Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
Specifier's comments:
1 Anchor Design
1.1 Input data
Anchor type and diameter: HIT-HY 200-A + HAS-U 8.8 HDG M16
Return period (service life in years): 50
Item number: 2223703 HAS-U 8.8 HDG M16x190 (element) /
434674 HIT-HY 200-A (adhesive)
Effective embedment depth: hef,opti = 80.0 mm (hef,limit = 320.0 mm)
Material: 8.8
Evaluation Service Report: ETA 11/0493
Issued I Valid: 14.12.2020 | -
Proof: Design Method EN 1992-4, Chemical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 15.0 mm
Anchor plate
CBFEM
: lx x ly x t = 250.0 mm x 400.0 mm x 15.0 mm;
CBFEM
- The anchor calculation is based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
Anchor forces are calculated based on a component-based Finite Element Method (CBFEM)
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
N
NEd £ NRd,p = Rk,p EN 1992-4, Table 7.1
gM,p
0 Ap,N
NRk,p = NRk,p · 0
· y g,Np · y s,Np · y re,N · y ec1,Np · y ec2,Np EN 1992-4, Eq. (7.13)
Ap,N
0
NRk,p = y sus · t Rk · p · d · hef EN 1992-4, Eq. (7.14)
y sus =1 EN 1992-4, Eq. (7.14a)
Rk,c
³ 1.00 EN 1992-4, Eq. (7.18)
k3
t Rk,c = · √hef · fck EN 1992-4, Eq. (7.19)
p·d
c
y s,Np = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.20)
ccr,Np £
1
y ec1,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec1,N £
1+ (
scr,Np )
1
y ec2,Np = 1.00 EN 1992-4, Eq. (7.21)
2 · ec2,N £
1+ (
scr,Np )
2 0 2 2 2
Ap,N [mm ] Ap,N [mm ] t Rk,ucr,20 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm] fc,cyl [N/mm ]
213,200 57,600 18.00 240.0 120.0 ∞ 25.00
0
yc t Rk,ucr [N/mm ]
2
k3 t Rk,c [N/mm ]
2
y g,Np y g,Np
1.025 18.45 11.000 9.79 1.000 1.000
Group anchor ID
1-6
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,1 £
1+ (
scr,N )
1
y ec2,N = 1.00 EN 1992-4, Eq. (7.6)
2 · eN,2 £
1+ (
scr,N )
z
y M,N = 2.0 - 1.00 EN 1992-4, Eq. (7.7)
1.5 · hef ³
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
213,200 57,600 120.0 240.0 25.00
Group anchor ID
1-6
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)
0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
62.800 1.000 62.800 1.250 50.240 4.355
V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · min {NRk,c; NRk,p} EN 1992-4, Eq. (7.39c)
0 A
NRk,c = NRk,c · 0c,N · y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)
2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
38,950 57,600 120.0 240.0 2.000 25.00
Group anchor ID
2
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
1.5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)
Steel failure
a a
bN + bV £ 1.0
Concrete failure
1.6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates as per current regulations (ETAG 001/Annex C, EOTA
TR029, etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor
plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above.
The proof if the rigid base plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• Attention! In case of compressive anchor forces a buckling check as well as the proof of the local load transfer into and within the base
material (incl. punching) has to be done separately.
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Bore hole cleaning must be performed according to instructions for use (blow 4 times with the hand pump, brush 4 times, blow again 4 times
with the hand pump).
• Characteristic bond resistances depend on short- and long-term temperatures.
• Edge reinforcement is not required to avoid splitting failure
• The anchor design methods in PROFIS Engineering require rigid anchor plates, as per current regulations (AS 5216:2021, ETAG 001/Annex
C, EOTA TR029 etc.). This means that the anchor plate should be sufficiently rigid to prevent load re-distribution to the anchors due to
elastic/plastic displacements. The user accepts that the anchor plate is considered close to rigid by engineering judgment."
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
Hilti HAS-U threaded rod with HIT-HY 200 injection mortar with 80 mm embedment h_ef, M16, Hot dip galvanized, Hammer drilled installation
per ETA 11/0493
y
125.0 125.0
60.0
5 6
200.0
140.0
3 4
x
140.0
200.0
1 2
60.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
2.2 Summary
Description Profile Anchor plate Welds [%] Concrete [%]
sEd [N/mm²] ePl [%] sEd [N/mm²] ePl [%] Hole bearing
[%]
1 Combination 1 223.60 0.08 236.39 0.66 7 103 81
2 Combination 2 244.49 4.51 257.64 10.77 3 155 192
2.3 Anchor plate classification
Results below are displayed for the decisive load combinations: Combination 2
Anchor tension forces Equivalent rigid anchor plate (CBFEM) Component-based Finite Element Method
(CBFEM) anchor plate design
Anchor 1 67.102 kN 153.397 kN
Anchor 2 67.101 kN 154.373 kN
Anchor 3 23.612 kN 136.758 kN
Anchor 4 23.612 kN 137.878 kN
Anchor 5 -0.007 kN 4.996 kN
Anchor 6 -0.007 kN 5.201 kN
User accepted to consider the selected anchor plate as rigid by his/her engineering judgement. This means the anchor design guidelines can
be applied.
