Professional Documents
Culture Documents
Pocket
Manual
Service Diagnosis
VRV Series
i
VRV Series
ii
VRV Series
iii
VRV Series
iv
VRV Series
VRVII 2
R-22
VRVII-S 3
Air Cooled
Inverter
VRVII 4
M(A)
VRVII-S 5
Water
VRV-WII 6
Cooled
R-410A VRVIII 7
Water
VRV-WIII 11
Cooled
1
2
Indoor Units
Type Model Name Symbol
Ceiling Mounted Cassette Type (Double Flow) FXC 20L 25L 32L 40L 50L 63L 80L - 125L - -
Ceiling Mounted Cassette Type (Multi Flow) FXF - 25L 32L 40L 50L 63L 80L 100L 125L - -
1. R-22
Ceiling Mounted Cassette Corner Type FXK - 25L 32L 40L - 63L - - - - -
FXD-PVE 20P 25P 32P - - - - - - - -
FXD-PVET 20P 25P 32P - - - - - - - - VE
Slim Ceiling Mounted Duct Type
FXD-MVE 20M 25M 32M 40M 50M 63M - - - - -
FXD-MVET 20M 25M 32M 40M 50M 63M - - - - -
Applicable Models
Ceiling Mounted Low Silhouette Duct Type FXYD 20KA 25KA 32KA 40KA 50KA 63KA - - - - -
Ceiling Mounted Built-in Type FXS 20L 25L 32L 40L 50L 63L 80L 100L 125L - -
1-1. VRVII M(A) Series
Ceiling Mounted Built-in Type (Rear Suction) FXYB 20K 25K 32K 40K 50K 63K 80K 100K 125K - - V1
Ceiling Mounted Duct Type FXM - - - 40L 50L 63L 80L 100L 125L 200L 250L
Ceiling Suspended Type FXH - - 32L - - 63L - 100L -
Wall Mounted Type FXA 20L 25L 32L 40L 50L 63L - - - VE
Floor Standing Type FXL 20L 25L 32L 40L 50L 63L - - -
Concealed Floor Standing Type FXN 20L 25L 32L 40L 50L 63L - - -
Outdoor Units
Type Model Name Symbol
5M(A) 8M(A) 10M(A) 12M(A) 14M(A) 16M(A) 18M(A) 20M(A) 22M(A) 24M(A) 26M(A) Y1(E)
Heat Pump RXY YL(E)
28M(A) 30M(A) 32M(A) 34M(A) 36M(A) 38M(A) 40M(A) 42M(A) 44M(A) 46M(A) 48M(A) TL(E)
5M(A) 8M(A) 10M(A) 12M(A) 14M(A) 16M(A) 18M(A) 20M(A) 22M(A) 24M(A) 26M(A)
Cooling Only RX Y1
28M(A) 30M(A) 32M(A) 34M(A) 36M(A) 38M(A) 40M(A) 42M(A) 44M(A) 46M(A) 48M(A)
VRV Series
Indoor Units
Type Model Name Symbol
Ceiling Mounted Cassette Type (Double Flow) FXC 20L 25L 32L 40L 50L 63L 80L - 125L
Ceiling Mounted Cassette Type (Multi Flow) FXF - 25L 32L 40L 50L 63L 80L 100L 125L
VRV Series
Ceiling Mounted Cassette Corner Type FXK - 25L 32L 40L - 63L - - -
VE
Slim Ceiling Mounted Duct Type FXD 20M 25M 32M 40M 50M 63M - - -
Ceiling Mounted Low Silhouette Duct Type FXYD 20KA 25KA 32KA 40KA 50KA 63KA - - -
Ceiling Mounted Built-in Type FXS 20L 25L 32L 40L 50L 63L 80L 100L 125L
Ceiling Mounted Built-in Type (Rear Suction) FXYB 20K 25K 32K 40K 50K 63K 80K 100K 125K V1
Ceiling Mounted Duct Type FXM - - - 40L 50L 63L 80L 100L 125L
1-2. VRVII-S M Series
Outdoor Units
Type Model Name Symbol
Heat Pump RXYM 4M 5M 6M VM
Cooling Only RXM 4M 5M 6M VMT
3
4
Indoor Units
Type Model Name Symbol
Ceiling Mounted Cassette Type (Double Flow) FXCQ 20M 25M 32M 40M 50M 63M 80M - 125M - -
Ceiling Mounted Cassette Type (Multi Flow) FXFQ - 25M 32M 40M 50M 63M 80M 100M 125M - -
Ceiling Mounted Cassette Corner Type FXKQ - 25MA 32MA 40MA - 63MA - - - - -
2. R-410A
Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA - - - - -
Floor Standing Type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA - - - - -
Concealed Floor Standing Type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA - - - - -
Ceiling Suspended Cassette Type FXUQ - - - - - - 71MA 100MA 125MA - - V1
Connection Unit BEVQ - - - - - - 71MA 100MA 125MA - - VE
Outdoor Units
Type Model Name Symbol
5MA 8MA 10MA 12MA 14MA 16MA 18MA 20MA 22MA 24MA 26MA Y1(E)
Heat Pump RXYQ YL(E)
28MA 30MA 32MA 34MA 36MA 38MA 40MA 42MA 44MA 46MA 48MA TL(E)
5MA 8MA 10MA 12MA 14MA 16MA 18MA 20MA 22MA 24MA 26MA
Cooling Only RXQ Y1
28MA 30MA 32MA 34MA 36MA 38MA 40MA 42MA 44MA 46MA 48MA
8M 10M 12M 14M 16M 18M 20M 22M 24M 26M 28M
Heat Recovery REYQ Y1B
30M 32M 34M 36M 38M 40M 42M 44M 46M 48M
VRV Series
Indoor Units
Type Model Name Symbol
Ceiling Mounted Cassette Type (Double Flow) FXCQ 20M 25M 32M 40M 50M 63M 80M - 125M
VRV Series
Ceiling Mounted Cassette Type (Multi Flow) 600X600 FXZQ 20M 25M 32M 40M 50M - - - -
Ceiling Mounted Cassette Type (Multi Flow) FXFQ - 25M 32M 40M 50M 63M 80M 100M 125M
Ceiling Mounted Casette Corner Type FXKQ - 25M 32M 40M - 63M - - -
Slim Ceiling Mounted Built-in Type (L.S.P) FXDQ 20N 25N 32N 40N 50N 63N - - -
Ceiling Mounted Built-in Type (M.S.P) FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M VE
Ceiling Mounted Duct Type FXMQ - - - 40M 50M 63M 80M 100M 125M
2-2. VRVII-S M Series
Outdoor Units
Type Model Name Symbol
Heat Pump RXYMQ 4M 5M 6M V4A
5
6
Indoor Units
Type Model Name Symbol
Ceiling Mounted Cassette Type (Double Flow) FXCQ 20M 25M 32M 40M 50M 63M 80M - 125M - -
Ceiling Mounted Cassette Type (Multi Flow) FXFQ - 25M 32M 40M 50M 63M 80M 100M 125M - -
Ceiling Mounted Cassette Corner Type FXKQ - 25MA 32MA 40MA - 63MA - - - - -
FXDQ-PVE 20P 25P 32P - - - - - - - -
FXDQ-PVET 20P 25P 32P - - - - - - - -
Slim Ceiling Mounted Duct Type
FXDQ-NAVE 20NA 25NA 32NA 40NA 50NA 63NA - - - - -
FXDQ-NVET 20N 25N 32N 40N 50N 63N - - - - - VE
Ceiling Mounted Built-in Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M - -
2-3. VRV-WII M Series
Ceiling Mounted Duct Type FXMQ - - - 40MA 50MA 63MA 80MA 100MA 125MA 200MA 250MA
Ceiling Suspended Type FXHQ - - 32MA - - 63MA - 100MA - - -
Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA - - - - -
Floor Standing Type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA - - - - -
Concealed Floor Standing Type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA - - - - -
Ceiling Suspended Cassette Type FXUQ - - - - - - 71MA 100MA 125MA - - V1
Connection Unit BEVQ - - - - - - 71MA 100MA 125MA - - VE
Outside Units
Type Model Name Symbol
Y1
Heat Pump RWEYQ 10M 20M 30M YL
TL
VRV Series
Indoor Units
Type Model Name Symbol
Ceiling Mounted Cassette Type (Round Flow) FXFQ - 25P 32P 40P 50P 63P 80P 100P 125P - - -
Ceiling Mounted Cassette Type (Compact Multi Flow) FXZQ 20M 25M 32M 40M 50M - - - - - - -
VRV Series
Ceiling Mounted Cassette Type (Double Flow) FXCQ 20M 25M 32M 40M 50M 63M 80M - 125M - - -
Ceiling Mounted Cassette Corner Type FXKQ - 25MA 32MA 40MA - 63MA - - - - - -
FXDQ-PBVE 20PB 25PB 32PB - - - - - - - - -
FXDQ-PBVET 20PB 25PB 32PB - - - - - - - - -
Slim Ceiling Mounted Duct Type
FXDQ-NBVE - - - 40NB 50NB 63NB - - - - - -
FXDQ-NBVET - - - 40NB 50NB 63NB - - - - - -
VE
Ceiling Mounted Built-in Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100MA 125M - - -
2-4. VRVIII P(A) Series
7
8
Outdoor Units
Type Model Name Symbol B
5P(A) 8P(A) 10P(A) 12P(A) 14P(A) 16P(A) 18P(A) 20P(A) 22P(A) 24P(A) 26P(A)
Y1(E)
28P(A) 30P(A) 32P(A) 34P(A) 36P(A) 38P(A) 40P(A) 42P(A) 44P(A) 46P(A) 48P(A)
YL(E)
50P(A) 52P(A) 54P(A)
Heat Pump RXYQ
5P 8P 10P 12P 14P 16P 18P 20P 22P 24P 26P
28P 30P 32P 34P 36P 38P 40P 42P 44P 46P 48P TL(E)
50P 52P 54P
5P(A) 8P(A) 10P(A) 12P(A) 14P(A) 16P(A) 18P(A) 20P(A) 22P(A) 24P(A) 26P(A)
Cooling Only RXYQ 28P(A) 30P(A) 32P(A) 34P(A) 36P(A) 38P(A) 40P(A) 42P(A) 44P(A) 46P(A) 48P(A) Y1
50P(A) 52P(A) 54P(A)
8P 10P 12P 14P 16P 18P 20P 22P 24P 26P 28P
Heat Recovery REYQ Y1
30P 32P 34P 36P 38P 40P 42P 44P 46P 48P
VRV Series
VRV Series
9
Indoor Units
10
Type Model Name Symbol
Ceiling Mounted Cassette Type (Double Flow) FXCQ 20M 25M 32M 40M 50M 63M 80M - 125M
Ceiling Mounted Cassette Type (Multi Flow) FXFQ - 25M 32M 40M 50M 63M 80M 100M 125M
Ceiling Mounted Cassette Corner Type FXKQ - 25MA 32MA 40MA - 63MA - - -
FXDQ-PVE 20P 25P 32P - - - - - -
FXDQ-PVET 20P 25P 32P - - - - - -
Slim Ceiling Mounted Duct Type
FXDQ-NAVE 20NA 25NA 32NA 40NA 50NA 63NA - - -
FXDQ-NVET 20N 25N 32N 40N 50N 63N - - - VE
2-6. VRVIII-S P Series
Ceiling Mounted Built-in Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M
Ceiling Mounted Duct Type FXMQ - - - 40MA 50MA 63MA 80MA 100MA 125MA
Ceiling Suspended Type FXHQ - - 32MA - - 63MA - 100MA -
Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA - - -
Floor Standing Type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA - - -
Concealed Floor Standing Type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA - - -
Ceiling Suspended Cassette Type FXUQ - - - - - - 71MA 100MA 125MA V1
Connection Unit BEVQ - - - - - - 71MA 100MA 125MA VE
Outdoor Units
Type Model Name Symbol
Heat Pump RXYMA 4P 5P 6P
VE
Cooling Only RXMQ 4P 5P 6P
VRV Series
Indoor Units
Type Model Name Symbol
Ceiling Mounted Cassette Type (Round Flow) FXFQ - 25P 32P 40P 50P 63P 80P 100P 125P - - -
Ceiling Mounted Cassette Type (Compact Multi Flow) FXZQ 20M 25M 32M 40M 50M - - - - - -
VRV Series
Ceiling Mounted Cassette Type (Double Flow) FXCQ 20M 25M 32M 40M 50M 63M 80M - 125M - - -
Ceiling Mounted Cassette Corner Type FXKQ - 25MA 32MA 40MA - 63MA - - - - - -
FXDQ-PBVE 20PB 25PB 32PB - - - - - - - - -
2-7. VRV-WIII
Outside Units
Type Model Name Symbol
8P 10P 16P 18P 20P
Y1
Heat Pump 24P 26P 28P 30P -
RWEYQ
Heat Recovery - 10P - - 20P
YL, TL
- - - 30P -
11
Symptom-based Troubleshooting
1. Symptom-based
Troubleshooting
Symptom Supposed Cause Countermeasure
1 The system does not start Blowout of Turn OFF the power
operation at all. fuse(s) supply and then
replace the fuse(s).
Cutout of • If the knob of any
breaker(s) breaker is in its
OFF position,
turn ON the
power supply.
• If the knob of any
circuit breaker is
in its tripped
position, do not
turn ON the
power supply.
ON
Knob
Tripped
OFF
Circuit breaker
Power failure After the power
failure is reset,
restart the system.
2 The system starts operation but Blocked air inlet or outlet Remove
makes an immediate stop. of indoor or outdoor unit obstacle(s).
Clogged air Clean the air
filter(s) filter(s).
3 The system does not cool or Blocked air inlet or outlet Remove
heat air well. of indoor or outdoor unit obstacle(s).
Clogged air filter(s) Clean the air filter(s).
Enclosed outdoor unit(s) Remove the enclosure.
Improper set Set the temperature to
temperature a proper degree.
Airflow rate set to Set it to a proper
"LOW" airflow rate.
Improper direction Set it to a proper
of air diffusion direction.
Open window(s) or door(s) Shut it tightly.
[In cooling] Direct sunlight Hang curtains or
received shades on windows.
[In cooling] Too many persons The model must
staying in a room be selected to
[In cooling] Too many heat sources match the air
(e.g. OA equipment) conditioning load.
located in a room
12
Symptom-based Troubleshooting
13
Symptom-based Troubleshooting
14
Symptom-based Troubleshooting
15
Symptom-based Troubleshooting
16
Symptom-based Troubleshooting
17
Troubleshooting by Remote Controller
2. Troubleshooting by Remote
Controller
2.1 The INSPECTION / TEST
Button
The following modes can be selected by using the
[Inspection/Test Operation] button on the remote control.
Service data can be obtained.
• Error code history
• Temperature data of various sections
Indoor unit settings Service settings can be made.
can be made • Forced fan ON
• Filter sign time • Airflow direction/Airflow rate setting
Depress
• Airflow direction
Inspection/Test Operation
• Others
button for more than 4
Field seconds.
setting Service
mode mode
Depress Press
Inspection/Test Operation Inspection/Test Operation
button for more than 4 button once.
seconds.
Normal
Press
Inspection/Test Operation
mode Press
button once. Inspection/Test Operation
button once.
Or after 30 minutes
After 10 seconds
Test
Inspection operation
mode Press mode
Inspection/Test Operation
button once.
Following codes can Thermostat is forcibly
be checked. turned ON.
• Error codes
• Indoor model code
• Outdoor model code
18
Troubleshooting by Remote Controller
Display of indoor
unit for which an
error has been
detected
Inspection
display
Error code
Inspection/Test
button
Note:
1. Pressing the INSPECTION/TEST button will blink the
check indication.
2. While in service mode, holding down the ON/OFF
button for a period of 5 seconds or more will clear the
error history indication shown above. In this case, on
the codes display, the error code will blink twice and
then change to “00” (= Normal), the Unit No. will
change to “0”, and the operation mode will
automatically switch from service mode to normal
mode (displaying the set temperature).
19
Troubleshooting by Remote Controller
Screen
Operation lamp
20
Troubleshooting by Remote Controller
Error code
Applicable
model names
21
Troubleshooting by Remote Controller
22
Troubleshooting by Remote Controller
Normal status
Enters inspection mode from
normal status when the INSPECTION/
TEST button is pressed.
If no button is pressed
for 1 minute, equipment
returns to normal status.
3
Press
MODE
When MODE selector selector
button is pressed or button.
no button is pressed
for 1 minute, equipment
returns to normal status.
If no button is pressed
for 1 minute, equipment
returns to normal status.
23
24
Error
Code
Error Contents FXC FXF FXK FXD FXYD FXS FXYB
FXM40- FXM200/
125L 250L
FXH FXA FXL FXN
Reference
Page
2.4
A0 External Protection Device
R-22
h h h h h h h h h h h h h 46
Abnormality
A1 PCB Abnormality h h h h h h h h h h h h h 48
A3 Drain Level Control
h h h h h h h h 49
System (S1L) Abnormality
A6 Fan Motor (M1F) Lock,
h h h 52
Overload
2.4.1 Indoor Unit
Air Abnormality
CJ Room Temperature
Thermistor in Remote h h h h h h h h h h h h h 90
Controller Abnormality
25
∗ For the model names, refer to P.2~11.
26
Error Reference
Error Contents FXCQ FXZQ FXFQ FXKQ FXDQ FXSQ FXMQ-P FXMQ-MA FXHQ FXAQ FXLQ FXNQ FXUQ
Code Page
External Protection Device
A0 h h h h h h h h h h h h h 46
Abnormality
R-410A
A1 PCB Abnormality h h h h h h h h h h h h h 48
Drain Level Control
A3 h h h h h h 49
System (S1L) Abnormality
Fan Motor (M1F) Lock,
A6 h h h 52
Overload
Indoor Unit Fan Motor
A6 h 55
Abnormality
Overload / Overcurrent /
A6 Lock of Indoor Unit Fan h 57
Motor
Overload / Overcurrent /
A6 Lock of Indoor Unit Fan h 61
Motor
Swing Flap Motor (M1S)
A7 h h h h 63
Abnormality
Power Supply Voltage
A8 h 66
Abnormality
Electronic Expansion
A9 h h h h h h h h h h h h h 68
Valve Coil Abnormality
Combination Abnormality
C6 (between Indoor unit PCB h 82
and Fan PCB)
Thermistor for Suction Air
C9 h h h h h h h h h h h h h 84
Abnormality
Thermistor for Discharge
CA h h h h h h h h h h h h h 86
Air Abnormality
Humidity Sensor System
CC h 88
Abnormality
Room Temperature
CJ Thermistor in Remote h h h h h h h h h h h h h 90
Controller Abnormality
27
∗ For the model names, refer to P.2~11.
