting the same in working order.
Testing and calibration of protective relays and metering devices Job 0 2200 2200 -- 2200
4.3.5 through primary Injection up to 3000 AMP (3 coils sets)
Routine maintenance of Transformer in operation covering check for Job 0 4300 4300 -- 4300
Insulation Resistance, oil breakdown strength, reconditioning
4.3.6 /replacement of silica gel, cleaning of transformer & topping up of oil
if required. (excluding cost of transformer oil)
4.3.7 Testing of transformer oil for dielectric breakdown strength. Job 0 320 320 -- 320
Measurement of earthing resistance by loop test after isolating & Job 0 1950 1950 -- 1950
4.3.8
cleaning joint.
Dismantling and refitting of transformer including cost of required
4.3.9
new M.S. bolts of following capacity transformer
(a) 250 kVA Ea. 455 1495 1950 -- 1950
(b) 315 kVA Ea. 455 1495 1950 -- 1950
(c) 500 kVA Ea. 375 1725 2100 -- 2100
(d) 750 kVA Ea. 315 2185 2500 -- 2500
(e) 1000 kVA Ea. 425 2875 3300 -- 3300
(f) 1600 kVA Ea. 550 3450 4000 -- 4000
Replacing old and unserviceable gasket of Top cover plate of
4.3.10 Transformer having following capacity.

(a) 250 kVA Ea. 357 58 415 -- 415


(b) 315 kVA Ea. 357 58 415 -- 415
(c) 500 kVA Ea. 482 58 540 -- 540
(d) 750 kVA Ea. 722 58 780 -- 780
(e) 1000 kVA Ea. 952 58 1010 -- 1010
(f) 1600 kVA Ea. 2442 58 2500 -- 2500
Replacing old & unserviceable gasket bushing of HT for the following
4.3.11 capacity Transformer

(a) 250 kVA Ea. 185 35 220 -- 220

S.O.R. Mech 2019-20


Page 61 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
(b) 315 kVA Ea. 205 35 240 -- 240
(c) 500 kVA Ea. 245 35 280 -- 280
(d) 750 kVA Ea. 265 35 300 -- 300
(e) 1000 kVA Ea. 295 35 330 -- 330
(f) 1600 kVA Ea. 315 35 350 -- 350
Replacing old & unserviceable gasket bushing of LT for the following
4.3.12 capacity Transformer

(a) 250 kVA Ea. 125 35 160 -- 160


(b) 315 kVA Ea. 125 35 160 -- 160
(c) 500 kVA Ea. 165 35 200 -- 200
(d) 750 kVA Ea. 190 35 225 -- 225
(e) 1000 kVA Ea. 235 35 270 -- 270
(f) 1600 kVA Ea. 245 35 280 -- 280
4.3.13 Removing the core plate of the following capacity Transformer.
(a) 250 kVA Ea. 0 1250 1250 -- 1250
(b) 315 kVA Ea. 0 1500 1500 -- 1500
(c) 500 kVA Ea. 0 1500 1500 -- 1500
(d) 750 kVA Ea. 0 2000 2000 -- 2000
(e) 1000 kVA Ea. 0 2500 2500 -- 2500
(f) 1600 kVA Ea. 0 2700 2700 -- 2700
Removing washer ring for the coils of the following capacity
4.3.14 Transformer

(a) 250 kVA Ea. 58 12 70 -- 70


(b) 315 kVA Ea. 68 12 80 -- 80
(c) 500 kVA Ea. 108 12 120 -- 120
(d) 800 kVA Ea. 118 12 130 -- 130
(e) 1000 kVA Ea. 128 12 140 -- 140
(f) 1600 kVA Ea. 188 12 200 -- 200
Replacing the burnt unserviceable HT side winding coils for the
4.3.15 transformer including rewinding, varnishing, vacuuming etc.

(a) For Copper Coils Kg. 422 58 480 -- 480


(b) For Aluminium coils Kg. 202 58 260 -- 260
Replacing the burnt/ unserviceable LT side winding coils for
4.3.16 transformer including rewinding, varnishing, vacuuming etc.

(a) For Copper Coils Kg. 382 58 440 -- 440


(b) For Aluminium Coils Kg. 182 58 240 -- 240
4.3.17 Insulating the HT/ LT copper Aluminium coils of transformer. Kg. 185 35 220 -- 220
Reinsulating the HT/ LT Copper/ Alum. Coils of the following
4.3.18 capacity transformer

(a) 250 kVA Kg. 42 58 100 -- 100


(b) 315 kVA Kg. 42 58 100 -- 100
(c) 500 kVA Kg. 72 58 130 -- 130
(d) 750 kVA Kg. 82 58 140 -- 140
(e) 1000 kVA Kg. 92 58 150 -- 150
(f) 1600 kVA Kg. 107 58 165 -- 165
4.3.19 Inside painting of 250/ 315/ 500/750/ 1000 kVA transformer Ea. 1527 173 1700 -- 1700
4.3.20 Outside painting of Transformer for the following capacity
(a) 250/ 315/ 400/ 500 kVA Ea. 1620 230 1850 -- 1850
(b) 750/ 1000 kVA Ea. 1827 173 2000 -- 2000
Replacing the valve of the Transformer of rating capacity 250/ 315/
4.3.21 500/ 750/ 1000 kVA of following size

(a) 3/4" Ea. 241 29 270 -- 270


(b) 1" Ea. 531 29 560 -- 560

S.O.R. Mech 2019-20


Page 62 of 166
Section- "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
(c) 1.1/4" Ea. 386 29 415 -- 415
(d) 1.1/2" Ea. 431 29 460 -- 460
Replacing the oil level glass of the 250/ 315/ 500/ 750/ 1000kVA by Ea. 67 23 90 -- 90
4.3.22 new one

4.3.23 Replacing the breather of the Transformer of following capacity.


(a) 250/ 315kVA Ea. 1842 58 1900 -- 1900
(b) 500/ 750/ 1000kVA Ea. 2442 58 2500 -- 2500
Repairing of off load Tap changing of 250/ 315/ 500/ 750/ 1000kVA Ea. 1170 230 1400 -- 1400
4.3.24 Transformer.

Replacement of On load Tap changing of 250/ 315/500/750/ Ea. 3470 230 3700 -- 3700
4.3.25 1000kVA Transformer.

Replacing H.T. bushing of 250/ 315/ 500/750/ 1000kVA Transformer Ea. 202 23 225 -- 225
4.3.26 by new one

Replacing H.T Bushing metal parts of 250/ 315/ 500/ 750/ 1000kVA Ea. 281 29 310 -- 310
4.3.27 Transformer by new one.

Replacing H.T Bushing all other parts of 250/ 315/ 500/ 750/ Ea. 151 29 180 -- 180
4.3.28 1000kVA Transformer

Replacing L.T. bushing of following capacity Transformer Ea.


4.3.29

(a) 250/ 315 kVA Ea. 77 23 100 -- 100


(b) 500 / 750 / 1000 kVA Ea. 107 23 130 -- 130
Replacing L.T. Bushing metal parts of 250/315/ 315/ 500/ 750/ 395 35 430 -- 430
4.3.30 1000kVA Transformer by new one.

Replacing L.T. Bushing all/ other parts of the 250/ 315/ 500/750/ Ea. 565 35 600 -- 600
4.3.31 1000kVA Transformer.

Drying the repaired transformer with appropriate heat air of following


4.3.32 capacity transformer.

(a) 250kVA/ 315kVA Ea. 0 2150 2150 -- 2150


(b) 500kVA Ea. 0 2250 2250 -- 2250
(c) 750kVA Ea. 0 2500 2500 -- 2500
(d) 1000kVA Ea. 0 2700 2700 -- 2700
Carrying out routine tests as per relevant IS/ IEC standards for
4.3.33 following capacity transformer.

(a) 250/ 315kVA Ea. 0 1750 1750 -- 1750


(b) 500/ 750/ 1000 kVA Ea. 0 3000 3000 -- 3000
Assembling the repaired / replaced copper/ Aluminium coils of the
4.3.34 following capacity transformer

(a) 250/ 315/ 500kVA Ea. 0 2200 2200 -- 2200


(b) 750/ 1000 kVA Ea. 0 2300 2300 -- 2300
Conveyance charges for transformer from workshop to site or back
4.3.35 one side)

(a) Local up to 10km Ea. 0 450 450 -- 450


(b) Outside Divisional Head Quarter for first 30km from store Ea. 0 500 500 -- 500
(c) Add for each block of additional 30km Ea. 0 250 250 -- 250
4.3.36 Loading/ Unloading transformer on one side
(a) 250/ 315/ 500kVA Ea. 0 3600 3600 -- 3600
(b) 750/ 1000kVA Ea. 0 5900 5900 -- 5900
Supplying & fixing Steel Chequered Plate having 7 mm thickness, Sq.M 3127 173 3300 -- 3300
4.3.37 duly painted with two coats of black Japan colour. (Average Wt. 61.1 tr.
kg/ Sq.Mtr.)
Supplying & fixing Steel Chequered Plate having 10 mm thickness, Sq.M 4127 173 4300 -- 4300
4.3.38 duly painted with two coats of black Japan colour. (Average Wt. 84.6 tr.
kg/ Sq.Mtr.)
Supplying & fixing Steel Chequered Plate having 12 mm thickness, Sq.M 5170 230 5400 -- 5400
4.3.39 duly painted with two coats of black Japan colour. (Average Wt. tr.
200.3 kg/ Sq.Mtr.)

S.O.R. Mech 2019-20


Page 63 of 166
Section - "D"

Approved Rate for 2019-20

Sr. No. Description of Item Unit Prevailing Rates


Material Labour Total rates of inclusive
GST of GST
REPAIRING OF MACHINERIES
SECTION 6--1 REPAIRING OF MONO BLOCK PUMP MOTORS
5-1-1. Removing the pump set from foundation after removing suction & discharge
connection pipes & all wiring connections taking it to workshop & open it for
fault finding , refitting the same, after carrying out repairing, taking back on site
refitting on foundation with pipe & wiring connections & put in working condition.
(Excludes cost of repairing. Includes to & from transportation)

(a) Up to 3 HP Job 0.00 165.00 165.00 5.0% 173.25


(b) Above 3 HP to 7.5 HP Job 0.00 220.00 220.00 5.0% 231.00
(c)10 Hp to 20 HP Job 0.00 330.00 330.00 5.0% 346.50
5-1-2. Removing deteriorated gasket, gland packing, washer nuts & bolts before
refitting of motor pump set.
(a) Up to 3 HP Ea. 55.00 33.00 88.00 12.0% 98.56
(b) Above 3 HP to 7.5 HP Ea. 88.00 33.00 121.00 12.0% 135.52
(c)10 Hp to 20 HP Ea. 121.00 33.00 154.00 12.0% 172.48
5-1-3. Rewinding of 1 HP 230V single phase motor as per original winding design by Ea. 495.00 55.00 550.00 12.0% 616.00
using super enamelled copper Wire and putting the same in working condition as
per original.
5-1-4. Rewinding of 2 HP 3 phase 440V motor as per original winding design by using Ea. 605.00 110.00 715.00 12.0% 800.80
super enamelled copper Wire and putting the same in working condition as per
original.
5-1-5. Rewinding of 3 H.P., 3 phase 440V motor as per original winding design by Ea. 990.00 132.00 1122.00 12.0% 1256.64
using super enamelled copper Wire and putting the same in working condition as
per original.
5-1-6. Rewinding of 5 H.P., 3 phase 440V motor as per original winding design by Ea. 1650.00 165.00 1815.00 12.0% 2032.80
using super enamelled copper Wire and putting the same in working condition as
per original.
5-1-7. Rewinding of 7.5 H.P., 3 phase 440V motor as per original winding design by Ea. 2145.00 220.00 2365.00 12.0% 2648.80
using super enamelled copper Wire and putting the same in working condition as
per original.
5-1-8. Rewinding of 10 H.P., 3 phase 440V motor as per original winding design by Ea. 2750.00 330.00 3080.00 12.0% 3449.60
using super enamelled copper Wire and putting the same in working condition as
per original.
5-1-9. Rewinding of 12.5 H.P., 3 phase 440V motor as per original winding design by Ea. 3850.00 330.00 4180.00 12.0% 4681.60
using super enamelled copper Wire and putting the same in working condition as
per original.
5-1-10. Rewinding of 15 H.P., 3 phase 440V motor as per original winding design by Ea. 4950.00 385.00 5335.00 12.0% 5975.20
using super enamelled copper Wire and putting the same in working condition as
per original.

5-1-11. Rewinding of 20 H.P., 3 phase 440V motor as per original winding design by Ea. 5500.00 550.00 6050.00 12.0% 6776.00
using super enamelled copper Wire and putting the same in working condition as
per original.
5-1-12. Replacing burnout unserviceable ball bearing / Roller bearing suitable for Ea.
following motors for mono block pump sets
(A) For 1 H.P. motor/pump Ea. 154.00 44.00 198.00 12.0% 221.76
(B) For 2 H.P. motor/pump Ea. 220.00 44.00 264.00 12.0% 295.68
(C) For 3 H.P. motor/pump Ea. 275.00 44.00 319.00 12.0% 357.28
(D) For 5 H.P. motor/pump Ea. 308.00 66.00 374.00 12.0% 418.88
(E) For 7.5 H.P. motor/pump Ea. 385.00 66.00 451.00 12.0% 505.12
(F) For 10/12.5 H.P. motor/pump Ea. 550.00 66.00 616.00 12.0% 689.92
(G) For 15 H.P. motor/pump Ea. 638.00 110.00 748.00 12.0% 837.76
(H) For 20 H.P. motor/pump Ea. 660.00 110.00 770.00 12.0% 862.40
SECTION 6--2 REPAIRING OF OPEN WELL HORIZONTAL MONO PUMP SETS

5-2-1. Dewatering sump well by hiring pump sets & temporary pipe connections of
following sump capacity
(a) up to 5000 Ltr Job 0.00 220.00 220.00 5.0% 231.00
(b) Above 5000 Ltr to 20000 Ltr Job 0.00 275.00 275.00 5.0% 288.75
(c) Above 20000 Ltr to 1 Lac Ltr Job 0.00 385.00 385.00 5.0% 404.25
(d) Above 1 Lac Ltr Job 0.00 550.00 550.00 5.0% 577.50
5-2-2. Opening the open well sub. mono pump set for fault finding , carry out required
repairs refitting the same with necessary oiling, greasing & overhauling & making
pump set in good working condition. (Excludes cost of repairing. Includes to &
from transportation)
(i) 1.0 HP to 5HP Ea. 0.00 350.00 350.00 5.0% 367.50
(ii) 7.5 to 15HP Ea. 0.00 385.00 385.00 5.0% 404.25
(iii) Above 15HP Ea. 0.00 495.00 495.00 5.0% 519.75

S.O.R. Mech - 2019-20


Page 64 of 166
Section - "D"

5-2-3. Rewinding single phase 230V motor for open well horizontal mono pump set by
using polycab copper winding wire & putting the same in working order for pump
capacity of
(a) 0.5 HP - 230V Ea. 1012.00 110.00 1122.00 12.0% 1256.64
(b) 1HP - 230 V Ea. 1375.00 110.00 1485.00 12.0% 1663.20
5-2-4. Rewinding 3 phase, 440V motor for open well horizontal mono pump set by
using poly. cap copper winding wire & putting the same in working order for
pump capacity of
(a) 0.5 H.P./ 1 HP / 1.5 HP - 440V Ea. 1210.00 110.00 1320.00 12.0% 1478.40
(b) 2 HP / 3 HP - 440V Ea. 1485.00 110.00 1595.00 12.0% 1786.40
(c)5 HP - 440V Ea. 1870.00 220.00 2090.00 12.0% 2340.80
(d) 7.5 HP - 440V Ea. 2255.00 220.00 2475.00 12.0% 2772.00
(e) 10 HP - 440V Ea. 3135.00 275.00 3410.00 12.0% 3819.20
(f) 12.5 HP - 440V Ea. 3245.00 275.00 3520.00 12.0% 3942.40
(g) 15 HP - 440V Ea. 3465.00 275.00 3740.00 12.0% 4188.80
(h) 20 HP - 440V Ea. 3685.00 330.00 4015.00 12.0% 4496.80
(i) 25 HP - 440V Ea. 4455.00 385.00 4840.00 12.0% 5420.80
(j) 30 HP - 440V Ea. 5200.00 415.00 5615.00 12.0% 6288.80
5-2-5. Replacement of S.S. sleeves for shaft of open well horizontal submersible pump
sets for
(i) 1HP to 5HP Ea. 319.00 55.00 374.00 12.0% 418.88
(ii) 7.5 to 15HP Ea. 578.00 55.00 633.00 12.0% 708.96
(iii) Above 15HP Ea. 957.00 55.00 1012.00 12.0% 1133.44
5-2-6. Replacement of Stainless Steel bushing fitted in end shield for open well
horizontal submersible pump set
(i) 1HP to 5 HP Ea. 506.00 55.00 561.00 12.0% 628.32
(ii) 7.5Hp to 15 HP Ea. 770.00 55.00 825.00 12.0% 924.00
(iii) above 15 HP Ea. 935.00 55.00 990.00 12.0% 1108.80
5-2-7. Replacement of Gun metal /Bronze bushing for open well horizontal
submersible pump set
(i) 1HP to 5 HP Ea. 220.00 55.00 275.00 12.0% 308.00
(ii) 7.5Hp to 15 HP Ea. 330.00 55.00 385.00 12.0% 431.20
(iii) above 15 HP Ea. 385.00 55.00 440.00 12.0% 492.80
5-2-8. Replacing gasket, oil, nuts, bolts & washers for open well horizontal submersible
pump sets.
(i) 1HP to 5 HP Ea. 220.00 55.00 275.00 12.0% 308.00
(ii) 7.5Hp to 15 HP Ea. 330.00 55.00 385.00 12.0% 431.20
(iii) above 15 HP Ea. 385.00 55.00 440.00 12.0% 492.80
5-2-9. Replacement of Bronze / Carbon thrust bearing with fibber plate & bushing
suitable for open well horizontal submersible pump set for
(i) 1HP to 5 HP Ea. 1210.00 55.00 1265.00 12.0% 1416.80
(ii) 7.5Hp to 15 HP Ea. 1573.00 55.00 1628.00 12.0% 1823.36
(iii) above 15 HP Ea. 2057.00 55.00 2112.00 12.0% 2365.44
5-2-10. Replacement of cast iron impeller for openwell horizontal submersible pump
pump sets
(i) 1HP to 5 HP Ea. 275.00 110.00 385.00 12.0% 431.20
(ii) 7.5Hp to 15 HP Ea. 495.00 165.00 660.00 12.0% 739.20
(iii) above 15 HP Ea. 825.00 165.00 990.00 12.0% 1108.80
5-2-11. Replacement of Bronze / Gunmetal impeller for open well horizontal submersible
pump set
(i) 1HP to 5 HP Ea. 825.00 110.00 935.00 12.0% 1047.20
(ii) 7.5Hp to 15 HP Ea. 990.00 165.00 1155.00 12.0% 1293.60
(iii) above 15 HP Ea. 1210.00 165.00 1375.00 12.0% 1540.00
SECTION 6--3 REPAIRING OF SUBMERSIBLE PUMP SETS
5-3-1. Opening the submersible pump set for fault finding , carry out required repairs
refitting the same with necessary oiling, greasing & overhauling & making pump
set in good working condition. (Excludes cost of repairing. Includes to & from
transportation)

(i) 1HP to 5HP Ea. 0.00 275.00 275.00 5.0% 288.75


(ii) 7.5 to 15HP Ea. 0.00 385.00 385.00 5.0% 404.25
(iii) 20HP to 35 HP Ea. 0.00 495.00 495.00 5.0% 519.75
(iv) Above 35 HP Ea. 0.00 660.00 660.00 5.0% 693.00
5-3-2. Rewinding of submersible motor by using approved make PVC insulated copper
winding Cores of suitable size complete with connection. Capacity Suitable for
pump of following size. Dismantled Materials to be retained by agency.

(A) 5 HP Ea. 1815.00 165.00 1980.00 12.0% 2217.60


(B) 7.5 H.P Ea. 2277.00 165.00 2442.00 12.0% 2735.04
(C) 10 to 15 H.P Ea. 3091.00 275.00 3366.00 12.0% 3769.92
(D) 16 to 20 H.P Ea. 3542.00 330.00 3872.00 12.0% 4336.64
(E) 21 to 25 H.P Ea. 4433.00 385.00 4818.00 12.0% 5396.16
(F) 26 to to 35 H.P Ea. 5698.00 495.00 6193.00 12.0% 6936.16
(G) 36 to 45 H.P Ea. 8349.00 1144.00 9493.00 12.0% 10632.16
(H) 46 to 54 H.P Ea. 10758.00 2002.00 12760.00 12.0% 14291.20
(I) 55 to 75 H.P Ea. 22770.00 2530.00 25300.00 12.0% 28336.00
5-3-3. Replacement of bronze/ carbon thrust bearing with fibre plate & housing for
(i)150 mm. dia. Ea. 1430.00 110.00 1540.00 12.0% 1724.80
(ii)200 mm. dia Ea. 2068.00 110.00 2178.00 12.0% 2439.36

S.O.R. Mech - 2019-20


Page 65 of 166
Section - "D"

5-3-4. Replacement of motor bush, upper/ lower with sleeve with following material
(A) Bronze
(i)150 mm. dia. Ea. 495.00 55.00 550.00 12.0% 616.00
(ii)200 mm. dia Ea. 990.00 55.00 1045.00 12.0% 1170.40
(B)Rubber
(i)150 mm. dia. Ea. 297.00 22.00 319.00 12.0% 357.28
(ii)200 mm. dia Ea. 495.00 22.00 517.00 12.0% 579.04
5-3-5. Replacement of stage casing bowl with nuts and bolts.
(A)C.I.
(i)150 mm. dia. Ea. 330.00 55.00 385.00 12.0% 431.20
(ii)200 mm. dia Ea. 495.00 55.00 550.00 12.0% 616.00
(B)Bronze
(i)150 mm. dia. Ea. 550.00 55.00 605.00 12.0% 677.60
(ii)200 mm. dia Ea. 693.00 55.00 748.00 12.0% 837.76
5-3-6. Replacement of Bronze impeller with neck ring.
(i)150 mm. dia. Ea. 396.00 55.00 451.00 12.0% 505.12
(ii)200 mm. dia Ea. 605.00 55.00 660.00 12.0% 739.20
5-3-7. Replacement of Shaft sleeve stainless steel.
(i)150 mm. dia. Ea. 55.00 11.00 66.00 12.0% 73.92
(ii)200 mm. dia Ea. 138.00 11.00 149.00 12.0% 166.88
5-3-8. Replacement of Bowl bearing/ bush
(A) Rubber
(i)150 mm. dia. Ea. 308.00 55.00 363.00 12.0% 406.56
(ii)200 mm. dia Ea. 605.00 55.00 660.00 12.0% 739.20
(B) Lead
(i)150 mm. dia. Ea. 693.00 55.00 748.00 12.0% 837.76
(ii)200 mm. dia Ea. 1100.00 55.00 1155.00 12.0% 1293.60
5-3-9. Replacement of S.S.Shaft for
(A) 3 stage pump
(i)150 mm. dia. Ea. 286.00 28.00 314.00 12.0% 351.68
(ii)200 mm. dia Ea. 473.00 44.00 517.00 12.0% 579.04
(B) Add per stage
(i)150 mm. dia. Ea. 83.00 11.00 94.00 12.0% 105.28
(ii)200 mm. dia Ea. 121.00 11.00 132.00 12.0% 147.84
5-3-10. Replacement of suction strainer
(i)150 mm. dia. Ea. 94.00 17.00 111.00 12.0% 124.32
(ii)200 mm dia. Ea. 187.00 22.00 209.00 12.0% 234.08

S.O.R. Mech - 2019-20


Page 66 of 166
Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates Rates
No. Prevailing
exclusive of inclusive of
rates of GST
GST GST
1 3 Phase Borewell Submersible Pump Sets

I Electric motor driven Borewell submersible pump set conforming to I.S. 8034 and motor conforms to IS-9283 working at 3 phase
400/440 volt 50 C/S A.C. supply & 2900 R.P.M.
II Cat No. Discharge in Head in mtr Mini Motor
LPM HP
a) 1.0 90 60.0 3.00 No 10,970 12% 12,286
b) 1.1 90 90.0 5.00 No 12,900 12% 14,448
c) 1.2 90 120.0 6.00 No 14,500 12% 16,240
d) 1.3 90 150.0 7.50 No 17,000 12% 19,040
e) 1.4 90 180.0 10.00 No 19,800 12% 22,176
f) 2.0 135 60.0 4.00 No 11,100 12% 12,432
g) 2.1 135 90.0 6.00 No 13,100 12% 14,672
h) 2.2 135 120.0 7.50 No 15,120 12% 16,934
i) 2.3 135 150.0 10.00 No 18,000 12% 20,160
j) 2.4 135 180.0 12.50 No 20,340 12% 22,781
k) 2.5 135 210.0 15.00 No 25,530 12% 28,594
l) 2.6 135 240.0 17.50 No 26,100 12% 29,232
m) 2.7 135 255.0 17.50 No 26,430 12% 29,602
n) 3.0 180 72.0 6.00 No 12,510 12% 14,011
o) 3.1 180 108.0 10.00 No 16,110 12% 18,043
p) 3.2 180 144.0 12.50 No 19,370 12% 21,694
q) 3.3 180 163.0 12.50 No 20,110 12% 22,523
r) 3.4 180 180.0 12.50 No 22,190 12% 24,853
s) 3.5 180 215.0 15.00 No 25,551 12% 28,617
t) 3.6 180 255.0 20.00 No 29,820 12% 33,398
u) 3.7 180 275.0 22.50 No 31,000 12% 34,720
v) 4.0 240 72.0 7.50 No 13,025 12% 14,588
w) 4.1 240 108.0 25.00 No 16,700 12% 18,704
x) 4.2 240 144.0 15.00 No 21,480 12% 24,058
y) 4.3 240 170.0 17.50 No 24,120 12% 27,014
z) 4.4 240 190.0 20.00 No 25,600 12% 28,672
aa) 4.5 240 210.0 20.00 No 31,150 12% 34,888
ab) 4.6 240 230.0 25.00 No 28,000 12% 31,360
ac) 4.7 240 250.0 25.00 No 30,750 12% 34,440
ad) 5.0 320 55.0 7.50 No 14,211 12% 15,916
ae) 5.1 320 92.0 12.50 No 16,600 12% 18,592
af) 5.2 320 130.0 17.50 No 21,750 12% 24,360
ag) 5.3 320 150.0 20.00 No 24,100 12% 26,992
ah) 6.0 400 60.0 10.00 No 16,430 12% 18,402
ai) 6.1 400 90.0 15.00 No 21,130 12% 23,666
aj) 6.2 400 120.0 20.00 No 26,700 12% 29,904
ak) 6.3 400 150.0 22.50 No 31,000 12% 34,720
al) 7.0 510 52.0 12.50 No 20,110 12% 22,523
am) 7.1 510 87.0 20.00 No 27,810 12% 31,147
an) 7.2 510 123.0 25.00 No 32,100 12% 35,952
ao) 7.3 510 141.0 30.00 No 34,600 12% 38,752
ap) 7.4 510 159.0 35.00 No 35,600 12% 39,872
aq) 7.5 510 175.0 40.00 No 38,310 12% 42,907
ar) 8.0 800 72.0 25.00 No 28,900 12% 32,368
as) 8.1 800 108.0 35.00 No 33,760 12% 37,811
at) 8.2 800 144.0 45.00 No 40,500 12% 45,360
au) 8.3 800 162.0 50.00 No 41,850 12% 46,872
av) 8.4 800 180.0 55.00 No 46,160 12% 51,699
aw) 8.5 800 198.0 60.00 No 48,430 12% 54,242
ax) 9.0 1,200 63.0 27.50 No 30,810 12% 34,507

S.O.R. Mech 2019-20


Page 67 of 166
Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates Rates
No. Prevailing
exclusive of inclusive of
rates of GST
GST GST
ay) 9.1 1,200 105.0 45.00 No 40,900 12% 45,808
az) 9.2 1,200 126.0 55.00 No 45,750 12% 51,240
ba) 9.3 1,200 147.0 65.00 No 50,310 12% 56,347
bb) 9.4 1,200 167.0 75.00 No 57,810 12% 64,747
bc) 9.5 1,200 187.0 80.00 No 66,482 12% 74,459
bd) 10.0 600 50.0 12.50 No 21,240 12% 23,789
be) 10.1 600 83.0 17.50 No 28,400 12% 31,808
bf) 10.2 600 116.0 25.00 No 30,350 12% 33,992
bg) 10.3 600 132.0 30.00 No 35,550 12% 39,816
bh) 10.4 600 149.0 35.00 No 38,770 12% 43,422
bi) 10.5 600 165.0 40.00 No 39,600 12% 44,352
bj) 10.6 600 180.0 45.00 No 40,840 12% 45,741
bk) SP1 1,700 52.0 30.00 No 52,863 12% 59,207
bl) SP2 1,700 86.0 55.00 No 70,214 12% 78,640
bm) SP3 2,000 50.0 35.00 No 60,288 12% 67,523
bn) SP4 2,000 74.0 50.00 No 77,296 12% 86,572
bo) SP5 2,900 45.0 45.00 No 74,500 12% 83,440
bp) SP6 2,900 68.0 65.00 No 97,100 12% 108,752
bq) LD2.0 420 72.0 12.50 No 21,800 12% 24,416
br) LD2.1 420 108.0 20.00 No 29,520 12% 33,062
bs) LD2.2 420 144.0 27.50 No 32,240 12% 36,109
bt) LD2.3 420 180.0 35.00 No 36,000 12% 40,320
bu) LD2.4 420 216.0 40.00 No 37,440 12% 41,933
bv) LD2.5 420 252.0 40.00 No 102,090 12% 114,341
bw) HD-1 5,000 40.0 75.00 No 90,102 12% 100,914
bx) HD-2 5,000 60.0 110.00 No 131,694 12% 147,497
by) HD-3 7,500 40.0 110.00 No 133,106 12% 149,079
bz) HD-4 7,500 60.0 160.00 No 199,659 12% 223,618
2 Control Panel Board
2.1 DOL / Star Delta starter suitable for local & remote pump control application consisting of MPCB, overload relay and contactors
as per Type II coordination including digital voltmeter, analogue ammeter with selector switch, run hour meter, required
protective relays & control accessories.
a) D. O. L. up to 3 HP No. 5,770 18% 6,809

b) D. O. L. up to 5 HP No. 5,770 18% 6,809

c) D. O. L. up to 7.5 HP No. 6,986 18% 8,243

d) S. D. from 8 to 10 HP No. 7,607 18% 8,976

e) S. D. from 11 to 15 HP No. 9,266 18% 10,934

f) S. D. from 16 to 20 HP No. 11,476 18% 13,542

2.2 Auto Transformer Starter suitable for local & remote pump control application consisting of Auto Transformer (vacuum
impregnated, air cooled having three (3) tappings at 50%, 65% and 80%), incomer MCCB / MPCB, overload relay and contactors
as per Type II coordination including digital MFM with RS 485 communication port, analogue type ammeter with selector switch,
run hour meter, required protective relays & control accessories.
a) A. T. S. from 21 to 30 HP No 20,230 18% 23,871

b) A. T. S. from 31 to 35 HP No 22,844 18% 26,956

c) A. T. S. from 36 to 45 HP No 27,836 18% 32,846

d) A. T. S. from 46 to 50 HP No 31,503 18% 37,174

e) A. T. S. from 51 to 60 HP No 38,532 18% 45,468

f) A. T. S. from 61 to 70 HP No 42,716 18% 50,405

g) A. T. S. from 71 to 80 HP No 54,800 18% 64,664

h) A. T. S. from 81 to 90 HP No 65,260 18% 77,007

S.O.R. Mech 2019-20


Page 68 of 166
Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates Rates
No. Prevailing
exclusive of inclusive of
rates of GST
GST GST
2.3 Microprocessor based soft starter, fully automatic 415V suitable for local & remote pump control application consisting of
incomer MCCB of suitable rating, semi conductor fuses, microprocessor based soft starter with built in by pass arrangement
(conforming to IS/ IEC 60947-4-1-2-3) with RS 485 communication port, external display unit with keypad including temperature
scanner with minimum 10 channels - suitable for accepting RTD (Pt 100) / thermister inputs, digital MFM with RS 485
communication port, analogue type ammeter with selector switch, run hour meter, required protective relays & control
accessories.

a) MP based soft starter- 100 HP No 185,894 18% 219,355

b) MP based soft starter from 101 to 120 HP No 210,431 18% 248,309

c) MP based soft starter from 121 to 130 HP No 210,431 18% 248,309

d) MP based soft starter from 131 to 140 HP No 210,431 18% 248,309

e) MP based soft starter from 141 to 150 HP No 226,613 18% 267,403

f) MP based soft starter from 151 to 160 HP No 226,613 18% 267,403

3 PVC insulated flat / round submersible copper cables

3.1 PVC insulated flat submersible cable as per detailed technical specifications of R/C of GWSSB conforming to IS 694, IEC 60227 /
60228.
a) 2 RMT 25.23 18% 29.77
1 R x 3 C x 1.5 mm
b) 2 RMT 38.73 18% 45.70
1 R x 3 C x 2.5 mm
c) 2 RMT 57.67 18% 68.05
1 R x 3 C x 4.0 mm
d) 1 R x 3 C x 6.0 mm2 RMT 80.14 18% 94.57

e) 2 RMT 129.07 18% 152.30


1 R x 3 C x 10.0 mm
f) 1 R x 3 C x 16.0 mm2 RMT 206.51 18% 243.68

g) 2 RMT 306.24 18% 361.36


1 R x 3 C x 25.0 mm
h) 2 RMT 434.80 18% 513.06
1 R x 3 C x 35.0 mm
Note: Above rates of Flat PVC copper cables are based on IEEMA circular no. IEEMA (PVC) Cable/02 of 2018 issued on Dtd. 09.03.2018
(Month of February 2018). Notional base price of electrolytic copper wire Rod is Rs. 4,81,473/MT and Notional base price of PVC compund
is Rs. 1,33,000/M.T. of grade CW-22.
3.2 PVC insulated round submersible cable as per detailed technical specifications of R/C of GWSSB conforming to IS 694, IEC
60227 / 60228.
a) 1 R x 3 C x 1.5 mm2 RMT 34.00 18% 40.12

b) 1 R x 3 C x 2.5 mm2 RMT 65.00 18% 76.70

c) 1 R x 3 C x 4.0 mm2 RMT 98.00 18% 115.64

d) 1 R x 3 C x 6.0 mm2 RMT 143.00 18% 168.74

e) 1 R x 3 C x 10.0 mm2 RMT 231.00 18% 272.58

f) 1 R x 3 C x 16.0 mm2 RMT 365.00 18% 430.70

g) 1 R x 3 C x 25.0 mm2 RMT 570.00 18% 672.60

h) 1 R x 3 C x 35.0 mm2 RMT 785.00 18% 926.30

4A Monobloc pump 3 phase 400/440 vott, 50 c/s. A.C. Supply & 2800 RPM following IS 9079 at departmental stores with following
MOC : Casing: CI-FG260, Impeller : Bronze & Shaft : SS:410

Sr. No Rating Discharge Head


H.P LPM mtr.
a) 5 285 24 No. 13,600 12% 15,232

b) 7.5 545 24 No. 20,000 12% 22,400

c) 7.5 550 33 No. 20,000 12% 22,400

d) 12.5 980 30 No. 30,600 12% 34,272

e) 17.5 1750 31 No. 39,500 12% 44,240

f) 15 1140 39 No. 32,700 12% 36,624

g) 20 1900 33 No. 39,500 12% 44,240

4B Monoblock pump 3 phase 400/440 vott, 50 c/s. A.C. Supply & 2800 RPM following IS 9079
MOC : Casing: CI-FG260, Impeller : SS-CF8M & Shaft : SS:410
Sr. No Rating Discharge Head
H.P LPM mtr.

