You are on page 1of 179

CFB Boiler Design, Operation and

Maintenance

By Pichai Chaibamrung

1
Content Day1
1. Introduction to CFB
2. Hydrodynamic of CFB
3. Combustion in CFB
4. Heat Transfer in CFB
5. Basic design of CFB
6. Operation
7. Maintenance
8. Basic Boiler Safety
9. Basic CFB control

2
Objective
— To understand the typical arrangement in CFB
— To understand the basic hydrodynamic of CFB
— To understand the basic combustion in CFB
— To understand the basic heat transfer in CFB
— To understand basic design of CFB
— To understand theory of cyclone separator

Know Principle Solve Everything

3
1. Introduction to CFB
1.1 Development of CFB
1.2 Typical equipment of CFB
1.3 Advantage of CFB

4
1.1 Development of CFB
— 1921, Fritz Winkler, Germany, Coal Gasification
— 1938, Waren Lewis and Edwin Gilliland, USA, Fluid Catalytic Cracking,
Fast Fluidized Bed
— 1960, Douglas Elliott, England, Coal Combustion, BFB
— 1960s, Ahlstrom Group, Finland, First commercial CFB boiler, 15
MWth, Peat

5
1.2 Typical Component of CFB Boiler

6
1.2 Typical Component of CFB Boiler
Wind box and grid nozzle
primary air is fed into wind box.
Air is equally distributed on
furnace cross section by passing
through the grid nozzle. This will
help mixing of air and fuel for
completed combustion

7
1.2 Typical Component of CFB Boiler
Bottom ash drain
coarse size of ash that is not
take away from furnace by
fluidizing air will be drain
at bottom ash drain port
locating on grid nozzle
floor by gravity.
bottom ash will be cooled
and conveyed to silo by
cooling conveyor.

8
1.2 Typical Component of CFB Boiler
HP Blower
supply high pressure air to
fluidize bed material in loop
seal so that it can overflow to
furnace

Rotameter

Supplying of HP
blower to loop seal 9
1.2 Typical Component of CFB Boiler
Cyclone separator
located after furnace exit and
before convective part.
use to provide circulation by
trapping coarse particle back to
the furnace
Fluidized boiler without this
would be BFB not CFB

10
1.2 Typical Component of CFB Boiler
Evaporative or Superheat Wing Wall
located on upper zone of furnace
it can be both of evaporative or SH
panel
lower portion covered by erosion
resistant materials

11
1.2 Typical Component of CFB Boiler
Fuel Feeding system
solid fuel is fed into the lower
zone of furnace through the
screw conveyor cooling with
combustion air. Number of
feeding port depend on the
size of boiler

12
1.2 Typical Component of CFB Boiler
Refractory
refractory is used to protect
the pressure part from
serious erosion zone such as
lower bed, cyclone separator

13
1.2 Typical Component of CFB Boiler
Solid recycle system (Loop seal)
loop seal is located between
dip leg of separator and
furnace. Its design physical is
similar to furnace which have
air box and nozzle to
distribute air. Distributed air
from HP blower initiate
fluidization. Solid behave like
a fluid then over flow back to
the furnace.

14
1.2 Typical Component of CFB Boiler
Kick out
kick out is referred to
interface zone between
the end of lower zone
refractory and water tube.
It is design to protect the
erosion by by-passing the
interface from falling
down bed materials

15
1.2 Typical Component of CFB Boiler
Lime stone and sand system
lime stone is pneumatically feed or gravitational feed into
the furnace slightly above fuel feed port. the objective is to
reduce SOx emission.
Sand is normally fed by gravitation from silo in order to
maintain bed pressure. Its flow control by speed of rotary
screw.

16
1.2 Typical Arrangement of CFB Boiler

17
1.3 Advantage of CFB Boiler
— Fuel Flexibility

18
1.3 Advantage of CFB Boiler
— High Combustion Efficiency
- Good solid mixing
- Low unburned loss by cyclone, fly ash recirculation
- Long combustion zone
— In situ sulfur removal
— Low nitrogen oxide emission

19
2. Hydrodynamic in CFB
2.1 Regimes of Fluidization
2.2 Fast Fluidized Bed
2.3 Hydrodynamic Regimes in CFB
2.4 Hydrodynamic Structure of Fast Beds

20
2.1 Regimes of Fluidization
— Fluidization is defined as the operation through which fine
solid are transformed into a fluid like state through
contact with a gas or liquid.

21
2.1 Regimes of Fluidization
— Particle Classification

Distribution Size (micron)


CFB1 CFB2 BFB
100% <600 <1000 <1680

75% <250 <550 <1190

50% <180 <450 <840

25% <130 <250 <590

100% >100 >420

22
2.1 Regimes of Fluidization
— Particle Classification

23
2.1 Regimes of Fluidization
— Comparison of Principal Gas-Solid Contacting Processes

24
2.1 Regimes of Fluidization
— Packed Bed
The pressure drop per unit height of a packed beds of a uniformly size
particles is correlated as (Ergun,1952)

Where U is gas flow rate per unit cross section of the bed called
Superficial Gas Velocity

25
2.1 Regimes of Fluidization
— Bubbling Fluidization Beds
Minimum fluidization velocity is velocity where the fluid
drag is equal to a particle’s weight less its buoyancy.

