Professional Documents
Culture Documents
Final GIS AIS E House Sub Station
Final GIS AIS E House Sub Station
SPECIFICATION
E-HOUSE
(CSS 33/11 KV)
WBSEDCL
TECHNICAL SPECIFICATION FOR E-HOUSE of 33/11 KV SUB-STATION
1.0 SCOPE
This specification describes the requirements for design, manufacture, testing at
manufacturer’s works, supply, installation and Commissioning at site of prefabricated metal
electrical room with GIS Switchgear System and associated auxiliary equipment.
IEC 62271-200 AC metal-enclosed switchgear & control gear for rated voltage
above 1 KV and up to and including 52 KV
IEC 60694 Common clauses for high voltage switchgear and control gear
standards
IEC 62271-103 High voltage switches for rated voltages above 1 KV and less
than 52 KV.
IEC 60233 Tests for hollow insulators for use in electrical equipment
IS 8828/1996 MCB
6.01 LIGHTING
• The electrical panel can be wall mounted type and shall have feeders for lighting
circuits, sockets, battery chargers, air conditioning units, F&A panels, spare etc. The
incoming supply for this panel shall be from a 3 phase 4 wire 433V 50Hz supply
and will have a main TPN MCB of sufficient rating depending upon the load inside
E-house. The feeders shall be through 2 pole MCBs for single phase circuits and 4P
MCBs for 3 phase circuits. The feeders shall be arranged such that the load shall be
balanced among three phases. The enclosure shall be of minimum IP41 rating, powder
coated paint.
• The wiring circuit of the E House for lightings will include a suitable 1-phase power input
socket, distribution board with MCB for the light connections and other additional
points as required.
• Sufficient quantity 240 V, 1 Ph, 5 A socket outlet shall be provided inside the E-House.
• Electrical wiring has to be done as per respective IS standard with proper
earthing system. All wires used for lighting system should be by FRLS 1100V grade.
• Lux level shall be 300 lumen inside the E-house and outside platforms/ stairs
shall be 100 lumen. The luminaries used shall be LED type of sufficient wattage to
cater the required Lux requirement.
• Motion / Occupancy Sensors shall be installed within E-House which shall
perform zone wise lighting system control.
• The enclosure shall be furnished complete with factory installed of emergency
lighting and with EXIT light fixtures at each access doors. Twenty percent of
total lighting fixtures shall be emergency lighting with UPS/Battery backup. The
lighting system shall provide immediate emergency light (for at least 1 Hour) upon
failure of the normal power source, and shall switch off automatically when power
is restored.
6.02 GROUNDING
• Internal Earthing inside enclosure with suitable cross sectional GI flats
• The E-House shall be furnished complete with ground pads which shall bond of electrical
equipment enclosure frames and ground buses to the E-House frame at the exterior
base in two locations and at opposite ends of the e House so as to provide a continuous
path to ground.
• The Grounding system shall connect to each end of the ground bus in each
assembly of installed equipment.
6.03 FIRE DETECTION & CONTROL, SURVEILLANCE SYSTEM AND AIR CONDITIONING
SYSTEM
• The Fire Detection – alarm & control system, surveillance system and Air conditioning
system shall be installed in line with manufacturer’s recommendation and WBSEDCL
Technical Specification.
9.0 PAINTING
Corrosion-prone steel components of the switchgear cubicles – unless they are made of
stainless steel – must be protected by zinc phosphating. Large-sized front components
visible from the outside, such as doors or covers, should be coated additionally by
scratch-proof textured paint. The colour coating should be provided in the colour RAL
7032 (pebble grey).
Busbar shall be of made of electrolytic high grade Copper of adequate size and bus bar
size calculation/supporting type test report shall be submitted for approval (current
density of copper shall not exceeded more than 1.6 Amp/sq.mm). They shall be
adequately supported on insulators to withstand electrical and mechanical stresses due
to specified short circuit currents.
Busbar shall be supported on the insulators such that the conductor expansion and
contraction are allowed without straining the insulators.
Bus bar cross-section shall be uniform throughout the length of switchgear board. Bus
bars shall be in SF6 gas insulated compartment.
All piping for SF6 gas including their fittings shall be made of non- magnetic stainless
steel housings.
Busbar insulators shall be of arc and track resistant, high strength, non- hygroscopic,
non-combustible type and shall be suitable to withstand stresses due to over-voltages,
and short circuit current. In case of organic insulator partial discharge shall be limited
to 50 pico coulomb at rated Voltage X 1.1/√3. The temperature of the busbars and all
other equipment, when carrying the rated current continuously shall be limited as per
the stipulations of relevant Standards, duly considering the specified ambient
temperature (55° C). Clearances between phases and between phase and earth shall be
kept liberally so as to obtain high reliability.
2 No. of Poles 3
4 Frequency 50Hz
7 Total Break time for any current upto 3 cycles max (60ms)
The Earthing Disconnector will operate always de-energized and the making capacity is
provided by the circuit-breaker, which is designed for these purposes. The Disconnector
must be according to the latest edition of the IEC 62271-102 and shall meet requirements as
specified in paragraph ratings. The indication of the position of the Disconnector must be
mechanical. The Operating mechanism must be outside the SF 6 atmosphere and accessible
from the front. The Disconnector must be of single rotation-driving axis both for the
Disconnector and the Earthing switch. It is mandatory that the operation from “closed to
busbar” to “ready to earth” is made in two separate operations, closed - open and open - ready
to earth. These are completely independent operations, with two separated operating access.
Isolators or isolators combined with earthing switches (switches-Open, Close Earthed) shall
be motor operated. In case of emergency, Manual operation must be possible. The earthing
position of all 3 phases must be visible via a mechanical position indicator (MIMIC) directly
connected to the drive shaft on panel front Fascia. The mechanical operation of
isolator/disconnector switch must be possible with door closed for operator safety.
The interlocks shall be provided as per standards. It shall be possible to control these
switches from front of the panel & remotely from SCADA through IED. Key interlocks shall
also be provided for local manual operations.
i) The switchboard must be fitted with all the interlocks needed to prevent incorrect
operations which may jeopardize safety of personnel in charge of operating the
installation, as well as the efficiency and reliability of the apparatus. Internal
mechanical interlocks of the panel with the circuit breaker closed, the interrogation
slide is locked for the disconnector and the earthing switch. (Restriction to the
insertion of Hand Crank for Disconnector-Earth Switch when CB is ON).
ii) The interrogation slide always release some insertion opening only (disconnector or
earthing switch), or both of them are locked.(To ensure that either Disconnector -or
Earth Switch operating at a time)
The crank for the disconnector and earthing switches can only be removed in its
appropriate end position.
iii) When the crank on the disconnector or earthing switch is still in place, or when the
interrogation slide is open, the following components are locked:
- ON push button of circuit breaker
- ON pulse is interrupted
iv) In particular, the following mechanical interlocks at least must be provided to
prevent;
i. Operation in busbar if the circuit breaker is closed.
ii. Closing of the earthing switch when busbar isolator are closed.
f. PT and CT secondary neutral point earthing shall be at one place only on the terminal
block. Such earthing shall be made through links so that earthing of one secondary
circuit may be removed without disturbing the earthing of other circuits.
g. The panel shall have Voltage Presence Indicator (VPI) to warn the operator against
earthing of live connections.
h. All hinged doors shall be earthed through flexible earthing braid.
i. Separate earthing for switchgear and composite VCB panel shall be provided.
c. The secondary windings of CTs & PTs shall be earthed at one point through a
removable link, with provision for attaching test links.
g. To allow this switchboard with the primary directly plugged to the line. A remote
operated isolator has to be installed to enable disconnecting of the bus voltage
transformer from line for partial discharge and cable testing.
h. Currant transformers shall be rated to withstand the thermal and magnetic stresses
resulting from the maximum available through fault current, the momentary and time
rating requirements same as that of the switchgear.
l. Name plates shall be fixed in a position so that details can easily be read when fitted in
the cubicle.
m. Bus bar voltage transformers shall have provisions for safely disconnecting the
fuses and transformers from energized bus. Where plug in with drawable types are
used shutters shall be provided to automatically seal off the high voltage spouts when
the transformers are withdrawn.
p. Accessible test links and terminals, with the following facilities, shall be provided for
each CT and PT
• Source side short circuit of CT secondary.
• Burden side short circuit of CT secondary.
• Insertion of external device (including injection test set) in secondary lead of each CT
or star point lead.
• Each phase and neutral of VT secondary for test equipment take off.
• Connection of any source side transformer's differential protection relays
q. CT Technical Parameters
ii. Primary Current rating 400-200 Amps 400-200 Amps 400-200 Amps
ii. Primary Current rating 400-200 Amps 400-200 Amps 400-200 Amps
i. Voltage class 12 KV 36 KV
ii. Rated primary voltage(kV rms) 11000 / √3V 33000/√3
Location Mounting
3. CABLE TERMINATIONS:
3.1 Power cables shall be bottom entry, unless specified otherwise. Facilities shall be
provided for cable testing and current and voltage injection. A socket/bushing and plug
assembly shall be provided for the power cables.
3.2 Connections for power cables shall be plug in type/push on, according to DIN
47637outer cone type as per relevant IEC.
3.3 Cable terminating facilities and terminals shall be for the specified cable type, gland
and conductor size.
3.4 Terminal blocks shall be arranged and positioned to afford easy access for carrying out
external cable termination, testing, inspection and maintenance. There shall be
clear space allowed between the terminals and the gland-plate for the spread in gland
termination of external conductors.
3.5 The panel wiring shall be on one Side of the terminal block only. No more than two wires
shall be connected to a terminal.