S.O.R. Mech 2019-20


Page 69 of 166
Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates Rates
No. Prevailing
exclusive of inclusive of
rates of GST
GST GST
a) 5 285 24 No. 12,600 12% 14,112

b) 7.5 545 24 No. 18,100 12% 20,272

c) 7.5 550 33 No. 18,100 12% 20,272

d) 12.5 980 30 No. 28,900 12% 32,368

e) 17.5 1750 31 No. 38,200 12% 42,784

f) 15 1140 39 No. 31,000 12% 34,720

g) 20 1900 33 No. 38,200 12% 42,784

5 Monoset sub. pump 3 phase 400/440 vott, 50 c/s. A.C. Supply & 2900 RPM , following IS 14220
MOC : Casing: CI-FG260, Impeller : Bronze & Shaft : SS:410
Sr. No Category Rating H.P. Discharge Headmtr.
LPM
a) SM - 2.1 4 220 22.5 No 9,930 12% 11,122

b) SM - 2.2 5.5 360 24 No 10,800 12% 12,096

c) SM - 2.3 6.5 438 22.5 No 10,525 12% 11,788

d) SM - 2.4 10 530 27 No 12,160 12% 13,619

e) SM - 2.5 10 498 32.5 No 12,900 12% 14,448

f) SM - 2.6 12.5 600 40 No 15,711 12% 17,596

g) SM - 2.7 15 690 40 No 17,230 12% 19,298

h) SM - 2.8 15 600 46 No 17,960 12% 20,115

i) SM - 2.9 15 440 52 No 17,500 12% 19,600

j) SM - 2.10 25 700 70 No 28,500 12% 31,920

k) SM - 2.5.1 5.5 510 16 No 10,870 12% 12,174

l) SM - 2.5.2 6.5 440 26 No 11,210 12% 12,555

m) SM - 2.5.3 10 720 25 No 13,050 12% 14,616

n) SM - 2.5.4 15 900 37 No 24,050 12% 26,936

o) SM - 2.5.5 15 750 42 No 24,300 12% 27,216

p) SM - 2.5.6 25 1000 58 No 32,200 12% 36,064

q) SM - 3.1 10 700 24 No 13,670 12% 15,310

r) SM - 3.2 12.5 1000 24 No 16,470 12% 18,446

s) SM - 3.3 10 700 27 No 14,270 12% 15,982

t) SM - 3.4 15 870 32.5 No 17,140 12% 19,197

u) SM - 3.5 17.5 1300 32 No 25,100 12% 28,112

v) SM - 3.6 20 1175 37 No 25,300 12% 28,336

w) SM - 3.7 25 1300 50 No 34,581 12% 38,731

x) SM - 4.1 7.5 1275 11 No 13,240 12% 14,829

y) SM - 4.2 10 1450 12.5 No 15,030 12% 16,834

z) SM - 4.3 12.5 1160 20 No 15,400 12% 17,248

aa) SM - 4.4 15 1250 25 No 18,550 12% 20,776

ab) SM - 4.5 17.5 1600 26 No 24,980 12% 27,978

ac) SM - 4.6 20 1500 30 No 25,240 12% 28,269

ad) SM - 4.7 25 1860 34 No 32,700 12% 36,624

6 Single phase Borewell sub pump motor set


MOC: Casing: CI-FG260, Impeller : Bronze & Shaft : SS:410
Category Discharge Head H.P.

a) Q-1.1 20 60 1 No 7,131 12% 7,987

b) Q-1.2 20 90 1.5 No 7,790 12% 8,725

S.O.R. Mech 2019-20


Page 70 of 166
Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates Rates
No. Prevailing
exclusive of inclusive of
rates of GST
GST GST
c) Q-1.3 20 110 1.5 No 8,719 12% 9,765

d) Q-1.4 20 150 2 No 8,662 12% 9,701

e) Q-1.5 20 180 3 No 11,610 12% 13,003

f) Q-2.1 40 60 1.5 No 7,638 12% 8,555

g) Q-2.2 40 90 3 No 9,293 12% 10,408

h) Q-2.3 40 110 3 No 10,350 12% 11,592

i) Q-2.4 40 150 3 No 13,365 12% 14,969

j) Q-2.5 40 180 4 No 15,444 12% 17,297

k) Q-3.1 60 60 2 No 8,538 12% 9,563

l) Q-3.2 60 90 3 No 10,448 12% 11,702

7(A) Labour Charge for fishing out Sub pump set fallen in the tube well of size 150mm/200mm/250mm dia. Including carting of
required mats, fixtures for fishing to site of work and also including carting charges of the fished out Sub pump set and
accessories to the respective departmental store including loading and unloading.
a) Job Up to 150 Mtr. Job 20,381 5% 21,400

b) Job Up to 150 Mtr. Job 25,905 5% 27,200

7(B) Labour Charge for fishing out struck up Sub pump set /pipes /cable etc. from 165/200/250 mm bore by applying sp. Tech with sp.
Tools /Fixtures by Agency.
a) Job Up to 150 Mtr. Job 17,762 5% 18,650

b) Job Up to 150 Mtr. Job 20,571 5% 21,600

S.O.R. Mech 2019-20


Page 71 of 166
Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates
No. Prevailing
Rates exclusive of GST inclusive of
rates of GST
GST
8 Providing, Supplying, Erecting approved make coupled vaccum pump set with horizontal foot mounted TEFC squirrel cage motor having under mentioned
capacity working on 3ph, 50hz, 415V±10%, with base plate, DOL starter,cable,GI medium duty suction pipes-10 mtr. long, specials, valve, PVC tank of 250 ltr
capacity etc. complete.Material of Constructions: Impeller- SSCF8M, Shaft- SS410, Casing-CIFG260

a) 1 H.P. No. 17,500 Incl. 17,500 12% 19,600

b) 2 H.P. No. 21,800 Incl. 21,800 12% 24,416

c) 3 H.P. No. 32,000 Incl. 32,000 12% 35,840

d) 5 H.P. No. 43,700 Incl. 43,700 12% 48,944

e) 7.5 H.P. No. 55,700 Incl. 55,700 12% 62,384

f) 10.0 H.P. No. 32,700 Incl. 32,700 12% 36,624

9 Supply of Horizontal Mono-Submersible Pump set (Drain pump) as per IS: 14220 / 1994 & its latest amendments of following duty parameters with suitable
submersible motor as per IS: 9283 / 1994 & its latest amendments working on 3 ø, 415 V ± 10%, 50 ± 3% Hz power supply, rated speed 2900 RPM of
following duty capacity. Material of Constructions: Impeller- High tensile brass / LTB II; Casing- CI FG 260; Pump & Motor shaft- SS 304; Bearing Bush- LTB
III
Flow Head

a) 10 m³/hr. 10.0 mtr. No. 13,200 Incl. 13,200 12% 14,784

b) 20 m³/hr. 10.0 mtr. No. 13,200 Incl. 13,200 12% 14,784

c) 30 m³/hr. 10.0 mtr. No. 16,850 Incl. 16,850 12% 18,872

d) 40 m³/hr. 10.0 mtr. No. 16,850 Incl. 16,850 12% 18,872

e) 50 m³/hr. 10.0 mtr. No. 17,770 Incl. 17,770 12% 19,902

10 Providing and erecting portable diesel driven self priming horizontal mono pump set (Dewatering set) with four wheel trolley, GI medium duty delivery
pipes, specials, suction strainer etc. complete set Material of Constructions: Impeller-Bronze, Casing-C.I., Shaft-Carbon Steel

12-30 LPS 6-12 mtr Head No. 25,720 Incl. 25,720 12% 28,806

11 HSCF Pumps

A Supply, Testing & Commissioning of Horizontal Split casing centrifugal pump motor set of specified duty parameters & guaranteed efficiency of following
MOC with specified capacity, horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%,
rated speed 1450 RPM along with fabricated MS base frame, coupling, coupling guard, foundation bolts etc. as per relevant IS.
M.O.C.: Impeller & Wearing Rings: Bronze LTB II IS: 318, Casing: CI FG 260 IS: 210 , Shaft: SS 410, Shaft Sleeve: Bronze LTB II IS: 318 or SS 410, Mechanical
Seal (above 30 kW) , Base Frame: MS.
Rating

a) Upto 30 KW per 6,607 6,607 12% 7,400


KW
b) 31 KW to 75 KW per 5,946 5,946 12% 6,660
KW
c) 76 KW to 132 KW per 5,850 5,850 12% 6,552
KW
d) 133 KW to 315 KW per 5,600 5,600 12% 6,272
KW
e) Above 315 KW per 5,300 5,400 12% 6,048
KW
B Supply, Testing & Commissioning of Horizontal Split casing centrifugal pump motor set of specified duty parameters & guaranteed efficiency of following
MOC with specified capacity, horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%,
rated speed 1450 RPM along with fabricated MS base frame, coupling, coupling guard, foundation bolts etc. as per relevant IS.
M.O.C.: Impeller & Wearing Rings: CF8M, Casing: Cast Steel WCB , Shaft: SS 410, Shaft Sleeve: SS 410, Mechanical Seal (above 30 kW), Base Frame: MS.
Rating

a) Upto 30.0 KW per 7,598 7,598 12% 8,510


KW
b) 31.0 KW to 75.0 KW per 6,838 6,838 12% 7,659
KW
c) 76.0 KW to 132.0 KW per 6,600 6,600 12% 7,392
KW
d) 133 KW to 315 KW per 6,440 6,440 12% 7,213
KW
e) Above 315 KW per 6,095 6,095 12% 6,826
KW
C Erection Charges for Motor rating (without material supply)

a) Upto 30.0 KW Job - 5,952 5,952 5% 6,250

b) 31.0 KW to 75.0 KW Job - 11,905 11,905 5% 12,500

c) 76.0 KW to 132.0 KW Job - 17,857 17,857 5% 18,750

d) 133 KW to 315 KW Job - 23,810 23,810 5% 25,000

e) Above 315 KW Job - 30,952 30,952 5% 32,500

12 End Suction Back Pullout Pump

A Supply, Testing & Commissioning of End Suction Back Pull-out centrifugal pump motor set with base frame of specified duty parameters & guaranteed
efficiency of following MOC with specified capacity horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50
Hz ± 3%, 415 V ± 10%, rated speed 1450 RPM along with fabricated MS base frame, coupling, coupling guard, foundation bolts etc. as per relevant IS.
M.O.C.: Impeller & Wearing Rings: Bronze LTB II IS: 318, Casing: CI FG 260 IS: 210 , Shaft: SS 410, Shaft Sleeve: Bronze LTB II IS: 318 or SS 410,
Mechanical Seal (above 30 kW), Base Frame: MS.
Rating

a) Upto 30 KW per 4,910 4,910.00 12% 5,499


KW

Page 72 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates
No. Prevailing
Rates exclusive of GST inclusive of
rates of GST
GST
b) 31 KW to 75 KW per 4,400 4,400.00 12% 4,928
KW
c) 76 KW to 132 KW per 4,230 4,230.00 12% 4,738
KW
d) 133 KW to 315 KW per 3,910 3,910.00 12% 4,379
KW
B Supply, Testing & Commissioning of End Suction Back Pull-out centrifugal pump motor set with base frame of specified duty parameters & guaranteed
efficiency of following MOC with specified capacity horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50
Hz ± 3%, 415 V ± 10%, rated speed 1450 RPM along with fabricated MS base frame, coupling, coupling guard, foundation bolts etc. as per relevant IS.
M.O.C.: Impeller & Wearing Rings: CF8M, Casing: Cast Steel WCB , Shaft: SS 410, Shaft Sleeve: SS 410, Mechanical Seal (above 30 kW), Base Frame: MS.
Rating

a) Upto 30.0 KW per 5,303 5,303 12% 5,939


KW
b) 31.0 KW to 75.0 KW per 4,752 4,752 12% 5,322
KW
c) 76.0 KW to 132.0 KW per 4,568 4,568 12% 5,117
KW
d) 133 KW to 315 KW per 4,223 4,223 12% 4,730
KW
13 Vertical Turbine Pumps

A Supply, Testing & Commissioning of Vertical Turbine pump motor set of specified duty parameters & guaranteed efficiency of following MOC with specified
capacity horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%, rated speed 1450
RPM along with column and bowl assembly, discharge head, base channel/RSJ etc. complete as per relevant IS.
M.O.C.: Impeller & Sealing Rings:CF8M, Bowl & Suction Bell: CI FG 260 IS: 210 with 2% Ni , Shaft with coupling: SS 410, Column Pipe: M.S. ERW,
Mechanical Seal (above 30 kW), Base Plate: MS, Line Bearing: Thordon type, Suction Strainer: S.S.
Rating

a) upto 30.0 KW per 11,808 11,808 12% 13,225


KW
b) 31.0 KW to 75.0 KW per 11,808 11,808 12% 13,225
KW
c) 76.0 KW to 132.0 KW per 11,808 11,808 12% 13,225
KW
d) 133 KW to 315 KW per 11.295 11.295 12% 12.650
KW
e) Above 315 KW per 11.295 11.295 12% 12.650
KW
B Supply, Testing & Commissioning of Vertical Turbine pump motor set of specified duty parameters & guaranteed efficiency of following MOC with specified
capacity horizontal foot mounted TEFC squirrel cage induction motor, working on three phase AC supply with 50 Hz ± 3%, 415 V ± 10%, rated speed 1450
RPM along with column and bowl assembly, discharge head, base channel/RSJ etc. complete as per relevant IS.
M.O.C.: Impeller & Sealing Rings: CF8M, Bowl & Suction Bell: Cast Steel WCB , Shaft with coupling: SS 410, Column Pipe: M.S. Mechanical Seal (above 30
kW),ERW, , Base Plate: MS, Line Bearing: Thordon type, Suction Strainer: S.S.
Rating

a) Upto 30.0 KW per 11,808 Incl. 11,808 12% 13,225


KW
b) 31.0 KW to 75.0 KW per 11,808 Incl. 11,808 12% 13,225
KW
c) 76.0 KW to 132.0 KW per 11,808 Incl. 11,808 12% 13,225
KW
d) 133 KW to 315 KW per 11,295 Incl. 11,295 12% 12,650
KW
e) Above 315 KW per 11,295 Incl. 11,295 12% 12,650
KW
C Erection Charges for Motor rating (without material supply)

a) Upto 30.0 KW Job - 31,250 31,250 5% 32,813

b) 31.0 KW to 75.0 KW Job - 50,000 50,000 5% 52,500

c) 76.0 KW to 132.0 KW Job - 75,000 75,000 5% 78,750

d) 133 KW to 315 KW Job - 75,000 75,000 5% 78,750

e) Above 315 KW Job - 75,000 75,000 5% 78,750

14 Expansion Bellows

Supply, testing & commissioning of flange ends Expansion Bellow as per EJMA standards of overall length of minimum 300 mm, designed for 15 mm axial
compression and 5 mm axial extension with tie rods etc. of following MOC & pressure ratings.
MOC: Bellows: SA 240 Gr. 304; Internal Sleeve: SA 240 Gr. 304; Weldends: IS 2062 Gr. B; Flanges: IS 2062 Gr. B (Drilling as per IS 1538 /IS 6392 ) & Limit
Rods & Nuts: CS - IS 1367.
A PN - 1.0

Size Width Nos.

a) NB 100 mm 300 mm Nos. 2,850 Incl. 2,850 12% 3,192

b) NB 125 mm 300 mm Nos. 3,400 Incl. 3,400 12% 3,808

c) NB 150 mm 300 mm Nos. 3,880 Incl. 3,880 12% 4,346

d) NB 200 mm 300 mm Nos. 5,180 Incl. 5,180 12% 5,802

e) NB 250 mm 300 mm Nos. 6,454 Incl. 6,454 12% 7,228

Page 73 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates
No. Prevailing
Rates exclusive of GST inclusive of
rates of GST
GST
f) NB 300 mm 300 mm Nos. 8,500 Incl. 8,500 12% 9,520

g) NB 350 mm 300 mm Nos. 10,700 Incl. 10,700 12% 11,984

h) NB 400 mm 300 mm Nos. 13,750 Incl. 13,750 12% 15,400

i) NB 450 mm 300 mm Nos. 15,650 Incl. 15,650 12% 17,528

j) NB 500 mm 300 mm Nos. 18,500 Incl. 18,500 12% 20,720

k) NB 600 mm 300 mm Nos. 24,400 Incl. 24,400 12% 27,328

l) NB 700 mm 300 mm Nos. 31,300 Incl. 31,300 12% 35,056

m) NB 750 mm 300 mm Nos. 36,800 Incl. 36,800 12% 41,216

n) NB 800 mm 300 mm Nos. 39,980 Incl. 39,980 12% 44,778

o) NB 900 mm 300 mm Nos. 44,980 Incl. 44,980 12% 50,378

p) NB 1000 mm 350 mm Nos. 73,500 Incl. 73,500 12% 82,320

q) NB 1100 mm 350 mm Nos. 84,000 Incl. 84,000 12% 94,080

r) NB 1200 mm 350 mm Nos. 92,927 Incl. 92,927 12% 104,078

s) NB 1300 mm 350 mm Nos. 99,027 Incl. 99,027 12% 110,910

t) NB 1400 mm 350 mm Nos. 106,654 Incl. 106,654 12% 119,452

u) NB 1500 mm 350 mm Nos. 112,654 Incl. 112,654 12% 126,172

v) NB 1600 mm 400 mm Nos. 118,580 Incl. 118,580 12% 132,810

w) NB 1700 mm 400 mm Nos. 124,427 Incl. 124,427 12% 139,358

x) NB 1800 mm 450 mm Nos. 130,227 Incl. 130,227 12% 145,854

y) NB 1900 mm 450 mm Nos. 135,954 Incl. 135,954 12% 152,268

z) NB 2000 mm 450 mm Nos. 141,627 Incl. 141,627 12% 158,622

aa) NB 2200 mm 500 mm Nos. 154,227 Incl. 154,227 12% 172,734

ab) NB 2400 mm 500 mm Nos. 166,754 Incl. 166,754 12% 186,764

ac) NB 2500 mm 550 mm Nos. 172,280 Incl. 172,280 12% 192,954

B PN - 1.6

Size Width Nos.

a) NB 100 mm 300 mm Nos. 3,000 Incl. 3,000 12% 3,360

b) NB 125 mm 300 mm Nos. 3,600 Incl. 3,600 12% 4,032

c) NB 150 mm 300 mm Nos. 4,080 Incl. 4,080 12% 4,570

d) NB 200 mm 300 mm Nos. 5,480 Incl. 5,480 12% 6,138

e) NB 250 mm 300 mm Nos. 6,827 Incl. 6,827 12% 7,646

f) NB 300 mm 300 mm Nos. 9,000 Incl. 9,000 12% 10,080

g) NB 350 mm 300 mm Nos. 11,100 Incl. 11,100 12% 12,432

h) NB 400 mm 300 mm Nos. 14,700 Incl. 14,700 12% 16,464

i) NB 450 mm 300 mm Nos. 17,400 Incl. 17,400 12% 19,488

j) NB 500 mm 300 mm Nos. 19,500 Incl. 19,500 12% 21,840

k) NB 600 mm 300 mm Nos. 26,000 Incl. 26,000 12% 29,120

l) NB 700 mm 300 mm Nos. 33,100 Incl. 33,100 12% 37,072

m) NB 750 mm 300 mm Nos. 39,727 Incl. 39,727 12% 44,494

n) NB 800 mm 300 mm Nos. 42,380 Incl. 42,380 12% 47,466

o) NB 900 mm 300 mm Nos. 47,680 Incl. 47,680 12% 53,402

p) NB 1000 mm 350 mm Nos. 45,254 Incl. 45,254 12% 50,684

q) NB 1100 mm 350 mm Nos. 88,200 Incl. 88,200 12% 98,784

r) NB 1200 mm 350 mm Nos. 98,480 Incl. 98,480 12% 110,298

Page 74 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates
No. Prevailing
Rates exclusive of GST inclusive of
rates of GST
GST
s) NB 1300 mm 350 mm Nos. 104,954 Incl. 104,954 12% 117,548

t) NB 1400 mm 350 mm Nos. 113,054 Incl. 113,054 12% 126,620

u) NB 1500 mm 350 mm Nos. 119,380 Incl. 119,380 12% 133,706

v) NB 1600 mm 400 mm Nos. 125,580 Incl. 125,580 12% 140,650

w) NB 1700 mm 400 mm Nos. 131,880 Incl. 131,880 12% 147,706

x) NB 1800 mm 450 mm Nos. 138,027 Incl. 138,027 12% 154,590

y) NB 1900 mm 450 mm Nos. 144,080 Incl. 144,080 12% 161,370

z) NB 2000 mm 450 mm Nos. 150,127 Incl. 150,127 12% 168,142

aa) NB 2200 mm 500 mm Nos. 163,480 Incl. 163,480 12% 183,098

ab) NB 2400 mm 500 mm Nos. 176,754 Incl. 176,754 12% 197,964

ac) NB 2500 mm 550 mm Nos. 182,580 Incl. 182,580 12% 204,490

C PN - 2.0

Size Width Nos.

a) NB 100 mm 300 mm Nos. 3,627 Incl. 3,627 12% 4,062

b) NB 125 mm 300 mm Nos. 3,927 Incl. 3,927 12% 4,398

c) NB 150 mm 300 mm Nos. 4,227 Incl. 4,227 12% 4,734

d) NB 200 mm 300 mm Nos. 5,680 Incl. 5,680 12% 6,362

e) NB 250 mm 300 mm Nos. 7,127 Incl. 7,127 12% 7,982

f) NB 300 mm 300 mm Nos. 11,250 Incl. 11,250 12% 12,600

g) NB 350 mm 300 mm Nos. 13,900 Incl. 13,900 12% 15,568

h) NB 400 mm 300 mm Nos. 18,400 Incl. 18,400 12% 20,608

i) NB 450 mm 300 mm Nos. 21,750 Incl. 21,750 12% 24,360

j) NB 500 mm 300 mm Nos. 24,400 Incl. 24,400 12% 27,328

k) NB 600 mm 300 mm Nos. 32,500 Incl. 32,500 12% 36,400

l) NB 700 mm 300 mm Nos. 38,580 Incl. 38,580 12% 43,210

m) NB 750 mm 300 mm Nos. 41,327 Incl. 41,327 12% 46,286

n) NB 800 mm 300 mm Nos. 44,080 Incl. 44,080 12% 49,370

o) NB 900 mm 300 mm Nos. 51,480 Incl. 51,480 12% 57,658

p) NB 1000 mm 350 mm Nos. 92,927 Incl. 92,927 12% 104,078

q) NB 1100 mm 350 mm Nos. 100,180 Incl. 100,180 12% 112,202

r) NB 1200 mm 350 mm Nos. 107,327 Incl. 107,327 12% 120,206

s) NB 1300 mm 350 mm Nos. 114,380 Incl. 114,380 12% 128,106

t) NB 1400 mm 350 mm Nos. 123,227 Incl. 123,227 12% 138,014

u) NB 1500 mm 350 mm Nos. 130,127 Incl. 130,127 12% 145,742

v) NB 1600 mm 400 mm Nos. 136,880 Incl. 136,880 12% 153,306

w) NB 1700 mm 400 mm Nos. 143,727 Incl. 143,727 12% 160,974

x) NB 1800 mm 450 mm Nos. 150,427 Incl. 150,427 12% 168,478

y) NB 1900 mm 450 mm Nos. 157,027 Incl. 157,027 12% 175,870

z) NB 2000 mm 450 mm Nos. 163,627 Incl. 163,627 12% 183,262

aa) NB 2200 mm 500 mm Nos. 178,180 Incl. 178,180 12% 199,562

ab) NB 2400 mm 500 mm Nos. 192,627 Incl. 192,627 12% 215,742

ac) NB 2500 mm 550 mm Nos. 199,027 Incl. 199,027 12% 222,910

D PN - 2.5

Size Width Nos.

Page 75 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates
No. Prevailing
Rates exclusive of GST inclusive of
rates of GST
GST
a) NB 100 mm 300 mm Nos. 4,500 Incl. 4,500 12% 5,040

b) NB 125 mm 300 mm Nos. 4,980 Incl. 4,980 12% 5,578

c) NB 150 mm 300 mm Nos. 5,354 Incl. 5,354 12% 5,996

d) NB 200 mm 300 mm Nos. 7,227 Incl. 7,227 12% 8,094

e) NB 250 mm 300 mm Nos. 9,054 Incl. 9,054 12% 10,140

f) NB 300 mm 300 mm Nos. 13,500 Incl. 13,500 12% 15,120

g) NB 350 mm 300 mm Nos. 16,650 Incl. 16,650 12% 18,648

h) NB 400 mm 300 mm Nos. 22,050 Incl. 22,050 12% 24,696

i) NB 450 mm 300 mm Nos. 26,100 Incl. 26,100 12% 29,232

j) NB 500 mm 300 mm Nos. 29,250 Incl. 29,250 12% 32,760

k) NB 600 mm 300 mm Nos. 39,000 Incl. 39,000 12% 43,680

l) NB 700 mm 300 mm Nos. 48,980 Incl. 48,980 12% 54,858

m) NB 750 mm 300 mm Nos. 52,480 Incl. 52,480 12% 58,778

n) NB 800 mm 300 mm Nos. 55,980 Incl. 55,980 12% 62,698

o) NB 900 mm 300 mm Nos. 65,380 Incl. 65,380 12% 73,226

p) NB 1000 mm 350 mm Nos. 113,400 Incl. 113,400 12% 127,008

q) NB 1100 mm 350 mm Nos. 127,227 Incl. 127,227 12% 142,494

r) NB 1200 mm 350 mm Nos. 136,280 Incl. 136,280 12% 152,634

s) NB 1300 mm 350 mm Nos. 145,254 Incl. 145,254 12% 162,684

t) NB 1400 mm 350 mm Nos. 156,480 Incl. 156,480 12% 175,258

u) NB 1500 mm 350 mm Nos. 165,254 Incl. 165,254 12% 185,084

v) NB 1600 mm 400 mm Nos. 173,827 Incl. 173,827 12% 194,686

w) NB 1700 mm 400 mm Nos. 182,527 Incl. 182,527 12% 204,430

x) NB 1800 mm 450 mm Nos. 191,027 Incl. 191,027 12% 213,950

y) NB 1900 mm 450 mm Nos. 199,427 Incl. 199,427 12% 223,358

z) NB 2000 mm 450 mm Nos. 207,780 Incl. 207,780 12% 232,714

aa) NB 2200 mm 500 mm Nos. 226,280 Incl. 226,280 12% 253,434

ab) NB 2400 mm 500 mm Nos. 244,627 Incl. 244,627 12% 273,982

ac) NB 2500 mm 550 mm Nos. 252,754 Incl. 252,754 12% 283,084

Page 76 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
15 SEWAGE NoN CLOG, END SUCTION TYPE HORIZONTAL CENTRIFUGAL PUMP

Supply of non clog sewage end suction type horizontal centrifugal pump set of required capapcity & head with suitable TEFC squirrel cage
foot mounted induction motor working on three phase 50 Hz ± 3%, 415V ± 10% AC supply, 1500 RPM synchronous speed along with base
frame, coupling with guard, foundation bolts, strainer etc. complete set as per relevant IS & following M.O.C: Casing: 1.5 to 2% Ni. C.I;
Impeller & wearing ring: SS-CF8M, Shaft with sleeve: S.S. & Base frame: C.I., Guide Pipe: SS.

1 Up to 18.5 kW (25 HP) Set 60,654 - 60,654 12% 67,933

2 22 kW (30 HP) Set 78,393 - 78,393 12% 87,800

3 30 kW (40 HP) Set 78,393 - 78,393 12% 87,800

4 37 kW (50 HP) Set 81,397 - 81,397 12% 91,165

5 45 kW (60 HP) Set 122,453 - 122,453 12% 137,147

6 55 kW (75 HP) Set 140,906 - 140,906 12% 157,815

7 75 kW (100 HP) Set 185,968 - 185,968 12% 208,284

8 90 kW (120 HP) Set 321,867 - 321,867 12% 360,491

9 110 kW (150 HP) Set - - - 12% -

10 125/132 kW (170/180 HP) Set 457,767 - 457,767 12% 512,699

11 150/160 kW (200/215 HP) Set - - - 12% -

12 180/200 kW (240/270 HP) Set 529,293 - 529,293 12% 592,808

13 250 kW (335 HP) Set 629,429 - 629,429 12% 704,961

14 315 kW (425 HP) Set 629,429 - 629,429 12% 704,961

16 SEWAGE NoN CLOG, END SUCTION TYPE VERTICAL CENTRIFUGAL PUMP

Supply of non clog seweage vertically mounted end suction type vertical centrifugal pump set of required capapcity & head with suitable
TEFC squirrel cage foot mounted induction motor working on three phase 50 Hz ± 3%, 415V ± 10% AC supply, 1500 RPM synchronous
speed including suitable provision of extended shaft of 2 meters length to couple with motor along with base frame, coupling with guard,
foundation bolts, strainer etc. complete set as per relevant IS & following M.O.C: Casing: 1.5 to 2% Ni. C.I; Impeller & wearing ring: SS /
CF8M, Shaft with sleeve: S.S. & Base frame: C. I; Guide Pipe: S. S.

1 Up to 18.5 kW (25 HP) Set 72,785 - 72,785 12% 81,519

2 22 kW (30 HP) Set 94,071 - 94,071 12% 105,359

3 30 kW (40 HP) Set 94,071 - 94,071 12% 105,359

4 37 kW (50 HP) Set 97,676 - 97,676 12% 109,397

5 45 kW (60 HP) Set 146,943 - 146,943 12% 164,576

6 55 kW (75 HP) Set 169,087 - 169,087 12% 189,378

7 75 kW (100 HP) Set 223,162 - 223,162 12% 249,941

8 90 kW (120 HP) Set 386,241 - 386,241 12% 432,590

9 110 kW (150 HP) Set - - - 12% -

10 125/132 kW (170/180 HP) Set 549,320 - 549,320 12% 615,239

11 150/160 kW (200/215 HP) Set - - - 12% -

12 180/200 kW (240/270 HP) Set 635,151 - 635,151 12% 711,369

13 250 kW (335 HP) Set 755,316 - 755,316 12% 845,954

14 315 kW (425 HP) Set 755,316 - 755,316 12% 845,954

17 POLDER TYPE SUBMERSIBLE PUMP

Providing submersible, Non clog type with required capapcity & head as per IS 8034 suitable for water having upto 10000 PPM turbidity
with suitable submersible wet type, water cooled, squirrel cage motor to IS 9283, working on three phase, 50 Hz +/-3%, 415V +/- 10%, AC
supply, 2900 RPM synchroNous speed with 10 mtr copper conductor flat cable from pump to starter panel with cable end terminations (4)
all supports, clamps, pipe fittings alongwith mechanical seal, bearing bush, strainer etc. complete set & following M.O.C: Casing CI, SS
CF8M impeller, Bronze: wearing ring & Bearing bush, TC mechanical seal, CS/S.S.bearing, S.S shaft with sleeve, SS strainer & MS motor
body.

Page 77 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1 Upto 3 HP Set 67,600 - 67,600 12% 75,712

2 5 HP Set 71,700 - 71,700 12% 80,304

3 7.5 HP Set 80,600 - 80,600 12% 90,272

4 10 HP Set 88,000 - 88,000 12% 98,560

5 12.5 HP Set 101,500 - 101,500 12% 113,680

6 15 HP Set 139,514 - 139,514 12% 156,256

7 20 HP Set 144,464 - 144,464 12% 161,799

8 25 HP Set 172,200 - 172,200 12% 192,864

9 30 HP Set 180,900 - 180,900 12% 202,608

10 40 HP Set 330,900 - 330,900 12% 370,608

11 50 HP Set 297,098 - 297,098 12% 332,750

12 60 HP Set 343,446 - 343,446 12% 384,660

13 75 HP Set 412,500 - 412,500 12% 462,000

14 100 HP Set 463,950 - 463,950 12% 519,624

18 SUBMERSIBLE SEWAGE NON-CLOG VERTICAL PUMP

Providing sewage submersible, Non clog type suitable for working on Air filled Dry type motor, three phase, 50 Hz +/-3%, 415V +/- 10%, AC
supply, 1500 RPM synchronous speed with 3 core flat copper cable from pump to starter panel with cable end terminations (4) all
supports, clamps, pipe fittings alongwith mechanical seal, bearing bush, strainer etc. complete set & following M.O.C: Casing CI, SS CF8M
impeller, Bronze: wearing ring & Bearing bush, TC mechanical seal, CS/S.S.bearing, S.S shaft with sleeve, SS strainer & MS motor body.

1 Upto 3 Hp Set 121,957 - 121,957 12% 136,592

2 5 HP Set 136,099 - 136,099 12% 152,431

3 7.5 HP Set 157,886 - 157,886 12% 176,832

4 10 HP Set 173,052 - 173,052 12% 193,818

5 12.5 HP Set 229,187 - 229,187 12% 256,690

6 15 HP Set 253,436 - 253,436 12% 283,849

7 20 HP Set 318,050 - 318,050 12% 356,216

8 25 HP Set 329,905 - 329,905 12% 369,494

9 30 HP Set 404,131 - 404,131 12% 452,627

10 40 HP Set 556,606 - 556,606 12% 623,399

11 50 HP Set 584,801 - 584,801 12% 654,977

12 60 HP Set 659,668 - 659,668 12% 738,828

13 75 HP Set 957,106 - 957,106 12% 1,071,959

14 100 HP Set 990,214 - 990,214 12% 1,109,040

19 11 KV Double / Four Pole Structure Assembly

19.1 11 kV Two Pole Structure Assembly:


SITC of 11 kV double pole 9 mtr. high structure made of 6" X 3" 'I" section girder, 4" X 2" channels, clamps, nuts, bolts, stay wires including earthing
system with following accessories duly connected with ACSR conductors as per approved drawing & in compliance with requirement of IEC.
(a) 11 kV, 200 A drop out fuses with Synthetic Resin Bonded Paper (SRBP) tubes: 1 Set (01 piece per phase).
(b) 11 kV, 400 A G.O.D. switch complete with earth switch, insulators, operating handle with galvanised pipe, square bar: 1 Set.
(c) 11 kV lightning arrestor with clamps: 3 Nos.
(d) 11 kV Disc Insulators (70KN): 3 Nos.
(e) 11 kV Pin Insulators (5KN): 3 Nos.
(f) 20 mm dia. GI. Stay Sets Complete: 2 Set.

11 kV Double Pole Structure Assembly Each 96,120 24,543 120,663 18% 142,383

Page 78 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
19.2 11 kV Four Pole Structure Assembly:
SITC of 11 kV double pole 9 mtr. high structure made of 6" X 3" 'I" section girder, 4" X 2" channels, clamps, nuts, bolts, stay wires including earthing
system with following accessories duly connected with ACSR conductors as per approved drawing & in compliance with requirement of IEC.
(a) 11 kV, 200 A drop out fuses with Synthetic Resin Bonded Paper (SRBP) tubes: 2 Set (01 piece per phase/circuit).
(b) 11 kV, 400 A G.O.D. switch complete with earth switch, insulators, operating handle with galvanised pipe, square bar: 2 Set.
(c) 11 kV lightning arrestor with clamps: 3 Nos.
(d) 11 kV Disc Insulators (70KN): 9 Nos.
(e) 11 kV Pin Insulators (5KN): 6 Nos.
(f) 20 mm dia. GI. Stay Sets Complete: 2 Set

11 kV Four Pole Structure Assembly Each 116,640 34,542 151,182 18% 178,395

20 Transformer

20.1 SITC of outdoor type, three phase, oil immerged, distribution transformer of required KVA & voltage ratio, copper double wound, vector group -
Dyn11, HV delta connected & LV star connected with neutral brought out connected to provide separate earthing terminals, bushing / cable box on
HV side and cable box on LV side suitable for cables or bus duct as per requirement with standard fittings, conforming to IS: 1180 (Part-1) / 2014 with
its latest amendment including first fill of transformer oil & following accessories.
(a) Oil conservator with filling holes with cap and prismatic oil level gauge.
(b) Silica Gel dehydrating breather charged with silica gel
(c) Oil drain cum sampling valve with plug
(d) Oil filter valve
(e) Lifting Eyes / Hooks / Lugs
(f) Two earthing terminal
(g) Diagram and rating plate
(h) Air release plug
(i) Explosion vent with diaphragm
(j) Thermometer pocket
(k) Four bi-directional plain roller with base channel with hauling holes
(l) Fixed / Separate type radiator banks
(m) Off circuit externally operated tapping switch (For rating < 1000 kVA)
(n) 100 mm stem type oil temperature indicator (For rating < 500 kVA)
(o) Bucholtz relay with shut off valve (For rating ≥ 500 KVA)
(p) 150 mm dial type oil temperature indicator with Alarm / Trip contact (For rating ≥ 500 kVA)
(q) 150 mm dial type winding temperature indicator with Alarm / Tip contact (For rating ≥ 1000 kVA)
(r) Marshalling box (For rating ≥ 500 kVA)
(s) 150 mm dia. magnetic type oil gauge (For rating ≥ 1600 kVA)
(t) Inspection cover & Jacking lugs (For rating ≥ 1600 kVA)
20.1.1 With off circuit tap changer ± 7.5% in steps of 2.5%

Voltage Ratio (kV) Rating Maximum


(11/0.433), (6.6/433) & (kVA) Total Losses
(3.3/0.433) (kW)
@ 50% /
@ 100% /
% Imp

a Eff. Level-2 160 0.67/ 1.95/ 4.5 Set 350,997 30,000 380,997 18% 449,576

b Eff. Level-3 0.57/ 1.7/ 4.5 Set 386,097 30,000 416,097 18% 490,994

c Eff. Level-2 200 0.78/ 2.3/ 4.5 Set 412,860 30,000 442,860 18% 522,575

d Eff. Level-3 0.67/ 2.1/ 4.5 Set 454,146 30,000 484,146 18% 571,292

e Eff. Level-2 250 0.98/ 2.93/ 4.5 Set 491,593 30,000 521,593 18% 615,480

f Eff. Level-3 0.92/ 2.7/ 4.5 Set 540,752 30,000 570,752 18% 673,488

g Eff. Level-2 315 1.02/ 3.1/ 4.5 Set 581,574 30,000 611,574 18% 721,658

h Eff. Level-3 0.95/ 2.75/ 4.5 Set 639,732 30,000 669,732 18% 790,283

i Eff. Level-2 400 1.25/ 3.45/ 4.5 Set 659,757 35,000 694,757 18% 819,814

j Eff. Level-3 1.15/ 3.3/ 4.5 Set 725,733 35,000 760,733 18% 897,665

k Eff. Level-2 500 1.51/ 4.3/ 4.5 Set 715,996 35,000 750,996 18% 886,175

l Eff. Level-3 1.43/ 4.1/ 4.5 Set 787,595 35,000 822,595 18% 970,662

m Eff. Level-2 630 1.86/ 5.3/ 4.5 Set 839,720 35,000 874,720 18% 1,032,170

n Eff. Level-3 1.74/ 4.85/ 4.5 Set 923,692 35,000 958,692 18% 1,131,257

o Eff. Level-2 800 2.28/ 6.4/ 5.0 Set 873,523 40,000 913,523 18% 1,077,957

p Eff. Level-3 2.14/ 5.83/ 5.0 Set 960,875 40,000 1,000,875 18% 1,181,033

q Eff. Level-2 1000 2.7/ 7.7/ 5.0 Set 1,003,940 40,000 1,043,940 18% 1,231,850

r Eff. Level-3 2.62/ 7.0/ 5.0 Set 1,104,334 40,000 1,144,334 18% 1,350,314

20.1.2 With on load tap changer ± 10% steps of 1.25% with RTCC & AVR.

Page 79 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
Voltage Ratio (kV) Rating Maximum Total
(11/0.433), (6.6/433) & (kVA) Losses (kW)
(3.3/0.433) @ 50% Load /
a Eff. Level-2 1000 2.79/ 7.7/ 5.0 Set 1,580,415 50,000 1,630,415 18% 1,923,890

b Eff. Level-3 3.3/ 9.2/ 5.0 Set 1,738,457 50,000 1,788,457 18% 2,110,379

c Eff. Level-2 1250 3.3/ 9.20/ 5.0 Set 1,637,960 50,000 1,687,960 18% 1,991,793

d Eff. Level-3 3.2/ 8.44/ 5.0 Set 1,801,756 50,000 1,851,756 18% 2,185,073

e Eff. Level-2 1600 4.2/ 11.8/ 6.25 Set 1,854,261 50,000 1,904,261 18% 2,247,028

f Eff. Level-3 3.97/ 11.3/ Set 2,039,687 50,000 2,089,687 18% 2,465,831
6.25
g Eff. Level-2 2000 5.05/ 15.0/ Set 2,065,220 60,000 2,125,220 18% 2,507,760
6.25
h Eff. Level-3 4.79/ 14.1/ Set 2,271,743 60,000 2,331,743 18% 2,751,456
6.25
i Eff. Level-2 2500 6.15/ 18.5/ Set 2,335,597 60,000 2,395,597 18% 2,826,805
6.25
j Eff. Level-3 5.9/ 17.5/ 6.25 Set 2,569,157 60,000 2,629,157 18% 3,102,405

20.2 SITC of outdoor type, three phase, oil immerged, power transformer of required KVA & voltage ratio, copper double wound, vector group - Dyn11, HV
delta connected & LV star connected with neutral brought out connected to provide separate earthing terminals, bushing / cable box on HV side and
cable box on LV side suitable for cables or bus duct as per requirement with standard fittings, conforming to IS: 2026 - 2011 with its latest
amendment including first fill of transformer oil & following accessories.
(a) Oil conservator with filling holes with cap and prismatic oil level gauge. (b) Silica Gel dehydrating breather charged with silica gel (c) Oil drain cum
sampling valve with plug (d) Oil filter valve (e) Lifting Eyes / Hooks / Lugs (f) Two earthing terminal (g) Diagram and rating plate (h) Air release plug (i)
Explosion vent with diaphragm (j) Thermometer pocket
(k) Four bi-directional plain roller with base channel with hauling holes (l) Fixed / Separate type radiator banks (m) Off circuit externally operated
tapping switch (For rating < 1000 kVA)
(n) 100 mm stem type oil temperature indicator (For rating < 500 kVA) (o) Bucholtz relay with shut off valve (For rating ≥ 500 KVA) (p) 150 mm dial
type oil temperature indicator with Alarm / Trip contact (For rating ≥ 500 kVA) (q) 150 mm dial type winding temperature indicator with Alarm / Tip
contact (For rating ≥ 1000 kVA) (r) Marshalling box (For rating ≥ 500 kVA)
(s) 150 mm dia. magnetic type oil gauge (For rating ≥ 1600 kVA) (t) Inspection cover & Jacking lugs (For rating ≥ 1600 kVA)
20.2.1 With off circuit tap changer ± 7.5% in steps of 2.5%

Voltage Ratio (kV) Rating Maximum


(kVA) Losses (kW)
a 11/3.3 160 As per Set 256,200 30,000 286,200 18% 337,716
CBIP Manual
b 11/3.3 200 Set 298,123 30,000 328,123 18% 387,185

c 11/3.3 250 Set 330,730 30,000 360,730 18% 425,662

d 11/3.3 315 Set 367,996 35,000 402,996 18% 475,535

e 11/3.3 400 Set 433,210 35,000 468,210 18% 552,488

f 11/3.3 500 Set 517,057 35,000 552,057 18% 651,428

g 11/3.3 630 Set 596,246 35,000 631,246 18% 744,871

h 11/3.3 750 Set 656,803 40,000 696,803 18% 822,227

i 11/3.3 800 Set 698,726 40,000 738,726 18% 871,697

j 11/3.3 1000 Set 791,890 40,000 831,890 18% 981,630

k 11/6.6 160 Set 246,883 30,000 276,883 18% 326,722

l 11/6.6 200 Set 293,465 30,000 323,465 18% 381,689

m 11/6.6 250 Set 326,072 30,000 356,072 18% 420,165

n 11/6.6 315 Set 363,338 35,000 398,338 18% 470,038

o 11/6.6 400 Set 428,552 35,000 463,552 18% 546,991

p 11/6.6 500 Set 512,399 35,000 547,399 18% 645,931

q 11/6.6 630 Set 591,588 35,000 626,588 18% 739,374

r 11/6.6 750 Set 652,145 40,000 692,145 18% 816,731

s 11/6.6 800 Set 689,410 40,000 729,410 18% 860,704

t 11/6.6 1000 Set 981,012 40,000 1,021,012 18% 1,204,794

20.2.2 With on load tap changer ± 10% in steps of 1.25% with RTCC & AVR

Page 80 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
Voltage Ratio (kV) Rating Maxim
(kVA) um
Losse
s (kW)
No
Load
Loss
&
Load
Loss

a 11/3.3 1000 As per Set 1,183,176 40,000 1,223,176 18% 1,443,348


CBIP Manual
b 11/3.3 1250 Set 1,403,974 50,000 1,453,974 18% 1,715,689

c 11/3.3 1600 Set 1,467,325 50,000 1,517,325 18% 1,790,444

d 11/3.3 2000 Set 1,720,730 50,000 1,770,730 18% 2,089,461

e 11/3.3 2500 Set 1,788,739 60,000 1,848,739 18% 2,181,512

f 11/3.3 3150 Set 1,937,801 70,000 2,007,801 18% 2,369,205

g 11/3.3 3500 Set 2,156,735 70,000 2,226,735 18% 2,627,547

h 11/3.3 4000 Set 2,343,062 70,000 2,413,062 18% 2,847,413

i 11/6.6 1000 Set 1,173,860 40,000 1,213,860 18% 1,432,355

j 11/6.6 1250 Set 1,280,998 50,000 1,330,998 18% 1,570,578

k 11/6.6 1600 Set 1,462,667 50,000 1,512,667 18% 1,784,947

l 11/6.6 2000 Set 1,597,754 50,000 1,647,754 18% 1,944,350

m 11/6.6 2500 Set 1,784,081 60,000 1,844,081 18% 2,176,016

n 11/6.6 3150 Set 1,933,143 70,000 2,003,143 18% 2,363,708

o 11/6.6 3500 Set 2,147,419 70,000 2,217,419 18% 2,616,554

p 11/6.6 4000 Set 2,343,062 70,000 2,413,062 18% 2,847,413

q 66/6.6 5000 Set 3,423,759 80,000 3,503,759 18% 4,134,435

r 66/6.6 6300 Set 4,038,638 80,000 4,118,638 18% 4,859,993

s 66/6.6 7500 Set 4,085,219 90,000 4,175,219 18% 4,926,759

t 66/6.6 10000 Set 4,085,219 90,000 4,175,219 18% 4,926,759

u 66/6.6 12500 Set 5,030,829 100,000 5,130,829 18% 6,054,378

v 66/6.6 15000 Set 5,818,061 110,000 5,928,061 18% 6,995,111

w 66/6.6 20000 Set 6,768,328 120,000 6,888,328 18% 8,128,227

x 66/11 5000 Set 3,433,075 80,000 3,513,075 18% 4,145,428

y 66/11 6300 Set 4,052,612 80,000 4,132,612 18% 4,876,482

z 66/11 7500 Set 4,099,194 90,000 4,189,194 18% 4,943,249

aa 66/11 10000 Set 4,565,011 100,000 4,665,011 18% 5,504,713

ab 66/11 12500 Set 4,993,564 100,000 5,093,564 18% 6,010,405

ac 66/11 15000 Set 5,832,035 110,000 5,942,035 18% 7,011,601

ad 66/11 20000 Set 6,791,619 120,000 6,911,619 18% 8,155,711

ae 11/0.433 3150 Set 2,142,761 70,000 2,212,761 18% 2,611,057

af 11/0.433 3500 Set 2,387,781 70,000 2,457,781 18% 2,900,181

ag 11/0.433 4000 Set 2,515,415 70,000 2,585,415 18% 3,050,789

20.3 Casting of transformer plinth / foundation including oil soak pit (where required) in situ reinforced cement concrete in M 20 using granite,
quartzite trap metal of size 6 mm to 20 mm for RCC work including providing of 53 grade cement & Fe 415 grade TMT bars, scaffolding,
centering, form work, curing etc. complete.