26
2.1 Regimes of Fluidization
— Bubbling Fluidization Beds
For B and D particle, the bubble is started when superficial
gas is higher than minimum fluidization velocity
But for group A particle the bubble is started when
superficial velocity is higher than minimum bubbling
velocity

27
2.1 Regimes of Fluidization
— Turbulent Beds
when the superficial is continually increased through a
bubbling fluidization bed, the bed start expanding, then
the new regime called turbulent bed is started.

28
2.1 Regimes of Fluidization

29
2.1 Regimes of Fluidization
— Terminal Velocity

Terminal velocity is the particle velocity when the


forces acting on particle is equilibrium

30
2.1 Regimes of Fluidization
— Freeboard and Furnace Height
- considered for design heating-surface area
- considered for design furnace height
- to minimize unburned carbon in bubbling
bed
- the freeboard heights should be exceed or
closed to the transport disengaging heights

31
2.2 Fast Fluidization
— Definition

32
2.2 Fast Fluidization
— Characteristics of Fast Beds
- non-uniform suspension of slender particle agglomerates or clusters moving
up and down in a dilute
- excellent mixing are major characteristic
- low feed rate, particles are uniformly dispersed in gas stream
- high feed rate, particles enter the wake of the other, fluid drag on the leading
particle decrease, fall under the gravity until it drops on to trailing particle

33
2.3 Hydrodynamic regimes in a CFB
Cyclone Separator :
Swirl Flow
Back Pass:
Pneumatic Transport

Furnace Upper SA:


Fast Fluidized Bed
Lower Furnace below SA:
Turbulent or bubbling
fluidized bed

Return leg and lift leg :


Pack bed and Bubbling Bed

34
2.4 Hydrodynamic Structure of Fast Beds
— Axial Voidage Profile
Secondary air is fed

Bed Density Profile of 135 MWe CFB Boiler (Zhang et al., 2005)

35
2.4 Hydrodynamic Structure of Fast Beds
— Velocity Profile in Fast Fluidized Bed

36
2.4 Hydrodynamic Structure of Fast Beds
— Velocity Profile in Fast Fluidized Bed

37
2.4 Hydrodynamic Structure of Fast Beds
— Particle Distribution Profile in Fast Fluidized Bed

38
2.4 Hydrodynamic Structure of Fast Beds
— Particle Distribution Profile in Fast Fluidized Bed

39
2.4 Hydrodynamic Structure of Fast Beds
— Particle Distribution Profile in Fast Fluidized Bed
Effect of SA injection on particle
distribution by M.Koksal and
F.Hamdullahpur (2004). The
experimental CFB is pilot scale CFB.
There are three orientations of SA
injection; radial, tangential, and mixed

40
2.4 Hydrodynamic Structure of Fast Beds
— Particle Distribution Profile in Fast Fluidized Bed
Increasing solid circulation
Increasing SA to 40%
rate effect to both
does not significant on
lower and upper zone
suspension density above
of SA injection point
SA injection point
which both zone is
but the low zone is
denser than low
denser than low SA ratio
solid circulation rate

No SA, the suspension With SA 20% of PA,


density is proportional the solid particle is hold up
l to solid circulation rate when compare to no SA

41
2.4 Hydrodynamic Structure of Fast Beds
— Effects of Circulation Rate on Voidage Profile

higher solid recirculation rate

42
2.4 Hydrodynamic Structure of Fast Beds
— Effects of Circulation Rate on Voidage Profile

Pressure drop across the L-valve is


proportional to solid recirculation rate

higher solid recirculation rate

43
2.4 Hydrodynamic Structure of Fast Beds
— Effect of Particle Size on Suspension Density Profile
- Fine particle - - > higher suspension density
- Higher suspension density - - > higher heat transfer
- Higher suspension density - - > lower bed temperature

44
2.4 Hydrodynamic Structure of Fast Beds
— Core-Annulus Model
- the furnace may be spilt into two zones : core and
annulus
core

Core
- Velocity is above superficial velocity
annulus
- Solid move upward

Annulus
- Velocity is low to negative
- Solids move downward

45
2.4 Hydrodynamic Structure of Fast Beds
— Core-Annulus Model

core

annulus

46
2.4 Hydrodynamic Structure of Fast Beds
— Core Annulus Model
- the up-and-down movement solids in the core and
annulus sets up an internal circulation
- the uniform bed temperature is a direct result of internal
circulation

47
3. Combustion in CFB
3.1 Coal properties for CFB boiler
3.2 Stage of Combustion
3.3 Factor Affecting Combustion Efficiency
3.4 Combustion in CFB
3.5 Biomass Combustion

48
3.1 Coal properties for CFB Boiler
Properties
- coarse size coal shall be crushed by coal crusher
- sizing is an importance parameter for CFB boiler improper size might
result in combustion loss
- normal size shall be < 8 mm

49
3.2 Stage of Combustion
A particle of solid fuel is injected into an FB undergoes the
following sequence of events:
- Heating and drying
- Devolatilization and volatile combustion
- Swelling and primary fragmentation (for some types of coal)
- Combustion of char with secondary fragmentation and attrition

50
3.2 Stages of Combustion
— Heating and Drying
- Combustible materials constitutes around 0.5-5.0% by
weight
of total solids in combustor
- Rate of heating 100 °C/sec – 1000 °C/sec
- Heat transfer to a fuel particle (Halder 1989)