3.6 Terminal blocks shall be shrouded or provided with transparent covers. Pinch screw type
terminals are not acceptable.
3.7 Terminals for different voltages shall be separated by partitions. CT wiring and control
wiring shall not be on the same terminal stripe.
3.8 A terminal box or chamber with un-drilled gland plate or entry panel of sufficient
dimensions to terminate the specified cables shall be provided.
3.9 Positioning of cable terminations shall avoid obstruction of other cable terminations;
removable covers etc. and provide for easy access for terminating cables.
3.10 Cable supports shall be provided (where practicable)to avoid undue strain on the cable
termination.
3.11 Separate terminal arrangements shall be provided for each panel and for power and
control cables.
3.12 SCADA terminal should be terminated in separate SCADA Panel for both 11 KV & 33 KV
separately
4.0 Low voltage Compartment (Instrument Chamber)
4.1 The panels shall be with low voltage compartment consisting control switches,
indication and metering instruments, protection relays and other secondary
equipment’s. The dynamic mimic shall be provided on the front fascia and not on the
LV chamber.
4.2 The front side shall have Mimic as per single line diagram with control switches and
mechanical and electrical ‘Position indicators’ circuit breakers, disconnectors and
earth switches
4.4 The Communication device shall have USB/RJ 45 communication port in the front
for the setting software use and at the back there has to be of this communication
port: 2xRJ-45 Ethernet port.
4.5 The Communication device shall support following communication protocols: Native
IEC 60870-5-104, Modbus TCP, Modbus RTU, Human-Machine communication,
display and Human-machine communication, PC.
4.6 The IEC 61850 communication has to support peer to peer communication (GOOSE).
The IEC 61850 interface has to able configure through setting software. Also the
same setting software has to be able to generate ICD files.
4.7 Live line Indicators: - Capacitive voltage indicators shall be provided on feeder side
in outgoing feeders, on bus side & feeder side in incoming feeders and on both the
sides in Bus coupler to indicate the voltage presence in each phase and to prevent
the closing of earth switch in case the part is live. It shall have sufficient output
contacts for substation Automation System and interlock purpose.
4.9 End termination required for cables should be touch proof type, EURO mould.
5.0 . M E T E R I N G P R O T E C T I O N , C O N T R O L A N D I N D I C A T I O N :
5.1 Meters and relays shall be capable of withstanding, without damage the secondary currents
associated with the maximum available through fault current same as switchgear rated
fault current. External zero adjustment shall be possible to facilitate adjustment without
dismantling the instrument.
5.2 Protection and metering devices shall be flush mounted, where possible shall be
withdrawable.
5.3 Protective relays shall be of the solid state, microprocessor-based programmable type
with serial communication facilities.
5.4 Relays should have Check – Synchronization facility.
5.5 Protective relays shall have electrical-reset facilities and clear operation indication,
e.g. light emanating diodes. Non-tripping relays may be self-resetting if an indication of
operation remains until hand reset.
5.6 Relay shall have front RJ 45/USB port for communication to a local PC with rear RJ45 port
for connection to remote operation on IEC61850 protocol without any external convertor.
5.7 Relay shall have circuit breaker failure protection built-in.
5.8 Trip Relay should have electrical reset facility.
5.9 Relay shall have under and over voltage protection for Incomer Panels.
5.10 Indication lamps (green-open, red-closed, amber-tripped, white-trip circuit healthy plus
Service Position, and Circuit Earthed) shall be provided for each circuit breaker. Status
of spring charging mechanism (Charged or Discharged) and positive drive mechanical
position indicators, visible without opening the cubicle door, shall be provided for each
circuit breaker. Volt-free contacts for remote indication shall be provided. Indications
may be incorporated in the multifunction relay via relay LEDs.
5.11 Control of circuit breakers shall be carried out from a control switch at the low voltage
compartment door. Provisions shall be implemented at the switchgear for breaker
control from a remote control panel. Where a multifunction relay is specified the control
feature available in the relay may also be used. Switchgear mounted and remote manual
tripping facilities shall act direction the trip coil. Manual trips via relays are not
acceptable.
5.12 As minimum, the following signal/indication shall be provided locally and remotely:
Conditions Locally Remote
5.13 Alarm Scheme – Alarm & Annunciation and scheme must be at Feeder & Bus coupler.
a) Alarm scheme for trip alarm due to electrical faults-
Trip commands due to operation of protective relays will actuate bell and will be
cancelled by the circuit breaker control handle. Auto trip lamp will glow on the panel and
there will be flag indication on the concerned protective relay/auxiliary relay of the
panel.
b) Alarm scheme for non trip alarm:
This scheme will conform to the following:
i. The closing of an initiating contact snail actuate a buzzer and will be
accompanied by a flag indication on the concerned auxiliary relay.
ii. The closing of an initiating contact shall glow a lamp, which will not reset until
the fault has cleared.
iii. It shall be possible to silence tree buzzer by pressing ‘accept' pushbutton. If
after canceling the alarm but before resetting the visual signal, the same fault
persists the buzzer shall be suppressed.
iv. If after canceling the alarm but before resetting the visual signal some other fault
takes place then the alarm accompanied by the flag indication on the concerned
auxiliary relay shall take place.
v. If after canceling the alarm and after resetting the visual signal, the same
fault appears or some other fault takes place, the alarm flag indication and non-
trip lamp indication shall reappear as usual.
vi. The non-trip alarm acceptance shall be by means of a pushbutton and resetting of
visual signal may also be done through a push button.
vii. Non-trip Alarm and buzzer shall be actuated in case of low SF6 pressure in any of
the compartments in the GIS as well as for AC fail, DC fail, Transformer non
trip supervision.
viii. Means shall be provided for test checking the alarm and lamp circuits.
ix. The equipment shall be suitable for 110VDC operations.
6.1 The device shall contain all the necessary protection functions/ completed
protection scheme for feeder and motor applications. The functions are as
follows (including separate Relay for differential & REF Protection):
• Overcurrent (50/51), 3 stages
• Earth fault (50N/51N), 4 stages
• Directional overcurrent (67), 4 stages
• Directional earth fault (67N), 3 stages
• Broken line (46R)
• Thermal overload (49)
• Zero sequence voltage (59N), 2 stages
• Overvoltage (59), 3 stages
• Under voltgae (27), 3 stages
• Over frequency (81H), 2 stages
• Under frequency (81L), 2 stages
• Rate of change of frequency (81R)
• Magnetizing inrush (68F2)
• Over excitation (68F5)
• Reverse power (32)
• Auto reclose function (79)
• Circuit breaker failure (50BF)
• Synchrocheck (25)
• Latched trip (86)
• Programmable stages (99), 8 pcs
6.2 Overcurrent protection shall have a wide range of time overcurrent protection curve
settings, providing a choice of curve types:
6.3 Pick-up setting of three over current stages have to be able to control remotely.
6.4 Changing setting groups has to able to do via: manually, digital inputs, virtual inputs,
virtual outputs or LED indicator signals.
6.5 The device shall have force start and trip condition for testing.
6.6 Any protection function has to be able to block by internal and external signals using
block matrix.
11 Class of insulation
12 Class of accuracy
(a) For metering
(b) For
Protection
(c) PS Class
13 Short circuit current rating and its duration
14 One minute power frequency dry withstand voltage
15 1.2/50 micro sec. impulse withstand test voltage
16 One minute power frequency withstand test voltage
on secondary
17 Instrument safety factor
18 Type of primary winding
panels and all the protection relays, measuring and indicating instruments and the control and
monitoring devices and accessories, including current transformers and voltage transformers shall
comply with the provisions and requirements of the standards of the International Electrotechnical
The latest revision or edition in effect at the time of bid invitation shall apply. Where references
are given to numbers in the old numbering scheme from IEC it shall be taken to be the equivalent
number in the new five-digit number scheme. The bidder shall specifically state the precise
standard, complete with identification number, to which the various equipment and materials are
manufactured and tested. The bid document may not contain a full list of standards to be used, as
they only are referred to where useful for clarification of the text.
2.0 Scope of Work: This Specification covers the design and engineering, manufacture,
testing at the manufacturer‘s factory, painting, packing for transport, insuring,
transportation by road and delivery at destination point of 12 kV, 800 A, 18.4KA,
Multi panel, shunt trip, Indoor Type, motor operated, spring closing Vacuum Circuit
Breaker having SCADA compatible facilities and complete with all accessories as
specified hereinafter.
Climatic condition: The equipment is required to operate satisfactorily under the following site
conditions:
3.1 Tropicalization
(a) All equipment must be designed for operations in the severe tropic climate conditions
and fully comply with climatic aging tests as per IEC 60932-class 2.
In choosing materials their finishes, due regard shall be given to the humid tropical
conditions under which the switchgear will be called upon to work. The
manufacturer shall submit details of his usual practice which have proven
satisfactory for application to the parts of the Switchgear panels, which may be
affected by tropical conditions.
• Metals:
Iron and Steel are generally to be painted or galvanized as appropriate.
Indoor parts may alternatively have chromium or copper-nickel plates or
other approved protective finish.
Small iron and steel parts (other than rustless steel) of all instruments and
electrical equipment, the cores of electromagnets and the metal parts of relays
and mechanisms shall be treated in an appropriate manner to prevent rusting.