20.3.1 RCC plinth / foundation for transformer of capacity ≤ 315 KVA.

System Voltage (Pri)/ Transf Plinth


Tap Switch ormer Dimensions
Rating (L x W x H)
(kVA)
a up to 11 kV/ OCTC 160 1250x1250x Set 30,000 - 30,000 18% 35,400
1500
b 200 1250x1250x Set 30,000 - 30,000 18% 35,400
1500

Page 81 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
c 250 1250x1250x Set 30,000 - 30,000 18% 35,400
1500
d 315 1250x1250x Set 30,000 - 30,000 18% 35,400
1500
20.3.2 RCC plinth / foundation for transformer of capacity ˃315 & ≤ 630 KVA.

System Voltage (Pri)/ Transf Plinth


Tap Switch ormer Dimensions
Rating (L x W x H)
(kVA)
a up to 33 kV/ OCTC 400 1500x1500x Set 35,000 - 35,000 18% 41,300
1500
b 500 1500x1500x Set 35,000 - 35,000 18% 41,300
1500
c 630 1500x1500x Set 35,000 - 35,000 18% 41,300
1500
20.3.3 RCC plinth / foundation for transformer of capacity ˃630 & ≤1000 KVA.

System Voltage (Pri)/ Transf Plinth


Tap Switch ormer Dimensions
Rating (L x W x H)
(kVA)
a up to 33 kV/ OCTC 750 1750x1750x Set 40,000 - 40,000 18% 47,200
1000
b 800 1750x1750x Set 40,000 - 40,000 18% 47,200
1000
c 1000 1500x1500x Set 40,000 - 40,000 18% 47,200
1500
20.3.4 RCC plinth / foundation for distribution transformer of capacity ≥1000 & ≤1600 KVA.

System Voltage(Pri)/ Transf Plinth


Tap Switch ormer Dimensions
Rating (L x W x H)
(kVA)
a up to 33 kV/ OLTC 1000 1750x1750x Set 50,000 - 50,000 18% 59,000
1000
b 1250 1750x1750x Set 50,000 - 50,000 18% 59,000
1000
c 1600 1750x1750x Set 50,000 - 50,000 18% 59,000
1000
20.3.5 RCC plinth / foundation for distribution transformer of capacity ˃1600 & ≤2500 KVA.

System Voltage(Pri)/ Transf Plinth


Tap Switch ormer Dimensions
Rating (L X W X H)
(kVA)
a up to 33 kV/ OLTC 2000 2000 x 2000 x Set 60,000 - 60,000 18% 70,800
1000
b 2500 2000 x 2000 x Set 60,000 - 60,000 18% 70,800
1000
20.3.6 RCC plinth / foundation for transformer of 2000 x 2000 x
capacity ˃2500 & ≤4000 KVA. 1000
System Voltage(Pri)/ Transf Plinth
Tap Switch ormer Dimensions
Rating (L X W X H)
(kVA)
a up to 66 kV/ OLTC 3150 2250 x 2250 x Set 70,000 - 70,000 18% 82,600
1000
b 3500 2250 x 2250 x Set 70,000 - 70,000 18% 82,600
1000
c 4000 2250 x 2250 x Set 70,000 - 70,000 18% 82,600
1000
20.3.7 RCC plinth / foundation for distribution transformer of capacity ˃4000 & ≤10000 KVA.

System Voltage(Pri)/ Transf Plinth


Tap Switch ormer Dimensions
Rating (L X W X H)
(kVA)
a up to 66 kV/ OLTC 5000 2500 x 2500 x Set 80,000 - 80,000 18% 94,400
500
b 6300 2500 x 2500 x Set 80,000 - 80,000 18% 94,400
500
c 7500 2500 x 2500 x Set 80,000 - 80,000 18% 94,400
500
d 10000 2500 x 2500 x Set 80,000 - 80,000 18% 94,400
500
20.3.8 RCC plinth / foundation for distribution transformer of capacity ˃10000 & ≤20000 KVA.

Page 82 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
System Voltage(Pri)/ Transf Plinth
Tap Switch ormer Dimensions
Rating (L X W X H)
(kVA)
a up to 66 kV/ OLTC 12500 3000 x 2500 x Set 90,000 - 90,000 18% 106,200
500
b 15000 3000 x 2500 x Set 90,000 - 90,000 18% 106,200
500
c 20000 3000 x 2500 x Set 90,000 - 90,000 18% 106,200
500
21 Microprocessor Based LV Variable Frequency Drive

Supplying, erecting, commissioning of 415 V Fully automatic microprocessor based Variable Frequency drive for pump control application
as per general specification as under:
The VFD unit shall have modular construction, 6 Pulse Bridge rectifier, speed control by means of sensorless vector control (open loop),
high torque at low frequencies, locking at high and low frequency settings, In-built PID control, frequency accuracy of ± 0.1 % (min),
frequency resolution of ± 0.1 Hz (min), protections against; a) overload (motor and drive), b) short circuit, c) ground fault, d) input/ output
phase loss (open circuit), e) stalling, f) input/ output undervoltage (momentary power loss restart), g) input/ output overvoltage, h) over-
frequency, i) Input surge, j) over temperature of heatsink, k) loss of remote speed signal etc. The VFD shall also have user-friendly
programming software & it shall be capable of at least two level parameter setting with password lock for critical parameters,
programming for I/Os, speed search function, copy parameters (upload/download) to other identical unit, tuning to energy saving mode
(maximum efficiency), event/fault recording (last 5 faults in non-volatile memory) & RS485 communication port (MODBUS RTU protocol)
with required software.

a) 2.2 kW No. 12,758 4,545 17,303 18% 20,418

b) 3 kW No. 13,749 4,545 18,294 18% 21,587

c) 4 kW No. 13,749 4,545 18,294 18% 21,587

d) 5.5 kW No. 13,749 4,545 18,294 18% 21,587

e) 7.5 kW No. 18,148 4,545 22,693 18% 26,778

f) 11 kW No. 21,668 4,545 26,213 18% 30,931

g) 15 kW No. 29,147 4,545 33,692 18% 39,757

h) 18.5 kW No. 35,196 4,545 39,741 18% 46,894

i) 22 kW No. 42,895 4,545 47,440 18% 55,979

j) 30 kW No. 47,294 4,545 51,839 18% 61,170

k) 37 kW No. 70,153 4,545 74,698 18% 88,144

l) 45 kW No. 75,114 4,545 79,659 18% 93,998

m) 55 kW No. 88,319 4,545 92,864 18% 109,580

n) 75 kW No. 97,263 4,545 101,808 18% 120,133

o) 90 kW No. 122,374 4,545 126,919 18% 149,764

p) 110 kW No. 137,481 4,545 142,026 18% 167,591

q) 132 kW No. 173,777 4,545 178,322 18% 210,420

r) 160 kW No. 195,773 4,545 200,318 18% 236,375

s) 200 kW No. 263,963 4,545 268,508 18% 316,839

t) 250 kW No. 285,960 4,545 290,505 18% 342,796

u) 315 kW No. 307,958 4,545 312,503 18% 368,754

v) 355 kW No. 422,963 4,545 427,508 18% 504,459

w) 400 kW No. 503,083 4,545 507,628 18% 599,001

22 Microprocessor Based LV Soft Starter

22.1 Supplying, erecting & commissioning of 415 V Fully automatic Microprocessor based soft starter with external bypass arrangement for
pump control application as per general specification as under:
Control Method -Torque Control, Input voltage- 415V, 3 Phase, Input frequency -50/ 60 Hz (±5%), Confirmative to standard - IEC 61947-4-
2UL,CSA,CE,
Motor protection - inbuilt Thermal Protection, Starter protection - SC UV, Phase unbalance, Phase failure, EMC Std- IEC 61000-4-2 Level-3
& IEC 61000-4-3-Level-3, Built in communication as per RS 485.
a 30 kW No 33,539 4,545 38,084 18% 44,939

Page 83 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
b 37 kW No 38,198 4,545 42,743 18% 50,437

c 45 kW No 45,651 4,545 50,196 18% 59,231

d 55 kW No 48,446 4,545 52,991 18% 62,529

e 75 kW No 55,899 4,545 60,444 18% 71,324

f 90 kW No 59,625 4,545 64,170 18% 75,721

g 110 kW No 70,805 4,545 75,350 18% 88,913

h 132 kW No 78,258 4,545 82,803 18% 97,708

i 160 kW No 101,549 4,545 106,094 18% 125,191

j 220 kW No 194,340 4,545 198,885 18% 234,684

k 250 kW No 229,555 4,545 234,100 18% 276,238

l 315 kW No 288,901 4,545 293,446 18% 346,266

m 355 kW No 325,421 4,545 329,966 18% 389,360

n 400 kW No 325,421 4,545 329,966 18% 389,360

22.2 Supplying, erecting & commissioning of 415 V Fully automatic Microprocessor based soft starter with built in bypass arrangement for
pump control application as per general specification as under:
Control Method -Torque Control, Input voltage- 415V, 3 Phase, Input frequency - 50/ 60 Hz (±5%), Confirmative to standard - IEC 61947-4-
2UL,CSA,CE,
Motor protection - inbuilt Thermal Protection, Starter protection - SC UV, Phase unbalance, Phase failure, EMC Std- IEC 61000-4-2 Level-3
& IEC 61000-4-3-Level-3, Built in communication as per RS 485.
a 30 kW No 27,950 4,545 32,495 18% 38,344

b 37 kW No 30,744 4,545 35,289 18% 41,641

c 45 kW No 32,608 4,545 37,153 18% 43,841

d 55 kW No 36,334 4,545 40,879 18% 48,237

e 75 kW No 43,787 4,545 48,332 18% 57,032

f 90 kW No 46,582 4,545 51,127 18% 60,330

g 110 kW No 54,035 4,545 58,580 18% 69,124

h 132 kW No 61,488 4,545 66,033 18% 77,919

i 160 kW No 77,326 4,545 81,871 18% 96,608

j 220 kW No 102,480 4,545 107,025 18% 126,290

k 250 kW No 115,523 4,545 120,068 18% 141,680

l 315 kW No 128,566 4,545 133,111 18% 157,071

m 355 kW No 166,763 4,545 171,308 18% 202,143

n 400 kW No 166,763 4,545 171,308 18% 202,143

23 1.1 kV Grade Cable- Aluminium / Copper Conductor

23.1 Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round wire
armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes:

a 3 Core x 2.5 Sq mm Meter 49 6 55 18% 65

b 3 Core x 4.0 Sqmm Meter 49 6 55 18% 65

c 3 Core x 6.0 Sqmm Meter 57 6 63 18% 74

d 3 Core x 10 Sqmm Meter 71 6 77 18% 91

e 3 Core x 16 Sqmm Meter 76 6 82 18% 97

f 3 Core x 25 Sqmm Meter 96 6 102 18% 120

g 3 Core x 35 Sqmm Meter 121 8 129 18% 152

Page 84 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
h 3 Core x 50 Sqmm Meter 153 8 161 18% 190

i 3 Core x 70 Sqmm Meter 206 12 218 18% 257

j 3 Core x 95 Sqmm Meter 256 12 268 18% 316

k 3 Core x 120 Sqmm Meter 305 12 317 18% 374

l 3 Core x 150 Sqmm Meter 376 12 388 18% 458

m 3 Core x 185 Sqmm Meter 460 18 478 18% 564

n 3 Core x 240 Sqmm Meter 588 18 606 18% 715

o 3 Core x 300 Sqmm Meter 711 18 729 18% 860

p 3 Core x 400 Sqmm Meter 903 24 927 18% 1,094

q 3 Core x 500 Sqmm Meter 1,223 24 1,247 18% 1,472

r 3 Core x 630 Sqmm Meter 1,622 24 1,646 18% 1,943

23.2 Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round wire
armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes:

a 3.5 Core x 25 Sqmm Meter 108 12 120 18% 142

b 3.5 Core x 35 Sqmm Meter 136 12 148 18% 175

c 3.5 Core x 50 Sqmm Meter 177 12 189 18% 223

d 3.5 Core x 70 Sqmm Meter 240 17 257 18% 303

e 3.5 Core x 95 Sqmm Meter 290 17 307 18% 362

f 3.5 Core x 120 Sqmm Meter 362 17 379 18% 447

g 3.5 Core x 150 Sqmm Meter 428 23 451 18% 532

h 3.5 Core x 185 Sqmm Meter 534 23 557 18% 658

i 3.5 Core x 240 Sqmm Meter 672 29 701 18% 828

j 3.5 Core x 300 Sqmm Meter 824 29 853 18% 1,007

k 3.5 Core x 400 Sqmm Meter 1,048 35 1,083 18% 1,278

l 3.5 Core x 500 Sqmm Meter 1,426 35 1,461 18% 1,724

m 3.5 Core x 630 Sqmm Meter 1,936 36 1,972 18% 2,327

23.3 Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round wire
armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes:

a 4 Core x 2.5 Sqmm Meter 57 6 63 18% 74

b 4 Core x 4.0 Sqmm Meter 57 6 63 18% 74

c 4 Core x 6.0 Sqmm Meter 64 6 70 18% 83

d 4 Core x 10 Sqmm Meter 81 6 87 18% 103

e 4 Core x 16 Sqmm Meter 91 6 97 18% 115

f 4 Core x 25 Sqmm Meter 116 6 122 18% 144

g 4 Core x 35 Sqmm Meter 151 12 163 18% 192

h 4 Core x 50 Sqmm Meter 195 12 207 18% 244

i 4 Core x 70 Sqmm Meter 264 12 276 18% 326

j 4 Core x 95 Sqmm Meter 322 12 334 18% 394

k 4 Core x 120 Sqmm Meter 395 18 413 18% 488

l 4 Core x 150 Sqmm Meter 485 18 503 18% 594

Page 85 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
m 4 Core x 185 Sqmm Meter 603 18 621 18% 733

n 4 Core x 240 Sqmm Meter 770 24 794 18% 937

o 4 Core x 300 Sqmm Meter 927 24 951 18% 1,122

p 4 Core x 400 Sqmm Meter 1,179 24 1,203 18% 1,420

q 4 Core x 500 Sqmm Meter 1,600 24 1,624 18% 1,917

r 4 Core x 630 Sqmm Meter 2,164 24 2,188 18% 2,582

23.4 Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Copper conductor, galvanised steel flat strip / round wire armoured,
extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable trays / conduit /
pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-1) & IEC:60502 (Part-1), of following sizes:

a 3 Core x 2.5 Sqmm Meter 64 6 70 18% 83

b 3 Core x 4.0 Sqmm Meter 85 6 91 18% 107

c 3 Core x 6.0 Sqmm Meter 117 6 123 18% 145

d 3 Core x 10 Sqmm Meter 179 6 185 18% 218

e 3 Core x 16 Sqmm Meter 254 6 260 18% 307

f 3 Core x 25 Sqmm Meter 417 12 429 18% 506

g 3 Core x 35 Sqmm Meter 574 12 586 18% 692

h 3 Core x 50 Sqmm Meter 782 12 794 18% 937

i 3 Core x 70 Sqmm Meter 1,110 12 1,122 18% 1,324

j 3 Core x 95 Sqmm Meter 1,594 12 1,606 18% 1,895

k 3 Core x 120 Sqmm Meter 2,003 18 2,021 18% 2,385

l 3 Core x 150 Sqmm Meter 2,500 18 2,518 18% 2,971

m 3 Core x 185 Sqmm Meter 3,076 18 3,094 18% 3,651

n 3 Core x 240 Sqmm Meter 3,963 24 3,987 18% 4,705

o 3 Core x 300 Sqmm Meter 4,932 24 4,956 18% 5,848

p 3 Core x 400 Sqmm Meter 5,659 24 5,683 18% 6,706

23.5 Supply, laying, testing & commissioning of 1.1 kV grade, XLPE insulated, stranded Copper conductor, galvanised steel flat strip / round wire
armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-1) & IEC:60502 (Part-1), of following
sizes:

a 3.5 Core x 25 Sqmm Meter 502 12 514 18% 607

b 3.5 Core x 35 Sqmm Meter 658 12 670 18% 791

c 3.5 Core x 50 Sqmm Meter 914 12 926 18% 1,093

d 3.5 Core x 70 Sqmm Meter 1,293 17 1,310 18% 1,546

e 3.5 Core x 95 Sqmm Meter 1,862 17 1,879 18% 2,217

f 3.5 Core x 120 Sqmm Meter 2,386 17 2,403 18% 2,836

g 3.5 Core x 150 Sqmm Meter 2,883 23 2,906 18% 3,429

h 3.5 Core x 185 Sqmm Meter 3,596 23 3,619 18% 4,271

i 3.5 Core x 240 Sqmm Meter 4,619 29 4,648 18% 5,485

j 3.5 Core x 300 Sqmm Meter 5,754 29 5,783 18% 6,824

k 3.5 Core x 400 Sqmm Meter 7,485 35 7,520 18% 8,874

23.6 Supply, laying, testing & commissioning of 1.1 kV grade, XLPE insulated, stranded Copper conductor, galvanised steel flat strip / round wire
armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes:

Page 86 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
a 4 Core x 2.5 Sqmm Meter 60 6 66 18% 78

b 4 Core x 4.0 Sqmm Meter 108 6 114 18% 135

c 4 Core x 6.0 Sqmm Meter 151 6 157 18% 185

d 4 Core x 10 Sqmm Meter 231 6 237 18% 280

e 4 Core x 16 Sqmm Meter 333 6 339 18% 400

f 4 Core x 25 Sqmm Meter 549 6 555 18% 655

g 4 Core x 35 Sqmm Meter 757 12 769 18% 908

h 4 Core x 50 Sqmm Meter 1,036 12 1,048 18% 1,237

i 4 Core x 70 Sqmm Meter 1,483 12 1,495 18% 1,764

j 4 Core x 95 Sqmm Meter 2,133 12 2,145 18% 2,531

k 4 Core x 120 Sqmm Meter 2,685 18 2,703 18% 3,190

l 4 Core x 150 Sqmm Meter 3,350 18 3,368 18% 3,974

m 4 Core x 185 Sqmm Meter 4,120 18 4,138 18% 4,883

n 4 Core x 240 Sqmm Meter 5,311 24 5,335 18% 6,296

o 4 Core x 300 Sqmm Meter 6,617 24 6,641 18% 7,837

p 4 Core x 400 Sqmm Meter 8,682 24 8,706 18% 10,273

24 11 kV (Earthed / Unearthed) Grade Cable- Aluminium Conductor

24.1 Supply, laying, testing & commissioning of 6.35 / 11 kV (E) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round
wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-2) & IEC:60502 (Part-2) of following sizes:

a 3 Core x 35 Sqmm Meter 315 30 345 18% 407

b 3 Core x 50 Sqmm Meter 356 30 386 18% 456

c 3 Core x 70 Sqmm Meter 423 30 453 18% 535

d 3 Core x 95 Sqmm Meter 500 36 536 18% 633

e 3 Core x 120 Sqmm Meter 577 36 613 18% 724

f 3 Core x 150 Sqmm Meter 644 36 680 18% 803

g 3 Core x 185 Sqmm Meter 749 36 785 18% 927

h 3 Core x 240 Sqmm Meter 899 36 935 18% 1,104

i 3 Core x 300 Sqmm Meter 1,046 36 1,082 18% 1,277

j 3 Core x 400 Sqmm Meter 1,314 36 1,350 18% 1,593

24.2 Supply, laying, testing & commissioning 11 / 11 kV (UE) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip/ round wire
armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-2) & IEC:60502(Part-2), of following sizes:

a 3 Core x 70 Sqmm Meter 319 30 349 18% 412

b 3 Core x 95 Sqmm Meter 646 36 682 18% 805

c 3 Core x 120 Sqmm Meter 751 36 787 18% 929

d 3 Core x 150 Sqmm Meter 830 36 866 18% 1,022

e 3 Core x 185 Sqmm Meter 928 36 964 18% 1,138

f 3 Core x 240 Sqmm Meter 1,092 36 1,128 18% 1,331

g 3 Core x 300 Sqmm Meter 1,256 36 1,292 18% 1,525

h 3 Core x 400 Sqmm Meter 1,476 36 1,512 18% 1,785

25 6.6 kV (Earthed/ Unearthed) Grade Cable- Aluminium Conductor

Page 87 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
25.1 Supply, laying, testing & commissioning 3.8 / 6.6 kV (E) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round wire
armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-2) & IEC:60502 (Part-2) of following sizes:

a 3 Core x 70 Sqmm Meter 396 30 426 18% 503

b 3 Core x 95 Sqmm Meter 471 36 507 18% 599

c 3 Core x 120 Sqmm Meter 550 36 586 18% 692

d 3 Core x 150 Sqmm Meter 620 36 656 18% 775

e 3 Core x 185 Sqmm Meter 715 36 751 18% 887

f 3 Core x 240 Sqmm Meter 865 36 901 18% 1,064

g 3 Core x 300 Sqmm Meter 1,031 36 1,067 18% 1,259

h 3 Core x 400 Sqmm Meter 1,290 36 1,326 18% 1,565

25.2 Supply, laying, testing & commissioning 6.6 / 6.6 kV (UE) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round
wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-2) & IEC:60502(Part-2) of following sizes:
*6.6kV (UE) = 11kV (E)

a 3 Core x 70 Sqmm Meter 423 30 453 18% 535

b 3 Core x 95 Sqmm Meter 500 36 536 18% 633

c 3 Core x 120 Sqmm Meter 577 36 613 18% 724

d 3 Core x 150 Sqmm Meter 644 36 680 18% 803

e 3 Core x 185 Sqmm Meter 749 36 785 18% 927

f 3 Core x 240 Sqmm Meter 899 36 935 18% 1,104

g 3 Core x 300 Sqmm Meter 1,046 36 1,082 18% 1,277

h 3 Core x 400 Sqmm Meter 1,314 36 1,350 18% 1,593

26 3.3 kV (Earthed/ Unearthed) Grade Cable- Aluminium Conductor

26.1 Supply, laying, testing & commissioning of 3.3 / 3.3 kV (UE) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip / round
wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-2) & IEC:60502 (Part-2) of following
sizes:* 3.3kV (E) = 3.3kV (UE)
a 3 Core x 70 Sqmm Meter 370 30 400 18% 472

b 3 Core x 95 Sqmm Meter 448 36 484 18% 572

c 3 Core x 120 Sqmm Meter 527 36 563 18% 665

d 3 Core x 150 Sqmm Meter 595 36 631 18% 745

e 3 Core x 185 Sqmm Meter 701 36 737 18% 870

f 3 Core x 240 Sqmm Meter 831 36 867 18% 1,023

g 3 Core x 300 Sqmm Meter 982 36 1,018 18% 1,202

h 3 Core x 400 Sqmm Meter 1,193 36 1,229 18% 1,451

27 Cable Terminals (Lugs)


Providing & fitting crimping type Cable Terminals (Lugs) conforming to IS of following types and sizes
27.1 Aluminium Tubular Terminals (in Sq.mm.)

a 2.5 Each 1 - 1 18% 1.2

b 4 Each 1 - 1 18% 1.18

c 6 Each 1 - 1 18% 1.18

d 10 Each 2 - 2 18% 2.36

e 16 Each 2 - 2 18% 2.36

f 25 Each 3 - 3 18% 3.54

g 35 Each 4 - 4 18% 4.72

Page 88 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
h 50 Each 5 - 5 18% 5.90

i 70 Each 8 - 8 18% 9.44

j 95 Each 9 - 9 18% 10.62

k 120 Each 13 - 13 18% 15.34

l 150 Each 16 - 16 18% 18.88

m 185 Each 21 - 21 18% 24.78

n 240 Each 35 - 35 18% 41.30

o 300 Each 49 - 49 18% 57.82

p 400 Each 71 - 71 18% 83.78

q 500 Each 103 - 103 18% 122

r 630 Each 139 - 139 18% 164

27.2 Aluminium Tubular Terminals(Long Barrel) (in Sq.mm.)

a 2.5 Each 2 - 2 18% 2.36

b 4 Each 2 - 2 18% 2.36

c 6 Each 2 - 2 18% 2.36

d 10 Each 2 - 2 18% 2.36

e 16 Each 3 - 3 18% 3.54

f 25 Each 3 - 3 18% 3.54

g 35 Each 4 - 4 18% 4.72

h 50 Each 7 - 7 18% 8.26

i 70 Each 10 - 10 18% 11.80

j 95 Each 11 - 11 18% 12.98

k 120 Each 16 - 16 18% 18.88

l 150 Each 21 - 21 18% 24.78

m 185 Each 25 - 25 18% 29.50

o 240 Each 44 - 44 18% 51.92

p 300 Each 64 - 64 18% 75.52

q 400 Each 90 - 90 18% 106

r 500 Each 129 - 129 18% 152

s 630 Each 170 - 170 18% 201

27.3 Aluminium Reducer Terminals (in Sq.mm.)

a 2.5 Each 3 - 3 18% 3.54

b 4 Each 3 - 3 18% 3.54

c 6 Each 3 - 3 18% 3.54

d 10 Each 4 - 4 18% 4.72

e 16 Each 6 - 6 18% 7.08

f 25 Each 9 - 9 18% 10.62

g 35 Each 12 - 12 18% 14.16

h 50 Each 12 - 12 18% 14.16

i 70 Each 21 - 21 18% 24.78

Page 89 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
j 95 Each 31 - 31 18% 36.58

k 120 Each 41 - 41 18% 48.38

l 150 Each 54 - 54 18% 63.72

m 185 Each 69 - 69 18% 81.42

n 240 Each 109 - 109 18% 129

o 300 Each 139 - 139 18% 164

27.4 Copper Tubular Terminals (in Sq.mm.)

a 2.5 Each 5 - 5 18% 5.90

b 4 Each 7 - 7 18% 8.26

c 6 Each 7 - 7 18% 8.26

d 10 Each 10 - 10 18% 11.80

e 16 Each 14 - 14 18% 16.52

f 25 Each 21 - 21 18% 24.78

g 35 Each 22 - 22 18% 25.96

h 50 Each 33 - 33 18% 38.94

i 70 Each 49 - 49 18% 57.82

j 95 Each 73 - 73 18% 86.14

k 120 Each 93 - 93 18% 110

l 150 Each 125 - 125 18% 148

m 185 Each 183 - 183 18% 216

o 240 Each 249 - 249 18% 294

p 300 Each 341 - 341 18% 402

q 400 Each 481 - 481 18% 568

27.5 Copper Tubular Terminals (Long Barrel) (in Sq.mm.)

a 2.5 Each 4 - 4 18% 4.72

b 4 Each 6 - 6 18% 7.08

c 6 Each 6 - 6 18% 7.08

d 10 Each 8 - 8 18% 9.44

e 16 Each 10 - 10 18% 11.80

f 25 Each 15 - 15 18% 17.70

g 35 Each 23 - 23 18% 27.14

h 50 Each 38 - 38 18% 44.84

i 70 Each 59 - 59 18% 69.62

j 95 Each 88 - 88 18% 104

k 120 Each 122 - 122 18% 144

l 150 Each 151 - 151 18% 178

m 185 Each 218 - 218 18% 257

o 240 Each 306 - 306 18% 361

p 300 Each 407 - 407 18% 480

q 400 Each 637 - 637 18% 752

Page 90 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
27.6 Copper Reducer Terminals (in Sq.mm.)

a 2.5 Each 8 - 8 18% 9.44

b 4 Each 8 - 8 18% 9.44

c 6 Each 8 - 8 18% 9.44

d 10 Each 10 - 10 18% 11.80

e 16 Each 15 - 15 18% 17.70

f 25 Each 24 - 24 18% 28.32

g 35 Each 32 - 32 18% 37.76

h 50 Each 35 - 35 18% 41.30

i 70 Each 55 - 55 18% 64.90

j 95 Each 80 - 80 18% 94.40

k 120 Each 99 - 99 18% 117

l 150 Each 137 - 137 18% 162

m 185 Each 179 - 179 18% 211

o 240 Each 284 - 284 18% 335

p 300 Each 360 - 360 18% 425

q 400 Each 813 - 813 18% 959

28 Cable Glands:

Providing & fitting heavy duty brass cable glands (nickel-plated) with washers & rubber ring conforming to IS, suitable for 3, 3½ & 4 core cables of
following type & sizes:
28.1 Single Compression Brass Cable Glands

Suitable for cable Size of


gland in
Sq mm Core mm Inch

a 2.5 2 to 4 19 `3/4 Each 19 - 19 18% 22.42

b 4 3 to 4 22 `7/8 Each 24 - 24 18% 28.32

c 6 3 to 4 22 `7/8 Each 24 - 24 18% 28.32

d 10 3 to 4 25 `1 Each 28 - 28 18% 33.04

e 16 3 to 4 28 `1 1/8 Each 41 - 41 18% 48.38

f 25 3 to 4 32 `1 1/4 Each 49 - 49 18% 57.82

g 35 3 to 3½ 32 `1 1/4 Each 49 - 49 18% 57.82

h 50 3 to 3½ 35 `1 3/8 Each 62 - 62 18% 73.16

i 70 3 to 3½ 38 `1 1/2 Each 77 - 77 18% 90.86

j 95 3 to 3½ 45 `1 3/4 Each 94 - 94 18% 111

k 120 3 to 3½ 45 `1 3/4 Each 94 - 94 18% 111

l 150 3 to 3½ 50 `2 Each 120 - 120 18% 142

m 185 3 to 3½ 57 `2 1/4 Each 154 - 154 18% 182

n 240 3 to 3½ 63 `2 1/2 Each 184 - 184 18% 217

o 300 3 to 3½ 70 `2 3/4 Each 219 - 219 18% 258

p 400 3 to 3½ 82 `3 1/4 Each 311 - 311 18% 367

q 630 3 to 3½ 100 `4 Each 449 - 449 18% 530

28.2 Double Compression Brass Cable Glands

Page 91 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
Suitable for cable Size of
gland in
Sq mm Core mm Inch

a 2.5 2 to 4 19 `3/4 Each 73 - 73 18% 86

b 4 3 to 4 22 `7/8 Each 107 - 107 18% 126

c 6 3 to 4 22 `7/8 Each 107 - 107 18% 126

d 10 3 to 4 25 `1 Each 120 - 120 18% 142

e 16 3 to 4 28 `1 1/8 Each 154 - 154 18% 182

f 25 3 to 4 32 `1 1/4 Each 203 - 203 18% 240

g 35 3 to 3½ 32 `1 1/4 Each 203 - 203 18% 240

h 50 3 to 3½ 35 `1 3/8 Each 240 - 240 18% 283

i 70 3 to 3½ 38 `1 1/2 Each 270 - 270 18% 319

j 95 3 to 3½ 45 `1 3/4 Each 392 - 392 18% 463

k 120 3 to 3½ 45 `1 3/4 Each 392 - 392 18% 463

l 150 3 to 3½ 50 `2 Each 448 - 448 18% 529

m 185 3 to 3½ 57 `2 1/4 Each 522 - 522 18% 616

n 240 3 to 3½ 63 `2 1/2 Each 720 - 720 18% 850

o 300 3 to 3½ 70 `2 3/4 Each 813 - 813 18% 959

p 400 3 to 3½ 82 `3 1/4 Each 1,157 - 1,157 18% 1,365

q 630 3 to 3½ 100 `4 Each 2,447 - 2,447 18% 2,887

29 Cable Terminations / Jointing Kits for 1.1kV grade PVC/ XLPE Cable

Providing & fitting heat shrink cable termination/ jointing kits for 1.1kV grade PVC/ XLPE insulated cable including necessary earth connectivity
connection, material & consummables making the termination/ joint complete ensuring the joint resistance is within the permissble limit as per IS, of
following types & sizes:
29.1 Indoor / Outdoor End Termination Kit

sq mm core

a 4 to 16 3C / 3.5C / 4C Each 527 325 852 18% 1,005

b 25 to 50 3C /3.5C / 4C Each 572 400 972 18% 1,147

c 70 to 150 3C/ 3.5C / 4C Each 595 450 1,045 18% 1,233

d 185 to 300 3C/ 3.5C / 4C Each 629 575 1,204 18% 1,421

e 400 3C / 3.5C / 4C Each 833 675 1,508 18% 1,779

f 500 to 630 3C / 3.5C / 4C Each 986 700 1,686 18% 1,989

29.2 Straight Through Joints (Tubular Sleeve Version)

sq mm core

a 1.5 to 6 3C / 3.5C / 4C Each 624 325 949 18% 1,120

b 10 to 16 3C /3.5C / 4C Each 680 375 1,055 18% 1,245

c 25 to 50 3C/ 3.5C / 4C Each 901 450 1,351 18% 1,594

d 70 to 150 3C/ 3.5C / 4C Each 1,224 500 1,724 18% 2,034

e 185 to 300 3C / 3.5C / 4C Each 1,870 600 2,470 18% 2,915

f 400 to 500 3C / 3.5C / 4C Each 2,210 675 2,885 18% 3,404

29.3 Straight Through Joints (Cold Applied Insulations & Sealing System)

a 6 to 16 3C / 3.5C / 4C Each 761 400 1,161 18% 1,370

Page 92 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
b 25 to 50 3C /3.5C / 4C Each 900 500 1,400 18% 1,652

c 70 to 95 3C/ 3.5C / 4C Each 1,299 600 1,899 18% 2,241

d 120 to 185 3C/ 3.5C / 4C Each 1,760 700 2,460 18% 2,903

e 240 3C / 3.5C / 4C Each 1,931 800 2,731 18% 3,223

f 300 3C / 3.5C / 4C Each 2,319 900 3,219 18% 3,798

g 400 3C / 3.5C / 4C Each 3,157 1,000 4,157 18% 4,905

30 Cable Terminations / Jointing Kits for 3.3 kV (E/UE) / 6.6 kV (E) XLPE Cable

Providing & fitting heat shrink cable termination/ jointing kits for 3.3 kV (E/UE) / 6.6 kV (E) grade XLPE insulated cable including necessary earth
connectivity connection, material & consummables making the termination/ joint complete ensuring the joint resistance is within the permissble limit
as per IS, of following types & sizes:
30.1 Indoor Terminations Kit suitable for

a 16 to 35 3C Each 2,416 325 2,741 18% 3,234

b 50 to 95 3C Each 2,511 400 2,911 18% 3,435

c 120 to 185 3C Each 3,353 450 3,803 18% 4,488

d 240 to 300 3C Each 3,944 575 4,519 18% 5,332

e 400 3C Each 4,164 675 4,839 18% 5,710

30.2 Outdoor Terminations Kit suitable for

a 16 to 35 3C Each 4,377 325 4,702 18% 5,548

b 50 to 95 3C Each 4,445 400 4,845 18% 5,717

c 120 to 185 3C Each 4,601 450 5,051 18% 5,960

d 240 to 300 3C Each 5,258 575 5,833 18% 6,883

e 400 3C Each 5,698 675 6,373 18% 7,520

30.3 Straight Through Joints Kit suitable for

a 16 to 35 3C Each 4,404 325 4,729 18% 5,580

b 50 to 95 3C Each 5,118 400 5,518 18% 6,511

c 120 to 185 3C Each 8,046 450 8,496 18% 10,025

d 240 to 300 3C Each 8,436 575 9,011 18% 10,633

e 400 to 500 3C Each 8,983 675 9,658 18% 11,396

31 Cable Terminations / Jointing Kits for 6.6 kV (UE) / 11 kV (E) grade XLPE Cable

Providing & fitting heat shrink cable termination/ jointing kits for 6.6 kV (UE) / 11 kV (E) grade XLPE insulated cable including necessary earth
connectivity connection, material & consummables making the termination/ joint complete ensuring the joint resistance is within the permissble limit
as per IS, of following types & sizes:
31.1 Indoor Terminations Kit suitable for

a 16 to 35 3C Each 2,794 325 3,119 18% 3,680

b 50 to 95 3C Each 3,431 400 3,831 18% 4,521

c 120 to 185 3C Each 4,021 450 4,471 18% 5,276

d 240 to 300 3C Each 4,223 575 4,798 18% 5,662

e 400 3C Each 4,511 675 5,186 18% 6,119

31.2 Outdoor Terminations Kit suitable for

a 16 to 35 3C Each 4,243 675 4,918 18% 5,803

b 50 to 95 3C Each 4,844 725 5,569 18% 6,571

c 120 to 185 3C Each 5,198 850 6,048 18% 7,137

d 240 to 300 3C Each 5,838 925 6,763 18% 7,980

Page 93 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
e 400 3C Each 6,141 1,000 7,141 18% 8,426

31.3 Straight Through Joints Kit suitable for

a 16 to 35 3C Each 7,187 675 7,862 18% 9,277

b 50 to 95 3C Each 8,044 725 8,769 18% 10,347

c 120 to 185 3C Each 10,248 850 11,098 18% 13,096

d 240 to 300 3C Each 11,195 925 12,120 18% 14,302

e 400 to 500 3C Each 12,417 1,000 13,417 18% 15,832

32 Cable Terminations / Jointing Kits for 11 kV (UE) grade XLPE Cable

32.1 Indoor Terminations Kit suitable for

a 25 to 50 3C Each 3,264 675 3,939 18% 4,648

b 70 to 95 3C Each 4,217 725 4,942 18% 5,832

c 120 to 185 3C Each 5,394 850 6,244 18% 7,368

d 240 to 300 3C Each 6,060 925 6,985 18% 8,242

e 400 to 500 3C Each 6,384 1,000 7,384 18% 8,713

32.2 Outdoor Terminations Kit suitable for

a 25 to 50 3C Each 5,775 675 6,450 18% 7,611

b 70 to 95 3C Each 6,934 725 7,659 18% 9,038

c 120 to 185 3C Each 7,943 850 8,793 18% 10,376

d 240 to 400 3C Each 10,562 925 11,487 18% 13,555

e 500 to 630 3C Each 11,614 1,000 12,614 18% 14,885

32.3 Straight Through Joints Kit suitable for

a 25 to 50 3C Each 13,605 675 14,280 18% 16,850

b 70 to 95 3C Each 15,954 725 16,679 18% 19,681

c 120 to 185 3C Each 16,857 850 17,707 18% 20,894

d 240 to 300 3C Each 21,298 925 22,223 18% 26,223

e 400 to 500 3C Each 24,465 1,000 25,465 18% 30,049

33 415V LV Induction Motor

33.1 Supply, installation, testing & commissioning totally enclosed fan cooled squirrel cage induction motor, foot / flanged mounted enclosure having IP-55
degree of protection, continuously rated (S1) duty suitable for operation on 415 V ± 10%, 3 phase, 50Hz ± 5% AC supply with ambient temperature
500 C, Class F insulation (temperature rise limited to class B) conforming to high energy efficiency (IE-2) as per IS 12615:2011.