51
3.2 Stages of Combustion
Devolatilization and volatile combustion
- first steady release 500-600 C
- second release 800-1000C
- slowest species is CO (Keairns et al., 1984)
- 3 mm coal take 14 sec to devolatilze
at 850 C (Basu and Fraser, 1991)

52
3.2 Stages of Combustion
— Char Combustion
2 step of char combustion
1. transportation of oxygen to carbon surface
2. Reaction of carbon with oxygen on the carbon surface
3 regimes of char combustion
- Regime I: mass transfer is higher than kinetic rate
- Regime II: mass transfer is comparable to kinetic rate
- Regime III: mass transfer is very slow compared to kinetic rate

53
3.2 Stage of Combustion
— Communition Phenomena During Combustion
Attrition, Fine particles from
Volatile release in non-porous coarse particles through
particle cause the high mechanical contract like
internal pressure result in abrasion with other particles
break a coal particle into
fragmentation

Char burn under regime I


which is mass transfer is
higher than kinetic trasfer.
The sudden collapse or other
Volatile release cause the type of second fragmentation
particle swell call percolative fragmentation
occurs

Char burn under regime I, II,


the pores increases in size à
weak bridge connection of
carbon until it can’t withstand
the hydrodynamic force. It will
fragment again call “
secondary fragmentation”

54
3.3 Factor Affecting Combustion Efficiency
— Fuel Characteristics
the lower ratio of FC/VM result in higher combustion
efficiency (Makansi, 1990), (Yoshioka and Ikeda,1990),
(Oka, 2004) but the improper mixing could result in lower
combustion efficiency due to prompting escape of volatile
gas from furnace.

55
3.3 Factor Affecting Combustion Efficiency
— Operating condition (Bed Temperature)
- higher combustion temperature --- > high combustion
efficiency Limit of Bed temp
-Sulfur capture
-Bed melting
-Water tube failure

High combustion temperature result in high


oxidation reaction, then burn out time
decrease. So the combustion efficiency
increase. 56
3.3 Factor Affecting Combustion Efficiency
— Fuel Characteristic (Particle size)

-The effect of this particle size is not clear


-Fine particle, low burn out time but the
probability to be dispersed from cyclone
the high
-Coarse size, need long time to burn out.
-Both increases and decreases are
possible when particle size decrease

57
3.3 Factor Affecting Combustion Efficiency
— Operating condition (superficial velocity)
- high fluidizing velocity decrease combustion efficiency because
Increasing probability of small char particle be elutriated from
circulation loop

- low fluidizing velocity cause defluidization, hot spot and sintering

58
3.3 Factor Affecting Combustion Efficiency
— Operating condition (excess air)
- combustion efficiency improve which excess air < 20%

Combustion loss
decrease
significantly when
excess air < 20%.
Excess air >20% less
significant improve
combustion efficiency.

59
3.3 Factor Affecting Combustion Efficiency
Operating Condition
The highest loss of combustion result from elutriation of char particle
from circulation loop. Especially, low reactive coal size smaller than 1
mm it can not achieve complete combustion efficiency with out fly
ash recirculation system.
However, the significant efficiency improve is in range 0.0-2.0 fly ash
recirculation ratio.

60
3.4 Combustion in CFB Boiler
— Lower Zone Properties
- This zone is fluidized by primary air constituting about
40-80% of total air.
- This zone receives fresh coal from coal feeder and
unburned coal from cyclone though return valve
- Oxygen deficient zone, lined with refractory to protect
corrosion
- Denser than upper zone

61
3.4 Combustion in CFB Boiler
— Upper Zone Properties
- Secondary is added at interface between lower and upper
zone
- Oxygen-rich zone
- Most of char combustion occurs
- Char particle could make many trips around the furnace
before they are finally entrained out through the top of
furnace

62
3.4 Combustion in CFB Boiler
— Cyclone Zone Properties
- Normally, the combustion is small when compare to in
furnace
- Some boiler may experience the strong combustion in
this zone which can be observe by rising temperature in
the cyclone exit and loop seal

63
3.5 Biomass Combustion
— Fuel Characteristics
- high volatile content (60-80%)
- high alkali content à sintering, slagging, and fouling
- high chlorine content à corrosion

64
3.5 Biomass Combustion
— Agglomeration
SiO2 melts at 1450 C
Eutectic Mixture melts at 874 C

Sintering tendency of fuel is indicated by the following


(Hulkkonen et al., 2003)

65
3.5 Biomass Combustion
Options for Avoiding the Agglomeration Problem
- Use of additives
- china clay, dolomite, kaolin soil
- Preprocessing of fuels
- water leaching
- Use of alternative bed materials
- dolomite, magnesite, and alumina
- Reduction in bed temperature

66
3.5 Biomass Combustion
— Agglomeration

67
3.5 Biomass Combustion
— Fouling
- is sticky deposition of ash due to evaporation of alkali salt
- result in low heat transfer to tube

68
3.5 Biomass Combustion
— Corrosion Potential in Biomass Firing
- hot corrosion
- chlorine reacts with alkali metal à from low
temperature melting alkali chlorides
- reduce heat transfer and causing high temperature
corrosion

69
4. Heat Transfer in CFB
4.1 Gas to Particle Heat Transfer
4.2 Heat Transfer in CFB

70
4.1 Gas to Particle Heat Transfer
— Mechanism of Heat Transfer

In a CFB boiler, fine solid particles


agglomerate and form clusters or
stand in a continuum of generally
up-flowing gas containing sparsely
dispersed solids. The continuum is
called the dispersed phase, while
the agglomerates are called the
cluster phase.
The heat transfer to furnace wall
occurs through conduction from
particle clusters, convection from
dispersed phase, and radiation
from both phase.

