Professional Documents
Culture Documents
en Repair instruction
A/C Service Unit
en 2 | ACS 511 |
Contents 9. Troubleshooting 23
9.1 Service messages 23
1. Symbols used 3 9.2 Fault messages 23
1.1 In the documentation 3
1.1.1 Warning notices - 10. Emptying the ACS 511 24
Structure and meaning 3 10.1 Automatic emptying 24
1.1.2 Symbols in this documentation 3 10.2 Extraction of internal refrigerant circuit with sec-
1.2 On the product 3 ond A/C service unit 24
RR ACS 511 must be connected to a properly grounded Pressure switch Switches the compressor off if the normal
operating pressure is exceeded.
electrical connection.
Safety valve The safety valve opens if the design pres-
RR The vehicle A/C service using the ACS 511 must be sure is exceeded.
prepared and implemented such that the vehicle Fuse Interrupts the power supply to ACS 511 in
air conditioning system circuit does not have to be the event of too high current.
opened (for example by removing the radiator or Vents The ACS 511 is provided with vents in the
bottom of the housing to ensure the ex-
engine).
change of air even when switched off.
RR Never remove any components from inside the
ACS 511 except for maintenance or repair purposes.
RR If damage to the ACS 511 is established, terminate
usage immediately and contact customer service.
RR The service hoses and quick-release couplings must
be regularly checked for wear and replaced if dam-
aged.
5. Description of unit
5.1 ACS 511
5 7
4
6
3 6
7 1
2
2
1
8
3
9
10
4
11
5
12
5.2 Display and control panel 5.3 Selection and function keys
Keys Name Operation
The high and low pressure gages show the current pres-
sure during the air conditioning service on the vehicle. Stop Cancel and return.
The small pressure gage is used to monitor the internal
cylinder pressure.
Various functions are assigned to the MENU function
The selection and function keys on the control panel key in the ACS 511 software. The functions of the keys
are used to control the menus and the service phases. are defined in the menu bar of the ACS 511 software.
Bosch supplies a PS2 stick for updating the ACS 511 5.4 Input keys
software. If required, the PS2 stick can be inserted in The input keys can be used to enter letters, numbers
the PS2 stick port to update the firmware/software. and special characters in the input boxes.
6.2 Settings
Input Menu <VACUUM>
6.3 Repair
6.8 Flushing (optional)
Input Menu
CHANGE FILTER Input Menu
CHANGE OIL SET VACUUM TIME
1. + <3>
2. Enter 5555.
3. Confirm with E.
<Flush>
6.5 Menu
Input Menu 1 Menu 2
PERFORMANCE TESTS
DIAGNOSTIC
TANK FILLING
<Menu>
TANK RECYCLING
ZEROING OIL SCALES
REPORT MANAGEMENT PRINT REPORT
EXPORT DATA
DELETE DATA
7. Hydraulics diagram
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13
8. Service phases iiThe combo filter (F2) cleans the extracted refriger-
ant of suspended particles and moisture.
iiThis section describes all of the ACS 511 service
phases. In addition, it explains the hydraulic and iiIn the evaporator/oil separator (5), the oil taken in
electric circuits by presenting the hydraulic diagram from the compressor is separated from the refriger-
and providing a brief description of the components ant and fed back to the compressor.
involved in each function.
iiIf the pressure at sensor P1 falls below the value
8.1 Recovery saved in the software, the function stops automati-
cally, the program waits 5 minutes for a pressure
iiIn this service phase, the refrigerant is extracted increase and, if necessary, restarts with a second
from the vehicle air conditioning system. recovery cycle.
1. The ACS 511 is connected to the vehicle with the At the end of this phase, the solenoid valves EV10, EV3
service hoses T1 and T2. and EV5 are closed and the compressor 6 is turned off.
2. Open the service quick-release coupling valves.
?? The pressure on the high and low pressure side of
the vehicle air conditioning system is indicated on
the pressure gages M1 and M2.