3.2.1 General
a) The design, dimensions and materials of all parts shall be such that they will not suffer
damage under the most adverse conditions nor result in deflections and vibrations, which
might adversely affect the operation of the equipment. Mechanisms shall be constructed
b) The equipment and apparatus shall be designed and manufactured in the best and most
substantial and workmanlike manner with materials best suited to their respective
practice.
c) Whenever possible, all similar parts, including spare parts, shall be made
interchangeable. Such parts shall be of the same materials and workmanship and
d) All equipment shall be designed to minimise the risk of fire and consequential damage, to
prevent ingress of vermin and dust and accidental contact with electrically energized or
moving parts. The switchgear panels shall be capable of continuous operation with
obtained in a tropical climate and where the switchgear is called upon to frequently
interrupt fault currents on the system and also where the duty of operation is high.
a) All steel castings and welding shall be stress-relieved by heat treatment before machining,
b) Liberal factors of safety shall be used throughout, especially in the design of all
EMC(Electromagnetic Compatibility, IEC 61000) directives. The rating and design criteria
v. Frequency 50 HZ
The AC supply shall be used for power circuit and for lighting, indication, motor
controls and similar small power circuits. Unless otherwise specified, the equipment provided
under this tender is to be capable of reliable operation at voltages as low as 85% of the rated
voltage, and to withstand continuously up to 110% supply voltage above the rated value of
The auxiliary dc supply shall be used for controls, indication, alarm, protection
relays, and circuit breaker tripping and closing circuit, etc. All equipment and apparatus
including the circuit breakers, protective relays, control devices and accessories,
satisfactory operation at 80% to 130% of the rated dc supply voltage. However, in case
of VCB, for tripping the range should be 70% to 110% and for closing that should be
85% to 110%.
3.2.4 Electrical controls, auxiliaries and power supplies
(a) Responsibility for electrical control and auxiliaries.
The manufacturer shall provide all control, indication, alarm and protection devices and all
auxiliary equipment with wiring and interconnecting cable which are integral parts of or are
directly associated with or mounted on the switchgear panels to be supplied under this
tender. The design of protection and control schemes for the switchgear panels shall be
Interlocking devices shall be incorporated in the control circuit to ensure safety, and
proper sequence and correct operation of the equipment. The scheme will be finalised during
a) Switchgear shall electrically be designed to avoid local corona formation and discharge likely
to cause radio interference.
b) The design of jointing of adjacent metal parts and surfaces shall be such as to prevent
corrosion of the contact surfaces and to maintain good electrical contact under service
conditions.
c) Particular care shall be taken during manufacture of busbar and fittings and
during subsequent handling to ensure smooth surface free from abrasion. All joints on the
busbar and the circuit within the switchgear board shall be silver or tin-plated to ensure good
electrical connection.
In the event of direct conflict between various order documents, the precedence of
authority of documents shall be as follows –
4.8 Extensibility The Switchgear shall be designed so that future units can
be added to each sides (unless coupled to other euipment).
A removable plate will cover any unused openings in the
side of the panel.
4.9 Extension Bus and Bus In case of Single feeder panels, Identical Bus Bars and Bus Wires
Wires for connection with adjacent Incomer / Bus Coupler / Feeder
needs to be supplied.
4.10 Separate compartment for Bus bar, circuit breaker, HV incoming / outgoing cable,
LV instruments & relays.
4.11 Breaker compartment Separate with lockable handle (design with breaker trolley as
door the front cover is not acceptable)
4.12 Breaker to bus Through seal off bushings/Spout
bar compartment
4.13 Breaker to cable Through seal off bushings/Spout
compartment
4.14 Pressure relief devices To be provided for each HV Compartment. Each compartment
shall be separated from adjacent one by sheet steel barrier.
4.16 Fixing arrangement Concealed hinged Bolted with SS bolts and Neoprene rubber
i. Doors gasket , washer
ii. Covers
iii. Gasket
4.20 Prevention of Internal Arc Shall be type tested against internal arc as per provision in
IEC 62271-200. The Circuit Breaker, busbars and cable
compartments shall be provided with arc venting outlet. The
doors for the compartment shall be capable of withstanding
the effects of maximum internal arcing fault without being
blown off and causing danger to personnel and other
equipment. This should be proven by successful testing for
18.4 KA with duration 0.1 second as per relevant IEC
standard.
4.21 Test Terminal Block 13 Ways, 50A, 1100V with back connection. Dia of Entries
is 5 mm & overall dimension 250X50 mm, covered with
insulated cover. TTB should be disconnecting link type
suitable for 3 Phase 4 Wire Energy Meter. Screw type TTB
not acceptable.
4.22 Multiway terminal Block Delinking type, Rail/Channel mounted, Terminal Connector
and low voltage wiring to be used in CT Circuit & Screw type for other Circuit. The
Terminal Blocks should be suitable for 2.5 sq.mm wire and
covered with insulated transparent cover. Pitch should be
minimum 8mm & 10mm for Screw type & Delinking type
connectors respectively.
The low voltage cable shall be enclosed in grounded
metal conduit when routed through a high voltage
compartment. Control wiring shall be neatly bundled and tie
wrapped where applicable. Wiring shall be protected from
rubbing against door flanges or other parts of the
enclosure.
4.23 Cable Tray Netted Metal cable Tray of suitable size at the rear side of
Switchgear, preferably running at the top along the panel
for carrying the signal cables for SCADA interface to be
provided.
4.24 Remote Terminal Box To be provided suitably at the back side of the panel for
termination of the following cables :
A . Main AC / DC
B . Inter trip from up stream
C . SCADA related terminations
D . Inter connection for Differential protection etc.
4.29.2 Label for identification For bus side and cable side shutters
4.29.3 Warning label on shutters of Clearly visible label ―isolate elsewhere before earthing‖ be
incoming and other provided
connections
4.30 Breaker electrical
4.30.1 Trip coil supervision relay To be given for breaker close and open condition.
4.30.7 PT supply bus in all panels Fed normally by Bus PT with changeover facility.
The circuit breaker shall be provided with motor operated
4.30.8 Spring Charge Limit switch spring
Aux. Contact Configuration charged closing. Spring charging by motor should be smooth
and hassle free and there should be nominal sound during
spring charging. Motor should be 230 Volt AC operated,
Tripping of the circuit breakers shall be through "Shunt trip"
coils
rated for 30V DC auxiliary supply. It shall be possible to trip
the
breaker manually in case of necessity.
4.30.9 Local/ Remote selector Switch should be 4 pole in each position, 2 way lockable and
switch stay put type.
5.1 Current Transformers Shall be cast resin type with insulation class of E or better.
Contact tips on primary side shall be silver plated. Correct
polarity shall be invariably marked on each primary and
secondary terminal.
Primary shall be wound or bar type, rigid, high conductivity
grade copper conductor. Unavoidable joints on the primary
conductor shall be welded type, preferably lap type. Current
density at any point shall not exceed 1.6 A/sq.mm. Suitable
insulated copper wire of electrolytic grade shall be used for
CT
secondary winding. Multi ratio in CT shall be achieved by
reconnection of secondary winding tapping. The secondary
terminals shall have screw type terminals. The screw should
have sufficient length for connection of at least two nos
wires
with plain and spring washers and minimum 10 mm clearance
between the adjacent screw.
6.2.0 Mounting Rail mounted on top of the Unit and connected on bus side.
It can be plugged into and withdraw from service by pulling
or pushing the PT by the handle provided on the PT. This
action traverses the PT along the rails and shall
automatically operate the spout shutters. The shutter drive
also forms a latch which holds the PT in the service position
and this latch shall be required to be released before PT can
be isolated.
Access to the PT and the reinforcement in the Panel for
allowing a person to stand on the Top should be provided.
Sealing arrangement of the PT with the carriage and
secondary fuses are to be provided.
Mounting of PT on the breaker truck is not acceptable.
7.2. Earth bus joints A ground bus rated to carry maximum fault current shall be
furnished along the full length of the panel board. Each
stationary unit shall be grounded directly to ground bus. All
bolted joints in the bus will be effected by connection of
two bolts.
7.7. Metallic cases of relays, Connected to the earth bus by independent copper wires of
instruments and other LT size not less than 2.5 sq mm with green colour insulation. For
panel mounted equipment this purpose LT compartment should have a clear designated
earth bus to which earth connections from all components are
to be connected.
7.8. CT & PT Secondary neutral Earthed at one place at the terminal blocks through links.
Flush Mounted, back connected, dust proof with Industrial
8.0 Indicating Meters grade
―A‖ classification and conforms to IS:1248(1968)
8.1 CT operated Ammeter 3 no. Digital Ammeters to be provided in Incomer and Feeder
panels for measuring load current of each phases.
Display : 3 ½ -digit display,
Aux. Power: : 230 V AC
CTR: 600/1A for Incomer and 200/1A for Feeders.(Site
Selectable)
Accuracy Class: 1.0 or less.
Size : 96 X 48 mm.
8.2. Direct Ammeter 1 nos. Separate Digital Ammeter to be provided for
measuring heater current drawal in all the Panels.
Display : 3 ½ -digit display,
Aux. Power: : 230 V AC
Accuracy Class : 1.0 or less.
Size : 96 X 48 mm.
12.2. Local / Remote selector 2 way, 4 poles in each position lockable and stay put type.
switch
12.3 Selector switch for voltmeter 4 Positions ( RY-YB-BR-OFF), 3 ways.
12.4. Toggle ON/Off switches For heater / illumination circuit
4 Position (PT1-PT2-PT3-OFF), 8 Poles in each position.
12.5 PT Selector switch Current
rating 16 Amps
12.6 Push button of IED(Relay) Wired up to specified DI contact of Relay.
Reset
12.7 Emergency trip push button Red colour with stay put, Current rating 10 Amps.
12.8 Push button for Announciator 2 nos. push button one for annunciation accept and one for
Accept & Reset announciation reset to be wired upto announciator.