71
4.1 Heat Transfer in CFB Boiler
— Effect of Suspension Density and particle size

Heat transfer coefficient is proportional to the square root of suspension density

72
4.1 Heat Transfer in CFB Boiler
— Effect of Fluidization Velocity

No effect from fluidization velocity when leave the suspension density constant

73
4.1 Heat Transfer in CFB Boiler
— Effect of Fluidization Velocity

74
4.1 Heat Transfer in CFB Boiler
— Effect of Fluidization Velocity

75
4.1 Heat Transfer in CFB Boiler
— Effect of Vertical Length of Heat Transfer Surface

76
4.1 Heat Transfer in CFB Boiler
— Effect of Bed Temperature

77
4.1 Heat Transfer in CFB Boiler
— Heat Flux on 300 MW CFB Boiler (Z. Man, et. al)

78
4.1 Heat Transfer in CFB Boiler
— Heat transfer to the walls of commercial-size

Low suspension density low


heat transfer to the wall.

79
4.1 Heat Transfer in CFB Boiler
— Circumferential Distribution of Heat Transfer Coefficient

80
5 Design of CFB Boiler
— 5.1 Design and Required Data
— 5.2 Combustion Calculation
— 5.3 Heat and Mass Balance
— 5.4 Furnace Design
— 5.5 Cyclone Separator

81
5.1 Design and Required Data
The design and required data normally will be specify by owner
or client. The basic design data and required data are;
Design Data :
- Fuel ultimate analysis - Weather condition
- Feed water quality - Feed water properties

Required Data :
- Main steam properties - Flue gas temperature
- Flue gas emission - Boiler efficiency

82
5.2 Combustion Calculation
— Base on the design and required data the following data
can be calculated in this stage :
- Fuel flow rate - Combustion air flow rate
- Fan capacity - Fuel and ash handling capacity
- Sorbent flow rate

83
5.3 Heat and Mass Balance
Main steam
Heat input

Radiation
Heat output

Feed water
Blow down

Flue gas

Moisture in fuel Unburned in fly ash


and sorbent

Fuel and
sorbent
Combustion air

Unburned in Moisture in
bottom ash combustion air
84
5.3 Heat and Mass Balance
— Mass Balance Mass input

Mass output

SolidSolid
Fluein
gas
Make up Flue gas
bed material

Fuel and
sorbent

Moisture in fuel fly ash


and sorbent

Fuel and
sorbent

Make up
bed material
fly ash
bottom ash
bottom ash

85
5.4 Furnace Design
— The furnace design include: 1. Furnace cross section
1. Furnace cross section Criteria
2. Furnace height - moisture in fuel
3. Furnace opening - ash in fuel
- fluidization velocity
- SA penetration
- maintain fluidization in lower
zone at part load

86
5.4 Furnace Design
2. Furnace height 3. Furnace opening
Criteria Criteria
- Heating surface - Fuel feed ports
- Residual time for sulfur - Sorbent feed ports
capture - Bed drain ports
- Furnace exit section

87
5.5 Cyclone Separator
— 6.1 Theory
— 6.2 Critical size of particle

88
5.5 Cyclone Separator
— The centrifugal force on the particle entering the cyclone
is

— The drag force on the particle can be written as

— Under steady state drag force = centrifugal force

89
5.5 Cyclone Separator

— Vr can be considered as index of cyclone efficiency, from


above equation the cyclone efficiency will increase for :

- Higher entry velocity


- Large size of solid
- Higher density of particle
- Small radius of cyclone
- low value of viscosity of gas

90
5.5 Cyclone Separator
— The particle with a diameter larger than theoretical cut-
size of cyclone will be collected or trapped by cyclone
while the small size will be entrained or leave a cyclone

— Actual operation, the cut-off size diameter will be defined


as d50 that mean 50% of the particle which have a
diameter more than d50 will be collected or captured.

91
6. Operation

92
Content
6.1 Before start
6.2 Grid pressure drop test
6.3 Cold Start
6.4 Normal Operation
6.5 Normal Shutdown
6.6 Hot Shutdown
6.7 Hot Restart
6.8 Malfunction and Emergency

93
6.1 Before Start
— all maintenance work have been completely done
— All function test have been checked
— cooling water system is operating
— compressed air system is operating
— Make up water system
— Deaerator system
— Boiler feed water pump
— Condensate system
— Oil and gas system
— Drain and vent valves
— Air duct, flue gas duct system
94
6.1 Before Start
— Blow down system
— Sand feeding system
— Lime stone feeding system
— Solid fuel system
— Ash drainage system
— Control and safety interlock system

95
6.2 Grid Pressure Drop Test
— For check blockage of grid
nozzle
— Furnace set point = 0
— Test at every PA. load
Pf= 0
— Compare to clean data or design
data
— Shall not exceed 10% from
design data
— Perform in cold condition
Pb
Pw