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
8.2 Draining oil into the used oil bottle The used oil bottle scales (13) weigh the drained used
At the end of recovery, the solenoid valve EV7 opens oil and ACS 511 saves the value for fresh oil filling in
and the oil previously separated out in the evaporator/ automatic mode.
oil separator (4) drains into the used oil bottle (9).
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
8.3 Vacuum phase and recycling iiIf the pressure in the vehicle air conditioning system
(simultaneous) is below the set value, the vehicle air conditioning
system is empty and the ACS 511 starts vacuum
iiDuring vacuum generation in the vehicle air condi- generation.
tioning system, the refrigerant is prepared in the
internal refrigerant cylinder to remove the non-con- iiIf the pressure is above the set value, there is still re-
densing gases before filling and to filter the refriger- frigerant in the vehicle air conditioning system, and
ant. it must be extracted before vacuum generation.
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
8.4 Leak test iiIf the pressure at P 1 falls below the value saved in
the software during the leak test, an error message
iiThe leak test starts after the vacuum phase. is displayed.
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
8.6 Fresh oil filling iiIf "Fresh oil filling" has been selected in the service
process, the quantity of fresh oil entered is fed into
iiBy default, individual service phases are linked to the vehicle air conditioning system along with the
other service phases as they are needed to fully per- refrigerant.
form the individual operation selected.
iiThe filling quantity is checked by the scales (12),
iiOil from the fresh oil bottle is used to top up the which ends the filling process after the quantity pre-
vehicle air conditioning system compressor oil. viously entered in the service process.
iiEV8 opens and the fresh oil (1) is fed into the vehicle
M2 air conditioning system with the refrigerant.
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
8.7 UV contrast medium filling iiIf "UV contrast medium filling" has been selected in
the service process, a defined quantity (time con-
iiBy default, individual service phases are linked to trolled) entered is fed into the vehicle air condition-
other service phases as they are needed to fully per- ing system along with the refrigerant.
form the individual operation selected.
iiEV9 opens and the UV contrast medium (11) is fed
iiThe vehicle air conditioning system is partly filled into the vehicle air conditioning system with the
with UV contrast medium to facilitate detection of refrigerant.
leaks in the event of damage to the vehicle air condi-
tioning system.
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
8.9 Separating and returning compressor iiThis oil is separated from the refrigerant in the com-
oil pressor oil separator (5) and is then fed back to the
compressor (6).
iiDuring the recovery phase and preparation of the
refrigerant, small quantities of compressor oil get
into the internal circuit.
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
8.10 Non-condensing gases iiThe pressure of the internal refrigerant cylinder in-
creases during the recovery phase and when prepar-
iiThe drain valve (V5) for non-condensing gases opens ing the refrigerant.
if the pressure in the refrigerant cylinder is higher
than the set opening pressure (normally between 12 iiThe safety valve (V 6) opens at a factory set pressure
and 14 bar). (approx. 20 bar) to limit the pressure in the internal
refrigerant cylinder.
M2
HIGH
T2
EV3
M1 EV10
LOW EV5 EV6
T1 P1 EV9 EV8 EV1
VU3 VU1 2
M3
11 1 P
12
P2 3 F1
HP
V5 V6
VU2
F2 5
4
V1 V3 V4 V2
10
EV7
6 7
9
C 13 active
9. Troubleshooting
9.1 Service messages
Service message Actions
CHANGE OIL Change vacuum pump oil.
REPLACE FILTER Replace combo filter
(see section 7.3)
10. Emptying the ACS 511 10.2 Extraction of internal refrigerant cir-
cuit with second A/C service unit
!!When repairing internal components, we recommend
extracting the internal hoses on the ACS 511 to iiIf recovery cannot be performed due to a defective
ensure that no refrigerant can escape when the hose compressor, a second A/C service unit or an external
lines are opened. compressor is required to remove the refrigerant
from the internal refrigerant circuit. To do this, start
iiThis extraction is carried out by automatic emptying the "Recycle" function to open the corresponding
or, if there is a technical defect, by using a second solenoid valves.