450/750 V grade PVC insulated stranded flexible copper
13.0 Internal wiring wire.
13.1. Wire Size 2.5 sq. mm for CT circuit, 1.5 sq mm for PT and 1.5 sq.
mm for control circuit, 4.0 sq. mm for Main, AC & DC and Bus
wiring.
i. A suitable wiring duct system firmly fixed on the panel
and having covers shall be installed for front to rear and
inter
panel wiring to provide easy access for inspection and
replacement of the wires.
ii. Wiring between terminals of the various devices shall
be point to point. Splices or tee connection will not be
acceptable.
iii. Facilities for short-circuiting the current transformer
secondary while the switchgear is in service shall be
provided.
iv. Wires shall be suitably bunched adequately supported
to prevent sagging. and it shall have sufficient clearance from
High voltage system.
v. Sufficient Bus wires shall be provided for
interconnecting with adjacent units both ways and also for
future connection.
13.2 Wiring Colour code
13.2.1 PT and CT Red Phase : Red, Yellow Phase : Yellow
Blue Phase : Blue, Neutral : Black.
13.2.2 DC Circuit Gray
13.2.3 AC Circuit Black
13.2.4 Earth Green
13.3 Ferrules At both ends of wire with same stated marking. Plastic
ferrules shall be used conforming IS.
Interlocked type (one additional red
colour ferrule for all wires in trip circuit)
13.3.1.10 Spare contact circuit U1, U2, U3 .../ S1, S2, S3 .......
13.4 Lugs Tinned copper, pre-insulated, fork type and pin type as
applicable. Only Ring type is acceptable in CT &PT Circuit.
17.0 HT Cable Termination Cable entry from rear bottom side for Incomer and
Outgoing feeders .The cable termination shall be located at
least
250 mm from the CT primary terminals. For Incomer, double
cable termination arrangement to be provided with two sets
of
nut and bolts. Copper terminator strip of adequate size shall
be
provided for termination of cables and shall have adequate
height inside to accommodate the heat shrinkable type indoor
cable termination.
18.0 Multi-core cable Incoming Panel- External DC supply from DCDB, External AC
supply from ACDB, Remote Electrical Close and trip
termination box-- Purpose operation,
Inter trip operation from upstream 33 kV circuit, Breaker
spare
aux. Contacts. Spare contacts of L/R Switch and Spring
Charge
Limit Switch etc.
Feeder Panel -- Remote electrical close/trip operation,
remote
indication for close, trip , spring charged and trip ckt
supervision,
status of L/R switch, Local annunciation for remote close and
trip
operation, Breaker spare aux. Contacts.
19.0 Operation Counter Each breaker shall be provided with operation counter.
21.0 Insulated spacer It shall be made of insulated fibre glass materials shall be
provided in High voltage system, to protect from absorption
of
moisture present in the air.
22.0 PT selection scheme Each Incoming and outgoing breaker panel shall be
provided with suitable manually operated selector switch
having break before make type contacts including
necessary wiring for selection of voltage from different PT
secondary‘s available for connection with energy meters.
Each panel should be provided with 3 PT scheme and
current rating of the PT Selector Switch should be
minimum 16 Amp. Voltmeter of incoming breaker panel shall
be connected directly from respective PT secondary of
associated unit.
Electromagnetic Relay thermal rating shall be such that the fault clearance
23.1.8 Compatibility times
on any combination of current and time multiplier settings
shall
not exceed the thermal withstand capability of the relay.
Compliant to EMC directives as per IEC.
23.7.1 For each breaker panel To be provided with anti pumping relay/contactor (94),
(plug-in type contactor will not be accepted)
23.7.2 Auxiliary relays, coupling To effect interlocks and to exchange signals of status &
relays, transducers etc. control from remote.
24.0 Additional Requirement The schematic diagram of control and indication circuit on a
durable sticker shall be fixed in a suitable place in Incomer
and
feeder panels and Annunciation scheme in the Bus Coupler
panel.
The wiring arrangement, position of fuse, TBs etc, in the
panel should be such that each and every connection can be
accessed easily. Fuse tops can be opened /inserted easily.
Only ring type sockets should be used for wire termination in
TB/
Relays/ Meters/TTB etc. Fork type socket can be used in
Annunciator only.
Separate switch to be used for cubicle light instead of
Door
switch.
Circuit Label incorporating identification, information of
incoming/outgoing/bus coupler breaker shall be provided.
Connection diagram plates for the PT and CT shall be provided
as per provision in the relevant IS.
All name, rating , circuit label, connection diagram plate
shall be fixed with screws or by riveting instead of fixing by
adhesive.
26.2 Space heater location Two nos. each in Breaker & HV cable compartment
to be mounted on an insulator.
26.3 Space heater Monitoring One AC Ammeter with 0-1.0Amp range shall be
provided in series with the heaters to monitor the current
drawal of the Heaters. Size :96x48mm.
and 100mmX150mm(approx).
28.2 Lettering
Identification plates/labels
28.4 at Approved design (not stickers)
each cubicle and each
instrument
28.5 On front top door of panel
Manufacturer name plate
Operating sequence
31.3 Paint shade RAL 7032 for external & internal surface
31.4 Paint thickness Minimum 80 microns
32.0 Type Test
32.1 Type Tests The product must be of type tested quality as per all tests in
IEC/Indian standards. Such tests shall be done at any NABL
accredited laboratory.
32.2 Type test report validity Last five years from due date of bid submission
period
A . Switchgear Panel (with circuit breaker installed)
32.3 Type test report to be a. Lightning Impulse Voltage withstand Test
submitted along with the bid b. H.V. dry 1 min power frequency withstand test
c. Short time and peak withstand current test
d. Short circuit test with basic duties
e . Single phase breaking capacity test.
f. Cable charging breaking current test
g. Temperature Rise test
h. IP Test
i. Internal Arc Test as per IEC 62271-200
j. Horizontal Acceleration due to seismic force (if
available)
B. Circuit Breaker
a. Mechanical Endurance Test as per M2 Class of
IEC
C. Current Transformer
a. Short Time Current Test
b. Impulse Voltage Withstand Test
c. Temperature Rise Test
D. Potential Transformer
a. Impulse Voltage Withstand Test
b. Temperature Rise Test
E. -Copies of test certificates in respect of
following
bought out items:-
a. Vacuum Interrupter.
b. Insulators
c. Bus Bar Material
d. Terminal connectors
e. KEMA / CPRI Certification for relay/IED i.r.o.
IEC61850 compliance
Note : All the type test report on Switchgear
Panel
& Circuit Breaker to be conducted with
offered Vacuum Interrupter.
a ) Dimensional Checks
Complete Switchgear Panel b) Operational Tests
test c) Primary Injection Tests
38.1 d) Calibration Tests on Relays and Instruments
e) Power frequency Withstand Test
f) Insulation Test
g) Contact resistance test of Primary joints
h) Power frequency Withstand Test on secondary Wiring
Routine tests.
18.4kA Circuit Breaker test a) Operation test.
( six copies of test report to
be b) Dielectric Test on the main circuit.
38.2 submitted with Offer) c) Dielectric tests on controls and auxiliary circuits.
d) Measurement of resistance of the main circuit.
e) Timing test
f) Design and visual checks
g) Test Certificate for all resin cast/moulded components of
circuit breakers whose partial discharge measurement are
specified in the relevant IEC (No. 62271-100, Clause No.6.2.9)
38.5
Protection Relay Tests a. Relay Pick-up test for all functions and phases
( six copies of test report to
be b. Relay timing test for all functions and phases
submitted before with
Offer) c. Conformance Test as per IEC 61850
-----------------------------------
ANNEXURE – A
1.0 Switchgear
1.1 Type Metal clad, air insulated with VCB type circuit
breaker
1.2 Service Indoor
1.3 Mounting Free standing, floor mounted
1.4 System voltage 11KV
1.5 Highest System voltage 12 KV
1.6 Frequency 50HZ, ± 3%
1.7 Phase 3
1.8
Rated current @ 50 DEG C
1.9 ambient 800 Amp.
1.10 Short time rating for 3 sec. 18.4KA
1.11 Insulation level (PF rms / impulse 28 / 75 KV
peak)
1.12 System ground Solidly earthed
1.13 Enclosure degree of protection IP 5X for high and low voltage compartment
1.14 Bus bar – Main @ 50 DEG C 1600A, Current Density 1.6 Amp/sq.mm.(Max)
ambient
1.15 Material electrolytic copper, tinned /Silver plated
1.16 Bus Bar sleeve Full voltage sleeved with shrouds on joints
1.17 Bus identification Colour coded (R-Y-B)
To be capable to safely withstand stress due
1.18 Bus end connection to
max. Short circuit current and thermal expansion.
Necessary provision to be made for testing
current
transformer primary by removing insulated
portion
without difficulty.
1.19 Temperature rise above Ambient 40DEG C for conventional joints, 55DEG C for
silver plated joints
1.20 Riser Bus electrolytic copper, tinned /Silver plated,
800A, Current Density 1.6 Amp/sq.mm.(Max)
For the design and erection of Busbars the following minimum clearance shall be
1.21 observed
1.25 Hardware GI
1.27 Power and control cable entry From bottom for Power Cable. For control cables
through Remote Terminal Box installed at the
backside of the Panel.
2.0 Circuit Breaker
2.1 Type of isolation & Drawout Horizontal isolation & Horizontal Drawout.
3.2. Type Triple core, Dual ratio, Cast resin, Indoor type .
Marking on primary and secondary terminal as per
requirement of IEC 60044-1, IS 2705 and shall
be
indelibly marked. The secondary terminals shall
have screw type terminals.
