Professional Documents
Culture Documents
Troubleshooting Guide
ERROR 2: NO SOW.......................................................................................................................................................................... 5
GLOSSARY.........................................................................................................................................................................................99
NO APPARENT POWER TO SYSTEM
POSSIBLE CAUSES
2) Power input to DCE control from the plant is not correct (should be 480VAC +/- 10%, 60 cycle, 3-phase).
Or (should be 277VAC +/- 10% in reference to ground).
3) Verify that all power is available to, and inside, the controller. See “Procedure for Power
Verification” in Appendix A.
2
ASSIST MODULE IS NOT POWERED UP
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Fuses F7, F8, F9, or F10 along the upper back wall of the DCE cabinet are bad. See Appendix B Fig. 7. Check all
of these fuses.
NOTE: If fuses F7, F8, or F9 are bad, you will also see that, along with no power to ASSIST
Module, the Feeders are not powered up. Also, be sure you have performed the Note above
concerning the “Procedure for Power Verification” in Appendix A.
3) Check for 120vac on the ASSIST power supply at pins L (black wire) and N (white wire).
a. If you measure 120vac at L and N, the power supply is bad and must be replaced.
b. If 120vac is not measured, check for 120vac at X9 (pins 1 and 2) inside DCE control. Unplug the cable
from X9 inside the DCE control and check pins 1 and 2 on the DCE connector X9 itself.
1. If you measure 120vac at X9 pins 1 and 2, there is a bad 120vac cable between X9 and the
ASSIST module.
2. If you do not read 120vac at X9 pins 1 and 2, see the schematic below to troubleshoot.
120vac to
ASSIST module
480vac to 120vac
step-down
transformer
3
ERROR 1: WELD TOOL REMAINS IN R POSITION
DEFINITION: Weld tool remains in rear position longer than pre-set time after “Start” signal received from
robot/PLC.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
4) Bad head forward/back valve or solenoid on feeder. If valve is equipped with manual actuator, test for functioning
of the valve spool by manually operating the valve.
5) Bad or disconnected valve solenoid cable running from feeder ETF Feeder CPU Board connector X16, through
cable assembly (#55110) to valve pack assembly.
4
ERROR 2: NO SOW
DEFINITION: Stud On Work (SOW) not detected 1200ms after weld tool moves forward to the work piece.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) No stud in collet
a. Check stud level in feeder bowl/rail.
b. Check for broken or worn collet.
c. Check for jam at feeder bowl/escapement.
d. Check for kinked or worn feed tube.
e. Check air supply to system. Should be 80psi.
f. Check “feed time” is programmed correctly in “Weld Parameters”.
g. Piston assembly inside Weld Tool in need of lubrication.
h. Bad Weld Tool Receiver.
2) Depending on the Feeder style, refer to the following: (See Appendix B Fig. 5 to identify your feeder)
a. For ETF12, ETF13, style feeders:
1. Bad fuse F1 on ETF Motor Driver Board. See Appendix B Fig. 3 and 4.
2. Bad ETF Motor Driver Board. See Appendix B Fig. 3 and 4.
3. Bad or misadjusted motors on feeders. See Appendix 4 for motor adjustment locations.
b. For ETF52 style feeders:
1. Bad fuse F1 on ETF Motor Driver Board. See Appendix B Fig. 3 and 4.
2. Bad ETF Motor Driver Board. See Appendix B Fig. 3 and 4.
c. For ETF90 style feeders:
1. Bad Rail Kicker Assembly. See Appendix B Fig. 8.
2. Bad Rail Kicker Assembly air valve/solenoid. See Appendix B Fig. 8.
3. Bad Knife Assembly air cylinder. See Appendix B Fig. 8.
4. Bad Knife Assembly air valve/solenoid. See Appendix B Fig. 8.
3) Weld tool/Gun cannot reach the work piece. Check cable dressing/fixturing.
5
ERROR 3: WELD TOOL NOT IN R POSITION
DEFINITION: Welder Control does not detect that the weld tool is in the rear position.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Low air pressure at feeder. Should be at least 80psi.
4) Bad head forward/back valve or solenoid on feeder. If valve is equipped with manual actuator, test for functioning
of the valve spool by manually operating the valve.
5) Bad or disconnected valve solenoid cable running from feeder ETF Feeder CPU connector X16, through cable
assembly (#55110) to valve pack assembly.
6
ERROR 4: SOW NOT RESET
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
3) Weld tool/gun too close to work surface after weld. Collet or newly fed stud is touching the previously welded
stud.
a. With weld tool in the rear position, re-teach robot so that there is approx. 1.5” between stud and work
surface to allow for proper weld tool travel.
7
ERROR 5: WELD PROCEDURE SEQUENCE FAULT
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
5) Faulty Valve Cable assembly (#55110) that runs from ETF Feeder CPU connection X16 to Valve Pack
assembly.
6) Possible faulty DCE ZCPU Board in DCE cabinet. See Appendix B Fig. 3.
7) Possible faulty Aux. Power Supply Board on inside door of DCE control.
8
ERROR 6: PROGRAM NOT SELECTED
DEFINITION: Welder Control does not detect program bit selection from Robot/PLC.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) The welder control has more than one program active AND the Robot / PLC I/O is not wired up to select program
bits.
a. In this case, check to make sure that only program 1 is active . If you want to weld with more than one
program, you must wire your Robot/PLC I/O for program bit selection.
Program number 1
----------------------------------------
<Options “Crawl”>
If using a Robot / PLC and selecting program bits, you can check the data for the external program setting in the
following manner.
a. Enter a program (bit) 1 via the Robot / PLC interface. The “Program Number” line should now say “1”.
Turn off bit 1 input.
b. Enter the program (bit) 2 via the Robot / PLC interface. The “Program Number” line should now say “2”.
Turn off bit 2 input.
c. Enter the program (bit) 4 via the Robot / PLC interface. The “Program Number” line should now say “4”.
Turn off bit 4 input.
d. Enter the program (bit) 8 via the Robot / PLC interface. The “Program Number” line should now say “8”.
“8”. Turn off bit 8 input.
9
PROGRAM NOT SELECTED (CONT.)
e. Enter the program (bit) 16 via the Robot / PLC interface. The “Program Number” line should now say
“16”. Turn off bit 16 input.
f. Enter the program (bit) 32 via the Robot / PLC interface. The “Program Number” line should now say
“32”. Turn off bit 32 input.
g. Enter the program (bit) 64 via the Robot / PLC interface. The “Program Number” line should now say
“64”. Turn off bit 64 input.
If this does not work correctly, the Robot / PLC interface is incorrectly wired or the I/O cable is defective.
(HAND-GUN OPERATION)
b. For handgun operation, activate Program Number One and ONLY Program Number One of each
Outlet (Weld Tool). Deactivate all other programs using the following procedure
From the “Main Menu”, select “Programming” and press the “Enter” key. Scroll down to the “De/activate
programs” option and press the “Enter” key. Enter the outlet number of the affected outlet and press “Enter” key.
All of the active programs will be highlighted. Using the arrow keys position the arrow cursor in front of program
“2”. Press and hold the “-“ key until the only program highlighted for this outlet is program “1”.
----------------------------------------
Options “Crawl”
10
ERROR 7: PROGRAM NOT ACTIVE
DEFINITION: The program selected by robot/PLC has not been activated in the Welder Control software.
NOTE: FOR HANDGUN OPERATION GO TO STEP 4
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) From the “Main Menu”, select “Programming” and press the “Enter” key. Select the “Weld Parameter”; press
“Enter”. The “Weld Parameter” sub-menu is used to activate programs , enter weld currents, weld times, arc
voltages, tolerances, and other options for up to 127 programs per outlet. At this point, you are on line 1 and need to
specify which outlet (SKK/PK) you want. In this example we will use outlet 1; press “1” and “Enter”. Now select
the program that you want activated; in this example press “1” then “Enter”. Use the up/down arrow keys to select
“Program active” line. Use the “+” key until the “Program active” line says “yes”. Do this for all program
numbers to be used by the Robot/PLC.
