You are on page 1of 5

PMA KS 108 flexible

Compact PLC with


touch operating screen

5,7“ colour display

PLC functions in accordance


with IEC 61131-3

Integrated visualization system

Comprehensive PMA function library

I/O integration via CAN and/or Ethernet

Communication via field bus and Ethernet

 Compact, robust hardware APPLICATIONS data. An optional OPC server permits


convenient access to the process data,
 Touch-screen operation
 Machine building e.g. from a PC.
 Brilliant color display  Plant engineering
Thanks to the proven function blocks in the
 Operating system ‚embedded‘ Linux  Factory automation
PMA library, fast and highly efficient
 Process automation
 Realtime Soft PLC runtime  Plastics processing programming is ensured, as well as utmost
 Building automation functional safety.
 Programming according to
IEC 61131-3 Design
DESCRIPTION
 PMA function library: The KS 108 is a particularly compact
Controller, Programmer, ... General device intended for mounting e.g. in control
with comfortable parametrization As the central element in an automation panels.
dialogs system, the PMA KS 108 performs
all the relevant sequencing tasks: The computer core consists of a 'low
 Multitasking power' processor, which operates with-
 Convenient debugging and  Soft PLC for realtime operation out the need for additional cooling.
commissioning tools to IEC 6 1131-3 The program is stored in an onboard
 Visualization and operation Flash memory. Thanks to this design, the
 Fully integrated graphical control terminal's hardware is particularly
visualization editor robust for a long service life.
Adjustable task priorities permit individual
 Fast, efficient data exchange bet- adaptation of partial tasks to the require-
ments of the sequencing program. This Visualization is provided by a fully graphic
ween visualization and soft PLC
makes optimum use of processor perfor- colour displays with resolutions from 320 x
 Graphical PLC configuration for mance for short response times. 240 pixels. The displays feature excellent
the Vario I/O system In this way, short cycle times of the Soft readability and brightness, plus long-life
PLC are ensured, together with fast background lighting.
 Onboard CAN interface
response of the user interface.
Moreover, the resistive touch feature
 Optional field bus modules
Integration of a sequencing program and a permits direct operation via the screen.
 Access to variables via network user interface in one piece of equipment No other external operating controls (e.g.
(Ethernet TCP/IP) with a common programming environment buttons, ...) are required.
results in decisive time and cost advanta-
ges. Moreover, the Engineering is simpli-
fied. Thanks to the joint use of data in the
sequencing program and for visualization,
possible error sources are eliminated.

Via the Ethernet interface, the control


terminal can be linked into existing
networks very easily.

By means of network variables, other


PLCs are able to access the common
IEC 61131 programming environment BlueLib function library KS108_CONTROL
ai_PV_1 ao_SPeff
Programming of the terminal is based on The BlueLib library contains a ai_PV_2 ao_PV
the standard IEC 61131-3. The CoDeSys comprehensive range of functions based ai_PV_3 ao_AV
system is completely compatible with the on the experience of PMA controllers for ai_SPext ao_DV
standard, and offers convenient the following operations: ai_OVCP ao_SP
ai_OVCM ao_AVout1
programming in all of the languages
ai_PF ao_AVout2
defined in IEC 61131:  Controlling ai_AVhm ao_Bl_no
 Profiling ai_AVadd do_AV1
 Instruction List (IL)  Scaling ai_Cas c do_AV2
 Function Block Diagram (FBD)  Arithmetic di_hide do_c_fail
di_lock do_off
 Ladder Diagram (LD)  etc. di_inc do_a_m
 Structured Text (ST) di_dec do_AV_AV2
 Sequential Function Chart (SFC) Futhermore it provides function blocks to di_PV_fail do_SPe_SPi
 Continuous Function Chart (CFC) connect the I/O systems vario I/O and rail di_PF_fail do_pi_p
line. di_a_m do_o_run
di_SP_SP2 do_o_s tab
Powerful test functions greatly reduce the di_SPe_SPi do_o_err
necessary programming and Integrated parametrization dialogs di_pi_p do_DV_s up
commissioning times. Every function block of the BlueLib library di_d_ovcP
automatically supplies the associated di_d_ovcM
di_track
parametrization dialog.
di_AV_AV2
This will start in CoDeSys by simply di_off
double-click the function block inside the di_s m _hm
CFC-Editor. di_os tart
di_SPs top
di_gr_off
Right picture: Controller function block. di_rs tart
Below the associated parametrization di_o_hide
dialog. di_oplock
tData

 Monitoring of variables
 Writing and forcing of variables
 Breakpoints and stepping
 Single-cycle operation
 Sequence monitoring
 Recording and graphical
representation of variables (tracing)
 Online change of programs

The integrated visualization system has


access to all the variables used by the
sequencing program, thus eliminating the
risk of multiple definitions.
Numerous functions are available for
creating user-specific operating screens.