4.2. Type Dual core, Dual ratio, Cast resin, Indoor type.
Marking on primary and secondary terminal as per
requirement of IEC 60044-1, IS 2705 and shall
be
indelibly marked. The secondary terminals shall
have screw type terminals.
5.9 Primary and secondary fuses HRC current limiting type, primary fuse
replacement shall be possible with VT in
withdrawn
position
Annexure - B
Standard Make of Relay and Fitments
VCB Panel Manufacturer should be the VCB Manufacturer.
Annexure-C
Legend of Devices associated with Multi panel Shunt trip vacuum Circuit Breaker
Annexure D
Sl Device Quantity
no.
Incomer Feeder Bus coupler
1. Numerical O/C & E/F Relay 1 No. 1 No. Nil
2. Trip Relay 1 No. 1 No. 1 No.
3. AC Supervision Relay Nil Nil 1 No.
4. Annuanciator 1 No. 1 No. 1 No.
5. AC Ammeter ( CT operated ) 3 No. 3 No. Nil
6. AC Voltmeter 1 No. Nil Nil
7. DC Voltmeter Nil Nil 1 No.
8. Ammeter ( Heater Ckt.) 1 No. 1 No. 1 No.
9. Current Transformer 3 No. 3 No. Nil
10. Potential Transformer 1 Set Nil Nil
11. Energy meter 1 No. 1 No. Nil
12. TTB 1 No. 1 No. Nil
13. Indicating Lamp 6 No. 6 No. 4 No.
14. MCB ( DC Ckt) 1 No. Nil 1 No.
15. MCB ( AC Ckt, 16 Amps) 1 No. Nil 1 No.
16. MCB ( Motor ckt.) 1 No. 1 No. 1 No.
17. 3 Position PT Selector Switch (16 Amps) 1 No. 1 No. Nil
18. Voltage Selector Switch 1 No. Nil Nil
19. Electronic Buzzer (DC Volt operated) Nil Nil 1 No.
20. Electronic Buzzer (AC Volt operated) Nil Nil 1 No.
21. Heater with controller 1 Set 1 Set 1 Set
22. T-N-C Switch 1 No. 1 No. 1 No.
23. Local – Remote Switch 1 No. 1 No. 1 No.
24. Push Button for Emergency Trip 1 No. 1 No. 1 No.
25. Push Button for Relay reset 1 No. 1 No. Nil
1 No. for every three
26. Spring Charging Handle Panel.
No. for every three
27. VCB Operating Handle 1 Panel
28. HRC Fuse & Link As required As required As required
29 Trip circuit S/V relay 1 no. 1 no. 1 no.
30 Push button for Annunciator Accept & Reset 2 nos. 2 nos. 2 nos.
31 DC supervision relay 0 0 1 no.
NB: The Bidder has to include list of other Items for the Equipment to meet our Technical
requirement.
Annexure-G
1. General :
Name of the Company
Office address
Factory address
2. Panel Make
Type & Designation
Application
Standard
Rated Voltage
Highest Voltage
Normal Current
Frequency
STC for 3 Sec.
Breaking Capacity
Making Capacity
Power frequency withstand voltage
Impulse withstand voltage
AC Aux. Voltage.
DC Aux. Voltage
Degree of Protection for HV & LV Compartment
Thickness of metal sheet ( mm ).
For load-bearing member
For Doors & covers
Dimension of Incomer Panel in mm ( H x W x D )
Dimension of Outgoing Panel in mm ( H x W x D )
Dimension of Bus-Coupler &
Trunk Panel in mm ( H x W x D )
Single feeder panels to be supplied with Bus
Bar for connection with adjacent Incomer /
Bus Coupler / Feeder. [Yes/ No ]
HV Cable termination height in the cable
compartment
3. Bus Bar
Material Shape
Cross sectional area of main
Bus. Cross sectional area of
Riser. Type of plating
Normal Current currying capacity
STC for 3 Sec.
Rise over ambient at normal current
Current density for main Bus & Riser
Phase to Phase clearance
Phase to ground clearance
Type of insulation
Colour Identification
6. Vacuum Bottle
Make
Rated voltage
Type and model no.
Normal current
Breaking capacity
Making capacity
STC for 3 Sec.
Maximum contact separation length
Minimum Mechanical life in no. of operation
Minimum Electrical Life in no. of operation at
rated normal current
Minimum Electrical Life in no. of operation at
rated full short circuit current
Power frequency withstand voltage (dry)
Impulse withstand voltage
Contact material
Type of plating
Contact pressure
7. Current Transformer
Make
Reference Standard
Type
Voltage Frequency
Insulation level
Class of insulation
Ratio (Incomer & Feeder)
Class of accuracy (Incomer & Feeder)
Burden (Incomer & Feeder)
STC for 1 Sec.
ISF of Metering Core at lower ratio
Vk & Magnetising Current(at lower ratio)
Fixing Arrangement
8. Potential Transformer
Make
Reference Standard
Insulation level
Class of insulation
Type
Frequency
Winding connection
Type of Core connection
Ratio
Class of accuracy
Burden per Phase
Over Voltage Factor for 8 hrs.
Fixing position.
Fixing arrangement
Primary Fuse rating
9. O/C & E/F Relay
Make
Type Model no.
Ordering Code
10. Trip Relay
Make
Type
Model no.
Whether Electrically Resettable(Yes/No)
11. Digital Ammeter ( CT operated ) Make
Type
Size
Basic CTR
Accuracy class
AC Aux. voltage
Fixing type.
12. Digital Ammeter ( Heater circuit )
Make
Type
Size
Current range Accuracy
class AC Aux. voltage
Fixing type.
13. Digital Volt meter ( PT operated )
Make
Type
Size
PTR
Accuracy class
AC Aux. voltage
Fixing type.
14. Analog Voltmeter ( DC Circuit )
Make
Type
Size
Accuracy class
Fixing type.
15. Energy meter
Make
Type
Model no.
16. Terminal connector
Make
Type
Size
17. Control Switch
Make
Type
Contact configuration
AC & DC Current rating
AC Voltage rating.
18. Spring Charge Limit Switch
Make
Type
No of contact ( NO + NC )
No of spare contact ( NO + NC )
AC & DC Current rating
AC Voltage rating.
19. Local Remote Switch.
Make
Type
Contact configuration
AC & DC Current rating
AC Voltage rating.
20. Spring charging motor
Make
Type
Rated AC Voltage
Rated wattage
AC Voltage variation for operation
21. Operation counter
Make
Type
Operation count range
22. Space heater
Make
Type
Rated AC Voltage
Wattage
23. Thermostat
Make
Setting range
24. Indication Lamp
Make
Type
25. Auxiliary contact switch
Make
Type
No of contact ( NO + NC )
No of spare contact ( NO + NC )
AC & DC Current rating
AC Voltage rating.
26. Annunciator
Make
No of window.
Aux voltage
No of inbuilt push switch.
27 Voltage selector switch
Make
Type
28 PT selector switch
Make
Type
Current Rating
29 TTB
Make
Type
Size
30 Terminal Block
Make
Type
31 MCB
Make
Type
32 Fuse & Link Unit
Make
Type
33 HRC Fuse
Make
Type
Operation Instruction
b) Chart
---------------------------------------
ANNEXURE-H
GTP for Numerical Feeder (Non directional)
Protection Relay
Bidders
Sl. No. Feature and Function response
1.1 Make
Type
Ordering code (with supporting
documents)
1.2 Conformance to
i. IEC255-4
ii. IEC 61850
b. Withstanding capability of
Electromagnetic interference as per
relevant part of IEC 61850
17. Mounting
18. Watchdog
b. CT Ratio setting
c. Earth fault current with time
delay IEC
Curves, 2nd stage for instantaneous
trip(less than 50 ms)
d. High set with delay
e. IEC Curves for all O/C and E/F
have
user selectable?
a. No. of Digital Output
20. Contacts
b. Contact rating
Lifespa
24. n
25. Compliance to Type Test
26. Communication Port
a. Rear port- details
b. Front port-details
Whether Communication Ports
27. are
native to the Relay
Protocol supported for Rear
28. Port
ANNEXURE- J
01 Manufacturer Name
02 Type and
designation(Literature
to be submitted)
3. Electrical reset
4. Mounting
5. Operating Time
7. No. of NO Contact
8. No. of NC Contact
ANNEXURE-E
Technical Specification for Non-directional over current and earth fault relay
Operational The operation of Relay shall be possible both locally from the Switchgear and
4. Philosophy remote &
Local Work station. The local position shall be displayed in remote / local
workstation and
operation shall be blocked if the switch is in Local. Clear control
remote priorities shall
prevent initiation of operation of a single switch at the same time from more
than one of the
various control levels and there shall be interlocks among various control levels.
The priority
shall always be with the lowest enabled control level. Relay accuracy shall not be
affected
by system frequency fluctuation.
5. Status/Optical 1. Minimum 7 number status inputs are required
Inputs/Digital
inputs 2. All status inputs should be 30 V DC.
3. Setting group is required to be changed with any Digital input status.
4. Trip circuit supervision with DI status
The digital inputs shall be acquired by exception with 1ms resolution.
5. Contact
bouncing in digital inputs shall not be assumed as change of state.
Relay should have comprehensive self diagnostic feature with remote
6. indication of
relay failure and alarm shall be generated without tripping of circuit
7. Provision of Testing output relays without any current injection.
8. No. of programmable LEDs- at least 4 nos. with latching option.
Memory and The relay setting and programming should be stored in EEPROM so that
7. Recording 1. during
Feature Aux. Power failure the said data is not lost.