WELD PROGRAMMING
----------------------------------------
Outlet: 1 Weld Program: 1
Stud ID……………………….._____________
Program Active………………yes
Start Delay…………………….. 200 ms
Weld Current………………….1300 A
Weld Time………………………..28 ms
Lift / Penetration………………1.20 mm -0.10mm
Optimization…………………….no
• To verify, from the “Main Menu” scroll down to “Status”; press “Enter”. Select “Customer
Interface” line; press “Enter”.
Program number 1
----------------------------------------
<Options “Crawl”>
Continued next page
11
PROGRAM NOT ACTIVE (CONT.)
If using a Robot / PLC and selecting program bits, you can check the data for the external program setting in the
following manner:
a. Enter a program (bit) 1 via the Robot / PLC interface. The “Program Number” line should now say “1”.
Turn off bit 1 input.
b. Enter the program (bit) 2 via the Robot / PLC interface. The “Program Number” line should now say “2”.
Turn off bit 2 input.
c. Enter the program (bit) 4 via the Robot / PLC interface. The “Program Number” line should now say “4”.
Turn off bit 4 input.
d. Enter the program (bit) 8 via the Robot / PLC interface. The “Program Number” line should now say “8”.
“8”. Turn off bit 8 input.
e. Enter the program (bit) 16 via the Robot / PLC interface. The “Program Number” line should now say
“16”. Turn off bit 16 input.
f. Enter the program (bit) 32 via the Robot / PLC interface. The “Program Number” line should now say
“32”. Turn off bit 32 input.
g. Enter the program (bit) 64 via the Robot / PLC interface. The “Program Number” line should now say
“64”. Turn off bit 64 input.
If this does not work correctly, the Robot / PLC interface is incorrectly wired or the I/O cable is defective.
(HAND-GUN OPERATION)
1. For handgun operation, activate Program Number One and ONLY Program Number One. Deactivate all other
programs using the following procedure
From the “Main Menu”, select “Programming” and press the “Enter” key. Scroll down to the “De/activate
programs” option and press the “Enter” key. Enter the outlet number of the affected outlet and press “Enter” key.
All of the active programs will be highlighted. Using the arrow keys position the arrow cursor in front of program
“2”. Press and hold the “-“ key until the only program highlighted for this outlet is program “1”.
----------------------------------------
<Options “Crawl”>
12
ERROR 13: LIFT FAULT
DEFINITION:
1. Flag from ETF that there is an error in the position of the LM as detected by the ETF A1 CPU.
2. ETF did not acknowledge the “lift on” command from the SMPS.
3. SMPS did not measure pilot voltage.
4. ETF did not acknowledge the “lift off” command from the SMPS.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Ensure that the PWM Board polarity jumpers X22 and X23 are in the correct position. Refer to Appendix B,
“Stud Polarity Set-up Procedure”.
2) Faulty weld tool. Replace or repair (refer to weld tool tear-down procedure).
a. Faulty LM motor inside weld tool.
b. Faulty Encoder Board inside weld tool.
c. Faulty wiring inside weld tool.
13
ERROR 14: SHORT CIRCUIT WELD
DEFINITION: Welder Control has not detected that the stud has lifted off of the work piece during the weld.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Faulty weld tool. Replace or repair (refer to weld tool tear-down procedure).
a. Faulty LM motor inside weld tool.
b. Faulty Encoder Board inside weld tool.
c. Faulty wiring inside weld tool.
2) Faulty Multi-cable assembly (cable that runs from feeder to the weld tool).
a. Check Pin A for continuity from end to end.
b. Check Pin B for continuity from end to end.
14
ERROR 15: DROP DOWN TIMEOUT
DEFINITION: The drop down time of the weld tool/gun exceeded 20ms.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
15
ERROR 16: NO ARC, OPEN CIRCUIT
DEFINITION: Arc is extinguished during weld process (either during Pilot Arc or Main Arc phases).
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Movement of work piece during weld process. Check “Start delay” of all active programs; ensure at least 200ms
of “Start Delay” time. Take steps to arrest work piece motion during weld process.
2) Weld tool was removed from the work at the beginning of the weld. Monitor weld tool for movement during weld
process.
3) Lift setting is too high for hand held gun or the weld tool/gun-to-work angle is not at 90 degrees.
7) Defective SMPS.
a. Replace power supply using the “Changing the DCE Power Supply” procedure in Appendix A.
16
ERROR 17: MEASUREMENT LINE BROKEN
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Check PWM Polarity jumpers X22 and X23 for correct setting. Refer to Appendix B Fig. 1 “Stud Polarity Set-
up Procedure”.
1. Feeder Application- inside the DCE control cabinet, disconnect weld power cable and
“measurement line” connection of the affected weld tool. SEE APPENDIX B, FIG. 9 and 10.
a. On the cables use Ohmmeter to verify continuity (0Ω) between the weld power
cable and “Measurement Line” wire.
1. Continuity No?
a. Bad Weld tool. Unplug cables from weld tool and check for
continuity between the Control Cable Connector pin “K” and the Weld
Power Cable Connector on weld tool itself. Should read continuity.
b. Bad Multi-cable package assembly (cable between Feeder and Weld
tool). Replace.
c. Bad “Measurement Line” wire, (wire between DCE cabinet and
Feeder).
d. Bad Weld Power cable (cable between DCE cabinet and Feeder).
e. Bad CPU Board inside Feeder JIC box.
1. Continuity Yes?
a. Faulty PWM in SMPS (Switching Mode Power Supply).
b. Faulty SMPS. Replace power supply using Appendix A “Changing
the DCE Power Supply”.
1. SMB Box (Protective Gas Application ONLY)- inside the DCE control cabinet, disconnect
weld power cable and control cable of the affected weld tool.
(CONTINUED NEXT PAGE)
17
MEASUREMENT LINE BROKEN (CONTINUED)
a. On the cables use Ohmmeter to verify continuity (0Ω) between the weld power-
cable and pin “K” of the control cable.
1. Continuity No?
a. Bad Control Cable (DCE cabinet to SMB Box)
b. Break in SMB Box. Check X2 pin “K” to Multi-cable connection pin
“K”. Should read continuity.
c. Bad Weld tool. Unplug cables from weld tool and check for
continuity between the Control Cable Connector pin “K” and the Weld
Power Cable Connector on weld tool itself. Should read continuity.
d. Bad Multi-cable package assembly (cable between SMB Box and
Weld tool). Replace.
e. Bad Weld Power cable (DCE cabinet to SMB Box).
2. Continuity Yes?
a. Faulty PWM in SMPS (Switching Mode Power Supply).
b. Faulty SMPS. Replace power supply using the “Changing the DCE
Power Supply” procedure in Appendix A.
18
ERROR 18: USER COUNTER MAINTENANCE REQUIRED
DEFINITION: The “User Counter” fault limit for the amount of weld cycles has been reached. This is a user-
defined limit and the user-defined action should be taken. The limit of this counter is customer-
defined and tailored by the customer to the application.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Plug Keypad into the DCE control. From the “Main Menu”, highlight “Maintenance Functions” and press “Enter”.
Highlight the line “Maintenance Statistics” and press “Enter”. At upper right hand corner of “Maintenance
Counters”, enter the number of the affected weld tool and press “Enter”. You will see the following screen:
Number of Welds
___________________________________________________
<Options “Crawl”>
a. Highlight “Reset!” under the “User” column and press the “Enter” key. A banner reading
“Press <ENT> to confirm!”
will be displayed. Press the “Enter” key to confirm and, after a second or two, the line “Act.” under the
column “User” will be reset to a count of “0”.
b. Be sure to take the appropriate user-defined actions that determined the reason for using this counter for
this weld tool.
c. Reset any remaining faults and continue with normal welding operations.