A/C service unit.
iiThe compressor power supply for the ACS 511 must
Warning – Risk of frostbite from escaping be disconnected before extraction.
refrigerant
Refrigerant causes severe frostbite on the 1. Close shutoff valves V1, V3, V2, and V4 on the re-
skin. frigerant cylinder and disconnect the blue and red
¶¶ Check the service hoses for damage. hoses from the refrigerant cylinder.
¶¶ Firmly connect the service quick-release 2. Connect the blue hose to the low pressure side of
couplings to the service hoses. the second A/C service unit.
¶¶ Wear safety goggles. 3. Connect the red hose to the high pressure side of
¶¶ Wear protective gloves. the second A/C service unit.
4. Open the valves V1 and V2.
10.1 Automatic emptying 5. Open both valves on the second A/C service unit and
recover the refrigerant from the first, defective A/C
iiRefrigerant in the internal hoses is extracted into the service unit.
internal refrigerant cylinder. ?? A pressure increase test is performed at the end
of recovery.
1. Service hoses (T1, T2) are not connected to the 6. Close the two valves on the second A/C service
vehicle. unit and disconnect the hoses from the refrigerant
2. Close service quick-release couplings. cylinder.
3. Open HP and LP valves on the ACS 511. ""Repairs can be performed.
4. Start recovery.
""Automatic emptying is performed.
11. TROUBLESHOOTING AND If the pressure at the pressure gages falls slowly:
ANALYSIS 1. Check filter (F 1).
If clogged, clean with compressed air (blow out).
2. Check function of valve VU2.
iiThis section briefly describes the various faults, and 3. Valves V1 and V3 must be open.
the components that can cause the faults. 4. Check expansion valve (3) with a pressure gage. Op-
erating pressure must be between 2 and 2.3 bar.
!!Before carrying out any service intervention, re- 5. Check compressor (6).
duce the ACS 511 pressure so that no refrigerant is
released. ACS 511 ends the recovery phase but the pressure at
the pressure gages does not change.
11.1 Faults during recovery 1. Valves V1, V2, V3, and V4 must be open.
11.1.1 Compressor starts 2. HP and LP valves must be open.
3. Check that pressure sensor (P1) functions properly.
iiEV3 and EV5 are closed for automatic self-cleaning.
The pressure at the pressure gages may not change. 11.1.2 Compressor does not start
1. Check fuses F 2 and F 3 (T 12.5 A) on control PCB.
1. Service hoses (T1, T2) are not connected to the 2. Check whether 12 Volt (DC) is applied at the com-
vehicle. pressor relay coil.
2. Close service quick-release couplings. 3. Check whether the compressor relay trips after
3. Open HP and LP valves on the ACS 511. pressing the recovery key. It may be necessary to
replace the keypad or the control card.
iiIf the pressure at the pressure gages decreases dur- 4. Check whether 230 Volt is applied at the compressor
ing self cleaning, check whether EV3 and EV5 are relay output pins.
supplied with power. ?? If no voltage is applied, the computer PCB is de-
fective and must be replaced.
Power applied: ?? If voltage is applied, the current consumption
?? Computer PCB (control PCB) defective. must be measured.
""Replace computer PCB (control PCB). 5. Measure current consumption. At 0 A or >=6 A the
compressor must be replaced.
No voltage applied:
?? Solenoid valve leaking.
""Clean or replace solenoid valve.
Power applied:
?? Solenoid valve defective.
""Clean or replace solenoid valve.
No voltage applied:
?? Computer PCB (control PCB) defective.
""Replace computer PCB (control PCB).
11.1.3 Fault messages that can occur during recovery 11.2 Faults during the vacuum phase
11.2.1 The vacuum pump starts
"CYLINDER FULL"
iiThe vacuum pump starts but no vacuum is generated
iiCheck the weight of the internal refrigerant cylinder in the vehicle air conditioning system
and reduce the quantity of refrigerant in the internal
refrigerant cylinder. 1. Disconnect service hoses from vehicle.