Relay should have event log, trip log and DR record. All logs should go in
2. to history.
All tripping of relay should initiate DR in auto without extra binary
3. input. Triggering
of DR with binary input should be user configurable.
The last 2 fault DR records should be in flash memory and DR will not
4. erase in case
of DC supply fail for more than 2 days.
Should be able to record at least 5 Oscillographic disturbances and 5
5. fault records
and 250 event records.
Minimum Four no. of latest trip log with cause of trip should be stored in
6. memory
along with date and time stamping. The memory should not be lost
with the
switching off of DC.
The relay should have fault-recording feature with current waveform
7. and Digital
Input status. The fault waveform should consist of minimum four
current waveforms
of three phase current and zero sequence current and DI status.
Triggering time for
Pre and Post should have user selectable. This record should be in flash
memory
for minimum 7(seven) days even after switching off the DC supply.
8. The fault should be date and time stamped.
9. Communication protocol IEC 61850.
30 V DC to - 25% to + 10%, 2 wire unearthed system. Necessary software shall
8. Auxiliary Supply be in-built
for proper shutdown and restart in case of power failure. Auxiliary supply
burden will be
around 20Watt.
9. Rated CT/PT 5/1 Amp(User selectable) , CTs used to be protection class
secondary
10. Rated frequency 50 HZ +/- 3%
11. Ambient condition 1. Operating ambient temperature upto 55 Deg C
2. Operating Humidity upto 100 %
Relay shall meet the requirement for withstanding electromagnetic
3. interference
according to relevant parts of IEC 61850. Failure of single component
within the
equipment shall neither cause unwanted operation nor lead to a complete
system
breakdown.
Module and
12. Mounting 1. Relay should be flush mounted type
If module is draw-out type then it should have CT shorting facility of
2. make before
break type.
3. Mounting in switchgears located in non AC rooms.
Galvanic isolation between field connection and relay hardware should be
4. there.
Watchdog and The relay should have facility to monitor the healthiness of its circuits and
13. self components by
own monitoring system. In case of any problems, the alarm should be generated
monitoring by one of
the output contacts. The alarm as soft signal to be sent to SCADA
system as well.
Necessary support documentation explaining the self diagnostic feature shall be
furnished.
Relay
16. software and 1. The relay should have native IEC 61850 Communication Protocol.
Man Machine
Interface 2. Should have password protected key padlock.
Necessary software for relay setting , retrieving DR, event log, trip log
3. should be
supplied by the Bidder. Necessary License is to be issued for
WBSEDCL, if
required.
Bidder has to supply communication hardware for relay setting, DR
4. downloading
from front port. This device should be compatible to USB/Ethernet
port.
It shall be possible to transfer the data stored in the DFR to
5. computer on
IEEE/COMTRADE format. The data format shall be compatible for
dynamic
protection relay testing on relay test kit. COMTRADE data viewing
software to be
provided.
6. Multiuser/Corporate license for installation on minimum 7 nos. of PCs.
Date and Time stamping with faults and record. The clock should be powered
17. Date and time from internal
cell and should not required setting after every DC switching. The internal cell
life minimum
5 years. Time synchronization by IRIG-B or SNTP. For time synchronization
through SNTP
is to be provided from clock signal coming from RTU. In case of IRIG-
B, time
synchronization will be done with GPS clock signal from GPS receiver located at
substation.
Manuals, Drawings The relays should be supplied with manuals with all technical and
19. and 1. operating
Literature instructions.
All the internal drawings indicating the logics and block diagram details
2. explaining
principle of operation should be given at the time of supply.
3. Mapping details shall be submitted in IEC format.
As part of this offer, Bidder shall have to provide necessary support during
20. Assistance in integration of
commissioning relays with the third party SCADA system which will be commissioned in future.
Each IED shall be clearly marked with manufacturer‘s Name, type, serial
26. Name Plate and no. and
electrical rating data. Name plates shall be made of anodized aluminium
marking with white
engraving on black surface.
27. Performance Relays will be guaranteed for the period of five years from the date of last
Guarantee dispach.
Any problem in the said period should be attended free of charge
inclusive of repair/replacement of relays/ component (both H/W, S/W).
Type
28. Test Dielectric Withstand Test—IEC 60255-5
High Voltage Impulse Test, class III --- IEC 60255-5(5kV peak, 1.2/50
micro Sec;3
Positive and 3 negative shots at interval of 5 Sec.)
DC Supply Interruption ---- IEC 60255-11
AC Ripple on DC supply ---- IEC 60255-11
Voltage Dips and Short Interruptions --- IEC 61000-4-11
High frequency Disturbance ---- IEC 60255-22-1, Class III
Fast Transient Disturbance ---- IEC 60255-22-4, Class-IV
Surge withstand capability ---- IEEE/ANSI C 37.90.1(1989)
Degree of Protection
Electromagnetic compatibility
Mechanical stress/vibration test
Temperature withstand
Type test reports for the above tests shall be submitted for the approval of
WBSEDCL along
with Tender. Wherever the above mentioned standards and IEC 61850 overlap,
the latter
will prevail.
Offer with all relevant documents for numerical relay may be submitted
30. Offer for relay with different
make as per Annexure-B alongwith the Bid but after placement of order,
drawing for
approval needs to be submitted with only one type of accepted offered relay.
ANNEXURE-I
STANDARD
TECHNICAL SPECIFCATION
FOR
FOR
11 KV FEEDER METER
TECHNICAL SPECIFCATION FOR 3PHASE 4 WIRE CT, PT OPERATED 3PHASE LAG PLUS
LEAD ONLY FULLY STATIC AMR COMPATIBLE TRI-VECTOR ENERGY METERS FOR 11
KV FEEDER.
1.0 SCOPE
Design, manufacturing, testing, supply and delivery of AC, 3 Phase, 4 Wire, CT,PT operated lag
plus lead only fully Static and AMR compatible Tri-Vector Energy Meters for measurement of
different electrical parameters listed elsewhere in the document including Active Energy
(kWh/MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/MVAh) etc.
2.0 APPLICATION
IS-14697:1999(2004) Specification for AC Static Transformer operated Watt Hour & VAR-
Hour meters (class 0.5S);
IS-15959:2011 Data Exchange for Electricity Meter Reading Tariff & Load Control – Companion
Specification
IEC 62052-11 Electricity metering equipment (AC) –General requirements, tests and test
conditions - Part 11: Metering equipment;
IEC 62053-22 Electricity metering equipment (AC) –Particular requirements - Part-22: Static
Meters for Active Energy (Class 0.5S);
IEC 62053-23 Electricity metering equipment (AC) –Particular requirements - Part-23: Static
Meters for Reactive Energy;
Guidelines on ―Data Exchange for Electricity Meter Reading, Tariff and Load Control –
Companion Specification‖
IEC 62056-21 Electricity metering: Data exchange for meter reading, tariff and load control-
Part 21:
Direct local data exchange
IEC 62056-31 Electricity metering: Data exchange for meter reading, tariff and load control -
Part 31:
Local Area Network data exchange
IEC 62056-61 Electricity metering: Data exchange for meter reading, tariff and load control-
Part 61:
Object identification system (OBIS)
The equipment meeting with the requirements of other authoritative standards, which ensure
equal or better quality than the standard mentioned above, also shall be considered; in case of
conflict the Guidelines on ―Data Exchange for Electricity Meter Reading, Tariff and Load
Control – Companion Specification‖ enclosed with this document as annexure shall prevail upon.
4.0 GENERAL TECHNICAL REQUIREMENTS
2 FREQUENCY 50 Hz ± 5%
9 POWER CONSUMPTION The active and apparent power consumption, in each voltage
circuit, at reference voltage, reference temperature and
reference frequency shall not exceed 1. 5 W and 8 VA.
Under normal condition of use, winding and insulation shall not reach a temperature,
which might adversely affect the operation of the meters. IS14697:1999(2004) should be
followed.
The meters shall be suitably designed and treated for normal life and satisfactory
operation under hot & hazardous tropical climate conditions and shall be dust and vermin proof.
All the parts & surface, which are subject to corrosion, shall either be made of such material or
shall be provided with such protective finish which provides suitable protection to them from
any injurious effect of excessive humidity.
The case, winding, voltage circuit, sealing arrangements, registers, terminal block,
terminal cover & name plate etc. shall be in accordance with the relevant standards. The meter
should be compact & reliable in design, easy to transport & immune to vibration & shock involved
in the transportation & handling. The construction of the meter should ensure consistence
performance under all conditions especially during heavy rains / very hot weathers. The
insulating materials used in the meter should be non-hygroscopic, non-ageing & have tested
quality.
The meter should be housed in a safe, high grade, unbreakable, fire resistant, UV
stabilized, virgin Polycarbonate/ High grade engineering plastic/Thermosetting Plastic casing of
projection mounting type. The meter cover should be transparent, for easy reading of
displayed parameters, and observation of operation indicators. The meter base may or may not
be transparent, but it should not be black in colour. The meter casing should not change
shape, size, and dimensions when subjected to 200 hrs on UV test as per ASTMD 53. It should
withstand 650 deg. C. glow wire test and heat deflection test as per ISO 75.
Meters must be supplied with 2 (two) nos. manufacturers‘ seals between meter base and
meter cover at both the sides.
Both the communication port (Optical and RS 485 port) should have proper sealing
arrangement.
The bidder shall submit relevant documents (collected form Meter Manufacturer)
regarding the procurement of polycarbonate material. The polycarbonate material of only the
following manufacturers shall be used.
a) G.E. Plastics/Sabic: LEXAN 943A or LEXAN 143 or equivalent for Meter & Terminal
cover, and LEXAN 503R or 500R or equivalent for base.
