You are on page 1of 40

ACS 810

A/C service unit

en Repair instructions A/C service unit


en | 2 | ACS 810 | 

en – Contents 9. Troubleshooting 22
9.1 Service messages 22
1. Symbols used 3 9.2 Fault messages 22
1.1 In the documentation 3
1.1.1 Warning notices - Structure and 10. Emptying the ACS 810 23
meaning 3 10.1 Automatic emptying 23
1.1.2 Symbols in this documentation 3 10.2 Extraction of internal refrigerant circuit with
1.2 On the product 3 second A/C service unit 23

2. Important information 4 11. TROUBLESHOOTING AND ANALYSIS 24


11.1 Faults during recovery 24
3. Test equipment and auxiliary materials 4 11.1.1 Compressor starts 24
11.1.2 Compressor does not start 24
4. Safety regulations 5 11.1.3 Fault messages that can occur during
4.1 Handling refrigerant R134a 5 recovery 25
4.2 Working on the vehicle 5 11.1.4 Other fault messages 25
4.3 Notes on operation 6 11.2 Faults during the vacuum phase 25
4.4 Maintenance work 6 11.2.1 The vacuum pump starts 25
4.5 Safety devices 6 11.2.2 The vacuum pump does not start 25
4.6 PED directive 2014/68/EU 6 11.2.3 Fault message that can occur during the
vacuum phase 26
5. Product description 7 11.3 Faults during refrigerant preparation 26
5.1 Description of unit 7 11.4 Non-condensing gases are not drained 26
5.1.1 Front view 7 11.5 Faults during filling with refrigerant 26
5.1.2 Rear view 7 11.5.1 Vehicle air conditioning system cannot
5.1.3 Display and control panel 8 be filled 26
5.1.4 Selection and function keys 8 11.5.2 Other fault messages 26
5.1.5 Input keys 8
12. Component test and maintenance 27
6. Program structure 9 12.1 Vacuum pump 27
6.1 Calibration and tare 9 12.2 Pressure sensor P1 27
6.2 Settings 9 12.3 Pressure switch P2 27
6.3 Repair 9 12.4 Expansion valve 27
6.4 Vehicle and customer data 9 12.5 Periodic check of the non-condensable gas
6.5 Menu 9 purge valve 28
6.6 Manual mode 9 12.6 Combo filter 28
6.7 Automatic mode 9 12.6.1 Replacement of combo filter 28
6.8 Flush (optional) 9 12.6.2 Reset filter 29
6.9 Enter 9 12.7 Vacuum pump 30
12.7.1 Changing vacuum pump oil 30
7. Hydraulics diagram 10 12.7.2 Reset of oil change interval 30

8. Service phases 11
8.1 Recovery 11
8.2 Draining oil into the used oil bottle 13
8.3 Vacuum phase 14
8.4 Leak test 16
8.5 Refrigerant preparation 17
8.6 Fresh oil filling 18
8.7 Filling refrigerant 19
8.8 Separating and returning compressor oil 20
8.9 Non-condensing gases 21

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Symbols used | ACS 810 | 3 | en

13. Calibration 31 1. Symbols used


13.1 Internal refrigerant cylinder scale 31
13.2 Tara values 31 1.1 In the documentation
13.3 Pressure sensor 32 1.1.1 Warning notices - Structure and meaning
13.3.1 Checking the adjustment 32 Warning notices warn of dangers to the user or
13.3.2 Adjusting the pressure sensor 32 people in the vicinity. Warning notices also indicate
the consequences of the hazard as well as preventive
14. Component test 33 action. Warning notices have the following structure:
14.1 LCD 33
14.2 Outputs 33 KEY WORD – Nature and source of hazard!
Warning
14.3 Control PCB input signal 33 symbol Consequences of hazard in the event of
14.4 Printer 33 failure to observe action and information
14.5 Counter 34 given.
14.6 Service printout 34 ¶ Hazard prevention action and
14.7 Draining oil 34 information.

15. Changing basic settings 35 The key word indicates the likelihood of occurrence
and the severity of the hazard in the event of non-
16. Software 36 observance:
16.1 Vehicle database 36
16.2 Data backup 36 Key word Probability of Severity of danger if
occurrence instructions not observed
16.3 Software update 36
16.4 Loading a data backup 36 DANGER Immediate Death or severe injury
impending danger
WARNING Possible impending Death or severe injury
17. Circuit diagram 37 danger
17.1 Control PCB 37 CAUTION Possible dangerous Minor injury
17.2 Computer printed circuit board 38 situation

1.1.2 Symbols in this documentation

Symbol Designation Explanation


Attention Warns about possible property
! damage.
Information Practical hints and other
i
useful information.
1. Multi-step Instruction consisting of several
2. operation steps.
One-step Instruction consisting of one step.
e
operation
Intermediate An instruction produces a visible

result intermediate result.
Final result There is a visible final result on
"
completion of the instruction.

1.2 On the product

! Observe all warning notices on products and


ensure they remain legible.

¶ Wear safety goggles.

¶ Wear protective gloves.

¶ Protect against dampness and moisture.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 4 | ACS 810 | Important information

2. Important information 3. Test equipment and


auxiliary materials
Installation and/or repairs must only be performed
by trained and instructed Bosch customer service
representatives or companies authorized by Bosch R General tools for electricians and A/C mechanics
If the units are opened or modified by unauthorized R Digital multimeter (e.g. MMD 003)
persons, any warranty claims become void. R Loctite 542 (for thread seal) and 222 (for thread
lock)
Electrical systems and devices must only be put into R Cleaning agent (e.g. brake cleaner)
operation when in proper operating condition (details R Calibrating weight 10 - 20 kg for internal refrigerant
can be found in the EDIS-Info 200108_084). This scale
requirement is met if following modification or repair R Leak detector (1 689 100 057)
(initial testing) it is ensured that the requirements R Simulator (optional)
of the electrical engineering directives were adhered
to. To check this, tests should be performed, the
nature and extent of which are based on the measures
specified in the electrical engineering directives (e.g.
in Germany DGUV Vorschrift 3). The type and extent
of the tests are described in VDE 0701/0702 Part 1
within Germany. The relevant national directives must
be complied with.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Safety regulations | ACS 810 | 5 | en

4. Safety regulations R R134a is not to be used in areas in which there


is a danger of explosion. Fire, naked flames and
! Always carefully read and observe all the safety smoking are prohibited. Welding and soldering are
regulations before using the Bosch product. not permitted.
R High temperatures and UV radiation may chemically
¶ Wear safety goggles.
separate the R134a. The resultant products cause
coughing and nausea.
R R134a is not to be mixed with other refrigerants.
¶ Wear safety gloves. The mixing of refrigerants can damage the vehicle
air conditioning system.