FI

96
6.3 Cold Start
-100 mm normal level
Fill boiler Start Fan
ID,HP,SA,PA

Boiler Interlock Purge


300 S

Low level cut off


Start up Burner Boiler Warm Up
Tb 150-200 C

30-50 mbar, Tb 550-600 C


Feed Bed Material Feed Solid Fuel

Raise to MCR

97
Fill Boiler
-Close all water side drain valve
-Open all air vent valve at drum and
superheat
-Open start up vent valve 10-15%
-Slowly feed water to drum until level 1/3 of
sigh glass

98
Start Fan

1.Start ID.Fan

2.Start HP Blower 4.Start PA.Fan

3.Start SA.Fan

99
Boiler Interlock
Emergency stop in order

Furnace P. < Max (2/3)


Trip Solid Fuel
ID. Fan running
Trip Soot Blower
HP Blower start
Trip Oil
Drum level > min (2/3)

SA. Fan running Trip Sand

PA. Fan running Trip Bottom Ash

HP. Blower P. > min Trip Lime Stone


PA. Flow to grid > min

Flue gas T after Furnace < max


100
Purge
— To carry out combustible gases
— To assure all fuel are isolated
from furnace
— Before starting first burner for
cold start
— If bed temp < 600 C or OEM
recommend and no burner in
service
— Total air flow > 50%
— 300 sec for purging time

101
Purge
NFPA85: CFB Boiler purge logic

102
Start up burner
— Help to heat up bed temp to allowable temperature for
feeding solid fuel
— Will be stopped if bed temp > 850 C
— Before starting, all interlock have to passed
— Main interlock
— Oil pressure > minimum
— Control air pressure > minimum
— Atomizing air pressure > minimum

103
Start up burner
NFPA85 - Typical burner safety for CFB boiler

104
Drum and DA low level cut-off
— Test for safety
— During burner are operating
— Open drain until low level
— Signal feeding are not allow
— Steam drum low level = chance
to overheating of water tube
— DA low level = danger for BFWP

105
Boiler warm up
— Gradually heating the boiler to reduce the effect of
thermal stress on pressure part, refractory and drum swell
— Increase bed temp 60-80 C/hr by adjusting SUB
— Control flue gas temperature <470 C until steam flow >
10% MCR
— Close vent valves at drum and SH when pressure > 2 bar
— Continue to increase firing rate according to
recommended start up curve
— Operate desuperheater when steam temperature are with
in 30 C of design point
— Slowly close start up and drain valve while maintain steam
flow > 10% MCR
106
Feed bed material
— Bed material should be sand which size is according to
recommended size
— Start feed sand when bed temp >150 C
— Do not exceed firing rate >30% if bed pressure <20 mbar
otherwise overheating may occur for refractory and nozzle
— Continue feed bed material unit it reach 30 mbar

107
Feed solid fuel
— Must have enough bed material
— Bed temperature > 600 C or manufacturer
recommendation or refer to NFPA85 Appendix H
— Pulse feed every 90 s
— Placing lime stone feeding, ash removal system
simultaneously
— Slowly decrease SUB firing rate while increasing solid fuel
feed rate
— Stop SUB one by one, observe bed temperature increasing
— Turn to auto mode control

108
Rise to MCR
— Continue rise pressure and temperature according to
recommended curve until reach design point
— Drain bottom ash when bed pressure >45-55 mbar
— Slowly close start up valve
— Monitor concerning parameters

109
6.4 Normal Operation
Changing Boiler load (manual)

— Increasing — Decreasing
- manual increase air flow - manual decrease air flow
- manual increase fuel flow - manual decrease fuel flow
- monitor excess oxygen - monitor excess oxygen
- monitor steam pressure - monitor steam pressure

110
6.4 Normal Operation
Furnace and Emission Monitoring

— Furnace and emssion


- monitor fluidization in hot
loop
- monitor gas side pressure drop
- monitor bed pressure
- monitor bed temperature
-monitor wind box pressure
- monitor SOx, Nox, CO

111
6.4 Normal Operation
Bottom ash and Soot Blower

— Bottom ash drain — Soot blower


- automatic or manual draining - initiate soot blower to clean
of bottom ash shall be judged by the heat exchanger surface in
commissioning engineer for the convective part
design fuel. - frequent of soot blowing
- when fuel is deviated from the depend on the degradation of
design, operator can be judge by heat transfer coefficient.
themselves that draining need - normally 10 C higher than
to perform or not. normal value of exhaust
- bed pressure is the main temperature
parameter to start draining

112
6.4 Normal Operation
— Boiler Walk Down
- boiler expansion joint
- Boiler steam drum
- Boiler penthouse
- Safety valve
- Boiler lagging
- Spring hanger
- Valve and piping
- Damper position
- Loop seal
- Bottom screw
- Combustion chamber
- Fuel conveyor
113
6.4 Normal Operation
— Sizing Quality
- crushed coal, bed material, lime stone and bottom ash
sizing shall be periodically checked by the operator
- sieve sizing shall be performed regularly to make sure
that their sizing is in range of recommendation

114
6.5 Normal Shut Down
1. Reduce boiler load to 50% MCR
2. Place O2 control in manual mode
3. Monitor bed temperature
4. Continue reducing load according to shut down curve
5. Maintain SH steam >20 C of saturation temperature
6. Start burner when bed temperature <750 C
7. Empty solid fuel and lime stone with bed material >650 C
8. Decrease SUB firing rate according to suggestion curve
9. Maintain drum level in manual mode
10. Stop solid fuel, line stone, sand feeding system