19
ERROR 19: COLLET MAINTENANCE REQUIRED
DEFINITION: The “Collet Maintenance Counter” fault limit for the amount of weld cycles has been reached.
This counter is used to alert the customer that the collet needs to be changed on this weld tool.
The limit of this counter is customer-defined and tailored by the customer to the appl ication.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Plug Keypad into the DCE control. From the “Main Menu”, highlight “Maintenance Functions” and press “Enter”.
Highlight the line “Maintenance Statistics” and press “Enter”. At upper right hand corner of “Maintenance
Counters”, enter the number of the affected weld tool and press “Enter”. You will see the following screen:
Number of Welds
___________________________________________________
<Options “Crawl”>
a. Highlight “Reset!” under the “Collet” column and press the “Enter” key. A banner reading
“Press <ENT> to confirm!”
will be displayed. Press the “Enter” key to confirm and, after a second or two, the line “Act.” under the
column “Collet” will be reset to a count of “0”.
b. Be sure that the collet has been replaced.
c. Reset any remaining faults and continue with normal welding operations.
20
ERROR 20: WELDTOOL MAINTENANCE REQUIRED
DEFINITION: The “Weldtool Maintenance Counter” fault limit for the amount of weld cycles has been
reached. This counter is used to alert the customer that the weld tool needs rebuilding/cleaning.
The limit of this counter is customer-defined and tailored by the customer to the application.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Plug Keypad into the DCE control. From the “Main Menu”, highlight “Maintenance Functions” and press “Enter”.
Highlight the line “Maintenance Statistics” and press “Enter”. At upper right hand corner of “Maintenance
Counters”, enter the number of the affected weld tool and press “Enter”. You will see the following screen:
Number of Welds
___________________________________________________
<Options “Crawl”>
a. Highlight “Reset!” under the “Weldtool” column and press the “Enter” key. A banner reading
“Press <ENT> to confirm!”
will be displayed. Press the “Enter” key to confirm and, after a second or two, the line “Act.” under the
column “Weldtool” will be reset to a count of “0”.
b. Be sure that the weldtool had been rebuilt/cleaned.
c. Reset any remaining faults and continue with normal welding operations.
21
ERROR 22: FEEDTUBE MAINTENANCE REQUIRED
DEFINITION: The “Feedtube Maintenance Counter” fault limit for the amount of weld cycles has been
reached. This counter is used to alert the customer that the feed tube needs inspection/replacement. The
limit of this counter is customer-defined and tailored by the customer to the application.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Plug Keypad into the DCE control. From the “Main Menu”, highlight “Maintenance Functions” and press “Enter”.
Highlight the line “Maintenance Statistics” and press “Enter”. At upper right hand corner of “Maintenance
Counters”, enter the number of the affected weld tool and press “Enter”. You will see the following screen:
Number of Welds
___________________________________________________
<Options “Crawl”>
a. Highlight “Reset!” under the “Feedtube” column and press the “Enter” key. A banner reading
“Press <ENT> to confirm!”
will be displayed. Press the “Enter” key to confirm and, after a second or two, the line “Act.” under the
column “Feedtube” will be reset to a count of “0”.
b. Be sure that the feed tube had been inspected/replaced.
c. Reset any remaining faults and continue with normal welding operations.
22
ERROR 23: HANDGUN SEQUENCE NOT FOLLOWED
DEFINITION: The correct sequence of operation while welding with a handgun was not observed.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. Se e “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) Angularity is misadjusted. Adjust angularity. See Appendix A “PK560 HANDGUN SET-UP (3 STEPS)”.
4) A problem with the Stud on Work detection circuitry, (system not detecting SOW). See “NO SOW” fault Error 2.
NOTE: If desired, you can program the system to weld without regard to Angularity. See the following procedures:
a) Plug Keypad into DCE control. From “Main Menu”, select “Programming” and press “Enter”. Select “Outlet
Programming” and press “Enter”. Select the appropriate Outlet number and press “Enter”.
Outlet Programming
Feeder Programming.<↓>
Highlight the line “Check Stud Length. and use the “plus” and “minus” key to set this line to “no”. Try
welding. If you cannot yet weld, go back up to Step 3.
PK560 manually fed hand guns: next page
23
HAND GUN SEQUENCE NOT FOLLOWED (CONTINUED)
a) Plug Keypad into DCE control. From “Main Menu”, select “Programming”, press “Enter”. Select “Outlet
Programming”, press “Enter”. Select the Outlet number of the PK560 hand gun that you wish to modify,
press “Enter”. You should see the following screen:
Outlet Programming
Angularity.....................no
Maintenance counter.<↓>
b) Highlight the line “Angularity” and use your “plus” and “minus” keys to change this value to “no”. Try
welding.
24
ERROR 25: WRONG STUD LOADED
DEFINITION: The DCE control has identified an incorrect stud loaded into the weld tool. This identification
was made via the lift measuring circuit in the weld tool by checking “pre-load” of stud after
weld tool achieved Stud-On-Work.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Ensure that the correct length stud is loaded in the weld tool and feeder.
2) DCE control is programmed wrong. See Appendix A “Programming Stud Length Detection Weld Head”.
5) Bad Multi-Cable assembly that runs from the Weld Tool to the Feeder.
6) Bad ETF Feeder CPU Board. See Appendix B Fig. 3 and 15.
25
ERROR 26: FEEDER OR STUD DIVIDER FUNCTION FAULT
DEFINITION:
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
26
ERROR 30: WELD OUT OF TOLERANCE
DEFINITION: One or more of the measured weld parameters was outside the pre-programmed tolerance
range:
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
At keypad, hit “ESC” key until “Main Menu” is displayed at the top of the screen. Hit the “F4” key to access the “Weld
Parameter Monitor” screen. Punch in the number of the faulted weld head. The screen now displays the results of the
last weld on the faulted head.
Any highlighted lines on this screen represent an out of tolerance measurement. Refer to the following chart to
troubleshoot the appropriate “Weld Out of Tolerance” value.
VI. PEAK ARC VOLTAGE (see page 35) NOTE: Aluminum Welding ONLY
VII. DROP ARC VOLTAGE (see page 37) NOTE: Aluminum Welding ONLY
27
I. WELD CURRENT
-The actual weld current measured during the weld was found to be outside of the +30 amp or –30 amp fixed tolerance
values.
28
II. WELD TIME
1) Tolerances for “Weld Time” are programmed too tight. From the “Main Menu”, highlight the line “Programming”
and press “Enter”. Highlight “Weld Programming” and press “Enter”. The “Weld Programming” sub-menu is
used to program weld currents, weld times, arc voltages, tolerances, and other options for up to 127 programs per
outlet. At this point, you are on line 1 and need to specify which outlet you want. In this example we will use outlet
1; press “1” and “Enter”. Then select the program you want, in this example we will use program 1; press “1” then
“Enter”. You will see the following screen :
Weld Parameters.<↓>
2) The “Drop Down Time ” has increased causing the weld time to increase.
a. See Error 15: Drop Down Time Out.