2. Open HP and LP valves.
"PRESSURE VALVE TOO HIGH" 3. Check whether the hose connected to the vacuum
1. Valves V1, V2, V3, and V4 must be open. pump is correctly connected at both ends and is not
2. Check contacts for pressure switch (P2). clogged.
4. Check the oil level in the vacuum pump.
iiIf the pressure is below 14.5 bar, voltage must be
present between pin 1 and pin 2, while pin 1 and iiThe oil level should be in the middle of the sight
pin 4 are open. glass between the "full" and "empty" marks.
iiIf the pressure is above 14,5 bar, the contacts 5. Check the pump vacuum output (the pressure must
between pin 1 and pin 2 open, while the pin 1 and fall to less than 0.05 mbar within 3 minutes).
pin 4 contacts close. 6. If a vacuum of less than 0.05 bar is reached:
Check whether voltage is present at EV1 and EV10.
?? If the pressure switch (P2) does not work in this 7. Valves EV8 and EV9 must not leak.
way, replace it. 8. Check whether EV1 switches
?? If the pressure switch is working correctly, check ?? If voltage is present and EV1 switches, replace the
the wiring and the control PCB. vacuum pump.
¶¶ Check the pump vacuum output (the pressure must
iiIf no fault can be identified with the pressure switch fall to less than 0.05 mbar within 3 minutes).
(P2), the line to the internal refrigerant cylinder
must be checked for clogging and the valve VU2 for 11.2.2 The vacuum pump does not start
clear passage. 1. Check the oil level in the vacuum pump.
2. Check whether the vacuum pump is turned on (on/
off switch on the rear of the vacuum pump).
11.1.4 Other fault messages 3. Check fuses F 2 and F 3 (12.5 A) on the control PCB.
Please see chapter 8.2 4. Check whether the relay trips after pressing the
vacuum key.
5. Check whether the vacuum pump is being supplied
with power (230 Volt).
11.2.3 Fault message that can occur during the vacu- 11.5 Faults during filling with refrigerant
um phase
11.5.1 Vehicle air conditioning system cannot be
"A/C SYSTEM FULL" filled
1. Check hose connections on the internal refrigerant
¶¶ Check the pressure at the pressure gages M 1 and M 2. cylinder.
?? Pressure above 0.3 bar, perform recovery. 2. Valves V1, V2, V3 and V4 must be open.
?? Pressure below 0.3 bar, adjust pressure sensor P 1. 3. HP and LP valves must be open.
""If the message is still displayed, replace the pressure 4. Check the calibration of the scales.
sensor.
""If the message is still displayed, replace the com- iiEnsure that the refrigerant scales are not blocked.
puter PCB.
iiYou must ensure that the control PCB applies the set
11.3 Faults during refrigerant preparation weight value; if not, check whether the refrigerant
cylinder contains sufficient refrigerant for the filling
1. Check hose connections on the internal refrigerant process.
cylinder.
2. Valves V1, V2, V3 and V4 must be open. iiCheck whether EV6 and EV3 are supplied with
3. Check EV7 for leaks. power. If so, they must be replaced. If they are not
4. Check filter F 1 for impurities and clean with com- supplied, the connecting cables and the control PCB
pressed air. must be checked.
5. Check function of valve VU2
6. Check the expansion valve (3) for the correct pres- 11.5.2 Other fault messages
sure value (2 - 2.3 bar). Please see chapter 8.2
7. Check whether the internal refrigerant circuit is
soiled or clogged.
!!The vacuum pump oil must always be changed after To check the pressure switch, carry out the following
10 hours of operation. steps:
1. Close V1 - V4.
Property Value/range
2. Remove the red hose from the internal refrigerant
Operating voltage 230 VAC ± 10 % cylinder and connect the red service hose to the
Frequency 50/60 Hz internal refrigerant cylinder.
Vacuum pump oil filling capacity 250 ml
3. Close both valves on the refrigerant cylinder.
Output 70 l/min.
4. Remove the blue hose from the internal refrigerant
Max. vacuum 0.05 mbar
cylinder and connect a pressure gage using a T-
piece.
To check correct operation of the pump, carry out the 5. Open V4
following steps: 6. Open V1
1. Check the oil level in the vacuum pump. 7. Start the recovery function.
8. As soon as the pressure reaches 14.5 bar, recovery
iiThe oil level should be in the middle of the must be ended, and the message
sight glass between the "full" and "empty" marks. PRESSURE VALUE TOO HIGH is displayed.