A 2 Pole / 3000 RPM, Horizontal Foot Mounted (All ratings in kW)

a 0.37 No. 3,759 380 4,139 18% 4,884

b 0.55 No. 4,223 427 4,650 18% 5,487

c 0.75 No. 4,374 442 4,816 18% 5,683

d 1.1 No. 4,775 482 5,257 18% 6,203

e 1.5 No. 5,732 579 6,311 18% 7,447

f 2.2 No. 7,334 741 8,075 18% 9,529

g 3.7 No. 9,005 909 9,914 18% 11,699

h 5.5 No. 13,905 1,404 15,309 18% 18,065

i 7.5 No. 15,231 1,538 16,769 18% 19,787

j 9.3 No. 25,485 2,574 28,059 18% 33,110

Page 94 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
k 11 No. 27,905 2,818 30,723 18% 36,253

l 15 No. 32,108 3,243 35,351 18% 41,714

m 18.5 No. 41,610 4,203 45,813 18% 54,059

n 22 No. 43,077 4,351 47,428 18% 55,965

o 30 No. 64,734 6,538 71,272 18% 84,101

p 37 No. 78,862 7,965 86,827 18% 102,456

q 45 No. 101,255 10,227 111,482 18% 131,549

r 55 No. 145,664 14,712 160,376 18% 189,244

s 75 No. 188,589 19,048 207,637 18% 245,012

t 90 No. 217,046 21,922 238,968 18% 281,982

u 110 No. 271,314 27,403 298,717 18% 352,486

v 125 No. 319,150 32,234 351,384 18% 414,633

w 132 No. 330,854 33,416 364,270 18% 429,839

x 150 No. 362,321 36,594 398,915 18% 470,720

y 160 No. 362,321 36,594 398,915 18% 470,720

z 180 No. 422,522 42,675 465,197 18% 548,932

aa 200 No. 422,522 42,675 465,197 18% 548,932

ab 225 No. 469,260 47,395 516,655 18% 609,653

ac 250 No. 469,260 47,395 516,655 18% 609,653

ad 275 No. 510,141 51,524 561,665 18% 662,765

ae 315 No. 510,141 51,524 561,665 18% 662,765

B 2 Pole / 3000 RPM, Flange mounted (All ratings in kW)

a 0.37 No. 3,871 391 4,262 18% 5,029

b 0.55 No. 4,350 439 4,789 18% 5,651

c 0.75 No. 4,505 455 4,960 18% 5,853

d 1.1 No. 4,918 497 5,415 18% 6,390

e 1.5 No. 5,903 596 6,499 18% 7,669

f 2.2 No. 7,554 763 8,317 18% 9,814

g 3.7 No. 9,275 937 10,212 18% 12,050

h 5.5 No. 14,322 1,447 15,769 18% 18,607

i 7.5 No. 15,688 1,584 17,272 18% 20,381

j 9.3 No. 26,249 2,651 28,900 18% 34,102

k 11 No. 28,741 2,903 31,644 18% 37,340

l 15 No. 33,071 3,340 36,411 18% 42,965

m 18.5 No. 42,858 4,329 47,187 18% 55,681

n 22 No. 43,077 4,351 47,428 18% 55,965

o 30 No. 67,932 6,861 74,793 18% 88,256

p 37 No. 82,767 8,359 91,126 18% 107,529

q 45 No. 106,279 10,734 117,013 18% 138,075

r 55 No. 152,894 15,442 168,336 18% 198,636

Page 95 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
s 75 No. 197,579 19,955 217,534 18% 256,690

t 90 No. 227,459 22,973 250,432 18% 295,510

u 110 No. 284,439 28,728 313,167 18% 369,537

v 125 No. 334,788 33,814 368,602 18% 434,950

w 132 No. 346,957 35,043 382,000 18% 450,760

x 150 No. 379,997 38,380 418,377 18% 493,685

y 160 No. 379,997 38,380 418,377 18% 493,685

z 180 No. 443,209 44,764 487,973 18% 575,808

aa 200 No. 443,209 44,764 487,973 18% 575,808

ab 225 No. 492,282 49,720 542,002 18% 639,562

ac 250 No. 492,282 49,720 542,002 18% 639,562

ad 275 No. 535,209 54,056 589,265 18% 695,333

ae 315 No. 535,209 54,056 589,265 18% 695,333

C 4 Pole / 1500 RPM, Horizontal Foot Mounted (All ratings in kW)

a 0.37 No. 3,973 401 4,374 18% 5,161

b 0.55 No. 4,518 456 4,974 18% 5,869

c 0.75 No. 4,594 464 5,058 18% 5,968

d 1.1 No. 5,407 546 5,953 18% 7,025

e 1.5 No. 5,906 597 6,503 18% 7,674

f 2.2 No. 7,739 782 8,521 18% 10,055

g 3.7 No. 9,898 1,000 10,898 18% 12,860

h 5.5 No. 13,638 1,377 15,015 18% 17,718

i 7.5 No. 15,883 1,604 17,487 18% 20,635

j 9.3 No. 26,738 2,701 29,439 18% 34,738

k 11 No. 26,738 2,701 29,439 18% 34,738

l 15 No. 33,231 3,356 36,587 18% 43,173

m 18.5 No. 43,103 4,353 47,456 18% 55,998

n 22 No. 45,511 4,597 50,108 18% 59,127

o 30 No. 62,796 6,342 69,138 18% 81,583

p 37 No. 80,435 8,124 88,559 18% 104,500

q 45 No. 94,897 9,585 104,482 18% 123,289

r 55 No. 135,049 13,640 148,689 18% 175,453

s 75 No. 171,939 17,366 189,305 18% 223,380

t 90 No. 198,440 20,042 218,482 18% 257,809

u 110 No. 238,965 24,135 263,100 18% 310,458

v 125 No. 267,236 26,991 294,227 18% 347,188

w 132 No. 279,885 28,268 308,153 18% 363,621

x 150 No. 325,972 32,923 358,895 18% 423,496

y 160 No. 325,972 32,923 358,895 18% 423,496

z 180 No. 386,591 39,046 425,637 18% 502,252

Page 96 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
aa 200 No. 393,847 39,779 433,626 18% 511,679

ab 225 No. 433,274 43,761 477,035 18% 562,901

ac 250 No. 433,274 43,761 477,035 18% 562,901

ad 275 No. 493,326 49,826 543,152 18% 640,919

ae 315 No. 495,756 50,071 545,827 18% 644,076

af 355 No. 622,995 62,923 685,918 18% 809,383

ag 375 No. 870,422 87,913 958,335 18% 1,130,835

D 4 Pole / 1500 RPM, Flanged Mounted (All ratings in kW)

a 0.37 No. 4,092 413 4,505 18% 5,316

b 0.55 No. 4,654 470 5,124 18% 6,046

c 0.75 No. 4,732 478 5,210 18% 6,148

d 1.1 No. 5,569 562 6,131 18% 7,235

e 1.5 No. 6,083 614 6,697 18% 7,902

f 2.2 No. 7,971 805 8,776 18% 10,356

g 3.7 No. 10,195 1,030 11,225 18% 13,246

h 5.5 No. 14,047 1,419 15,466 18% 18,250

i 7.5 No. 16,359 1,652 18,011 18% 21,253

j 9.3 No. 27,582 2,786 30,368 18% 35,834

k 11 No. 27,540 2,782 30,322 18% 35,780

l 15 No. 34,228 3,457 37,685 18% 44,468

m 18.5 No. 44,397 4,484 48,881 18% 57,680

n 22 No. 46,876 4,734 51,610 18% 60,900

o 30 No. 64,657 6,530 71,187 18% 84,001

p 37 No. 82,820 8,365 91,185 18% 107,598

q 45 No. 97,720 9,870 107,590 18% 126,956

r 55 No. 139,069 14,046 153,115 18% 180,676

s 75 No. 176,905 17,867 194,772 18% 229,831

t 90 No. 204,202 20,624 224,826 18% 265,295

u 110 No. 245,911 24,837 270,748 18% 319,483

v 125 No. 275,060 27,781 302,841 18% 357,352

w 132 No. 288,019 29,090 317,109 18% 374,189

x 150 No. 335,487 33,884 369,371 18% 435,858

y 160 No. 335,487 33,884 369,371 18% 435,858

z 180 No. 405,399 40,945 446,344 18% 526,686

aa 200 No. 405,399 40,945 446,344 18% 526,686

ab 225 No. 446,008 45,047 491,055 18% 579,445

ac 250 No. 446,008 45,047 491,055 18% 579,445

ad 275 No. 510,365 51,547 561,912 18% 663,056

ae 315 No. 510,365 51,547 561,912 18% 663,056

af 355 No. 641,494 64,791 706,285 18% 833,416

Page 97 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
ag 375 No. 913,686 92,282 1,005,968 18% 1,187,042

E 6 Pole / 1000 RPM, Horizontal Foot Mounted (All ratings in kW)

a 0.37 No. 4,793 484 5,277 18% 6,227

b 0.55 No. 4,884 493 5,377 18% 6,345

c 0.75 No. 5,686 574 6,260 18% 7,387

d 1.1 No. 6,319 638 6,957 18% 8,209

e 1.5 No. 7,982 806 8,788 18% 10,370

f 2.2 No. 9,509 960 10,469 18% 12,353

g 3.7 No. 14,890 1,504 16,394 18% 19,345

h 5.5 No. 16,209 1,637 17,846 18% 21,058

i 7.5 No. 26,255 2,652 28,907 18% 34,110

j 9.3 No. 32,689 3,302 35,991 18% 42,469

k 11 No. 32,658 3,299 35,957 18% 42,429

l 15 No. 42,651 4,308 46,959 18% 55,412

m 18.5 No. 55,531 5,609 61,140 18% 72,145

n 22 No. 60,346 6,095 66,441 18% 78,400

o 30 No. 94,816 9,576 104,392 18% 123,183

p 37 No. 135,843 13,720 149,563 18% 176,484

q 45 No. 162,466 16,409 178,875 18% 211,073

r 55 No. 184,898 18,675 203,573 18% 240,216

s 75 No. 229,169 23,146 252,315 18% 297,732

t 90 No. 285,783 28,864 314,647 18% 371,283

u 110 No. 317,698 32,087 349,785 18% 412,746

v 125 No. 352,944 35,647 388,591 18% 458,537

w 132 No. 370,152 37,385 407,537 18% 480,894

x 150 No. 443,607 44,804 488,411 18% 576,325

y 160 No. 383,560 38,740 422,300 18% 498,314

z 180 No. 472,961 47,769 520,730 18% 614,461

aa 200 No. 437,243 44,162 481,405 18% 568,058

ab 225 No. 509,841 51,494 561,335 18% 662,375

ac 250 No. 470,557 47,526 518,083 18% 611,338

ad 275 No. 611,165 61,728 672,893 18% 794,014

ae 315 No. 708,256 71,534 779,790 18% 920,152

F 6 Pole / 1000 RPM, Flanged Mounted (All ratings in kW)

a 0.37 No. 4,937 499 5,436 18% 6,414

b 0.55 No. 5,031 508 5,539 18% 6,536

c 0.75 No. 5,856 591 6,447 18% 7,607

d 1.1 No. 6,508 657 7,165 18% 8,455

e 1.5 No. 8,221 830 9,051 18% 10,680

f 2.2 No. 9,795 989 10,784 18% 12,725

Page 98 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
g 3.7 No. 15,336 1,549 16,885 18% 19,924

h 5.5 No. 16,695 1,686 18,381 18% 21,690

i 7.5 No. 27,043 2,731 29,774 18% 35,133

j 9.3 No. 33,669 3,401 37,070 18% 43,743

k 11 No. 33,638 3,397 37,035 18% 43,701

l 15 No. 43,931 4,437 48,368 18% 57,074

m 18.5 No. 57,197 5,777 62,974 18% 74,309

n 22 No. 62,156 6,278 68,434 18% 80,752

o 30 No. 97,637 9,861 107,498 18% 126,848

p 37 No. 139,894 14,129 154,023 18% 181,747

q 45 No. 167,317 16,899 184,216 18% 217,375

r 55 No. 190,412 19,232 209,644 18% 247,380

s 75 No. 235,852 23,821 259,673 18% 306,414

t 90 No. 294,092 29,703 323,795 18% 382,078

u 110 No. 326,964 33,023 359,987 18% 424,785

v 125 No. 363,268 36,690 399,958 18% 471,950

w 132 No. 380,992 38,480 419,472 18% 494,977

x 150 No. 380,992 38,480 419,472 18% 494,977

y 160 No. 394,803 39,875 434,678 18% 512,920

z 180 No. 450,096 45,460 495,556 18% 584,756

aa 200 No. 450,096 45,460 495,556 18% 584,756

ab 225 No. 484,410 48,925 533,335 18% 629,335

ac 250 No. 484,410 48,925 533,335 18% 629,335

ad 275 No. 641,463 64,788 706,251 18% 833,376

ae 315 No. 729,311 73,660 802,971 18% 947,506

33.2 Supply, installation, testing & commissioning totally enclosed fan cooled squirrel cage induction motor, foot / flanged mounted enclosure having IP-
55 degree of protection, continuously rated (S1) duty suitable for operation on 415 V ± 10%, 3 phase, 50Hz ± 5% AC supply with ambient
temperature 50 deg. C, Class F insulation (temperature rise limited to class B) conforming to premium efficiency (IE-3) as per IS 12615:2011 and IS /
IEC 60034-1:2017.
A 2 Pole / 3000 RPM, Horizontal Foot Mounted (All ratings in kW)

a 0.37 No. 4,324 437 4,761 18% 5,618

b 0.55 No. 4,859 491 5,350 18% 6,313

c 0.75 No. 5,032 508 5,540 18% 6,537

d 1.1 No. 5,822 588 6,410 18% 7,564

e 1.5 No. 6,590 666 7,256 18% 8,562

f 2.2 No. 8,433 852 9,285 18% 10,956

g 3.7 No. 10,588 1,069 11,657 18% 13,755

h 5.5 No. 15,993 1,615 17,608 18% 20,777

i 7.5 No. 17,515 1,769 19,284 18% 22,755

j 9.3 No. 29,470 2,976 32,446 18% 38,286

k 11 No. 32,092 3,241 35,333 18% 41,693

l 15 No. 36,929 3,730 40,659 18% 47,978

Page 99 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
m 18.5 No. 47,850 4,833 52,683 18% 62,166

n 22 No. 49,538 5,003 54,541 18% 64,358

o 30 No. 74,327 7,507 81,834 18% 96,564

p 37 No. 90,129 9,103 99,232 18% 117,094

q 45 No. 116,328 11,749 128,077 18% 151,131

r 55 No. 170,535 17,224 187,759 18% 221,556

s 75 No. 217,196 21,937 239,133 18% 282,177

t 90 No. 250,643 25,315 275,958 18% 325,630

u 110 No. 314,239 31,738 345,977 18% 408,253

v 125 No. 366,063 36,972 403,035 18% 475,581

w 132 No. 384,125 38,797 422,922 18% 499,048

x 160 No. 421,017 42,523 463,540 18% 546,977

y 180 No. 488,145 49,303 537,448 18% 634,189

z 200 No. 491,606 49,652 541,258 18% 638,684

aa 225 No. 546,567 55,203 601,770 18% 710,089

ab 250 No. 546,567 55,203 601,770 18% 710,089

ac 275 No. 594,180 60,012 654,192 18% 771,947

ad 315 No. 594,180 60,012 654,192 18% 771,947

B 2 Pole / 3000 RPM, Flange mounted (All ratings in kW)

a 0.37 No. 4,453 450 4,903 18% 5,786

b 0.55 No. 5,005 505 5,510 18% 6,502

c 0.75 No. 5,183 523 5,706 18% 6,733

d 1.1 No. 5,996 606 6,602 18% 7,790

e 1.5 No. 6,788 686 7,474 18% 8,819

f 2.2 No. 8,686 877 9,563 18% 11,284

g 3.7 No. 10,905 1,101 12,006 18% 14,167

h 5.5 No. 16,472 1,664 18,136 18% 21,400

i 7.5 No. 18,041 1,822 19,863 18% 23,438

j 9.3 No. 30,354 3,066 33,420 18% 39,436

k 11 No. 33,054 3,338 36,392 18% 42,943

l 15 No. 38,036 3,842 41,878 18% 49,416

m 18.5 No. 49,286 4,978 54,264 18% 64,032

n 22 No. 52,016 5,254 57,270 18% 67,579

o 30 No. 78,004 7,878 85,882 18% 101,341

p 37 No. 94,589 9,553 104,142 18% 122,888

q 45 No. 122,104 12,333 134,437 18% 158,636

r 55 No. 179,016 18,081 197,097 18% 232,574

s 75 No. 227,736 23,001 250,737 18% 295,870

t 90 No. 262,856 26,548 289,404 18% 341,497

u 110 No. 329,632 33,293 362,925 18% 428,252

Page 100 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
v 125 No. 384,047 38,789 422,836 18% 498,946

w 132 No. 403,012 40,704 443,716 18% 523,585

x 160 No. 441,748 44,617 486,365 18% 573,911

y 180 No. 512,293 51,742 564,035 18% 665,561

z 200 No. 515,867 52,103 567,970 18% 670,205

aa 225 No. 573,576 57,931 631,507 18% 745,178

ab 250 No. 573,576 57,931 631,507 18% 745,178

ac 275 No. 623,569 62,981 686,550 18% 810,129

ad 315 No. 623,569 62,981 686,550 18% 810,129

C 4 Pole / 1500 RPM, Horizontal Foot Mounted (All ratings in kW)

a 0.37 No. 4,172 421 4,593 18% 5,420

b 0.55 No. 5,201 525 5,726 18% 6,757

c 0.75 No. 5,283 534 5,817 18% 6,864

d 1.1 No. 6,217 628 6,845 18% 8,077

e 1.5 No. 6,793 686 7,479 18% 8,825

f 2.2 No. 8,901 899 9,800 18% 11,564

g 3.7 No. 11,381 1,149 12,530 18% 14,785

h 5.5 No. 15,686 1,584 17,270 18% 20,379

i 7.5 No. 18,263 1,845 20,108 18% 23,727

j 9.3 No. 28,217 2,850 31,067 18% 36,659

k 11 No. 32,087 3,241 35,328 18% 41,687

l 15 No. 39,879 4,028 43,907 18% 51,810

m 18.5 No. 51,726 5,224 56,950 18% 67,201

n 22 No. 52,337 5,286 57,623 18% 67,995

o 30 No. 71,435 7,215 78,650 18% 92,807

p 37 No. 92,360 9,328 101,688 18% 119,992

q 45 No. 109,016 11,011 120,027 18% 141,632

r 55 No. 158,137 15,972 174,109 18% 205,449

s 75 No. 198,602 20,059 218,661 18% 258,020

t 90 No. 229,373 23,167 252,540 18% 297,997

u 110 No. 276,423 27,919 304,342 18% 359,124

v 125 No. 309,245 31,234 340,479 18% 401,765

w 132 No. 324,321 32,756 357,077 18% 421,351

x 160 No. 378,328 38,211 416,539 18% 491,516

y 180 No. 443,800 44,824 488,624 18% 576,576

z 200 No. 458,158 46,274 504,432 18% 595,230

aa 225 No. 504,093 50,913 555,006 18% 654,907

ab 250 No. 504,093 50,913 555,006 18% 654,907

ac 275 No. 577,679 58,346 636,025 18% 750,510

ad 315 No. 577,679 58,346 636,025 18% 750,510

Page 101 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
D 4 Pole / 1500 RPM, Flanged Mounted (All ratings in kW)

a 0.37 No. 4,708 476 5,184 18% 6,117

b 0.55 No. 5,357 541 5,898 18% 6,960

c 0.75 No. 5,442 550 5,992 18% 7,071

d 1.1 No. 6,404 647 7,051 18% 8,320

e 1.5 No. 6,996 707 7,703 18% 9,090

f 2.2 No. 9,168 926 10,094 18% 11,911

g 3.7 No. 11,722 1,184 12,906 18% 15,229

h 5.5 No. 16,156 1,632 17,788 18% 20,990

i 7.5 No. 18,811 1,900 20,711 18% 24,439

j 9.3 No. 29,064 2,935 31,999 18% 37,759

k 11 No. 33,049 3,338 36,387 18% 42,937

l 15 No. 41,076 4,149 45,225 18% 53,366

m 18.5 No. 53,278 5,381 58,659 18% 69,218

n 22 No. 53,907 5,445 59,352 18% 70,035

o 30 No. 73,555 7,429 80,984 18% 95,561

p 37 No. 95,102 9,605 104,707 18% 123,554

q 45 No. 112,264 11,339 123,603 18% 145,852

r 55 No. 162,852 16,448 179,300 18% 211,574

s 75 No. 204,368 20,641 225,009 18% 265,511

t 90 No. 236,062 23,842 259,904 18% 306,687

u 110 No. 284,524 28,737 313,261 18% 369,648

v 125 No. 318,331 32,151 350,482 18% 413,569

w 132 No. 333,859 33,720 367,579 18% 433,743

x 160 No. 389,487 39,338 428,825 18% 506,014

y 180 No. 465,725 47,038 512,763 18% 605,060

z 200 No. 471,711 47,643 519,354 18% 612,838

aa 225 No. 519,024 52,421 571,445 18% 674,305

ab 250 No. 519,024 52,421 571,445 18% 674,305

ac 275 No. 594,610 60,056 654,666 18% 772,506

ad 315 No. 594,818 60,077 654,895 18% 772,776

E 6 Pole / 1000 RPM, Horizontal Foot Mounted (All ratings in kW)

a 0.37 No. 5,512 557 6,069 18% 7,161

b 0.55 No. 5,618 567 6,185 18% 7,298

c 0.75 No. 6,540 660 7,200 18% 8,496

d 1.1 No. 7,370 744 8,114 18% 9,575

e 1.5 No. 9,181 927 10,108 18% 11,927

f 2.2 No. 10,936 1,105 12,041 18% 14,208

g 3.7 No. 17,130 1,730 18,860 18% 22,255

h 5.5 No. 18,640 1,883 20,523 18% 24,217

Page 102 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
i 7.5 No. 31,507 3,182 34,689 18% 40,933

j 9.3 No. 35,456 3,581 39,037 18% 46,064

k 11 No. 37,558 3,793 41,351 18% 48,794

l 15 No. 49,050 4,954 54,004 18% 63,725

m 18.5 No. 63,859 6,450 70,309 18% 82,965

n 22 No. 69,398 7,009 76,407 18% 90,160

o 30 No. 108,923 11,001 119,924 18% 141,510

p 37 No. 159,255 16,085 175,340 18% 206,901

q 45 No. 190,473 19,238 209,711 18% 247,459

r 55 No. 216,562 21,873 238,435 18% 281,353

s 75 No. 265,051 26,770 291,821 18% 344,349

t 90 No. 331,278 33,459 364,737 18% 430,390

u 110 No. 368,740 37,243 405,983 18% 479,060

v 125 No. 409,905 41,400 451,305 18% 532,540

w 132 No. 429,972 43,427 473,399 18% 558,611

x 160 No. 445,671 45,013 490,684 18% 579,007

y 180 No. 509,000 51,409 560,409 18% 661,283

z 200 No. 509,000 51,409 560,409 18% 661,283

aa 225 No. 547,710 55,319 603,029 18% 711,574

ab 250 No. 547,710 55,319 603,029 18% 711,574

ac 275 No. 702,057 70,908 772,965 18% 912,099

ad 315 No. 829,208 83,750 912,958 18% 1,077,290

F 6 Pole / 1000 RPM, Flanged Mounted (All ratings in kW)

a 0.37 No. 5,677 573 6,250 18% 7,375

b 0.55 No. 5,786 584 6,370 18% 7,517

c 0.75 No. 6,736 680 7,416 18% 8,751

d 1.1 No. 7,590 767 8,357 18% 9,861

e 1.5 No. 9,456 955 10,411 18% 12,285

f 2.2 No. 11,264 1,138 12,402 18% 14,634

g 3.7 No. 17,644 1,782 19,426 18% 22,923

h 5.5 No. 19,199 1,939 21,138 18% 24,943

i 7.5 No. 32,451 3,278 35,729 18% 42,160

j 9.3 No. 36,520 3,688 40,208 18% 47,445

k 11 No. 38,684 3,907 42,591 18% 50,257

l 15 No. 50,521 5,103 55,624 18% 65,636

m 18.5 No. 65,774 6,643 72,417 18% 85,452

n 22 No. 71,481 7,220 78,701 18% 92,867

o 30 No. 112,167 11,329 123,496 18% 145,725

p 37 No. 164,005 16,564 180,569 18% 213,071

q 45 No. 196,159 19,812 215,971 18% 254,846

Page 103 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
r 55 No. 223,031 22,526 245,557 18% 289,757

s 75 No. 272,810 27,554 300,364 18% 354,430

t 90 No. 341,025 34,443 375,468 18% 443,052

u 110 No. 379,611 38,341 417,952 18% 493,183

v 125 No. 422,011 42,623 464,634 18% 548,268

w 132 No. 442,679 44,711 487,390 18% 575,120

x 160 No. 458,850 46,344 505,194 18% 596,129

y 180 No. 524,078 52,932 577,010 18% 680,872

z 200 No. 524,078 52,932 577,010 18% 680,872

aa 225 No. 563,950 56,959 620,909 18% 732,673

ab 250 No. 563,950 56,959 620,909 18% 732,673

ac 275 No. 736,902 74,427 811,329 18% 957,368

ad 315 No. 853,893 86,243 940,136 18% 1,109,360

34 LT Power Capacitor

34.1 Supply & erecting heavy duty APP type capacitor unit, vacuum impregnated with non-PCB / non toxic oil, internally delta connected with built in
internal fuses complete with discharge resistances & terminal cover, rated for 440 V AC, 3 Phase, 50Hz as per IS - 13585 Part-1.
APP type Capacitor kVAR 259 26 285 18% 336

35 Cable Trays & Accessories

35.1 Supply & laying MS ladder type cable trays with side channels of size - 75 x 15 x 15 mm / 100 x 15 x 15 mm & rungs of size - 35 x 15 x 15 mm
spaced at 250 mm apart, fabricated from 2 mm thick sheet steel in standard length of 2.5 meter, duly finished with one coat of red oxide & two coats
of aluminium paint as per IS including accessories such as coupler plates / fish plates, bends, tees, reducers, elbows, covers and electro-galvanized
hardware etc, erected on existing support as per specification and instruction of engineer in charge.

a 150(W) x 75(H) x 2.0 mm Thick Rmt. 231 23 254 18% 300

b 300(W) x 75(H) x 2.0 mm Thick Rmt. 267 27 294 18% 347

c 450(W) x 75(H) x 2.0 mm Thick Rmt. 303 31 334 18% 394

d 600(W) x 75(H) x 2.0 mm Thick Rmt. 340 34 374 18% 441

e 750(W) X 75(H) x 2.0 mm Thick Rmt. 375 38 413 18% 487

f 150(W) x 100(H) x 2.0 mm Thick Rmt. 277 28 305 18% 360

g 300(W) x 100(H) x 2.0 mm Thick Rmt. 313 32 345 18% 407

h 450(W) x 100(H) x 2.0 mm Thick Rmt. 349 35 384 18% 453

i 600(W) x 100(H) x 2.0 mm Thick Rmt. 385 39 424 18% 500

j 750(W) X 100(H) x 2.0 mm Thick Rmt. 421 43 464 18% 548

35.2 Supply & laying MS perforated type cable trays with returned edge/ flange, fabricated from 2.0 mm thk sheet steel in the standard length of 2.5 mtrs,
duly finished with one coat of red oxide & two coats of aluminium paint as per IS including accessories such as coupler plates / fish plates, bends,
tees, reducers, elbows, covers and electro-galvanized hardware etc, erected on existing support as per specification and instruction of engineer in
charge.
a 100(W) x 35(H) x 2.0 mm Thick Rmt. 154 16 170 18% 201

b 150(W) x 35(H) x 2.0 mm Thick Rmt. 200 20 220 18% 260

c 300(W) x 35(H) x 2.0 mm Thick Rmt. 337 34 371 18% 438

d 450(W) x 35(H) x 2.0 mm Thick Rmt. 473 48 521 18% 615

e 600(W) x 35(H) x 2.0 mm Thick Rmt. 611 62 673 18% 794

f 100(W) x 50(H) x 2.0 mm Thick Rmt. 182 18 200 18% 236

g 150(W) x 50(H) x 2.0 mm Thick Rmt. 228 23 251 18% 296

h 300(W) x 50(H) x 2.0 mm Thick Rmt. 365 37 402 18% 474

i 450(W) x 50(H) x 2.0 mm Thick Rmt. 502 51 553 18% 653

Page 104 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
j 600(W) x 50(H) x 2.0 mm Thick Rmt. 636 64 700 18% 826

C Supply & laying GI ladder type cable trays with side channels of size - 75 x 15 x 15 mm/ 100 x 15 x 15 mm & rungs of size - 35 x15 x 15 mm spaced
at 250 mm apart, fabricated from 2 mm thick sheet steel in standard length of 2.5 meter, duly hot dipped galvanized after fabrication as per IS 2629-
1989/ IS 4759-1984 including accessories such as coupler plates/ fish plates, bends, tees, reducers, elbows, covers and electro-galvanized
hardware etc, erected on existing support as per specification and instruction of engineer in charge.

a 150(W) x 75(H) x 2.0 mm Thick Rmt. 305 31 336 18% 396

b 300(W) x 75(H) x 2.0 mm Thick Rmt. 352 36 388 18% 458

c 450(W) x 75(H) x 2.0 mm Thick Rmt. 399 40 439 18% 518

d 600(W) x 75(H) x 2.0 mm Thick Rmt. 450 45 495 18% 584

e 750(W) X 75(H) x 2.0 mm Thick Rmt. 496 50 546 18% 644

f 150(W) x 100(H) x 2.0 mm Thick Rmt. 365 37 402 18% 474

g 300(W) x 100(H) x 2.0 mm Thick Rmt. 414 42 456 18% 538

h 450(W) x 100(H) x 2.0 mm Thick Rmt. 460 46 506 18% 597

i 600(W) x 100(H) x 2.0 mm Thick Rmt. 507 51 558 18% 658

j 750(W) X 100(H) x 2.0 mm Thick Rmt. 559 56 615 18% 726

D Supply & laying GI perforated type cable trays with returned edge/ flange, fabricated from 2.0 mm thk sheet steel in the standard length of 2.5 mtrs,
duly hot dipped galvanized after fabrication as per IS 2629-1989 / IS 4759-1984 including accessories such as coupler plates/ fish plates, bends,
tees, reducers, elbows, covers and electro-galvanized hardware etc, erected on existing support as per specification and instruction of engineer in
charge.
a 100(W) x 35(H) x 2.0 mm Thick Rmt. 207 21 228 18% 269

b 150(W) x 35(H) x 2.0 mm Thick Rmt. 269 27 296 18% 349

c 300(W) x 35(H) x 2.0 mm Thick Rmt. 451 46 497 18% 586

d 450(W) x 35(H) x 2.0 mm Thick Rmt. 633 64 697 18% 822

e 600(W) x 35(H) x 2.0 mm Thick Rmt. 818 83 901 18% 1,063

f 100(W) x 50(H) x 2.0 mm Thick Rmt. 248 25 273 18% 322

g 150(W) x 50(H) x 2.0 mm Thick Rmt. 305 31 336 18% 396

h 300(W) x 50(H) x 2.0 mm Thick Rmt. 491 50 541 18% 638

i 450(W) x 50(H) x 2.0 mm Thick Rmt. 673 68 741 18% 874

j 600(W) x 50(H) x 2.0 mm Thick Rmt. 859 87 946 18% 1,116

E Supply & laying FRP ladder type cable trays with C shaped side channels of size - 75 x 25 x 25 mm for 150 mm wide and 100 x 75 x 75 mm for 300
mm wide & above, rungs of 25 mm square hollow tube spaced at 300 mm apart, manufactured as per NEMA FGI-1993 / IS 6746 - 1994/ ASTM-D
standards using corrosion resistant polyester flame retardant U.V stabilised resin & various types of glass fibres with glass content ≥ 55% with
minimum thickness of 3.0 mm for all sizes upto 150 mm (W) & 4.0 mm thickness for all sizes of 300 mm & above, supplied in standard length of 3 mtr
including accessories such as coupler plates/ fish plates, bends, tees, reducers, elbows, covers and electro-galvanized / SS-304 hardware etc,
erected on existing support as per specification and instruction of engineer in charge.

a 150(W) x 75(H) x 4 mm Thick Rmt. 450 45 495 18% 584

b 300(W) x 100(H) x 4 mm Thick Rmt. 601 61 662 18% 781

c 450(W) x 100(H) x 4 mm Thick Rmt. 660 67 727 18% 858

d 600(W) x 100(H) x 4 mm Thick Rmt. 719 73 792 18% 935

e 750(W) x 100(H) x 4 mm Thick Rmt. 779 79 858 18% 1,012

F Supply & laying FRP perforated type cable trays manufactured as per NEMA FGI-1993 / IS 6746 - 1994/ ASTM-D standards using corrosion resistant
polyester flame retardant U.V stabilised resin & various types of glass fibres with glass content ≥ 55% with minimum thickness of 3.0 mm for all
sizes upto 150 mm (W) & 4.0 mm thickness for all sizes of 300 mm & above, supplied in standard length of 3 mtr including accessories such as
coupler plates/ fish plates, bends, tees, reducers, elbows, covers and electro-galvanized / SS-304 hardware etc, erected on existing support as per
specification and instruction of engineer in charge.
a 100(W) x 30(H) x 3mm thick Rmt. 147 15 162 18% 191

b 150(W) x 50(H) x 3 mm Thick Rmt. 273 28 301 18% 355

c 300(W) x 50(H) x 4 mm Thick. Rmt. 301 30 331 18% 391

Page 105 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
d 450(W) x 50(H) x 4 mm Thick Rmt. 909 92 1,001 18% 1,181

e 600(W) x 50(H) x 4 mm Thick Rmt. 1,232 124 1,356 18% 1,600

36 Rate per KW for comprehensive work of S.I.T.C. of Electro-mechanical components for headworks of R.W.S.S.(This is only for the purpose
of rough estimation)
A Electro mechanical components of Pumping Station having installed capacity up to ≤ 75 kW with working load not exceding 75 KW

Supply, installation, testing & commissioning of electro-mechanical equipments of water supply pumping system viz. pumping machinery
(of following type & rating), valves (SV/BFV/DPCV), Suction-delivery-discharge header pipes & specials, expansion bellows, flow meter (full
bore electromagnetic - For size ≤ 1400 mm) / ultrasonic - For size ≥ 1500 mm), material handling system (motorised chain pulley block with
geared travelling trolley), vaccum pumps with accessories or horizontal mono submersible (drain) pump with accessories including LV
MCC - APFC panels, LT XLPE insulated Cu / Al armoured / PVC insulated round Copper submersible cables with tray & kits, earthing
system, fire extinguisher, Exhaust Fan, safety accessories etc. as per specifications.

1 Horizontal split casing KW 20,000 2,000 22,000 Incl. 22,000

2 End suction (Back Pull Out) KW 18,000 1,750 19,750 Incl. 19,750

3 Volute type submerged centrifugal KW 22,000 2,250 24,250 Incl. 24,250

4 Vertical Turbine KW 22,000 2,500 24,500 Incl. 24,500

B Electro mechanical components of Water Supply Pumping Station having installed capacity ranging from>75 kW to ≤ 200 KW with working
load exceding 75 KW but below 320 KW.
Supply, installation, testing & commissioning of electrical & mechanical equipments of water supply pumping system viz. pumping
machinery (of following type & rating), valves (SV/BFV/DPCV), Suction-delivery-discharge header pipes & specials, expansion bellows,
flow meter (full bore electromagnetic - For size ≤ 1400 mm) / ultrasonic - For size ≥ 1500 mm)electromagnetic - For size ≤ 1400 mm) /
ultrasonic - For size ≥ 1500 mm), material handling system (EOT), vaccum pump with accessories or horizontal mono submersible (drain)
pump with accessories including 11 kV switchyard with dristribution transformer, LV MCC - APFC panels, HT / LT XLPE insulated Cu / Al
armoured / PVC insulated round Copper submersible cables with tray & kits, earthing system, fire extinguisher, exhaust fan safety
accessories etc. as per specifications.

1 Horizontal split casing KW 20,000 2,000 22,000 Incl. 22,000

2 Volute type submerged centrifugal KW 24,000 2,250 26,250 Incl. 26,250

3 Vertical Turbine KW 24,000 2,500 26,500 Incl. 26,500

C Electro mechanical components of Water Supply Pumping Station having installed capacity > 200 KW with working load exceding 320 KW.

Supply, installation, testing & commissioning of electrical & mechanical equipments of water supply pumping system viz. pumping
machinery (of following type & rating), valves (SV/BFV/DPCV), Suction-delivery-discharge header pipes & specials, expansion bellows,
flow meter (full bore electromagnetic - For size ≤ 1400 mm) / ultrasonic - For size ≥ 1500 mm), material handling system (EOT), vaccum
pumps with accessories or horizontal mono submersible (drain) pump with accessories, fire extinguisher, exhaust fan including 11 kV
switchyard with dristribution transformer, HT switchgear panel, LV MCC - APFC panels, HT / LT XLPE insulated Cu / Al armoured / PVC
insulated round Copper submersible cables with tray & kits, earthing system, safety accessories etc. as per specifications.

1 Horizontal split casing KW 24,000 2,000 26,000 Incl. 26,000


2 Volute type submerged centrifugal KW 26,000 2,500 28,500 Incl. 28,500
3 Vertical Turbine KW 27,500 2,750 30,250 Incl. 30,250
D Electro mechanical components of water supply system of different type of pumps ranging from > 75 kW but ≤ 200 kW
Supply, installation, testing & commissioning of electrical & mechanical equipments of water supply pumping system viz. pumping
machinery (of following type & rating), valves (SV/BFV/DPCV), Suction-delivery-discharge header pipes & specials, expansion bellows,
flow meter (full bore electromagnetic - For size ≤ 1400 mm) / ultrasonic - For size ≥ 1500 mm), material handling system (EOT), horizontal
mono submersible (drain) pump with accessories, fire extinguisher, exhaust fan including 11 kV switchyard with dristribution transformer,
HT switchgear panel, LV MCC - APFC panels, HT / LT XLPE insulated Cu / Al armoured / PVC insulated round Copper submersible cables
with tray & kits, earthing system, safety accessories with PLC based instrumentation with control system as per specifications.

1 Horizontal split casing KW 20,000 2,000 22,000 Incl. 26,000

2 Volute type submerged centrifugal KW 24,000 3,000 27,000 Incl. 28,500

3 Vertical Turbine KW 24,000 3,000 27,000 Incl. 30,250

E Electro mechanical components of water supply system of different


type of pumps ranging from > 200 kW but ≤ 450 kW
Supply, installation, testing & commissioning of electrical & mechanical equipments of water supply pumping system viz. pumping
machinery (of following type & rating), valves (SV/BFV/DPCV), Suction-delivery-discharge header pipes & specials, expansion bellows,
flow meter (full bore electromagnetic - For size ≤ 1400 mm) / ultrasonic - For size ≥ 1500 mm), material handling system (EOT), horizontal
mono submersible (drain) pump with accessories, fire extinguisher, exhaust fan including 11 kV switchyard with dristribution transformer,
HT switchgear panel, LV MCC - APFC panels, HT / LT XLPE insulated Cu / Al armoured / PVC insulated round Copper submersible cables
with tray & kits, earthing system, safety accessories with PLC based instrumentation with control system as per specifications.

1 Horizontal split casing KW 24,000 2,000 26,000 Incl. 26,000

2 Volute type submerged centrifugal KW 26,000 3,000 29,000 Incl. 28,500

Page 106 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
3 Vertical Turbine KW 27,500 3,000 30,500 Incl. 30,250

Note:- Rates are inclusive of all equipments / accessories required for satisfactory & Successful execution of electromechanical system in water supply
pumping system based on different type of pumping machinery but exclude cost of operation , maintanance & Repairs . Pleae refer basic &
mandatory electrical & mechanical component of water supply pumping system & design guide lines in brief attached here with

37 Single Girder H.O.T. Crane

37.1 Providing & erecting Single girder type H.O.T. crane with geared travelling trolly with seven mtr lift complete with manually operated chain
pulley block, long travel rail track (40 mm sq. bar), moving or cross girder, brake, safety device, etc. & tested to 50% overload

Capacity Span Long Lift


travel
Tonne m m m

1.1 1T 0m-6 12 m 6m- set 135,000 25,000 160,000 18% 188,800


m 10 m
1.2 1T 6m-9 12 m 6m- set 140,000 25,000 165,000 18% 194,700
m 10 m
1.3 1T 9m- 12 m 6m- set 145,000 25,000 170,000 18% 200,600
12 m 10 m
2.1 2T 0m-6 12 m 6m- set 155,000 25,000 180,000 18% 212,400
m 10 m
2.2 2T 6m-9 12 m 6m- set 162,500 25,000 187,500 18% 221,250
m 10 m
2.3 2T 9m- 12 m 6m- set 165,000 25,000 190,000 18% 224,200
12 m 10 m
3.1 3T 0m-6 12 m 6m- set 215,000 25,000 240,000 18% 283,200
m 10 m
3.2 3T 6m-9 12 m 6m- set 225,000 25,000 250,000 18% 295,000
m 10 m
3.3 3T 9m- 12 m 6m- set 230,000 25,000 255,000 18% 300,900
12 m 10 m
37.2 Single Girder E.O.T. Crane

Providing & erecting Single girder type fully electrically operated E.O.T. crane with electrically operated hoist, class II duty, geared
travelling trolley with seven meter lift complete with long travel rail track (40 mm sq. bar), moving or cross girder, all three motions
electrically operated by suitable rating motor IP 54, control panel & down pendant control block, brake, safety device, cables form motor to
starter panel & other required accessories & tested as per IS Specifications.