28
Refrigerant R-22 R-410A
Reference
Series VRVII VRVII-S VRVII VRVIII VRV-WII VRV-WIII VRVII-S VRVIII-S VRVIII-Q
Page
Error Contents M(A) M M(A) P(A) M P M P P
E1 PCB Abnormality h h h h h h h h h 92
E2 Earth Leakage by Leak Detection PCB Assy h h h h 94
E3 Actuation of High Pressure Sensor h h h h 97
Abnormal Discharge Pressure h h h h h 99
E4 Actuation of Low Pressure Sensor h h h h 102
Abnormal Suction Pressure h h h h h 104
2.4.2 Outdoor Unit
29
30
Refrigerant R-22 R-410A
Reference
Series VRVII VRVII-S VRVII VRVIII VRV-WII VRV-WIII VRVII-S VRVIII-S VRVIII-Q
Page
Error Contents M(A) M M(A) P(A) M P M P P
J8 Thermistor System Abnormality h 178
J9 Subcooling Heat Exchanger Gas Pipe Thermistor Abnormality h h h h h h h h h 180
JA High Pressure Sensor Abnormality h h h 182
Discharge Pipe Pressure Sensor Abnormality h h h h h h 185
JC Low Pressure Sensor Abnormality h h h 188
Suction Pipe Pressure Sensor Abnormality h h h h h h 191
L1 Inverter PCB Abnormality h 194
Inverter PCB Abnormality h 197
Inverter PCB Abnormality h 200
L4 Inverter Radiation Fin Temperature
h 202
Rise Abnormality
Inverter Radiation Fin Temperature
h h h h h h 205
Rise Abnormality
L5 Momentary Overcurrent of Inverter Compressor h 207
Momentary Overcurrent of Inverter Compressor h h h h h h h h 210
L8 Momentary Overcurrent of Inverter Compressor h 213
Momentary Overcurrent of Inverter Compressor h h h h h h h h 216
Troubleshooting by Remote Controller
Refrigerant R-22 R-410A
Reference
Series VRVII VRVII-S VRVII VRVIII VRV-WII VRV-WIII VRVII-S VRVIII-S VRVIII-Q
Page
Error Contents M(A) M M(A) P(A) M P M P P
L9 Inverter Compressor Startup Failure h 219
Inverter Compressor Startup Failure h h h h h h h h 223
LC Transmission Error between
h h 226
Inverter and Control PCB
Transmission Error between
h h h h h 229
Inverter and Control PCB
Transmission Error between
h h 231
Inverter and Control PCB
Troubleshooting by Remote Controller
31
32
Refrigerant R-22 R-410A
Reference
Series VRVII VRVII-S VRVII VRVIII VRV-WII VRV-WIII VRVII-S VRVIII-S VRVIII-Q
Page
Error Contents M(A) M M(A) P(A) M P M P P
PJ Field Setting Abnormality after
Replacing Main PCB or h h 247
Combination of PCB Abnormality
Field Setting Abnormality after
Replacing Main PCB or h h 249
Combination of PCB Abnormality
U0 Refrigerant Shortage Alert h h h 250
Refrigerant Shortage Alert h h 253
Refrigerant Shortage Alert h h h h 256
U1 Reverse Phase, Open Phase h h h h h h 259
U2 Power Supply Insufficient or
h 261
Instantaneous Error
Power Supply Insufficient or
h 266
Instantaneous Error
Power Supply Insufficient or
h 269
Instantaneous Error
Power Supply Insufficient or
h 272
Instantaneous Error
Power Supply Insufficient or
h h h 277
Instantaneous Error
Troubleshooting by Remote Controller
Refrigerant R-22 R-410A
Reference
Series VRVII VRVII-S VRVII VRVIII VRV-WII VRV-WIII VRVII-S VRVIII-S VRVIII-Q
Page
Error Contents M(A) M M(A) P(A) M P M P P
U2 Power Supply Insufficient or
h h 280
Instantaneous Error
U3 Check Operation is not Executed h h h h h h h h h 283
U4 Transmission Error between Indoor
h 285
Units and Outdoor Units
Transmission Error between Indoor
h h 289
Units and Outdoor Units
Transmission Error between Indoor
h h h h h h 294
Units and Outdoor Units
Troubleshooting by Remote Controller
33
34
Refrigerant R-22 R-410A
Reference
Series VRVII VRVII-S VRVII VRVIII VRV-WII VRV-WIII VRVII-S VRVIII-S VRVIII-Q
Page
Error Contents M(A) M M(A) P(A) M P M P P
UA Improper Combination of Indoor and Outdoor
h h 321
Units, Indoor Units and Remote Controller
Improper Combination of Indoor and Outdoor
h 325
Units, Indoor Units and Remote Controller
Improper Combination of Indoor and Outdoor
h h h h h h 332
Units, Indoor Units and Remote Controller
UC Address Duplication of Centralized
h h h h h h h h h 335
Controller
UE Transmission Error between
h h h h h h h h h 336
Centralized Controller and Indoor Unit
UF System is not Set yet h h h h h h h h h 341
UH System Abnormality, Refrigerant
h h h h h h h h h 343
System Address Undefined
Troubleshooting by Remote Controller
Troubleshooting by Remote Controller
35
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
AH - 03 Transmission error (between Check for the connection of the
the self-cleaning decoration harness connector between the
panel and the indoor unit) panel PCB and the indoor unit
[when the self-cleaning PCB.
decoration panel is mounted]
AH - 04 Dust detection sensor error Check for the connections of the
[when the self-cleaning connector X12A on the panel
decoration panel is mounted] PCB and the connectors X18A
and X19A on the sensor PCB.
AH - 05 Dust collection sign error Check for clogging with dust at
[when the self-cleaning the dust collection port as well as
decoration panel is mounted] in the brush unit, S-shaped pipe,
and dust box. Furthermore,
check for any stains of the light
receiving and emitting parts of
the infrared unit.
AH - 06 Air filter rotation error Check for anything getting in the
[when the self-cleaning way of rotating the filter (e.g. the
decoration panel is mounted] filter comes off or the drive gear
is clogged with foreign matters).
AH - 07 Damper rotation error The damper does not rotate
[when the self-cleaning normally. Check for any foreign
decoration panel is mounted] matters around the damper and
for the operation of the gear and
limit switch.
AH - 08 Filter self-cleaning operation The unit has not yet completed
error the filter self-cleaning operation
[when the self-cleaning even after the lapse of specified
decoration panel is mounted] period of time. Check for any
external noise, etc.
AH - 09 Filter self-cleaning operation The unit has been put into a state
start disabled error in which the filter self-cleaning
[when the self-cleaning operation is disabled. Check the
decoration panel is mounted] unit for the operating conditions.
AJ - 01 Capacity setting error There is an error in the capacity
setting of the indoor unit PCB.
AJ - 02 Electronic expansion valve There is a fault in the setting of
setting error the gear type electronic
expansion valve/direct acting
type electronic expansion valve.
C1 - 01 Transmission error (between Check for the conditions of
indoor unit PCB and the PCB transmission between the indoor
for the fan) unit PCB and the PCB for the
fan.
36
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
C6 - 01 Faulty combination of indoor A combination of indoor unit PCB
unit PCB and the PCB for the and the PCB for the fan is faulty.
fan Check whether the capacity
setting adaptor is correct and the
type of the PCB for the fan is
correct.
U4 - 01 Indoor-Outdoor transmission Refer to the “U4” flow chart.
error
UA - 13 Refrigerant type error The type of refrigerant used for
the indoor unit is different from
that used for the outdoor unit.
UA - 15 Not applicable for self- An outdoor unit is not applicable
cleaning decoration panel for the self-cleaning decoration
[when the self-cleaning panel is connected.
decoration panel is mounted]
37
Troubleshooting by Remote Controller
38
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
E7 - 01 Fan motor 1 lock (Master)
E7 - 02 Fan motor 2 lock (Master)
E7 - 05 Fan motor 1 instantaneous Refer to the following to make a
overcurrent (Master) diagnosis of the fan motor of the
E7 - 06 Fan motor 2 instantaneous relevant unit.
overcurrent (Master)
E7 - 09 Fan motor 1 IPM error
(Master)
E7 - 10 Fan motor 2 IPM error
(Master)
E7 - 13 Fan motor 1 lock (Slave 1) { For fan motor lock, refer to
E7 - 14 Fan motor 2 lock (Slave 1) E7-01, -02, -13, -14, -25,
and -26.
E7 - 17 Fan motor 1 instantaneous
overcurrent (Slave 1)
E7 - 18 Fan motor 2 instantaneous
overcurrent (Slave 1)
E7 - 21 Fan motor 1 IPM error (Slave 1)
{ For instantaneous
E7 - 22 Fan motor 2 IPM error (Slave 1) overcurrent, refer to E7-05,
E7 - 25 Fan motor 1 lock (Slave 2) -06, -17, -18, -29, and -30.
E7 - 26 Fan motor 2 lock (Slave 2)
E7 - 29 Fan motor 1 instantaneous
overcurrent (Slave 2)
E7 - 30 Fan motor 2 instantaneous
{ For IPM error, refer to E7-09,
overcurrent (Slave 2)
-10, -21, -22, -33, and -34.
E7 - 33 Fan motor 1 IPM error (Slave 2)
E7 - 34 Fan motor 2 IPM error (Slave 2)
E9 - 01 Electronic expansion valve 1 coil error (Master) Refer to the “E9” flow chart of
each manual and make a
E9 - 04 Electronic expansion valve 2 coil error (Master)
diagnosis of the relevant
E9 - 05 Electronic expansion valve 1 coil error (Slave 1) electronic expansion valve of the
E9 - 07 Electronic expansion valve 2 coil error (Slave 1) relevant unit based on the Error
code shown to the left.
E9 - 08 Electronic expansion valve 1 coil error (Slave 2)
E9 - 10 Electronic expansion valve 2 coil error (Slave 2)
F3 - 01 Discharge pipe temperature Refer to the “F3” flow chart of
error (Master) each manual and make a
diagnosis of the relevant unit
F3 - 03 Discharge pipe temperature
based on the Error code shown
error (Slave 1)
to the left.
F3 - 05 Discharge pipe temperature
error (Slave 2)
39
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
F6 - 02 Excess refrigerant charge Excess refrigerant charge was
error detected during test run.
F6 - 03 Excess refrigerant charge Excess refrigerant charge was
warning detected during operation other
than test run.
H7 - 01 Fan motor 1 signal error Refer to the “H7” flow chart of
(Master) each manual and make a
diagnosis of the relevant unit
H7 - 02 Fan motor 2 signal error
based on the Error code shown
(Master)
to the left.
H7 - 05 Fan motor 1 signal error
(Slave 1)
H7 - 06 Fan motor 2 signal error
(Slave 1)
H7 - 09 Fan motor 1 signal error
(Slave 2)
H7 - 10 Fan motor 2 signal error
(Slave 2)
H9 - 01 Faulty outdoor air thermistor Refer to the “H9” flow chart of
(Master) each manual and make a
diagnosis of the relevant unit
H9 - 02 Faulty outdoor air thermistor
(Slave 1) based on the Error code shown
to the left.
H9 - 03 Faulty outdoor air thermistor
(Slave 2)
J2 - 01 Faulty current sensor Refer to the “J2” flow chart of
(Master: STD compressor 1) each manual and make a
diagnosis of the relevant
J2 - 02 Faulty current sensor
compressor of the relevant unit
(Master: STD compressor 2)
based on the Error code shown
J2 - 03 Faulty current sensor (Slave to the left.
1: STD compressor 1)
J2 - 04 Faulty current sensor (Slave
1: STD compressor 2)
J2 - 05 Faulty current sensor (Slave
2: STD compressor 1)
J2 - 06 Faulty current sensor (Slave
2: STD compressor 2)
J2 - 07 Current sensor error
(System)
40
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
J3 - 01 Faulty discharge pipe Refer to the “J3” flow chart of
thermistor 1 (Master: INV. each manual and make a
compressor) diagnosis of the relevant
compressor of the relevant unit
J3 - 02 Faulty discharge pipe
based on the Error code shown
thermistor 2 (Master: STD
to the left.
compressor 1)
J3 - 03 Faulty discharge pipe
thermistor 3 (Master: STD
compressor 2)
J3 - 04 Faulty discharge pipe
thermistor 1 (Slave 1: INV.
compressor)
J3 - 05 Faulty discharge pipe
thermistor 2 (Slave 1: STD
compressor 1)
J3 - 06 Faulty discharge pipe
thermistor 3 (Slave 1: STD
compressor 2)
J3 - 07 Faulty discharge pipe
thermistor 1 (Slave 2: INV.
compressor)
J3 - 08 Faulty discharge pipe
thermistor 2 (Slave 2: STD
compressor 1)
J3 - 09 Faulty discharge pipe
thermistor 3 (Slave 2: STD
compressor 2)
J5 - 01 Faulty suction pipe Refer to the “J5” flow chart of
thermistor (Master) each manual and make a
diagnosis of the relevant
J5 - 02 Faulty accumulator inlet
thermistor of the relevant unit
thermistor (Master)
based on the Error code shown
J5 - 03 Faulty suction pipe to the left.
thermistor (Slave 1)
J5 - 04 Faulty accumulator inlet
thermistor (Slave 1)
J5 - 05 Faulty suction pipe
thermistor (Slave 2)
J5 - 06 Faulty accumulator inlet
thermistor (Slave 2)
41
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
J6 - 01 Faulty heat exchanger Refer to the “J6” flow chart of
thermistor (Master) each manual and make a
J6 - 02 Faulty heat exchanger diagnosis of the relevant
thermistor based on the Error
thermistor (Slave 1)
code shown to the left.
J6 - 03 Faulty heat exchanger
thermistor (Slave 2)
J7 - 01 Faulty liquid pipe thermistor Refer to the “J7” flow chart of
(Master) each manual and make a
J7 - 02 Faulty liquid pipe thermistor diagnosis of the relevant
thermistor based on the Error
(Slave 1)
code shown to the left.
J7 - 03 Faulty liquid pipe thermistor
(Slave 2)
J9 - 01 Faulty subcooling heat Refer to the “J9” flow chart of
exchanger outlet thermistor each manual and make a
(Master) diagnosis of the relevant
thermistor based on the Error
J9 - 02 Faulty subcooling heat
code shown to the left.
exchanger outlet thermistor
(Slave 1)
J9 - 03 Faulty subcooling heat
exchanger outlet thermistor
(Slave 2)
JA - 01 Faulty high pressure sensor Refer to the “JA” flow chart of
(Master) each manual and make a
diagnosis of the relevant sensor
JA - 02 Faulty high pressure sensor
based on the Error code shown
(Slave 1)
to the left.
JA - 03 Faulty high pressure sensor
(Slave 2)
JC - 01 Faulty low pressure sensor Refer to the “JC” flow chart of
(Master) each manual and make a
diagnosis of the relevant sensor
JC - 02 Faulty low pressure sensor
based on the Error code shown
(Slave 1)
to the left.
JC - 03 Faulty low pressure sensor
(Slave 2)
L1 - 01 Instantaneous overcurrent The inverter PCB may be faulty.
(Master: Inverter PCB) Refer to the “L1” flow chart of
each manual and make a
L1 - 02 Current sensor error (Master:
diagnosis of the relevant unit
Inverter PCB)
based on the Error code shown
L1 - 03 Current offset error (Master: to the left.
Inverter PCB)
42
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
L1 - 04 IGBT error (Master: Inverter The inverter PCB may be faulty
PCB) or a PCB other than the specified
one is mounted. Refer to the “L1”
flow chart of each manual and
make a diagnosis of the relevant
unit based on the Error code
shown to the left.
L1 - 07 Instantaneous overcurrent The inverter PCB may be faulty.
(Slave 1: Inverter PCB) Refer to the “L1” flow chart of
each manual and make a
L1 - 08 Current sensor error (Slave
diagnosis of the relevant unit
1: Inverter PCB)
based on the Error code shown
L1 - 09 Current offset error (Slave 1: to the left.
Inverter PCB)
L1 - 10 IGBT error (Slave 1: Inverter The inverter PCB may be faulty
PCB) or a PCB other than the specified
one is mounted.
Refer to the “L1” flow chart of
each manual and make a
diagnosis of the relevant unit
based on the Error code shown
to the left.
L1 - 12 Instantaneous overcurrent The inverter PCB may be faulty.
(Slave 2: Inverter PCB) Refer to the “L1” flow chart of
each manual and make a
L1 - 13 Current sensor error (Slave
diagnosis of the relevant unit
2: Inverter PCB)
based on the Error code shown
L1 - 14 Current offset error (Slave 2: to the left.
Inverter PCB)
L1 - 15 IGBT error (Slave 2: Inverter The inverter PCB may be faulty
PCB) or a PCB other than the specified
one is mounted.
Refer to the “L1” flow chart of
each manual and make a
diagnosis of the relevant unit
based on the Error code shown
to the left.
L4 - 01 Radiation fin temperature Refer to the “L4” flow chart of
rise (Master: Inverter PCB) each manual and make a
diagnosis of the relevant unit
L4 - 02 Radiation fin temperature
based on the Error code shown
rise (Slave 1: Inverter PCB)
to the left.
L4 - 03 Radiation fin temperature
rise (Slave 2: Inverter PCB)
L5 - 03 Current offset error (Master) Refer to the “L5” flow chart of each
manual and make a diagnosis of
L5 - 05 Current offset error (Slave 1)
the relevant unit based on the
L5 - 07 Current offset error (Slave 2) Error code shown to the left.
43
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
L8 - 03 INV. compressor Refer to the “L8” flow chart of
instantaneous overcurrent each manual and make a
error (Master) diagnosis of the relevant
compressor of the relevant unit
L8 - 06 INV. compressor
based on the Error code shown
instantaneous overcurrent
to the left.
error (Slave 1)
L8 - 07 INV. compressor
instantaneous overcurrent
error (Slave 2)
L9 - 01 INV. compressor startup Refer to the “L9” flow chart of
failure (Master) each manual and make a
diagnosis of the relevant
L9 - 05 INV. compressor startup
compressor of the relevant unit
failure (Slave 1)
based on the Error code shown
L9 - 06 INV. compressor startup to the left.
failure (Slave 2)
LC - 01 Transmission error [between Refer to the “LC1” flow chart of
INV. PCB and main PCB] each manual and make a
(Master) diagnosis of the relevant unit
based on the Error code shown
LC - 06 Transmission error [between
to the left.
INV. PCB and main PCB]
(Slave 1)
LC - 08 Transmission error [between
INV. PCB and main PCB]
(Slave 2)
P1 - 01 Unbalanced power supply Refer to the “P1” flow chart of
voltage (Master) each manual and make a
P1 - 02 Unbalanced power supply diagnosis of the relevant unit
based on the Error code shown
voltage (Slave 1)
to the left.
P1 - 03 Unbalanced power supply
voltage (Slave 2)
PJ - 04 Faulty combination of INV. Refer to the “PJ” flow chart of
PCB (Master) each manual and make a
PJ - 05 Faulty combination of INV. diagnosis of the relevant unit
based on the Error code shown
PCB (Slave 1)
to the left.
PJ - 06 Faulty combination of INV.
PCB (Slave 2)
U0 - 03 Gas shortage alarm Refer to the “U0” flow chart.
44
Troubleshooting by Remote Controller
Error Troubleshooting
code Description of error Description of diagnosis
U1 - 01 Reverse phase/open phase Refer to the “U1” flow chart of
for power supply (Master) each manual and make a
U1 - 04 Reverse phase for power diagnosis of the relevant unit
based on the Error code shown
supply [with power supply
to the left.
turned ON] (Master)
U1 - 05 Reverse phase/open phase
for power supply (Slave 1)
U1 - 06 Reverse phase for power
supply [with power supply
turned ON] (Slave 1)
U1 - 07 Reverse phase/open phase
for power supply (Slave 2)
U1 - 08 Reverse phase for power
supply [with power supply
turned ON] (Slave 2)
45
Troubleshooting by Indication on the Remote Controller
3. Troubleshooting by
Indication on the Remote
Controller
3.1 A0 External Protection Device
Abnormality
Remote Controller Display
A0
Applicable Models
All indoor models
Supposed Causes
Actuation of external protection device
Improper field setting
Defective indoor unit PCB
46
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
External
protection
device is connected YES
to terminals T1 and Actuation of
T2 of the indoor external
unit terminal protection
block. device.
NO
Check the setting state of
the external ON/OFF
input by remote
controller.
