(Hybrid Solution )
Cabinets overview
3 12 November 2019
PC 1000 - ICC 330 H1 C4
• Battery Branch > 2 ×250 A Fuse
• LLVD Branch 2 ×80 A MCB, 2 ×63A MCB (LLVD1)
• BLVD Branch 1 ×63 A MCB, 4 ×32 A MCB, 2 ×16 A MCB (LLVD2)
• AC input (4*25mm) connected to AC panel
• Commissioning switch on auto mode (the system is under automatic control)
• Rectifiers Group ( 7 PSU with power 3000 W for each one and
• DG battery charger with output 12.5 – 14.2 V connected to DG battery
installed in slot 8
• Cabinet dimensions ( 1600 mm x 650 mm x 820 mm)
Battery charger
4
PC 1000 - ICC 330 H1 C4
• GIM board is interference card for:
DG hybrid signal (DG1 port NC and COM (2)
AI 1 to detect the fuel level (6)
5
PC 1000 - ESC720
• Dimensions >( 2030 mm x 815 mm x 735 mm)
• Max Capacity 8 Lithium modules
• Module Capacity 100 AH
• Contains 4 DC power bus bars
• DC cables size 35 mm from DC bars to ICC on
fuse 250 A
COM_IN
COM_OUT
+ VE
SMU Air Condition Connections
Battery Connections - VE
7
System Cables Connections
8
System Cables Connections
9
Hybrid Activation
• From SMU Site Maintain Pass 000001 Gen Self Check Yes
• After few minutes the result should be succeed if all connection are OK
• Get IP from System Wizard and log into the cabinet via browser (HTTPS:/ cabinet IP ) and check configuration
• We should make sure that the firmware is upgraded(the same view for inserted PS’S)
admin
Changeme
10
Check The Software Version
12
Management Configuration
13
DOD and Max Charge time
14
Total and remaining capacity check
16
Fuel Sensor Parameters
• We should test below alarms from the site and check TT as usual :
DG start failure – DG stop failure – DG abnormal start – DG abnormal stop
Rectifier communication failure - Load fuse break-Fan alarm-battery temperature
Li battery Failure - Door alarms – fuel level
23
Alarms simulation
• We must check hybrid operation is OK
• 1st condition DG is ON
Trip DG CB
Cabinet alarmed “Generator abnormal stop or Genset work abnormal ” then clear it after checking
Convert DG on manual mode
Wait till the remaining capacity reach 100% (we can accelerate charging by switching off some LI battery
modules)
Cabinet alarmed >”Generator fail to stop or Genset work abnormal “then clear it by backing DG on auto mode
and switch on all LI batteries
• 2nd condition DG is OFF
Put DG on manual mode
Cabinet alarmed >”Generator abnormal start or Genset work abnormal “ then clear it by backing on auto mode
Trip DG CB or trip
Set DOD 5% or (100 - remaining capacity )
Cabinet alarmed >”Generator fail to start or Genset work
24
abnormal “then clear it and reset DOD to 55%
Mohamed El Zayat