Sr No Capacity Span Long Lift


travel
Tonne m m m

1.1 1T 0m-6 12 m 6m- set 285,000 25,000 310,000 18% 365,800


m 10 m
1.2 1T 6m-9 12 m 6m- set 335,000 25,000 360,000 18% 424,800
m 10 m
1.3 1T 9m- 12 m 6m- set 345,000 25,000 370,000 18% 436,600
12 m 10 m
2.1 2T 0m-6 12 m 6m- set 325,000 25,000 350,000 18% 413,000
m 10 m
2.2 2T 6m-9 12 m 6m- set 375,000 25,000 400,000 18% 472,000
m 10 m
2.3 2T 9m- 12 m 6m- set 400,000 25,000 425,000 18% 501,500
12 m 10 m
3.1 3T 0m-6 12 m 6m- set 406,000 25,000 431,000 18% 508,580
m 10 m
3.2 3T 6m-9 12 m 6m- set 420,000 25,000 445,000 18% 525,100
m 10 m
3.3 3T 9m- 12 m 6m- set 440,000 25,000 465,000 18% 548,700
12 m 10 m
4.1 5T 0m-6 12 m 6m- set 420,000 25,000 445,000 18% 525,100
m 10 m
4.2 5T 6m-9 12 m 6m- set 485,000 25,000 510,000 18% 601,800
m 10 m
4.3 5T 9m- 12 m 6m- set 500,000 25,000 525,000 18% 619,500
12 m 10 m
5.1 6T 0m-6 12 m 6m- set 435,000 25,000 460,000 18% 542,800
m 10 m
5.2 6T 6m-9 12 m 6m- set 500,000 25,000 525,000 18% 619,500
m 10 m
5.3 6T 9m- 12 m 6m- set 625,000 25,000 650,000 18% 767,000
12 m 10 m
6.1 7.5 T 0m-6 12 m 6m- set 525,000 25,000 550,000 18% 649,000
m 10 m
6.2 7.5 T 6m-9 12 m 6m- set 585,000 25,000 610,000 18% 719,800
m 10 m

Page 107 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
6.3 7.5 T 9m- 12 m 6m- set 645,000 25,000 670,000 18% 790,600
12 m 10 m
38A Double Girder E.O.T. Crane

Providing & erecting Double girder type fully electrically operated E.O.T. crane with electrically operated hoist, class II duty, geared
travelling trolley with seven meter lift complete with long travel rail track (40 mm sq. bar), moving or cross girder, all three motions
electrically operated by suitable rating motor IP 54, control panel & down pendant control block, brake, safety device, cables form motor to
starter panel & other required accessories & tested as per IS Specifications

Sr No Capacity Span Long Lift


travel
Tonne m m m

1.1 10 T 0m-6 12 m 6m- set 825,000 25,000 850,000 18% 1,003,000


m 10 m
1.2 10 T 6m-9 12 m 6m- set 950,000 25,000 975,000 18% 1,150,500
m 10 m
1.3 10 T 9m- 12 m 6m- set 1,090,000 25,000 1,115,000 18% 1,315,700
12 m 10 m
2.1 15 T 0m-6 12 m 6m- set 1,050,000 25,000 1,075,000 18% 1,268,500
m 10 m
2.2 15 T 6m-9 12 m 6m- set 1,400,000 25,000 1,425,000 18% 1,681,500
m 10 m
2.3 15 T 9m- 12 m 6m- set 1,595,000 25,000 1,620,000 18% 1,911,600
12 m 10 m
3.1 20 T 0m-6 12 m 6m- set 1,600,000 25,000 1,625,000 18% 1,917,500
m 10 m
3.2 20 T 6m-9 12 m 6m- set 1,675,000 25,000 1,700,000 18% 2,006,000
m 10 m
3.3 20 T 9m- 12 m 6m- set 1,810,000 25,000 1,835,000 18% 2,165,300
12 m 10 m
38B Double Girder Circular E.O.T. Crane

Sr No Capacity Diamet Long Lift


er of travel
Pump
House/
Intake

Tonne m m m

1.1 10 T 0m-6 12 m 6m- set 850,000 45,000 895,000 18% 1,056,100


m 10 m
1.2 10 T 6m-9 12 m 6m- set 975,000 45,000 1,020,000 18% 1,203,600
m 10 m
1.3 10 T 9m- 12 m 6m- set 1,250,000 45,000 1,295,000 18% 1,528,100
12 m 10 m
2.1 15 T 0m-6 12 m 6m- set 1,075,000 45,000 1,120,000 18% 1,321,600
m 10 m
2.2 15 T 6m-9 12 m 6m- set 1,275,000 45,000 1,320,000 18% 1,557,600
m 10 m
2.3 15 T 9m- 12 m 6m- set 1,350,000 45,000 1,395,000 18% 1,646,100
12 m 10 m
3.1 20 T 0m-6 12 m 6m- set 1,275,000 65,000 1,340,000 18% 1,581,200
m 10 m
3.2 20 T 6m-9 12 m 6m- set 1,460,000 65,000 1,525,000 18% 1,799,500
m 10 m
3.3 20 T 9m- 12 m 6m- set 1,850,000 85,000 1,935,000 18% 2,283,300
12 m 10 m
39 Chain Pulley Block

Providing Chain pulley block with triple gear arrangement, lifting hook, laod chain & hand chain & locking device etc

1T Manually 6m set 12,000 Incl. 12,000 12% 13,440.00


Operated
Additional lift Manually 1m set 500 Incl. 500 5% 525.00
Operated
2T Manually 6m set 14,500 Incl. 14,500 12% 16,240.00
Operated
Additional lift Manually 1m set 700 Incl. 700 5% 735.00
Operated
3T Motorized 6m set 18,800 Incl. 18,800 12% 21,056.00
Operated
Additional lift Motorized 1m set 1,200 Incl. 1,200 5% 1,260.00
Operated
40 LV APFC PANEL

Page 108 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
Supply, installaton, testing & commissioning LV APFC panel consisting of required capacitor banks for continuous duty to improve P.F. 0.85 to 0.99 in
required steps enclosed in dust & vermin proof compartment, indoor type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for
base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm for internal partitions, minimum degree of protection - IP 42,
busbar chamber, required size of Al bus bar/ terminals, minimum 10 stage APFC relay, metering, indicating lamps, push buttons, with detuned
reactor complete as per IS: 16636-2017 with latest ammendment & detailed technical specification and data sheet as under.

40.1 Up to 50 KVAR capacity: APFC panel consisting following items.


a) 125 A, 50 kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle b) 0-125 A range analogue ammeter of 96 x 96 mm size with
selector switch
c) 3nos. 125 / 5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable rating MCCB / MCB &Contactors for each capacitor bank
e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil, internally delta connected with built in internal fuses
complete with discharge resistances & terminal cover) of approoved make in required steps with well suited detuned reactor is placed in series with
each capacitor step. (e.g., 50 KVAR capacity will be provided in steps of 2 nos x 5 KVAR, 2 nos x 7.5KVAR & 2 nos x12.5 KVAR). f) Enclosure
dimensions- 1600 (H) x 1150 (W) x 600 (D)
As per above specification No 108,691 7,575 116,266 18% 137,194

40.2 Above 50 & up to 100 KVAR: APFC panel consisting following items.
a) 250 A, 50kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle b) 0-250 A range analogue ammeter of 96 x 96 mm size with
selector switch
c) 3nos. 250 / 5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable rating of MCCB / MCB & Contactors for each capacitor bank
e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil, internally delta connected with built in internal fuses
complete with discharge resistances & terminal cover) of approved make in required steps with well suited detuned reactor is placed in series with
each capacitor step. ( e.g., 100 KVAR capacity will be provided in steps of 2 nos x 5 KVAR, 2 nos x 10KVAR, 2 nos x 15 KVAR & 2 nos x 20 KVAR) f)
Enclosre dimensions- 2100 (H) x 1150 (W) x 600 (D)
As per above specification No 150,097 7,575 157,672 18% 186,053

40.3 Above 100 & up to 200 KVAR: APFC panel consisting following items.
a) 400 A, 50 kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle b) 0-400 A range analogue ammeter of 96 x 96 mm size with
selector switch
c) 3nos. 400 / 5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable rating of MCCB / MCB & Contractors for each capacitor bank
e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil, internally delta connected with built in internal fuses
complete with discharge resistances & terminal cover) of approved make in required steps with well suited detuned reactor is placed in series with
each capacitor step. (e.g., 200 KVAR capacity will be provided in steps of 2 nos x 5 KVAR, 2 nos x 15KVAR, 2 nos x 30 KVAR & 2 nos x 50 KVAR) f)
Enclosure dimensions- 2100 (H) x 1250 (W) x 600 (D)

As per above specification No 205,000 7,575 212,575 18% 250,839

40.4 Above 200 & up to 300 KVAR: APFC panel consisting following items.
a) 630 A, 50 kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle b) 0-630 A range analogue ammeter of 96 x 96 mm size with
selector switch
c) 3nos. 630/5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable rating of MCCB/ MCB & Contractor for each capacitor bank
e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB/ non toxic oil, internally delta connected with built in internal fuses
complete with discharge resistances & terminal cover) of approved make in required steps (e.g., 300 KVAR capacity will be provided in steps of 2nos
x 5 KVAR, 2 nos x 10 KVAR, 2 nos x 15KVAR, 2 nos x 20 KVAR, & 4 nos x 50 KVAR) f) Enclosure dimensions- 1900 (H) x 1200 (W) x 600 (D)

As per above specification No 362,303 7,575 369,878 18% 436,456

40.5 Above 300 & up to 400 KVAR: APFC panel consisting following items.
a) 800 A, 50 kA for 1sec. TP, MDO type, ACB with TM based release & accessories b) 0-800 A range analogue ammeter of 96 x 96 mm size with
selector switch
c) 3nos. 800 / 5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable rating of MCCB/ MCB & Contractor for each capacitor bank
e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil, internally delta connected with built in internal fuses
complete with discharge resistances & terminal cover) of approved make in required steps with well suited detuned reactor is placed in series with
each capacitor step. (e.g., 400 KVAR capacity will be provided in steps of 2 nos x 5 KVAR, 2 nos x 10 KVAR, 2 nos x 15KVAR, 2 nos x 20 KVAR & 6
nos x 50 KVAR) f) Enclosre dimensions- 2100 (H) x 1250 (W) x 1000 (D)

As per above specification No 533,103 7,575 540,678 18% 638,000

41 LV MCC Panel with ATS / Micro processor based soft starter

S.I.T.C of LV MCC Panel totally enclosed, dust & bermin proof, indoor type, minimum degree of protection - IP 52 as per IS: 2147, operation on 3-
Phase, 4 Wire, 415V, 50Hz, Neutral effectively grounded, with instrumentation compartments accomodating LED type indicating lamps, control
contactors as per IS: 13947, CT of accuracy class- I as per IS: 2705, relays, meters & control MCBs, air insulated electrolitic grade Aluminum busbar
for three phase & neutral system with incomming breaker- microprocessor based Air Circuit Breakers (electrically operated drawout type)/ air break
fixed type MCCB with trip free mechanism, current limiting type as per IS: 8828, Motor Contractor (as per type -2 coordination), Overload Relay with
built-in single phasing prevention feature & auxiliary feeders as per SLD drawings, momentary contact type push buttons, equipment fittings, bus
bars, cable boxes, cable gland, incoming & ougoing cable connection for 1100V grade, Aluminium/ Copper conductor XLPE/ PVC insulated & PVC
sheathed armoured cable, 10% spare terminals, power wiring using 1100V grade, FRLS insulated copper conductor wires conforming to IS: 694 &
8130, cable compartments/ alleys of minimum 300 mm size, GI earth bus bar for entire length. MCC shall be fabricated from cold rolled, coled
annealed (CRCA) sheet steel & minimum thickness of various members shall be as follows:
Base Frame/ Channel/ Gland Plate - 3 mm, Load Bearing Members/ Doors - 2 mm and Internal Partitions - 1.6 mm.

41.1 Auto Transformer Starter with MCCB, Contactor, O/L relay, cast resin type CT, Digital MFM, Analog Ammeter, SPP, Timer etc.

a 22 1W 700 x 450 x No. 20034 2525.00 22559 18% 26,620


800
2W+ 1500 x 600 x No. 85180 4545.00 89725 18% 105,876
1S 2175
3W+ 2200 x 600 x No. 128255 5050.00 133305 18% 157,300
2S 2175

Page 109 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
b 30 1W 700 x 450 x No. 28750 2525.00 31275 18% 36,905
800
2 W + 1500 x 600 x No. 113379 4545.00 117924 18% 139,150
1S 2175
3 W + 2200 x 600 x No. 148764 5050.00 153814 18% 181,501
2S 2175
c 37 1W 700 x 450 x No. 39503 4545.00 44048 18% 51,977
800
2 W + 1500 x 600 x No. 153891 5050.00 158941 18% 187,550
1S 2175
3 W + 2200 x 600 x No. 205162 5050.00 210212 18% 248,050
2S 2175
d 45 1W 700 x 450 x No. 40977 5050.00 46027 18% 54,312
800
2 W + 1500 x 600 x No. 169272 5050.00 174322 18% 205,700
1S 2175
3 W + 2200 x 600 x No. 225670 5050.00 230720 18% 272,250
2S 2175
e 55 1W 700 x 450 x No. 45700 5050.00 50750 18% 59,885
800
2 W + 1500 x 600 x No. 212070 5050.00 217120 18% 256,202
1S 2175
3 W + 2200 x 600 x No. 303979 5050.00 309029 18% 364,654
2S 2175
41.2 Microprocessor based Soft Starter with built-in by pass contactor,Semiconductor Fuses, Harmonic Filters, cast resin type CT, Digital MFM,
Analog Ammeter & minimum 10 Channel Temperature Scanner with RS 485 communication port.
a 75 1W 700 x 600 x No. 108106 6060.00 114166 18% 134,715
2175
2 W + 2700 x 600 x No. 461169 7070.00 468239 18% 552,522
1S 2175
3 W + 4100 x 4100 x No. 699761 7070.00 706831 18% 834,061
2S 600 x 600 x
b 90 1 W 2175 2175
700 x 600 x No. 126555 6060.00 132615 18% 156,486
2175
2 W + 2700 x 600 x No. 562320 7070.00 569390 18% 671,880
1S 2175
3 W + 4100 x 600 x No. 815431 7070.00 822501 18% 970,551
2S 2175
c 110 1W 700 x 600 x No. 126555 7070.00 133625 18% 157,678
2175
2 W + 2700 x 600 x No. 570000 7070.00 577070 18% 680,943
1S 2175
3 W + 4400 x 900/600 No. 857581 7070.00 864651 18% 1,020,289
2S x 2175
d 125 1W 700 x 600 x No. 145391 7070.00 152461 18% 179,904
2175
2 W + 2700 x 600 x No. 651304 7070.00 658374 18% 776,882
1S 2175
3 W + 4400 x 4400 x No. 951269 7070.00 958339 18% 1,130,840
2S 900/6 900/60
e 132 1W 00 x x 600
700 0 xx No. 164025 7070.00 171095 18% 201,893
2175
2 W + 2700 x 600 x No. 613000 7070.00 620070 18% 731,683
1S 2175
3 W + 4400 x 900/600 No. 970000 7070.00 977070 18% 1,152,943
2S x 2175
f 160 1W 700 x 600 x No. 182756 7070.00 189826 18% 223,995
2175
2 W + 3000 x 900/600 No. 690000 7070.00 697070 18% 822,543
1S x 2175
3 W + 4400 x 900/600 No. 1087000 7070.00 1094070 18% 1,291,003
2S x 2175
g 180 1W 700 x 600 x No. 196584 7070.00 203654 18% 240,312
2175
2 W + 3000 x 900/600 No. 823920 7070.00 830990 18% 980,568
1S x 2175
3 W + 4400 x 4400 x No. 1217088 7070.00 1224158 18% 1,444,506
2S 900/6 900/60
h 200 1W 00 x x 600
700 0 xx No. 204715 7070.00 211785 18% 249,906
2175
2 W + 3000 x 900/600 No. 858064 7070.00 865134 18% 1,020,859
1S x 2175
3 W + 4400 x 900/600 No. 1267894 7070.00 1274964 18% 1,504,457
2S x 2175
i 225 1W 700 x 600 x No. 220225 8585.00 228810 18% 269,996
2175
2 W + 3000 x 900/600 No. 913579 8585.00 922164 18% 1,088,153
1S x 2175
3 W + 4400 x 900/600 No. 1363396 8585.00 1371981 18% 1,618,937
2S x 2175

Page 110 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
j 250 1W 700 x 600 x No. 248331 8585.00 256916 18% 303,161
2175
2 W + 3000 x 900/600 No. 1007650 8585.00 1016235 18% 1,199,158
1S x 2175
3 W + 4400 x 900/600 No. 1560126 8585.00 1568711 18% 1,851,079
2S x 2175
k 300 1W 800 x 900 x No. 261953 8585.00 270538 18% 319,235
2175
2 W + 3000 x 900/600 No. 1020026 8585.00 1028611 18% 1,213,761
1S x 2175
3W+ 5000 x No. 1562665 8585.00 1571250 18% 1,854,075
2S 1200/900 x
l 315 1W 8002175
x 900 x No. 280583 8585.00 289168 18% 341,218
2175
2W+ 3300 x No. 1079665 8585.00 1088250 18% 1,284,135
1S 1200/900 x
3W+ 2175x
5000 No. 1655817 8585.00 1664402 18% 1,963,994
2S 1200/900 x
m 375 1W 8002175
x 900 x No. 351386 8585.00 359971 18% 424,766
2175
2W+ 3300 x No. 1307058 8585.00 1315643 18% 1,552,458
1S 1200/900 x
3W+ 2175x
5000 No. 1991095 8585.00 1999680 18% 2,359,622
2S 1200/900 x
41.3 Microprocessor based Soft Starter with external by pass2175
contactor,Line Contactor,Semiconductor Fuses, Harmonic Filters, cast resin type
CT, Digital MFM, Analog Ammeter & minimum 10 Channel Temperature Scanner with RS 485 communication port.
a 75 1W 700 x 600 x No. 118262 6060.00 124322 18% 146,700
2175
2 W + 2700 x 600 x No. 492104 7070.00 499174 18% 589,025
1S 2175
3 W + 4100 x 600 x No. 752302 7070.00 759372 18% 896,059
2S 2175
b 90 1W 700 x 600 x No. 125524 6060.00 131584 18% 155,270
2175
2 W + 2700 x 600 x No. 513894 7070.00 520964 18% 614,738
1S 2175
3 W + 4100 x 600 x No. 788621 7070.00 795691 18% 938,915
2S 2175
c 110 1W 700 x 600 x No. 131204 7070.00 138274 18% 163,163
2175
2 W + 2700 x 600 x No. 530932 7070.00 538002 18% 634,843
1S 2175
3 W + 4400 x 900/600 No. 817017 7070.00 824087 18% 972,422
2S x 2175
d 125 1W 700 x 600 x No. 140040 7070.00 147110 18% 173,590
2175
2 W + 2700 x 600 x No. 557441 7070.00 564511 18% 666,123
1S 2175
3 W + 4400 x 900/600 No. 861195 7070.00 868265 18% 1,024,553
2S x 2175
e 132 1W 700 x 600 x No. 156469 7070.00 163539 18% 192,976
2175
2 W + 2700 x 600 x No. 601991 7070.00 609061 18% 718,692
1S 2175
3 W + 4400 x 900/600 No. 943340 7070.00 950410 18% 1,121,484
2S x 2175
f 160 1W 700 x 600 x No. 169054 7070.00 176124 18% 207,826
2175
2 W + 3000 x 900/600 No. 639746 7070.00 646816 18% 763,243
1S x 2175
3 W + 4400 x 900/600 No. 1006265 7070.00 1013335 18% 1,195,735
2S x 2175
g 180 1W 700 x 600 x No. 226099 7070.00 233169 18% 275,139
2175
2 W + 3000 x 900/600 No. 810881 7070.00 817951 18% 965,182
1S x 2175
3 W + 4400 x 900/600 No. 1291492 7070.00 1298562 18% 1,532,303
2S x 2175
h 200 1W 700 x 600 x No. 242436 7070.00 249506 18% 294,417
2175
2 W + 3000 x 900/600 No. 859892 7070.00 866962 18% 1,023,016
1S x 2175
3 W + 4400 x 900/600 No. 1373176 7070.00 1380246 18% 1,628,691
2S x 2175
i 225 1W 700 x 600 x No. 251072 8585.00 259657 18% 306,396
2175
2 W + 3000 x 900/600 No. 885802 8585.00 894387 18% 1,055,377
1S x 2175
3 W + 4400 x 900/600 No. 1416360 8585.00 1424945 18% 1,681,435
2S x 2175

Page 111 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
j 250 1W 700 x 600 x No. 282700 8585.00 291285 18% 343,717
2175
2W+ 3000 x 900/600 No. 980684 8585.00 989269 18% 1,167,337
1S x 2175
3W+ 4400 x 900/600 No. 1574495 8585.00 1583080 18% 1,868,034
2S x 2175
k 300 1W 800 x 900 x No. 307891 8585.00 316476 18% 373,442
2175
2W+ 3000 x 900/600 No. 1056256 8585.00 1064841 18% 1,256,513
1S x 2175
3W+ 5000 x No. 1700451 8585.00 1709036 18% 2,016,663
2S 1200/900 x
l 315 1W 8002175
x 900 x No. 345802 8585.00 354387 18% 418,177
2175
2W+ 3300 x No. 1169899 8585.00 1178484 18% 1,390,611
1S 1200/900 x
3W+ 2175x
5000 No. 1889856 8585.00 1898441 18% 2,240,161
2S 1200/900 x
m 375 1W 8002175
x 900 x No. 377334 8585.00 385919 18% 455,385
2175
2W+ 3300 x No. 1264584 8585.00 1273169 18% 1,502,339
1S 1200/900 x
3W+ 2175x
5000 No. 2047663 8585.00 2056248 18% 2,426,372
2S 1200/900 x
42 HV VCB SWITCHGEAR PANEL 2175

42.1 Supply, installation, testing & commissioning both side extensible, Indoor type HV Switchgear panel confirming to IS-3427, IS-2516 (Part-I & II.sec.1 )
& IEC-60056 & IEC-62271-100/200 for use on 3phase, 50 Hz, unearthed AC supply system and having breaking/ ruptuing capacity of 150 MVA (26.3
kA for 3sec) complete with spring charged mechanism, ON-OFF mechanical push button, operation counters, Breaker TNC switch, Breaker L/R
switch, necessary auxiliary switches, closing coil, shunt trip, protection relays & Indicators etc., complete.
The panel shall comprise of air insulated busbars provided with heat shrinkable PVC sleeves. The VCB trolley shall comprise of three vacuum
interrupters with epoxy support insulators and self aligning finger type isolating contacts and necessary mechanical interlocks, safety shutters,
isolating plugs. Enclosure shall be openable from front as well as rear end. The breaker shall be Manual cum motorised mechanism with following
accessories.
a) 96 x 96 mm square flush mounting type Ammeter & Volt meter with selector switches
b) Multi function meter
c) Double core, cast resin type current transofrmer having ratio as per requirement, one core for metering & one core for protection having required
class of accuracy.
d) Instantaneous under voltage relay & Temperature rise tripping Relay,
e) Triple pole IDMTL two over current and one earth fault relay with current setting range 50-200% and 10-40%
f) Electrical closing. coil & shunt trip coil operating on 110 V DC.
g) Auxiliary relay for anti pumping device.
h) Three limb, drawout type, feeder connected, cast resin insulated, three phase Potential transformer having ratio & burden as per reqirement &
Class 0.5 accuracy.
i) Annunciator Windows, Common Hooter / Alarm bell operating on 230 AC / 110 V DC
j) Cable boxes suitable to terminate 3 core XLPE cable of required size (As per design).
k) 230V A.C. to 110 V D.C.power pack for closing & tripping circuit common.
l) Breaker ON-OFF, Auto trip and spring charged indicators.
m) Phase indicating & panel illumination lamps with plug socket.
n) Space Heater with Thermostat.
a 3.3 kV HV Switchgear Panel- Comprising of 1250 A Vacuum circuit Set 3,589,070 22,725 3,611,795 18.00% 4,261,918
breaker for 2 nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2nos. O / G for 3.3 / 0.433kV Auxiliary
transformers

b 3.3 kV HV Switchgear Panel- Comprising of 800 A Vacuum circuit Set 3,589,070 22,725 3,611,795 18% 4,261,918
breaker for 2nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2 nos. O/G for 3.3 / 0.433kV Auxiliary
transformers

c 3.3 kV HV Switchgear Panel- Comprising of 630 A Vacuum circuit Set 3,589,070 22,725 3,611,795 18% 4,261,918
breaker for 2nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2nos. O/G for 3.3 / 0.433kV Auxiliary
transformers

d 3.3 kV HV Switchgear Panel- Comprising of 1250 A Vacuum circuit Set 3,046,005 22,725 3,068,730 18% 3,621,101
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2nos. O / G for 3.3 / 0.433kV Auxiliary
transformers

e 3.3 kV HV Switchgear Panel- Comprising of 800 A Vacuum circuit Set 3,046,005 22,725 3,068,730 18% 3,621,101
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2nos. O/G for 3.3 / 0.433kV Auxiliary
transformers

f 3.3 kV HV Switchgear Panel- Comprising of 630 A Vacuum circuit Set 3,046,005 22,725 3,068,730 18% 3,621,101
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2nos. O / G for 3.3 / 0.433kV Auxiliary
transformers

Page 112 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
42.2 Supply, installation, testing & commissioning both side extensible, Indoor type HV Switchgear panel confirming to IS-3427, IS-2516 (Part-I & II.sec.1 )
& IEC-60056 & IEC-62271-100/200 for use on 3phase, 50 Hz, unearthed AC supply system and having breaking/ ruptuing capacity of 500 MVA (26.3
kA for 3sec) complete with spring charged mechanism, ON-OFF mechanical push button, operation counters, Breaker TNC switch, Breaker L/R
switch, necessary auxiliary switches, closing coil, shunt trip, protection relays & Indicators etc., complete.
The panel shall comprise of air insulated busbars provided with heat shrinkable PVC sleeves. The VCB trolley shall comprise of three vacuum
interrupters with epoxy support insulators and self aligning finger type isolating contacts and necessary mechanical interlocks, safety shutters,
isolating plugs. Enclosure shall be openable from front as well as rear end. The breaker shall be Manual cum motorised mechanism with following
accessories.
a) 96 x 96 mm square flush mounting type Ammeter & Volt meter with selector switches
b) Multi function meter
c) Double core, cast resin type current transofrmer having ratio as per requirement, one core for metering & one core for protection having required
class of accuracy.
d) Instantaneous under voltage relay & Temperature rise tripping Relay,
e) Triple pole IDMTL two over current and one earth fault relay with current setting range 50-200% and 10-40%
f) Electrical closing. coil & shunt trip coil operating on 110 V DC.
g) Auxiliary relay for anti pumping device.
h) Three limb, drawout type, feeder connected, cast resin insulated, three phase Potential transformer having ratio & burden as per reqirement &
Class 0.5 accuracy.
i) Annunciator Windows, Common Hooter / Alarm bell operating on 230 AC/ 110 V DC
j) Cable boxes suitable to terminate 3 core XLPE cable of required size (As per design).
k) 230V A.C. to 110 V D.C.power pack for closing & tripping circuit common.
l) Breaker ON-OFF, Auto trip and spring charged indicators.
m) Phase indicating & panel illumination lamps with plug socket.
n) Space Heater with Thermostat.
a 6.6 kV HV Switchgear Panel- Comprising of 1250 A Vacuum circuit Set 3,589,070 27,270 3,616,340 18.00% 4,267,281
breaker for 2nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2 nos. O / G for 6.6 / 0.433kV Auxiliary
transformers

b 6.6 kV HV Switchgear Panel- Comprising of 800 A Vacuum circuit Set 3,589,070 27,270 3,616,340 18.00% 4,267,281
breaker for 2nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2 nos. O/G for 6.6 / 0.433kV Auxiliary
transformers

c 6.6 kV HV Switchgear Panel- Comprising of 630 A Vacuum circuit Set 3,066,964 27,270 3,094,234 18% 3,651,196
breaker for 2nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2 nos. O/G for 6.6 / 0.433kV Auxiliary
transformers

d 6.6 kV HV Switchgear Panel- Comprising of 1250 A Vacuum circuit Set 3,046,005 27,270 3,073,275 18% 3,626,465
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2 nos. O/G for 6.6 / 0.433kV Auxiliary
transformers

e 6.6 kV HV Switchgear Panel- Comprising of 800 A Vacuum circuit Set 3,046,005 27,270 3,073,275 18% 3,626,465
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2 nos. O/G for 6.6 / 0.433kV Auxiliary
transformers
f 6.6 kV HV Switchgear Panel- Comprising of 630 A Vacuum circuit Set 3,046,005 27,270 3,073,275 18% 3,626,465
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2nos. O/G for 6.6 / 0.433kV Auxiliary
transformers

42.3 Supply, installation, testing & commissioning both side extensible, Indoor type HV Switchgear panel confirming to IS-3427, IS-2516 (Part-I & II.sec.1 )
& IEC-60056 & IEC-62271-100/200 for use on 3phase, 50 Hz, unearthed AC supply system and having breaking/ ruptuing capacity of 500 MVA (26.3
kA for 3sec) complete with spring charged mechanism, ON-OFF mechanical push button, operation counters, Breaker TNC switch, Breaker L/R
switch, necessary auxiliary switches, closing coil, shunt trip, protection relays & Indicators etc., complete.
The panel shall comprise of air insulated busbars provided with heat shrinkable PVC sleeves. The VCB trolley shall comprise of three vacuum
interrupters with epoxy support insulators and self aligning finger type isolating contacts and necessary mechanical interlocks, safety shutters,
isolating plugs. Enclosure shall be openable from front as well as rear end.
The breaker shall be Manual cum motorised mechanism with following accessories.
a) 96 x 96 mm square flush mounting type Ammeter & Volt meter with selector switches
b) Multi function meter
c) Double core, cast resin type current transofrmer having ratio as per requirement, one core for metering & one core for protection having required
class of accuracy.
d) Instantaneous under voltage relay & Temperature rise tripping Relay,
e) Triple pole IDMTL two over current and one earth fault relay with current setting range 50-200% and 10-40%
f) Electrical closing. coil & shunt trip coil operating on 110 V DC.
g) Auxiliary relay for anti pumping device.
h) Three limb, drawout type, feeder connected, cast resin insulated, three phase Potential transformer having ratio & burden as per reqirement &
Class 0.5 accuracy.
i) Annunciator Windows, Common Hooter / Alarm bell operating on 230 AC/ 110 V DC
j) Cable boxes suitable to terminate 3 core XLPE cable of required size (As per design).
k) 230V A.C. to 110 V D.C.power pack for closing & tripping circuit common.
l) Breaker ON-OFF, Auto trip and spring charged indicators. m) Phase indicating & panel illumination lamps with plug socket. n) Space Heater with
Thermostat.
a 11 kV HV Switchgear Panel- Comprising of 1250 A Vacuum circuit Set 3,589,070 31,815 3,620,885 18.00% 4,272,644
breaker for 2 nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2nos. O / G for 11 / 0.433kV Auxiliary
transformers

Page 113 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
b 11 kV HV Switchgear Panel- Comprising of 800 A Vacuum circuit Set 3,589,070 31,815 3,620,885 18% 4,272,644
breaker for 2 nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2nos. O / G for 11 / 0.433kV Auxiliary
transformers
c 11 kV HV Switchgear Panel- Comprising of 630 A Vacuum circuit Set 3,589,070 31,815 3,620,885 18% 4,272,644
breaker for 2nos. Incomer, 1no. Bus coupler, 8 nos. O/G feeders for
Motor Soft Starters, 2nos. O / G for 11 / 0.433kV Auxiliary
transformers

d 11 kV HV Switchgear Panel- Comprising of 1250 A Vacuum circuit Set 3,046,005 31,815 3,077,820 18% 3,631,828
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2nos. O/G for 11 / 0.433kV Auxiliary transformers

e 11 kV HV Switchgear Panel- Comprising of 800 A Vacuum circuit Set 3,046,005 31,815 3,077,820 18% 3,631,828
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2nos. O/G for 11 / 0.433kV Auxiliary transformers

f 11 kV HV Switchgear Panel- Comprising of 630 A Vacuum circuit Set 3,046,005 31,815 3,077,820 18% 3,631,828
breaker for 2nos. Incomer, 1no. Bus coupler, 6 nos. O/G feeders for
Motor Soft Starters, 2 nos. O/G for 11 / 0.433kV Auxiliary
transformers

g 11 kV HV Switchgear Panel- Comprising of 1250 A Vacuum circuit Set 843,008 31,815 874,823 18% 1,032,291
breaker for 1no. Incomer, 2 nos. O / G feeders for 11/0.433kV
distribution transformers

h 11 kV HV Switchgear Panel- Comprising of 800 A Vacuum circuit Set 801,090 31,815 832,905 18% 982,828
breaker for 1no. Incomer, 2no. O / G feeders for 11/0.433kV
distribution transformers

i 11 kV HV Switchgear Panel- Comprising of 630 A Vacuum circuit Set 797,830 31,815 829,645 18% 978,981
breaker for 1no. Incomer, 2no. O / G feeders for 11/0.433kV
distribution transformers

j 11 kV HV ICOG Switchgear Panel- Comprising of 1250 A Vacuum Set 281,779 31,815 313,594 18% 370,041
circuit breaker for 1no. Incomer, 1no. O / G feeders for 11/0.433kV
distribution transformers

k 11 kV HV ICOG Switchgear Panel- Comprising of 800 A Vacuum Set 281,779 31,815 313,594 18% 370,041
circuit breaker for 1no. Incomer, 1no. O / G feeders for 11/0.433kV
distribution transformers

l 11 kV HV ICOG Switchgear Panel- Comprising of 630 A Vacuum Set 281,779 31,815 313,594 18% 370,041
circuit breaker for 1no. Incomer, 1no. O / G feeders for 11/0.433kV
distribution transformers

43 Solar System
43.1.1 Supply Solar PV Panels 900 wp, Each modules not less then 175 wp No. 47,277 Incl. 47,277 5% 49,641
should be in accordance with requirement of national & international
certificates such as IEC 61215 & 61730 for DC type Submersible
pump with MPPT controller.

43.1.2 Supply Solar PV Panels 1200 wp, Each modules not less then 175 61,553 Incl. 61,553 5% 64,630
wp should be in accordance with requirement of national &
international certificates such as IEC 61215 & 61730 for DC type
Submersible pump with MPPT controller.

43.1.3 Supply Solar PV Panels 1800 wp, Each modules not less then 175 94,554 Incl. 94,554 5% 99,282
wp should be in accordance with requirement of national &
international certificates such as IEC 61215 & 61730 for DC type
Submersible pump with MPPT controller.

43.1.4 Supply Solar PV Panels 2450 wp, Each modules not less then 175 171,456 Incl. 171,456 5% 180,029
wp should be in accordance with requirement of national &
international certificates such as IEC 61215 & 61730 for DC type
Submersible pump with MPPT controller.

43.2.1 Supply DC Submersible pump Discharge 7200 LPD for 90 Mtr. With 78,149 Incl. 78,149 12% 87,527
Controller Drive. MOC: SS 316
43.2.2 Supply DC Submersible pump Discharge 10000 LPD for 120 Mtr. 83,812 Incl. 83,812 12% 93,869
With Controller Drive. MOC: SS 316
43.2.3 Supply DC Voltage Submersible pump Discharge 10000 LPD for 170 93,558 Incl. 93,558 12% 104,785
Mtr. With Controller Drive.
43.2.4 Supply DC Submersible pump Discharge 10000 LPD for 200 Mtr. 103,000 Incl. 103,000 12% 115,360
With Controller Drive. MOC: SS 316

Page 114 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
43.3.1 Installation, Testing and Commissiioning of SPV Panel with pole with 48,435 Incl. 48,435 18% 57,154
panel mounting frames. AC/Dc sub. Pump with Solar drive required
cableling and G.I.Piping with all installation work with transportation
etc with required bar fencing with single gate etc.900Wp

43.3.2 ---as above---1200Wp 62,000 Incl. 62,000 18% 73,160

43.3.3 ---as above---1800Wp 77,172 Incl. 77,172 18% 91,063

43.3.4 ---as above---2400Wp 108,781 Incl. 108,781 18% 128,362

43.4.1 5 Years Comprehensive O&M work of above work with insurance of 15,434 Incl. 15,434 18% 18,212
all items like SPV Panel, Pump, Cable, G.I.Pipe, Controller etc for
entire period i.o. 05 years etc.900Wp

43.4.2 ---as above---1200Wp 16,467 Incl. 16,467 18% 19,430

43.4.3 ---as above---1800Wp 21,258 Incl. 21,258 18% 25,084

43.4.5 ---as above---2400Wp 32,607 Incl. 32,607 18% 38,477

44 Providing Submerged centrifugal pumpsets(water immersed, dry air filled, class "F" insulated TEWC motor integrally mounted on volute
casing pumpsets for water duty, 3-phase, 50Hz±3%,415V±10% along with suitable foundation/ installation device with cable length from
pumps to panels & of following Material of Construction:
Impeller-CF8M, Casing-C.I. FG 260, Wearing Ring -SS, TC mechanical seal, CS/S.S.bearing, S.S shaft with sleeve, SS strainer & MS motor
body.
A Rating

1 upto 30.0 KW per 9,695.00 - 9,695.00 12% 10,858


KW
2 31.0 KW to 75.0 KW per 9,695.00 - 9,695.00 12% 10,858
KW
3 76.0 KW to 132.0 KW per 10,115.00 - 10,115.00 12% 11,329
KW
4 133 KW to 315 KW per 11,000.00 - 11,000.00 12% 12,320
KW
5 Above 315 KW per 11,000.00 - 11,000.00 12% 12,320
KW
B Erection Charges for Pumpsets (without material supply)

1 upto 30.0 KW Job - 19,950.00 19,950.00 5% 20,948

2 31.0 KW to 75.0 KW Job - 33,250.00 33,250.00 5% 34,913

3 76.0 KW to 132.0 KW Job - 53,200.00 53,200.00 5% 55,860

4 133 KW to 315 KW Job - 80,000.00 80,000.00 5% 84,000

5 Above 315 KW Job - 80,000.00 80,000.00 5% 84,000

45 LV POWER CONTROL CENTER (PCC)

1 Supply, installation, testing and commissioning LV Distribution Board (LVDB) totally enclosed, dust & vermin proof, indoor type, fabricated from
CRCA sheet steel with minimum thickness of 3 mm for base frame/ channel/ gland plates, 2.0 mm for load bearing members/ doors & 1.6 mm for
internal partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for operation on 3-Phase, 4 Wire, 415V, 50Hz, Neutral effectively
grounded, with instrumentation compartments accomodating meters, aux / protective relays, LED type indicating lamps & control MCBs as per IS:
13947, current & voltage transformers as per IS: 2705, air insulated electrolitic grade Aluminum/ Copper busbar for three phase & neutral system, GI
earth bus for entire length, power/ control wiring using 1100V grade, FRLS insulated copper conductor wires conforming to IS: 694 & 8130,
equipment fittings, horizontally running busbar compartment height of minimum 300 mm, incoming & ougoing cable connections for 1100V grade,
Aluminium/ Copper conductor XLPE/ PVC insulated & PVC sheathed armoured cable. LVDB shall have required incomming/ buscoupler/ outgoing
modules of following type & ratings.