ON/OFF
input from
outside (mode
No. 12, first code
No. 1) has been set YES
to external protection Change the
device input (second second code No.
code No. 03) by to "01" or "02".
remote
controller.
NO
Replace the
indoor unit PCB.
47
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective indoor unit PCB
External factor (Noise etc.)
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
48
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Proper power supply is not provided
Defective float switch or short circuit connector
Defective drain pump
Drain clogging, upward slope, etc.
Defective indoor unit PCB
Loose connection of connector
49
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is power NO
supply 220~240V Provide
provided? 220~240V power
supply.
YES
The
float switch
is connected to NO
connector of the
indoor unit
PCB. A
YES short circuit
connector is NO
Connect either a
connected to short circuit
The PCB.
float connector or float
switch contact switch and turn
YES ON again.
is forming a short YES
circuit (continuity check
with connector
disconnected)
Becomes
normal when NO
NO connector of the indoor Defective indoor
unit PCB is short unit PCB.
circuited
YES
Loose the
Water builds NO connection of
up in the drain connector.
pan.
YES
Modify the float
switch's
The connection and
drain turn ON again.
pump is
connected to NO
Connect the
connector terminals drain pump and
of the indoor turn ON again.
unit PCB.
YES
A
50
Troubleshooting by Indication on the Remote Controller
The
drain pump
works when the YES
power supply is reset Check the drain
for the indoor unit. piping for
clogging or
upward slope,
etc.
NO
The
voltage
of terminals
Y1 and Y2 or
connector is NO
220~240 V (within 5 Replace the
minutes of resetting indoor unit PCB.
the power
supply).
YES
Replace the
drain pump or
check for dirt,
etc.
51
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Broken wires, short circuits, and loose connections in
the fan motor harness
Defective fan motor
(Broken wires or defective insulation)
Abnormal signal output from the fan motor (defective
circuit)
Defective PCB
Instantaneous disturbance in the power supply voltage
Fan motor lock
(Due to motor or external causes)
The fan does not rotate due to foreign matters
blocking the fan.
Disconnection of the connector between the high-
power PCB and the low-power PCB.
52
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are there
any foreign matters YES
Remove the
around the fan? foreign matters.
NO
Is the
connector for
the fan motor NO
properly connected to Properly connect
the indoor unit the connector.
PCB? (∗1)
YES
By
disconnecting
the connector for
the fan motor from the NO
Replace the fan
indoor unit PCB, the motor.
fan can be lightly
rotated by
hand.
YES
Disconnect the connector
from the fan motor, and
then make measurement
of resistance between
pins. (∗2)
Is the
resistance
between the pins NO
more than the Replace the fan
judgement motor.
criteria?
YES
Replace the
indoor unit PCB.
53
Troubleshooting by Indication on the Remote Controller
Note:
∗1. If any junction connector is provided between the
connector on the indoor unit PCB and the fan motor,
also check whether or not the junction connector is
properly connected.
∗2. All resistance measuring points and judgement
criteria.
(Example) 1 2 3 4 5
FXA(Q) 1 White FG FXF(Q) — — FG Vsp Vcc
{ { { { {
2 Orange Vsp { { {
3 Brown Vcc Vdc GND —
1 2 3
4 Blue GND Judgement Criteria
5 — Measuring point Criteria
FG-GND 1MΩ or more
6 — Vsp-GND 100kΩ or more
Vcc-GND 100Ω or more
7 Red Vdc Vdc-GND 100kΩ or more
54
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective indoor fan motor
Broken wires
Defective contact
55
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the connector NO
securely Properly connect
connected? the connectors.
(At this time,
check for any
defective
YES connector
contact or broken
Is wires.)
the
power of
approx. 12VDC
supplied between
the Pins1 and 3 when YES Check the indoor
the connector is unit fan motor
disconnected and and the wiring
the power circuits of the fan
supply turns
ON? motor.
NO
Replace the
indoor unit PCB.
56
Troubleshooting by Indication on the Remote Controller
3.6 A6 Overload/Overcurrent/Lock
of Indoor Unit Fan Motor
Remote Controller Display
A6
Applicable Models
R-22: FXM40~125L
R-410A: FXMQ50~140P
Supposed Causes
The clogging of a foreign matter
The disconnection of the fan motor connectors
The disconnection of the connectors between the
indoor unit PCB and fan PCB
Defective fan PCB
Defective fan motor
57
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
There is a
foreign matter YES
Remove the
around the fan. foreign matter.
NO
The
fan motor
connectors of the YES
fan PCB are Connect
disconnected. correctly.
NO
The
connectors
between the
indoor unit PCB and YES
Connect
the fan PCB are correctly.
disconnected.
NO
The
fuse on the
fan PCB is not in a NO
Replace the fan
conduction state. PCB.
YES
The
fan can be
moved lightly
by hand after the fan NO
motor connector of the Replace the fan
fan PCB is motor.
removed.
YES
A
58
Troubleshooting by Indication on the Remote Controller
The
resistance
between the
power wire terminals YES
of the fan motor and Replace the fan
motor frame (meal motor.
part) is 1 MΩ
or below.
NO
Remove the power wire
connector from the fan
motor and measure the
resistance between U
and V, V and W, and W
and U phases (*1).
The
resistors
among U, V, and NO
W are unbalanced or Replace the fan
short-circuited. motor.
YES
Between
VCC and GND
terminals, and YES
between GND and HW, Replace the fan
HV, or HU terminals motor.
are short-
circuited.
NO
59
Troubleshooting by Indication on the Remote Controller
The
HAP
lamp of the
indoor PCB YES
blinks and the HAP Replace the fan
lamp of the fan PCB.
PCB is OFF.
NO
Replace the fan
motor.
Note:
∗1. Measurement of power wire connector.
Remove the connector from the fan PCB and
measure the resistance between the U and V, V and
W, and W and U phases of the motor connector (with
five core wire) and check that each phase are
balanced (within a permissible dispersion range of
±20%).
∗2. Measurement of signal wire connector.
Remove the connector and measure the resistance
between GND and VCC, HW, HV, or HU terminals of
the motor connector (with five core wire).
Connector power wire use Connector signal wire use
4 4 Pink Vcc
3 White V 3 Orange HW
2 2 Blue HV
1 Black W 1 Yellow HU
60
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective power supply for the indoor unit fan motor
Clogged drain piping
Actuation of the indoor unit safety device
Defective contact in the fan wiring circuit
61
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
power supply
cable of the indoor NO
unit fan properly Properly connect
connected? the cable.
YES
Replace the
indoor unit PCB.
62
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective swing motor
Defective connection cable (power supply and limit
switch)
Defective airflow direction adjusting flap-cam
Defective indoor unit PCB
63
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is power
supply 220~240V NO
Provide
provided? 220~240V power
supply.
YES
Indoor
unit is a model NO
equipped with a swing Replace the
flap function indoor unit PCB.
YES
The
swing motor
works when the YES
power supply is turned
OFF and then
back ON.
The
connector is NO
NO connected to the Connect the
indoor unit PCB. connector and
turn ON again.
YES
The limit NO
switch functions Replace the
normally. swing motor.
YES
The
relay cable is YES
After short circuited or Replace the limit
turning disconnected. switch relay
the swing- cable.
flap ON and
then stopping NO
with the remote
controller, the voltage
of the indoor unit PCB is NO Replace the
220 ~ 240 VAC (60 Hz) indoor unit PCB.
when turned ON
again (within 30
seconds of
turning ON
again).
YES
A
64
Troubleshooting by Indication on the Remote Controller
When
the airflow
direction flap-
cam mechanism is NO
disconnected from the Replace the
swing motor, operation swing motor.
is normal when
turned ON
again.
YES
Take the flap-
cam mechanism
apart,
reassemble and
turn ON again.
65
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective power supply voltage.
Defective connection on signal line.
Defective wiring.
Instantaneous blackout, others.
66
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
There are
problems on the YES
condition of power Correct any fault.
supply described
above.
NO
YES
"A8" Reoccurrence Check and
of error. correct each
wiring.
NO
It is possible to
have external
factor, such as
brownout and
instantaneous
blackout.
67
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective electronic expansion valve coil
Defective PCB indoor unit
Defective relay cables
68
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
When power NO
Replace the
is supplied. electronic
expansion valve
YES main body.
Electronic
expansion valve is NO
connected to indoor Shut the power
unit PCB. supply OFF after
connection and
then restart.
YES
Check (∗1) of
electronic expansion NO
Replace the
valve coil indicates electronic
normal. expansion valve
coil.
YES
Relay
cables short YES
circuit or Replace the
disconnected. relay cables.
NO
When restarting
the operation
after shutting the
power supply
OFF does not
work, replace the
indoor unit PCB.
69
Troubleshooting by Indication on the Remote Controller
Note:
∗1: How to check the electronic expansion valve coil
Remove the connector for electronic expansion valve
from PCB. Measure the resistance value between
pins and check the continuity to judge the condition.
1) White
70
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Humidifier unit (optional accessory) leaking
Defective drain piping (upward slope, etc.)
Defective indoor unit PCB
71
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Field
drain piping
has a defect such as YES
Modify the drain
upward sloping. piping.
NO
A
humidifier
unit (optional YES
accessory) is installed Check if the
on the indoor humidifier unit is
unit. leaking.
NO
Defective indoor
unit PCB.
72
Troubleshooting by Indication on the Remote Controller
Supposed Causes
The capacity setting adaptor was not installed.
Defective indoor unit PCB
73
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
The
indoor unit NO
PCB was replaced Replace the
with a spare indoor unit PCB.
PCB.
YES
The
capacity
setting adaptor NO
need to be installed Replace the
when replacing indoor unit PCB.
the PCB.
YES
Install a capacity
setting adaptor.
74
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective connection of the connector between indoor
unit PCB and fan PCB
Defective indoor unit PCB
Defective fan PCB
External factor, such as instantaneous blackout
75
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is
the
connector
between indoor NO
unit PCB and fan PCB Connect the
accurately connector
connected? (∗1) accurately.
YES
Confirm the condition of
transmission on indoor
unit PCB using field
setting mode. (∗2)
Under
above NO
field setting mode, Replace the
second code No. is indoor unit PCB.
"01".
YES
"C1" YES
Reoccurrence Replace the fan
of error. PCB.
NO
Connect it and
continue the
operation (It is
possible to have
a cause, such as
instantaneous
blackout).
76
Troubleshooting by Indication on the Remote Controller
Note:
∗1. Pull out and insert the connector once and check it is
absolutely connected.
∗2. Method to check transmission part of indoor unit
PCB.
Turn OFF the power and remove the connector of
indoor unit PCB.
Short circuit the connector.
After turning ON the power, check below numbers
under field setting from remote controller.
(Confirmation: Second code No. at the condition
of first code No. 21 on mode No. 41)
↓
Determination 01: Normal
Other than 01: Transmission error on
indoor unit PCB
77
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor for liquid pipe
Defective indoor unit PCB
78
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
5 kΩ to 90 kΩ NO
CHECK 11 Replace the
thermistor.
YES
Replace the
indoor unit PCB.
79
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor for gas pipe
Defective indoor unit PCB
80
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
5 kΩ to 90 kΩ NO
CHECK 11 Replace the
thermistor.
YES
Replace the
indoor unit PCB.
81
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective fan PCB.
Defective connection of capacity setting adaptor
Field setting error.
82
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or
Caution parts may be damaged.
Is the NO
type of fan PCB Replace it with
correct? the correct fan
PCB.
YES
Was
the
NO indoor unit PCB
replaced with a spare
PCB?
YES
Was
the correct
capacity setting
adaptor installed NO
when replacing it Install the correct
with a spare capacity setting
PCB? adaptor.
YES
After establishing
transmission for
indoor and
outdoor,
diagnose the
operation again.
83
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor for suction air
Defective indoor unit PCB
84
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
5 kΩ to 90 kΩ NO
CHECK 11 Replace the
thermistor.
YES
Replace the
indoor unit PCB.
85
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective indoor unit thermistor for air outlet
Defective indoor unit PCB
86
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Connector is NO
connected to the Connect the
indoor unit PCB. thermistor and
turn ON again.
YES
Resistance
is normal when
measured after
disconnecting the NO
thermistor from the indoor Replace the
unit PCB. (7.2kΩ ~ thermistor.
112kΩ)
CHECK 11
YES
Replace the
indoor unit PCB.
87
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective sensor
Disconnection
88
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
YES
Does it function It is normal.
normally? (Poor connector
contact)
NO
Is
"CC"
displayed on the YES Replace the
remote controller? humidity sensor
(∗2) PCB (∗3).
NO
It is believed that
external factors
(noise or else)
other than failure
caused the error.
Note:
∗1. To delete the history, the ON/OFF button of the
remote controller must be pressed and held for 5
seconds in the check mode.
∗2. To display the code, the Inspection/Test Operation
button of the remote controller must be pressed and
held in the normal mode.
∗3. If "CC" is displayed even after replacing the humidity
sensor PCB assy and taking the steps ∗1 and ∗2,
replace the indoor unit PCB assy.
89
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective room temperature thermistor in remote
controller
Defective remote controller PCB
90
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is "CJ"
displayed on the YES
remote controller? Replace the
remote controller.
NO
External factor
other than
equipment error.
(for example,
noise etc.)
Note:
∗1. How to delete “history of error codes”.
Press the ON/OFF button for 4 seconds and more
while the error code is displayed in the inspection
mode.
91
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective outdoor unit main PCB
Defective connection of inside/outside relay wires
92
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check if
inside / outside
relay wires of outdoor YES Connect the
unit main PCB is inside/outside
disconnected. relay wires
correctly.
NO
Replace the
outdoor unit main
PCB.
93
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective compressor
94
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Turn OFF the power
supply, and then
disconnect compressor
lead wire.
Check
the compressor Insulation fault
for insulation using a Replace the
megger tester. defective part.
Not fault
Check the
whole product for Insulation fault
insulation resistance Replace the
using a megger defective part.
tester.
Not fault
Check the
connectors of the
high pressure switch Disconnected
Securely connect
line for any the connectors.
disconnection.
Connected
Check the
earth leakage YES
detection PCB for any Replace the
broken wire in it. earth leakage
detection PCB.
No
95
Troubleshooting by Indication on the Remote Controller
Check
whether there
is continuity No continuity (∗1)
between both connector Replace the
ends of the earth earth leakage
leakage detection PCB.
detection
PCB.
Continuity
Check
whether there is
continuity between No continuity
Replace the high
both ends of high pressure switch.
pressure
switch.
Continuity
Normal
Note:
∗1. It is normal that there is no continuity between both
ends of connector when the power supply turns OFF
and for a period of 9 seconds at maximum after the
power supply turns ON.
96
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Actuation of outdoor unit high pressure switch
Defective high pressure switch
Defective outdoor unit PCB
Instantaneous power failure
Defective high pressure sensor
97
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are
the high
pressure switch NO
connectors connected Connect the
to the outdoor connector and
main PCB operate again.
(∗1)
YES
Contact
pressure switch YES
Actuation of high
or pressure switch pressure switch.
is open. (∗1)
NO
Operation is
normal when turned YES
ON again by remote There was an
controller. instantaneous
power failure or
a past safety
NO device actuated.
Re-check the
refrigerant
system.
Replace the
outdoor unit
PCB.
Note:
∗1. Actuation of high pressure switch
• The outdoor unit PCB connector is disconnected.
• Is the outdoor unit heat exchanger dirty?
• Defective outdoor unit fan
• Is the refrigerant overcharged?
• Defective high pressure sensor
98
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Actuation of high pressure switch
Defective high pressure switch
Defective outdoor unit main PCB
Instantaneous power failure
Defective high pressure sensor
99
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
NO Is the
high pressure NO
switch operating value Replace the high
normal? pressure switch.
YES
Are the
characteristics of NO
the high pressure Replace the high
sensor normal? pressure sensor.
(∗1)
YES
Service Checker
Connect the service checker to compare the “high
pressure” value checked with the Service Checker
and the actual measurement value by pressure
sensor (∗1).
100
Troubleshooting by Indication on the Remote Controller
Check
if the “high
pressure” value
and the actual NO
measurement value Replace the
by pressure outdoor unit main
sensor are the PCB.
same.
YES
· The high pressure sensor is normal, and the
pressure detected with the PCB is also normal.
· The high pressure has really become high.
Note:
∗1. Make a comparison between the voltage of the
pressure sensor and that read by the pressure gauge.
(As to the voltage of the pressure sensor, make
measurement of voltage at the connector, and then
convert it to pressure. CHECK 12 )
∗2: Make measurement of voltage of the pressure sensor.
+5V Connector for high
pressure sensor (Red)
(4) Red
(3) Black High
pressure
(2) sensor
Micro-computer
A/D input (1) White
101
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Abnormal drop of low pressure
Defective low pressure sensor
Defective outdoor unit PCB
Stop valve is not opened.
102
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is stop valve NO
Open stop valve.
opened?
YES
Low
pressure at stop YES
due to error is Refrigerant
abnormal. shortage,
refrigerant
NO system clogging,
wiring and piping
wrong
connection, stop
Measure valve closed,
the voltage electronic
(VL) of connector expansion valve
pin No. (2) - (3) of fully close error.
YES
outdoor unit PCB. (∗1) Replace the low
Is the relationship pressure sensor.
between low
voltage and VL
normal?
NO
Replace the
outdoor unit
PCB.
Note:
∗1. Make measurement of voltage of the pressure sensor.
Outdoor unit PCB Connector for
+5V
low pressure
sensor (Blue)
Low pressure sensor
Red
GND Black
Micro-computer White
A/D input
103
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Abnormal drop of low pressure
Defective low pressure sensor
Defective outdoor unit PCB
Stop valve is not opened.
Clogged filter
104
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is NO
the stop valve Open the stop
open? valve.
YES
Are the
characteristics NO
of the low pressure Replace the low
sensor normal? pressure sensor.
(∗1)
YES
Service Checker
Connect the service checker to compare the “low
pressure” value checked with the Service Checker
and the actual measurement value by pressure
sensor (∗1).
Check if
the “low
pressure” value
and the actual NO
measurement value by Replace the
pressure sensor outdoor unit main
are the same. PCB.
YES
· The low pressure sensor is normal, and the
pressure detected with the PCB is also normal.
· The low pressure has really become low.
105
Troubleshooting by Indication on the Remote Controller
Note:
∗1. Make a comparison between the voltage of the
pressure sensor and that read by the pressure
gauge.
(As to the voltage of the pressure sensor, make
measurement of voltage at the connector, and then
convert it to pressure. CHECK 12 )
∗2. Make measurement of voltage of the pressure
sensor.
+5V
Connector for low pressure sensor
(Blue)
(4) Red
(1)
106
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Compressor lock
High differential pressure
Incorrect UVWN wiring
Defective inverter PCB
Stop valve is not opened
107
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is NO
the stop valve Open the stop
open? valve.
YES
Is
the UVWN NO
Connect
wiring normal? correctly.
YES
Is high YES
differential pressure Remedy the
starting? cause.
NO
Check
and see
whether YES
compressor is short- Replace the
circuited or compressor.
ground.
NO
Are
inverter output NO
voltages the same for Replace the
3 phases? outdoor unit
inverter PCB.
YES
Does low
or high
pressure vary even YES
instantaneously when
restarting
compressor?
NO
Replace the
compressor.
108
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Inverter compressor lock
High differential pressure
Incorrect UVW wiring
Defective inverter PCB
Stop valve is not opened.
109
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the stop NO
Local factor
valve open? Open the stop
YES valve.
Are the
relay wires to the NO
Replace the
compressor connecting wires
correct? and then
YES securely connect
the connectors.