4.1 Handling refrigerant R134a 4.2 Working on the vehicle

Avoid all skin contact with the refrigerant. If high-voltage components or high-voltage
The low boiling point of the refrigerant wires are inexpertly handled, there is a risk of
(approx. -30 °C) can lead to frostbites. fatal injury from high voltages and the possible
Should it nevertheless come into contact transmission of current through the body.
with the skin, remove any moistened
clothing immediately and rinse the affected R De-energization is only to be performed by a qualified
skin with copious amounts of water. electrician, a qualified electrician for specific tasks
(hybrid), or a power systems engineer.
R R134a is colorless, has a weak intrinsic odor and is R Work on vehicles with high-voltage components
heavier than air. It displaces oxygen and may flow into is only ever to be performed in a safe, de-
repair pits. Should refrigerant escape (malfunction), energized condition by persons with the minimum
always ensure adequate ventilation and air extraction qualification "Trained to perform electrical work".
(especially in pits). Exit the workshop. R Even after deactivating the high-voltage vehicle
electrical system, the high-voltage battery may still
Never inhale refrigerant and oil vapors. be live.
The vapors can irritate the eyes, nose and R The operating condition cannot be established
respiratory system. If liquid refrigerant from any running noise, as the electric machine is
comes into contact with the eyes, rinse them silent when stationary.
thoroughly with water for 15 minutes. Then R In gear positions "P" and "N" the engine or electric
obtain medical help even if no pain is felt. motor may start spontaneously depending on the
charge of the high-voltage battery.
R Before connecting the ACS 810 to a vehicle air R Never open or damage high-voltage batteries.
conditioning system or an external refrigerant R On accident vehicles, never touch high-voltage
cylinder, make sure the quick-release couplings are components or exposed high-voltage wires before
not leaking. deactivating the high-voltage vehicle electrical system.
R Only ever use external refrigerant cylinders
provided with safety valves and certified in line
with the applicable standards.
R Before switching off the ACS 810, make sure
all filling and drainage operations have been
completed. This prevents refrigerant escaping into
the environment.

Do not use compressed air with R134a.


Some air mixtures with R134a are highly
flammable. Such mixtures are a potential
hazard and may lead to fire or explosions
and thus cause damage or injury.

R Refrigerant extracted from a vehicle air conditioning


system may be contaminated with moisture, lubricant,
dirt and traces of other gases.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 6 | ACS 810 | Safety regulations

4.3 Notes on operation 4.4 Maintenance work


R Never perform any maintenance work which is not
! Observe the pertinent legal regulations or expressly recommended in this manual. Contact
directives to ensure safe handling of pressurized customer service if components have to be
devices. replaced other than in the course of maintenance
work.
R The ACS 810 must be operated in an environment R We recommend calibrating the internal refrigerant
corresponding to the directive BGR 157 with scales at least once per year. Please contact
respect to the exchange of air. customer service.
R Observe local laws or directives so as to ensure the
safety of the pressurized device. The ACS 810 must 4.5 Safety devices
be constantly monitored when in operation. Never
leave the ACS 810 unattended when in operation. ! For safety reasons it is advisable to use a residual
R Position the ACS 810 on all four wheels on a flat, current operated circuit breaker (rccb) with the
vibration-proof surface such that proper operation following specifications:
of the scales is guaranteed.
R The ACS 810 can be secured in position by locking Parameters Specification

the brake. Rated voltage 230 VAC ± 10 %


R The ACS 810 must always be transported in its Rated frequency 50 Hz
operating position. Never lay the ACS 810 on its Rated current 230 VAC 10 A
side, as oil could then escape from the vacuum Rated tripping current 30 mA
pump, or the built-in compressor could be Tripping switch C

damaged. Overview of safety devices:


R There are no additional safety systems for
protecting the ACS 810 against damage resulting Description Operation

from natural catastrophes. Pressure switch Switches the compressor off if the normal
operating pressure is exceeded.
R ACS 810 must be connected to a properly
Safety valve The safety valve opens if the design
grounded electrical connection.
pressure is exceeded.
R The vehicle A/C service using the ACS 810 must be Fuse Interrupts the power supply to ACS 810 in
prepared and implemented such that the vehicle the event of too high current.
air conditioning system circuit does not have to be Vents The ACS 810 is provided with vents in
opened (for example by removing the radiator or the bottom of the housing to ensure the
exchange of air even when switched off.
engine).
R Never remove any components from inside
the ACS 810 except for maintenance or repair 4.6 PED directive 2014/68/EU
purposes. The machine includes parts subject to PED EU
R If damage to the ACS 810 is established, terminate directive 2014/68/EU, Pressure Equipment Directive.
usage immediately and contact customer service. PED directive regulates all the pressurized part
R The service hoses and quick-release couplings defining for them categories based on volume-
must be regularly checked for wear and replaced if pressure ratio and based on fluid refrigerant type.
damaged. Those parts then have not to be anyhow modified nor
removed. Under the responsibility of the owner, the
WARNING: Warranty is not valid in all machine and parts falling in the scope of PED shall be
cases of improper use of the machine and checked either during commissioning and periodically
if the machine is not submitted to periodic fulfilling local country regulations and norms.
ordinary and extraordinary maintenance Parts in the scope of PED are:
(according to PED directive 2014/68/ R Tank.
EU) provided in this original instructions. R Pressure relieve valve.
The manufacturer therefore declines all R High pressure switch.
responsibilities for any damage resulting R Recovery group.
from not observing all the instructions and R Piping.
warnings provided to the user regarding
installation, use and maintenance. i Call Bosch service center to get technical
specifications for each part listed.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Product description | ACS 810 | 7 | en

5. Product description 5.1.2 Rear view

5.1 Description of unit


5.1.1 Front view 7
5 6

6 4

2
4

3 3
7

2
8 4
1

9
5

Fig. 2: Rear view


1 Service quick-release coupling (LP)
FV
_A
CS 2 Service quick-release coupling (HP)
81
0 3 Service hose (5 m)
10 4 Service hose mount
5 Rear wheels
6 Power cord (socket)
Fig. 1: Front view 7 Master switch
1 Valve high pressure (HP)
2 Valve low pressure (LP)
3 Printer
4 Display and control panel
5 Gage low-pressure pressure (LP)
6 Gage high-pressure valve (HP)
7 Pressure gage of internal refrigerant cylinder
8 Fresh oil bottle
9 Used oil bottle
10 Front wheels with locking brake

i The high (6) and low pressure (5) gages show the
current pressure during the air conditioning service
on the vehicle. The small gage (7) is used to check
the bottle pressure in the internal refrigerant
cylinder.

i The two valve settings are labeled as follows:


$ C (Close) = valve is closed
$ O (Open) = valve is open

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 8 | ACS 810 | Product description

5.1.3 Display and control panel 5.1.4 Selection and function keys
The display and control panel of the operating unit
control the menus and the service phases. Keys Name Operation

Refrigerant is extracted from the


Evacuation
vehicle.
R Control up R Upward cursor movement.
6 R Vacuum R A vacuum is generated.

R Control R Cursor movement to the right.


right R Vehicle air conditioning system
5 7
R Filling is filled with refrigerant.
4
R Control R Cursor movement to the left.
3
left R Automatic service run: Air
2 R Automatic conditioning service is carried
8 out according to saved
1 parameters.
R Control R Downward cursor movement.
10 9 down R Flush components of the
R Flushing vehicle air conditioning.
Fig. 3: Display and control panel Call up various function for
1 Flushing Menu service
2 Automatic service and data management.
3 Filling Call up databases:
4 Vacuum R USER SPECS
Database
5 Removal by suction R VEHICLE DATAS
6 LCD display
7 Key panel
8 Vehicle database Enter (E) Confirm and take over.
9 PS2 interface 1)
10 Function light

Stop Terminate and return.


For updating firmware/software or database
1)

Various functions are assigned to the <MENU>


function key in the ACS 810 software. The functions of
the keys are defined in the menu line of the ACS 810
software.

5.1.5 Input keys


The input keys can be used to enter letters, numbers
and special characters in the input boxes.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Program structure | ACS 810 | 9 | en

6. Program structure 6.6 Manual mode


Input Menu
6.1 Calibration and tare
SELECT PORTS
Input Menu ...