9. Drain the pressure into the internal refrigerant cylin-
2. Attach pressure gage to intake connection. der by opening the high pressure valve.
3. Start vacuum generation
""A vacuum of 0.05 mbar must be achieved. iiWhen replacing the pressure switch, a special weight
sealant must be used.
12.2 Pressure sensor P1
1. Check whether a voltage of 24 Volt (DC) is present 12.4 Expansion valve
between pin 1 (-) and pin 2 (+).
iiThe expansion valve is a pressure control valve that
iiIf no voltage is present, check the control PCB and is set to a value between 2 and 2.3 bar and main-
replace if necessary. tains a constant pressure before the oil separator.
2. Check whether an output signal is present between !!The refrigerant cylinder must contain at least 4 kg of
pin 1 (-) and pin 3 (+). refrigerant.
iiThe output signal is between 0 V and 10 Volt, i.e. 1. Connect the low pressure hose to the connection
1.0 Volt corresponds to 1.6 bar. If the pressure gage after the expansion valve using the adapter supplied.
shows 3 bar relative (4 bar absolute), the voltage 2. Close HP and LP valves.
must be 2.5 Volt. 3. Start the recycling function.
""After around 10 minutes, the pressure value must be
iiWhen replacing the pressure sensor, a special thread between 2 and 2.3 bar.
sealant (e.g. Loctite 577) must be used.
12.5 Combo filter iiMake sure the old sealing rings are removed before
12.5.1 Replacement of combo filter attaching the new combo filter.
Warning – Risk of frostbite from escaping !!When installing a new combo filter, make sure that
refrigerant the seals are positioned correctly.
Refrigerant causes severe frostbite on the
skin. !!Take care not to damage any hoses or electrical con-
¶¶ Check the service hoses for damage. nections when replacing the combo filter.
¶¶ Firmly connect the service quick-release
couplings to the service hoses. !!Never re-use an old combo filter.
¶¶ Wear safety goggles.
¶¶ Wear protective gloves. 7. Close the housing.
""The combo filter has been replaced.
iiAfter 50 of refrigerant has been prepared using the
combo filter, the message "CHANGE FILTER" ap- iiReturn with <Stop>.
pears on the display.
iiThe operating instructions recommend having the 12.5.2 Resetting the replacement interval
combo filter replaced by customer service.
!!Follow the additional ACS 511 menu prompting.
!!Follow the additional ACS 511 menu prompting.
1. Call up the start screen.
1. Call up the start screen. 2. Press <3> and <Flush> simultaneously and release.
2. Press <Recovery>. ?? The message ENTER CODE 0000 is displayed.
?? SELECT PORTS? 3. Enter 5555 and confirm with E .
1 HP & LP PORTS 4. Select "CHANGE FILTER" with o u and confirm
2 HP PORT with E .
3 LP PORT ?? The current quantity (in kg) of filtered refrigerant
3. Select <1>,<2> or <3>; confirm with E. is displayed.
""ACS 511 performs a self-cleaning process, then the 5. Press <MENU> until filtered refrigerant quantity is
recovery phase. reset to zero.
""The filter replacement interval is reset.
iiPressure gage must reach 0 bars.
iiReturn with <Stop>.
4. Disconnect the ACS 511 from the power supply.
5. Carefully open the ACS 511 housing.
6. Replace the combo filter.
3
Fig. 5: Vacuum pump
1 Sight glass
2 OIl fill plug
3 Drain plug
13.1 Internal refrigerant cylinder scales iiAccording to the display, the calibration weight must
be entered in ml. However, we recommend enter-
iiDetach the rear panel and remove the refrigerant ing the weight in grams. Because of the density of
cylinder from the scales. 1.0 kg/m³ 250 g corresponds to a value of 250 ml.
iiIt is not necessary to detach the lines from the refrig- 1. Call up the start screen.
erant cylinder. If you want to detach the hoses, close 2. Press <3> and <Flush> simultaneously and release.
the valves on the hoses and on the cylinder. ?? The message ENTER CODE 0000 is displayed.