Grade corresponding to
b) BAYER/SABIC : above
d) MITSUBISHI : -Do-
e) TEJIN : -Do-
f) DUPONT : -Do-
The meter cover should be fixed to the meter base (case) with Unidirectional Screws,
so that the same cannot be opened by use of screwdrivers. The meter shall withstand external
magnetic influence as per latest amendments of CBIP Technical Report No. 304.
The terminals may be grouped in a terminal block having adequate insulating properties
and mechanical strength. The terminal block should be made from best quality non-hygroscopic,
flame retardant material (capable of passing the flammability tests) with nickel plated brass
inserts / alloy inserts for connecting terminals.
The terminals in the terminal block shall be of adequate length in order to have proper
grip of conductor with the help of screw adjustable metal plates to increase the surface of
contact and reduce the contact resistance. The screws shall have thread size not less than M 4
and head having 4-6mm. diameters. The screws shall not have pointed ends at the end of
threads. All terminals and connecting screws should be of tinned/nickel plated brass material.
The internal diameter of terminal hole should be minimum 5.5 mm. The holes in the
insulating material shall be of sufficient size to accommodate the insulation of conductor also.
The meter shall be suitable designed for satisfactory operation under the hot and
hazardous tropical climate conditions and shall be dust and vermin proof. All the parts and
surface, which are subject to corrosion, shall either be made of such material or shall be
provided with such protective finish, which provided suitable protection to them from any
injurious effect of excessive humidity.
13.0 MANUFACTURING PROCESS, ASSEMBLY AND TESTING
Meters shall be manufactured using latest and ‗state of the art‘ technology and
methods prevalent in electronics industry. The meter shall be made from high accuracy and
reliable surface mount technology (SMT) components. All inward flow of major components and
sub assembly parts (CT, PT, RTCs / Crystal, LCDs, LEDs, power circuit electronic components
etc.) shall have batch and source identification. Multilayer ‗PCB‘ assembly with ‗PTH‘ using
surface mounted component shall have adequate track clearance for power circuits. SMT
component shall be assembled using automatic ‗pick-and-place‘ machines, Reflow Soldering oven,
for stabilized setting of the components on ‗PCB‘. For soldered PCBs, cleaning and washing of
cards, after wave soldering process is to be carried out as a standard practice. Assembly line of
the manufacturing system shall have provision for testing of sub-assembled cards. Manual
placing of components and soldering, to be minimized to items, which cannot be handled by
automatic machine. Handling of ‗PCB‘ with ICs / C-MOS components, to be restricted to bare
minimum and precautions to prevent ‗ESD‘ failure. Complete assembled and soldered PCB should
undergo functional testing using Computerized Automatic Test Equipment.
Fully assembled and finished meter shall under go ‗burn-in‘ test process for 24
Hours at 55 degree Celsius (Max. temperature to not exceed 60 degree Celsius) under base
current (Ib) load condition.
Test points should be provided to check the performance of each block/stage of the
meter circuitry.
RTC shall be synchronized with NPL time at the time of manufacture. Meters testing
at intermediate and final stage shall be carried out with testing instruments, duly calibrated
with reference standard, with traceability of source and date.
Meter shall have Scroll Lock facility to display any one desired parameter
continuously from display parameters.
Auto display cycling of each parameter should be minimum 10-12 Seconds. The time
between two auto display cycles shall be 100-120 sec. OBIS code in display is not required.
It should be possible to easily identify the single or multiple displayed parameters
through symbols/legend on the meter display itself or through display annunciation.
AUTO MODE:
i) LCD Test
xix)Self Diagnosis
xxiv)Self Diagnosis
i) Meter Sl No
The register shall be able to record and display starting from zero, for a minimum
of 2500 hours, the energy corresponding to rated maximum current at reference voltage and
unity power factor. The register should not roll over in between this duration.
High resolution registers required in display min 4 digits (for kWh) and 6 digit
(for MWh) after decimal in case of Energy.
No decimal is required for main KWh, KVAh, KVarh (lag & lead) display. If display
is in MWH, digits after decimal may go up to KWH registration.
Push button mechanism should be of high quality and should provide trouble free
service for a long span of time. Up and Down scrolling facility should be there for Push Button
Mode. If there is separate button for MD reset, it should also have scrolling facility.
MD RESET OPTION
i) Billing Date at 00:00 Hrs of 1st day of the Month (Programmable)
ii) Push button
iii) By Authenticated Command from BCS through HHU or directly from PC/REMOTE
MD reset button should have proper sealing arrangement. Specific operation should
be available in downloading data.
16.0 PERFORMANCE UNDER INFLUENCE QUANTITIES
a) Hand Held Unit (HHU) or directly through BCS and this shall authentication
from BCS for individual meter.
The meter should have facilities to record Active, Apparent Energies and MD with a
facility of 8 time zones. The time zones should be user programmable through authenticated
command from BCS with the help of HHU. At present only 3 (Three) TOD zones to be activated in
following manners;
TOD – 1 06:00 Hrs to 17:00 Hrs
It should be possible to read the meter-display visually and with MRI and in
absence of input voltages with the help of internal battery for display in power off condition
or external battery pack/PPU. The interface should be inductive coupling.
22.0 BASE COMPUTER SOFTWARE (BCS): Exclusively used for the manufacturers
meter only.
The BCS should be user friendly. Windows 8 / 7 based BCS shall be supplied. The
data transfer should be reliable and fraud proof. BCS should give all details pertaining to billing
and load survey data. The meter condition details should also be transferred into the BCS
including abnormalities/anomalies of voltage current conditions or tamper conditions which can
occur due to mistake in connections or intentionally done for the purpose of tamper.
The software should show electrical conditions existing at the time of reading the
meter in tabular forms as well as in graphical format (Phase diagram) i.e. Phase diagram is
required for voltage, current & PF only.
All the information about energy, maximum demand and their respective TOD
register readings, billing register readings and billing history readings should be shown in a
manner which user can understand quickly, preferably in tabular format.
All the load survey data should be available in numerical as well as graphical format.
It should also be possible to view this data in daily, weekly and monthly formats. The load
survey graph should show the respective values.
All the information about tamper events should be accompanied with date and time
stamping along with the ‗SNAPSHOT‘ (details) of the respective electrical conditions. This
information should be displayed in the sequence in which it happened, in cumulative format as
well as in summary format. The cumulative format should segregate a particular tamper
information and summary report should show count of tamper occurrence, restoration and the
duration for which meter has remained under tamper condition.
In BCS, tamper events must be followed as per Table 32-38 as per IS 15959.
However, final tamper logic will be given at the time of sample testing. Before issuing the
purchase order bidder has to confirm with letter to comply the said tamper logic. In display,
first tamper occurrence & last tamper occurrence & restoration with date & time and total
tamper count must be available.
The BCS should have the facility for ASCII conversion of all recorded meter data.
There should be user friendly approach for viewing meter data for the reading collected now or
for the reading collected in the past. All information about a particular consumer should be
segregated and available at one place so that locating any consumer's past data is easy. It
should be possible to locate/retrieve data on the basis of one of the following particulars:
a) Consumer ID/Number.
d) Location.
The BCS shall have multi level password for data protection and security. The first
level should allow the user to enter the system. The different software features shall be
protected by different passwords. The configuration of passwords should be user definable.
The software installed on one PC should not be copy-able on to another PC.
It is very important that the BCS has the feature to export available data
to ASCII format for integrating with the WBSEDCL billing system. Here again a wizard
should be available whereby user can select file format (for ASCII), what data to
export, the field width selection (whether 8 characters or 10 characters, to include
decimal point or not, number of digits after decimal point etc).
Help should be available with the software so that user can use all the features
of the software by just reading the Help contents.
23.0 LOAD SURVEY:
The meter should be capable of recording load survey data of Phase wise Voltage,
Phase wise current, Average Power Factor, Active Energy and Apparent Energy for a period of
minimum 45 days for 15-minute integration period. Real time & date should be shown in all the
load survey graphs and table.
The meter should be capable of measuring Fundamental Energy as well Total Energy
i.e. Fundamental plus Harmonics energy. Total Energy shall be made available on meter-display
and the same only shall be used for billing purpose. Fundamental Energy should be provided in
display.
The Fundamental Energy shall be logged in the meter memory and be capable
of downloading to the BCS through the HHU and be available for viewing at the BCS
end.
Every meter shall have a nameplate clearly visible and indelible and distinctly
marked in accordance with the relevant Standard mentioning ―Category – A‖. The following
information should appear on an external plate attached to the meter cover.
The meter shall also store name plate details as given in the Table - 30 of IS
15959:2011
26.0 COMMUNICATION CAPABILITY
The meter shall be provided with two ports for communication of the
measured/collected data. The hardware port (with sealing facility) compatible with RS 485
specifications which shall be used for remote access through suitable Modem and an Optical
port complying with hardware specifications detailed in IEC-62056-21. This shall be used for
local data downloading through a DLMS compliant HHU or direct through BCS.
Both ports shall support the default and minimum baud rate of 9600 bps.
Optical Cord (i.e. Optical Port of Meter to PC) must be USB type.
Data downloading time from meter to HHU/PC should be within 2 min for meter
data (without load survey) and within 6 min for meter data with load survey.
To enable local reading of meters data a DLMS compliant HHU (DOS Based) shall be
used. The HHU shall be as per IS 15959:2011. It shall be compatible to the DLMS compliant
energy meters that are to be procured/supplied on the basis of the specification having at least
one USB communication port.