115
6.5 Normal Shut Down
11. Maintain drum level near upper limit
12. Continue fluidizing the bed to cool down the system at 2
C/min by reducing SUB firing rate
13. Stop SUB at bed temperature 350 C
14. Continue fluidizing until bed temperature reach 300 C
15. Slowly close inlet damper of PAF and SAF so that IDF
can control furnace pressure in automatic mode
16. Stop all fan after damper completely closed
17. Stop HP blower 30 S after IDF stopped
18. Stop chemical feeding system when BFWP stop
19. Continue operate ash removal system until it empty

116
6.5 Normal Shut Down
20. Open vent valve at drum and SH when drum pressure
reach 1.5-2 bar
21. Open manhole around furnace when bed temp < 300 C

117
6.6 Emergency Shut down
— Boiler can be held in hot stand by condition about 8 hrs
— Hot condition is bed temp >650 C otherwise follow cold
star up procedure
— Boiler load should be brought to minimum
— Stop fuel feeding
— Wait O2 increase 2 time of normal operation
— Stop air to combustion chamber to minimize heat loss

118
6.7 Hot restart
— Purge boiler if bed temperature < 600 C
— Start SUBs if bed temperature > 500 C
— Monitor bed temperature rise
— If bed temperature does not rise after pulse feeding solid
fuel. stop feeding and start purge

119
6.8 Malfunction and Emergency
— Bed pressure
— Bed temperature
— Circulation
— Tube leak
— Drum level

120
Bed Pressure
Bed pressure is an one of importance
parameter that effect on boiler efficiency
and reliability.
Measured above grid nozzle about 20 cm.

Pf= 0

Pb
Pw

FI
121
Bed Pressure
— Effect of low bed pressure
- poor heat transfer
- boiler responds
- high bed temperature
- damage of air nozzle and refractory
— Effect of high bed pressure
- increase heat transfer
- more efficient sulfur capture
- more power consumption of fan

122
Bed Pressure
— Cause of low bed pressure
- loss of bed material
- too fine of bed materials
- high bed temperature

— Cause of high bed pressure


- agglomeration
- too coarse of bed material

123
Bed Temperature
— Measured above grid nozzle about
20 cm
— Measured around the furnace cross
section
— It is the significant parameter to
operate CFB boiler

124
Bed temperature
— Effect of high bed temperature
- ineffective sulfur capture
- chance of ash melting
- chance of agglomeration
- chance to damage of air nozzle

125
Bed temperature
— Cause of high bed temperature
- low bed pressure
- too coarse bed material
- too coarse solid fuel
- improper drain bed material
- low volatile fuel
- improper air flow adjustment

126
Circulation
— Circulation is particular
phenomena of CFB boiler.
— Bed material and fuel are
collected at cyclone separator
— Return to the furnace via loop
seal
— HP blower supply HP air to
fluidize collected materials to
return to furnace

127
Circulation
— Effect of malfunction circulation
- No circulation result in forced shut down
- high rate of circulation
- high circulation rate need more power of blower
- low rate of circulation

128
Circulation
— Cause of malfunction circulation
- insufficiency air flow to loop seal nozzle
- insufficient air pressure to loop seal
- plugging of HP blower inlet filter
- blocking or plugging of loop seal nozzle
-

129
Tube leak
— Water tube leak
- furnace pressure rise
- bed temperature reduce
- stop fuel feeding
- open start up valve
- don’t left low level of drum
- continue feed water until flue gas temp < 400 C
- continue combustion until complete
- small leak follow normal shut down

130
Drum level
Sudden loss of drum level
- when the cause is known and immediately correctable
before level reach minimum allowable. Reestablish steam
drum level to its normal value and continue boiler
operation
-if the cause is not known. Start immediate shut down
according to emergency shut down procedure

131
Drum level
Gradual loss of drum level
- boiler load shall be reduced to low load
- find out and correct the problem as soon as possible
- if can not maintain level and correct the problem, boiler
must be taken out of service and normal shut down
procedure shall be applied.

132
7. Maintenance

133
Before maintenance work
— Make sure that all staff are understand about safety
instruction for doing CFB boiler maintenance work
— Make sure that all maintenance and safety equipments
shall be a first class

134
Overview Boiler Maintenance
Refractory and tube are the main
area that need to be checked

135
6.1 Windbox Inspection
— Inspect sand inside windbox
after shutdown
— Drain pipe
— Crack
— Air gun pipe

— Refractory
— Crack, wear and fall down inspect Drain pipe
by hammer(knocking) if burner is
under bed design

136
6.2 Furnace Inspection
— Nozzle :
— Wear
— Fall-off

— Refractory
— Crack, wear and fall down inspect
by hammer knocking if burner is
under bed design
— Feed fuel port Refractory
— Wear
— Crack

— Burner

Burner Feed Fuel


137
Nozzle
6.2 Furnace Inspection
— Limestone port
— Crack
— Deform
— Refractory damage at connection
between port and refractory
— Secondary & Recirculation Air
port
— Crack
— Deform
— Refractory damage at connection
between port and refractory
— Bed Temperature
— Check thermo well deformation
— Check wear