Is the
connection of NO
UVW phase order Ensure correct
correct? connection.
W
YES
U
Is the
Power OFF wiring the same NO V
as in the wiring Ensure correct
diagram. connection.
YES
The
insulation
resistance of the YES
compressor is low Replace the
(not more than compressor.
100kΩ).
NO
The
compressor coil YES
has disconnection
of wires.
NO
Restart the
compressor, and NO
Power ON then check whether or Conclude the
not the error work
There is a
recurs. possibility of
defective
YES pressure
equalizing.
A Check the
refrigerant
system.
110
Troubleshooting by Indication on the Remote Controller
Has the
compressor
started up at high YES
Defective
differential pressure pressure
(∗1)? equalizing
Check the
refrigerant
NO system.
Remove the connection
between the compressor
and inverter. Set the
power transistor check
mode ON using “Setting
mode (2)” of the outdoor
unit PCB.
Check
if the inverter
output voltage NO
Replace the
between 3 phases is outdoor unit
within ± 5V. inverter PCB.
YES
Replace the
inverter
compressor.
Note:
∗1. Pressure difference between high pressure and low
pressure before starting.
∗2. The quality of power transistors/diode modules can
be judged by executing CHECK 4 .
111
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Inverter compressor lock
High differential pressure
Incorrect UVWN wire connection
Defective inverter PCB
Stop valve is not opened
112
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is NO
the stop valve Open the stop
opened? valve.
YES
Is the
UVWN wire NO
connection Connect
proper? properly.
YES
Is it a high
differential pressure YES
Eliminate the
at the time of causes.
startup? (∗1) The hot gas
bypass valve
may not be
NO opened.
Check it.
Restart operation after
resetting operation.
The
inverter NO
compressor operates Replace the
normally. compressor.
YES
Disconnect the connection
between the compressor
and the inverter and turn
on power transistor check
mode setting using
“Setting Mode 2” on the
outside unit PCB.
113
Troubleshooting by Indication on the Remote Controller
Inverter
output voltage
among 3 phases is
within ±5V for TL NO
Replace the
power supply and inverter PCB.
±10V for YL
power
supply.
YES
Replace the
inverter
compressor.
Note:
∗1. Difference in pressure between high and low
pressures before startup
∗2. The quality of the power transistor diode module can
be assessed also by means of measurement of
resistance between terminals.
114
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Stop valve is not opened
Obstacles at the air outlet
Improper power voltage
Defective magnetic switch
Defective compressor
Defective current sensor
115
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is NO
the stop valve Open the stop
open? valve.
YES
Obstacle YES
exists around the air Remove the
outlet. obstacle.
NO
Is
the power NO
supply voltage Correct the
normal? power voltage.
YES
Is the NO
magnetic switch Replace the
normal? magnetic switch.
YES
Check the wiring from power supply ~ current
sensor ~ MgS ~ compressor
Is above NO
wiring correct? Correct wiring.
YES
Is
current NO
sensor correct? Replace the
corresponding
current sensor.
YES
Replace the
compressor.
116
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective fan motor
Defect or connection error of the connectors/ harness
between the fan motor and PCB
The fan can not rotate due to any foreign substances
entangled.
Clear condition: Continue normal operation for 5
minutes
117
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check if
any foreign YES
substances around Remove the
the fan. foreign
substances.
NO
Check if YES
any connector is Insert the
disconnected. connector.
NO
Relay
connectors YES
have any connection Correct the
error. connection of the
relay connectors.
NO
118
Troubleshooting by Indication on the Remote Controller
No
continuity of YES
fuse on the fan Replace the fan
inverter PCB. inverter PCB.
NO
Unable to
rotate the fan
manually with ease YES
when removing the Replace the
connector of the corresponding
fan motor. fan motor.
NO
Resistance
value between
the power supply YES
wire terminal of fan Replace the
motor and the motor corresponding
frame (metal) is fan motor.
1MΩ and
below.
NO
CHECK 16
Check fan motor
connector (power supply
wire)
The
resistance
value between
UVW phases of fan YES
motor is out of balance, Replace the
or short circuit corresponding
between UVW fan motor.
phases.
NO
B
119
Troubleshooting by Indication on the Remote Controller
CHECK 17
Check fan motor
connector (signal wire)
The
signal wire
short circuits YES
between Vcc and GND Replace the
and between UVW corresponding
and GND. fan motor.
NO
Put the power supply ON
to check the following
LED lamps.
1) HAP lamp on the
compressor PCB
2) HAP lamp on the fan
inverter PCB
HAP
lamp on the
fan inverter PCB
does not blink on the YES
condition, but the HAP Replace the fan
lamp on the inverter PCB.
compressor PCB
is blinking.
NO
Replace the fan
motor 2.
120
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective fan motor
Defect or connect ion error of the connectors/ harness
between the fan motor and PCB
The fan can not rotate due to any foreign substances
entangled.
Clear condition: Continue normal operation for 5
minutes
121
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check if
any foreign YES
Remove the
substances around foreign
the fan. substances.
NO
Check if YES
any connector is Insert the
disconnected. connector.
NO
Relay
connectors have YES
Correct the
any connection connection of the
error. relay connectors.
NO
A
122
Troubleshooting by Indication on the Remote Controller
No YES
continuity of fuse on Replace the PCB.
main PCB.
NO
Unable to
rotate the fan
manually with ease YES
Replace the
when removing the corresponding
connector of the fan motor.
fan motor.
NO
Resistance
value between
the power supply wire YES
terminal of fan motor and Replace the
the motor frame corresponding
(metal) is 1MΩ fan motor.
and below.
NO
CHECK 16
Check fan motor
connector (power supply
wire)
The
resistance
value between
UVW phases of fan YES
motor is out of balance, Replace the
or short circuit corresponding
between UVW fan motor.
phases.
NO
123
Troubleshooting by Indication on the Remote Controller
CHECK 17
Check fan motor
connector (signal wire)
The
signal wire
short circuits
between Vcc and YES
Replace the
GND and between corresponding
UVW and fan motor.
GND.
NO
Replace the
PCB.
124
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective fan motor
The harness connector between fan motor and PCB is
left in disconnected, or defective connector
Fan does not run due to foreign matters tangled
Clearing condition: Operate for 5 minutes (normal)
125
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Connector of YES
fan motor is Connect the
disconnected. connector.
NO
Is there
any obstacle YES
Remove the
around the fan? obstacle.
NO
Can the
fan be turned
smoothly with NO
hand after disconnect Replace the fan
the connector of motor of outdoor
fan motor? unit.
YES
CHECK 16
Check on connector of
fan motor (Power
supply cable)
CHECK 17
Check on pulse input of
position signal of fan
inverter PCB
Is the pulse NO
inputted? Replace the fan
motor of outdoor
YES unit.
Replace the
outdoor unit
PCB.
126
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective fan motor
The harness connector between fan motor and PCB is
left in disconnected, or defective connector
Fan does not run due to foreign matters tangled
Clearing condition: Operate for 5 minutes (normal)
127
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Connector YES
of fan motor is Connect the
disconnected. connector.
NO
Harness
connector
between
compressor inverter YES
PCB and fan inverter Connect the
PCB is harness
disconnected. connector.
NO
Is
there any YES
obstacle around the Remove the
fan? obstacle.
NO
YES
CHECK 17
Check on pulse input of
position signal of fan
inverter PCB
128
Troubleshooting by Indication on the Remote Controller
Is the
LED (HAP) NO
on fan inverter PCB Replace the fan
blinking? inverter PCB.
YES
CHECK 16
Check on connector of
fan motor (Power supply
cable)
Are the
resistance
values between
phases of U, V, W NO
balanced? Is there any Replace the fan
short circuiting motor of outdoor
between phases unit.
of U, V, W?
YES
CHECK 17
Check on connector of fan
motor (Signal wire)
Is the
resistance
value between Vcc NO
and UVW, and GND Replace the fan
and UVW motor of outdoor
balanced? unit.
YES
Replace the fan
inverter PCB.
129
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Disconnection of connectors for electronic expansion
valve
Defective electronic expansion valve coil
Defective outdoor unit main PCB
130
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Return to YES
External factor
normal? other than error
(for example,
NO noise etc.).
Check the electronic expansion valve corresponding
to the error code “E9” in the monitor mode.
{ When Check 4 shows as follows:
→ Electronic expansion valve for
main use
{ When Check 4 shows as follows:
→ Electronic expansion valve for
subcooling Master unit
{ Explanation of “ ” Slave unit 1
Slave unit 2
System
The
connector of
outdoor unit PCB for NO
Ensure correct
electronic expansion connection.
valve is
connected.
YES
The coil
resistance of NO
electronic expansion Replace the
valve is normal. electronic
(∗1) expansion valve
coil.
YES
Replace the
outdoor unit
PCB.
131
Troubleshooting by Indication on the Remote Controller
Note:
∗1. Make measurement of resistance between the
connector pins, and then make sure the resistance
falls in the range of 40 to 50Ω.
(Orange) 1
(Red) 2
Measuring points Judgement criteria
(Yellow) 3 1-6
2-6
(Black) 4 40~50Ω
3-6
5 4-6
COM[+] (Gray) 6
132
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective electronic expansion valve coil
Defective outside unit PCB
Defective connecting cable
133
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Return to YES
External factor
normal? other than error
NO (for example,
noise etc.).
Electronic
expansion valve is NO
connected to outside After connecting,
unit PCB. turn the power
OFF and then
back ON again.
YES
Normal
when coil check NO
(∗1) of the electronic Replace the
expansion valve is electronic
checked. expansion valve
coil.
YES
The
relay cable is YES
short-circuited or Replace the relay
disconnected. cable.
NO
Replace the
outside unit PCB.
Note:
∗1. Coil check method for the electronic expansion valve
coil
Discount the electronic expansion valve from the
PCB and check the continuity between the connector
pins.
134
Troubleshooting by Indication on the Remote Controller
(Normal)
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × { × { ×
Approx. Approx.
300Ω 150Ω
2. Yellow × { × {
Approx. Approx.
300Ω 150Ω
3. Orange × { ×
Approx.
150Ω
4. Blue × {
Approx.
150Ω
5. Red ×
6. Brown
{: Continuity
×: No continuity
(1) White
135
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor
Defective outdoor unit PCB
136
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check
if discharge
pipe thermistor NO
Replace the
property is normal. discharge pipe
(∗1) thermistor.
YES
Service Checker
Connect the service checker to compare the
temperature of discharge pipe by using service
checker with actual measurement value of
discharge pipe thermistor CHECK 11 .
Check if
temperature of
discharge pipe by
using service checker NO
is the same with actual Replace the
measurement value outdoor unit main
of discharge pipe PCB.
thermistor.
YES
· Discharge pipe thermistor is normal and the
temperature detection of the main PCB is also
normal.
· Actually the temperature of discharge pipe is high.
137
Troubleshooting by Indication on the Remote Controller
Note:
∗1. Compare the resistance value of discharge pipe
thermistor and the value based on the surface
thermometer.
138
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor
Defective outside unit PCB
139
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are
discharge
pipe thermistor NO
Replace the
characteristics discharge pipe
normal? thermistor.
(∗1)
YES
Is PCB NO
detection temperature Replace the main
normal? PCB.
(∗2)
YES
· The discharge pipe thermistor is normal and the
main PCB temperature detection is also normal.
· In fact, discharge pipe temperature is rising.
CHECK 3
Note:
∗1. Compare the resistance values of the discharge pipe
thermistor with measurements of a surface
thermometer.
(For temperature and resistance characteristics of a
thermistor, refer to P.371.)
∗2. Compare the discharge pipe temperature checked
by the Service
Checker with the resistance of the thermistor (refer to
∗1).
140
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor
Defective outdoor unit PCB
141
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
YES
Replace the
outdoor unit
PCB.
142
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Refrigerant overcharge
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Defective liquid pipe thermistor
143
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are
the above NO
thermistor installed Install the
on pipes thermistor
correctly? correctly.
YES
Remove the outdoor air
thermistor, heat
exchanger deicer
thermistor and the liquid
pipe thermistor from the
outdoor unit PCB and
measure resistance with
a tester.
Is the
characteristic of
the above thermistor NO
normal? Replace the
thermistor.
CHECK 11
YES
Rectify the
overcharge of
refrigerant.
144
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Excessive refrigerant charging
Suction pipe thermistor removed
Subcooling heat exchanger outlet thermistor removed
145
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
thermistor NO
mounted properly? Mount the
thermistor
properly before
operation.
YES
Remove the suction
pipe thermistor and the
subcooling heat
exchanger outlet
thermistor from the
outside unit PCB and
measure the resistance
with a tester.
Does it NO
function normally? Replace the
thermistor if it
functions
YES abnormally
before operation.
Carry out check
operation again.
Does the NO
error code "F6" Continue the
repeat? operation.
YES
• There is a possibility that there are other causes
of refrigerant overfilling.
CHECK 5
146
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Refrigerant overcharge
Disconnection of the receiver gas pipe thermistor
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the
suction pipe
and subcooling heat NO
exchanger gas pipe Install the
thermistor installed thermistor
on pipes correctly.
correctly?
YES
Is the
characteristic
of the suction pipe
and subcooling heat NO
Replace the
exchanger gas pipe thermistor.
thermistor
normal?
YES
Refrigerant
overcharged.
147
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective high pressure switch
Broken of high pressure switch harness
Defective connection of high pressure switch
connector
Defective compressor
Defective outdoor unit PCB
Broken of lead wire
148
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
protection HPS
connector correctly NO
connected to the Connect it
outdoor unit correctly.
PCB?
YES
Wait for 10 minutes after
unit stops, then check the
following.
Is there
continuity at the NO
control and protection Replace the high
high pressure pressure switch
switch? where there is no
continuity.
YES ∗ If normal, the
resistance will
be 10Ω or less.
Is there a
disconnection or YES
insulation failure at Replace the
the compressor compressor.
coil? ∗ If there is a
compressor
NO error, there is
the possibility
that the INV.
PCB and
outdoor unit
PCB have been
damaged.
Check that
each of these
PCBs is
normal.
Is there NO
continuity at the lead Replace the lead
wire? wire.
YES
Replace the sub
PCB.
149
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective fan motor signal (circuit error)
Broken, short circuited or disconnection connector of
fan motor connection cable
Defective fan Inverter PCB
150
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check the fan motor corresponding to the error code “H7” in the
monitor mode.
When check 3 shows as follows:
→ Fan motor 1 (M1F)
When check 3 shows as follows:
→ Fan motor 2 (M2F)
Identify outdoor unit based on Check 4.
Check if
signal wire
connector for the NO
Ensure correct
corresponding fan the connection.
motor is
normal.
YES
A
151
Troubleshooting by Indication on the Remote Controller
Check if the
resistance of the
fan motor lead wire NO
between Vcc and UVW Replace the fan
and between GND motor.
and UVW are
balanced.
YES
Replace the
inverter PCB.
zFor fan motor
1: replace the
inverter PCB
zFor fan motor
2: replace the
fan inverter
PCB
Note:
∗1. Check procedure for fan motor connector
(1) Power OFF the fan motor.
(2) Remove the connector on the PCB to measure the
following resistance value.
Judgement criteria: resistance value between each
phase is within ±20%
Connector for signal wires.
X2A
5 Gray GND
4 Pink Vcc
Measure the
resistance
3 Orange W between Vcc-
UVW and
GND-UVW.
2 Blue V
1 Yellow U
152
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Abnormal fan motor signal (circuit error)
Broken, short or disconnection connector of fan motor
connection cable
Defective fan Inverter PCB
153
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
fan motor
connector NO
connected to PCB for Connect
fan inverter correctly.
correctly?
YES
The
resistance
of fan motor read
wire connector pins NO
Replace the fan
between Vcc-UVW motor.
and GND-UVW
balanced?
YES
Replace the fan
inverter PCB.
5 Gray GND
4 Pink Vcc
Measure the
resistance
3 Orange W between Vcc-
UVW and
GND-UVW.
2 Blue V
1 Yellow U
154
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor connection
Defective thermistor for outdoor air
Defective outdoor unit PCB
155
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Connector is NO
connected to outdoor Connect the
unit PCB. connector and
turn ON again.
YES
Resistance
is normal when
measured after
disconnecting the NO
thermistor from the Replace the
outdoor unit thermistor.
PCB.
CHECK 11
YES
Replace the
outdoor unit
PCB.
156
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective outdoor air thermistor
Defective outdoor unit PCB
157
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Connector is NO
connected to outdoor Connect the
unit PCB. connector and
turn ON again.
YES
Resistance
is normal when
measured after
disconnecting the NO
thermistor from the Replace the
outdoor unit PCB. thermistor.
CHECK 11
YES
Replace the
outdoor unit
PCB.
The alarm indicator is displayed when the fan only is
being used also.
158
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Clogged water piping system
Insufficient heat exchanger water
Dirty heat exchanger
Disconnected connector
Defective thermistor on the heat exchanger gas side
Defective low pressure sensor
159
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Clogged
water piping
system (mixing in of YES
foreign particles, Remove the clog.
solenoid valve
for water
use)
NO
Is the
amount of
water of heat NO
exchanger 50 Secure the
l/minute or enough water.
more?
YES
Is the
connection
between the
thermistor on the NO
heat exchanger gas side Connect the
and the low connector
pressure sensor properly.
proper?
YES
160
Troubleshooting by Indication on the Remote Controller
Are
characteristics
of the thermistor on
the heat exchanger gas NO
Replace the
side and the low thermistor/sensor
pressure sensor if any of its
normal? characteristics
(∗1) are abnormal.
YES
Disconnect the
connection between the
compressor and the
inverter and turn ON the
power transistor check
mode setting using
“Setting Mode 2” on the
outside unit PCB.
The
output
voltage
among three NO
phases is within ±5V Replace the
for TL power supply inverter PCB.
and ±10V for Y1,
YL power
supply.
YES
Replace the
outside unit main
PCB.
∗1: For thermistor/sensor characteristics, refer to P.369.
∗2: The quality of the power transistor diode module can
be assessed by means of measurement of
resistance between terminals (Refer to P.354).
161
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective high pressure sensor
Connection of low pressure sensor with wrong
connection.
Defective outdoor unit PCB.
Defective connection of high pressure sensor
162
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the
characteristics
of the high
pressure sensor
normal? (Make a NO
comparison between the Replace the high
voltage pressure sensor.
characteristics and
the gauge
pressure.)
YES
If the
PCB
pressure
detection
normal? (Make a
comparison between NO
Replace the
the checker pressure outdoor unit sub
data and the voltage PCB.
characteristics.)
YES
163
Troubleshooting by Indication on the Remote Controller
Are the
characteristics of NO
the high pressure Replace the high
sensor pressure sensor.
normal?
YES
Replace the
outdoor unit sub
PCB.
164
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective current sensor
Defective outdoor unit PCB
Defective compressor
165
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check the current sensor corresponding to the error code “J2” in the
monitor mode.
{ Check 4 shows as follows:
→ Current sensor for constant rate compressor 1
{ Check 4 shows as follows:
→ Current sensor for constant rate compressor 2
{ Explanation for “ ”
Master unit
Slave unit 1
Slave unit 2
System
Is the
connector for
current sensor NO
connected to outdoor Connect the
unit PCB? connector, and
operate the unit
again.
YES
Are
the current
sensors inversely YES
connected to 2 STD Correct the
compressors? connections
between the
current sensors
and the STD
NO compressors.
Applicable YES
compressor coil wire Replace the
is broken. compressor.
NO
Is the
current
sensor mounted on NO
Mount the
the T-phase and R- current sensor
phase wire? correctly, and
operate the unit
YES again.