 Basic elements: rectangle, ellipse,


graphics, etc.
 Complex elements: alarm handling,
 trends, tables, etc.
 Animation
 Various data entry keypads
 etc
TECHNICAL DATA

PROCESSOR INFLUENCING FACTORS

CPU: Freescale Power PC / 266 MHz Power supply


Fanless cooling No effect. No loss of data in case of a
64 MByte RAM / 32 MByte free power supply failure (Flash, EEPROM)
16 MByte Flash / 8 MByte free
16kByte RAM (Retain) Vibration test
Real time clock Sinusoidal oscillations in accordance with
Backup: Lithium battery IEC 60068-2-6 and EN 60068-2-6;
Test Fc: 10…150Hz, 1g

DISPLAY Shock test


To IEC 60068-2-27 and EN 60068-2-27
5,7-inch colour TFT or CSTN, Test Ea: 15g for 10 ms, half sine wave
Resolution: QVGA 320 x 240 pixels
256 colours, resistive touch operation
ELECTROMAGNETIC COMPATIBILITY

INTERFACES Immunity test


In accordance with 61000-6-2 and
Serial interfaces EN 61326-1, Industry
Type: RS 232, 9-pin Sub-D
Max. cable length: 12 m Emission test
In accordance with 61000-6-4 and
Type: RS 485, 9-pin Sub-D EN 61326-1, Industry
Galvanic isolated,
Max. cable length: 1000 m
GENERAL
CAN interface
galvanic isolated, 9 pol. Sub-D, Weight
max. cable length according to CANopen approx. 1,5 kg
standard
Protection class
Network Front panel: IP 65
Ethernet interface (10/100 Base-T) Rear: IP 20
Galvanic isolated
Electrical safety
USB interface Complies with EN 61 010-1
USB Host (Typ A, front access) and IEC 61131-2
Over-voltage category II
Expansion interface Contamination degree 2
Slot for I/O module Protection Class III
Slot for fielbus module
Slot for SD card CE marking
Fulfills the EU Directives for electro-
magnetic compatibility and low voltage.
POWER SUPPLY
USL / CNL (cULus)
Supply voltage: Type 1 (indoor use)
24 V DC (18…32V / SELV) File: E208286
Galvanic isolated
Residual ripple: ≤ 4 Vss Standard accessories
Current consumption: typical 1A, max. 2 A Supply voltage terminal
Mounting accessories

ENVIRONMENTAL CONDITIONS

Permissible temperatures
For specified accuracy: 0...50°C
Storage & transport: -20...70 °C

Relative humidity: max. 85%


no condensation
Fig. 1: Overall dimensions KS 108

Fig. 2: Fitting dimensions KS 108


Fig. 3: Connections KS 108

Ordering information

Description Order-No. Function


KS 108 with PMA front K108-230-00000 Compact Panel-PLC with touch screen, 5,7-inch TFT colour display
KS 108 with neutral front K108-330-00x00 Compact Panel-PLC with touch screen, 5,7-inch TFT colour display
Standard interfaces 0 Ethernet, CAN (isolated), RS232, RS485 (isolated), Front-USB
Optional interfaces 1 Additionally: CAN (not isolated), RS232, USB (Rear side)

Accessories

Description Order-No. Function


CoDeSys programming tool PMA-PLC-TOOLS01 Installation-CD with CoDeSys IEC 61131-3 programming system
8 port Ethernet switch EDG-6528L 8 port industrial switch for rail mounting

Recommended I/O systems

Description Order-No. Function


vario I/O KSVC-xxx-xxxxx See data sheet ... (www.pma-online.de)
rail line RL40-xxx-xxxxx See data sheet ... (www.pma-online.de)

PMA Your local representative:


Prozeß- und Maschinen- Automation GmbH
P.O. Box 31 02 29
34058 Kassel / Germany
Tel.: +49 561 505 1307
Fax.: +49 561 505 1710
Fray Junípero Serra, 27 - 28039 Madrid
E-mail: mailbox@pma-online.de Tel: +34 915 670 325 - Fax: +34 915 670 549
Internet: http://www.pma-online.de info@termya.es – www.termya.es

Printed in Germany – Edition 11/2008 – Subject to alteration without notice – 9498-737-54113

You might also like