TANK CALIBRATION <RECOVERY>


+ <3> IN OIL CALIBRATION R Automatic emptying
1)
1.
2. Enter 1111. OUT OIL CALIBRATION 1) R Extraction
3. Confirm with E. R Oil drain
PRES. CALIBRATION
R Pressure test
TANK TARE
IN OIL TARE 1)
Input Menu
OUT OIL TARE 1)

SET VACUUM TIME


...
6.2 Settings
<VACUUM>
Input Menu
LANGUAGE Input Menu

1. + <3> DATE/TIME SELECT PORTS


2. Enter 2222. UNIT OF MEASURE ...
3. Confirm with E. HOSES LENGTH
<CHARGE>
CONTRAST
GARAGE ADDRESS
FLUSHING
6.7 Automatic mode
OIL SCALE 1)

UV DYE 1)
Input Menu
DATABASE UPDATE
SELECT PORTS
SERIAL NUMBER ...
EXPERT MODE
<AUTOMATIC>
6.3 Repair
Input Menu
6.8 Flush (optional)
CHANGE FILTER
1. + <3> CHANGE OIL Input Menu
2. Enter 5555. SET VACUUM TIME
3. Confirm with E. ...

<FLUSH>
6.4 Vehicle and customer data
Input Menu 1 Menu 2
6.9 Enter
STANDARD SPECS EUROPEAN DATABASE
USER SPECS SELECT MODEL : Input Menu
DELETE MODEL : Information on current filling
<Database>
ADD MODEL : capacities of fresh and used
oil bottles and the internal
VEHICLE DATAS
<ENTER> refrigerant cylinder
6.5 Menu
1)
Not supported for ACS 810 or without functionality
Input Menu 1 Menu 2
PERFORMANCE TESTS
DIAGNOSTIC
TANK FILLING
<Menu>
TANK RECYCLING
ZEROING OIL SCALES 1)

REPORT MANAGEMENT PRINT REPORT


EXPORT DATA
DELETE DATA

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 10 | ACS 810 | Hydraulics diagram

7. Hydraulics diagram
M2
HIGH
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Service phases | ACS 810 | 11 | en

8. Service phases i The combo filter (F2) cleans the extracted


refrigerant of suspended particles and moisture.
i This section describes all of the ACS 810 service
phases. In addition, it explains the hydraulic i In the evaporator/oil separator (5), the oil taken
and electric circuits by presenting the hydraulic in from the compressor is separated from the
diagram and providing a brief description of the refrigerant and fed back to the compressor.
components involved in each function.
i If the pressure at sensor P1 falls below the
8.1 Recovery value saved in the software, the function stops
automatically, the program waits 5 minutes for a
i In this service phase, the refrigerant is extracted pressure increase and, if necessary, restarts with a
from the vehicle air conditioning system. second recovery cycle.

1. The ACS 810 is connected to the vehicle with the At the end of this phase, the solenoid valves EV10,
service hoses T1 and T2. EV3 and EV5 are closed and the compressor 6 is
2. Open the service quick-release coupling valves. turned off.
? The pressure on the high and low pressure side
of the vehicle air conditioning system is indicat-
ed on the pressure gages M1 and M2.

i Opening the HP and LP valves on the ACS 810


causes the refrigerant to flow to the solenoid valves
EV10 (open) and EV3 (closed).

i The pressure sensor P1 checks the pressure of the


vehicle air conditioning system (whether or not
there is refrigerant in the vehicle air conditioning
system).

3. starts extraction of the refrigerant.


? The solenoid valves EV10, EV3 and EV5 are
opened and the compressor (6) is started.

R The refrigerant flows through the solenoid valves


EV 10, EV3 and EV5, the mechanical filter (F1), the
expansion valve (3), and the condenser/separator
(4).
R The expansion valve maintains a constant pressure
at the evaporator/oil separator (4).
R In the evaporator/oil separator (4), the oil
extracted from the vehicle air conditioning system
is separated from the refrigerant and routed into
the used oil bottle.
R The refrigerant then flows on through the combo
filter (F2) and the compressor (6) into the
condenser/separator (5), and finally into the
internal refrigerant cylinder.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 12 | ACS 810 | Service phases

M2
HIGH
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Service phases | ACS 810 | 13 | en

8.2 Draining oil into the used oil bottle


At the end of recovery, the solenoid valve EV7 opens
and the oil previously separated out in the evaporator/
oil separator (4) drains into the used oil bottle (9).

M2
HIGH
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 14 | ACS 810 | Service phases

8.3 Vacuum phase i If the pressure in the vehicle air conditioning


system is below the set value, the vehicle air
i During vacuum generation in the vehicle air conditioning system is empty and the ACS 810
conditioning system, the refrigerant is prepared starts vacuum generation.
in the internal refrigerant cylinder to remove the
non-condensing gases before filling and to filter the i If the pressure is above the set value, there is still
refrigerant. refrigerant in the vehicle air conditioning system,
and it must be extracted before vacuum generation.
1. The ACS 810 is connected to the vehicle with the
service hoses T1 and T2.
2. Open the service quick-release coupling valves. 3. Press the <Vacuum> key.
? The pressure on the high and low pressure side ? EV1 and EV10 are opened
of the vehicle air conditioning system is indicat- ? The vacuum pump (2) starts.
ed on the pressure gages M1 and M2.
i The vacuum pump generates a maximum vacuum
i Opening the HP and LP valves on the ACS 810 of 0,033 mbar. This depends on the duration of
causes the refrigerant to flow to the pressure vacuum generation.
sensor P1 (solenoid valves EV1, EV3, and EV10
are closed). P1 checks the pressure in the vehicle i The refrigerant in the internal refrigerant cylinder
air conditioning system (refrigerant present in the is fed through the internal refrigerant circuit and
vehicle air conditioning system or not). prepared in each vacuum phase.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Service phases | ACS 810 | 15 | en

M2
HIGH
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 16 | ACS 810 | Service phases

8.4 Leak test i If the pressure at P1 falls below the value saved in
the software during the leak test, an error message
i The leak test starts after the vacuum phase. is displayed.

i The HP and LP valves are open and all solenoid


valves are closed. After the specified vacuum time
has elapsed, EV1 is closed to perform the leak test.

M2
HIGH
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Service phases | ACS 810 | 17 | en

8.5 Refrigerant preparation i In that way, refrigerant is sucked from internal


refrigerant cylinder (7) and is conveyed through the
1. Press the <MENU> key. filter F1, the expansion valve (3), the Evaporator/ oil
2. Select <R134a PREPARATION> and confirm with E. separator (4) until reaching the internal refrigerant
" ACS 810 starts internal preparation of the refrigerant. cylinder (7) again, as it happens in the recovery stage.
" EV5 and EV6 are opened and the compressor (6)
starts. i Internal preparation of the refrigerant is the same
process that the ACS 810 performs in the recovery
M2 phase to clean the refrigerant recovered from the
HIGH vehicle air conditioning system.
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 18 | ACS 810 | Service phases

8.6 Fresh oil filling 1. Open valve of service quick coupler T2.
2. Open HP valve.
i You can only fill new fresh oil into a vehicle A/C 3. Open solenoid valve EV8.
system, if there is vacuum inside the A/C system. ? The pressure difference makes fresh oil in the
So you have to start first the vacuum phase. graduated bottle be sucked inside the vehicle A/C
system.
i After evacuating the vehicle A/C system, recovered
i As buses often have huge quantities of oil (even
oil has to be replaced with new oil. The oil
more than 1 kg), for the oil replenishing the
replenishing occurs by pressure difference.
refrigerant pump (11) is also used that allows the
replenishing of the hole quantity needed.
M2
HIGH 4. After filling fresh oil, close solenoid valve EV8 and
T2 switch off the refrigerant pump (11).