29
III. PENTRATION DEPTH
1) Asked for unattainable “Penetration Depth” or tolerances for “Penetration Depth” are programmed too tight. From
the “Main Menu”, highlight the line “Programming” and press “Enter”. Highlight “Weld Programming” and press
“Enter”. The “Weld Programming” sub-menu is used to program weld currents, weld times, arc voltages,
tolerances, and other options for up to 127 programs per outlet. At this point, you are on line 1 and need to specify
which outlet you want. In this example we will use outlet 1; press “1” and “Enter”. Then select the program you
want, in this example we will use program 1; press “1” then “Enter”. You will see the following screen :
Weld Parameters.<↓>
30
IV. ARC VOLTAGE
1) Tolerances for “Pilot Arc” or “Main Arc” are programmed too tight. From the “Main Menu”, highlight the line
“Programming” and press “Enter”. Highlight “Weld Programming” and press “Enter”. The “Weld Programming”
sub-menu is used to program weld currents, weld times, arc voltages, tolerances, and other options for up to 127
programs per outlet. At this point, you are on line 1 and need to specify which outlet you want. In this example we
will use outlet 1; press “1” and “Enter”. Then select the program you want, in this example we will use program 1;
press “1” then “Enter”. You will see the following screen :
Weld Parameters.<↓>
b. If you have poor weld quality you may use the “Optimization”. See “keypad screen” page 1 above:
1. Current – adjusts weld current to compensate for oil.
2. Time – adjusts weld time to compensate for oil.
3. Vdce – adjusts lift height to maintain specific voltage; compensates for oil
31
(ARC VOLTAGE - CONTINUED)
32
V. WELD ENERGY
1) Tolerances for “Weld Energy” is programmed too tight. From the “Main Menu”, highlight the line “Programming”
and press “Enter”. Highlight “Weld Programming” and press “Enter”. The “Weld Programming” sub-menu is
used to program weld currents, weld times, arc voltages, tolerances, and other options for up to 127 programs per
outlet. At this point, you are on line 1 and need to specify which outlet you want. In this example we will use outlet
1; press “1” and “Enter”. Then select the program you want, in this example we will use program 1; press “1” then
“Enter”. You will see the following screen :
Weld Parameters.<↓>
33
(WELD ENERGY - CONTINUED)
NOTE: The calculation for the measured value is: “Energy (J) = Current x Time x Voltage (Vw)”.
Deviations in any of the 3 factors, either singly or in combination, can cause the Energy, measured in Jules (J), to
be out of tolerance.
8) Review the weld to see which of the 3 factors (Current, Time, Voltage) may be contributing to higher or lower than
normal “Weld Energy” readings:
From the “Main Menu”, select “Maintenance Functions” and press “Enter”. Select the “WOP
Memory” and press “Enter”. Punch in the number of the affected Outlet, press “Enter”. The
following screen will be displayed (this is an example page):
Use the <↑> and <↓> arrow keys to “page” through the recorded WOPs until you see the WOP
caused by Energy. You will know this by the highlighted line “Enj”. Examine the column “Act” for
lines, “Vw”, “Iw”, and “tw” to see what may be contributing to the high or low “Enj” reading.
In the example above, both Iw and tw are higher than normal though both are in tolerance. However,
when plugged into the equation:
a. Review the values that apply and in the relevant cases do the following:
a. For higher or lower “Vw” (Main Arc Voltages): See “Arc Voltage” Step 2.
b. For higher or lower “Iw” (Main Arc Current): See “Weld Current” Step 1.
c. For higher or lower “tw” (Weld Time): See “Drop Down Timeout”.
34
VI. PEAK ARC VOLTAGE
1) Tolerance for “Peak Arc Voltage” is programmed too tight. From the “Main Menu”, highlight the line
“Programming” and press “Enter”. Highlight “Weld Programming” and press “Enter”. The “Weld Programming”
sub-menu is used to program weld currents, weld times, arc voltages, tolerances, and other options for up to 127
programs per outlet. At this point, you are on line 1 and need to specify which outlet you want. In this example we
will use outlet 1; press “1” then “Enter”. Then select the program you want, in this example we will use program 1;
press “1” then “Enter”. You will see the following screen :
Monitored Parameters.<↓>
Weld Parameters.<↓>
Select the line “Varc Peak Detect”. Adjust the tolerance for “Varc Peak Detect” as necessary by
highlighting the value on this line and use the “plus” and “minus” keys to change the value. The
actual tolerance entered will depend on the application and should always be set to a range that is
consistent with maintaining good welds.
b. If you have poor weld quality you may use the “Optimization”. See “keypad screen” page 1 above:
1. Current – adjusts weld current to compensate for oil.
2. Time – adjusts weld time to compensate for oil.
3. Vdce – adjusts lift height to maintain specific voltage; compensates for oil.
35
(PEAK ARC VOLTAGE - CONTINUED)
3) PWM Board is defective.
a. Replace PWM Board using Appendix B Fig. 1 “Stud Polarity Setup Procedure” to make certain you use
proper polarity.
36
VII. DROP ARC VOLTAGE
1) Tolerance for “Drop Arc Voltage” is programmed too tight. From the “Main Menu”, highlight the line
“Programming” and press “Enter”. Highlight “Weld Programming” and press “Enter”. The “Weld Programming”
sub-menu is used to program weld currents, weld times, arc voltages, tolerances, and other options for up to 127
programs per outlet. At this point, you are on line 1 and need to specify which outlet you want. In this example we
will use outlet 1; press “1” and “Enter”. Then select the program you want, in this example we will use program 1;
press “1” then “Enter”. You will see the following screen :
Monitored Parameters.<↓>
Weld Parameters.<↓>
Select the line “Varc Drop Detect”. Adjust the tolerance for “Varc Drop Detect” as necessary by
highlighting the value on this line and use the “plus” and “minus” keys to change the value. The
actual tolerance entered will depend on the application and should always be set to a range that is
consistent with maintaining good welds.
37
ERROR 31: WELD ABORTED DUE TO PILOT ARC VOLTAGE
DEFINITION: Pilot Arc voltage out of toleranceàABORT WELD. *** ALUMINUM WELDING ONLY ***
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Tolerance for “Pilot Arc Voltage” is programmed too tight. From the “Main Menu”, highlight the line
“Programming” and press “Enter”. Highlight “Weld Programming” and press “Enter”. The “Weld Programming”
sub-menu is used to program weld currents, weld times, arc voltages, tolerances, and other options for up to 127
programs per outlet. At this point, you are on line 1 and need to specify which outlet you want. In this example we
will use outlet 1; press “1” and “Enter”. Then select the program you want, in this example we will use program 1;
press “1” then “Enter”. You will see the following screen :
Monitored Parameters.<↓>
Weld Parameters.<↓>
Select the line “Varc Pilot Limits”. Adjust the tolerances for “Varc Pilot Limits” as necessary by
highlighting the values on this line and use the “plus” and “minus” keys to change these values. The
actual tolerance entered will depend on the application and should always be set to a range that is
consistent with maintaining good welds.
38
(WELD ABORTED DUE TO PILOT ARC VOLTAGE - CONTINUED)
39
ERROR 32: POWER SUPPLY REGULATION OUT OF RANGE
DEFINITION: Occurs while welding. The PWM detects, for a 5ms duration, that the SMPS was unable to
deliver the requested current.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1. Determine what Program (1-127) is being used at the problem spot or spots. Examine
the “Weld Current” or “Iw” value programmed for these programs .
2. Using the Programmed “Iw”, use the graph below to determine the maximum weld
“loop” or cable length (Lc).
Iw (Vs) Lc
2000
1800
1600
1400
Iw (Amps)
1200
1000
800
600
400
200
0
0 50 100 150 200 250
Lc (Feet)
40
(POWER SUPPLY REGULATION OUT OF RANGE - CONTINUED)
3. Subtract L2 from Lc, the remainder is the length that L1+ L3 should NOT exceed.
Equipment Requirements
Cable Length Design Procedure
L1 L2
L3
L1 = Length of the cable connecting the welder controller and the feeder
L2 = Length of the cable connecting the feeder and the weld head
L3 = Length of the weld common cable
4. Choose lengths for L1 and L3, which are within this range from the standard length table
given below:
L1 L2 L3
8 ft. (2.5 m) 8 ft. (2.5 m) 26 ft. (8.0 m)
13 ft. (4.0 m) 20 ft. (6.0 m) 32 ft. (10 m)
26 ft. (8.0 m) 26 ft. (8.0 m) 40 ft. (12 m)
32 ft. (10 m) 30 ft. (9.0 m) 46 ft. (14 m)
40 ft. (12 m)
3) Copper grounding block not to specification: ¼” square contact surface at 30lbs of pressure on work.