2.4 Profile/Stiffeners/Plate
Profile and stiffeners are verified at the level of the steel to concrete connection. The connection design does not replace the steel design for
critical cross sections, which should be performed outside of PROFIS Engineering.
Results
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
Part Load Material sEd [N/mm²] ePl [%] fy [N/mm²] gM0 fy/gM0 elim [%] Status
combination [N/mm²]
Plate Combination S 235 257.64 10.77 235.00 1.00 235.00 5.00 NOT OK
2
Profile Combination S 235 237.58 1.23 235.00 1.00 235.00 5.00 OK
2
Profile Combination S 235 244.49 4.51 235.00 1.00 235.00 5.00 OK
2
Profile Combination S 235 242.53 3.58 235.00 1.00 235.00 5.00 OK
2
Profile Combination S 235 241.33 3.01 235.00 1.00 235.00 5.00 OK
2
235.00 N/mm²
0.00 N/mm²
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
5.00%
0.00%
2.4.2 Hole bearing
Decisive load combination: 2 - Combination 2
Plate hole bearing resistance, EN1993-1 - 8 section 3.6.1:
Equations
k1 ab fu d t
Fb,Rd =
gM2
VEd
Utilization =
Fb,Rd
Variables
k1 ab fu [N/mm²] d [mm] t [mm] gM2
Anchor 1 2.50 0.92 360.00 16.0 15.0 1.25
Anchor 2 2.50 1.00 360.00 16.0 15.0 1.25
Anchor 3 2.50 0.76 360.00 16.0 15.0 1.25
Anchor 4 2.50 0.98 360.00 16.0 15.0 1.25
Anchor 5 2.50 1.00 360.00 16.0 15.0 1.25
Anchor 6 2.50 1.00 360.00 16.0 15.0 1.25
Results
VEd [kN] Fb,Rd [kN] Utilization [%] Status
Anchor 1 4.320 159.402 3 OK
Anchor 2 4.356 172.800 3 OK
Anchor 3 1.588 131.274 2 OK
Anchor 4 2.025 168.850 2 OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 12
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
2.5 Welds
Profiles are modeled without taking the corner radius into account. Special rules for welding (e.g. for cold-formed profiles ...) are not taken into
account by the software.
Equations
Results
Edge sw,Ed [N/mm²] sw,Rd [N/mm²] s┴,Rd [N/mm²] Utilization [%] Utilizationc [%] Status
Member 1-tfl 1 466.22 360.00 259.20 130 118 NOT OK
Member 1-bfl 1 556.68 360.00 259.20 155 151 NOT OK
Member 1-w 1 501.32 360.00 259.20 140 113 NOT OK
Member 1-w 2 500.19 360.00 259.20 139 113 NOT OK
2.6 Concrete
Decisive load combination: 2 - Combination 2
According to EN1992-1-1 section 6.7(4), the concrete should have sufficient reinforcement to take into account the tensile forces that develop
due to the fixture attachment. The definition of the reinforcement in the concrete is out of scope of PROFIS Engineering.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
12
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 13
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
0.00 N/mm²
2.6.2 Verification of compression in concrete under the anchor plate around the profile as per EN1992-1 section 6.7 and EN1993-1-8,
section 6.2.5
Equations
fjd
bj kj acc fck
=
gc
N
s = Aeff
Utilization =
s
fjd
Variables
N [kN] Aeff [mm²] bj kj acc fck [N/mm²] gc
678.562 10,581 0.67 3.00 1.00 25.00 1.50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
13
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 14
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
Results
s [N/mm²] fjd [N/mm²] Utilization [%] Status
64.13 33.50 192 NOT OK
2.8 Warnings
● By using the CBFEM calculation functionality of PROFIS Engineering you may act outside the applicable design codes and your specified
anchor plate may not behave rigid. Please, validate the results with a professional designer and/or structural engineer to ensure suitability
and adequacy for your specific jurisdiction and project requirements.
● The anchor is modeled considering stiffness values determined from load displacement curves tested in an independent laboratory.
Please note that no simple replacement of the anchor is possible as the anchor stiffness has a major impact on the load distribution
results.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
14
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 15
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
3 Summary of results
Design of the anchor plate, anchor, welds and other elements are based on CBFEM (component based finite element method) and Eurocode
regulations.
Load combination Max. utilization Status
Anchors Combination 2 558% NOT OK
Anchor plate Combination 2 110% NOT OK
Welds Combination 2 155% NOT OK
Concrete Combination 2 192% NOT OK
Profile Combination 2 100% OK
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
15
Hilti PROFIS Engineering 3.0.73
www.hilti.co.il
Company: Page: 16
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Copy - Anchos for sign Hayfa harbor - no stiffeners 2 Date: 2.11.2021
Fastening point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
16