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Service phases | ACS 810 | 19 | en

8.7 Filling refrigerant


1. Press the key .
i The refrigerant in the internal refrigerant cylinder is ? EV3, EV6 and EV10 are opened.
used for filling the vehicle air conditioning system. ? Refrigerant pump (11) will start.
? Refrigerant flows from the internal refrigerant
i Refrigerant can only be added to a vehicle air cylinder through valves V4 and V2, through the
conditioning system under a vacuum. The vacuum solenoid valves EV3, EV6 and EV10, the HP valve
phase must therefore be performed before filling. (when filling on the high pressure side) and
along the service hose T2 into the vehicle air
conditioning system.
2. The filling quantity is checked by the scale (8),
M2 which end the filling process after the quantity
HIGH
previously entered in the service process.
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 20 | ACS 810 | Service phases

8.8 Separating and returning i This oil is separated from the refrigerant in the
compressor oil compressor oil separator (5) and is then fed back
to the compressor (6).
i During the recovery phase and preparation of the
refrigerant, small quantities of compressor oil get
into the internal circuit.

M2
HIGH
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Service phases | ACS 810 | 21 | en

8.9 Non-condensing gases i The pressure of the internal refrigerant cylinder


increases during the recovery phase and when
i The drain valve (V6) for non-condensing gases preparing the refrigerant.
opens if the pressure in the refrigerant cylinder
is higher than the set opening pressure (normally i The safety valve (V5) opens at a factory set
between 12 and 14 bar). pressure (approx. 18 bar) to limit the pressure in
the internal refrigerant cylinder.
M2
HIGH
T2

EV10 EV3

M1
LOW EV5 EV6
T1 P1 EV1
EV8
P
11
2 M3
VU1

P
1

P2 3 F1

HP
V5 V6

F2 5
4
10
V1 V3 V4 V2

EV7

6 7
9
C
8

Des. Description Des. Description


1 Fresh oil tank F2 Combi filter
2 Vacuum pump VU1 Oil non-return valve
3 Expansion valve EV1 Vacuum solenoid valve
4 Evaporator/oil separator EV3 Flow solenoid valve
5 Compressor oil separator EV5 Recovery solenoid valve
6 Compressor EV6 Filling solenoid valve
7 Internal refrigerant cylinder EV7 Oil drain solenoid valve
8 Refrigerant cylinder scale EV8 Oil injection solenoid valve
9 Used oil bottle EV10 Refrigerant pump by-pass solenoid valve
10 Heat exchanger P1 Pressure sensor
11 Refrigerant pump P2 Pressure switch
T1 Low pressure hose V1 Tank vapour side hose valve
T2 High pressure hose V2 Tank liquid side hose valve
M1 Low pressure gage V3 Tank vapour side valve
M2 High pressure gage V4 Tank liquid side valve
M3 Internal refrigerant cylinder pressure gage V5 Safety valve
F1 Coarse filter V6 Non condensable drain valve

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 22 | ACS 810 | Troubleshooting

9. Troubleshooting
9.1 Service messages
Service message Actions
CHANGE OIL Change vacuum pump oil
(see section 12.7.1)
REPLACE FILTER Replace combo filter
(see section 12.6.1)

9.2 Fault messages


failure indication Actions
HIGH PRESSURE There is excess pressure at the outlet of the compressor.
Turn off the ACS 810 and wait approx. 30 minutes.
PROGRAM ERROR Error in the software.
FULL TANK The internal refrigerant cylinder has been filled to maximum filling level.
Carry out several refill procedures to reduce the internal refrigerant quantity.
HIGH RECOVERY TIME The recovery time exceeds the set maximum duration. Check the vehicle air
conditioning system for leaks. If error persists, contact customer service.
A/C SYSTEM EMPTY There is no refrigerant in the vehicle air conditioning system.
A/C SYSTEM FULL There is refrigerant in the air conditioning system.
INCOMPLETE CHARGE The filling time exceeds the safe maximum duration set.
Pressure in internal refrigerant cylinder corresponds to pressure in vehicle
air conditioning system.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Emptying the ACS 810 | ACS 810 | 23 | en

10. Emptying the ACS 810 10.2 Extraction of internal refrigerant


circuit with second A/C service unit
! When repairing internal components, we
recommend extracting the internal hoses on the i If recovery cannot be performed due to a defective
ACS 810 to ensure that no refrigerant can escape compressor, a second A/C service unit or an
when the hose lines are opened. external compressor is required to remove the
refrigerant from the internal refrigerant circuit. To
i This extraction is carried out by automatic do this, start the "Recycle" function to open the
emptying or, if there is a technical defect, by using corresponding solenoid valves.
a second A/C service unit.
i The compressor power supply for the ACS 810
Warning – Risk of frostbite from escaping must be disconnected before extraction.
refrigerant
Refrigerant causes severe frostbite on the 1. Close shutoff valves V1, V3, V2, and V4 on the
skin. refrigerant cylinder and disconnect the blue and
¶ Check the service hoses for damage. red hoses from the refrigerant cylinder.
¶ Firmly connect the service quick-release 2. Connect the blue hose to the low pressure side of
couplings to the service hoses. the second A/C service unit.
¶ Wear safety goggles. 3. Connect the red hose to the high pressure side of
¶ Wear protective gloves. the second A/C service unit.
4. Open the valves V1 and V2.
10.1 Automatic emptying 5. Open both valves on the second A/C service unit
and recover the refrigerant from the first, defective
i Refrigerant in the internal hoses is extracted into A/C service unit.
the internal refrigerant cylinder. ? A pressure increase test is performed at the end
of recovery.
1. Service hoses (T1, T2) are not connected to the 6. Close the two valves on the second A/C service
vehicle. unit and disconnect the hoses from the refrigerant
2. Close service quick-release couplings. cylinder.
3. Open HP and LP valves on the ACS 810. " Repairs can be performed.
4. Start recovery.
" Automatic emptying is performed.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 24 | ACS 810 | TROUBLESHOOTING AND ANALYSIS

11. TROUBLESHOOTING AND If the pressure at the pressure gages falls slowly:
ANALYSIS 1. Check filter (F1).
If clogged, clean with compressed air (blow out).
2. Valves V1 and V3 must be open.
i This section briefly describes the various faults, 3. Check expansion valve (3) with a pressure gage.
and the components that can cause the faults. Operating pressure must be between 2 and 2.3 bar.
4. Check compressor (6).
! Before carrying out any service intervention, reduce
the ACS 810 pressure so that no refrigerant is ACS 810 ends the recovery phase but the pressure at
released. the pressure gages does not change.
1. Valves V1, V2, V3, and V4 must be open.
11.1 Faults during recovery 2. HP and LP valves must be open.
11.1.1 Compressor starts 3. Check that pressure sensor (P1) functions
properly.
i EV3 and EV5 are closed for automatic self-cleaning.
The pressure at the pressure gages may not 11.1.2 Compressor does not start
change. 1. Check fuses F 2 and F 3 (T 12.5 A) on control PCB.
2. Check whether 12 Volt (DC) is applied at the
1. Service hoses (T1, T2) are not connected to the compressor relay coil.
vehicle. 3. Check whether the compressor relay trips after
2. Close service quick-release couplings. pressing the recovery key. It may be necessary to
3. Open HP and LP valves on the ACS 810. replace the keypad or the control card.
4. Check whether 230 Volt is applied at the
i If the pressure at the pressure gages decreases compressor relay output pins.
during self cleaning, check whether EV3 and EV5 ? If no voltage is applied, the computer PCB is de-
are not supplied with power. fective and must be replaced.
? If voltage is applied, the current consumption
Power applied: must be measured.
? Computer PCB (control PCB) defective. 5. Measure current consumption. At 0 A or >=8 A the
" Replace computer PCB (control PCB). compressor must be replaced.