41
ERROR 33: COMMON MEASUREMENT LINE BROKEN
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Check PWM Polarity jumpers X22 and X23 for correct setting. See Appendix B Fig. 1 “Stud Polarity Setup
Procedure”.
NOTE: The Common Measurement Line is a wire that runs in parallel with the Weld Common
Power cable to the work-piece grounding block. Both the Weld Common cable and the
Common Measurement Line are tied to the grounding block.
3. At the DCE cabinet, with all cables hooked up, use an ohm-meter to check for continuity
(0Ω) between the nut on the back of the Common Measurement Line banana plug
connector and the Weld Common cable connector. See Fig. 9 or 10 in Appendix B.
a. If an “open” is read at this check, either a break exists in the Weld Common cable
or the Common Measurement Line wire, or one of these wires is not attached at the
work-piece grounding block.
42
ERROR 34: SAFETY CIRCUIT FAULT
DEFINITION: Output voltage of SMPS (Switching Mode Power Supply) is continuously checked for limit
voltage of 48V. When exceeded, the power supply stops operating (this may happen when arc
voltage is interrupted).
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad plant power input to DCE cabinet. Power should be reliable 480VAC +/- 10%, 3-phase, 50-60hz.
43
ERROR 35: SYSTEM CONFIGURATION FAULT
DEFINITION: Improper cable configurations between DCE cabinet and supporting equipment (PKE Box,
SD2, or SDX modules).
1. PKE Box (if used) is plugged into an Outlet other than Outlet 1.
2. If using SD2 (2 feeders feeding 1 head) or SDX (multiple feeders feeding 1 head) system; feeders not hooked
up in a consecutive order (Outlets 1, 2, 3, etc.).
3. SD2 (2 feeders feeding 1 head) or SDX (multiple feeders feeding 1 head) system; Master Feeder cannot be
hooked up on outlet 5.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
44
ERROR 38: FIBER OPTIC TO FEEDER
DEFINITION: Welder Control DCE ZCPU Board has lost fiber-optic communication with the feeder.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad fuse F2 on ETF Feeder CPU Board E510A. See Appendix B Fig. 3.
2) Bad fuse F7, F8, or F9 along upper back wall of DCE Welder Control. See Appendix B Fig. 7.
7) Bad Relay K2 (power to feeders) inside the DCE Welder Control. See Appendix B Fig. 7.
8) Bad Safety Board (inside DCE control). See Appendix B Fig. 11.
45
ERROR 39: FIBER OPTIC TO CUSTOMER INTERFACE
DEFINITION: Welder Control DCE ZCPU Board has lost fiber-optic communication with the Customer
Interface Board.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad Fiber Optic cable that runs between DCE ZCPU and Customer Interface Board.
2) Robot/PLC is not sending the necessary 24vdc power to the Customer Interface Board.
46
ERROR 40: FIBER OPTIC TO POWER SUPPLY
DEFINITION: Welder Control DCE ZCPU Board has lost fiber-optic communication with the PWM Board on
the SMPS Power Supply.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad Fiber Optic Cable that runs between DCE ZCPU and PWM (on the Power Supply).
4) Bad Safety Board. SEE APPENDIX A “DCE SAFETY BOARD TRUTH TABLE”; ALSO SEE
APPENDIX B Fig. 11 FOR LOCATION OF SAFETY BOARD.
47
ERROR 41: SMPS- PROGRAM NOT LOADED
DEFINITION: Fault occurs when DCE ZCPU sends program to PWM on the Power Supply, but PWM does
not acknowledge receipt of the program.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) Bad RAM module on the DCE ZCPU Board. See Appendix B Fig. 7.
48
ERROR 42: FEEDER- RELAYS STILL ENERGIZED
DEFINITION: DCE ZCPU orders the ETF CPU Board Relay K1 to switch off; Relay di d not turn off. DCE
ZCPU will order this relay turned off prior to DCE Relay K2 switching off all power to the
feeder. The DCE ZCPU should get a report from the feeder that ETF CPU Board K1 was
turned off prior to feeder power-down.
This is a safety feature that turns off 24vEXT/INT power in the feeder in case Relay K2 in the
DCE fails to open its contacts during “E-Stop” or “Op-Stop”.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad ETF Feeder CPU Board. See Appendix B Fig. 3 and 15.
2) Bad Safety Board in DCE. SEE APPENDIX A “DCE SAFETY BOARD TRUTH TABLE”; ALSO SEE
APPENDIX B Fig. 11 FOR LOCATION OF SAFETY BOARD.
49
ERROR 44: TEACH MODE CONDITIONS NOT MET
DEFINITION: The “Operation-Stop Bypass” mode was entered within 3 seconds of entering the “Operation
Stop” mode.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Entered “Operation-Stop Bypass” mode too quickly after entering “Operation Stop” mode. You must wait at least
3 seconds after entering “Operation Stop” mode before you enter “Operation-Stop Bypass” mode.
2) Bad Safety Board. SEE APPENDIX A “DCE SAFETY BOARD TRUTH TABLE”; ALSO SEE
APPENDIX B Fig. 11 FOR LOCATION OF SAFETY BOARD.
50
ERROR 45: START WELD NOT RESET
DEFINITION: The “Start” signal from Robot/PLC was active at the time the Customer Interface Board was
powered up.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) The Robot/PLC has activated the “Start” signal before powering up the Customer Interface Board. Force the
“Start” signal off at the Robot/PLC and reset the fault, if necessary, at the DCE.
51
ERROR 46: NO STUD LOADED
DEFINITION: When using Stud Divider, SD2, and SDX, the selected feeder did not perform a feed cycle by the
time of welding.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) In “Outlet Programming”à “Auto Repeat Feed” was set to “No” and tried to feed.
52
ERROR 47: TEST CONDITIONS NOT MET
DEFINITION: While in “Status Test Process ” screen on Keypad, “Start” sent by Robot/PLC without the
Robot/PLC placing the DCE in a “test” mode.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Robot/PLC should place the DCE in an appropriate test mode before sending “Start” signal to the DCE while
keypad is in the “Status Test Process” screen of the Keypad.
a. Robot/PLC should use the Mode Select 1 and Mode Select 2 bits to set the proper test mode:
1. Mode Select 1 high; Mode Select 2 low --- Dry Cycle with part
2. Mode Select 1 low; Mode Select 2 high --- Dry Cycle without part.
NOTE: The Test Modes are used for test purposes only. The system will NOT weld while in these modes.
53
ERROR 49: FEEDER NOT IN AUTOMATIC
DEFINITION: A Keypad is connected to feeder and the “Manual” screen is displayed while the customer sends
the “Start” signal to the DCE.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Ensure that, if the Keypad is connected to the DCE, that the display is NOT in the “Manual” screen while trying to
weld in normal operations. If it is press the “ESC” key several times until you are in the “Main Menu” screen.
54
ERROR 61: ZCPU- RAM CARD MEMORY CONFIGURATION
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUS ES
1) Clear RAM (See “Clear RAM Procedure” in Appendix A) and reprogram the DCE.
3) Bad DCE ZCPU Board; replace and reprogram DCE. See Appendix B Fig. 7.
55
ERROR 62: ZCPU-RAM MODULE IS MISSING OR DEFECTIVE
DEFINITION:
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Clear RAM (See “Clear RAM Procedure” in Appendix A) and reprogram the DCE.
2) Bad RAM module in DCE ZCPU Board. Replace and reprogram DCE. See Appendix B Fig. 7.
3) Bad DCE ZCPU Board. Replace and reprogram DCE. See Appendix B Fig. 7.