Part-1

1.1 4000A, 3/ 4 Pole, ACB (Draw-out Type) with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu of 70 kA
at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro-Mechanical protections & interlocks
etc. ACB Module shall have enclosure dimension: 2000 (H) x 1100 (W) x 1200 (D) & following technical features:

1.1a 3 pole, MDO with Thermal Magnetic Release No. 280,963 5,500 286,463 18% 338,026

1.1b 3 pole, EDO with Thermal Magnetic Release No. 301,527 5,500 307,027 18% 362,292

1.1c 3 pole, MDO with Microprocessor Release No. 286,995 5,500 292,495 18% 345,144

1.1d 3 pole, EDO with Microprocessor Release No. 307,558 5,500 313,058 18% 369,408

1.1e 4 pole, MDO with Thermal Magnetic Release No. 338,996 5,500 344,496 18% 406,505

1.1f 4 pole, EDO with Thermal Magnetic Release No. 359,536 5,500 365,036 18% 430,742

Page 115 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.1g 4 pole, MDO with Microprocessor Release No. 345,028 5,500 350,528 18% 413,623

1.1h 4 pole, EDO with Microprocessor Release No. 365,567 5,500 371,067 18% 437,859

1.2 3200A, 3 / 4 Pole, ACB (Draw-out Type) with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu
of 60 kA at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro-Mechanical
protections & interlocks etc. ACB Module shall have enclosure dimension: 2000(H) x 1100(W) x 1100 (D) & following technical features:

1.2a 3 pole, MDO with Thermal Magnetic Release No. 233,113 5,500 238,613 18% 281,563

1.2b 3 pole, EDO with Thermal Magnetic Release No. 255,991 5,500 261,491 18% 308,559

1.2c 3 pole, MDO with Microprocessor Release No. 241,162 5,500 246,662 18% 291,061

1.2d 3 pole, EDO with Microprocessor Release No. 262,497 5,500 267,997 18% 316,236

1.2e 4 pole, MDO with Thermal Magnetic Release No. 276,539 5,500 282,039 18% 332,806

1.2f 4 pole, EDO with Thermal Magnetic Release No. 297,078 5,500 302,578 18% 357,042

1.2g 4 pole, MDO with Microprocessor Release No. 282,570 5,500 288,070 18% 339,923

1.2f 4 pole, EDO with Microprocessor Release No. 303,110 5,500 308,610 18% 364,160

1.3 2500A, 3/ 4 Pole, ACB (Draw-out Type) with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu of
60 kA at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro-Mechanical
protections & interlocks etc. ACB Module shall have enclosure dimension: 2000 (H) x 900 (W) x 1100 (D) & following technical features:

1.3a 3 pole, MDO with Thermal Magnetic Release No. 176,843 5,500 182,343 18% 215,165

1.3b 3 pole, EDO with Thermal Magnetic Release No. 199,721 5,500 205,221 18% 242,161

1.3c 3 pole, MDO with Microprocessor Release No. 184,891 5,500 190,391 18% 224,661

1.3d 3 pole, EDO with Microprocessor Release No. 207,769 5,500 213,269 18% 251,657

1.3e 4 pole, MDO with Thermal Magnetic Release No. 214,664 5,500 220,164 18% 259,794

1.3f 4 pole, EDO with Thermal Magnetic Release No. 235,017 5,500 240,517 18% 283,810

1.3g 4 pole, MDO with Microprocessor Release No. 220,044 5,500 225,544 18% 266,142

1.3f 4 pole, EDO with Microprocessor Release No. 241,048 5,500 246,548 18% 290,927

1.4 2000A, 3 &4 Pole, ACB (Draw-out Type) with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu of
50 kA at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro-Mechanical
protections & interlocks etc. ACB Module shall have enclosure dimension: 2000 (H) x 900 (W) x 1100 (D) & following technical features:
Enclosure dimension: 2000(H) x 900(W) x 1100 (D)

1.4a 3 pole, MDO with Thermal Magnetic Release No. 146,991 5,500 152,491 18% 179,939

1.4b 3 pole, EDO with Thermal Magnetic Release No. 169,869 5,500 175,369 18% 206,935

1.4c 3 pole, MDO with Microprocessor Release No. 155,039 5,500 160,539 18% 189,436

1.4d 3 pole, EDO with Microprocessor Release No. 177,917 5,500 183,417 18% 216,432

1.4e 4 pole, MDO with Thermal Magnetic Release No. 185,987 5,500 191,487 18% 225,955

1.4f 4 pole, EDO with Thermal Magnetic Release No. 208,819 5,500 214,319 18% 252,896

1.4g 4 pole, MDO with Microprocessor Release No. 194,035 5,500 199,535 18% 235,451

1.4f 4 pole, EDO with Microprocessor Release No. 214,851 5,500 220,351 18% 260,014

1.5 1600A, 3 & 4 Pole, ACB (Draw-out Type) with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu
of 50 kA at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro Mechanical
protections & interlocks etc. ACB Module shall have enclosure dimension: 2000 (H) x 800 (W) x 1000 (D) & following technical features:

1.5a 3 pole, MDO with Thermal Magnetic Release No. 122,474 5,500 127,974 18% 151,009

1.5b 3 pole, EDO with Thermal Magnetic Release No. 145,351 5,500 150,851 18% 178,004

1.5c 3 pole, MDO with Microprocessor Release No. 130,522 5,500 136,022 18% 160,506

1.5d 3 pole, EDO with Microprocessor Release No. 153,399 5,500 158,899 18% 187,501

1.5e 4 pole, MDO with Thermal Magnetic Release No. 151,559 5,500 157,059 18% 185,330

Page 116 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.5f 4 pole, EDO with Thermal- Magnetic Release No. 174,437 5,500 179,937 18% 212,326

1.5g 4 pole, MDO with Microprocessor Release No. 159,607 5,500 165,107 18% 194,826

1.5h 4 pole, EDO with Microprocessor Release No. 182,485 5,500 187,985 18% 221,822

1.6 1250A, 3 &4 Pole, ACB (Draw-out Type) with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu
of 50kA at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro Mechanical
protections & interlocks etc. ACB Module shall have enclosure dimension: 2000 (H) x 800 (W) x 1000 (D) & following technical features:

1.6a 3 pole, MDO with Thermal Magnetic Release No. 107,808 5,500 113,308 18% 133,703

1.6b 3 pole, EDO with Thermal Magnetic Release No. 130,685 5,500 136,185 18% 160,698

1.6c 3 pole, MDO with Microprocessor Release No. 115,857 5,500 121,357 18% 143,201

1.6d 3 pole, EDO with Microprocessor Release No. 138,734 5,500 144,234 18% 170,196

1.6e 4 pole, MDO with Thermal Magnetic Release No. 137,221 5,500 142,721 18% 168,411

1.6f 4 pole, EDO with Thermal Magnetic Release No. 160,098 5,500 165,598 18% 195,406

1.6g 4 pole, MDO with Microprocessor Release No. 145,270 5,500 150,770 18% 177,909

1.6h 4 pole, EDO with Microprocessor Release No. 168,147 5,500 173,647 18% 204,903

1.7 1000A, 3 &4 Pole, ACB (Draw-out Type) with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu
of 50kA at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro Mechanical
protections & interlocks etc. ACB Module shall have enclosure dimension: 2000(H) x 800(W) x 1000 (D) & following technical features:

1.7a 3 pole, MDO with Thermal Magnetic Release No. 95,728 5,500 101,228 18% 119,449

1.7b 3 pole, EDO with Thermal Magnetic Release No. 118,606 5,500 124,106 18% 146,445

1.7c 3 pole, MDO with Microprocessor Release No. 103,776 5,500 109,276 18% 128,946

1.7d 3 pole, EDO with Microprocessor Release No. 126,654 5,500 132,154 18% 155,942

1.7e 4 pole, MDO with Thermal Magnetic Release No. 122,668 5,500 128,168 18% 151,238

1.7f 4 pole, EDO with Thermal Magnetic Release No. 145,545 5,500 151,045 18% 178,233

1.7g 4 pole, MDO with Microprocessor Release No. 130,715 5,500 136,215 18% 160,734

1.7h 4 pole, EDO with Microprocessor Release No. 153,593 5,500 159,093 18% 187,730

1.8 800A, 3 &4 Pole, ACB (Draw-out Type) with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu of
50kA at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro Mechanical
protections & interlocks etc.
ACB module shall have enclosure dimension: 2000 (H) x 800 (W) x 1000 (D) & following technical features.

1.8a 3 pole, MDO with Thermal Magnetic Release No. 90,810 5,500 96,310 18% 113,646

1.8b 3 pole, EDO with Thermal Magnetic Release No. 113,687 5,500 119,187 18% 140,641

1.8c 3 pole, MDO with Microprocessor Release No. 98,859 5,500 104,359 18% 123,144

1.8d 3 pole, EDO with Microprocessor Release No. 121,736 5,500 127,236 18% 150,138

1.8e 4 pole, MDO with Thermal Magnetic Release No. 115,722 5,500 121,222 18% 143,042

1.8f 4 pole, EDO with Thermal Magnetic Release No. 138,600 5,500 144,100 18% 170,038

1.8g 4 pole, MDO with Microprocessor Release No. 123,770 5,500 129,270 18% 152,539

1.8h 4 pole, EDO with Microprocessor Release No. 152,191 5,500 157,691 18% 186,075

1.9 Above 400A, upto & including 630A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS / IEC 60947-2 with trip free mechanism, current
limiting type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC
potential free auxiliary contacts with all necessary Electro Mechanical protections & interlocks etc. MCCB module, when used as
Incommer/ Bus Coupler, shall have enclosure dimensions- 2000 (H) x 650 (W) x 600 (D) & following technical features:

1.9a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 33,460 4,000 37,460 18% 44,203
=100% of Icu), TM release
1.9b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 36,705 4,000 40,705 18% 48,032
=100% of Icu), Microprocessor release

Page 117 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.9c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 31,984 4,000 35,984 18% 42,461
=100% of Icu), TM release

1.9d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 34,701 4,000 38,701 18% 45,667
=100% of Icu), Microprocessor release

1.9e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 31,984 4,000 35,984 18% 42,461
=100% of Icu), TM release
1.9f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 34,701 4,000 38,701 18% 45,667
=100% of Icu), Microprocessor release

1.9g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 40,609 4,000 44,609 18% 52,639
=100% of Icu), TM release
1.9h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 46,940 4,000 50,940 18% 60,109
=100% of Icu), Microprocessor release

1.9i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 38,017 4,000 42,017 18% 49,580
=100% of Icu), TM release
1.9j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 42,685 4,000 46,685 18% 55,088
=100% of Icu), Microprocessor release

1.9k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 38,017 4,000 42,017 18% 49,580
=100% of Icu), TM release
1.9l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 42,685 4,000 46,685 18% 55,088
=100% of Icu), Microprocessor release

1.10 Above 400A, upto & including 630A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS / IEC 60947-2 with trip free mechanism, current
limiting type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC
potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used as
Outgoing(s), shall have enclosure dimensions- 600 (H) x 600 (W) x 600 (D) & following technical features:

1.10a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 33,460 4,000 37,460 18.00% 44,203
=100% of Icu), TM release

1.10b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 36,705 4,000 40,705 18.00% 48,032
=100% of Icu), Microprocessor release

1.10c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 31,984 4,000 35,984 18% 42,461
=100% of Icu), TM release
1.10d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 34,701 4,000 38,701 18% 45,667
=100% of Icu), Microprocessor release

1.10e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 31,984 4,000 35,984 18% 42,461
=100% of Icu), TM release

1.10f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 34,701 4,000 38,701 18% 45,667
=100% of Icu), Microprocessor release

1.10g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 40,609 4,000 44,609 18% 52,639
=100% of Icu), TM release

1.10h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 46,940 4,000 50,940 18% 60,109
=100% of Icu), Microprocessor release

1.10i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 38,017 4,000 42,017 18% 49,580
=100% of Icu), TM release
1.10j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 42,685 4,000 46,685 18% 55,088
=100% of Icu), Microprocessor release

1.10k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 38,017 4,000 42,017 18% 49,580
=100% of Icu), TM release

1.10l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 42,685 4,000 46,685 18% 55,088
=100% of Icu), Microprocessor release

1.11 Above 250A, upto & including 400A, 3 / 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism, current
limiting type with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC
potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used as
Incommer/ Bus Coupler, shall have enclosure dimensions- 1800 (H) x 600 (W) x 600 (D) & following technical features:

1.11a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 29,145 4,000 33,145 18% 39,111
=100% of Icu), TM release
1.11b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 33,434 4,000 37,434 18% 44,172
=100% of Icu), Microprocessor release

1.11c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 26,969 4,000 30,969 18% 36,543
=100% of Icu), TM release
1.11d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 32,345 4,000 36,345 18% 42,887
=100% of Icu), Microprocessor release

Page 118 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.11e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 26,969 4,000 30,969 18% 36,543
=100% of Icu), TM release
1.11f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 32,345 4,000 36,345 18% 42,887
=100% of Icu), Microprocessor release

1.11g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 34,380 4,000 38,380 18% 45,288
=100% of Icu), TM release

1.11h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 39,690 4,000 43,690 18% 51,554
=100% of Icu), Microprocessor release

1.11i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 31,690 4,000 35,690 18% 42,114
=100% of Icu), TM release

1.11j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 37,729 4,000 41,729 18% 49,240
=100% of Icu), Microprocessor release

1.11k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 31,690 4,000 35,690 18% 42,114
=100% of Icu), TM release

1.11l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 37,729 4,000 41,729 18% 49,240
=100% of Icu), Microprocessor release

1.12 Above 250A, upto & including 400A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism, current
limiting type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC
potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used as
Outgoing(s), shall have enclosure dimensions- 500 (H) x 600 (W) x 600 (D) & following technical features:

1.12a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 29,145 3,500 32,645 18% 38,521
=100% of Icu), TM release

1.12b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 33,434 3,500 36,934 18% 43,582
=100% of Icu), Microprocessor release

1.12c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 26,969 3,500 30,469 18% 35,953
=100% of Icu), TM release

1.12d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 32,345 3,500 35,845 18% 42,297
=100% of Icu), Microprocessor release

1.12e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 26,969 3,500 30,469 18% 35,953
=100% of Icu), TM release

1.12f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 32,345 3,500 35,845 18% 42,297
=100% of Icu), Microprocessor release

1.12g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 34,380 3,500 37,880 18% 44,698
=100% of Icu), TM release

1.12h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 39,690 3,500 43,190 18% 50,964
=100% of Icu), Microprocessor release

1.12i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 31,690 3,500 35,190 18% 41,524
=100% of Icu), TM release

1.12j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 37,729 3,500 41,229 18% 48,650
=100% of Icu), Microprocessor release

1.12k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 31,690 3,500 35,190 18% 41,524
=100% of Icu), TM release

1.12l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 37,729 3,500 41,229 18% 48,650
=100% of Icu), Microprocessor release

1.13 Above 80A, upto & including 250A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS / IEC 60947-2 with trip free mechanism, current
limiting type with Thermal-Magnetic / Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC
potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used as
Incommer/ Bus Coupler, shall have enclosure dimensions- 1800(H) x 600(W) x 600 (D) & following technical features:

1.13a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 24,830 3,500 28,330 18% 33,429
=100% of Icu), TM release

1.13b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 27,688 3,500 31,188 18% 36,802
=100% of Icu), Microprocessor release

1.13c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 23,370 3,500 26,870 18% 31,707
=100% of Icu), TM release

1.13d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 26,346 3,500 29,846 18% 35,218
=100% of Icu), Microprocessor release

1.13e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 21,246 3,500 24,746 18% 29,200
=100% of Icu), TM release

Page 119 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.13f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 26,346 3,500 29,846 18% 35,218
=100% of Icu), Microprocessor release

1.13g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 28,641 3,500 32,141 18% 37,926
=100% of Icu), TM release

1.13h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 32,923 3,500 36,423 18% 42,979
=100% of Icu), Microprocessor release

1.13i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 26,645 3,500 30,145 18% 35,571
=100% of Icu), TM release

1.13j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 31,894 3,500 35,394 18% 41,765
=100% of Icu), Microprocessor release

1.13k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 24,863 3,500 28,363 18% 33,468
=100% of Icu), TM release

1.13l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 31,894 3,500 35,394 18% 41,765
=100% of Icu), Microprocessor release

1.14 Above 80A, upto & including 250A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism, current
limiting type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC
potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used as
Outgoing(s), shall have enclosure dimensions- 400 (H) x 600 (W) x 600 (D) & following technical features:

1.14a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 24,830 3,500 28,330 18% 33,429
=100% of Icu), TM release

1.14b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 27,688 3,500 31,188 18% 36,802
=100% of Icu), Microprocessor release

1.14c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 23,370 3,500 26,870 18% 31,707
=100% of Icu), TM release
1.14d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 26,346 3,500 29,846 18% 35,218
=100% of Icu), Microprocessor release

1.14e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 21,246 3,500 24,746 18% 29,200
=100% of Icu), TM release

1.14f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 26,346 3,500 29,846 18% 35,218
=100% of Icu), Microprocessor release

1.14g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 28,641 3,500 32,141 18% 37,926
=100% of Icu), TM release

1.14h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 32,923 3,500 36,423 18% 42,979
=100% of Icu), Microprocessor release

1.14i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 26,645 3,500 30,145 18% 35,571
=100% of Icu), TM release

1.14j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 31,894 3,500 35,394 18% 41,765
=100% of Icu), Microprocessor release

1.14k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 24,863 3,500 28,363 18% 33,468
=100% of Icu), TM release
1.14l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 31,894 3,500 35,394 18% 41,765
=100% of Icu), Microprocessor release

1.15 Above 16A, upto & including 80A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism, current limiting
type with Thermal Magnetic/ Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC potential
free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used as Incommer/ Bus
Coupler, shall have enclosure dimensions- 1800(H) x 500(W) x 600 (D) & following technical features:

1.15a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 14,110 3,500 17,610 18% 20,780
=100% of Icu), TM release

1.15b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 21,935 3,500 25,435 18% 30,013
=100% of Icu), Microprocessor release

1.15c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 12,046 3,500 15,546 18% 18,344
=100% of Icu), TM release

1.15d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 20,281 3,500 23,781 18% 28,062
=100% of Icu), Microprocessor release

1.15e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 11,715 3,500 15,215 18% 17,954
=100% of Icu), TM release

Page 120 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.15f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 20,281 3,500 23,781 18% 28,062
=100% of Icu), Microprocessor release

1.15g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 16,644 3,500 20,144 18% 23,770
=100% of Icu), TM release

1.15h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 25,564 3,500 29,064 18% 34,296
=100% of Icu), Microprocessor release

1.15i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 13,574 3,500 17,074 18% 20,147
=100% of Icu), TM release

1.15j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 23,045 3,500 26,545 18% 31,323
=100% of Icu), Microprocessor release

1.15k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 13,078 3,500 16,578 18% 19,562
=100% of Icu), TM release

1.15l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 23,045 3,500 26,545 18% 31,323
=100% of Icu), Microprocessor release

1.16 Above 16A, upto & including 80A, 3 & 4 Pole, Air Break Fixed MCCB conforms to IS/ IEC 60947-2 with trip free mechanism, current limiting
type with Thermal Magnetic / Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum 2NO+2NC potential
free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used as Outgoing(s), shall
have enclosure dimensions- 300(H) x 500(W) x 600 (D) & following technical features:

1.16a 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 14,110 3,500 17,610 18.00% 20,780
=100% of Icu), TM release

1.16b 3 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 21,935 3,500 25,435 18% 30,013
=100% of Icu), Microprocessor release

1.16c 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 12,046 3,500 15,546 18% 18,344
=100% of Icu), TM release

1.16d 3 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 20,281 3,500 23,781 18% 28,062
=100% of Icu), Microprocessor release

1.16e 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 11,715 3,500 15,215 18% 17,954
=100% of Icu), TM release

1.16f 3 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 20,281 3,500 23,781 18% 28,062
=100% of Icu), Microprocessor release

1.16g 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 16,644 3,500 20,144 18% 23,770
=100% of Icu), TM release

1.16h 4 Pole, MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics No. 25,564 3,500 29,064 18% 34,296
=100% of Icu), Microprocessor release

1.16i 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 13,574 3,500 17,074 18% 20,147
=100% of Icu), TM release

1.16j 4 Pole, MCCB with Breaking Capacity of Icu=36 KA at 415V (Ics No. 23,045 3,500 26,545 18% 31,323
=100% of Icu), Microprocessor release

1.16k 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 13,078 3,500 16,578 18% 19,562
=100% of Icu), TM release
1.16l 4 Pole, MCCB with Breaking Capacity of Icu=25 KA at 415V (Ics No. 23,045 3,500 26,545 18% 31,323
=100% of Icu), Microprocessor release

1.17 Add for No Load Compansation KVAR banks (APP type) with detuned filters, MCCB, Power Contractor , Auto/ manual control with
switching on delay timer, housed in lower most compartment of incomer/ buscoupler module(s). KVAR bank, selected based on kva
rating of associated transformer(s), shall be of following capacity.

1.17a 125 kVAR for 4000A Incomer- approx 5% kVAR of 2500 kVA No. 43,781 3,200 46,981 18% 55,438
Transformer rating
1.17b 100 kVAR for 3200A Incomer- approx 5% kVAR of 2000 kVA No. 34,280 3,200 37,480 18% 44,226
Transformer rating
1.17c 80 kVAR for 2500A Incomer - approx 5% kVAR of 1600 kVA No. 27,125 3,200 30,325 18% 35,784
Transformer rating
1.17d 62.5 kVAR for 2000A Incomer- approx 5% kVAR of 1250 kVA No. 20,959 3,200 24,159 18% 28,508
Transformer rating
1.17e 50 kVAR for 1600A Incomer - approx 5% kVAR of 1000 kVA No. 16,581 3,200 19,781 18% 23,342
Transformer rating
1.17f 40 kVAR for 1250A Incomer - approx 5% kVAR of 800 kVA No. 13,115 3,200 16,315 18% 19,252
Transformer rating
1.17g 31.5 kVAR for 1000A Incomer - approx 5% kVAR of 630 kVA No. 10,516 3,200 13,716 18% 16,185
Transformer rating

Page 121 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.17h 25 kVAR for 800A Incomer- approx. 5% kVAR of 500 kVA No. 8,272 3,200 11,472 18% 13,537
Transformer rating
1.17i 20 kVAR for 630A Incomer- approx. 5% kVAR of 400 kVA No. 6,573 3,200 9,773 18% 11,532
Transformer rating
1.17j 15 kVAR for 500A Incomer- approx. 5% kVAR of 315 kVA No. 4,941 3,200 8,141 18% 9,606
Transformer rating
1.17k 12.5 kVAR for 400A Incomer- approx 5% kVAR of 250 kVA No. 4,090 3,200 7,290 18% 8,602
Transformer rating
1.17l 10 kVAR for 320A Incomer - approx 5% kVAR of 200 kVA No. 3,443 3,200 6,643 18% 7,839
Transformer rating.
1.17m 8 kVAR for 250A Incomer- approx. 5% kVAR of 160 kVA Transformer No. 2,695 3,200 5,895 18% 6,956
rating
1.17n 6.25 KVAR for 200A Incomer- approx. 5% kVAR of 125 kVA No. 2,147 3,200 5,347 18% 6,309
Transformer rating
1.17o 5 kVAR for 160A Incomer- approx. 5% kVAR of 100 kVA Transformer No. 1,721 3,200 4,921 18% 5,807
rating
1.17p 3 KVAR for 125A Incomer- approx. 5% kVAR of 63 kVA Transformer No. 1,035 3,200 4,235 18% 4,997
rating
Part-2

1.18 Add for providing indicating & measuring instruments complete with accessories, associated wiring & controls of following type & rating

1.18a R, Y & B Phase Indicating Lamps (63.5 / 110 / 230V AC) for Incoming No. 466 122 588 18% 694
module(s)

1.18b On/ Off/ Trip, spring charged , trip circuit healthy, Control Supply ON/ No. 512 122 634 18% 748
Healthy indicating lamps(24 / 110V DC or 110V AC) for ACB
controlled Incomming/ Buscoupler module(s).

1.18c On/ Off/ Trip, spring charged , trip circuit healthy indicating lamps (24- No. 512 122 634 18% 748
110V AC / DC) for ACB controlled Outgoing module(s).

1.18d On/ Off/ Trip, Control Supply ON/ Healthy Indicating lamps (24 / 110V No. 512 122 634 18% 748
DC or 110V AC) for MCCB controlled Incomming/ Buscoupler
module(s).

1.18e On/ Off/ Trip Indicating lamps(110 / 230V AC) for MCCB controlled No. 251 122 373 18% 440
Outgoing module(s).
1.18f 3 Ph, 4Wire Multifunction Meter, Class 1.0 or better, Flush Mounting- No. 7,731 140 7,871 18% 9,288
96 x 96 mm with RS 485 communication port for Incoming(s)/
Outgoings(s), as required.

1.18g AC Ameter, Analogue Type(96 x 96) & ASS for Incoming(s)/ No. 838 140 978 18% 1,154
Outgoings(s), as required.
1.18h AC Ameter, Analogue Type(144 x144) & ASS for Incoming(s)/ No. 1,616 140 1,756 18% 2,072
Outgoing(s), as required.
1.18i AC Ameter, Digital Type(96 x 96) with inbuilt ASS for Incoming(s)/ No. 1,616 140 1,756 18% 2,072
Outgoings(s), as required.

1.18j AC Voltmeter, Analogue Type(96 x 96) & VSS for Incoming(s)/ No. 838 140 978 18% 1,154
Outgoings(s), as required.

1.18k AC Voltmeter, Analogue Type(144 x 144) & VSS for Incoming(s)/ No. 1,616 140 1,756 18% 2,072
Outgoings(s), as required.

1.18l AC Volt meter, Digital Type(96 x 96) with inbuilt VSS for Incoming(s)/ No. 838 140 978 18% 1,154
Outgoings(s), as required.

1.18m Local/ Remote Selector Switch for ACB controlled Incommer/ Bus No. 433 140 573 18% 676
Coupler / Outgoings modules, as required.

1.18n TNC Switch for ACB controlled Incommer/ Bus Coupler / Outgoings No. 1,444 235 1,679 18% 1,981
modules, as required.

1.19 Add for providing instrument Transformers complete with accessories, associated wiring & controls, of following type & rating

1.19a Cast rasin insulated Current Transformer, Single Core with CTR 50- No. 838 145 983 18% 1,160
75/1A or 5A, 5-15VA, Class 1.0 or better for metering, as applicable

1.19b Resin Cast insulated Current Transformer, Double Core with CTR 50- No. 1,108 190 1,298 18% 1,532
75/1A or 5A, 5-15VA, Class 1.0 or better for metering/ 5P10 or better
for protection, as applicable

1.19c Resin Cast insulated Current Transformer, Single Core with CTR 100- No. 1,108 190 1,298 18% 1,532
150/1A or 5A, 5-15VA, Class 1.0 or better for metering, as applicable

Page 122 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.19d Resin Cast insulated Current Transformer, Double Core with CTR No. 1,108 190 1,298 18% 1,532
100-150/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering/ protection,
as applicable

1.19e Resin Cast insulated Current Transformer, Single Core with CTR 200- No. 1,253 190 1,443 18% 1,703
300/1A or 5A, 5-15VA, Class 1.0 for metering, as applicable

1.19f Resin Cast insulated Current Transformer, Double Core with CTR No. 1,281 190 1,471 18% 1,736
200-300/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering/ protection,
as applicable

1.19g Resin Cast insulated Current Transformer, Single Core with CTR 400- No. 1,490 190 1,680 18% 1,982
1000/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering, as applicable

1.19h Resin Cast insulated Current Transformer, Double Core with CTR No. 1,677 190 1,867 18% 2,203
400-1000/1A or 5A, 5-15VA, Class 1.0/ 5P10 for metering/ protection,
as applicable

1.19i Resin Cast insulated Current Transformer, Single Core with CTR No. 1,770 190 1,960 18% 2,313
1200-1500/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering, as
applicable

1.19j Resin Cast insulated Current Transformer, Double Core with CTR No. 1,770 190 1,960 18% 2,313
1200-1500/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering/
protection, as applicable

1.19k Resin Cast insulated Current Transformer, Single Core with CTR No. 2,282 190 2,472 18% 2,917
1600- 3000/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering, as
applicable

1.19l Resin Cast insulated Current Transformer, Double Core with CTR No. 2,282 255 2,537 18% 2,994
1600-3000/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering/
protection, as applicable

1.19m Resin Cast insulated Current Transformer, Single Core with CTR No. 2,609 295 2,904 18% 3,427
3200- 4000/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering, as
applicable

1.19n Resin Cast insulated Current Transformer, Double Core with CTR No. 2,584 295 2,879 18% 3,397
3200-4000/1A or 5A, 5-15VA, Class 1.0 / 5P10 for metering/
protection, as applicable

1.19o Resin Cast insulated Voltage Transformer, Single Core with PTR 415/ No. 13,553 735 14,288 18% 16,860
root3/ 110/ root3, 50VA, Class 1.0 or better for metering, as
applicable
1.19p Resin Cast insulated Voltage Transformer, Double Core with PTR No. 13,553 735 14,288 18% 16,860
415/ root3/ 110V/ root3/ 110V/ root3, 50 VA, Class 1.0 or better for
metering / 3P for protection, as applicabke

1.20 Add for providing LT Single Phase Control Transformers(Tape wound, dry type, low reactance with good regulation at short time loads to provide
control suppply voltages for control circuits of AC Motor Starters and/ or auxiliary euipment not intended for direct connection to the main circuit)
complete with accessories, associated wiring & controls, of following type & rating
1.20a 3500 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 15,192 1,445 16,637 18% 19,632

1.20b 3500 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 15,192 1,445 16,637 18% 19,632

1.20c 3500 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 15,192 1,445 16,637 18% 19,632

1.20d 3000 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 13,097 1,445 14,542 18% 17,160

1.20e 3000 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 13,097 1,445 14,542 18% 17,160

1.20f 3000 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 13,097 1,445 14,542 18% 17,160

1.20g 2500 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 11,085 1,445 12,530 18% 14,785

1.20h 2500 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 11,085 1,445 12,530 18% 14,785

1.20i 2500 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 11,085 1,445 12,530 18% 14,785

1.20j 2000 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 10,386 1,160 11,546 18% 13,624

1.20k 2000 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 10,386 1,160 11,546 18% 13,624

Page 123 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
1.20l 2000 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 10,386 1,160 11,546 18% 13,624

1.20m 1500 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 8,803 1,160 9,963 18% 11,756

1.20n 1500 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 8,803 1,160 9,963 18% 11,756

1.20o 1500 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 8,803 1,160 9,963 18% 11,756

1.20p 1000 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 6,055 1,160 7,215 18% 8,514

1.20q 1000 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 6,055 1,160 7,215 18% 8,514

1.20r 1000 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 6,055 1,160 7,215 18% 8,514

1.20s 750 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 4,634 755 5,389 18% 6,359

1.20t 750 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 4,634 755 5,389 18% 6,359

1.20u 750 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 4,634 755 5,389 18% 6,359

1.20v 630 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 4,472 755 5,227 18% 6,168

1.20w 630 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 4,100 755 4,855 18% 5,729

1.20x 630 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 3,690 755 4,445 18% 5,245

1.20y 500 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 3,866 755 4,621 18% 5,453

1.20z 500 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 3,479 755 4,234 18% 4,996

1.20aa 500 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 3,131 530 3,661 18% 4,320
1.20ab 400 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 3,261 530 3,791 18% 4,473
1.20ac 400 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 3,060 530 3,590 18% 4,236
1.20ad 400 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 2,754 530 3,284 18% 3,875
1.20ae 350 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 2,980 530 3,510 18% 4,142
1.20af 350 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 2,809 530 3,339 18% 3,940
1.20ag 350 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 2,527 530 3,057 18% 3,607
1.20ah 300 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 2,766 530 3,296 18% 3,889
1.20ai 300 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 2,490 530 3,020 18% 3,564

1.20aj 300 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 2,241 530 2,771 18% 3,270

1.20ak 250 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 2,515 530 3,045 18% 3,593

1.20al 250 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 2,264 530 2,794 18% 3,297

1.20am 250 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 2,037 530 2,567 18% 3,029
1.20an 200 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 2,096 510 2,606 18% 3,075
1.20ao 200 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 2,096 510 2,606 18% 3,075

1.20ap 200 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 1,886 510 2,396 18% 2,827

1.20aq 150 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 1,770 510 2,280 18% 2,690

1.20ar 150 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 1,593 510 2,103 18% 2,482

1.20as 150 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 1,434 510 1,944 18% 2,294

1.20at 100 VA , 415 / 240V AC with Tapping ± 5% insteps of 2.5% No. 1,285 510 1,795 18% 2,118

1.20au 100 VA , 415 / 110V AC with Tapping ± 5% insteps of 2.5% No. 1,285 510 1,795 18% 2,118

1.20av 100 VA , 415 / 24V AC with Tapping ± 5% insteps of 2.5% No. 1,216 510 1,726 18% 2,037

46 HFSR (Harmonic Free Series Reactor) soft starter

Supply, installation, testing & commissioning HFSR (Harmonic Free Series Reactor) HV soft starter panel suitable for 3-phase squirrel cage induction
motor & provided with built in bypass terminal for pump control application by torque control method as per tender specification.
Soft Starter shall be operated on 3-phase, 50 Hz, fault Level 3KA for 1Sec., with Copper bus bar & enclosure fabricated from 2mm CRCA sheet steel,
solidly earthed neutral system earthing complete with following associated necessary equipments & accessories.

46.1 Voltage level (KV) & KW Rating Line Side HFSR Soft Starter

a 3.3/6.6 315 No 335,340 18,180 353,520 18% 417,154

Page 124 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
b 3.3/6.6 355 No 344,655 18,180 362,835 18% 428,145

c 3.3/6.6 400 No 353,970 18,180 372,150 18% 439,137

d 3.3/6.6 450 No 363,285 18,180 381,465 18% 450,129

e 3.3/6.6 500 No 372,600 18,180 390,780 18% 461,120

11 463,887 18,180 482,067 18% 568,839

f 3.3/6.6 560 No 381,915 18,180 400,095 18% 472,112

11 470,408 18,180 488,588 18% 576,534

g 3.3/6.6 600 No 395,888 18,180 414,068 18% 488,600

11 484,380 18,180 502,560 18% 593,021

h 3.3/6.6 650 No 395,888 18,180 414,068 18% 488,600

11 484,380 18,180 502,560 18% 593,021

i 3.3/6.6 710 No 400,545 18,180 418,725 18% 494,096

11 503,010 18,180 521,190 18% 615,004

j 3.3/6.6 750 No 400,545 18,180 418,725 18% 494,096

11 503,010 18,180 521,190 18% 615,004

k 3.3/6.6 800 No 405,203 18,180 423,383 18% 499,592

11 512,325 18,180 530,505 18% 625,996

l 3.3/6.6 850 No 405,203 18,180 423,383 18% 499,592

11 512,325 18,180 530,505 18% 625,996

m 3.3/6.6 900 No 409,860 18,180 428,040 18% 505,087

11 516,983 18,180 535,163 18% 631,492

n 3.3/6.6 950 No 409,860 18,180 428,040 18% 505,087

11 516,983 18,180 535,163 18% 631,492

o 3.3/6.6 1000 No 419,175 18,180 437,355 18% 516,079

11 521,640 18,180 539,820 18% 636,988

46.2 Voltage level (KV) & KW Rating Neutral Side HFSR Soft Starter

a 3.3/6.6 315 No 307,395 18,180 325,575 18% 384,179

b 3.3/6.6 355 No 316,710 18,180 334,890 18% 395,170

c 3.3/6.6 400 No 326,025 18,180 344,205 18% 406,162

d 3.3/6.6 450 No 335,340 18,180 353,520 18% 417,154

e 3.3/6.6 500 No 344,655 18,180 362,835 18% 428,145

11 435,942 18,180 454,122 18% 535,864

f 3.3/6.6 560 No 353,970 18,180 372,150 18% 439,137

11 442,463 18,180 460,643 18% 543,559

g 3.3/6.6 600 No 367,943 18,180 386,123 18% 455,625

11 456,435 18,180 474,615 18% 560,046

h 3.3/6.6 650 No 367,943 18,180 386,123 18% 455,625

11 456,435 18,180 474,615 18% 560,046

i 3.3/6.6 710 No 372,600 18,180 390,780 18% 461,120

11 475,065 18,180 493,245 18% 582,029

Page 125 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
j 3.3/6.6 750 No 372,600 18,180 390,780 18% 461,120

11 475,065 18,180 493,245 18% 582,029

k 3.3/6.6 800 No 377,258 18,180 395,438 18% 466,617

11 484,380 18,180 502,560 18% 593,021

l 3.3/6.6 850 No 377,258 18,180 395,438 18% 466,617

11 484,380 18,180 502,560 18% 593,021

m 3.3/6.6 900 No 381,915 18,180 400,095 18% 472,112

11 489,038 18,180 507,218 18% 598,517

n 3.3/6.6 950 No 381,915 18,180 400,095 18% 472,112

11 489,038 18,180 507,218 18% 598,517

o 3.3/6.6 1000 No 391,230 18,180 409,410 18% 483,104

11 493,695 18,180 511,875 18% 604,013

47 Flux Compensated Magnetic Amplifier (FCMA) Soft Starter

Supply, installation, testing & commissioning FCMA (Flux compensated magnetic amplifier) HV soft starter panel suitable for 3-phase squirrel cage
induction motor & provided with built in bypass terminal for pump control application by torque control method as per tender specification.
Soft Starter shall be operated on 3-phase, 50 Hz, fault Level 3KA for 1Sec., with Copper bus bar & enclosure fabricated from 2mm CRCA sheet steel,
solidly earthed neutral system earthing complete with following associated necessary equipments & accessories.