Replace the
current sensor or
outdoor unit
PCB.
166
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective current sensor
Defective outdoor unit PCB
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
connector for
current sensor NO
connected to outdoor Connect the
unit PCB? connector, and
operate unit
again.
YES
Is the
current sensor NO
mounted on the T- Mount the
phase wire? current sensor
correctly, and
operate unit
YES again.
Replace the
current sensor
and outdoor unit
PCB.
167
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor for outdoor unit discharge pipe
Defective outdoor unit PCB
Defective thermistor connection
168
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Confirm which discharge
pipe thermistor is
abnormal using outdoor
unit "monitor mode".
Connector
is connected to NO
Connect the
outdoor unit PCB. connector and
turn ON again.
YES
Resistance
is normal when
measured after
disconnecting the NO
Replace the
thermistor from the thermistor.
outdoor unit PCB.
CHECK 11
YES
Replace the
outdoor unit
PCB.
169
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective heat exchanger gas pipe thermistor
Defective outside unit PCB
170
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
connector
for heat
exchanger gas pipe NO
thermistor connected Connect the
to outside unit connector and
PCB? operate unit
again.
YES
Is the
resistance
measured after
removing the NO
thermistor from outside Replace the
unit PCB normal? thermistor.
CHECK 11
YES
Replace the
outside unit PCB.
171
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor for outdoor unit suction pipe
Defective outdoor unit PCB
Defective thermistor connection
172
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Connector is NO
connected to outdoor Connect the
unit PCB. connector and
turn ON again.
YES
Resistance
is normal when
measured after
disconnecting the NO
thermistor from the Replace the
outdoor unit thermistor.
PCB.
CHECK 11
YES
Replace the
outdoor unit
PCB.
173
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor for outdoor unit coil
Defective outdoor unit PCB
Defective thermistor connection
174
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Confirm which thermistor
is abnormal using outdoor
unit "monitor mode".
Connector is NO
connected to outdoor Connect the
unit PCB. connector and
turn ON again.
YES
Resistance
is normal when
measured after
disconnecting the NO
thermistor from the Replace the
indoor unit PCB. thermistor.
CHECK 11
YES
Replace the
outdoor unit
PCB.
175
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective liquid pipe thermistor
Defective outdoor (outside) unit PCB
Defective thermistor connection
176
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Confirm which thermistor
is abnormal using outdoor
unit "monitor mode".
Is the
connector for
liquid pipe NO
thermistor connected to Connect the
outdoor (outside) connector and
unit PCB? turn ON again.
YES
Is the
resistance
measured after
removing the NO
thermistor from outdoor Replace the
(outside) unit PCB thermistor.
normal?
CHECK 11
YES
Replace the
outdoor (outside)
unit PCB.
177
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective thermistor
Defective connection of connector
Defective outdoor unit PCB (control PCB)
178
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check connectors for
connection.
NO
Normal? Connect
correctly.
YES
Remove thermistor from
outdoor unit PCB, then
measure the resistance
using a tester.
NO
Normal? Replace the
thermistor.
YES
Replace the
outdoor unit
control PCB.
179
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective subcooling heat exchanger gas pipe
thermistor
Defective outdoor unit PCB
180
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Confirm which thermistor
is abnormal using outdoor
unit "monitor mode".
Is the
connector for
subcooling heat
exchanger gas pipe NO
Connect the
thermistor connected connector and
to outdoor unit turn ON again.
PCB?
YES
Is the
resistance
measured after
removing the NO
thermistor from outdoor Replace the
unit PCB normal? thermistor.
CHECK 11
YES
Replace the
outdoor unit
PCB.
181
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective high pressure sensor system
Connection of low pressure sensor with wrong
connection.
Defective outdoor unit PCB.
Defective connection of high pressure sensor
182
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the
characteristics
of the high
pressure sensor
normal? (Make a NO
comparison between the Replace the high
voltage pressure sensor.
characteristics (∗1)
and the gauge
pressure.)
YES
Is
the
PCB
pressure
detection normal?
(Make a comparison NO
between the checker Replace the
pressure data and outdoor unit main
the voltage PCB.
characteristics
(∗1).)
YES
183
Troubleshooting by Indication on the Remote Controller
Are the
characteristics of NO
the high pressure Replace the high
sensor pressure sensor.
normal?
YES
Replace the
outdoor unit main
PCB.
Note:
∗1. Voltage measurement point
Red
GND Black
Micro-computer White
A/D input
184
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective high pressure sensor system
Connection of low pressure sensor with wrong
connection.
Defective outdoor (outside) unit PCB.
185
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
The
high pressure
sensor is connected NO
Connect the high
to outdoor (outside) pressure sensor
unit PCB. and turn ON
again.
YES
The
relationship
between the ∗1
VH and high
pressure is normal
(∗2) when voltage is YES
measured between Replace the
connector pins (1) outdoor (outside)
unit PCB.
and (3) of outdoor
(outside) unit
PCB
(∗1).
NO
Replace the high
pressure sensor.
186
Troubleshooting by Indication on the Remote Controller
GND Black
Micro-computer White
A/D input
187
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective low pressure sensor
Connection of high pressure sensor with wrong
connection
Defective outdoor unit PCB
Defective connection of low pressure sensor
188
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the
characteristics
of the low
pressure sensor
normal? (Make a NO
comparison between the Replace the low
voltage pressure sensor.
characteristics and
the gauge
pressure.)
YES
Is the
PCB
pressure
detection normal?
(Make a comparison NO
between the checker Replace the
pressure data and outdoor unit main
the voltage PCB.
characteristics
(∗1).)
YES
A
189
Troubleshooting by Indication on the Remote Controller
Are the
characteristics of NO
the low pressure Replace the low
sensor pressure sensor.
normal?
YES
Replace the
outdoor unit main
PCB.
Note:
∗1. Voltage measurement point
sensor
4 Red
GND
3 Black
Micro-computer 2 White
A/D input
1
190
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective low pressure sensor system
Connection of high pressure sensor with wrong
connection.
Defective outdoor (outside) unit PCB.
191
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
The low
pressure sensor is NO
connected to outdoor Connect low
(outside) unit pressure sensor
PCB. property and
restart system.
YES
The
relationship
between the ∗1
VH and low
pressure is normal
(∗2) when voltage is YES
measured between Replace the
connector pins (2) and outdoor (outside)
(3) of outdoor unit PCB A1P.
(outside) unit
PCB (A1P)
(∗1).
NO
Replace the low
pressure sensor.
192
Troubleshooting by Indication on the Remote Controller
Note:
∗1: Voltage measurement point
193
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Inverter PCB
z IPM failure
z Current sensor failure
z Drive circuit failure
194
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Do
the lead
wires have any YES
disconnection, broken Replace the lead
wire, short circuit, wires.
or ground
fault?
NO
Does
the power YES
supply normally It is supposed
come back that the error
ON? results from
external causes
NO other than
failures (e.g.
Is the exogenous
single system NO noises or
applied to the Multi system thunder).
outdoor unit?
While in monitor mode,
YES check the outdoor unit
Single system concerned.
While in monitor mode,
check whether the system
is right-hand (service
monitor PCB 1) or left-
hand (service monitor
PCB 3).
195
Troubleshooting by Indication on the Remote Controller
CHECK 4 NO
Check if the power
transistor is
normal.
Check if
YES insulation
resistance of the NO
Replace the
compressor is compressor and
100kΩ or compressor
more. inverter PCB at
the same time.
YES
Replace the
CHECK 4 inverter PCB.
Check if the power NO
transistor of the fan Replace the
driver is compressor
normal. inverter PCB and
fan inverter PCB.
YES
Replace the
inverter PCB.
196
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Main PCB
z IPM failure
z Current sensor failure
z Drive circuit failure
197
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Do
the lead
wires have any YES
disconnection, broken Replace the lead
wire, short circuit, wires.
or ground
fault?
NO
Does
the power YES
supply normally It is supposed
come back that the error
ON? results from
external causes
NO other than
failures (e.g.
exogenous
CHECK 4 NO noises or
Check if the power thunder).
transistor is
normal.
Check if
YES insulation
resistance of the NO
Replace the
compressor is outdoor unit main
100kΩ and PCB at the same
above. time.
YES
Replace the
A outdoor unit main
PCB.
198
Troubleshooting by Indication on the Remote Controller
CHECK 4
Check if the power NO
transistor of the fan Replace the
driver is outdoor unit main
normal. PCB.
YES
Replace the
outdoor unit main
PCB.
199
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective outdoor unit PCB
z IPM failure
z Current sensor failure
z Defective drive circuit
200
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Does
the power YES
supply normally It is supposed
come back that the error
ON? results from
external causes
NO other than
failures (e.g.
exogenous
CHECK 4 NO noises or
Check if the power thunder).
transistor is
normal.
Is the
YES insulation NO
resistance of the Replace the
compressor 100kΩ compressor and
or more? compressor
inverter PCB at
the same time.
YES
Replace the
inverter PCB.
CHECK 4
Check if the power NO
transistor of the fan Replace the
driver is compressor
normal. inverter PCB and
fan inverter PCB.
YES
Replace the
inverter PCB.
201
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Actuation of radiation fin thermal
Defective inverter PCB
Defective radiation fin thermistor
202
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
The
radiation
fin of the inverter YES
PCB concerned Defective
exceeded a radiation fin from
temperature the power unit
of 82˚C. • Blocked air
suction port
NO • Stained
radiation fin
Turn OFF the power • High outdoor air
supply, and then make temperature
measurement of • Fan propeller
resistance of the for damage
radiation fin thermistor.
Is the
thermistor NO
resistance normal? Replace the
CHECK 11 thermistor.
YES
Does
the error
recur when the YES
power supply turns ON Replace the
to start the compressor
compressor? inverter PCB.
NO
203
Troubleshooting by Indication on the Remote Controller
Continue operation.
z It is supposed
that the radiation
fin temperature
became high due
to some field
factors. In this
connection, check
the following
points:
• Stained
radiation fin
• Airflow
obstructed with
dirt or foreign
matters
• Damage to fan
propeller
• Too high
outdoor air
temperature
204
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Actuation of fin thermal
Defective inverter PCB
Defective radiation fin thermistor
205
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Temperature YES
of the radiation fin Defective power
rises. Actuates at unit radiation.
min. 96 ˚C • Intake port is
clogged
NO • Radiation fin is
dirty
Measure the resistance • Outdoor air
of the radiation fin temperature is
thermistor. high
Resistance
check of the radiation Abnormal
fin thermistor Replace the
thermistor.
CHECK 11
Normal
Is reset NO
possible? Replace the
inverter PCB
YES
Reset and
operate the unit.
206
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective compressor coil (disconnected, defective
insulation)
Compressor startup error (mechanical lock)
Defective inverter PCB
207
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Compressor inspection
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is NO
the stop valve Open the stop
open? valve.
YES
Check if
the compressor NO
Replace the
lead wires are compressor lead
normal. wires.
YES
Check
if the wiring NO
and connection to the Correct the
compressor are wiring and
normal. connection.
YES
Power OFF
Insulation
resistance of YES
the compressor is Replace the
100 kΩ or inverter
below. compressor.
NO
Compressor YES
coils are Replace the
disconnected. inverter
compressor.
NO
CHECK 4
Check if the NO
Replace the
power transistor is inverter PCB.
normal.
YES
A
208
Troubleshooting by Indication on the Remote Controller
Failure
occurs again after NO
Continue the
restarting the
unit.
YES
(
operation.
Momentary
power failure is
(
possible.
Replace the
inverter
compressor.
209
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective compressor coil (disconnected, defective
insulation)
Compressor startup error (mechanical lock)
Defective inverter PCB
210
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Compressor inspection
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
The
compressor's coil YES
is disconnected or the Replace the
insulation is compressor.
defective.
NO
Disconnect the connection
between the compressor
and inverter. Make the
power transistor check
mode setting ON by
service mode.
Inverter
output
voltage check
Inverter output
voltage is not
balanced. (Normal if
within ±10V for Y1, YL YES
Replace the
power supply and ±5V inverter unit.
for TL power supply)
Must be measured
when frequency
is stable.
NO
A
211
Troubleshooting by Indication on the Remote Controller
There is YES
instantaneous Correct the
power drop. power supply.
NO
Compressor
inspection
Inspect
according to the
diagnosis
procedure for
odd noises,
vibration and
operating status
of the
compressor.
212
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Compressor overload
Compressor coil disconnected
Defective inverter PCB
Disconnection of compressor
213
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Output current check
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is NO
the stop valve Open the stop
open? valve.
YES
Check if the NO
compressor lead wires Replace the
are normal. compressor lead
wires.
YES
Check
if the wiring NO
and connection to the Correct the
compressor are wiring and
normal. connection.
YES
Power OFF
Insulation
resistance of YES
the compressor is Replace the
100 kΩ or inverter
below. compressor.
NO
Compressor YES
coils are disconnected. Replace the
inverter
compressor.
NO
CHECK 4
NO
Check if the power Replace the
transistor is inverter PCB.
normal.
YES
Connect the compressor
lead wires then restart
the operation.
214
Troubleshooting by Indication on the Remote Controller
Error
code “L8” is NO
displayed again. Continue the
operation.
YES
Check if
the pressure
difference between
high pressure and low NO
Defective
pressure before pressure
restarting is equalizing in the
0.2MPa or refrigerant circuit.
below.
YES
Inspection of the
compressor.
215
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Compressor overload
Compressor coil disconnected
Defective inverter PCB
216
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Output current check
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
The
secondary
current of the
inverter is higher
than 16.5A (Y1, YL YES
power supply) and Compressor
25.1 A (TL power overload
supply) for Inspection of the
each compressor and
phase. refrigerant
system is
required.
NO
Compressor
inspection. The YES
compressor's coil is Replace the
disconnected. compressor.
NO
Disconnect the connection
between the compressor
and inverter. Make the
power transistor check
mode setting ON by
service mode.
217
Troubleshooting by Indication on the Remote Controller
Inverter
output
voltage check
Inverter output
voltage is not
balanced. (Normal if NO
within ±10V for Y1, YL Replace the
power supply and ±5V inverter PCB.
for TL power supply)
Must be measured
when frequency
is stable.
YES
After
turning ON NO
Reset and
again, "L8" blinks restart.
again.
YES
Compressor
inspection
Inspect
according to the
diagnosis
procedure for
odd noises,
vibration and
operating status
of the
compressor.
218
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Stop valve is not opened.
Defective compressor
Wiring connection error to the compressor
Large pressure difference before starting the
compressor
Defective inverter PCB
219
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check
if it is the first NO
time to start after B
installation.
YES
Check
if a right NO
amount of refrigerant Charge a right
is charged. amount of
refrigerant.
YES
Check
if the stop NO
Open the stop
valve is open. valve.
YES
Refrigerant
is melting in
refrigerant oil. (The YES
unit is out of power Cancel the
supply for more melting state of
than 6 hours.) refrigerant.
NO
Check if
the insulation
resistance of the NO
Cancel the
compressor is more melting state of
than 100kΩ. refrigerant.
YES
A
220
Troubleshooting by Indication on the Remote Controller
Check if the
compressor lead YES
wires are Fix the
disconnected. compressor lead
wire.
NO
Correct the
wiring then
supply power to
restart.
221
Troubleshooting by Indication on the Remote Controller
Refrigerant
is melting in
refrigerant oil. (The NO
unit is out of power Cancel the
supply for more melting state of
than 6 hours.) refrigerant.
YES
Check if
the insulation
resistance of the NO
Replace the
compressor is inverter
100kΩ or compressor.
more.
YES
Broken YES
inside the Replace the
compressor inverter
compressor.
NO
CHECK 4
NO
Check if the power Replace the
transistor is compressor
normal. inverter PCB.
YES
Recheck the
compressor/
refrigerant circuit.
222
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective compressor
Pressure differential start
Defective inverter PCB
223
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
The
difference
between high NO
and low pressure when Unsatisfactory
starting is above pressure
0.2MPa or equalization
more. Check refrigerant
system.
YES
Inverter
output
voltage check
Inverter output
voltage is not
balanced. (Normal if
within ±10V for Y1, YL NO
power supply and ±5V Replace the
for TL power supply) inverter PCB
Must be measured
when frequency
is stable.
YES
A
224
Troubleshooting by Indication on the Remote Controller
After
turning ON NO
Reset and
again, "L9" blinks restart.
again.
YES
Compressor
inspection
Inspect
according to the
diagnosis
procedure for
odd noises,
vibration and
operating status
of the
compressor.
225
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective connection between the inverter PCB and
control PCB
Defective control PCB (transmission section)
Defective inverter PCB
Defective noise filter
Defective fan inverter
Incorrect type of inverter PCB
Defective inverter compressor
Defective fan motor
External factor (Noise etc.)
226
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the
connectors of
the inverter PCB, NO
control PCB, and sub Properly connect
PCB all securely the connectors.
connected?
YES
Is the NO
type of the inverter Replace it with a
PCB correct? correct PCB.
YES
The INV.
compressor has YES
insulation resistance of Replace the
not more than compressor
100kΩ. (M1C).
NO
The fan
motor has YES
insulation resistance of Replace the fan
not more than motor.
1MΩ.
NO
The micro-
computer
normal monitor NO
Not the "LC"
(green) of the control error. Check the
PCB is blinking. error code again.
YES
A
227
Troubleshooting by Indication on the Remote Controller
The
micro-
computer normal NO
monitor (green) of the Replace the
inverter PCB is inverter PCB.
blinking. ∗ If the spare
PCB has
significant
damage, the
YES compressor is
probably get
defective. In
this case, carry
out inspections
on the
compressor
again.
The YES
"LC" error Replace the
recurs. control PCB.
NO
Continue the
operation.
(It is supposed
that the error
results from
causes such as
instantaneous
power failure.)
228
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective connection between the inverter PCB and
outdoor (outside) unit control PCB
Defective outdoor (outside) unit control PCB
(transmission section)
Defective inverter PCB
Defective noise filter
External factor (Noise etc.)
229
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the
connectors
between the main NO
PCB, and inverter Connect
PCB connected transmission
securely? wiring and turn
ON again.
YES
The
transmission
wiring between the YES
outdoor (outside) unit Fix the
PCB inverter unit is disconnection
disconnected. and turn ON
again.
NO
The micro-
computer monitor YES
(green) on the Defective
inverter PCB is outdoor (outside)
blinking. unit main PCB or
defective inverter
PCB.
NO
The
voltage
between 2 pins YES
of connector on the Replace the
inverter unit is 220 ~ inverter PCB.
240 V.
When the LC
NO error occur
again, replace
the control PCB.
230
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Error of connection between the inverter PCB and
outdoor unit control PCB
Defective outdoor unit control PCB (transmission
section)
Defective inverter PCB
Defective noise filter
External factor (Noise etc.)
231
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the
connectors
between the
outdoor unit main NO
PCB, fan drive PCB and Connect
inverter PCB transmission
connected wiring and turn
securely? ON again.
YES
The
transmission
wiring between
the outdoor unit PCB, YES
fan drive board and Fix the
inverter unit is disconnection
disconnected. and turn ON
again.
NO
The micro-
computer monitor NO
(green) on fan drive Check
board is connection of the
blinking. connector.
YES
The micro-
computer monitor YES
(green) on the inverter Defective
PCB is blinking. outdoor unit main
PCB or defective
inverter PCB.
NO
232
Troubleshooting by Indication on the Remote Controller
The
voltage
between red
and white of YES
connector on the Replace the
inverter unit is inverter PCB.
220 ~ 240 V.
When the LC
error occur
NO again, replace
the control PCB.