56
ERROR 97: FEEDER- DRUM DOOR OPEN
DEFINITION: Missing jumper or signal that connects X11 pins 4 and 6 of the ETF CPU Board (E510A).
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Powe r Verification” in Appendix A.
POSSIBLE CAUSES
1) Jumper between pins 4 and 6 of X11 on the ETF Feeder CPU Board. See Appendix B Fig. 15.
57
ERROR 98: FEEDER- STUD LEVEL LOW
DEFINITION: A low stud level is detected in the feeder as measured by the stud level proximity switch.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Low stud level exists in 1 or more feeders. Check stud level and refill if necessary.
3) Bad ETF Feeder CPU Board. See Appendix B Fig. 3 and 15.
58
ERROR 100: FEEDER- NO POWER TO AUX. SUPPLY
DEFINITION: One or more ETF CPU Board power supplies have failed.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad fuse F2 on ETF Feeder CPU Board E510A. See Appendix B Fig. 3.
2) Bad fuse F4 on ETF Feeder CPU Board E510A. See Appendix B Fig. 3.
3) Bad fuse F3 on ETF Feeder CPU Board E510A. See Appendix B Fig. 3.
10) Bad fuse F1 on ETF Feeder LM Amplifier Board E512A. See Appendix B Fig. 3..
11) Bad ETF Feeder CPU Board E510A. See Appendix B Fig. 3 and 15.
12) Bad ETF Feeder LM Amplifier Board E512A. See Appendix B Fig. 3.
59
ERROR 102: FEEDER- FEED RAIL NOT FILLED IN TIME
DEFINITION: Feed Rail Min. proximity switch did not detect full Feed Rail within 60 seconds of activation of
rail filling device.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
3) Bad fuse F1 on ETF Motor Driver Board 55052. See Appendix B Fig. 2, 3, and 4.
4) Bad ETF Motor Driver Board 55052. See Appendix B Fig. 2, 3, and 4.
6) Bad ETF Feeder CPU Board E510A. See Appendix B Fig. 3 and 15.
60
ERROR 103: FEEDER- AIR PRESSURE LOW
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Check input air pressure to feeder. Input air pressure should be 80-100psi.
2) Bad Air Pressure Monitor switch. Remove side cover of ETF Control Box. See Appendix B Fig.16.
3) Bad ETF Feeder CPU Board. See Appendix B Fig. 3 and 15.
61
ERROR 104: FEEDER- KNIFE NOT IN FRONT POSITION
DEFINITION: Only used in feeders that have escapement slide block/knife blade proximity switch. No
software yet written for this option.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
62
ERROR 106: FEEDER- FEED TUBE LOCKING SWITCH OPEN
DEFINITION: The Feed Tube Locking switch circuit is not complete. This is a switch used on handgun
systems to detect if the feed tube is attached or not. This switch is not used on weld heads BUT
IS jumpered inside the weld head. The connection made on the handgun or weld head is Pin C
to Pin H on the control cable.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Feed tube not properly mounted on handgun (if this is a handgun system). Ensure that feed tube, once mounted,
engages the Feed Tube Locking Switch.
3) Bad Multi-Cable assembly that runs from the feeder to the weld tool.
63
ERROR 107: FEEDER- SD-2 POSITION TIMEOUT
DEFINITION:
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
64
ERROR 109: FEED CYCLE TIMEOUT
DEFINITION:
1. DCE ZCPU did not get “Commence Feed Cycle” bit from feeder within 6 seconds of “Feed Initiate” from
DCE ZCPU.
2. DCE ZCPU did not get “Piston Back” bit from feeder in 6 seconds after “Feed Initiate” from DCE ZCPU.
3. DCE ZCPU did not get “Piston Fwd” bit from feeder 6 seconds after receiving “Piston Back” from feeder.
4. DCE ZCPU did not get “Feed Cycle Stop Acknowledge” from feeder.
5. If “Stud Arrival Sensor” is “On”, stud doesn’t arrive before feed cycle ends.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) On “T-Stud” feeders, incorrect “Load Time” or “Feed Time” programmed at “Outlet Programming”.
65
ERROR 117: FEEDER- DSP COMMUNICATION
DEFINITION: ETF Feeder reports to the DCE ZCPU inside the DCE that the Main Processor on the ETF
Feeder CPU Board is not talking to the DSP (slave processor) on the ETF Feeder CPU Board.
Note: Before proceeding to troubleshooting s teps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) Software problem. May need to reload software on the ETF CPU Board. Make sure that the correct software
version is loaded. Contact Emhart Teknologies for assistance.
66
ERROR 118: FEEDER- +5V KEYPAD NOT DETECTED
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
67
ERROR 119: FEEDER- LM/SOLENOID UNDER VOLTAGE
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
68
ERROR 120: WRONG CORRESPONDING STUD
DEFINITION: After the “Start” signal is give to the DCE by the Robot/PLC, the weld head moves forward to
the work. At this time the ETF Feeder CPU Board is informed of the value of pre-load as
measured by the Weld Tool Encoder Board, compares that value to the value it was taught to
recognize, and has calculated that the length of the stud did not give the correct pre-load
measurement; therefore the wrong stud is in the weld tool or stud is missing.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) Weld tool probe/flash shield “stick-out” misadjusted. Perform the following 2 procedures:
a. Adjust “stick-out” of weld tool See Appendix B Fig. 14.
. b. Use the appropriate procedure depending on whether you are using a Weld Head or Hand gun.
1. See Appendix A “Programming Stud Length Detection (Angularity) Hand Gun”.
2. See Appendix A “Programming Stud Length Detection Weld Head”.
3) Teaching of robot positioning is incorrect. If possible, at head forward, the stud and the probe should be in as close
to the same plane of the work piece as possible.
a. Readjust probe orientation at problem points on work piece.
b. Re-teach the robot positioning at the problem points on work piece.
5) Bad Multi-cable assembly running from the feeder to the weld tool (head or gun). Replace or repair cable
assembly.
6) Bad ETF Feeder CPU Board. Replace Board. See Appendix B Fig. 3.
69
ERROR 121: FEEDER- LM/SOLENOID OVER VOLTAGE
DEFINITION: A voltage measurement discrepancy on the LM Amplifier Board has been detected.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1. Bad fuse F1 on ETF Feeder LM Amplifier Board E512A. Do not confuse F1 on the ETF CPU board with F1 on
the LM Amplifier Board. Be sure to identify the LM Amplifier Board. See Appendix B Fig. 3.
70
ERROR 122: FEEDER- LM/SOLENOID NOT DETECTED
DEFINITION: ETF does not detect the wires connected to either the LM motor or Solenoid inside the Weld
Tool (depending on which configuration, LM or Solenoid, that the feeder is set up for).
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) Bad Multi-cable Assembly (cable that runs from the ETF Feeder to the Weld Head or Hand Gun).
4) Bad ETF Feeder LM Amplifier Board E512A or Solenoid Board (depending on which configuration, LM or
Solenoid, that the feeder is set up for). See Appendix B Fig. 3.
71
ERROR 123: FEEDER- SHORT CIRCUIT, LM/SOL. OUTPUT
DEFINITION: The ETF LM Amplifier Board detects a short circuit across the output pins to the LM motor
inside the LM Weld Tool.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad fuse F1 on ETF Feeder LM Amplifier Board E512A. Do not confuse F1 on the ETF CPU board with F1 on
the LM Amplifier Board. Be sure to identify the LM Amplifier Board. See Appendix B Fig. 3.
3) Bad Multi-cable Assembly (cable that runs from the ETF Feeder to the Weld Head or Hand Gun).
72
ERROR 124: FEEDER- AMPLIFIER GROUND FAULT
DEFINITION: The ETF LM Amplifier Board detects a short to ground in the LM circuit.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) Bad Multi-cable Assembly (cable that runs from the ETF Feeder to the Weld Head or Hand Gun).