47.1 Voltage level (KV) & Line Side FCMA Soft Starter
KW Rating
a 3.3 315 KW No 462,645 18,180 480,825 18% 567,374

6.6 465,750 18,180 483,930 18% 571,037

11 No 522,675 18,180 540,855 18% 638,209

b 3.3 355 KW 462,645 18,180 480,825 18% 567,374

6.6 No 465,750 18,180 483,930 18% 571,037

11 527,850 18,180 546,030 18% 644,315

c 3.3 400 KW No 485,415 18,180 503,595 18% 594,242

6.6 476,100 18,180 494,280 18% 583,250

11 No 533,025 18,180 551,205 18% 650,422

d 3.3 450 KW 485,415 18,180 503,595 18% 594,242

6.6 No 476,100 18,180 494,280 18% 583,250

11 538,200 18,180 556,380 18% 656,528

e 3.3 500 KW No 486,450 18,180 504,630 18% 595,463

6.6 507,150 18,180 525,330 18% 619,889

11 No 538,200 18,180 556,380 18% 656,528

f 3.3 560 KW 500,940 18,180 519,120 18% 612,562

6.6 No 507,150 18,180 525,330 18% 619,889

11 538,200 18,180 556,380 18% 656,528

g 3.3 630 KW No 550,620 18,180 568,800 18% 671,184

6.6 556,830 18,180 575,010 18% 678,512

11 No 548,550 18,180 566,730 18% 668,741

h 3.3 710 KW 584,775 18,180 602,955 18% 711,487

6.6 No 556,830 18,180 575,010 18% 678,512

11 569,250 18,180 587,430 18% 693,167

Page 126 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
i 3.3 800 KW No 588,915 18,180 607,095 18% 716,372

6.6 593,055 18,180 611,235 18% 721,257

11 No 569,250 18,180 587,430 18% 693,167

j 3.3 900 KW 595,125 18,180 613,305 18% 723,700

6.6 No 593,055 18,180 611,235 18% 721,257

11 579,600 18,180 597,780 18% 705,380

k 3.3 1000 KW No 602,370 18,180 620,550 18% 732,249

6.6 593,055 18,180 611,235 18% 721,257

11 No 595,125 18,180 613,305 18% 723,700

l 3.3 1120 KW 609,615 18,180 627,795 18% 740,798

6.6 No 621,000 18,180 639,180 18% 754,232

11 631,350 18,180 649,530 18% 766,445

m 3.3 1250 KW No 615,825 18,180 634,005 18% 748,126

6.6 621,000 18,180 639,180 18% 754,232

11 No 641,700 18,180 659,880 18% 778,658

n 3.3 1400 KW 642,735 18,180 660,915 18% 779,880

6.6 No 639,630 18,180 657,810 18% 776,216

11 683,100 18,180 701,280 18% 827,510

o 3.3 1500 KW No 666,540 18,180 684,720 18% 807,970

6.6 683,100 18,180 701,280 18% 827,510

11 No 714,150 18,180 732,330 18% 864,149

p 3.3 1600 KW 667,575 18,180 685,755 18% 809,191

6.6 No 695,520 18,180 713,700 18% 842,166

11 724,500 18,180 742,680 18% 876,362

47.2 Voltage level (KV) & KW Rating Neutral Side FCMA Soft Starter

a 3.3 315 KW No 429,525 18,180 447,705 18% 528,292

6.6 434,700 18,180 452,880 18% 534,398

11 No 465,750 18,180 483,930 18% 571,037

b 3.3 355 KW 429,525 18,180 447,705 18% 528,292

6.6 No 434,700 18,180 452,880 18% 534,398

11 465,750 18,180 483,930 18% 571,037

c 3.3 400 KW No 450,225 18,180 468,405 18% 552,718

6.6 445,050 18,180 463,230 18% 546,611

11 No 481,275 18,180 499,455 18% 589,357

d 3.3 450 KW 450,225 18,180 468,405 18% 552,718

6.6 No 445,050 18,180 463,230 18% 546,611

11 481,275 18,180 499,455 18% 589,357

e 3.3 500 KW No 453,330 18,180 471,510 18% 556,382

6.6 476,100 18,180 494,280 18% 583,250

11 No 507,150 18,180 525,330 18% 619,889

Page 127 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
f 3.3 560 KW 465,750 18,180 483,930 18% 571,037

6.6 No 476,100 18,180 494,280 18% 583,250

11 507,150 18,180 525,330 18% 619,889

g 3.3 630 KW No 507,150 18,180 525,330 18% 619,889

6.6 507,150 18,180 525,330 18% 619,889

11 No 527,850 18,180 546,030 18% 644,315

h 3.3 710 KW 543,375 18,180 561,555 18% 662,635

6.6 No 524,745 18,180 542,925 18% 640,652

11 548,550 18,180 566,730 18% 668,741

i 3.3 800 KW No 555,795 18,180 573,975 18% 677,291

6.6 560,970 18,180 579,150 18% 683,397

11 No 548,550 18,180 566,730 18% 668,741

j 3.3 900 KW 560,970 18,180 579,150 18% 683,397

6.6 No 560,970 18,180 579,150 18% 683,397

11 558,900 18,180 577,080 18% 680,954

k 3.3 1000 KW No 569,250 18,180 587,430 18% 693,167

6.6 560,970 18,180 579,150 18% 683,397

11 No 569,250 18,180 587,430 18% 693,167

l 3.3 1120 KW 574,425 18,180 592,605 18% 699,274

6.6 No 584,775 18,180 602,955 18% 711,487

11 610,650 18,180 628,830 18% 742,019

m 3.3 1250 KW No 584,775 18,180 602,955 18% 711,487

6.6 584,775 18,180 602,955 18% 711,487

11 No 621,000 18,180 639,180 18% 754,232

n 3.3 1400 KW 611,685 18,180 629,865 18% 743,241

6.6 No 607,545 18,180 625,725 18% 738,356

11 662,400 18,180 680,580 18% 803,084

o 3.3 1500 KW No 634,455 18,180 652,635 18% 770,109

6.6 654,120 18,180 672,300 18% 793,314

11 No 693,450 18,180 711,630 18% 839,723

p 3.3 1600 KW 636,525 18,180 654,705 18% 772,552

6.6 No 662,400 18,180 680,580 18% 803,084

11 703,800 18,180 721,980 18% 851,936

48 11kV Ring Main Unit (RMU)

1 Supply, Installation, testing & commissioning Indoor type 11 KV, 630 No 745,200 22,220 767,420 18% 905,556
Amp., 21kA for 3 sec. SF6 type extensible and motorized 5 way
smart Ring Main Unit (RMU) complete with (2 VCB + 3 LBS) with
FRTU and FPI with IP Protection, as per IS

2 Supply, Installation, testing & commissioning Indoor type 11 KV, 630 No 605,475 22,220 627,695 18% 740,680
Amp., 21kA for 3 sec. SF6 type extensible and motorized 4 way smart
Ring Main Unit (RMU) complete with (2 VCB + 2 LBS) with FRTU and
FPI with IP Protection, as per IS

Page 128 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
3 Supply, Installation, testing & commissioning Indoor type 11 KV, 630 No 465,750 22,220 487,970 18% 575,805
Amp., 21kA for 3 sec. SF6 type extensible and motorized 3 way smart
Ring Main Unit (RMU) complete with (1 VCB + 2 LBS) with FRTU and
FPI with IP Protection, as per IS

4 Supply, Installation, testing & commissioning Indoor type 11 KV, 630 No 605,475 22,220 627,695 18% 740,680
Amp., 21kA for 3 sec. SF6 type extensible and motorized 3 way smart
Ring Main Unit (RMU) complete with (3 VCB) with FRTU and FPI with
IP Protection, as per IS

5 Supply, Installation, testing & commissioning Indoor type 11 KV, 630 No 326,025 22,220 348,245 18% 410,929
Amp., 21kA for 3 sec. SF6 type extensible and motorized one way
smart Ring Main Unit (RMU) complete with LB and with FPI with IP
Protection, as per IS

6 Supply, Installation, testing & commissioning Indoor type 11 KV, 630 No 419,175 22,220 441,395 18% 520,846
Amp., 21kA for 3 sec. SF6 type extensible and motorized 3 way smart
Ring Main Unit (RMU) complete with (1 VCB + 2 LBS) with FRTU and
FPI with IP Protection, as per IS

7 Supply, Installation, testing & commissioning Outdoor type 11 KV, No 773,145 22,220 795,365 18% 938,531
630 Amp., 21kA for 3 sec. SF6 type non extensible and motorized 5
way smart Ring Main Unit (RMU) complete with (2 VCB + 3 LBS) with
FRTU and FPI with IP Protection, as per IS

8 Supply, Installation, testing & commissioning Outdoor type 11 KV, No 698,625 22,220 720,845 18% 850,597
630 Amp., 21kA for 3 sec. SF6 type extensible and motorized 4 way
smart Ring Main Unit (RMU) complete with (2 VCB + 2 LBS) with
FRTU and FPI with IP Protection, as per IS

9 Supply, Installation, testing & commissioning Outdoor type 11 KV, No 698,625 22,220 720,845 18% 850,597
630 Amp., 21kA for 3 sec. SF6 type extensible and motorized 3 way
smart Ring Main Unit (RMU) complete with (3 VCB) with FRTU and
FPI with IP Protection, as per IS

10 Supply, Installation, testing & commissioning Outdoor type 11 KV, No 512,325 22,220 534,545 18% 630,763
630 Amp., 21kA for 3 sec. SF6 type extensible and motorized 3 way
smart Ring Main Unit (RMU) complete with (1 VCB + 2 LBS) with
FRTU and FPI with IP Protection, as per IS

11 Supply, Installation, testing & commissioning Outdoor type 11 KV, No 344,655 22,220 366,875 18% 432,913
630 Amp. 21kA for 3 sec. SF6 type extensible and motorized one way
smart Ring Main Unit (RMU) complete with LB and with FPI with IP
Protection, as per IS

12 Supply, Installation, testing & commissioning Outdoor type 11 KV, No 419,175 22,220 441,395 18% 520,846
630 Amp., 21kA for 3 sec. SF6 type extensible and motorized one
way smart Ring Main Unit (RMU) complete with VCB and FPI with IP
Protection, as per IS

49 Servo Controlled Automatic Voltage Stabilizer

Providing, erecting Servo Controlled Automatic Voltage stabilizer


suitable for out put voltage of 415 Volt +/-1%, 3 Ph, 50 Hz, with
copper wound transformer (air/oil cooled) as mentioned below. The
stabilizer shall function satisfactorily even if incoming supply is
unbalanced between phases within range of 10%. The stabilizer
should be constructed in cubical box, with bi-directional wheels for
easy handling, necessary monitors and user's controls on front panel
such
as indication, alarm, volt meter and selector switch for measuring
input and out put voltage, Auto/Manual selector switch, Raise/Low
push buttons etc. Suitable capacity termination strips and bus bars for
incoming and out going cable should be provided. All three phases
shall be independently monitored and corrected. Following protections
and indications shall be incorporated
Over Voltage / Under Voltage, Single Phasing,Cut off contactor with
electronic output sensing unit
Servo Controlled Automatic Voltage Stabilizer (Out put 415 +/-1%)
Input 220 to 460 Volt

2 3 kVA Air Cooled No 52,981 233 53,214 18.0% 62,793

3 5 kVA Air Cooled No 61,346 303 61,649 18% 72,746

4 7.5 kVA Air Cooled No 69,148 464 69,612 18% 82,142

5 10 kVA Air Cooled No 90,553 698 91,251 18% 107,676

Page 129 of 166 S.O.R. Mech 2019-20


Section- "E"

Approved Rate for 2019-20

Rates exclusive of GST Prevailing Rates


Sr. No. Description of Item Unit
rates of GST inclusive of
Erection & GST
Supply Total
Overhead
6 12.5 kVA Air Cooled No 99,535 929 100,464 18% 118,548

7 15 kVA Air Cooled No 108,516 929 109,445 18% 129,145

8 20 kVA Air Cooled No 118,192 1,159 119,351 18% 140,834

9 25 kVA Air Cooled No 130,078 1,392 131,470 18% 155,135

10 30 kVA Air Cooled No 158,175 1,624 159,799 18% 188,563

11 40 kVA Air Cooled No 173,564 1,855 175,419 18% 206,994

12 50 kVA Air Cooled No 234,622 1,855 236,477 18% 279,043

13 60 kVA Air Cooled No 284,452 1,855 286,307 18% 337,842

14 75 kVA Air Cooled No 297,443 1,855 299,298 18% 353,172

15 100 kVA Air Cooled No 335,170 2,550 337,720 18% 398,510

16 125 kVA Air Cooled No 416,346 3,018 419,364 18% 494,850

Page 130 of 166 S.O.R. Mech 2019-20


Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
1 2 3 7 8 9 10
1 Full Bore Electromagnetic Flow Meter- Inbuilt Battery Power operated

Design, Supply, Installation, Testing, Commissioning of Full Bore Electromagnetic flow meter with factory calibration,
Inbuilt Battery Power Operated, flanged connection, Flow sensor, Indicator, transmitter and totaliser with all accessories
viz. surge arrestor, associated cables, cabinets, hardwares, etc complete as per following specifications:
I Flow Meter/ Sensor:

DC pulsed type, IP 68 Protection, Flanged process connection as per IS 1538 or equivalent standard, SS304/ Metallic Alloy
Flow Tube, SS316/ SS 316 L/ Hastelloy Sensor, SS316/ Hastelloy Grounding Ring/ Inbuilt Grounding Electrode,
Neoprene/Polyurethane/ Hard Rubber/ Rilsan lining, SS304/ Die Cast Aluminium/ Carbon steel with Anticorrosive Paint
Coil Housing with Junction Box, CS flanges.
II Flow Transmitter/ Converter ( Remote Field Mounted):

Microprocessor based, Modular design, 2 line LCD for indication of actual flow rate, forward, reverse, sum totaliser display,
±0.5% accuracy at 0.3 to 4 m/sec velocity,
one scalable pulse/ one status, one Modbus output, one GPRS/ GSM output, IP 67 protection, Die cast aluminium/
polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt EEPROM and Data Logger,
20 meters cable length for sensor to transmitter communication, Minimum 5 years battery lifetime, 3.6 VDC Non
Rechargeable Lithium-thionyl chloride/ Ni-Cd high power batteries, Hourly Basis Worldwide transmission of measured data
and events via e‐mail and SMS by integrated GSM/GPRS modem, Reliable data storage facility through integrated SD card
etc alongwith wall mounted/ stand mounted cabinet.

1A Full Bore Electromagnetic Flow Meter (Inbuilt Battery Power Operated)- PN 10

1 25mm Nominal Bore No 50,000 7,908 57,908 18% 68,331

2 40mm Nominal Bore No 54,000 8,101 62,101 18% 73,279

3 50mm Nominal Bore No 57,500 8,287 65,787 18% 77,629

4 65mm Nominal Bore No 74,750 8,583 83,333 18% 98,333

5 80mm Nominal Bore No 92,000 8,813 100,813 18% 118,959

6 100mm Nominal Bore No 100,000 9,109 109,109 18% 128,749

7 150mm Nominal Bore No 105,000 10,377 115,377 18% 136,145

8 200mm Nominal Bore No 130,000 13,211 143,211 18% 168,989

9 250mm Nominal Bore No 162,500 14,419 176,919 18% 208,764

10 300mm Nominal Bore No 195,000 15,688 210,688 18% 248,612

11 350mm Nominal Bore No 227,500 17,078 244,578 18% 288,602

12 400mm Nominal Bore No 260,000 18,633 278,633 18% 328,787

13 450mm Nominal Bore No 270,000 24,706 294,706 18% 347,753

14 500mm Nominal Bore No 300,000 28,042 328,042 18% 387,090

15 600mm Nominal Bore No 360,000 31,421 391,421 18% 461,877

1B Full Bore Electromagnetic Flow Meter (Inbuilt Battery Power Operated)- PN 16.
For PN 16 rating, 10% rise in rate to be considere on rate of PN 10 rating Item (Item No. 1A)

1C Full Bore Electromagnetic Flow Meter (Inbuilt Battery Power Operated)- PN 25


For PN 25 rating, 15% rise in rate to be considere on rate of PN 10 rating Item (Item No. 1A)
2 Full Bore Electromagnetic Flow Meter- Regular Power operated

Design, Supply, Installation, Testing, Commissioning of Full Bore Electromagnetic flow meter with factory calibrated,
Regular Power Operated, flanged connection, Flow sensor, Indicator, transmitter and totaliser with all accessories viz.
surge arrestor, associated cables, cabinets, hardwares, etc complete as per following specifications:

S.O.R. Mech 2019-20


Page 131 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
I Flow Meter/ Sensor:

DC pulsed type, IP 68 Protection, Flanged process connection as per IS 1538 or equivalent standard, SS304/ Metallic Alloy
Flow Tube, SS316/ SS 316 L/ Hastelloy Sensor, SS316/ Hastelloy Grounding Ring/ Inbuilt Grounding Electrode,
Neoprene/ Polyurethane/ Hard Rubber/ Rilsan lining, SS304/ Die Cast Aluminium/ Carbon steel with Anticorrosive Paint
Coil Housing with Junction Box, CS flanges.
II Flow Transmitter/ Converter ( Remote Field Mounted):

Microprocessor based, Modular design, 2 line LCD for indication of actual flow rate, forward, reverse, sum totaliser display,
±0.5% accuracy at 0.3 to 4 m/sec velocity, 4 to 20 mA with HART/Modbus output, one scalable pulse, one status output,
IP 67 protection, Die cast aluminium/ polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass window
enclosure, Inbuilt EEPROM and Data Logger, 20 meters cable length for sensor to transmitter communication etc
alongwith wall mounted/ stand mounted cabinet.
2A Full Bore Electromagnetic Flow Meter (Regular Power Operated)- PN 10

1 25mm Nominal Bore No 40,150 3,593 43,743 18% 51,617

2 40mm Nominal Bore No 47,054 3,593 50,647 18% 59,764

3 50mm Nominal Bore No 49,832 3,593 53,425 18% 63,042

4 65mm Nominal Bore No 53,787 3,593 57,380 18% 67,708

5 80mm Nominal Bore No 58,244 3,593 61,837 18% 72,968

6 100mm Nominal Bore No 62,244 3,593 65,837 18% 77,688

7 150mm Nominal Bore No 78,605 4,367 82,972 18% 97,907

8 200mm Nominal Bore No 101,426 4,623 106,049 18% 125,138

9 250mm Nominal Bore No 111,833 5,368 117,201 18% 138,297

10 300mm Nominal Bore No 127,851 6,571 134,422 18% 158,618

11 350mm Nominal Bore No 177,670 8,230 185,900 18% 219,362

12 400mm Nominal Bore No 201,632 9,488 211,120 18% 249,122

13 450mm Nominal Bore No 215,321 10,860 226,181 18% 266,894

14 500mm Nominal Bore No 251,759 11,365 263,124 18% 310,486

15 550mm Nominal Bore No 278,815 12,382 291,197 18% 343,612

16 600mm Nominal Bore No 290,402 12,820 303,222 18% 357,802

17 700mm Nominal Bore No 312,395 13,631 326,026 18% 384,711

18 750mm Nominal Bore No 334,376 14,455 348,831 18% 411,620

19 800mm Nominal Bore No 375,025 16,001 391,026 18% 461,411

20 900mm Nominal Bore No 427,360 17,965 445,325 18% 525,484

21 1000mm Nominal Bore No 457,503 20,955 478,458 18% 564,581

22 1100mm Nominal Bore No 536,819 25,300 562,119 18% 663,300

23 1200mm Nominal Bore No 585,620 27,600 613,220 18% 723,600

24 1300mm Nominal Bore No 634,422 29,900 664,322 18% 783,900

S.O.R. Mech 2019-20


Page 132 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
25 1400mm Nominal Bore No 683,224 32,200 715,424 18% 844,200

26 1500mm Nominal Bore No 732,025 34,500 766,525 18% 904,500

27 1600mm Nominal Bore No 780,827 36,800 817,627 18% 964,800

28 1700mm Nominal Bore No 829,629 39,100 868,729 18% 1,025,100

29 1800mm Nominal Bore No 878,431 41,400 919,831 18% 1,085,400

30 1900mm Nominal Bore No 927,232 43,700 970,932 18% 1,145,700

31 2000mm Nominal Bore No 976,034 46,000 1,022,034 18% 1,206,000

32 2100mm Nominal Bore No 1,024,836 48,300 1,073,136 18% 1,266,300

33 2200mm Nominal Bore No 1,073,637 50,600 1,124,237 18% 1,326,600

34 2300mm Nominal Bore No 1,122,439 52,900 1,175,339 18% 1,386,900

35 2400mm Nominal Bore No 1,171,241 55,200 1,226,441 18% 1,447,200

2B Full Bore Electromagnetic Flow Meter (Regular Power Operated)- PN 16


For PN 16 rating, 10% rise in rate to be considere on rate of PN 10 rating Item (Item No. 2A)
2C Full Bore Electromagnetic Flow Meter (Regular Power Operated)- PN 25
For PN 25 rating, 15% rise in rate to be considere on rate of PN 10 rating Item (Item No. 2A)
3 Insertion Type Ultrasonic Flow Meter

Design, Supply, Installation, Testing, Commissioning of Single/ Dual/ Four Path Insertion Ultrasonic flow meter working on
transit time principle, with factory calibrated and site verification, Regular Power Operated, Flow sensor, Indicator,
transmitter and totaliser with all accessories viz. surge arrestor, associated cables, cabinets, hardwares, etc complete as
per following specifications:
I Flow Meter/ Sensor:

2/ 4/ 8 nos insertion ultrasonic type sensor ( 1/ 2/ 4 Pair) with ball valve for online removal of sensors/ any other interaction/
retraction assembly, PN 16 pressure rating, SS 316 Sensor MOC, IP 68 Protection.

II Flow Transmitter/ Converter ( Remote Field Mounted):


Microprocessor based, Modular design,
2 line LCD for indication of actual flow rate, forward, reverse, sum totaliser display,
±1% accuracy at 0.3 to 4 m/sec velocity,
4 to 20 mA with HART, one scalable pulse output,
IP 65/ 67 protection,
Die cast aluminum/ polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt EEPROM
and Data Logger,
20 meters cable length for sensor to transmitter communication.
3A Dual Path ( 4 Nos Insertion Sensor)- for pipe No 488,700 20,000 508,700 18% 600,266
size ≥ 600 mm & ≤ 800 mm
3B Four Path ( 8 Nos Insertion Sensor) - for No 705,271 46,000 751,271 18% 886,500
pipe size > 800 mm & ≤ 4000 mm

4 Clamp On Ultrasonic Flow Meter- Fixed Type

Design, Supply, Installation, Testing, Commissioning of Fixed Type, Single Path Clamp On Ultrasonic flow meter working on transit time
principle, with factory calibrated and site verification, Regular Power Operated, Flow sensor, Indicator, transmitter and totaliser with all
accessories viz. surge arrestor, associated cabled, cabinets, hardwares, etc complete as per following specifications:

I Flow Meter/ Sensor:

2 nos magnetic clamp on ultrasonic type sensor ( 1 Pair) with SS belt according to pipe size and necessary fitting assembly, ABS/
Alluminium Alloy Sensor MOC, IP 68 Protection.
II Flow Transmitter/ Converter ( Remote Field Mounted):

S.O.R. Mech 2019-20


Page 133 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
Microprocessor based, Modular design,
2 line LCD for indication of actual flow rate, forward, reverse, sum totaliser display,
±1% accuracy at 0.3 to 4 m/sec velocity,
4 to 20 mA with HART, one scalable pulse output,
IP 65/ 67 protection,
Die cast aluminum/ polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt EEPROM and Data
Logger,
20 meters cable length for sensor to transmitter communication.
4A for pipe size 15 TO 80 mm No 178,295 14,874 193,169 18% 227,939

4B for pipe size 100 TO 700 mm No 182,832 15,253 198,085 18% 233,740

4C for pipe size 750 TO 4000 mm No 185,047 15,438 200,485 18% 236,572

5 Clamp On Ultrasonic Flow Meter- Portable Type

Design, Supply, Installation, Testing, Commissioning of Portable Type, Single Path Clamp On Ultrasonic flow meter
working on transit time principle, with site verification, Inbuilt Battery Power Operated, Flow sensor and Hand Held Indicator
with all accessories viz. battery charger, associated cabled, portable case, hardwares, etc complete as per following
specifications:
I Flow Meter/ Sensor:
2 nos magnetic clamp on ultrasonic type sensor ( 1 Pair) with SS belt according to pipe size and necessary fitting assembly,
ABS/ Alluminium Alloy Sensor MOC, IP 68 Protection.

II Flow Indicator/ Converter ( Hand Held):


Microprocessor based, Modular design,
minimum 2 line LCD for indication of actual flow rate, forward, reverse, sum totaliser display,
±1% accuracy at 0.3 to 4 m/sec velocity,
RS 232 output,
IP 65/ 67 protection,
Die cast aluminum/ polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass window enclosure.
20 meters cable length for sensor to transmitter communication.
5A for pipe size 15 TO 80 mm No 161,415 13,466 174,881 18% 206,360
5B for pipe size 100 TO 700 mm No 165,952 13,845 179,797 18% 212,160
5C for pipe size 750 TO 4000 mm No 168,167 14,030 182,197 18% 214,992
6 Acoustic Doppler Type Flow Meter- Regular Power Operated

Design, Supply, Installation, Testing, Commissioning of Accoustic Doppler Type flow meter, working on transit time
principle, with site verification, Regular Power Operated, Flow sensor with Mounting Stand, Indicator, Transmitter and
totalizer with all accessories viz. associated cabled, cabinets, hardwares, etc complete as per following specifications:
I Flow Meter/ Sensor:
Accoustic Doppler type Flow Meter with real time acoustic doppler current meter with RS232/serial digital interface(SDI)-12
interface, features programmable range selection, vertical acoustic beam for water level measurement, multi cell current
profiling, integrated temperature sensor, pressure sensor, memory storage an mounting stand.
II Flow Indicator/ Converter ( Hand Held):
Microprocessor based, Modular design, Regular power Operated,
minimum 2 line LCD for indication of actual flow rate, forward, reverse, sum totaliser display,
±1% accuracy at 0.3 to 4 m/sec velocity,
One current(4-20mA) with HART output, one scalable pulse, one status output, RS 232 output,
IP 65/ 67 protection,
Die cast aluminum/ polycarbonate/ SS316 with Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt EEPROM
and Data Logger,
20 meters cable length for sensor to transmitter communication.
Instrument shall have facility to connect with GPRS/ VHF/ VSAT modem.

6A Canal Depth 3- 5 Meter and width 5 - 10 No 1,002,250 83,614 1,085,864 18% 1,281,320
meter
6B Canal Depth 3- 20 Meter and width 20 - 25 No 1,126,740 94,000 1,220,740 18% 1,440,473
meter
7 Water Meters (Multijet/ Woltman Type):

S.O.R. Mech 2019-20


Page 134 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
7.1 Horizontal Inferential Multijet Type Water Meter- AMR Compatible:
Design, Supply, Installation, Testing, Commissioning of Horizontal Inferential Multijet Type Water Meter, Brass/ Bronze
body material, totalizer made of copper can/ suitable anti corrosive metallic material, totaliser metalic shall have 5 mm thick
glass cover suitable against antifraud attempts, Thread End process connection, IP 68 protection class, AMR Compatible
Water Meter, Dry dial, magnetically coupled, water meters complete with tubular strainer, brass nuts and nipples, ISO 4064 :
2005 with valid CE mark or ISI mark, mentioning notified body number along with MlD / OIML / ISO certification from a
recognized International laboratory.
The Totalizer should have facility to externally mount wireless AMR communication module without opening the meter for
upgradation to AMR in future.

a 15 mm No 1,425 119 1,544 18% 1,822

b 20 mm No 1,636 136 1,772 18% 2,091

c 25 mm No 5,824 486 6,310 18% 7,446

d 40 mm No 8,704 726 9,430 18% 11,127

7.2 Horizontal Inferential Multijet Type Water Meter- AMR Based:


Water Meter:
Design, Supply, Installation, Testing, Commissioning of Horizontal Inferential Multijet Type Water Meter, Brass/ Bronze
body material, totalizer made of copper can/ suitable anti corrosive metallic material, totaliser metalic shall have 5 mm thick
glass cover suitable against antifraud attempts, Thread End process connection, IP 68 protection class, AMR Water Meter,
Dry dial, magnetically coupled, water meters complete with tubular strainer, brass nuts and nipples, ISO 4064 : 2005 with
valid CE mark or ISI mark, mentioning notified body number along with MlD / OIML / ISO certification from a recognized
International laboratory.
AMR System :
AMR System shall be Walk By / Drive By mode, Wireless AMR trans-receivers shall be directly fitted on meter or inbuilt, IP
68 protection class, water meter & AMR Module shall be of same brand, Single Command based AMR Reading and
Minimum 90 days historical data retrive facility, alaram indication/ recording (for Reverse Flow, back flow, Peak
Flow,Minimum Flow, Low Battery Alram, Volume below threshold, Volume above threshold, Reverse Meter, Meter Stopped),
Minimum 10 years of AMR module bateery life considering one no. communication per day

a 15 mm No 5,117 427 5,544 18% 6,542

b 20 mm No 5,328 444 5,772 18% 6,811

c 25 mm No 9,516 794 10,310 18% 12,166

d 40 mm No 12,397 1,034 13,431 18% 15,849

7.3 METER READING DEVICE (For Manual Meter Reading / AMR Compatible / AMR Meter Reading)
Hand Held Unit / Meter Reading Device having IP 65 Protection class, windows/ android software base operating system,
minimum 1 GB RAM and 8 GB Flash Disk, GPRS / 3G / LTE network connectivity, GPS facility, Camera facility, data store
facility,

METER READING DEVICE/ Hand Held Unit No 121,325 - 121,325 18% 143,164

7.4 AMR Module for upgradation of AMR Compatible Meter :


AMR System shall be Walk By / Drive By mode, Wireless AMR trans-receivers shall be directly fitted on meter, IP 68
protection class, water meter & AMR Module shall be of same brand, Single Command based AMR Reading and Minimum
90 days historical data retrive facility, alaram indication/ recording (for Reverse Flow, back flow, Peak Flow,Minimum Flow,
Low Battery Alram, Volume below threshold, Volume above threshold, Reverse Meter, Meter Stopped), Minimum 10 years of
AMR module bateery life considering one no. communication per day.

AMR Module- No 3,693 308 4,001 18% 4,721


for upgradation of AMR Compatible Meter
For 15 mm to 300 mm size
7.5 Data Hosting Charges per Meter Per Annum Per - 90 90 18% 106
( For Calculation of O&M Charges) Meter
Per
Year

S.O.R. Mech 2019-20


Page 135 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
7.6 Meter Reading Softwre for Stadnard / AMR Compatible/ Mechnical MultiJEt AMR Meter / Ultrasonic AMR Meter:
Design, Supply, Installation, Testing, Commissioning of Web Based/ Cloud Based AMR Software for Mobile Based and
Web Based Application, software shall have various analysis tools which provides Alarm, Trends, Events, Data Logging and
Report Facility. Software shall collect meter data, store in to cloud and export to billing system with a pre-defined file format.
Considering the experience, knowledge of the meter data and expertise in meter data analysis the cloud based solution shall
be provided by reputed water meter manufacturer

Meter Reading Software No 500,000 - 500,000 18% 590,000

8 Water Meters (Woltman Type):

8.1 Woltman Type Bulk Water Meter- Standard:


Design, Supply, Installation, Testing, Commissioning of Woltman type Bulk Water Meter, CI/ Brass/ Bronze body material,
totalizer made of copper can/ suitable anti corrosive metallic material, totaliser metalic shall have 5 mm thick glass cover
suitable against antifraud attempts, Flange End process connection, IP 68 protection class, Woltman type Water Meter with
removable mechanism, magnetic drive, dry dial, and be fitted with a low mass rotor which is parallel to the direction of water
flow and exhibits dynamic thrust relief, water meters complete with T Type strainer, ISO 4064 : 2005 with valid CE mark
mentioning notified body number along with MlD / OIML / ISO certification from a recognized International laboratory.

a 50 mm No 9,495 792 10,287 18% 12,139

b 65 mm No 10,603 885 11,488 18% 13,556

c 80 mm No 14,770 1,232 16,002 18% 18,882

d 100 mm No 17,935 1,496 19,431 18% 22,929

e 125 mm No 18,463 1,540 20,003 18% 23,604

f 150 mm No 21,206 1,770 22,976 18% 27,112

g 200 mm No 28,485 2,377 30,862 18% 36,417

h 250 mm No 32,705 2,728 35,433 18% 41,811

i 300 mm No 35,870 2,993 38,863 18% 45,858

8.2 Woltman Type Bulk Water Meter- AMR Based:


Water Meter:
Design, Supply, Installation, Testing, Commissioning of Woltman type Bulk Water Meter, CI/ Brass/ Bronze body material,
totalizer made of copper can/ suitable anti corrosive metallic material, totaliser metalic shall have 5 mm thick glass cover
suitable against antifraud attempts, Flange End process connection, IP 68 protection class, AMR Woltman Type Water
Meter with removable mechanism, magnetic drive, dry dial, and be fitted with a low mass rotor which is parallel to the
direction of water flow and exhibits dynamic thrust relief, water meters complete with T Type strainer, ISO 4064 : 2005 with
valid CE mark mentioning notified body number along with MlD / OIML / ISO certification from a recognized International
laboratory.
AMR System :
AMR System shall be Walk By / Drive By mode, Wireless AMR trans-receivers shall be directly fitted on meter or inbuilt, IP
68 protection class, water meter & AMR Module shall be of same brand, Single Command based AMR Reading and
Minimum 90 days historical data retrive facility, alaram indication/ recording (for Reverse Flow, back flow, Peak
Flow,Minimum Flow, Low Battery Alram, Volume below threshold, Volume above threshold, Reverse Meter, Meter Stopped),
Minimum 10 years of AMR module bateery life considering one no. communication per day

a 50 mm No 16,353 1,365 17,718 18% 20,907

b 65 mm No 18,357 1,531 19,888 18% 23,468

c 80 mm No 18,463 1,540 20,003 18% 23,604

d 100 mm No 22,598 1,886 24,484 18% 28,891

e 125 mm No 33,633 2,806 36,439 18% 42,998

S.O.R. Mech 2019-20


Page 136 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
f 150 mm No 35,448 2,957 38,405 18% 45,318

g 200 mm No 51,695 4,313 56,008 18% 66,089

h 250 mm No 58,025 4,841 62,866 18% 74,182

i 300 mm No 61,190 5,105 66,295 18% 78,228

8.3 Strainer:
Design, Supply, Installation, Testing, Commissioning of External Striner for Woltman type Bulk Water Meter, Body: IS:210
FG200 , Strainer Frame : SS Perforated Sheet, SS 304, Mesh (30) : 58 Perforated Sheet, SS 304, Gasket: Rubber Cover:
IS:210FG200, Stud/Bolts/Nut: IS:1363CL4.6 & CL 4.0, Eye Bolt: IS:1363CL4.6 & CL4.0, Plug:13% CR.SS (AISI 410),
Flange Dimensions as per IS:1538 table 6/ BS-4504 PN16, with all necessary hardware to complete the installtion.

a 50 mm No 3,561 297 3,858 18% 4,552

b 65 mm No 4,705 393 5,098 18% 6,016

c 80 mm No 6,567 547 7,114 18% 8,395

d 100 mm No 7,702 642 8,344 18% 9,846

e 125 mm No 9,390 784 10,174 18% 12,005

f 150 mm No 12,977 1,083 14,060 18% 16,591

g 200 mm No 18,674 1,557 20,231 18% 23,873

h 250 mm No 25,742 2,147 27,889 18% 32,909

i 300 mm No 53,172 4,436 57,608 18% 67,977

9 Bulk Water Meters (Ultrasonic)/ Full Bore Inline Ultrasonic Flow Meter:

9.1 Full Bore Inline Ultrasonic Flow Meter- Inbuilt Battery Power/ Self Power operated (PN 16)
Design, Supply, Installation, Testing, Commissioning of Full Bore Inline Ultrasonic flow meter with factory calibrated, Inbuilt
Battery Power Operated, flanged connection, Flow sensor, Indicator, transmitter and totaliser with all accessories viz. surge
arrestor, associated cables, cabinets, hardwares, etc complete as per following specifications:
Flow Meter/ Sensor: Ultrasonic type, IP 68 Protection, Flanged process connection as per IS 1538 or equivalent standard,
SS304/ Metallic Alloy Flow Tube, SS316/ SS 316 L/ Hastelloy Sensor, SS316/ Hastelloy Grounding Ring/ Inbuilt Grounding
Electrode, Neoprene/Polyurethane/ Hard Rubber/ Rilsan lining, SS304/ Die Cast Aluminium/ Carbon steel with Anticorrosive
Paint Coil Housing with Junction Box, CS flanges.
Flow Transmitter/ Converter ( Remote Field Mounted inside the Cabinet): Microprocessor based, Modular design, 2 line LCD
for indication of actual flow rate, forward, reverse, sum totaliser display, ±0.5% accuracy at 0.3 to 4 m/sec velocity, one
scalable pulse, one status, one GPRS/ GSM output, IP 67 protection, Die cast aluminium/ polycarbonate/ SS316 with
Anticorrosive Paint/ PU finish with glass window enclosure, Inbuilt EEPROM and Data Logger,20 meters cable length for
sensor to transmitter communication, Minimum 5 years battery life time, 3.6 VDC Non Rechargeable Lithium-thionyl
chloride/ Ni-Cd high power batteries, Real time data logging at remote location with every 1 minute frequency for storage up
to 30 days period and Twice a day transmission of measured data and events via e‐mail and SMS as & when they occur by
integrated GSM/GPRS modem, Reliable data storage facility through integrated SD card 32 GB.

a 50 mm No 58,025 4,661 62,686 18% 73,970

b 65 mm No 73,850 4,661 78,511 18% 92,643

c 80 mm No 89,675 4,661 94,336 18% 111,317

d 100 mm No 136,095 7,203 143,298 18% 169,092

e 150 mm No 157,033 8,898 165,932 18% 195,799

S.O.R. Mech 2019-20


Page 137 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
f 200 mm No 201,695 10,593 212,288 18% 250,500

g 250 mm No 247,925 10,593 258,518 18% 305,052

h 300 mm No 267,119 13,559 280,678 18% 331,200

i 350 mm No 321,775 13,559 335,334 18% 395,695

j 400 mm No 433,605 20,339 453,944 18% 535,654

k 450 mm No 456,815 23,729 480,544 18% 567,042

l 500 mm No 501,125 27,119 528,244 18% 623,328

m 600 mm No 606,625 27,119 633,744 18% 747,818

10 Pressure & Vacuum Gauges with Accessories


10.1 Design, Supply, Installation, Testing, Commissioning of Bourdon Type Pressure Gauge, ±1% accuracy, Direct bottom 1/2"
NPT (M) process connection, IP 67, Glycerine filled, SS304 Case with Bayonet Type Bezel, SS316 L Bourdon Tube, SS
316 Movement material, Aluminium dial with black graduation on white background, Micro Zero adjustable pointer, neoprene
gasket, Blow out disc, shatter proof glass, SS tag plate etc as per IS 3624.
a) 100 mm Dial Size

i) 0 to 1 Kg/cm2 No 1,556 130 1,686 18% 1,989

ii) 0 to 2.1 Kg/cm2 No 1,055 88 1,143 18% 1,349

iii) 0 to 4 Kg/cm2 No 950 79 1,029 18% 1,214

iv) 0 to 6 Kg/cm2 No 950 79 1,029 18% 1,214

v) 0 to 10 Kg/cm2 No 950 79 1,029 18% 1,214

vi) 0 to 21 Kg/cm2 No 950 79 1,029 18% 1,214

b) 150 mm Dial Size

i) 0 to 1 Kg/cm2 No 1,594 133 1,727 18% 2,038

ii) 0 to 2.1 Kg/cm2 No 1,404 117 1,521 18% 1,795

iii) 0 to 4 Kg/cm2 No 1,303 109 1,412 18% 1,666

iv) 0 to 6 Kg/cm2 No 1,303 109 1,412 18% 1,666

v) 0 to 10 Kg/cm2 No 1,303 109 1,412 18% 1,666

vi) 0 to 20 Kg/cm2 No 1,303 109 1,412 18% 1,666

10.2 Design, Supply, Installation, Testing, Commissioning of Diaphragm sealed Pressure Gauge, ±1% accuracy, Direct bottom
1/2" NPT (M) process connection, IP 67, Glycerine filled, SS304 Case with Bayonet Type Bezel, SS316 L Diaphragm,
SS316 Bottom Housing Material, SS 316 Movement material, Aluminium dial with black graduation on white background,
Micro Zero adjustable pointer, neoprene gasket, Blow out disc, shatter proof glass, SS tag plate etc as per IS 3624.

a) 100 mm Dial Size

i) 0 to 1 Kg/cm2 No 3,033 253 3,286 18% 3,877

ii) 0 to 2.1 Kg/cm2 No 2,532 211 2,743 18% 3,237

iii) 0 to 4 Kg/cm2 No 2,427 202 2,629 18% 3,102

iv) 0 to 6 Kg/cm2 No 2,427 202 2,629 18% 3,102

v) 0 to 10 Kg/cm2 No 2,427 202 2,629 18% 3,102

vi) 0 to 21 Kg/cm2 No 2,427 202 2,629 18% 3,102

b) 150 mm Dial Size

S.O.R. Mech 2019-20


Page 138 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
i) 0 to 1 Kg/cm2 No 3,071 256 3,327 18% 3,926

ii) 0 to 2.1 Kg/cm2 No 2,881 240 3,121 18% 3,683

iii) 0 to 4 Kg/cm2 No 2,780 232 3,012 18% 3,554

iv) 0 to 6 Kg/cm2 No 2,780 232 3,012 18% 3,554

v) 0 to 10 Kg/cm2 No 2,780 232 3,012 18% 3,554

vi) 0 to 21 Kg/cm2 No 2,780 232 3,012 18% 3,554

10.3 Design, Supply, Installation, Testing, Commissioning of Vacuum Gauge, ±1% accuracy, Direct bottom 1/2" NPT (M)
process connection, IP 67, Glycerine filled, SS304 Case with Bayonet Type Bezel, SS316 L Bourdon Tube, SS 316
Movement material, Aluminium dial with black graduation on white background, Micro Zero adjustable pointer, neoprene
gasket, Blow out disc, shatter proof glass, SS tag plate etc as per IS 3624.

a) 100 mm Dial Size


i) -760 to 0 mmHg (-1 to 0 bar) No 1,583 132 1,715 18% 2,024

b) 150 mm Dial Size


i) -760 to 0 mmHg (-1 to 0 bar) No 1,899 159 2,058 18% 2,428

10.4 Design supply, installation , testing , commissioning of following Accessories


a) Diaphram seal for Pressure Gauge.
SS 316 L Diaphragm, SS316 Top chamber of diaphragm, SS316 Bottom Chamber of Diaphragm, PTFE Gasket, 1/2" NPT
(F) X 1/2" NPT (M) Process connection, Silicon DC 200 sealing fluid etc. complete to match pressure gauge.

i) Diaphragm Seal No 1,477 123 1,600 18% 1,888


b) Gauge cock for Pressure Gauge.
3 way gauge cock, 1/2" NPT (F) X 1/2" NPT (M) Process connection complete to match pressure gauge.

i) 3 Way Gauge Cock- SS316 No 739 62 801 18% 945

c) Pulsation Dampner/ Snubber for Pressure Gauge.


Suitable to withstand pressure up to 300 kg/cm2, Viton Gasket, 1/2" NPT (F) X 1/2" NPT (M) Process connection complete
to match pressure gauge.
i) Snubber- SS 316 No 380 31 411 18% 485

d) Syphon for Pressure Gauge:


1/2" NPT (F) X 1/2" NPT (M) Process connection complete to match pressure gauge.

i) Q Type Syphon-SS 316 No 1,161 97 1,258 18% 1,484

11 Pressure Transmitter:
Design, Supply, Installation, Testing and Commissioning of Sealed Diaphragm Type Pressure Transmitter.
Piezo-resistive sensor technolgy based pressure transmitter with Micro-processor based integral LED/ LCD display, with
accuracy of ± 0.3% of span, external zero and span adjustment, self diagnostics, temperature sensor for compensation. 15
to 36 V DC power supply, output signal of 4-20 mA DC with HART. Minimum IP 65 degree of protection. Aluminium housing
with epoxy coating, Accessories like snubbers for pump discharge applications, three way manifold, mounting brackets,
name plate etc. Material for accessories shall be SS. Protection Box/Canopy shall be provided for outside installed
transmitters.
Pressure Transmitter shall be suitable for following Range.

a 0 to 10 or 0 to 20 Kg/cm2 No 26,903 2,244 29,147 18% 34,393

12 Float & Board Type Level Indicator:

S.O.R. Mech 2019-20


Page 139 of 166
Section- "F"

Approved Rate for 2019-20


Sr.
Description of Item Unit Rates exclusive of GST
No. Total
Prevailing with GST
Erection &
Supply Total rates of GST
Overhead
Design, Supply, Installation, Testing and No. 12,133 1,012 13,145 18% 15,511
Commissioning of Float & Board Type Level
Indicator, guided construction, Full Range Travel,
FRP/ SS316 MOC of Float and Guide Wire Rope,
minimum 6” wide x aluminum powder coating
with black graduations and numerical on
calibrated gauge board, Red color pointer,
protection conduit, Elbow pulley, Tensioner,
Anchor, Rope Fastner, Gauge Brackets, Counter
Weight for rope type probe, spacer between the
probes, etc complete with calibration of
following sizes. 0 to 1 meter

a ---do----: Size: 0 to 2 Meter No. 13,188 1,100 14,288 18% 16,860

b ---do----: Size: 0 to 3 Meter No. 14,243 1,188 15,431 18% 18,209

c ---do----: Size: 0 to 4 Meter No. 15,298 1,277 16,575 18% 19,559

d ---do----: Size: 0 to 5 Meter No. 16,353 1,365 17,718 18% 20,907

13 Float/ Displacer Type Level Switch:

Design, Supply, Installation, Testing and Commissioning of Top mounted Displacer Type level switches with 2 nos SPDT
contacts of Micro switch rated 5 A, potential free power supply, Material of wetted parts shall be SS 316 and the material of
accessories shall be SS. IP 65 or equivalent degree of protection for enclosure, suitable for sump, ESR, tank, vessels
and underground reservoirs. The top mounted level switches shall be supplied with still tubes to suit the requirement.
. Accessories like name plate, mating flange, gaskets, fasteners, bolts & nuts, etc. shall be supplied with the Level
Switch of following Range.

a 0 to 5 Meter No 11,816 986 12,802 18% 15,106

14 Ultrasonic Level Transmitter

a Ultrasonic Type Level Transmitter with Remote Display :


Design, Supply, Installation, Testing and Commissioning of NOn Contact Ultrasonic Type Level Transmitter with Remote
Display.
Sensor:
The sensor should be non contact type, field mounting type, housing shall have minimum IP65 protection, PP/ PVC Sensor
MOC, with sensor to transmitter cable.
Remote Indicator cum Transmitter:
Microprocessor based indicator with LED / LCD digital display,panel/ wall mounting type, power supply shall be 110-240 Vac
or 15 to 36 Vdc, 50 Hz ± 10 %.
Accesories: Mounting bracket, nut, bolts etc as per system requirement and Hook up diagram of the Instruments.
Level Transmitter shall be suitable for following Range.
i) 0 to 4 Meter No 48,900 4,079 52,979 18% 62,515

ii) 0 to 10 Meter No 54,860 4,576 59,436 18% 70,134

b Ultrasonic Type Level Transmitter with Integral Display :


Design, Supply, Installation, Testing and Commissioning of NOn Contact Ultrasonic Type Level Transmitter with Integral
Display.
Sensor with Head Mounted Transmitter:
The sensor should be non contact type, field mounting type, housing shall have minimum IP65 protection, PP/ PVC Sensor
MOC, Microprocessor based indicator with LED / LCD digital display,panel/ wall mounting type, power supply shall be 110-
240 Vac or 15 to 36 Vdc, 50 Hz ± 10 %.
Accesories: Mounting bracket, nut, bolts etc as per system requirement and Hook up diagram of the Instruments.
Level Transmitter shall be suitable for following Range.

i) 0 to 4 Meter No 34,710 2,896 37,606 18% 44,375

ii) 0 to 8 Meter No 38,877 3,243 42,120 18% 49,702

iii) 0 to 15 Meter No 55,124 4,599 59,723 18% 70,473

S.O.R. Mech 2019-20


Page 140 of 166
TABLE-1

CURRENT RATINGS (ac) FOR TWO, THREE & FOUR CORE

650/1100 Volts, Armoured or un-Armoured Aluminium Conductor Cables as per IS:3961 (PART II)-1967

Nominal LAID DIRECT


Area of IN THE GROUND IN DUCTS IN AIR
Conductor 2 Core 3,3.5 & 4 2 Core 3,3.5 & 4 2 Core 3,3.5 & 4
mm2 Core Core Core
Amps Amps Amps Amps Amps Amps
1.5 18 16 16 14 16 13
2.5 25 21 21 18 21 18
4 32 28 27 23 27 23
6 40 35 34 30 35 30
10 55 46 45 39 47 40
16 70 60 58 50 59 51
25 90 76 76 63 78 70
35 110 92 92 77 99 86
50 135 110 115 95 125 105
70 160 135 140 115 150 130
95 190 165 170 140 185 155
120 210 185 190 155 210 180
150 240 210 210 175 240 205
185 275 235 240 200 275 240
240 320 275 275 235 325 280
300 355 305 305 260 365 315
400 385 335 345 290 420 375
CONDITIONS OF INSTALLATION

Maximum Conductor Temperature 70°C

Ambient Air Temperature 40°C

Ground Temperature 30°C

Depth of Laying for cables in Ground 75 Cmt.