No voltage applied:
? Solenoid valve leaking.
" Clean or replace solenoid valve.

i If the pressure at the pressure gages does not


decrease after self cleaning, check whether EV3,
EV5, and EV10 are supplied with power.

Power applied:
? Solenoid valve defective.
" Clean or replace solenoid valve.

No voltage applied:
? Computer PCB (control PCB) defective.
" Replace computer PCB (control PCB).

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


TROUBLESHOOTING AND ANALYSIS | ACS 810 | 25 | en

11.1.3 Fault messages that can occur during 11.2 Faults during the vacuum phase
recovery 11.2.1 The vacuum pump starts

"CYLINDER FULL" i The vacuum pump starts but no vacuum is


generated in the vehicle air conditioning system
i Check the weight of the internal refrigerant
cylinder and reduce the quantity of refrigerant in 1. Disconnect service hoses from vehicle.
the internal refrigerant cylinder. 2. Open HP and LP valves.
3. Check whether the hose connected to the vacuum
"PRESSURE VALVE TOO HIGH" pump is correctly connected at both ends and is
1. Valves V1, V2, V3, and V4 must be open. not clogged.
2. Check contacts for pressure switch (P2). 4. Check the oil level in the vacuum pump.

i If the pressure is below 16 bar, voltage must be i The oil level should be in the middle of the sight
present between pin 1 and pin 2, while pin 1 and glass between the "full" and "empty" marks.
pin 4 are open.
5. Check the pump vacuum output (the pressure must
i If the pressure is above 16 bar, the contacts fall to less than 0,033 mbar within 3 minutes).
between pin 1 and pin 2 open, while the pin 1 and 6. If a vacuum of less than 0,033 mbar is reached:
pin 4 contacts close. Check whether voltage is present at EV1 and EV10.
7. Valves EV8 and EV9 must not leak.
? If the pressure switch (P2) does not work in 8. Check whether EV1 switches
this way, replace it. ? If voltage is present and EV1 switches, replace
? If the pressure switch is working correctly, the vacuum pump.
check the wiring and the control PCB. ¶ Check the pump vacuum output (the pressure must
fall to less than 0,033 mbar within 3 minutes).
i If no fault can be identified with the pressure
switch (P2), the line to the internal refrigerant 11.2.2 The vacuum pump does not start
cylinder must be checked for clogging. 1. Check the oil level in the vacuum pump.
2. Check whether the vacuum pump is turned on (on/
off switch on the rear of the vacuum pump).
11.1.4 Other fault messages 3. Check fuses F 2 and F 3 (12.5 A) on the control
Please see chapter 9.2 PCB.
4. Check whether the relay trips after pressing the
vacuum key.
5. Check whether the vacuum pump is being supplied
with power (230 Volt).

i A voltage of 12 Volt (DC) must be present at the


pump relay coil; 230 Volt must be present at the
output contacts. If one of these voltages is not
present, the computer PCB must be replaced.

" Replace the vacuum pump if it does not start.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 26 | ACS 810 | TROUBLESHOOTING AND ANALYSIS

11.2.3 Fault message that can occur during the 11.5 Faults during filling with refrigerant
vacuum phase
11.5.1 Vehicle air conditioning system cannot be
"A/C SYSTEM FULL" filled
If the refrigerant pump works, but does not charge the
¶ Check the pressure at the pressure gages M 1 and A/C system, it is necessary to:
M 2.
? Pressure above 0.3 bar, perform recovery. 1. Check hose connections on the internal refrigerant
? Pressure below 0.3 bar, adjust pressure sensor cylinder.
P 1. 2. Valves V1, V2, V3 and V4 must be open.
" If the message is still displayed, replace the pressure 3. HP and LP valves must be open.
sensor. 4. Check the calibration of the scale.
" If the message is still displayed, replace the computer
PCB. i Ensure that the refrigerant scale are not blocked.

11.3 Faults during refrigerant preparation i You must ensure that the control PCB applies
the set weight value; if not, check whether the
1. Check hose connections on the internal refrigerant refrigerant cylinder contains sufficient refrigerant
cylinder. for the filling process.
2. Valves V1, V2, V3 and V4 must be open.
3. Check EV7 for leaks. i Check whether EV6 and EV3 are supplied with
4. Check filter F1 for impurities and clean with power. If so, they must be replaced. If they are not
compressed air. supplied, the connecting cables and the control
5. Check the expansion valve (3) for the correct PCB must be checked.
pressure value (2 - 2.3 bar).
6. Check whether the internal refrigerant circuit is If the refrigerant pump does not work, it is necessary
soiled or clogged. to:

i If the compressor does not start, make sure that a 1. Check the condition of the flying fuse (800 mA
supply voltage is connected to the compressor. If delayed) inside the power box.
no voltage is applied, check the supply leads and
the switching operation of the compressor relay. i Be sure that there is a 230 Volt during the filling
phase, but only after the switching off of the EV10
11.4 Non-condensing gases are not solenoid valve.
drained
i Be sure that there is 12 Volt (DC) direct current
¶ Mechanically test drain valve V6. on the refrigerant pump relay coil; be sure are 230
Volt on the outlet contacts. In case one of the two
voltages is absent, replace the control PCB.

11.5.2 Other fault messages


Please see chapter 9.2

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Component test and maintenance | ACS 810 | 27 | en

12. Component test and 12.3 Pressure switch P2


maintenance
i The pressure switch is normally closed between
contacts 1 and 2, and open between contacts 1
12.1 Vacuum pump and 4. The pressure switch opens at 16 bar.

! The vacuum pump oil must always be changed after To check the pressure switch, carry out the following
30 hours of operation. steps:
1. Close V1 - V4.
Property Value/range
2. Remove the red hose from the internal refrigerant
Operating voltage 230 VAC ± 10 % cylinder and connect the red service hose to the
Frequency 50/60 Hz internal refrigerant cylinder.
Vacuum pump oil filling capacity 590 ml 3. Close both valves on the refrigerant cylinder.
Output 283 l/min 4. Remove the blue hose from the internal refrigerant
Max. vacuum 0,033 mbar
cylinder and connect a pressure gage using a
T-piece.
To check correct operation of the pump, carry out the 5. Open V4.
following steps: 6. Open V1.
1. Check the oil level in the vacuum pump. 7. Start the recovery function.
8. As soon as the pressure reaches 16 bar, recovery
i The oil level should be in the middle of the must be ended, and the message
sight glass between the "full" and "empty" marks. PRESSURE VALUE TOO HIGH is displayed.
9. Drain the pressure into the internal refrigerant
2. Attach pressure gage to intake connection. cylinder by opening the high pressure valve.
3. Start vacuum generation.
" A vacuum of 0,033 mbar must be achieved. i When replacing the pressure switch, a special
weight sealant must be used.
12.2 Pressure sensor P1
1. Check whether a voltage of 24 Volt (DC) is present 12.4 Expansion valve
between pin 1 (-) and pin 2 (+).
i The expansion valve is a pressure control valve
i If no voltage is present, check the control PCB and that is set to a value between 2 and 2.3 bar and
replace if necessary. maintains a constant pressure before the oil
separator.
2. Check whether an output signal is present between
pin 1 (-) and pin 3 (+). ! The refrigerant cylinder must contain at least 6 kg
of refrigerant.
i The output signal is between 0 V and 10 Volt, i.e.
1.0 Volt corresponds to 1.6 bar. If the pressure 1. Connect the low pressure service hose to the
gage shows 3 bar relative (4 bar absolute), the connection after the expansion valve using the
voltage must be 2.5 Volt. adapter supplied.
2. Close HP and LP valves.
i When replacing the pressure sensor, a special 3. Start the recycling function.
thread sealant (e.g. Loctite 542) must be used. " After around 10 minutes, the pressure value must be
between 2 and 2.3 bar.