5) Bad ETF Feeder CPU Board E510A. See Appendix B Fig. 3..
73
ERROR 125: FEEDER- ENCODER NOT DETECTED
DEFINITION: ETF Feeder CPU Board does not detect the handshaking signals from the Weld Tool Encoder
Board. The Encoder Board is the board inside the Weld Tool that measures stud motion and
velocity.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
2) Bad Multi-cable Assembly (Cable package that runs from the Feeder to the Weld Tool).
74
ERROR 126: FEEDER- INSUFFICIENT ROOM FOR LIFT
DEFINITION: After the “Start” signal is give to the DCE by the Robot/PLC, the head moves forward to the
work. At this time the “Lift On” command is give to the LM Control. The LM Control
determines the “absolute position” (or pre-load distance) of stud as measured by the encoder
and has calculated that, given the total travel available, the programmed “Lift” trajectory
cannot be achieved.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Weld tool probe/flash shield “stick-out” misadjusted. Perform the following 2 procedures:
a. Adjust “stick-out” of weld tool using Appendix B Fig. 14.
. b. Use the appropriate procedure depending on whether you are using a Weld Head or Hand gun.
1. See Appendix A “Programming Stud Length Detection (Angularity) Hand Gun”.
2. See Appendix A “Programming Stud Length Detection Weld Head”.
2) Teaching of robot positioning is incorrect. If possible, at head forward, the stud and the probe should be in as close
to the same plane of the work piece as possible.
a. Readjust probe orientation at problem points on work piece.
b. Re-teach the robot positioning at the problem points on work piece.
4) Bad Multi-cable assembly running from the feeder to the weld tool (head or gun). Replace or repair cable
assembly.
5) Bad ETF Feeder CPU Board. Replace Board. See Appendix B Fig. 3.
75
ERROR 127: LIFT HEIGHT TIMEOUT
DEFINITION: If “Lift Off” command is not issued within 400ms of “Lift On”, the LM motor is switched off
and this fault is displayed.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Faulty PWM Board on SMPS (Switching Mode Power Supply). See Appendix B Fig. 9.
2) Faulty ETF Feeder CPU Board inside Feeder. See Appendix B Fig. 3.
76
ERROR 128: FEEDER- POWER SUPPLY OVER TEMP.
DEFINITION: Ambient temperature of the Servo Amplifier Board E512A has exceeded 85°C (or 185°F).
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Duty-cycle of LM Motor in weld head is too high. This can occur for the following reasons:
a. Stud lifted too long for the cycle time between welds.
b. Stud lifted too high for the cycle time between welds.
c. Ambient air temperature of plant environment too high for cycle time between welds.
77
ERROR 45: FEEDER- LM NOT READY.
DEFINITION: During attempt to weld, at least one fault was detected with the Linear Motor (LM) circuit.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Bad ETF Feeder LM Amplifier Board fuse F1 or F2. See Appendix B Fig. 3.
3) Bad ETF Feeder input power transformer F1T1. See Appendix B Fig. 3.
78
ERROR 146: FEEDER- SOLENOID CARD MISSING
DEFINITION: ETF CPU Board does not detect the presence of the Solenoid Board inside the Feeder.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) ETF Feeder LM Amplifier Board is not seated properly into the ETF CPU Board. See Appendix B Fig. 3.
a. Power down the DCE Control.
b. Remove and reseat the Solenoid Board.
c. Power up the DCE Control. If fault is still present, proceed to step 2.
79
ERROR 147: FEEDER- AMPLIFIER CARD MISSING
DEFINITION: ETF CPU Board does not detect that the Amplifier Board E512A is plugged into the ETF CPU
Board.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) ETF Feeder LM Amplifier Board is not seated properly into the ETF CPU Board. See Appendix B Fig. 3.
a. Power down the DCE Control.
b. Remove and reseat the Amplifier Board E512A.
c. Power up the DCE Control. If fault is still present, proceed to step 2.
80
ERROR 149: FEEDER- 140 VOLTAGE MISSING
DEFINITION: ETF Feeder CPU Board E510A does not detect 140 volts available at the ETF Feeder LM
Amplifier Board E512A.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
81
ERROR 151: FEEDER- 24V INTERNAL MISSING
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSE:
82
ERROR 152: FEEDER- 24V EXTERNAL MISSING
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
83
ERROR 153: FEEDER- 24V INTERNAL RELAYS MISSING
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
84
ERROR 154: FEEDER- 24V EXTERNAL RELAYS MISSING
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
85
ERROR 155: FEEDER- 15V KEYPAD MISSING
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
86
ERROR 156: FEEDER- +15V AMPLIFIER MISSING
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
87
ERROR 157: FEEDER- -15V AMPLIFIER VOLTAGE MISSING
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
88
ERROR 159: FEEDER- LM STUD STICKOUT NOT ENOUGH
DEFINITION: After the “Start” signal is give to the DCE by the Robot/PLC, the head moves forward to the
work. At this time the ETF Feeder CPU Board analyzes the position of the stud as measured by
the Weld Tool Encoder Board. The LM Control determines the “absolute position” (or pre-
load distance) of stud as measured by the encoder and has calculated that the programmed
“Penetration” depth cannot be achieved.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
WELD PROGRAMMING
----------------------------------------
Outlet: 1 Weld Program: 1
Stud ID……………………….._____________
Program Active…………………yes
Start Delay…………………….. 200 ms
Weld Current………………….1300 A
Weld Time………………………..28 ms
Lift / Penetration………………1.20 mm -0.10mm
Optimization…………………….no
89
ERROR 159: FEEDER- LM STUD STICKOUT NOT ENOUGH (Continued)
3) Teaching of robot positioning is incorrect. If possible, at head forward, the stud and the probe should be in as close
to the same plane of the work piece as possible.
a. Readjust probe orientation at problem points on work piece.
b. Re-teach the robot positioning at the problem points on work piece.
5) Bad Multi-cable assembly running from the feeder to the weld tool (head or gun). Replace or repair cable
assembly.
6) Bad ETF Feeder CPU Board. Replace Board. See Appendix B Fig. 3.
90
ERROR 160: FEEDER- COLOR MARKING IMPOSSIBLE
DEFINITION:
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
91
ERROR 161: WELDING PART NOT SUPPLIED
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
92
ERROR 162: WELDING PART NOT REMOVED
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
93
ERROR 164: FEEDER- LIFT NOT DETECTED BY ENCODER
DEFINITION: Encoder Board inside the weld head that is used to measure stud movement (lift, plunge, etc.)
did not measure the stud motion during the attempt to weld.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) Faulty weld tool. Replace or repair (refer to weld tool tear-down procedure).
a. Dirty or damaged Encoder Strip inside the weld tool.
b. Faulty Encoder Board inside weld tool.
c. Faulty wiring inside weld tool.
2) Faulty Multi-cable assembly (cable that runs from feeder to the weld tool).
a. Check Pin A for continuity from end to end.
b. Check Pin B for continuity from end to end.
94
ERROR 180: ATTEMPT TO WELD WITH DEFAULT SCHEDULE
DEFINITION: Tried to weld with a program that has not been modified from the default settings.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
1) You must change at least one value in “Weld Parameters” screen of “Programming”.
a. From the “Main Menu”, highlight the line “Programming” and press “Enter”. Highlight “Weld
Programming” and press “Enter”. The “Weld Programming” sub-menu is used to program weld currents,
weld times, arc voltages, tolerances, and other options for up to 127 programs per outlet. At this point, you
are on line 1 and need to specify which outlet you want. In this example we will use outlet 1; press “1” and
“Enter”. Then select the program you want, in this example we will use program 1; press “1” then “Enter”.