233
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Open phase
Voltage imbalance between phases
Defective main circuit capacitor
Defective inverter PCB
Defective relay in inverter PCB
Improper main circuit wiring
234
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is an
imbalance in
supply voltages in YES
excess of 14V for 460V
units or 6V for
230V units? YES
(See ∗1) Open phase? Open phase
Normalize the
NO field cause.
NO
Repair the
power supply
voltage
Is an imbalance.
imbalance in
voltages applied
to the inverter in YES
excess of 14V for 460V Parts or wiring
units or 6V for defect
230V units? After turning the
(See ∗2) power supply
OFF, check and
repair the main
circuit wiring or
NO parts.
<When voltage monitoring is possible:> (1) Loose or
disconnected
wiring
Using a device capable between
of constant recording of power supply
power supply voltage and inverter
record power supply (2) Magnetic
voltage between 3 contact
phases (L1~L2, L2~L3, disposition,
L3~L1) for about one fusion or
continuous week. contact is
poor.
No abnormalities are (3) Loose or
observed in the power disconnected
supply, but the imbalance noise filter
in voltage recurs.
Power supply voltage
imbalance
Even if the power supply
voltage is not unbalanced
when measuring it, there
are many cases where it
gets unbalanced during
night-time (around
6:00PM to 10:00PM).
measure
Replace the
inverter PCB.
A
235
Troubleshooting by Indication on the Remote Controller
Note:
∗1. Measure voltage at the power supply terminal block.
∗2. Measure voltage at terminals RED, WHITE and
BLACK wire of the diode module inside the inverter
while the compressor is running.
236
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Open phase
Voltage imbalance between phases
Defective main circuit capacitor
Defective inverter PCB
Defective magnetic contact switch
Improper main circuit wiring
237
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Imbalance in
supplied voltage is YES
in excess of 14 V (YL)
and 10V (TL). ∗1
YES
Open phase? Open phase
Normalize field
NO NO cause.
Fix power
supply voltage
imbalance.
Is the
voltage
imbalance applied YES
to the inverter in Part or wiring
excess of 14 V (YL) defect
and 10V (TL)? After turning the
∗2 power supply
OFF, check and
repair the main
NO circuit wiring or
<When voltage monitoring is possible:> parts.
(1) Loose or
disconnected
wiring
between
power supply
and inverter
Using a device capable (2) Magnetic
of constant recording of contact
power supply voltage disposition,
record power supply fusion or
voltage between 3 contact is
phases (L1 ~ L2, L2 ~ poor.
L3, L3~L1) for about (3) Loose or
one continuous week. disconnected
noise filter
∗1. Measure voltage at the power
supply terminal block.
∗2. Measure voltage at terminals
L1, L2 and L3 of the diode
module inside the inverter
while the compressor is
Power supply voltage imbalance running.
measure
238
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective radiation fin thermistor
Defective inverter PCB
Defective inverter compressor
Defective fan motor
239
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
YES
The INV.
compressor's YES
insulation resistance is Replace the
not more than compressor
100kΩ. (M1C).
NO
The fan
motor's insulation YES
resistance is not Replace the fan
more than motor.
1MΩ.
NO
Does the
error recur when YES
the power supply Replace the
turns ON? inverter PCB.
NO
Continue the
operation.
240
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective radiation fin thermistor
Defective inverter PCB
241
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
resistance of NO
thermistor Replace the
correct? inverter PCB.
(Thermistor can
YES not be removed
from the inverter
PCB)
Is the resetting NO
Replace the
possible? inverter PCB.
YES
After resetting,
restart.
242
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective (or no) field setting after replacing outdoor
unit main PCB
Mismatching of type of PCB
243
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Was
the PCB NO
replaced with a spare
PCB?
YES
Is the model NO
setting of the spare Make correct
PCB correct? setting of DIP
switch.
YES
Is the
type of the NO
compressor inverter Replace it with
PCB correct? the correct
compressor
inverter PCB.
YES
Is the
type of the fan NO
inverter PCB Replace it with
correct? the correct fan
inverter PCB.
YES
Does the
preparation NO
indication lamp on the Rectify the
main PCB turn connection
OFF? wiring.
YES
Replace the
outdoor unit
PCB.
244
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Mismatching of type of PCB
Defective (or no) field setting after replacing main PCB
245
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
type of the NO
compressor inverter Replace it with
PCB correct? the correct
compressor
inverter PCB.
YES
Is the
type of the fan NO
inverter PCB Replace it with
correct? the correct fan
inverter PCB.
YES
Is the
setting of dip NO
switches when replace Set the DIP
the main PCB switches
correct? correctly.
(After setting:
YES Reset the power
supply)
Does the
preparation NO
indication lamp (H2P) Rectify the
on the main PCB connection
turn OFF? wiring.
YES
Replace the
outdoor unit main
PCB.
246
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Defective (or no) field setting after replacing main PCB
Mismatching of type of PCB
247
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Has the
PCB been NO
replaced?
YES
When
replacing the NO
PCB, were field setting Correct the field
properly settings.
made?
YES
Is the type of NO
PCB correct? Replace with a
(∗1) correct PCB.
YES
Reset, and then
restart.
Note:
∗1. Type of PCB mismatching includes;
Main PCB
Inverter PCB (for compressor)
Fan driver PCB
248
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Mismatching of inverter PCB
Defective field setting
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Was the NO
PCB replaced? Replace the
PCB.
YES
Is the NO
PCB type Replace the PCB
correct? by the correct
one.
YES
Is the
field setting NO
when the PCB was Correct field
replaced setting.
correct?
YES
After resetting,
restart.
249
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Refrigerant shortage or refrigerant clogging (piping
error)
Defective thermistor
Defective low pressure sensor
Defective outdoor unit PCB
250
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
In cooling mode
Set up a pressure gauge at the service port on the
low pressure side.
Reset the operation using the remote controller
then restart.
Check
if the low NO
pressure is 0.1MPa
or below. (∗1)
Check if the
YES property of low NO
pressure sensor is Replace the low
normal. (∗2) pressure sensor.
YES
Replace the main
PCB.
Remove the
factor of
In heating mode decreasing low
Reset the operation using the remote controller pressure by
then restart. referring to
CHECK 2 .
Check if
the
temperature
difference between NO
the suction pipe and
the heat exchanger
is 20˚C and
over. Check if
the property
of suction pipe NO
thermistor and heat Replace the
YES exchanger thermistor thermistor.
are normal. (∗3)
YES
Replace the
outdoor unit main
PCB.
Remove the
factor of
superheating by
referring to
CHECK 3 .
251
Troubleshooting by Indication on the Remote Controller
Note:
∗1. Check the low pressure value by using pressure
gauge in operation.
∗2. Compare the actual measurement value by pressure
sensor with the value by the pressure gauge.
(To gain actual measurement value by pressure
sensor, measure the voltage at the connector
[between (2)-(3)] and then convert the value into
pressure CHECK 12 .)
∗3. Compare the thermistor resistance value with the
value on the surface thermometer.
252
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Refrigerant shortage or clogged refrigerant (wrong
piping)
Defective thermistor
Defective low pressure sensor
Defective main PCB
253
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
In cooling
Set up a pressure
gauge in the service
port on the low
pressure side.
Connect the Service
Checker.
Reset operation with a
remote controller and
restart operation.
Are
the low
pressure sensor NO
characteristics normal? Replace the low
(∗1) pressure sensor.
YES
Is the PCB
detector pressure NO
Replace the main
normal? (∗2) PCB.
YES
CHECK 2
Note:
∗1: Compare pressure sensor measurements with
pressure gauge readings.
(For measurements by a pressure sensor, measure
voltage between connectors (2) and (3) and convert
it to pressure in accordance with CHECK 12 .)
∗2: Compare low pressure measured by the Service
Checker with pressure sensor measurements (∗1).
254
Troubleshooting by Indication on the Remote Controller
In heating
Connect the Service
Checker.
After resetting
operation with a remote
controller, restart
operation.
Are
characteristics of
the suction pipe NO
thermistor and the heat Replace the
exchanger thermistor.
thermistor
normal?
(∗3)
YES
Is PCB
detection NO
temperature normal? Replace the main
(∗4) PCB.
YES
CHECK 3
Note:
∗3: Compare the thermistor resistance with surface
thermostat measurements.
∗4: Compare the suction pipe temperature checked by
the Service Checker with measurements obtained in
∗3 above.
255
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Shortage of gas or refrigerant system clogging
(incorrect piping)
Defective pressure sensor
Defective outdoor unit PCB
Defective thermistor
256
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
YES
Cooling
NO Low YES
pressure is 0.1 MPa Shortage of
or less. refrigerant,
closing of stop
NO valve or
refrigerant
system is
The clogged.
voltage Requires check
of of refrigerant
connector pins system.
(2) and (3) on
main outdoor unit YES
PCB is 0.8 VDC or less. Replace the main
(Low pressure sensor outdoor unit
output voltage) PCB.
CHECK 12
NO
The Replace the low
suction pipe pressure
temperature YES sensor.
minus coil temperature Shortage of gas
is 20 ˚C or or refrigerant
higher. system is
clogged.
Requires check
NO of refrigerant
system.
A
257
Troubleshooting by Indication on the Remote Controller
Resistance
is normal when
measured with the
suction pipe thermistor NO
and heat exchanger Replace the
thermistor disconnected thermistor.
from the outdoor unit
PCB.
CHECK 11
YES
Replace the
outdoor unit
PCB.
258
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Power supply reverse phase
Power supply open phase
Defective outdoor (outside) unit PCB
259
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
There is
an open phase
at the power supply YES
terminal of the Rectify the open
outdoor phase.
(outside) Requires
unit. inspection of field
power supply
NO section.
Operation
is normal if one YES
place of power supply Reverse phase
line phase is Countermeasure
replaced. of the problem is
completed by
phase
NO replacement.
Replace the
outdoor (outside)
unit PCB.
260
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Power supply insufficient
Instantaneous power failure
Open phase
Defective inverter PCB
Defective control PCB
Defective main circuit wiring
Defective compressor
Defective fan motor
Defective connection of signal cable
261
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check
for power
supply voltage.
Voltage between NO
Onsite causes.
phases: 460V ± 10% Make proper wire
or 208/230V connections
± 10%. without open
phase, erroneous
Power ON connections, or
YES erroneous order
of phases.
Unbalanced
power supply?
(Not more than 2%: NO
Onsite causes
Phase voltage of not Correct the
more than unbalanced
approx. 5V) loads to eliminate
the unbalanced
state.
YES Unbalanced
voltage will
For 230V units: cause extremely
(1) Does the power supply unbalanced
voltage fall in the current, thus
range of 230V±10%? impairing the
(2) Is there any open service life of or
phase or erroneous resulting in the
wiring in the power defective the
supply line? equipment.
(3) Is an imbalance in
power supply voltage
not more than 6V?
The
insulation YES
resistance is low (i.e., Replace the
not more than compressor.
100kΩ.)
NO
A
262
Troubleshooting by Indication on the Remote Controller
The
insulation YES
resistance is low (i.e., Replace the fan
not more than motor.
1MΩ.) Replace the fan
driver.
NO
Check the inverter power
transistor.
263
Troubleshooting by Indication on the Remote Controller
264
Troubleshooting by Indication on the Remote Controller
Stop YES
(standby) before the Recheck for the
fan rotates. power supply. If
there is no
NO problem with the
power supply,
replace the noise
filter PCB.
If the error
Stop recurs, replace
Power ON the inverter PCB.
(standby) YES
when the compressor Recheck for the
starts up. power supply. If
there is no
problem with the
NO power supply,
replace the
inverter PCB.
∗If the PCB
replaced is
badly damaged,
compressor is
likely to get
defective. To
make sure,
recheck the
compressor.
The "U2" YES
error recurs. Check the
harness, and
then replace it if
necessary.
NO
End of
measures:
∗ The error may
temporarily
result from
onsite causes.
Causes:
Instantaneous
power failure
(open phase),
noises, or else.
265
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Power supply insufficient
Instantaneous power failure
Open phase
Defective inverter PCB
Defective outdoor control PCB
Defective compressor
Defective main circuit wiring
Defective fan motor
Defective connection of signal cable
266
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
There are
problems on the YES
condition of power Correct the
supply described problem.
above.
NO
The
insulation
resistance of YES
compressor is not Replace the
more 100kΩ. compressor.
NO
The
insulation
resistance of fan YES
Replace the fan
motor is not more motor.
1MΩ. ∗ If the fan
motor is badly
damaged,
NO replace the
inverter PCB.
CHECK 4 NO
Is the power Replace the
transistor inverter PCB.
normal?
YES
267
Troubleshooting by Indication on the Remote Controller
Stop
(standby) before YES
Replace the
the fan rotates. noise filter PCB.
(Defective noise
NO filter)
Stop
(standby) when YES
the compressor Replace the
startup. inverter PCB.
∗ If the inverter
NO PCB is badly
damaged,
recheck the
compressor.
268
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Power supply insufficient
Instantaneous failure
Open phase
Defective inverter PCB
Defective outside control PCB
Defective magnetic contact switch.
Defective main circuit wiring
269
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is
connection
wire connected NO
Repair wiring.
between the
connector?
YES
Turn ON again.
Turn the NO
magnetic contact A
switch ON.
YES
The
voltage
between the
P2 (or P3) and
N3 terminals is 320 NO
VDC (Y1, YL) or more Replace the
and 190 VDC (TL) or inverter PCB.
less when the
compressor is
running.
YES
Monitor field
power supply.
270
Troubleshooting by Indication on the Remote Controller
Is
220 ~ 240 V
of power reaching YES
the magnetic contact Replace the
switch coil? magnetic contact
switch.
NO
Does
the voltage
between
terminals P2 (or P3) YES
and N3 gradually rise to Replace the
556 VDC (Y1, YL) or inverter PCB.
283 VDC (TL)
after turning
ON?
NO
Is 220 ~
240 V at the YES
connector inverter Replace the
PCB. inverter PCB.
NO
Is
220 ~ 240 V
at the connector NO
Replace the
outside PCB side? outside unit PCB.
YES
Check the
transmission
wiring between
the outside unit
PCB and inverter
unit.
271
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Power supply insufficient
Instantaneous power failure
Open phase
Defective outdoor unit control PCB
Defective main circuit wiring
Defective compressor
Defective fan motor
Defective connection of signal cable
272
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check
for power
supply voltage.
Voltage between NO
Onsite causes.
phases: 380 to 415V Make proper wire
Phase voltage: connections
220 to without open
240V phase, erroneous
Power ON connections, or
YES erroneous order
of phases.
Unbalanced
power supply?
(Not more than 2%: NO
Onsite causes
Phase voltage of not Correct the
more than unbalanced
approx. 5V) loads to eliminate
the unbalanced
state.
YES Unbalanced
voltage will
Disconnect the cable from cause extremely
the compressor, and then unbalanced
Power OFF check the compressor for current, thus
the insulation resistance. impairing the
service life of or
resulting in the
error of the
The equipment.
insulation YES
resistance is low (i.e., Replace the
not more than compressor.
100kΩ.)
NO
Disconnect the cable from
the fan, and then check
the fan motor for the
insulation resistance.
The
insulation YES
resistance is low (i.e., Replace the fan
not more than motor.
1MΩ.) Replace the fan
driver.
NO
A
273
Troubleshooting by Indication on the Remote Controller
274
Troubleshooting by Indication on the Remote Controller
Stop YES
(standby) before the Recheck for the
fan rotates. power supply. If
Power ON there is no
NO problem with the
power supply,
C replace the noise
filter PCB.
If the error
recurs, replace
the inverter PCB.
275
Troubleshooting by Indication on the Remote Controller
Stop
(standby) YES
when the compressor Recheck for the
starts up. power supply. If
there is no
problem with the
Power ON NO power supply,
replace the main
PCB.
∗If the PCB
replaced is
badly damaged,
compressor is
likely to get
defective. To
make sure,
recheck the
compressor.
The "U2" YES
error recurs. Check the
harness, and
then replace it if
necessary.
NO
End of
measures:
∗ The error may
temporarily
result from
onsite causes.
Causes:
Instantaneous
power failure
(open phase),
noises, or else.
276
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Power supply insufficient
Instantaneous failure
Open phase
Defective inverter PCB
Defective outdoor (outside) control PCB
Defective magnetic contact switch.
Defective main circuit wiring
277
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is
connection
wire connected NO
Repair the wiring.
between the
connector?
YES
Turn ON again.
Turn the NO
magnetic contact A
switch ON.
YES
The
voltage
between the
P2 (or P3) and
N3 terminals is 320 NO
VDC (YL) or more and Replace the
190 VDC (TL) or less inverter PCB.
when the
compressor is
running.
YES
Monitor field
power supply.
278
Troubleshooting by Indication on the Remote Controller
Is 220 ~
240 V of power
reaching the YES
Replace the
magnetic contact magnetic contact
switch coil? switch.
NO
Does
the voltage
between
terminals P2 (or P3) YES
and N3 gradually rise to Replace the
556 VDC (YL) or 283 inverter PCB.
VDC (TL) after
turning on?
NO
Is 220 ~
240 V at the YES
connector of inverter Replace the
PCB. inverter PCB.
NO
Is 220 ~
240 V at the NO
connector of outdoor Replace the
(outside) PCB outdoor (outside)
side? unit PCB.
YES
Check the
transmission
wiring between
the outdoor
(outside) unit
PCB and inverter
unit.
279
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Power supply insufficient
Instantaneous failure
Defective inverter PCB
Defective outdoor control PCB
Defective main circuit wiring
280
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is
connection
wire connected NO
between the Repair the wiring.
connector?
YES
Turn ON again.
Does the
voltage
between terminals NO
P and N gradually rise Replace the
to 283VDC after inverter PCB.
turning ON?
YES
The
voltage
between the P
and N terminals is NO
400VDC and 190VDC Replace the
or more when the inverter PCB.
compressor is
running.
YES
Is
220V applied YES
at LB and NB on Replace the
the noise filter inverter PCB.
PCB?
NO
A
281
Troubleshooting by Indication on the Remote Controller
Is
200V at the NO
connector of outdoor Monitor field
unit PCB side? power supply.
YES
Check the
transmission
wiring between
the outdoor unit
PCB and inverter
unit.
282
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Check operation is not executed.
283
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Has
the check NO
operation performed Press and hold
on outdoor unit BS4 on the
PCB? outdoor unit main
PCB for 5
YES seconds or more,
or turn ON the
field setting
mode 2-3 to
conduct a check
operation.
Performs the
check operation
again and
completes the
check operation.
When a leakage
detection
function is
needed, normal
operation of
charging
refrigerant must
be completed.
And then,
start once again
and complete a
check operation.
284
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Indoor to outdoor, outdoor to outdoor transmission
wiring F1, F2 disconnection, short circuit or wrong
wiring
Outdoor unit power supply is OFF
System address does not match
Defective indoor unit PCB
Defective outdoor unit PCB
285
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Has
the indoor
or outdoor unit
PCB been
replaced, or has the YES
indoor - outdoor or Press and hold
outdoor - outdoor the RESET
unit transmission button on the
wiring been outdoor unit main
modified? PCB for 5
seconds.
∗ The unit will not
operate for up
NO to 12 minutes.
All indoor
unit remote NO
controllers of the same
refrigerant system
display "U4".
Is indoor -
YES outdoor and
outdoor - outdoor unit YES
Replace the
transmission wiring indoor unit PCB
normal? indicated by the
Reset the power supply. error code "U4".
NO
Fix the indoor-
Outdoor outdoor or
unit PCB micro- NO outdoor-outdoor
computer monitor unit transmission
(HAP) blinks. wiring.