Thermal Resistivity of Soil 150 Cm/Watt.

Method of Installation Singly

Page 141 of 166


TABLE-2

Current-carrying capacities and associated voltage drops for single-core p.v.c insulated cables.

Non-armoured, with or without sheath (copper conductors)

Conductor operating temperature: 70°C

Installation methods (Enclosed) Installation methods (Clipped Direct) Installation method (Defined Conditions)
Flat or vertical (2 cables, single-
2 Cables 3 or 4 cables 2 Cables single-phase 3 or 4 cables phase a.c. or d.c. or 3 or 4 cables 3 or 4 cables
Conductor single-phase a.c or d.c three-phase a.c a.c or d.c three-phase a.c three-phase) three-phase a.c
cross Current Volt drop Current Volt Current Volt drop Current Volt Current current Volt
Sectional carrying per carrying drop carrying per ampere carrying drop carrying Volt drop per ampere carrying drop
Area capacity ampere capacity per capacity per metre capacity per per metre capacity per
per metre ampere ampere capacity ampere
per per Single d.c. Three per
metre metre Phase metre
Phase
1 2 3 4 5 6 7 8 9 10 11 12 12 14 15
mm2 A mV A mV A mV A mV A mV mV A
1 14 42 12 37 17 42 16 0.37 - - - - - -
1.5 17 28 14 24 21 28 20 0.24 - - - - - -
2.5 24 17 21 15 30 17 26 0.15 - - - - - -
4 32 11 29 9.2 40 11 36 9.2 - - - - - -
6 41 7.1 37 6.2 50 7.1 45 6.2 - - - - - -
10 55 4.2 51 3.7 68 4.2 61 3.7 - - - - - -
16 74 2.7 66 2.3 90 2.7 81 2.3 - - - - - -
25 97 1.7 87 1.5 118 1.7 106 1.5 - - - - - -
35 119 1.3 106 1.1 145 1.3 130 1.1 - - - - - -

Page 142 of 166


1 2 3 4 5 6 7 8 9 10 11 12 12 14 15
a.c d.c a.c d.c
50 145 0.97 0.91 125 0.84 175 0.93 0.91 160 0.82 195 0.95 0.91 0.85 170 0.8
70 185 0.71 0.63 160 0.62 220 0.65 0.63 200 0.59 240 0.68 0.63 0.62 210 0.59
95 230 0.56 0.45 195 0.48 270 0.48 0.45 240 0.45 300 0.52 0.45 0.49 260 0.42
120 260 0.48 0.36 220 0.42 310 0.40 0.36 280 0.38 350 0.44 0.36 0.43 300 0.34
150 - - - - - 355 0.34 0.29 320 0.34 410 0.39 0.29 0.39 350 0.29
185 - - - - - 405 0.29 0.24 365 0.3 470 0.35 0.24 0.36 400 0.25
240 - - - - - 480 0.24 0.18 430 0.27 560 0.36 0.18 0.38 480 0.22
300 - - - - - 560 0.22 0.14 500 0.25 660 0.33 0.14 0.35 570 0.19
400 - - - - - 680 0.2 0.12 610 0.24 800 0.3 0.12 0.33 680 0.17
500 - - - - - 800 0.18 0.086 710 0.23 910 0.28 0.086 0.31 770 0.16
630 - - - - - 910 0.17 0.068 820 0.22 1040 0.26 0.068 0.3 880 0.15

CORRECTION FACTORS
FOR AMBIENT TEMPERATURE
Ambient Temperature 25°C 35°C 40°C 45°C 50°C 55°C 60°C 65°C
Correction factor 1.06 0.94 0.87 0.79 0.71 0.61 0.5 0.35

Page 143 of 166


Table-3

EARTHING READY RECKONER


Sr No Item Copper Aluminum GI
Weight of Conductor
kg/MTR.
1 No. 14 " SWG Wire" 0.028 - 0.0254
0.0162
0.049 0.043
2 No. 12 " SWG Wire" (6 mm2)
0.02703
0.1155 0.102
3 No. 8 " SWG Wire" (10 mm2)
4 No. 6 " SWG Wire" 0.1668 - 0.1465
5 No. 4 " SWG Wire" 0.243 - 0.224
6 No. 2 " SWG Wire" 0.344 0.0945 0.305
7 25x3 MM Flat 0.67 0.202 0.59
8 32x6 MM Flat 1.715 0.518 1.51
9 50x6 MM Flat 2.68 0.81 2.36
10 600 x 600 x 6 MM Thick Plate 19.3 5.83 17
11 600 x 600 x 12 MM Thick Plate 38.6 11.66 34
RECOMMENDED EARTH CONDUCTORS
FOR MOTORS
1 Upto 15 HP 12 Swg. 6 mm2 8 Swg.
2 Upto 20 to 30 HP 8 Swg. 10 mm2 4 Swg.
3 Upto 35 to 50 HP 4 Swg. 35 mm2 25x3 mm Flat
4 Above 50 HP 25 x 3 MM Flat 25 x 6 MM Flat 32 x 6 MM Flat

GALVANISED EARTHING DETAILS

GI Approx Approx
Area Nominal
Cond. Weight Resistance
mm2 Dia mm
Size Kg/M Ohm/M.

14 S.W.G 3.24 2.03 0.026 0.0433


12 S.W.G 5.48 2.64 0.044 0.02565
10 S.W.G 8.35 3.26 0.067 0.0162
8 S.W.G 12.97 4.06 0.104 0.01063
4 S.W.G 27.27 5.89 0.218 0.00505
25x3 mm 75 - 0.600 0.0017
32x6 mm 192 - 1.536 0.0007
50x6 mm 300 - 2.400 0.00033

Page 144 of 166


TABLE-4

SELECTION TABLE FOR STARTER/RELAY/FUSE/CABLE FOR DOL MOTORS

Typical
Approximate DOL Starter/
KW Relay Backup Typical
HP 3 Phase Full Load Contactor
415V Scale in HRC Cable size
415V 50 HZ current in capacity in
50 HZ Amps fuse in sq.mm AL
Amps Amps.
Amps
0.50 0.4 1 12 0.8-1.6 6 1.5/2.5
0.75 0.55 1.5 12 1-1.5 6 1.5/2.5
1 0.75 2 12 1.4-2 10 1.5/2.5
1.5 1.1 2.6 12 2-3 10 1.5/2.5
2 1.5 3.5 12 2.5-4 15 1.5/2.5
3 2.25 5 16 4-6 20 1.5/2.5
4 3 6.2 16 4-6 20 1.5/2.5
5 3.75 7.5 16 5.5-8 25 2.5
6 4.5 9 16 6-10 25 2.5
7.5 5.6 11 16 8-12 25 4
10 7.5 14 16 11-12 35 4
12.5 9.3 18 30 14-20 50 6
15 11 21 30 17-25 50 6
17.5 13 24 30 20-32 63 10
20 15 28 30 22-32 63 10
25 18.5 35 38 25-40 80 16
30 22 40 70 30-45 100 25
35 26 47 70 38-63 125 25
40 30 55 70 38-63 125 25
45 33.5 60 70 45-70 160 35
50 37.5 66 70 50-90 160 35
60 45 80 105 50-90 160 50
75 56 100 105 70-110 200 70
90 67.5 120 170 90-150 250 95
120-
100 75 135 170 155 250 95
140-
150 112 200 400 200 350 185
210-
200 150 275 400 300 500 300/400
280-
225 170 300 400 300 600 300/400

Page 145 of 166


TABLE-5

SELECTION TABLE FOR STARTER/RELAY/FUSE/CABLE FOR STAR DELTA MOTOR

Typical Cable size


Typical sq.mm AL
HP 3 Approximate
KW Star Delta Starter Relay Backup
Phase Full Load
415V Contactor capacity in Scale in HRC
415V 50 current in
50 HZ Amps Main/Delta Star Amps fuse in
HZ Amps Supply Motor
Amps
side side

3 2.25 5 12 12 1.5-4 10 1.5/2.5 1.5/2.5


5 3.75 7.5 12 12 3-6 20 1.5/2.5 1.5/2.5
7.5 5.5 11 12 12 6-10 25 2.5 1.5/2.5
10 7.5 14 16 16 6-12 25 4 1.5/2.5
12.5 9.3 18 16 16 8-12 35 4 2.5
15 11 21 16 16 11-16 50 6 2.5
20 15 28 30 30 14-20 63 10 4
25 18.5 35 30 30 17-25 63 16 6
30 22 40 30 30 17-25 100 16 6
35 26 47 38 30 22-32 100 25 10
40 30 55 38 30 22-32 100 25 16
45 33.5 60 70 30 25-40 125 35 16
50 37 66 70 30 25-40 125 35 16
60 45 80 70 70 38-63 125 50 25
65 48.5 87 70 70 38-63 160 70 35
70 52 94 70 70 38-63 160 70 35
75 56 100 70 70 38-63 160 70 35
90 67.5 120 105 70 50-90 200 95 50
100 75 135 105 70 50-90 200 95 50
125 90 165 160 70 70-110 250 120 70
150 112 200 170 170 90-135 250 185 70
175 132 230 170 170 90-135 300 225 120
200 150 275 300 170 140-170 350 300/400 150
240 175 320 400 170 140-170 400 300/400 185
250 187.5 323 400 170 140-200 400 400 185
275 204 360 400 170 175-250 400 500 185
300 225 385 400 400 210-300 500 500 225
400 300 500 400 400 280-400 700 625 300/400

Page 146 of 166


TABLE 6

SIZE OF CAPACITORS IN KVAR REQUIRED FOR GIVEN DEGREE OF POWER FACTOR CORRECTION PER
KW OF LOAD

Initial Correction to
Power 0.85 0.9 0.95 0.98 Unity
1 2 3 4 5 6
0.50 1.112 1.248 1.403 1.529 1.732
0.51 1.066 1.202 1.357 1.483 1.686
0.52 1.024 1.16 1.315 1.441 1.644
0.53 0.98 1.116 1.217 1.397 1.6
0.54 0.939 1.075 1.23 1.356 1.559
0.55 0.899 1.035 1.19 1.316 1.519
0.56 0.86 0.996 1.151 1.277 1.48
0.57 0.822 0.958 1.113 1.239 1.442
0.58 0.785 0.921 1.076 1.202 1.405
0.59 0.748 0.884 1.039 1.165 1.368
0.60 0.714 0.849 1.005 1.131 1.334
0.61 0.679 0.815 0.97 1.096 1.299
0.62 0.645 0.781 0.936 1.062 1.265
0.63 0.613 0.749 0.904 1.03 1.233
0.64 0.58 0.716 0.871 0.997 1.2
0.65 0.549 0.685 0.84 0.966 1.169
0.66 0.518 0.654 0.809 0.935 1.138
0.67 0.488 0.624 0.779 0.905 1.108
0.68 0.459 0.595 0.75 0.876 1.079
0.69 0.429 0.565 0.72 0.84 1.049
0.70 0.4 0.536 0.691 0.811 1.02
0.71 0.372 0.508 0.663 0.783 0.992
0.72 0.343 0.479 0.634 0.754 0.963
0.73 0.316 0.452 0.607 0.727 0.936
0.74 0.289 0.425 0.58 0.7 0.909
0.75 0.262 0.398 0.553 0.673 0.882
0.76 0.235 0.371 0.526 0.652 0.855
0.77 0.209 0.345 0.5 0.62 0.829
0.78 0.183 0.319 0.473 0.594 0.803
0.79 0.156 0.292 0.447 0.567 0.776
0.80 0.13 0.266 0.421 0.541 0.75
0.81 0.104 0.24 0.395 0.515 0.724
0.82 0.078 0.214 0.369 0.489 0.698
0.83 0.052 0.188 0.343 0.463 0.672

Page 147 of 166


TABLE 6 Continue….

Initial
Power Correction to
0.85 0.9 0.95 0.98 Unity
1 2 3 4 5 6
0.84 0.026 0.162 0.317 0.437 0.645
0.85 - 0.136 0.291 0.417 0.62
0.86 - 0.109 0.264 0.39 0.593
0.87 - 0.083 0.238 0.364 0.567
0.88 - 0.054 0.209 0.335 0.538
0.89 - 0.028 0.183 0.309 0.512
0.90 - - 0.155 0.281 0.484
0.91 - - 0.124 0.25 0.453
0.92 - - 0.097 0.223 0.426
0.93 - - 0.066 0.192 0.395
0.94 - - 0.034 0.16 0.363
0.95 - - - 0.126 0.329
0.96 - - - 0.089 0.292
0.97 - - - 0.047 0.25
0.98 - - - - 0.203
0.99 - - - - 0.143

Sample: To find the capacitor rating required to correct a load of 100 kW

Method-1 (0.85 PF to 0.98)

Average Power Factor (CosØ1) = 0.85

Required Power Factor (CosØ2) = 0.98

Total kVAR Required= kW x [tan (cos−1Ø1) - tan (cos−1Ø2)]

Total kVAR Required=100 x [tan (cos−1 0.85) - tan (cos−1 0.98)]

Total kVAR Required=100 x [tan (0.55) - tan (0.20)] = 100 x (0.619-0.203) = 100 x 0.416

Total kVAR Required=41.6 kVAR ≅ 42 kVAR

Method-2 (0.85 PF to 0.98)

Required kVAR per kW (vide Table) = 0.417

Total Capacitor rating=0.417*100 = 41.7 kVAR ≅ 42 kVAR

Page 148 of 166


Table-7

DISTRIBUTION TRANSFORMER

Check before erection and commissioning

(1) Oil Test: 30 kV. Minimum across 2.5 mm gap for one minute.
(2) Insulation test: Minimum safe insulation resistance of windings at temperature.
30°C 40°C 50°C 60°C Voltage of
Meggar
415V 200 mΩ 100 50 25 500 Volts
3.3 & 6.6 kV 400 mΩ 200 100 50 1000 Volts
11 kV,22 kV 500 mΩ 250 125 65 2500 Volts
& 33 kV
(3) Ratio Test: 400V should be applied to HT side and Voltage to be measured on LT side. The ratio
should compare with the rated figures.
(4) Oil Level: Oil level should be checked up and topped if necessary.
(5) Breather: The silica in the breather should be blue.
(6) Diaphram: It should be in tact, and no crack is observed.
(7) Measurement of earth resistance: this should be less than 1 ohm.

Page 149 of 166


TABLE-8

TRANSFORMER OIL (Grade)- B.30 B.S. 148

Characteristic Limit
Sludge formation (Maximum) 0.3%
Moisture at 15.5°C 200 Redwood seconds
Moisture Nil
Dielectric strength 30 kV at 15°C to 20°C using 1/3 mm.
Diameter sphere, 2.5 mm apart
Flash Point (Minimum) 145°C
Evaporation (Maximum) 1.6%
Cold test -30°C
Acidity (Neutralization value)
Inorganic Nil
Organic (Max) 0.5 mg KoH/gram of oil

Limits of acidity of Transformer Oil

(1) When the acidity is less than 0.2 Mg/KOH/Gm. Of oil, the oil is in good condition from the stand
point of this test.
(2) When the acidity is between 0.2 mg and 0.5 mg/KOH/gm, no action need to be taken, if the oil is
satisfactory in all other respects.
(3) When the acidity is between 0.5 to 1.0 Mg/KOH/gm the oil should be kept under observation
and filtered if necessary.
(4) When the acidity exceeds 1 Mg/KOH/gm the oil should be reclaimed or discarded.

Page 150 of 166


Table-9

TYPE DESGINATION AND CORE IDENTIFICATION OF CABLES & WIRE AS PER IS: 1554 (1) & IS: 7098 (1)

Sr. No. Code Constituent


1 A Aluminum Conductor
2 Y Plain Copper Conductor PVC Insulated unsheathed cables
3 AY Aluminium Conductor OVC insulated unsheathed cables
4 YY Plain Copper Conductor PVC insulated unsheathed cables
4 AYY Aluminium conductor PVC insulated & PVC sheathed cables
5 YWY P/C insulated & sheathed, steel round wire armoured with copper conductor cable
6 YFY PVC insulated, Sheathed, steel flat wire armoured with copper conductor
7 AYWY PVC insulated & sheathed round steel wire armoured cable with Aluminium
conductor
8 AYFY PVC insulated sheathed, flat steel wire armoured cable with Aluminium conductor.
9 2X XLPE insulation
10 W Steel round wire Armour
11 Wa Non-Magnetic round wire Armour
12 F Steel strip Armour
13 Fa Non-Magnetic Strip Armour
14 FF Double Steel round wire Armour
15 WW Double Steel round wire Armour
16 Y PVC outer sheath

Understating cable code

1ST NUMERAL 2ND NUMERAL 3RD NUMERAL 4th NUMERAL


Type of Conductor Conductor Insulation Type of Armoring Type Outer Sheath
A Y F Y
Aluminium Conductor PVC insulated Steel Armoring PVC Sheathed
i.e AYFY- PVC insulated, PVC sheathed Steel Armored Aluminium cables

Page 151 of 166


TABLE-10

Typical mV drop Values for Joints

Sr. No. Type of Joints Test Current Max. mV Good mV


permissible
1 Terminal to link 100 2.5 0.5-1.0
2 Terminal to Lug 50 8.0 1.0-2.0
3 Terminal to Lug 100 5.0 1.0-2.0
4 Cable to Cable lug Rated 5.0 2.0
(Crimped Joint)

1. For Correct cable Lugs


a. The conductor should be fully accommodated within lug.
b. The cable lug should have a close fit as possible to the conductor.

2. Crimping Joints
a. Length f insulation to be stripped= barrel length+1-3 mm.
b. For cable size of 35 mm2 & above two/three clamps are recommended @ 3-4 mm distance.

Page 152 of 166


Table-11

IP EXPLANATION AND RATINGS

EN 60529 outlines an international classification system for sealing effectiveness of enclosures of electrical
equipment against the intrusion into the equipment of foreign bodies (i.e tools, dust, fingers) and
moisture. This classification system utilizes the letters “IP” (“Ingress Protection”) followed by two or three
digits. (A third digit is sometimes used. An “X” is used for one of the digits if there is only one class of
protection; i.e IPX4 which addresses moisture resistance only).

Degrees of Protection-First Digit

The first digit of the IP code indicates the degree that persons are protected against contact with moving
parts (other than smooth rotating shafts, etc.) and the degree that equipment is protected against solid
foreign bodies intruding into an enclosure.

0 No special protection
1 Protection from a large part of the body such as a hand (but no protection from deliberate
access); from solid objects greater than 50 mm in diameter.
2 Protection against fingers or other object not greater than 80mm in length and 12 mm in
diameter.
3 Protection from entry by tools, wires, etc. with a diameter of thickness greater than 1 mm.
4 Protection from entry by solid objects with a diameter or thickness greater than 1 mm.
5 Protection from the amount of dust that would interfere with the operation of the equipment.
6 Dust tight

Degrees of Protection-Second Digit

The second digit indicates the degree of protection of the equipment inside the enclosure against the
harmful entry of various forms of moisture. (e.g. dripping, spraying, submersion, etc.)

0 No special protection
1 Protection from dripping water
2 Protection from vertically dripping water
3 Protection from sprayed water
4 Protection from splashed water
5 Protection water projected from a nozzle.
6 Protection against heavy seas, or powerful jest of water
7 Protection against immersion
8 Protection against complete, continuous submersion in water.

Submersion depth and time must be specified by the end-user. The requirement must be more onerous
than IP 67.

Page 153 of 166


Page 154 of 166
TABLE-12

IS CODES

ELECTRICAL WORKS
IS 2551 Danger Notice Boards
IS 4064 Normal duty air break switches & composite units of air break switches & fuses for
voltages not exceeding 1000V
IS 1818 Alternating current isolators (disconnectors) & earthing switch
IS 2584 Test for Electrical Strength
IS 694 PVC insulated cables.
IS 375 Specification for marking and arrangement for switchgear busbar, main connection
and aux. wiring
IS 5216 Safety procedures & practice in electrical works
IS 2982 Copper conductors in insulated cable & chords
IS 5578 Guide for marking of insulated conductor
IS 1951 Polyvinyl chloride sleeving for electrical purposes
IS 3010 Part-I appliances-connectors
IS 3010 Part-II appliances-inlets
IS 2268 Electrical call bells and buzzers for indoor use.
IS 3412 Electrical water boilers
IS 302 Light electrical appliances
IS:2882 Storage type automatic electric water heaters
IS:3202 Climate proofing of electrical equipment code of practice
IS:732 Electrical wiring installation (System voltage not exceeding 650V) code of practice.
IS:3106 Selection, installation and maintenance of fuses (System voltage not exceeding
650V) code of practice.
IS:374 Fan and regulators ceiling type, electric
IS:1258 Bayonet lamp holders
IS:2086 carriers and bases used in rewireable type electric fuses up to 650V
IS:5561 Electric power connectors
IS:2675 Enclosed distribution fuse boards and cutouts for voltage not exceeding 1000V
IS:2208 HRC Cartridge fuse link up to 650V
IS:3961 Recommended current rating for Cables PVC insulated and PVC (Part-II) Sheathed
heavy duty
IS:371 Ceiling roses
IS:5987 Selection of switches (Voltage not exceeding 1000V) Code of Practice
IS:1646 Protection for fire safety of building Electrical installation
IS:3106 Selection, Installation of fuses (Voltage not exceeding 650V)
IS:5133 Part-I Boxes for enclosure of electrical accessories steel and cast-iron boxes
IS:5133 Part-I boxes made of insulated materials
IS:5649 Adaptors for flexible steel conduits
IS:419 Fittings for rigid non-metallic conduits
IS:4160 Interlocking switch socket outlet
IS:2412 Link clips for electrical wiring
IS:2509 Rigid non-metallic conduits for electrical installation

Page 155 of 166


IS:4615 Switch socket outlet (non-Interlocking type)
IS:3854 Switches for domestic and similar purpose
IS:1293 Three pin plugs and socket outlet
IS:3914 Selection of AC induction motor starters (Voltage not exceeding 1000V)
IS:10810 Cables: method of tests
IS:5908 Method of measurement of electrical installation in buildings
IS:1554 Specifications for PVC insulated electric cables for working voltage up to and including
1100V
IS:1753 Specifications for aluminum conductor for insulated conductors
IS:3975 Mild steel wires strips and tapes for armoring of cables
IS:5831 Specifications for PVC insulations and sheath of electric cables
IS:2147 Degree of protection provided by enclosures for low voltage switchgear and control
gear
IS:4237 General requirements for switchgear and control gear for voltage not exceeding
1100Volts
IS:1886 & IS: Selection & Installation and maintenance of transformer
11028
IS:3072 Installation and maintenance of switchgear
IS:900 Installation and maintenance of induction motor
IS:1255 Installation and maintenance of paper insulated power cables (up to and including
33KV)
IS:1866 Maintenance of insulating oil
IS:3561 Specification for electrical power connectors
IS:617 Specifications for aluminum, aluminum alloy and casting for general engineering
IS:159 Busbar and Busbar connections
IS:2629 & Galvanizing
IS: 2633
IS:3480 Flexible steel conduit for Electrical wiring
IS:3837 Accessories for rigid steel conduit for electrical wiring

IS:8623 Factory built accessories of Switchgear & Control gear for voltage up to and including
1000V AC and 1200V DC
IS:4648 Electrical layout in residential buildings
IS:2501 Copper tubes for general residential purposes
IS:1259 Mild steel tubes
IS:2667 Specifications for lightning protection against building and allied structures
IS:2309 Code of practice for lightning protection against building and allied structure
IS:3043 Code of practice for earthing
IS:2274 Electrical wiring installation (Voltage exceeding 650V)
IS:1653 Rigid steel conduits for electrical wiring (revised) with amendments
IS:1915 General and safety requirements for electrical lighting fitting
IS:5316 Guide for safety procedures and practices in electric works
IS:5124 Code of practice for installation and maintenance for AC induction motor starters
(Voltage not exceeding 1000V)
IS:1180 Outdoor type three phase distribution transformer
IS:5133 Boxes for enclosures of electrical accessories

Page 156 of 166


IS 16636 Automatic Power Factor Correction (APFC) Panels for Voltage Rating upto And
Including 1000 V.
IS 12615 Energy Efficient Induction Motors - Three Phase Squirrel Cage.
IEC 61439 Low-voltage switchgear and control gear assemblies
IS 7098 Crosslinked polyethylene insulated PVC sheathed cables
IS 2705/ Current Transformers
BS 7626
IS3231,3842 Electrical Relays for Power System protection
BS142/
IEC 255
IS: 1248 Electrical Indicating Instruments
BS: 89 IEC 51
IS :722 AC Electricity Meters
BS: 2692
IEC947.4.2 Microprocessor Soft Starter
EN50081-
1,50082-2
& 60204-1
IS 3427 & Metal Enclosed Switchgear
IS 13947
MECHANICAL WORKS
BS 5135 Specification for are welding of carbon manganese steels
BS 5316 Part-2 Specification for acceptance test for centrifugal, mixed flow and
axial pumps – Test for performance and efficiency
BS 6072 Method for magnetic particle flow detection
BS 6405 Specification for non-calibrated short link steel chain (Grade 30)
for general engineering purposes: Class 1 & 2
BS 6443 Method for penetrate flow detection
ASTM A-36 Specification for Structural Steel
ASTM A-216 Specification for Steel Castings, Carbon suitable for fusion welding
for high temperature service
ASTM A-276 Specification or stainless steel and heat resisting steel bars and
shapes
ASTM A-351 Specification for castings, Austenitic – Ferric (Duplex), for
Pressure containing parts
ASTM A-743 Specification for castings, Iron – Chromium, Iron – Chromium –
Nickel and Nickel Base Corrosion Resistant for general Application
ASTM A-744 Specification for castings, Iron Chromium – Nickel, Corrosion –
Resistant
IEC – 189 Low frequency cables and wires with PVC insulation and PVC Sheath
Part 1 & 2
AWWA C 501 Cast Iron Sluice Gates
ISO 17766 Centrifugal Pumps handling
IS 14220 Open well Submersible Pump sets
IS 8418 Horizontal centrifugal self-priming pumps
IS 1710 Pumps-Vertical turbine Mixed and Axial Flow for clear cold water

Page 157 of 166


IS 6595 Horizontal centrifugal pumps for clear, cold water
IS 5 Colours for ready mixed paints and enamels
IS 210 Grey Iron Castings
IS 318 Leaded Tin Bronze Ingots and Castings
IS/IEC 60034 Three Phase Induction Motors
IS 807 Code of Practice for Design, manufacture, erection and testing
(Structural Portion) of cranes and hoists
IS 1239 Mild Steel tubes, tubular and other wrought steel fittings
IS 1536 Centrifugally Cast (Spun) iron pressure pipe for water gas and
sewage
IS 1537 Vertically cast-iron pressure pipes for water, gas and sewage
IS 1538 Specification for cast iron fittings for pressure pipes for water, gas
and sewage
IS 1554 PVC insulated (Heavy duty) electric cables
IS 2062 Steel for general structural purposes
IS 2147 Degrees of protection provided by enclosures for low voltage
switch gear and control gear
IS 3177 Code of practice of electric overhead traveling cranes and gantry
cranes other than steel work cranes
IS 3624 Vacuum and Pressure gauges
IS 3815 Point hooks with shank for general engineering purposes
BS 2910 Methods for radiographic examination of fusion welded
circumferential butt joints in steel pipes
BS 3017 Specification for mild steel forged ram shorn hooks
BS 3100 Specification for steel castings for general engineering purposes
BS 3923 Methods for ultrasonic examination of welds
BS 4360 Specification for weldable structural steels
BS 4772 Specification for ductile iron pipes and fittings
BS 4870 Specification for approval testing of welding procedures
BS 4871 Specification for approval the sting of welders working to approved
welding procedures
BS 4942 Short chain link for lifting purposes
IS 5120 Technical requirements of roto dynamic special purpose pumps
IS 5600 Horizontal / vertical non-clog type centrifugal pump for sludge handling
IS 8034 Borewell Submersible Pump
IS 7090 Guide lines for rapid mixing devices
IS 7208 Guide lines for flocculator devices
IS 10261 Requirements for clarifier equipment for waste water treatment
IS 8413 Requirements for biological treatment and equipment
IS 8413 Activated sludge process and its modifications
Part-II
IS 10037 Requirements for sludge dewatering equipment, sludge
IS 10037 Drying beds, sand, gravel and under drains
Part I
IS 6280 Specification for Sewage Screens
IS 3938 Electric Wire rope hoists

Page 158 of 166


IS 6603 Stainless steel bars and Flats
IS 2800 Code of Practice Construction and development of Tubewell Borewell
IS 11189 Methods for Tubewell development
IS 13095 Butterfly valves for general purposes
Further, following codes and standards unless specified herein shall be referred to for pipe
lines, pipe work & fittings:
IS: 210 Specification for grey iron casting
IS:290 Specification for coal tar black paint
IS:456 Code of practice for plain and reinforced concrete
IS :458 Specification for pre-cast concrete pipes (with and without
reinforcement)
IS :516 Method of test for strength of concrete
IS :638 Specification for sheet rubber jointing and rubber insertion jointing
IS :783 Code of practice for laying of concrete pipes
Code of practice for use of metal arc welding for general
IS :816 construction in mild steel
IS :1367 Technical supply conditions for threaded steel fasteners
IS :1387 General requirements for the supply of metallurgical materials
IS :1500 Method for Brinell hardness test for metallic materials
IS :1536 Specification for centrifugally cast (spun) iron pressure pipes for water, gas and
sewage
IS :1537 Specification for vertically cast-iron pressure pipes for water, gas
and sewage
IS :1538 Specification for cast iron fittings for pressure pipes for water,
gas and sewage
IS :1916 Specification for steel cylinder pipes with concrete lining
and coating
IS :2078 Method for tensile testing of grey cast iron
IS:3589 Specification for MS Spirally Welded Pipes
IS :3597 Method of tests for concrete pipes
IS :3658 Code of practice for liquid penetrant flow detection
IS :5382 Specification for rubber sealing rings for gas mains, water mains and sewers
IS :5504 Specification for spiral welded pipes
IS :6587 Specification for spun hemp yarn
IS :7322 Specification for specials for steel cylinder reinforced concrete pipes
IS:8329 Specification for DI pipes
IS:9523 Specifications for DI fittings
IS:4984 Specifications for HDPE pipeline
IS:14846 Specifications for valves
IS :783 Code of practice for laying of concrete pipes
IS :3114 Code of practice for laying of cast iron pipes
IS :3764 Excavation work - Code of Safety
IS :4127 Code of practice for laying of glazed stoneware pipes
IS :5822 Code of practice for laying of electrically welded steel pipes for
water supply.
IS :6530 Code of practice for laying of asbestos cement pressure pipes.

Page 159 of 166


Instrumentation Codes & Standard

BIS Bureau of Indian Standard


AWWA American Water work Association

ISO International Organization for Standardization

BS British Standard

IEC International Electrotechnical Commission Standards


IS 779: 1994 Indian Standard for Water Meters (Domestic Type) Specification

IS 2373: 1981 Water Meters (Bulk Type)

IS 6784:1996 Methods for Performance Testing of Water Meters (Domestic Type) (Second
Revision)
BS 7405: 1991 BS 7405 classifies closed conduit flow meters

ISO 4185:1980 Specifies a method of determining the liquid flow-rate by measuring the mass of
liquid delivered into a weighing tank in a known time interval
ISO 4064- International Organization For Standardization for Water meters for cold potable
1:2014 water and hot water
-- Part 1: Metrological and technical requirements
ISO 4064- Water meters for cold potable water and hot water
2:2014 -- Part 2: Test methods

ISO 4064- Water meters for cold potable water and hot water
3:2014 -- Part 3: Test report format

ISO 4064- Water meters for cold potable water and hot water
4:2014 -- Part 4: Non-metrological requirements not covered in ISO 4064-1

ISO 4064- Water meters for cold potable water and hot water
5:2014 -- Part 5: Installation requirements

ISO/ IEC: General requirements for the competence of testing and calibration laboratories
17025
ISO 6817 Measurement of conductive liquid flow in closed
conduit- Methods using Electromagnetic Flow meter
ISO Measurement of fluid flow in closed conduits-
12242:2012 Ultrasonic transit time flow meters
ISO 7066-2 Assessment of uncertainty in the calibration & use of flow measurement device
ISO 3834-2: Quality requirements for fusion welding of metallic materials. Comprehensive quality
2005 requirements
IS 3043-2007 Code of practice for Safety Earthing

Page 160 of 166


IS 2309-1989 Code of Practice for the protection of buildings and allied structures against
lightning.
ISO 9001:2015 Requirements for a quality management system
DNP Distributed Network Protocol

BS EN 50081 Electromagnetic Compatibility


IEEE 587 Power Supply Surge Protection

IEC 61158-2 Industrial communication networks


IS 10553-1 Requirements for chlorination equipment,
(1983) Part I: General guidelines for chlorination plants including handling, storage and
safety of chlorine cylinders and drums
IS 10553-2 Requirements for chlorination equipment,
(1983) Part 2: Vacuum feed type chlorinators

IS 10553-4 Requirements for chlorination equipment,


(1983) Part 4: Gravity feed type gaseous chlorinators

IS 10553-5 Requirements of chlorination equipment,


(1987): Part 5: Bleaching powder solution feeder displacement type
chlorinator

Abbreviations used for Instrumentation & Control


Sr. No Short Form Full Form
1 PLC Programmable Logic Controller
2 CPU Central Processing Unit
3 DI Digital Input
4 DO Digital Output
5 AI Analogue Input
6 AO Analogue Output
7 RS 485 Recommended Standard 485
8 FO Fiber Optic
9 HMI Human Machine Interface on ICP
10 OWS Operator Work Station
11 RIO Remote Input Outputs
12 ICP Instrument Control Panel
13 MCC Motor Control Centre
14 PMCC Power cum Motor Control Centre
15 UPS Uninterrupted Power Supply
16 OLR Over Load Relay
17 STR Motor Starter
18 MOV Motor Operated Valve/ Motorized Valve
Actuator
19 DCDB DC Distribution Board
20 ACDB AC Distribution Board

Page 161 of 166


21 TCP Transmission Control Protocol
22 IP Internet Protocol
23 FIELD Field Instruments
24 BKR Breaker
25 TRAFO Transformer
26 N/A Not Applicable
27 - Details shall be furnished later
28 SD Card Secured Digital Card
29 HTTP Hypertext Transfer Protocol
30 HDMI High-Definition Multimedia Interface
31 GPS Global Positioning System
32 LTE Long Term Evolution
33 Cc/ Bcc Carbon Copy/ Blind Carbon Copy
34 DSL Digital Subscriber Line
35 URL Uniform Resource Locator
36 SMS Short Message Service
37 SSL Secure Sockets Layer
38 GIF Graphics Interchange Format
39 LCD Liquid Crystal Display

Flow Unit Conversion


Sr. No Unit-1 Unit-2
1 1 Litre/ Sec = 3.6 Meter³/ Hour (M³/Hr)
2 1 Litre/ Min = 0.06 M³/Hr
3 1 Litre/ Hr = 0.001 M³/Hr
4 1000 Litre = 1 M³
5 1 Million Litter Per Day (MLD) = 1000 (M³/Hr)

Pressure Unit Conversion


Sr. No Unit-1 Unit-2
1 1 Bar = 1.01972 Kg/ Cm²
2 1 Bar = 100 kPa
3 1 Bar = 0.987 atm
4 1 Bar = 14.5038 psia
5 14.7 pounds per square inch = 0 pounds per square inch gauge (PSIG)
absolute (psia)
6 1 Megapascal (Mpa) = 10.1976 Kg/ Cm²
7 1 Millimeter Mercury (0°C) (mmHg) = 0.00136 Kg/ Cm²
8 1 Pound per Square Inch (psi) = 0.07031 Kg/ Cm²
9 10 Meter Head = 1 Kg/ Cm²

Temperature Unit Conversion


1 Degree to Fahrenheit Equation: ( T (°C) × 9/5 )+ 32 = T(°F)

Page 162 of 166


Level Unit Conversion
Sr. No Unit-1 Unit-2
1 1 Meter = 1000 mm
2 1 Meter = 100 cm
3 1 Kilo Meter = 1000 meter

Page 163 of 166


11KV FOUR POLE STRUCTURE

Page 164 of 166


11KV DOUBLE POLE STRUCTURE

Page 165 of 166


Pipe Earthing and Plate Earthing Arrangement

Page 166 of 166


Nomenclature for DP Structure

Item Description
No
01 ACSR DOG CONDUCTOR
02 LIGHTNING ARRESTOR
03 11KV STRAIN INSULATOR DISC
04 11KV INSULATOR WITH PIN -5KN
05 11KV, 200A AB SWITCH WITH EARTH SWITCH
06 11KV 25A DO FUSE
07 STAY SET
08 DANGER BOARD
09 150MM DIA GI PIPE 3M LONG
GI CHAIN LINK WIRE FENCE, 2M HEIGHT
10 VERTICAL SUPPORT
INCLINED VERTICAL SUPPORT
2 ROWS LINE WIRE
11 1.5M WIDE X 2.5 M LOCKABLE GATE
12 OUTDOOR CABLE TERMINATION KIT
13 R.S.J. POLE 175 X 85 MM SIZE WITH 11M LONG
14 ISMC CHANNEL
15 BASE PLATE FOR POLE
16 1.0M LIGHTNING SPIKE
17 ANTI-CLIMBING DEVICE
18 25X6 MM GI FLAT
Nomenclature for Four Pole Structure

Item Description
No
01 10KV, 10KA Distribution type LA
02 11KV, 200A GOD Switch with Operating Handle
03 11KV Drop out Fuse
04 11KV Disc insulator string
05 11KV Pin Insulator
06 ACSR DOG CONDUCTOR
07 Anti-Climbing Device
08 DANGER BOARD
09 STAY SET
10 R.S.J. POLE 175 X 85 MM SIZE WITH 11M LONG
11 ISMC CHANNEL
12 ISA Angle 50 x 50 x 6
GI CHAIN LINK WIRE FENCE, 2M HEIGHT
13 VERTICAL SUPPORT
INCLINED VERTICAL SUPPORT
2 ROWS LINE WIRE
14 2.5M (WIDE) x 2M (HEIGHT) Lockable Gate
15 ISMC Channel (75 x 40 x 6 mm)
- Tension Stringing Hardware suitable for Single ACSR DOG
Conductor
- Cable Clamps
- 40mm dia GI straight Length GI conduit Pipe
- 150mm dia GI straight Length GI conduit Pipe
- PG Clamps
- GI Lightning Spike of 25NB (1M long) with test link
arrangement
- Outdoor cable termination kit
- MS Base plate 400 x 400 x 8 Thk
- 25 x3 GI Flat
- Barbed Wire

You might also like