3. Enter the value 1111 and confirm with E.
1. Call up the start screen. 4. Select "IN OIL CALIBRATION" and confirm with E .
2. Press <3> and <Flush> simultaneously and release. ?? The display shows
?? The message ENTER CODE 0000 is displayed. ZERO CALIBRATION.
3. Enter the value 1111 and confirm with E. 5. Remove the fresh oil bottle
4. Select "TANK CALIBRATION" and confirm with 6. Enter the figure 00.00 and confirm with E.
ENTER. ?? The display shows
?? The display shows WEIGHT CALIBRATION.
ZERO CALIBRATION. 7. Attach the calibrating weight
5. With an empty weighing plate, enter the figure 00.00 8. Enter the calibration weight value and confirm with
and confirm with E . E.
?? The display shows ""The menu containing the functions appears on the
WEIGHT CALIBRATION. display again.
6. Place the calibration weight on the weighing tray (a
value of between 10 kg and 20 kg is recommended). iiReturn with <Stop>.
7. Enter the calibration weight value and confirm with
E. iiThe fresh oil scales can also be calibrated without a
""The menu containing the functions appears on the calibration weight by filling the fresh oil bottle with
display again. oil and entering the exact measured total weight of
the fresh oil bottle.
iiReturn with <Stop>.
13.5 Pressure sensor iiIf the simulator is not available, a simplified adjust-
13.5.1 Checking the adjustment ment can be performed. This process definitely guar-
1. Call up the start screen. antees that the ACS 511 will function perfectly.
2. Press <3> and <Flush> simultaneously and release.
?? The message ENTER CODE 0000 is displayed. 1. Turn on the ACS 511.
3. Enter 1515 and confirm with E . 2. Open the HP and LP valves on the display and con-
4. Select "INPUTS TEST" with o u and confirm with E . trol panel.
?? The absolute values of the scales and of the pres- 3. Start the vacuum function and maintain the vacuum
sure sensor is displayed. in the hoses for 5 minutes (this subjects the pres-
5. Remove the service hoses on the ACS 511 and open sure sensor to a vacuum).
the HP and LP valves on the front panel so that the 4. After 5 minutes, stop the vacuum function and check
pressure sensor is subjected to the atmospheric on the pressure gages that there are no leaks.
pressure. 5. Call up the start screen.
6. Check that the pressure value read is between 0.900 6. Press <3> and <Flush> simultaneously and release.
and 1.100 bar (the typical value is 1.000 bar). ?? The message ENTER CODE 0000 is displayed.
7. Enter 1111 and confirm with E .
13.5.2 Adjusting the pressure sensor 8. Select "PRESSURE CALIBRATION" and confirm
with E .
iiThe pressure sensor is adjusted on the control PCB ?? ZERO CALIBRATION is displayed.
using the simulator, as the pressure sensor has been 9. Enter the value 0.000 on the keypad and confirm
officially calibrated in the factory. with E.
?? WEIGHT CALIBRATION is displayed.
iiPressure sensor 0 bar / 16 bar absolute 10. Detach the service hoses and set the pressure sen-
-1 bar / +15 bar relative. sor to atmospheric pressure.
11. Enter the value 1.000 on the keypad and confirm
1. Disconnect the pressure sensor from the control PCB. with E.
2. Connect the simulator to the control PCB. ?? The menu containing the functions appears on
3. Connect a multimeter to the simulator. the display again.
4. Call up the start screen.
5. Press <3> and <Flush> simultaneously and release. iiReturn with <Stop>.
?? The message ENTER CODE 0000 is displayed.
6. Enter 1111 and confirm with E . 12. Perform the adjustment check described above
7. Select "PRES. CALIBRATION" with o u and con- (see section 12.4.1).
firm with E .
?? ZERO CALIBRATION is displayed.
8. Turn the potentiometer on the simulator until a volt-
age of 0 V is displayed.
9. Enter the value 0.000 on the keypad and confirm
with E.
?? WEIGHT CALIBRATION is displayed.
10. Turn the potentiometer on the simulator until a
voltage of 3.00 V is displayed.