Secondary & Recirculation Air port

138
6.3 Kick-Out Inspection
— Refractory
— Wear
— Crack and fall down by
hammer(knocking)
— Water tube
— Wear
— Thickness

139
6.3 Kick-Out Inspection
— Water Tube:
— Thickness measuring
— Erosion at corner
— CO Corrosion due to incomplete
combustion at fuel feed side.
— Defect from weld build up
— Water tube sampling for internal
check every 3 years

Inside water tube inspect by borescope


welded build up excessive metal because use welding rod
size bigger than tube thickness 140
6.4 Superheat I (Wingwall)
— Water Tube:
— Thickness measuring
— Erosion at tube connection

— Refractory
— Crack and fall down by
hammer(knocking)
— Guard
— Crack
— fall down

141
6.4 Superheat I (Omega Tube)
— Offset Water Tube:
— Thickness measuring
— Erosion at offset tube
Omega Guard
— SH tube
— Thickness measuring
— Omega Guard
— Crack
— fall down

Offset Water 142

Tube
6.5 Roof
— Water Tube:
— Thickness measuring
— Erosion

— Refractory
— Crack, wear and fall down by
hammer(knocking)

143
6.6 Inlet Separator
— Water Tube:
— Thickness measuring near opening
have more erosion than another
tube because of high velocity of flue
gas
— Refractory
— Crack, wear and fall down by
hammer(knocking)

144
6.7 Steam Drum
— Surface :
— Surface were black by magnetite

— Deposits
— Deposits at bottom drum need to
check chemical analysis
— Cyclone Separator
— Loose
— Demister
— Blowdown hole
— Plugging
— U-Clamp
— Loose

Deposits at bottom drum


145
6.8 Separator
— Central Pipe:
— Deformation
— Crack

— Refractory
— Wear at impact zone due to high
impact velocity
— Crack and fall down by
hammer(knocking)

146
6.9 Outlet Separator
— Water Tube
— Tube Thickness
— Erosion

— Outlet Central Pipe:


—Support or Hook
— Refractory
—Crack and fall down by
hammer(knocking)

147
6.10 Screen Tube
— Water Tube
— Thickness measuring upper part of
screen tube at corner have more
erosion than another area because
of high velocity of flue gas
— Guard
— Loose
— Refractory
— Crack and fall down by upper part of screen tube at corner have more erosion
hammer(knocking)

Weld build up or install guard to prevent tube erosion 148


6.11 Superheat Tube
— Tube
— Thickness measuring
— High erosion between SH tube and
wall
— Steam erosion due to improper soot
blower

— Guard
— Fall down
— Crack

149
6.12 Economizer
— Water Tube
— Thickness measuring
— High erosion between economizer
tube and wall
— Steam erosion due to improper soot
blower
— Guard
— Fall down
— Crack

Guard

Install guard to
prevent tube erosion 150
6.13 Air Heater
— Tube
— Cold end corrosion due to high
concentrate SO3 in flue gas
— Steam erosion due to improper soot
blower

Inlet air heater

Cold end corrosion due to SO3 in fluegas 151


8. Basic Boiler Safety

152
Warning

Operating or maintenance procedure which, if


not as described could result in injured death
or damage of equipment

153
General safety precaution
— Electrical power shall be turned off before performing
installation or maintenance work. Lock out, tag out shall
be indicated
— All personal safety equipment shall be suit for each work
— Never direct air water stream into accumulation bed
material or fly ash. This will become breathing hazard
— Always provide safe access to all equipment ( plant from,
ladders, stair way, hand rail
— Post appropriate caution, warning or danger sign and
barrier for alerting non-working person
— Only qualify and authorized person should service
equipment or maintenance work
154
General safety precaution
— Do not by-pass any boiler interlocks
— Use an filtering dust mask when entering dust zone
— Do not disconnect hoist unless you have made sure that
the source is isolated

155
Equipment entry
— Never entry confine space until is has been cooled, purged
and properly vented
— When entering confine space such as separator, loop seal
furnace be prepared for falling material
— Always lock the damper, gate or door before passing
through them
— Never step on accumulation of bottom ash or fly ash. Its
underneath still hot
— Never use toxic fluid in confine space
— Use only appropriate lifting equipment when lift or move
equipment

156
Equipment entry
— Stand by personnel shall be positioned outside a confine
space to help inside person incase of emergency
— Be carefully aware the chance of falling down when enter
cyclone inlet or outlet.
— Don not wear contact lens with out protective eye near
boiler, fuel handing, ash handing system. Airborne particle
can cause eye damage
— Don not enter loop seal with out installing of cover over
loop seal downcomer to prevent falling material from
cyclone

157
Operating precautions
CFB boiler process
— Use planks on top of bed materials after boiler is cooled
down. This will prevent the chance of nozzle plugging
— Do not open any water valve when boiler is in service
— Do not operate boiler with out O2 analyzer
— Do not use downcomer blown donw when pressure > 7
bar otherwise loss of circulation may occure
— Do not operate CFB boiler without bed material
— When PA is started. PA flow to grid must be increase to
above minimum limit to fully fluidized bed maerial
— Do not operate CFB boiler with bed pressure > 80mbar.
This might be grid nozzle plugging