i Adjust the value by turning the hexagonal screw in


the expansion valve upper part, if the pressure is
not within the indicated range (between 2 and
2,3 bar).
$ Clockwise to increase the value.
$ Counterclockwise to decrease the value.

i In case of replacement, use the right o-rings and


perform the calibration as instruction above.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 28 | ACS 810 | Component test and maintenance

12.5 Periodic check of the non-condensable 12.6 Combo filter


gas purge valve 12.6.1 Replacement of combo filter

CAUTION: Only qualified technicians who


are authorized to use refrigerants may DANGER – Risk of electric shock from
carry out this procedure. dangerous voltage!
¶ Wear personal protective equipment Electric shocks resulting from contact
(glasses and gloves). with live parts (e.g. master switch, printed
¶ Do not go in front of the discharge flow. circuit boards) can cause injury, heart
¶ The valve does not require adjustment or failure and death.
lubrication. Do not tamper with it in any ¶ Disconnect the mains plug before
way. opening the ACS 810.

1 WARNING – Risk of frostbite from


escaping refrigerant
Refrigerant causes severe frostbite on the
skin.
¶ Check the service hoses for damage.
¶ Firmly connect the service quick-release
couplings to the service hoses.
¶ Wear safety goggles.
¶ Wear protective gloves.

Fig. 4: Periodic check of the non-condensable gas purge valve


1 Non-condensable gas purge valve i After 150 kg of refrigerant have been
processed through the filter, the message
i To ensure that the valve remains in good working "REPLACE FILTER" appears on the display. When
condition, periodically make it trip by pulling the this message appears, contact customer service to
metal ring at the top. order a new filter.

i While doing this, make sure that the pressure in the i It is advisable to have the combo filter changed by
cylinder is at least 8–10 bar. customer service.

i The valve should open sharply and then close ! Make sure the old sealing rings are removed before
firmly as soon as the metal ring is released. securing the new filter.

! This action must be quick, and do not repeat it ! Pay attention to correct positioning of the sealing
until only non-condensable gas is purged, with no rings when fitting a new filter.
refrigerant.
! Take care not to damage any hoses or electrical
i The frequency depends on the valve condition, connections when changing the filter.
and specifically on its cleanliness, which normally
depends on whether there are residues in the ! Never re-use an old filter.
cylinder or not.
! Observe the ACS 810 menu prompting.

1. Call up start screen.


2. Open the HP and LP valves on the display and
control panel.
3. Press <Recovery>.
? ACS 810 performs a self-cleaning process, then
the recovery phase.

i Pressure gauge must reach 0 bar.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Component test and maintenance | ACS 810 | 29 | en

4. Close the HP and LP valves on the display and 12.6.2 Reset filter
control panel.
5. Switch off ACS 810. ! Observe the ACS 810 menu prompting.
6. Disconnect ACS 810 from power supply.
7. Carefully open the ACS 810 housing. 1. Call up start screen.
8. Carefully remove the old Combo filter. 2. Press <3> and <Flush> simultaneously and release.
9. Insert the new Combo filter with the new sealing ? The message ENTER CODE 0000 is displayed.
rings and ensure correct positioning of the sealing 3. Enter code 5555 and confirm with E.
rings. 4. Select "CHANGE FILTER" with o u and confirm
with E.
? The current quantity (in kg) of filtered refriger-
ant is displayed.
5. Press <MENU> until filtered refrigerant quantity is
reset to zero.
" Filter change interval is reset.

i Return with <Stop>.

Fig. 5: Combo filter

10. Close the housing.


" The filter is replaced.

i Return with <Stop>.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 30 | ACS 810 | Component test and maintenance

12.7 Vacuum pump ! Do not use excessive force when securing and
12.7.1 Changing vacuum pump oil removing the oil drain and oil filling screw.

i The container for catching oil should have a


DANGER – Risk of electric shock from capacity of approx. 1 l.
dangerous voltage!
Electric shocks resulting from contact 1. Place a vessel under the drain.
with live parts (e.g. master switch, printed 2. Remove drain plug and oil fill plug from vacuum
circuit boards) can cause injury, heart pump.
failure and death. 3. Drain off all the oil.
¶ Disconnect the mains plug before 4. Screw on drain plug finger-tight.
opening the ACS 810. 5. Fill in vacuum pump oil.
6. Start the vacuum phase.
7. Check the oil level (sight glass).
ATTENTION – Risk of burns from hot
surfaces i The oil level should be in the middle between the
Contact with the hot vacuum pump "full" and "empty" marks.
surface will cause severe burns.
¶ Allow the vacuum pump to cool down. 12.7.2 Reset of oil change interval
¶ Wear protective gloves.
! Observe the ACS 810 menu prompting.

i The vacuum pump oil must always be changed after 1. Call up start screen.
30 hours of operation. The prompt "REPLACE OIL" 2. Press <3> and <Flush> simultaneously and release.
appears on the screen when the vacuum pump oil ? The message ENTER CODE 0000 is displayed.
needs changing. 3. Enter code 5555 and confirm with E.
4. Select "CHANGE OIL" with o u and confirm with
i Use the vacuum pump oil (item number E.
SP00100086) as specified by Bosch. ? Current runtime of vacuum pump is displayed.
5. Press <MENU> until vacuum pump runtime is set to
zero.
" Oil change interval is reset.

i Return with <Stop>.