11. Enter the value 4.800 on the keypad and confirm
with E.
?? The menu containing the functions appears on
the display again.
12. Remove the simulator and re-connect the pressure
sensor.
!!Follow the additional ACS 511 menu prompting. 1. Call up the start screen.
2. Press <3> and <Flush> simultaneously and release.
1. Call up the start screen. ?? The message ENTER CODE 0000 is displayed.
2. Press <3> and <Flush> simultaneously and release. 3. Enter 1515 and confirm with E .
?? The message ENTER CODE 0000 is displayed. 4. Select "INPUTS TEST" with o u and confirm with
3. Enter 1515 and confirm with E . E .
4. Select "DISPLAY TEST" with o u and confirm with
E . iiReturn with <Stop>.
14.2 Outputs iiThe values measured by the scales are absolute val-
ues, that means the real weight on the scales.
!!During this process, parts of the refrigerant circuit
are opened that may be pressurized. Therefore, 14.4 Printer
make sure beforehand that the pressure has been
drained from the refrigerant circuit (see section 8.1). iiThis function starts a short test print.
!!Follow the additional ACS 511 menu prompting. !!Heed the ACS 511 menu prompting.
iiThis function displays the total number of operations !!Follow the additional ACS 511 menu prompting.
performed with the ACS 511 since initial commis-
sioning. 1. Call up the start screen.
2. Press <3> and <Flush> simultaneously and release.
!!Follow the additional ACS 511 menu prompting. ?? The message ENTER CODE 0000 is displayed.
3. Enter 1515 and confirm with E .
1. Call up start screen. 4. Select "OIL DRAIN PROGRESS " with o u and
2. Press <3> and <Flush> simultaneously and release. confirm with E .
?? The message ENTER CODE 0000 is displayed.
3. Enter 1515 and confirm with E . iiReturn with <Stop>.
4. Select "COUNTERS " with o u and confirm with E .
?? EV7 appears on the display.
iiReturn with <Stop>. $$ Select <MENU> to open EV7.
$$ Leave EV7 open until there is no more pressure in
the compressor.
14.6 Service printout $$ Select <STOP> to close EV7 and perform the
maintenance tasks on the solenoid valve.
iiThis function allows you to print out a service report
containing important information about the A/C
services carried out.
!!Follow the additional ACS 511 menu prompting. iiReturn with <Stop>.
16. Software !!Do not use the PS2 stick with the new software ver-
sion, as the stick is cleared before the data backup.
16.1 Vehicle database
6. Insert PS2 stick.
iiThe vehicle database can be updated annually using 7. Confirm that any data on the stick will be deleted.
a PS2 stick. Further information can be obtained 8. After the backup, remove the stick.
from customer service. ""The data is saved.
!!Do not switch off ACS 511 during update process. 16.3 Software update
!!Follow the additional ACS 511 menu prompting. iiThe software is updated using a PS2 stick. Before
updating, perform a data backup (see section 13.2)
1. Call up the start screen. so that the calibration data and settings for the
2. Press <3> and <Flush> simultaneously and release. ACS 511 will not be lost.
?? The message ENTER CODE 0000 is displayed.
3. Enter 2222 and confirm with E . 1. Turn off the ACS 511.
4. Select "DATABASE UPDATE" with o u and con- 2. Insert the "System Software" PS2 stick.
firm with E . 3. Press and hold the <MENU> key.
?? INSERT THE KEY is displayed. 4. Turn on the ACS 511 and release the <MENU> key.
5. Remove plastic cover (input PS2 stick) between 5. The ACS 511 turns itself off after programming.
menu key and stop key. 6. Remove the PS2 stick.
6. Insert PS2 stick. 7. Turn on the ACS 511.
7. Activate or deactivate with o u and confirm with E.
?? The update is performed. 16.4 Loading a data backup
""Data base is updated.
iiThe calibration data previously saved (section 14.2)
iiReturn with <Stop>. can be reinstalled after the software update.
1
CPU
TANK
2
8
PRN
3
RS232-B
IN OIL
7 4
PROGRAM
6
5
RS-232