The
YES voltage between
terminals L1 and N of NO
Supply 220~240 V.
the outdoor unit PCB
is 220~240 V.
B
YES
A
286
Troubleshooting by Indication on the Remote Controller
The
fuse on the YES
outdoor unit's PCB is Replace the fuse.
burnt.
NO
Replace the
outdoor unit
PCB.
287
Troubleshooting by Indication on the Remote Controller
Operation NO
ready lamp (H2P) is
blinking.
YES
Lamp
does not go YES
OFF for 12 minutes or Press and hold
more. the RESET
button on the
outdoor unit PCB
NO for 5 seconds.
Is
indoor -
outdoor and
outdoor - outdoor unit NO
Fix the indoor -
transmission wiring outdoor or
normal? outdoor - outdoor
unit transmission
wiring.
YES
Disconnect
the outdoor -
outdoor unit
transmission wiring, and NO
Replace the
then check with a outdoor unit
single system PCB.
whether or not
it is normal.
YES
Mount the DIII-
NET expander
adaptor.
288
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Indoor to outdoor, outdoor to outdoor transmission
wiring F1, F2 disconnection, short circuit or wrong
wiring
Outdoor unit power supply is OFF
System address does not match
Defective outdoor unit main PCB
Defective indoor unit PCB
289
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
In
Confirmation
of error 4, LED Go on to P.282.
NO LED lamp
lamp indicates as
follows:? ( display
)
YES
Check
if indoor
unit PCB or
outdoor unit
PCB has been
replaced. Or check if YES
Press the
indoor-outdoor, outdoor- RESET button on
outdoor connecting the main PCB of
wires has been the master
modified. outdoor unit.
Keep pressing
for 5 seconds or
more. (Operation
NO does not start for
a maximum 12
Do minutes.)
all the
indoor remote
controllers within the NO
same refrigerant
circuit display
“U4”? Are
the indoor-
outdoor, outdoor- YES
YES outdoor connecting Replace the
wires normal? indoor unit PCB.
A
NO
Correct the
connecting wires.
290
Troubleshooting by Indication on the Remote Controller
Does
the normal
condition monitor
for the micro-computer NO
(HAP) on the outdoor
unit PCB blink?
Is the
voltage between NO
R, S terminals on the Correct the
YES outdoor unit PCB voltage (400V).
400V?
YES
Lights
do not go out for YES
Press the
12 minutes or RESET button on
more. the main PCB of
NO the outdoor unit
main PCB. Keep
pressing for 5
seconds or more.
Are
the indoor-
outdoor, outdoor- NO
outdoor connecting Correct the
wires normal? connecting wires.
YES
291
Troubleshooting by Indication on the Remote Controller
Check if the
operation is
normal with 1 circuit NO
after outdoor-outdoor Replace the
connecting wires are outdoor unit main
disconnected. PCB.
YES
Install DIII-Net
expander
adaptor.
292
Troubleshooting by Indication on the Remote Controller
Do all NO
the units indicate Continue the
“U9”? operation.
YES
Did
more than 2 NO
minutes pass since Make a diagnosis
“U9” was again based on
indicated? the indication in 2
minutes and
YES over.
The indoor units
PCB indicating
“U9” are normal.
Check the indoor
units in the other
circuits to
diagnose failure
according to the
corresponding
error codes.
293
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Indoor to outdoor, outside to outside unit transmission
wiring F1, F2 disconnection, short circuit or wrong
wiring
Outdoor (outside) unit power supply is OFF
System address does not match
Defective indoor unit PCB
Defective outdoor (outside) unit PCB
294
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Has the
indoor or
outdoor
(outside) unit PCB
been replaced, or has
the indoor - outdoor YES
Press and hold
(outside) or outdoor the RESET
(outside) - outdoor button on the
(outside) unit master outdoor
transmission (outside) unit
wiring been PCB for 5
modified? seconds.
∗ The unit will not
operate for up
to 12 minutes.
NO
All
indoor unit
remote controllers NO
of the same refrigerant
system display
"U4."
Is
indoor -
YES outdoor (outside)
and outdoor (outside) YES
-outdoor (outside) unit Replace the
transmission wiring indoor unit PCB.
normal?
Reset the power supply.
A NO
Fix the indoor -
outdoor (outside)
unit transmission
wiring.
295
Troubleshooting by Indication on the Remote Controller
Outdoor
(outside) unit
PCB micro- NO
computer monitor
(HAP) blinks.
The
voltage
between
YES terminals L1 and N of NO
Supply 220~240 V.
the outdoor (outside)
unit PCB is
220~240 V.
YES
The
fuse on the YES
outdoor (outside) unit's Replace the fuse.
PCB is burnt.
NO
The
secondary
voltage of the NO
Replace the
transformer is transformer.
about 22 V. replacement.
Operation ready NO YES
lamp (H2P) is Replace the
blinking. outdoor (outside)
unit PCB.
YES
Lamp
does not go off YES
for 12 minutes or Press and hold
more. the RESET
button on the
outdoor (outside)
NO unit PCB for 5
seconds.
B
296
Troubleshooting by Indication on the Remote Controller
Is indoor -
outdoor (outside)
unit and outdoor
(outside) unit - outdoor NO
(outside) unit Fix the indoor -
transmission wiring outdoor (outside)
normal? unit transmission
wiring.
YES
Replace the
outdoor (outside)
unit PCB.
297
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Indoor unit and remote controller transmission error
Connection of 2 main remote controllers (when using
2 remote controllers)
Defective indoor unit PCB
Defective remote controller PCB
Defective transmission caused by noise
298
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Using 2- YES
remote controllers
control.
NO SS1 of
NO both remote YES
controllers is set to Set one remote
"MAIN." controller to
"SUB"; turn the
power supply
OFF once and
All then back ON.
indoor unit PCB NO
micro-computer
monitors
blink.
YES Operation
returns to
normal when the NO
Replace the
power is turned OFF indoor unit PCB.
momentarily.
YES
Normal Normal
NO
There is
possibility of
error caused by
noise. Check the
surrounding area
and turn ON
again.
299
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Improper connection of transmission wiring between
outdoor unit and external control adaptor for outdoor
unit
Improper connection of transmission wiring between
outdoor units of multi outdoor unit connection
Improper cool/heat selection
Improper cool/heat unified address
(outdoor unit, external control adaptor for outdoor unit)
Defective outdoor unit PCB
Defective external control adaptor for outdoor unit
300
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check the LED lamps for
“Check 3” corresponding
to the error code “U7” and
for Check 4 in the
monitor mode.
Check 3 Check 4
Go on to the
Diagnosis Flow
1 (Defective
transmission
caused when
the external
control adaptor
for outdoor unit
Check 3 Check 4 is mounted)
Go on to the
Diagnosis Flow
2 (Transmission
alarm given
when the
external control
adaptor for
outdoor unit is
Check 3 Check 4 mounted)
Go on to the
Diagnosis Flow
3 (Abnormal
transmission
between the
master unit and
Check 3 Check 4 the slave unit 1)
Go on to the
Diagnosis Flow
4 (Abnormal
transmission
between the
master unit and
Check 3 Check 4 the slave unit 2)
Go on to the
Diagnosis Flow
5 (Multi-
connection
Check 3 Check 4 units)
Go on to the
Diagnosis Flow
6 (Erroneous
A manual address
settings of the
slave units 1
and 2)
301
Troubleshooting by Indication on the Remote Controller
Check 3 Check 4
Go on to the
Diagnosis Flow
7 (Connection
of 4 or more
outdoor units to
the same
Check 3 Check 4 circuit)
Go on to the
Diagnosis
Flow 8
(Defective
auto address
of the slave
units 1 and 2)
302
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 1
Check of error 3 Check of error 4
Check if any
disconnection or
connection error is YES
detected in connecting Correct the
wires with external connecting wiring
control adaptor with the external
for outdoor control adaptor
unit. for outdoor unit.
NO
Check if the
normal condition NO
monitor LED for the
outdoor unit PCB
blinks.
Check
if power is NO
YES supplied to the Supply the power
outdoor units. to the outdoor
A unit.
YES
Replace the
outdoor unit main
PCB.
303
Troubleshooting by Indication on the Remote Controller
Check if
the normal
condition monitor NO
LED for the external
control adaptor for
outdoor unit
blinks. Check if
the power
YES supply wire for the NO
external control Connect the
adaptor for outdoor power supply
unit is connected wire for the
to 5V supply external control
line. adaptor for
outdoor unit to
YES 5V supply line.
Replace the PCB
of the external
control adaptor
for outdoor unit.
Replace the
outdoor unit main
PCB.
304
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 2
Check of error 3 Check of error 4
Cool/Heat NO
selection is unified. C/H SELECT of
the external
control adaptor
YES for outdoor unit is
set to “IND”.
Setting of
C/H SELECT of
the external control YES
The unified
adaptor for outdoor addresses for
unit is “unified COOL/HEAT
MASTER”. within the
outdoor/outdoor
transmission are
NO duplicated. Set
the address
again.
Setting of
C/H SELECT of
the external control NO
Replace the
adaptor for outdoor outdoor unit main
unit is “SLAVE”. PCB.
YES
Check if
the normal NO
condition monitor LED
for the outdoor unit
main PCB
blinks. Check
if power is NO
YES supplied to the Supply the power
outdoor unit. to the outdoor
A unit.
YES
Replace the
outdoor unit main
PCB.
305
Troubleshooting by Indication on the Remote Controller
Check if
the normal
condition monitor NO
LED for the external
control adaptor for
outdoor unit
blinks. Check if
the power
YES supply wire for the NO
external control adaptor Connect the
for outdoor unit is power supply
connected to 5V wire for the
supply line. external control
Set adaptor for
the C/H outdoor unit to
SELECT of 5V supply line.
the external YES
control adaptor for NO
Replace the PCB
outdoor unit to “IND”. of the external
Then check if the control adaptor
error occurs for outdoor unit.
again.
YES
Replace the
outdoor unit main
PCB.
306
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 3
Check of error 3 Check of error 4
Check the
connection
status of
connecting wires
of the outdoor multi to NO
SLAVE 1. Check if the Replace the
wiring is disconnected outdoor unit main
or is about to be PCB of the
disconnected. SLAVE 1.
YES
Correct the
connecting wires
of the outdoor
multi and then
reset the power
supply.
307
Troubleshooting by Indication on the Remote Controller
Diagnosis Flow 4
Check of error 3 Check of error 4
Check the
connection
status of
connecting wires
of the outdoor multi to NO
SLAVE 2. Check if the Replace the
wiring is disconnected outdoor unit main
or is about to be PCB of the
disconnected. SLAVE 2.
YES
Correct the
connecting wires
of the outdoor
multi and then
reset the power
supply.
Diagnosis Flow 5
Check of error 3 Check of error 4
Check if the
outdoor unit is NO
connected to multi- Replace the
system. outdoor unit main
PCB.
YES
Remove the
connecting wires
of the outdoor
multi and then
reset the power
supply.
308
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 6
Check of error 3 Check of error 4
Check
the
connection
status of one of
the connecting wires NO
of outdoor multi. Check if Replace the
the wiring is broken outdoor unit main
or disconnected. PCB.
YES
Correct the
connecting wires
of the outdoor
multi and then
reset the power
supply.
Diagnosis Flow 7
Check of error 3 Check of error 4
In
the
connection
status of the NO
outdoor multi, check if Replace the
more than 4 outdoor outdoor unit main
units are PCB.
connected.
YES
Correct the
connecting wires
of the outdoor
multi and then
reset the power
supply.
309
Troubleshooting by Indication on the Remote Controller
Diagnosis Flow 8
Check of error 3 Check of error 4
Check
the
connection
status of the
connecting wires
of outdoor multi.
Check if the wiring has NO
Replace the
any connection error or outdoor unit main
broken, or is about to PCB.
be disconnected.
YES
Correct the
connecting wires
of the outdoor
multi and then
reset the power
supply.
310
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Improper connection of transmission wiring between
outdoor (outside) unit and external control adaptor for
outdoor (outside) unit.
Improper cool/heat selection
Improper cool/heat unified address (outdoor (outside)
unit, external control adaptor for outdoor (outside) unit)
Defective outdoor (outside) unit PCB
Defective external control adaptor for outdoor
(outside) unit
Improper connection of transmission wiring between
outdoor (outside) units of multi outdoor (outside) unit
connection.
311
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
outdoor
(outside) units NO
multi connection Fix the outdoor
transmission wiring (outside) units
normal? multi connection
transmission
wiring and reset
YES power.
Is the
indoor /
outdoor (outside) NO
Fix the indoor /
unit transmission outdoor (outside)
wiring normal? unit transmission
wiring.
YES
YES
C/H SELECT is set Replace the
to "IND". outdoor (outside)
unit PCB (A1P).
NO
Cool / NO
heat selection is Set C/H SELECT
unified. to "IND."
YES
C/H YES
SELECT is set to The cool / heat
"MASTER." unified address
for outdoor
NO (outside) units in
outdoor (outside) -
A outdoor (outside)
unit transmission
is duplicated. Set
the address
correctly.
312
Troubleshooting by Indication on the Remote Controller
C/H YES
SELECT is set to
"SLAVE."
Check
NO and see if the NO
following items are Fix the problem.
normal.
Does
an error occur NO
when the cool / heat Replace the
selector is set to outdoor (outside)
"IND?" unit outdoor
(outside) control
adaptor.
YES replacement
Replace the
outdoor (outside)
unit PCB.
313
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Transmission error between main and sub remote
controller
Connection between sub remote controllers
Defective remote controller PCB
314
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Using 2- NO
remote controllers
control.
SS1 of
YES remote controller NO
PCBs is set to Set SS1 to
"MAIN." "MAIN"; the
power supply
OFF once and
YES then back ON.
SS1 of
both remote NO
controllers is set to Turn the power
"SUB." OFF and then
back ON. If an
error occurs,
YES replace the
remote controller
PCB.
315
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Transmission error within or outdoor of other system
Defective electronic expansion valve in indoor unit of
other system
Defective PCB of indoor unit in other system
Improper connection of transmission wiring between
indoor and outdoor unit
316
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
All the
units are NO
indicating “U9”. Continue the
operation.
YES
“U9”
has been NO
displayed for 2 Re-diagnose by
minutes or display after
more. passage of 2
minutes or more.
YES
The outdoor unit
PCB indicated by
the error code
"U9" is normal.
Check for the
indoor unit of
other system,
and then conduct
troubleshooting
by diagnosis
according to the
Error Code
Flowchart.
317
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Transmission error within or outdoor (outside) of other
system
Error of electronic expansion valve in indoor unit of
other system
Defective PCB of indoor unit in other system
Improper connection of transmission wiring between
indoor and outdoor (outside) unit
318
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
"U9"
has been YES
displayed for 2 Re-diagnose by
minutes or display after
more. passage of 2
NO minutes or more.
NO
The "A1"
display blinks on the YES
remote controllers of Refer to failure
other units within the diagnosis for
same refrigerant
system. "A1" error code.
NO
The "A9"
display blinks on the YES
remote controllers of Refer to failure
other units within the diagnosis for
same refrigerant
system. "A9" error code.
NO
319
Troubleshooting by Indication on the Remote Controller
The "U4"
display blinks on the YES
remote controllers of other Refer to failure
units within the same diagnosis for
refrigerant "U4" error code.
system.
NO
Refer to failure
diagnosis for
"U5" error code.
320
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Excess of connected indoor units
Defective outdoor unit PCB
Mismatching of the refrigerant type of indoor and
outdoor unit.
Setting of outdoor unit PCB was not conducted after
replacing to spare PCB.
321
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check 3 Check 4
To Diagnosis
Flow 1
(Excessive
number of indoor
Check 3 Check 4 units connected)
To Diagnosis
Flow 2
(Connection of
erroneous
Check 3 Check 4 models of indoor
units)
To Diagnosis
Flow 3
(Combination
error of outdoor
Check 3 Check 4 units)
To Diagnosis
Flow 4
(Defective wiring
in units dedicated
to multi
connections)
322
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 1
Check 3 Check 4
The
number
of indoor units
connected to the YES
same refrigerant circuit Replace the
system should not outdoor unit main
be more than PCB.
64 units.
NO
The number of
indoor units
exceeds the
standard. Check
the connection to
correct.
Diagnosis Flow 2
Check 3 Check 4
Check if
the refrigerant YES
type of the outdoor unit Replace the
corresponds to that outdoor unit main
of the indoor PCB.
unit.
NO
Match the
refrigerant types
of the outdoor
unit and the
indoor unit.
323
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 3
Check 3 Check 4
Check
if the outdoor NO
unit PCB is replaced
with a spare
PCB.
Check if the
YES unit is not NO
connected to outdoor Replace the
units of different outdoor unit main
models. PCB.
YES
Check the model
of the outdoor
Is unit.
a correct NO
spare PCB Replace it with
procured? the correct spare
PCB.
YES
Check if
the spare PCB NO
Correct the
setting is correct. setting to reset
the power.
YES
Replace the
spare PCB.
Diagnosis Flow 4
Check 3 Check 4
Replace the
outdoor unit main
PCB.
324
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Excess of connected indoor units
Defective outdoor unit PCB
Mismatching of the refrigerant type of indoor and
outdoor unit.
Setting of outdoor unit PCB was not conducted after
replacing to spare PCB.
The outdoor unit PCB was replaced with wrong one.
325
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check 3 Check 4
To Diagnosis
Flow 1
(Excessive
number of indoor
units connected)
Check 3 Check 4
To Diagnosis
Flow 2
(Connection of
erroneous
models of indoor
units)
Check 3 Check 4
To Diagnosis
Flow 3
(Defective
combination of
outdoor units)
Check 3 Check 4
To Diagnosis
Flow 4
(Defective wiring
in units dedicated
to multi
connections)
Check 3 Check 4
To Diagnosis
Flow 5
(Connection of
erroneous
models of BS
units)
Check 3 Check 4
To Diagnosis
Flow 6
(Defective wiring
between outdoor
A units and BS
units)
326
Troubleshooting by Indication on the Remote Controller
Check 3 Check 4
To Diagnosis
Flow 7
(Defective wiring
between BS
units)
Check 3 Check 4
To Diagnosis
Flow 8
(Defective wiring
between indoor
units and BS
units)
327
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 1
Check 3 Check 4
The
number
of indoor
units connected to
the same refrigerant YES
Replace the
circuit system should outdoor unit main
not be more than PCB.
64 units.
NO
The number of
indoor units
exceeds the
standard. Check
the connection to
correct.
Diagnosis Flow 2
Check 3 Check 4
Check if
the refrigerant YES
type of the outdoor unit Replace the
corresponds to that outdoor unit main
of the indoor PCB.
unit.
NO
Match the
refrigerant types
of the outdoor
unit and the
indoor unit.
328
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 3
Check 3 Check 4
Check
if the outdoor
unit PCB is replaced NO
with PCB for spare
parts.
Check if the
YES unit is not NO
connected to outdoor Replace the
units of different outdoor unit main
models. PCB.
YES
Check the model
of the outdoor
unit.
Is a NO
correct spare PCB Replace it with
procured? the correct spare
PCB.
YES
Check if
the spare PCB NO
Correct the
setting is correct. setting to reset
the power.
YES
Replace the
spare PCB.
329
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 4
Check 3 Check 4
Is a YES
single unit Procure the
installed? correct model of
unit.
NO
The
connection
wiring of multi YES
outdoor units is broken Correct the
or disconnected. connection
wirings.
NO
Replace the
outdoor unit main
PCB.
Diagnosis Flow 5
Check 3 Check 4
Is the NO
model BS unit Connect the BS
connected? unit.