3 1

Fig. 6: Vacuum pump


1 Sight class
2 Oil fill plug
3 Drain plug

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Calibration | ACS 810 | 31 | en

13. Calibration 13.2 Tara values


The following Tara values for the Internal refrigerant
13.1 Internal refrigerant cylinder scale cylinder is set from the factory.

i Detach the rear panel and remove the refrigerant Internal refrigerant cylinder:
cylinder from the scale. ACS 810 = 18.5 kg

i It is not necessary to detach the lines from the Setting tara value:
refrigerant cylinder. If you want to detach the 1. Select the Tara value (Tara Internal refrigerant
hoses, close the valves on the hoses and on the cylinder).
cylinder. 2. Set the weight.
3. Confirm with <Enter>.
1. Call up the start screen.
2. Press <3> and <Flush> simultaneously and release. i Important note for older software versions:
? The message ENTER CODE 0000 is displayed. The Tara values are NOT displayed. You always will
3. Enter the value 1111 and confirm with E. see just value "0" in the menu where you can set
4. Select "TANK CALIBRATION" and confirm with the Tara value.
ENTER.
? The display shows ! If you confirm with <Enter> in this menu, you set
ZERO CALIBRATION. "0" as new Tara value. If you don't want to change
5. With an empty weighing plate, enter the figure the current value, you have to press the key "Stop".
00.00 and confirm with E .
? The display shows
WEIGHT CALIBRATION.
6. Place the calibration weight on the weighing
tray (a value of between 10 kg and 20 kg is
recommended).
7. Enter the calibration weight value and confirm with
E.
" The menu containing the functions appears on the
display again.

i Return with <Stop>.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 32 | ACS 810 | Calibration

13.3 Pressure sensor i If the simulator is not available, a simplified


13.3.1 Checking the adjustment adjustment can be performed. This process
1. Call up the start screen. definitely guarantees that the ACS 810 will function
2. Press <3> and <Flush> simultaneously and release. perfectly.
? The message ENTER CODE 0000 is displayed.
3. Enter 1515 and confirm with E . 1. Turn on the ACS 810.
4. Select "INPUTS TEST" with o u and confirm with E . 2. Open the HP and LP valves on the display and
? The absolute values of the scales and of the control panel.
pressure sensor is displayed. 3. Start the vacuum function and maintain the vacuum
5. Remove the service hoses on the ACS 810 and in the hoses for 5 minutes (this subjects the
open the HP and LP valves on the front panel pressure sensor to a vacuum).
so that the pressure sensor is subjected to the 4. After 5 minutes, stop the vacuum function and
atmospheric pressure. check on the pressure gages that there are no
6. Check that the pressure value read is between leaks.
0.900 and 1.100 bar (the typical value is 1.000 5. Call up the start screen.
bar). 6. Press <3> and <Flush> simultaneously and release.
? The message ENTER CODE 0000 is displayed.
13.3.2 Adjusting the pressure sensor 7. Enter 1111 and confirm with E .
8. Select "PRESSURE CALIBRATION" and confirm
i The pressure sensor is adjusted on the control PCB with E .
using the simulator, as the pressure sensor has ? ZERO CALIBRATION is displayed.
been officially calibrated in the factory. 9. Enter the value 0.000 on the keypad and confirm
with E.
i Pressure sensor 0 bar / 16 bar absolute ? WEIGHT CALIBRATION is displayed.
-1 bar / +15 bar relative. 10. Detach the service hoses and set the pressure
sensor to atmospheric pressure.
1. Disconnect the pressure sensor from the control 11. Enter the value 1.000 on the keypad and confirm
PCB. with E.
2. Connect the simulator to the control PCB. ? The menu containing the functions appears on
3. Connect a multimeter to the simulator. the display again.
4. Call up the start screen.
5. Press <3> and <Flush> simultaneously and release. i Return with <Stop>.
? The message ENTER CODE 0000 is displayed.
6. Enter 1111 and confirm with E . 12. Perform the adjustment check described above
7. Select "PRES. CALIBRATION" with o u and (see section 13.3.1).
confirm with E .
? ZERO CALIBRATION is displayed.
8. Turn the potentiometer on the simulator until a
voltage of 0 V is displayed.
9. Enter the value 0.000 on the keypad and confirm
with E.
? WEIGHT CALIBRATION is displayed.
10. Turn the potentiometer on the simulator until a
voltage of 3.00 V is displayed.
11. Enter the value 4.800 on the keypad and confirm
with E.
? The menu containing the functions appears on
the display again.
12. Remove the simulator and re-connect the pressure
sensor.

i Return with <Stop>.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Component test | ACS 810 | 33 | en

14. Component test 14.3 Control PCB input signal

14.1 LCD ! Follow the additional ACS 810 menu prompting.

! Follow the additional ACS 810 menu prompting. 1. Call up the start screen.
2. Press <3> and <Flush> simultaneously and release.
1. Call up the start screen. ? The message ENTER CODE 0000 is displayed.
2. Press <3> and <Flush> simultaneously and release. 3. Enter 1515 and confirm with E .
? The message ENTER CODE 0000 is displayed. 4. Select "INPUTS TEST" with o u and confirm with
3. Enter 1515 and confirm with E . E .
4. Select "DISPLAY TEST" with o u and confirm
with E . i Return with <Stop>.

i Return with <Stop> ? In order, the screen shows:


$ Weight of the internal refrigerant cylinder
i All display pixels, followed by the LED displays, are $ Weight of the fresh oil bottle (not used)
activated in sequence to ensure that they function $ Weight o the used oil bottle (not used)
properly. $ Pressure sensor value

14.2 Outputs i The values measured by the scales are absolute


values, that means the real weight on the scales.
! During this process, parts of the refrigerant circuit
are opened that may be pressurized. Therefore, 14.4 Printer
make sure beforehand that the pressure has been
drained from the refrigerant circuit (see section i This function starts a short test print.
10.1).
! Heed the ACS 810 menu prompting.
! Follow the additional ACS 810 menu prompting.
1. Call up start screen.
1. Call up the start screen. 2. Press <3> and <Flush> simultaneously and release.
2. Press <3> and <Flush> simultaneously and release. ? The message ENTER CODE 0000 is displayed.
? The message ENTER CODE 0000 is displayed. 3. Enter 1515 and confirm with E .
3. Enter 1515 and confirm with E . 4. Select "PRINTER TEST " with o u and confirm
4. Select "OUTPUTS TEST" with o u and confirm with E .
with E .
i Return with <Stop>.
i Return with <Stop>

i As soon as the outputs function test has been


called up, the compressor starts.

5. Press E to actuate the components in turn.


? The values switch in the following order:
Compressor
Vacuum pump
Solenoid valve EV1 - EV2 (EV2 not used)
Solenoid valve EV3 - EV4 (EV4 not used)
Solenoid valve EV5
Solenoid valve EV6
Solenoid valve EV7
Solenoid valve EV8
Solenoid valve EV9 (refrigerant pump)
Solenoid valve EV10 (by-pass solenoid valve
for refrigerant pump)

i Return with <Stop>.

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 34 | ACS 810 | Component test

14.5 Counter 14.7 Draining oil


Displays the following information:
$ Prepared refrigerant i This function opens the solenoid valve EV7 and
$ ACS 810 operating hours, drains the pressure in the compressor. This enables
$ Vacuum pump operating hours the solenoid valve EV7 to be serviced.

i This function displays the total number of ! Follow the additional ACS 810 menu prompting.
operations performed with the ACS 810 since
initial commissioning. 1. Call up the start screen.
2. Press <3> and <Flush> simultaneously and release.
! Follow the additional ACS 810 menu prompting. ? The message ENTER CODE 0000 is displayed.
3. Enter 1515 and confirm with E .
1. Call up start screen. 4. Select "OIL DRAIN PROGRESS " with o u and
2. Press <3> and <Flush> simultaneously and release. confirm with E .
? The message ENTER CODE 0000 is displayed.
3. Enter 1515 and confirm with E . i Return with <Stop>.
4. Select "COUNTERS " with o u and confirm with E .
? EV7 appears on the display.
i Return with <Stop>. $ Select <MENU> to open EV7.
$ Leave EV7 open until there is no more pressure
in the compressor.
14.6 Service printout $ Select <STOP> to close EV7 and perform the
maintenance tasks on the solenoid valve.
i This function allows you to print out a service
report containing important information about the
A/C services carried out.

! Follow the additional ACS 810 menu prompting.