158
Operating precautions
— on cold start up the rate of chance in saturated steam shall
not exceed 2 C/min
— On cold start up the change of flue gas temp at cyclone
inlet shall not exceed 70 C/min
— Do not add feed water to empty steam drum with
different temperature between drum metal and feed water
greater than 50 C
— All fan must be operated when add bed material

159
Operating precautions
Refractory
— When entering cyclone be aware a chance of falling down
— Refractory retain heat for long period. Be prepared for hot
surface when enter this area
— An excessive thermal cycle will reduce the life cycle of
refractory
— After refractory repair, air cure need to apply about 24 hr
or depend on manufacturer before heating cure
— Heating cure shall be done carefully otherwise refractory
life will be reduced

160
Operating precautions
Solid Fuel
— Chemical analysis of all solid fuel shall be determined for
first time and compared with OEM standard
— Sizing is important
— Burp feeding shall be performed during starting feeding
solid fuel instead of continuous feeding

161
9. Basic CFB Boiler Control

162
— Basic control
— Furnace control
— Main pressure control
— Main steam pressure control
— Drum level control
— Feed tank control
— Solid fuel control
— Primary air control
— Secondary air control
— Oxygen control

163
Basic control
— Simple feedback control
PR IM ARY VA RIA B LE

XT

K PR O CE S S
SE T P OIN T

A T A

f(x)

M A NIP U LAT E D VAR IA BLE

164
Basic control
— Simple feed forward plus feedback control
P R IM A R Y VA R IA B L E

XT

SECO NDARY
VA R IA B L E

YT

P ROCE SS

S E T P O IN T
A T A

f(x)

M A N IP U L AT E D VA R IA B LE

165
Basic control
— Simple cascade control
PR IM ARY VA RIABLE

XT

SEC O N DA RY
VAR IA BLE

ZT

PR O C ESS

SE T PO IN T
A T A

f(x)

M AN IPU LATED VAR IABLE

166
Basic control
Control Mode of PID
-MAN (Manual)
-AUT (Automatic)
-CAS (Cascade)
PID
SP

Percent 0-100 % PV CO 0-100%

Eng. Unit 0-15 m3/h 0-100% (closed à open)


Electrical signal 4-20 mA 4-20 mA

0-15 m3/h Signal to open


167
Feed water control
PID PID

Make up water

PT

Heating steam

LT

Pressure Level
-Manual mode 0-100% heating steam valve -Manual mode 0-100% make up water valve
position
-Auto mode, specify level set point
-Auto mode, specify pressure set point
-Temperature compensation
-Temperature compensation
-Protection, high level over flow
168
Drum Level control
Main steam Pressure
Main steam flow

A, SP
Manual mode, 0-100%
control valve
Auto mode, specify drum
level. Automatically adjust
valve Control valve
M, 0-100%
Protection
-lower limit
DP feed -2/3 principle
water pump - 10 s delay
-Close steam valve for low level
169
Main steam pressure control
PV

SP

FF

CO

170
Main steam
Pressure

Combustion
Total air SP Total Fuel SP
Calculation

X -

PA SP SA SP Fuel1 SP Fuel2 SP Fuel3 SP

PA.Fan SA.Fan Conveyor1 Conveyor2 Conveyor3

171
Solid Fuel Control

Cascade PID
Auto

WT

Manual M

Manual : speed of coal conveyor is


specified by operator
Auto : operator specify fuel flow load
Cascade: fuel flow set point calculated by
main steam pressure control

172
Primary air control
Manual: position of damper is
specified
Auto PID Auto: desired air flow is specified by
Cascade
operator
Cascade: set point is calculated from
master combustion
Flow (interlock) > minimum
PA wind box P > minimum
Manual
M
PV PA running
FT

173
Secondary air control

Auto PID FT
Cascade
Upper SA

PID Auto
Cascade

Manual

Manual
M
PV Manual
FT PT FT
Lower SA

174
HP Blower Control
— Pressure is controlled by control valve
— Control valve is connected to primary air
— It will release the air to primary air duct if pressure higher
than set point
— If operating unit stop due to disturbance or pressure fall
down, stand by unit shall be automatically started
— Pressure should be higher than 300 mbar, boiler interlock
— Pressure < 350 mbar parallel operation start

175
Furnace Pressure control

Auto PID Auto PID

Furnace PT
pressure

2/3 furnace P < max (35 mbar)

M Manual
Manual

176
Lime stone control
— Lime stone can be control by
— lime stone/ fuel flow ratio
— SO2 feed back control
— Manual feed rate

177
Fuel oil control

Pressure control

Auto

Pressure
control valve
M
Manual

Flow control
valve 178
Referenced
• Prabir Basu , Combustion and gasification in fluidized bed, 2006
• Fluidized bed combustion, Simeon N. Oka, 2004
• Nan Zh., et al, 3D CFD simulation of hydrodynamics of a 150 MWe circulating fluidized bed
boiler, Chemical Engineering Journal, 162, 2010, 821-828
• Zhang M., et al, Heat Flux profile of the furnace wall of 300 MWe CFB Boiler, powder
technology, 203, 2010, 548-554
• Foster Wheeler, TKIC refresh training, 2008
• M. Koksal and F. Humdullahper , Gas Mixing in circulating fluidized beds with secondary
air injection, Chemical engineering research and design, 82 (8A), 2004, 979-992

179

You might also like