YES
Replace the
outdoor unit PCB
concerned.
330
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Diagnosis Flow 6
Check 3 Check 4
Is the
wiring
between the NO
outdoor unit and the Correct the
BS unit correct? wiring.
Diagnosis Flow 7
Check 3 Check 4
Is the
wiring between the NO
Correct the
BS units correct? connection
wiring.
YES Replace the BS
unit PCB
concerned.
Diagnosis Flow 8
Check 3 Check 4
Is the
connection
wiring between NO
the indoor unit and the Correct the
BS unit correct? connection
wiring.
331
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Excess of connected indoor units
Defective outdoor (outside) unit PCB
Mismatching of the refrigerant type of indoor and
outdoor (outside) unit.
Setting of outdoor (outside) unit PCB was not
conducted after replacing to spare PCB.
332
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is the
outdoor (outside) YES
PCB replaced to spare The refrigerant
PCB ? classification has
not been set yet.
NO
The total of
indoor units
displaying "UA" and NO
indoor units connected There are too
to the same refrigerant many indoor
system is within units within the
connectable same refrigerant
number of system.
unit∗
YES
Press and hold the
RESET button on the
outside unit PCB for 5
seconds.
Does an NO
error occur? Normal
YES
333
Troubleshooting by Indication on the Remote Controller
Does the
refrigerant type of NO
indoor and outdoor Matches the
(outside) unit refrigerant type
match? of indoor and
outdoor (outside)
YES unit.
Replace the
outdoor (outside)
unit PCB.
Note:
∗ The number of indoor units that can be connected to a
single outside unit system depends on the type of
outside unit.
334
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Address duplication of centralized remote controller
Defective indoor unit PCB
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
335
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Transmission error between optional controllers for
centralized control and indoor unit
Connector for setting main controller is disconnected.
(or disconnection of connector for independent /
combined use changeover switch.)
Defective PCB for centralized remote controller
Defective indoor unit PCB
336
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Check
the indoor unit
for which “UE” is YES
displayed. Is the C
transmission error
(UE) caused on
all indoor
units?
NO
Is the
power
supply of the NO
indoor unit, on which the Make sure there
“UE” occurred, are no hazardous
turned situations, and
ON? then turn ON the
power supply.
YES
Has the
setting of
centralized
control group No. NO
been made with the
indoor unit on
which the “UE” Can
occurred? the setting of YES
centralized control Make correct
group No be setting of the
YES made? centralized
control group No.
NO
A
For VRV
systems, can
the setting of
centralized control NO
Check outdoor
group No. be made in units to which the
one and the same refrigerant
refrigerant system is
system? connected.
YES
337
Troubleshooting by Indication on the Remote Controller
A B
Was the
centralized control NO
group No. for indoor Check whether
unit changed? or not there are
no problems with
the transmission
YES wiring length,
types of cables
and wires,
number of units
connected, and
others. If no
problems,
replace the
indoor unit PCB.
338
Troubleshooting by Indication on the Remote Controller
Check
the
transmission
wiring between
centralized control
equipment for any
broken wire. For details, Abnormal Correct the
refer to information in the wiring.
“Procedure for
checking broken
wires” section.
CHECK 13
Normal
Check
the
transmission
wiring with the
master unit
centralized control
equipment for any Abnormal
broken wire. For details, Correct the
refer to information in wiring.
the “Procedure for
checking broken
wires” section.
CHECK 13
Normal
D
339
Troubleshooting by Indication on the Remote Controller
Has
the master
unit central setting NO
Correct the
connector been connection of the
connected? connector.
YES
Disconnect the
transmission wiring of the
master unit centralized
control equipment, and
then check the voltage
between the transmission
terminals (F1 and F2) of
the master unit
transmission equipment
using a multiple meter.
Is the
voltage
between the NO
terminals F1 (+) and F2 Replace the
(-) in the range of centralized
15.2 to 17.6 control
VDC? equipment.
YES
Centralized
control
equipment:
Normal
It is supposed
that the error
results from
external factors
(e.g. noises) from
other equipment.
340
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Improper connection of transmission wiring between
indoor-outdoor units and outdoor-outdoor units
Failure to execute check operation
Defective indoor unit PCB
Stop valve is not opened.
341
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Are the NO
stop valves opened? Open the stop
valve.
YES
Is the check NO
operation carried
out?
YES Is indoor -
outdoor and
outdoor-outdoor unit YES
Replace the
transmission wiring indoor unit PCB.
normal?
Is indoor -
outdoor and NO
NO
outdoor - outdoor unit After fixing
transmission wiring incorrect wiring,
normal? press and hold
the RESET
button on the
YES outdoor unit main
PCB for 5
seconds.
∗ The unit will not
run for up to 12
minutes.
Wiring check
operation may
not have been
carried out
successfully.
Note:
Wiring check operation may not be successful if carried
out after the outdoor unit has been OFF for more than 12
hours, or if it is not carried out after running all connected
indoor units in the fan mode for at least an hour.
342
Troubleshooting by Indication on the Remote Controller
Supposed Causes
Improper connection of transmission wiring between
indoor-outdoor units and outdoor-outdoor units
Defective indoor unit PCB
Defective outdoor unit main PCB
343
Troubleshooting by Indication on the Remote Controller
Troubleshooting
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
Caution may be damaged.
Is
electricity
being introduce
for the first time after YES
installation or after an
indoor or outdoor unit
PCB has been
replaced? Does
an error
occur even after
NO 12 minutes elapses
from the time when NO
Normal
electricity is
introduced to
indoor and
outdoor
units?
YES
Is
indoor -
outdoor and
outdoor - outdoor unit NO
After fixing
transmission wiring incorrect wiring,
normal? (∗1) press and hold
the RESET
button on the
YES outdoor unit main
Press and hold the PCB for 5
RESET button on the seconds.
outdoor unit PCB for 5 ∗ The unit will not
seconds run for up to 12
minutes.
Does an error NO
Normal
occur?
YES
A
344
Troubleshooting by Indication on the Remote Controller
Disconnect
the outdoor-
outdoor unit
transmission wiring to YES
create the one-system Mount the DIII-
status, and then NET expander
check whether or adaptor.
not the
system is
normal.
NO
Does a
“UH” error occur NO
for all indoor units in Replace the
the system? indoor unit PCB.
YES
Replace the
outdoor unit
PCB.
Note:
∗1. Check the correct wiring “indoor-outdoor” and
“outdoor-outdoor” by Installation manual.
∗2. What is Auto Address?
This is the address automatically assigned to indoor
units and outdoor units after initial power supply
upon installation, or after executing rewiring (Keep
pressing the RESET button for more than 4
seconds).
345
Troubleshooting by Indication on the Remote Controller
346
Troubleshooting by Indication on the Remote Controller
Improper model selection [In heating] ← Is the indoor unit too small
compared to the large-
sized outdoor unit?
Note:
∗1. In cooling, it is normal if the outdoor unit electronic
expansion valve (EVM) is fully open.
∗2. In heating, the indoor unit electronic expansion valve
is used for “subcooling degree control”.
347
Troubleshooting by Indication on the Remote Controller
348
Troubleshooting by Indication on the Remote Controller
349
Troubleshooting by Indication on the Remote Controller
Note:
∗1. For details of compressor capacity control while in
cooling, refer to “Compressor PI control”.
∗2. The “low pressure protection control” includes low
pressure protection control and hot gas bypass
control.
∗3. In cooling, the indoor unit electronic expansion valve
is used for “superheated degree control”.
∗4. In heating, the outdoor unit electronic expansion
valve (EVM) is used for “superheated degree control
of outdoor unit heat exchanger”.
350
Troubleshooting by Indication on the Remote Controller
Defective
Defective hot solenoid valve
gas bypass body
control
(∗1) Defective
service
monitor PCB
[In cooling only]
Defective Defective ← Are the coil
Defective Defective subcooling valve coil resistance and
discharge subcooling electronic insulation normal?
pipe electronic expansion Defective
temperature expansion valve valve body
control valve
control Defective ← Are the electric
Defective
(EV2) low characteristics
control
pressure normal?
(∗2) sensor
351
Troubleshooting by Indication on the Remote Controller
A
Defective Defective ← Are the coil resistance and
indoor unit valve coil insulation normal?
electronic
[In cooling] expansion Defective
If the indoor valve valve body
unit electronic
Defective gas ← Is the connector properly
expansion
pipe connected?
valve is
thermistor of Are the thermistor
throttled too
indoor unit resistance characteristics
much:
normal?
(∗3)
Defective ← Is the connector properly
Defective thermistor for connected?
control indoor unit Are the thermistor
liquid pipe resistance characteristics
Defective
normal?
superheated Defective
degree service
control. monitor PCB
High pipe Abnormal piping length ← Does the piping length fall
resistance in the permissible range?
Bent or crashed pipe ← Conduct visual checks
352
Troubleshooting by Indication on the Remote Controller
Note:
∗1. Refer to “Low pressure protection control” for hot gas
bypass control.
∗2. Refer to “Subcooling electronic expansion valve
control”.
∗3. “Superheating temperature control” in cooling is
conducted by indoor unit electronic expansion valve.
∗4. Superheating temperature control in heating is
conducted by outdoor unit electronic expansion valve
(EVM).
∗5. Judgement criteria of superheat operation:
1 Suction gas superheated degree: 10°C and over.
2 Discharge gas superheated degree: 45°C and
over, except immediately after compressor starts up
or is running under drooping control.
(Use the above values as a guide. Depending on the
other conditions, the unit may be normal despite the
values within the above range.)
353
Troubleshooting by Indication on the Remote Controller
[Preparation]
z Multiple ∗ Prepare the analog
tester type of multiple tester.
For the digital type of
multiple tester, those
with diode check
function are available
for the checking.
354
Troubleshooting by Indication on the Remote Controller
355
Troubleshooting by Indication on the Remote Controller
J1
J2
J3
N3 U V W
P1 P3
P1 P2 P3
DM IGBT
X10A K2
J1
L1
J2
L2
L3
J3
N3
U V W
X11A
356
Troubleshooting by Indication on the Remote Controller
357
Troubleshooting by Indication on the Remote Controller
A
Dirty evaporator ← Does the heat exchanger
get clogged?
Degraded
evaporating Decreased Defective ← Can the fan motor
capacity fan output fan motor be rotated with
Decreased hands?
airflow Are the motor coil
rate resistance and
Defective insulation normal?
service
monitor
PCB
(including
capacity
High setting)
airflow
passage
Dirty filter ← Is the air filter
resistance clogged?
Obstacles ← Is there any
obstacle in the
airflow passage?
Note:
∗1. “Superheating temperature control” in cooling is
conducted by indoor unit electronic expansion valve.
∗2. Superheating temperature control in heating is
conducted by outdoor unit electronic expansion valve
(EVM).
∗3. Guideline of superheated degree to judge as wet
operation
1 Suction gas superheated degree: Not more than
3°C; 2 Discharge gas superheated degree: Not
more than 15°C, except immediately after
compressor starts up or is running under drooping
control.
(Use the above values as a guide. Depending on the
other conditions, the unit may be normal despite the
values within the above range.)
358
Troubleshooting by Indication on the Remote Controller
Cooling
High pressure
drooping control
High pressure Frequency comes to
gradually rises with the minimum level.
increase in
frequency. Subcooled degree
becomes higher.
(Liquid connection
High pressure pipe temperature
lowers.)
(Low pressure is
maintained at a
constant level.)
Low pressure
Low pressure rises due
to decreased
compressor output.
Frequency
359
Troubleshooting by Indication on the Remote Controller
Frequency comes to
the minimum level.
(High pressure is maintained
at a constant level.)
High pressure
(Degree of overcharge)
Proper amount Higher degree of overcharge
360
Troubleshooting by Indication on the Remote Controller
Cooling
The opening degree of the indoor unit Fan control is activated for high
electronic expansion valve becomes pressure protection under
larger. cooling control at low outdoor
Either of the electronic expansion air temperature, i.e., the fan is
valves becomes fully open. hunting at high pressure.
Frequency comes to the minimum level.
High pressure
(Low pressure
is maintained at High pressure drops
a constant with decrease in
level.) compressor capacity.
Low pressure
Low pressure rises as the
opening degree of the indoor
unit electronic expansion
valve becomes larger.
Frequency slightly increases If frequency comes to the
under the capacity control. minimum level, low
pressure cannot be
Frequency maintained.
To maintain low
pressure,
frequency drops
due to the
capacity control.
361
Troubleshooting by Indication on the Remote Controller
Heating
The opening degree of the outdoor unit electronic expansion valve becomes larger.
The outdoor unit electronic expansion valve fully opens and frequency increases.
Discharge pipe or low pressure drooping control
Frequency comes to
High pressure the minimum level.
(High pressure
is maintained at
a constant
level.)
Low pressure
Frequency
362
Troubleshooting by Indication on the Remote Controller
363
Troubleshooting by Indication on the Remote Controller
Note:
∗ In case of construction during rainy reason, if dew
condensation occurs in the piping due to extended
construction period, or rainwater or else may enter the
piping during construction work:
364
Troubleshooting by Indication on the Remote Controller
365
Troubleshooting by Indication on the Remote Controller
Condition for
Code Name Major cause
determining error
L1 Defective • No output is given. • Defective heavy
inverter PCB current part of
compressor
L9 Defective • The compressor • Liquid sealing or
startup of motor fails to start up. defective
inverter compressor
compressor • Excessive oil or
refrigerant
• Defective inverter
PCB
E5 Inverter • The compressor is in • Defective
compressor the locked status compressor
lock (does not rotate).
L4 Radiation fin • The radiation fin • Defective fan
temperature temperature reaches • Running in
rise 87°C or more (while in overload for an
operation). extended period
of time
• Defective inverter
Protection device and others
PCB
U2 Power supply • The inverter power • Power supply
voltage error supply voltage is high error
or low. • Defective inverter
PCB
P1 Imbalanced • Power supply voltages • Power supply
power supply get significantly error (imbalanced
imbalanced among voltages of 2% or
three phases. more)
• Defective inverter
PCB
• Dead inverter
PCB
LC Transmission • With the outdoor unit • Broken wire in
error (between PCB, no communication
inverter PCB communications are line
and service carried out across • Defective service
monitor PCB) service monitor PCB - monitor PCB
inverter PCB - fan • Defective inverter
PCB. PCB
• Defective fan
PCB
PJ PCB • Any PCB of • PCB of different
mismatching specification different specification
from that of the mounted
product is connected.
P4 Defective • The radiation fin • Defective
radiation fin thermistor gets short radiation fin
thermistor circuited or open. thermistor
366
Troubleshooting by Indication on the Remote Controller
Overcurrent of inverter
compressor
For 460V units
An overcurrent of 19.0A
or more continues for a
period of 5 consecutive
seconds
An overcurrent of 16.1A
or more continues for a
period of 260 consecutive
seconds.
For 230V units
A current of 33.5A or
more continues for a
period of consecutive 5
sec.
A current of 27.6A or
more continues for a
period of consecutive 260
sec.
Power supply
Weak-current Inverter
Compressor
U2 P1 L1 P4 L4 PJ E5 L9
Imbalanced power PCB mismatching Defective startup of
supply voltage When incorrect inverter compressor
When inverter PCB is (Compressor stops
imbalance in connected running immediately
voltages among Radiation fin after it starts up.)
three phases temperature rise Inverter compressor lock
comes to 2% or When the (Compressor does not
more radiation fin run at all.)
Power supply temperature
voltage error reached 87˚C or
When the power more
supply voltage Defective radiation fin thermistor
falls out of the When the radiation fin
range of thermistor resistor detects an
460VAC±10% open circuit (-30˚C or less) or a
230VAC±10% short circuit (120˚C or more)
Defective radiation inverter
When the radiation heavy
current part of inverter gets
defective (gives no output)
367
Troubleshooting by Indication on the Remote Controller
Current
Error codes related to
compressor current Instantaneous
overcurrent L5
460V: 32.3A
(230V: 59.1A) Compressor overcurrent
(Electronic thermal 2) L8
Compressor overcurrent
460V: 19.0A (Electronic thermal 1) L8
5 consecutive sec.
(230V: 33.5A)
460V: 16.1A 260 consecutive sec.
(230V: 27.6A)
Max. control
Time
368
Troubleshooting by Indication on the Remote Controller
369
Troubleshooting by Indication on the Remote Controller
370
Troubleshooting by Indication on the Remote Controller
371
Troubleshooting by Indication on the Remote Controller
372
Troubleshooting by Indication on the Remote Controller
373
Troubleshooting by Indication on the Remote Controller
Short circuit
between the
outdoor-outdoor
unit terminal
parts.
374
Troubleshooting by Indication on the Remote Controller
375
Troubleshooting by Indication on the Remote Controller
Note:
∗1. The intelligent Touch Controller and the schedule
timer are not available for combined use.
∗2. The intelligent Touch Controller, centralized remote
controller, and the unified ON/OFF controller have
been set to "Provided with the master unit
centralized setting connector" at the factory. The
schedule timer has been set to "Not provided with
the master unit centralized setting connector" at the
factory, which is attached to the casing of the master
unit.
376
Troubleshooting by Indication on the Remote Controller
#1 #2 #3 #4
∗ #1 #2 #3 #4
Master/ Master/ Master/ Master/
Pattern 1-00~4-15 5-00~8-15 1-00~4-15 5-00~8-15
Slave Slave Slave Slave
CRC Master CRC Master CRC Slave CRC Slave
CRC Master — — CRC Slave — —
intelligent intelligent
Touch Master — — Touch Slave — —
Controller Controller
intelligent
CRC Master — — Touch Slave — —
Controller
intelligent
Touch Master — — CRC Slave — —
Controller
CRC Master — — — — — —
intelligent
Touch Master — — — — — —
Controller
Note:
CRC: Central remote controller <DCS302CA61>
intelligent Touch Controller: < DCS601C51 >
∗The patterns marked with “∗” have nothing to do with
those described in the list of setting of master unit
centralized setting connector.
377
Troubleshooting by Indication on the Remote Controller
Red U
Black W
378
Troubleshooting by Indication on the Remote Controller
5 Gray GND
4 Pink Vcc
Measure the resistance
3 Orange W values between Vcc
and U,V,W, and GND
and U,V,W.
2 Blue V
1 Yellow U
379
Warning z Daikin products are manufactured for export to numerous countries throughout the world. Prior to
purchase, please confirm with your local authorised importer, distributor and/or retailer whether
this product conforms to the applicable standards, and is suitable for use, in the region where the
product will be used. This statement does not purport to exclude, restrict or modify the application
of any local legislation.
z Ask a qualified installer or contractor to install this product. Do not try to install the product
yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or
explosion.
z Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
z Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Organization:
DAIKIN INDUSTRIES, LTD. Organization:
AIR CONDITIONING MANUFACTURING DIVISION DAIKIN INDUSTRIES
(THAILAND) LTD. All of the Daikin Group's business
Scope of Registration: facilities and subsidiaries in Japan
THE DESIGN/DEVELOPMENT AND MANUFACTURE OF Scope of Registration: are certified under the ISO 14001
COMMERCIAL AIR CONDITIONING, HEATING, COOLING, THE DESIGN/DEVELOPMENT international standard for
REFRIGERATING EQUIPMENT, HEATING EQUIPMENT, AND MANUFACTURE OF AIR environment management.
RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT CONDITIONERS AND THE
RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, COMPONENTS INCLUDING
JMI-0107 COMPRESSORS AND VALVES. JQA-1452 COMPRESSORS USED FOR
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
zSpecifications, designs and other content appearing in this brochure are current as of September 2011 but subject to change without notice.
Si30-701_A
Printed in Japan 09/2011 K AK