Minimum/Maximum Operating Pressures 20 psi (138 kPa) - 125psi (862 kPa)
Minimum/Maximum Operating Temperatures 40°F (4°C) - 110°F (43°C)
AC Adapter: U.S International
Supply Voltage 120 V AC 230V AC
Supply Frequency 60 Hz 50 Hz
Output Voltage 12 V AC 12 V AC
Output Current 500 mA 500 mA

No user serviceable parts are on the PC board, the motor, or the AC adapter. The means of
disconnection from the main power supply is by unplugging the AC adapter from the wall.

Table below contains a summary of specifications for the control valve and bypass valve.

QUICK REFERENCE SPECIFICATIONS

Service flow rate 1” (includes bypass and meter) 27 gpm (102.2 Ipm) @ 15 psig (103 kPa) drop
Backwash flow rate 1” (includes bypass) 27 gpm (102.2 Ipm) @ 25 psig (172 kPa) drop
Service flow rate 1.25” (includes meter) 34 gpm (128.7 Ipm) @ 15 psig (103 kPa) drop
Service flow rate 1.25” (includes bypass and meter) 32 gpm (121.1 Ipm) @ 15 psig (103 kPa) drop
Backwash flow rate 1.25” 32 gpm (121.1 Ipm) @ 25 psig (172 kPa) drop
Backwash flow rate 1.25” (includes bypass) 30 gpm (113.5 Ipm) @ 25 psig (172 kPa) drop
Minimum/Maximum Operating Pressures 20 psi (138 kPa) - 125 psi (862 kPa)
Minimum/Maximum Operating Temperatures 40°F (4°C) - 110°F (43°C)
AC Adapter: U.S International
Supply Voltage 120 V AC 230V AC
Supply Frequency 60 Hz 50 Hz
Output Voltage 12 V AC 12 V AC
Output Current 500 mA 500 mA

Regenerant Refill Rate 0.5 gpm (1.9 Ipm)


Injectors See Injector Graphs
Drain Line Flow Controls See Table 7
Inlet/Outlet Fitting Options (a) 1
 ” NPT elbow which has a unique drill out
feature to allow a 1/4” NPT connection to the
inlet and/or outlet
(b) 3/4” & 1” PVC solvent weld fitting

wd-14
(c) 1” straight brass sweat fitting
(d) 3/4” straight brass sweat fitting
(e) 1” plastic male NPT fitting
(f) 1 1/4” plastic male NPT fitting
(g) 1” plastic male BSPT fitting
(h) 1 1/4” plastic male BSPT fitting
Distributor Tube Opening WS1HR&HS Valve 1.05” outside diameter (3/4” NPS)
1.32” outside diameter (1” NPS)
Distributor Tube Opening WS1.25HR&HS Valve
32 mm outside diameter
Tank Thread 2 1/2” - 8 NPSM
Control Valve Weight 4.5 lbs. 2.0 kg
PC Board Memory Nonvolatile EEPROM
(electrically erasable programmable read-only
memory)
Compatible with regenerants/chemicals Sodium chloride, potassium chloride, potassium
permanganate, sodium bisulfite, chlorine and
chloramines.

wd-15
1. Timer does not display time of day a. AC adapter unplugged a. Connect Power
b. No electric power at b. R epair outlet or use working
outlet outlet
c. Defective AC adapter c. Replace AC adapter
d. Defective PC board d. Replace PC board
2. Timer does not display correct a. Switched outlet a. Use uninterrupted outlet
b. Power outage b. Reset time of day
c. Defective PC board c. Replace PC board
3. N
 o softening/filtering display when a. Bypass valve in bypass a. P ut bypass valve in service
water is flowing position position
b. Meter connection b. Connect meter to PC board
disconnected
c. Restricted/stalled meter c. Remove meter and check for
turbine rotation or foreign material
d. Defective meter d. Replace meter
e. Defective PC board e. Replace PC board
4. C
 ontrol valve regenerates at a. Power outages a. R eset control valve to correct
wrong time of day time of day
b. Time of day not set b. Reset to correct time of day
correctly
c. Time of regeneration c. Reset regeneration time
d. Control valve set at d. C heck control valve set-up
“on 0” (immediate procedure regeneration time
regeneration) option
e. Control valve set at e. Check control valve set-up
NORMAL + on 0 procedure regeneration time
option
5. ERROR followed by code number a. Control valve has just a. Press NEXT and REGEN for 3
been serviced seconds or unplug power source
ERROR code: 1
 001 - Unable to jack (black wire) and plug back
recognize start of in to reset control valve
regeneration b. Foreign mater is lodged b. Check piston and spacer stack
in control valve assembly for foreign matter.
ERROR code: 1002 - Unexpected c. High drive forces on c. Replace piston (s) and spacer
Stall piston stack assembly
d. Control valve piston not d. Press NEXT and REGEN for 3
ERROR code: 1003 - Motor ran too
in home position seconds or unplug power source
long, timed out trying
jack (black wire) and plug back
to reach next cycle
in to reset control valve
position
wd-16
ERROR code: 1004 - Motor ran to long, e. M  otor not inserted fully to e. Check motor and wiring. Replace
timed out trying to reach engage piston, motor wires motor if necessary.
home position broken or disconnected
motor failure
If other ERROR codes display contact the f. D  rive gear label dirty or f. Replace or clean drive gear
factory. damaged, missing or
broken gear
g. Drive bracket incorrectly g. Reset drive bracket property
aligned to back plate
h. P C board is damaged or h. Replace PC board
defective
i. PC board incorrectly i. Ensure PC board is correctly
aligned to drive bracket snapped on to drive bracket
6. C ontrol valve stalled in regeneration a. Motor not operating a. Replace motor
b. No electric power at outlet b. R  epair outlet or use working outlet
c. Defective AC adapter c. Replace AC adapter
d. Defective PC board d. Replace PC board
e. Broken drive gear or drive e. Replace drive gear or drive cap
cap assembly assembly
f. Broken piston retainer f. Replace drive cap assembly
g. Broken main regenerant g. Replace main regenerant piston
7. Control valve does not regenerate a. AC Adapter unplugged a. Connect AC adapter
automatically when REGEN button is b. N  o electric power at outlet b. R  epair outlet or use working outlet
depressed and held
c. Broken drive gear or drive c. R  eplace drive gear or drive cap
cap assembly assembly
d. Defective PC board d. Replace PC board
8. C ontrol valve does not regenerate a. Bypass valve in bypass a. P ut bypass valve in normal
automatically but does when REGEN position operating position
button is depressed b. Meter connection b. Connect meter to PC board
disconnected
c. Restricted/Installed meter c. R
 emove meter and check for
turbine rotation or foreign matter
d. Defective meter d. Replace meter

e. Defective PC board e. Replace meter

9. Time of day flashes on and off a. Power has been more than a. Reset the time of day
two hours, the AC adapter
was unplugged and then
plugged back into the wall
outlet, the AC adapter
plug was unplugged and
then plugged back into
the board or the NEXT
and REGEN buttons were
pressed to reset the valve.