1. Call up the start screen.


2. Press <3> and <Flush> simultaneously and release.
? The message ENTER CODE 0000 is displayed.
3. Enter 1515 and confirm with E .
4. Select "SERVICE PRINTING " with o u and
confirm with E .

i Return with <Stop>.

? The following data appears in the service print-


out:
$ Total quantity of refrigerant recovered
$ Vacuum pump operating hours
$ Scale adjustment date for internal refrigerant
cylinder
$ Fresh oil scale adjustment date (not used)
$ Used oil scale adjustment date (not used)

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Changing basic settings | ACS 810 | 35 | en

15. Changing basic settings 1. Call up the start screen.


2. Press <3> and <Flush> simultaneously and release.
i The set values guarantee that the ACS 810 will ? The message ENTER CODE 0000 is displayed.
function perfectly. These parameters may only be 3. Enter 5599 and confirm with E .
changed by an A/C service unit engineer and after 4. Select the relevant parameter with o u and
approval from the manufacturer. confirm with E .

! Follow the additional ACS 810 menu prompting. i Return with <Stop>.

Parameter Actions Default Parameter Actions Default


P1 System pressure empty. 1700 T16 Maximum time for the flushing 15
Absolute pressure value above which process.
recovery begins. If this time is exceeded, the function is
P2 Pressure at end of recovery. 600 ended and the process continues.
Absolute pressure value above which T20 Vacuum test time for flushing 120
recovery ends. operation.
P3 Vacuum test pressure. 300 Time in seconds for the vacuum test
Absolute pressure value after which duration in the flushing function.
the vacuum test turns out to be T21 EV7 oil outlet open duration. 240
negative. Time in seconds for which the solenoid
T1 Vacuum pump oil change threshold. 30 valve EV7 remains open during the oil
Number of hours before a prompt to outlet function.
change the vacuum pump oil appears W1 Combo filter replacement threshold. 150
on the display. Value in kilograms before a prompt to
T2 Time for automatic emptying. 140 replace the combo filter appears on
Value in seconds for duration of the display.
automatic emptying. W6 Max. capacity of small bottle. 10000
T3 Maximum time for recovery. 120 Value in grams that represents the
If this time is exceeded, the function maximum quantity for filling the small
is aborted and the message "LONG internal refrigerant cylinder.
EXTRACTION TIME" appears on the W8 Max. capacity of large bottle. 35000
display. Value in grams that represents the
T4 Weight variation monitoring threshold 60 maximum quantity for filling the large
Time in seconds in which the weight internal refrigerant cylinder.
(recovered quantity) must change HOSE Minimum time for cleaning the service 90
during recovery, otherwise the CLEANING hoses. This is the minimum value in
operation is aborted. TIME seconds for emptying the service hoses
T5 Oil outlet time. Time in minutes for the 5 after filling.
oil drainage duration. CONTROL Activates and deactivates the "Save 0 (off)
T7 Specified time for vacuum. The 60 REPORT data via ACUSB PC interface" function.
mean time recommended by car COMPEN- Activates and deactivates the 0 (off)
manufacturers is 20 minutes. SATION "Compensation at 0 in filling phase"
T8 Not used. – AT 0 function (i.e. compensation is
deactivated).
T9 Vacuum test duration. 300
Time for checking any pressure BYPASS Activates and deactivates the "Bypass" 0 (off)
increase after the vacuum function has function. If this function is activated,
been executed. the MENU key skips the waiting times
for the main ACS 810 functions.
T10 Recycling plus vacuum time. 10000
Time in minutes for the duration of the ECOLD Konfiguration Leiterplatte. 1
recycling plus vacuum function. 2006 Wert muss "1" betragen.
T13 Maximum time for the filling process. 50 RENAULT Mode required by Renault. 0 (off)
If this time is exceeded, the function CONFIG The times between two recoveries are
is aborted and the message "FILLING extended. This mode can be activated
INCOMPLETE" appears on the display. or deactivated as required
BACKUP See section "Data Backup". –

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 36 | ACS 810 | Software

16. Software ! Do not use the PS2 stick with the new software
version, as the stick is cleared before the data
16.1 Vehicle database backup.

i The vehicle database can be updated annually 6. Insert PS2 stick.


using a PS2 stick. Further information can be 7. Confirm that any data on the stick will be deleted.
obtained from customer service. 8. After the backup, remove the stick.
" The data is saved.
! Do not switch off ACS 810 during update process.
16.3 Software update
! Follow the additional ACS 810 menu prompting.
i The software is updated using a PS2 stick. Before
1. Call up the start screen. updating, perform a data backup (see section 16.2)
2. Press <3> and <Flush> simultaneously and release. so that the calibration data and settings for the
? The message ENTER CODE 0000 is displayed. ACS 810 will not be lost.
3. Enter 2222 and confirm with E .
4. Select "DATABASE UPDATE" with o u and 1. Turn off the ACS 810.
confirm with E . 2. Insert the "System Software" PS2 stick.
? INSERT THE KEY is displayed. 3. Press and hold the <MENU> key.
5. Remove plastic cover (input PS2 stick) between 4. Turn on the ACS 810 and release the <MENU> key.
menu key and stop key. 5. The ACS 810 turns itself off after programming.
6. Insert PS2 stick. 6. Remove the PS2 stick.
7. Activate or deactivate with o u and confirm with 7. Turn on the ACS 810.
E.
? The update is performed. 16.4 Loading a data backup
" Data base is updated.
i The calibration data previously saved (section 16.2)
i Return with <Stop>. can be reinstalled after the software update.

16.2 Data backup 1. Turn off the ACS 810.


2. Insert the "Data Backup" PS2 stick.
i This function enables you to save ACS 810 3. Press and hold the <MENU> key.
configuration data before a software update. A data 4. Turn on the ACS 810 and release the <MENU> key.
backup avoids the need to recalibrate the ACS 810 5. After recovery of the data, remove the PS2 stick
after a software update. and attach the plastic cover.
6. Check the calibration data.
! Do not turn off the ACS 810 while saving.

! Follow the additional ACS 810 menu prompting.

1. Call up the start screen.


2. Press <3> and <Flush> simultaneously and release.
? The message ENTER CODE 0000 is displayed.
3. Enter 5599 and confirm with E .
4. Select "BACKUP" with o u and confirm with E
.
? INSERT THE KEY is displayed.
5. Remove plastic cover (input PS2 stick) between
menu key and stop key.

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Circuit diagram | ACS 810 | 37 | en

17. Circuit diagram


17.1 Control PCB

Fig. 7: Control PCB

Fig. 8: Control PCB

Robert Bosch GmbH 1 689 975 253 | 2021-01-26


en | 38 | ACS 810 | Circuit diagram

17.2 Computer printed circuit board

9
CPU

1
8

TANK
CPU-1

PRN
IN OIL
7 4
PROGRAM

OUT OIL PRESSURE

6
5
RS-232

Fig. 9: Computer printed circuit board


1 Internal refrigerant scale connection
2 Printer power supply connection
3 Not used
4 Not used
5 Pressure sensor connection
6 Internal printer connection
7 Programming connection
8 Not used
9 Control PCB connection (supply PCB)

1 689 975 253 | 2021-01-26 Robert Bosch GmbH


Robert Bosch GmbH
Automotive Service Solutions
Franz-Oechsle-Straße 4 www.boschaftermarket.com
73207 Plochingen
DEUTSCHLAND
bosch.prueftechnik@bosch.com

http://www.downloads.bosch-automotive.com

1 689 975 253 | 2021-01-26

You might also like