You will see the following screen :
Weld Parameters.<↓>
NOTE: Ensure that you have entered ALL of the proper settings to achieve a proper weld
95
ERROR 202: POWER SUPPLY- TEMPERATURE TOO HIGH
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
96
ERROR 266: WRONG LOAD- OR FEEDTIME (SF52)
DEFINITION:
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
97
ERROR 268: PROGRAMMING IS NOT ALLOWED
DEFINITION: Programming of “Outlet Parameters” and “Weld Parameters” has been prohibited by dip-
switch 8 on the DCE ZCPU Board.
Note: Before proceeding to troubleshooting steps below, verify that all power is available to, and
inside, the controller. See “Procedure for Power Verification” in Appendix A.
POSSIBLE CAUSES
98
GLOSSARY
Angularity – A condition that must be achieved where the weld tool-to-work piece angle must be 90° plus or
minus a programmable tolerance. Angularity is measured by an Encoder Board in LM Weld Tools or by a
proximity switch in PK560 Handguns .
Arc Voltage – Voltage measured between the stud and the work piece once the stud has “lifted” off of the
work piece. The arc voltage is measured by the PWM Board in conjunction with the Measurement Line
and the Common Measurement Line . See Pilot Arc and Main Arc.
Auxiliary Power Supply Board – Power supply Board mounted on the inside door of the DCE cabinet.
Collet – The fingered chuck on the Weld Tool that holds the stud during the weld cycle.
Common Measurement Line – One of the wires used by the PWM Board as a voltmeter lead to measure
Arc Voltage. This line runs in parallel with the common weld power cable out to the grounding block for
the work piece, at which point the Common Measurement Line is attached to the common weld power cable.
COW – “Collet On Work”. This is an undesirable condition. Created when an empty collet (due, for
example, to a miss-fed stud or nut) in the weld tool is able to touch the grounded work piece. The DCE
“sees” Stud On Work (see SOW) and attempts to weld the collet to the work piece.
Customer Interface Board – The Board located inside the DCE that communicates with the Robot/PLC.
Drop Down Time – The time is takes the stud to travel from the lifted position back to the work piece during
the Plunge phase of the weld cycle.
Encoder Board – The circuit Board inside the Weld Tool (usually of the Linear Motor type) that measures
the actual lift distance achieved by the Weld Tool. It also measures the velocity of the Plunge action of the
stud.
ETF – Generic term for a Feeder used in DCE stud welding systems. Normally specified with numerical
suffix (for example: ETF12, ETF90, etc.)
ETF CPU Board – The central processing unit inside the Feeder.
ETF Filter Board – A circuit board inside the Feeder that routes the Lift signal to the Weld Tool.
Feeder – The device in welding system that automatically feeds the stud (or nut) to the Weld Tool.
Flash Shield – The round metal sleeve on the front end of Handguns that surrounds the Collet and stud.
Adjusted on PK560 guns to set Lift dimension (.045”). Adjusted on PLM guns to adjust Stick-Out. This
sleeve helps contain the arc “flash” during the weld process. It is also used to contain the Shield Gas in
operations where protective gas is required.
Note: Can be installed on Weld Heads where protective gas is required during the weld.
Handgun – One of the Weld Tools. A hand held device with trigger used by operator to weld the stud to the
99
work piece. See Weld Tool.
JIC Box – The control box on ETF Feeders that contains circuit boards necessary for Feeder operation.
Lift – The act of pulling (lifting) the stud off of the work during the weld cycle. Controlled by a Linear
Motor or by a Lift Coil inside the Weld Tool.
Lift Coil – An electro-magnet inside PK560 Weld Tools that causes the stud to lift off of the work piece.
Lift Height – The dimension to which the stud has been lifted off of the work piece after commencement of
the weld cycle. This height is programmable with Linear Motor Weld Tools and should be manually set to
.045” on PK560 Handguns .
Linear Motor – Device used in LM Weld Tools that causes the stud to lift off of the work piece.
LM Amplifier Board – A Board inside the Feeder that converts 5v lift signal generated by the ETF CPU
Board into 140v and sends it to the Linear Motor inside the Weld Tool via the ETF Filter Board.
Main Arc – Arc Voltage measured between the stud and the work piece during Weld Time phase of the
weld cycle. See Weld Time .
Measurement Line – One of the wires used by the PWM Board as a voltmeter lead to measure Arc
Voltage. This line runs in parallel with the Weld Tool weld power cable and is attached to the weld power
cable inside the Weld Tool.
Multi-cable Assembly – A cable assembly that runs from the Feeder to the Weld Tool. The assembly
contains a control cable, a weld power cable, and air lines (head forward, head back, piston forward, and
piston back). The assembly may also contain a Shield Gas line if needed.
Outlet – A term roughly interchangeable with Weld Tool (i.e. Head 1 = Outlet 1; Gun 1 = Outlet 1). This
term is used extensively on the keypad of the DCE control in place of Weld Tool, Weld Head, or Handgun.
See Weld Tool.
Pilot Arc – Arc Voltage measured between the stud and the work piece during the pilot phase of the weld
cycle.
PKE Box – The device that takes the place of a Feeder when using manually loaded PK560 Handguns .
The PK560 Handguns are plugged into this unit.
PK560 – A specific type of Handgun where the stud or nut is manually loaded by the operator into the front
of the gun each time a welding operation is to be performed. Usually followed by a letter designator (i.e.
PK560R, PK560B, etc.) to indicate the type of stud or nut for which this gun is set up.
Plunge – The process of driving the stud from the lifted position back to the work piece; accomplished by
using either a Linear Motor in an LM Weld Tool or a plunge spring in a PK560.
100
Preload – A measurement of the distance (upon seating the Probe or Flash Shield on the work piece) that
the stud has traveled in relation to the Probe or Flash Shield. This measurement is directly affected by the
adjustment of the Probe or Flash Shield.
Probe – Angled rod mounted next to the Collet on the front of Weld Heads . Used as a physical stop to halt
the pneumatic head forward motion. This probe has NO electrical properties whatsoever (i.e. it is not the
“ground” for weld current). See “Probe Set-up Procedure” in Appendix B Fig. 14.
Program – One of the 127 programmable heat schedules available to each of the 5 Outlets on a DCE welder
control. These programs are selectable by the Robot/PLC for the purpose of using different programs at
different weld positions on the work piece.
PWM Board – The circuit Board located on the front of the SMPS that controls output weld current,
measures output weld current, and measures the Arc Voltage.
Shield Gas – An inert protective gas (usually Argon) laid down around the weld zone to displace oxygen
during the weld. An SMB Box must be used to dispense the gas.
SOW – “Stud On Work”. This is a signal generated by touching the stud (held by Collet in weld tool) to the
grounded work-piece. Necessary for the weld process to continue.
Slide Rail – Refers to the pneumatically operated head forward and head back action of Weld Heads .
SMB Box – A module used to dispense Shield Gas from a remote source (such as an Argon bottle), through
the Multi-cable Assembly, through the Weld Tool, and out to the weld zone.
SMPS – “Switching Mode Power Supply”. The large square power supply located in the lower portion of
the DCE. This power supply produces the weld current.
Stick-Out – The distance that the stud extends out in front of the edge of the Probe or Flash Shield. This is
adjustable and should be set in accordance with the procedures in Appendix B Fig. 14.
Weld Energy – A measure of the energy applied to the weld. It is measured on every weld and displayed (in
Jules) on the keypad. The formula applied:
Energy (J) = Main Arc Voltage x Main Current x Weld Time
Weld Head – One of the Weld Tools; used typically on robot arms, pedestal stations, or inside a fixed tool.
Requires no human intervention. Under Robot/PLC control the weld head slides pneumatically forward to
the work piece, welds, and slides pneumatically to the rear position. See Weld Tool.
Weld Time – The duration of the weld phase (Main Current) of the weld cycle. Programmable by the user.
Weld Tool – The device that physically touches the stud or nut to the work piece for welding. This may take
the form of a Weld Head or Handgun.
101