The meter shall work satisfactorily under presence of various influencing conditions
like External Magnetic Field, Electromagnetic Field, Radio Frequency Interference, Vibrations,
Harmonic Distortion, Voltage/Frequency Fluctuations, and Electromagnetic High Frequency
Fields etc. The meter shall be immune to abnormal voltage/frequency generating devices and
shall record the occurrence and restoration of all tampers and related snapshots as per
Annexure – G of IS 15959:2011
The meters should work even in the presence of any two Potential wires. Meter should
work correctly irrespective of phase sequence.
c) Direct by PC.
Meter should have a continuous and clear indication / annunciation in its display if
top cover is removed/open and even refixed (non roll over) and only cover open must be logged
in BCS without any restoration. Auto scroll display may be sacrificed for that COVER OPEN .
Minimum 400 numbers of events preferable (compartment wise) i.e. 200 no.
events for occurrences & 200 no. events for restoration with date & time and snapshot
should be available in the meter memory.
Final tamper Logic and threshold values as per our requirement will be supplied
at the time of Sample Testing. Before issuing the purchase order, Bidder has to
confirm with letter about compliance of the said Tamper Logic within stipulated period.
All the tamper information logged by the meter should be available in BCS with
snapshot, Date & Time as per Table 39 of IS 15959:2011 with occurrence and restoration.
Properly designed meter tamper logic with threshold value, should be provided and
clearly explained in the bid. The tamper logic should be capable of discriminating the system
abnormalities from source side and load side and it should not log / record tamper due to
source side abnormalities. The meter should be able to distinguish between HT PT fuse blowing
and Single Phasing and record the former.
Meters shall be fully type tested as per relevant Standard (IS 15959) (latest
version). The type test certificates should be submitted as per IS 15959 along with the offer.
Offer without Type Test Report shall be liable for rejection. The type test certificate shall not
be more than five years old from the Due date of submission of Tender.
All acceptance tests as per relevant standards shall be carried out at Meter
Manufacturer‘s Works in the presence of WBSEDCL representatives.
Further Purchaser shall reserve the right to pick up energy meters at random from
the lots offered and get the meter tested from NABL accredited lab. The supplier has no
right to contest the test results NABL accredited lab or for additional test and has to
replace/take corrective action at the cost of the supplier.
31.0 INSPECTION:
The inspection shall be carried out at any stage of manufacture, by the WBSEDCL
authorized representatives, with prior intimation to the supplier. The manufacturer shall grant all
reasonable facilities for testing free of charge for inspection and testing to satisfy the
purchaser that the materials to be supplied are in accordance with their specification.
The supplier shall keep the WBSEDCL informed in advance, about the
manufacturing program so that the arrangement can be made for inspection.
The representative / Engineer of the WBSEDCL attending the above testing shall carry
out testing as per relevant standards and issue test certificate approval to the manufacturer and
give clearance for dispatch.
The meter manufacturer shall have a comprehensive quality assurance program at all
stages of manufacture for ensuring products giving reliable, trouble free performance. Details of
the Manufacturer‘s quality assurance and test set up shall be furnished with the bid. A detailed
quality assurance program shall be finalized with the successful bidder during the award stage.
Bidder (collected from Meter Manufacturer) shall furnish following information along
with his bid:
b) Copy of system manual showing ‗QAP‘ (Quality Assurance Plan) as actually practiced
during manufacturing and final testing.
c) List of raw materials and critical components (ASIC chip, crystal clock, memory
register Chip, transformers, optical ports etc.) with their suppliers and procurement details.
f) Testing and calibration facility, date of calibration of test bench, manpower data of
bench
The Bidder (Meter Manufacturer) shall have at least the following testing facilities to
ensure accurate calibration:
b) Running at no load
c) Starting current test
d) Limits of error
e) Dial Test
g) Repeatability of error
h) Transportation test
i) Tamper Test
j) Ageing Test
The Bidder (Meter Manufacturer) shall give a detailed list of bought out items with name
of the manufacturer and details about quality control.
34.0 GUARANTEE
Equipment (Meter & CMRI) supplied shall be guaranteed for a period of 5 years from
the date of last despatch. Bidders shall guarantee to replace the meters, which are found to be
defective/inoperative at the time of installation, or become inoperative/ defective during
guarantee period. Replacements shall be effected within 1 month from the date of intimation.
Every meter shall have three fixing holes one at the top and two at the bottom. The top
hole shall be provided with a special clip at the back of the meter so that holding screw is not
accessible to the consumer after the fixing of the meters. The lower fixing screws shall be provided
under the sealed terminal cover. The requisite fixing screws shall be supplied with each meter.
Necessary provision may be kept for fixing the utility seal also.
The manufacturers seal provided with the meter should be of high quality with
tamper proof features.
36.0 Supply of Power Pack , HHU , Communication Cord (HHU to PC & Meter to PC)
For every 50 nos. of meters and part thereof one power pack (if not internal battery)
and one HHU (DOS based) & 50 nos. communication cord for each type ( Meter to CMRI and Meter
to PC USB type) should be supplied free of cost. The guarantee period of HHU and Power Pack will
be of 60 months from the date of last despatch.
After opening of the Techno-Commercial Bid, Bidder has to submit two nos offer
Meter within 15 days from the date of intimation to C.E.DTD,WBSEDCL for sample test in
presence of Bidder‘s representative along with inherent features, BCS and sample of seal, Type
Test Certificates, DLMS Certificate and with the test results and ISI Certificate, Tamper
Logic, Display Parameters List.
Offer with all relevant documents for Energy Meter may be submitted with
different make as per Annexure-B alongwith the Bid but after placement of order,
drawing for approval needs to be submitted with only one type of accepted offered
Energy Meter.
38.0 SCHEDULES:
The Bidder (collected from Meter Manufacturer) shall submit the following
schedules (as per Standard Format), which is part and parcel of the Specification.
Normally the offer should be as per Technical Specification without any deviation.
But any deviation from Specified Standards, Specified Test Requirement, Technical
Specification felt necessary to improve performance, efficiency and utility of
equipment must be mentioned in the ‘Deviation Schedule’ with reasons of such
deviation. Such deviation suggested may or may not be accepted. Deviations not
mentioned in Deviation Schedule will never be considered.
Schedule - A
Manufacturer‟s
Sl.No. Description Required Specification
particulars
1 Current Element
Measurement /Computing
2 chips
3 Memory chips
4 Display modules
5 Communication modules
6 Optical port
7 Power Supply
8 Electronic components
9 Mechanical parts
10 Battery
11 RTC / Micro controller
SCHEDULE-C
Pre-Qualification Conditions for HT Static Meters
SCHEDULE - D
Component Specifications:
The meters shall be designed and manufactured using SMT (Surface Mount
Technology) components, except for power supply components, LCD etc., which are PTH
type. All the material and electronic power components used in the manufacture of the
meter shall be of highest quality and reputed makes so as to ensure higher reliability, longer
life and sustained accuracy.
Sl. Component
Requirement Make / origin
no. Function / Feature
IS 15959:2011
2. Current - IR 1.0.31.7.0.255 3
3. Current – IY 1.0.51.7.0.255 3
4. Current – IB 1.0.71.7.0.255 3
NOTES : -
The items at Sl No 5), 6) and 7) are for 3Ф / 4W system of measurement with
NEUTRAL as reference point.
Signed Power factor – (+ indicates lag) and (- indicates lead).
The parameters at Sl No 18) to 22) hold cumulative values at that instant from the
date of manufacturing or installation of meter as the case may be.
The above list is identified for the purpose of communication to HOST or HHU.
The utilities may choose, based on needs, additional parameters for display purpose
ONLY. Item at Sl No 21) refers to the Billing Period Counter
Item at Sl No 23) - Data type to be same as for attribute 2 of IC 8, Clock.
IS 15959:2011
Table 28 : Block Load Survey Parameters for Class C Meters (Required in Class A Meter)
NOTES : -
1 ) The parameters listed in this table are for load survey purpose and are logged
as per the block period time.
2 )The parameters at Sl No 2) to 9) are the average values during the block
period time and stored at the end of that time block.
3 )The parameters at Sl No 10) to 13) are the actual energy consumption during that
time block.
4 )Capture objects for 3 Ф / 4W are items at Sl No 1) to 7) and 10) to 13)
5 )Support for Selective access shall be as defined in Section 11.3
IS 15959:2011
Table 29 : Billing Profile Parameters for Class C Meters (Required in Class A Meter)
23. MD – kW 1.0.1.6.0.255 4 / 2 ,5
33
. MD – kVA – TZ1 1.0.9.6.1.255 4 / 2 ,5
34
. MD – kVA – TZ2 1.0.9.6.2.255 4 / 2 ,5
35
. MD – kVA – TZ3 1.0.9.6.3.255 4 / 2 ,5
36
. MD – kVA – TZ4 1.0.9.6.4.255 4 / 2 ,5
(Clause F-1)
NOTE : - For item Sl No 4), a value of ―0‖ indicates 3P-3W; a value of ―1‖ indicates 3P-4W
Table 31 Programmable Parameters
(Clause F-2)
NOTES : -
1 . The parameters are programmable by the utility engineers with required access
rights.
2 . Unit for Demand Integration Period and profile capture period is in ―seconds‖.
3 . Programming of any of the parameters shall increment the ―Cumulative
programming count‖ value.
Sl No Event ID Descriptions
Sl No Event Descriptions
ID
Sl No Event Descriptions
ID
Sl No Event Descriptions
ID
Sl No Event Descriptions
ID
Neutral
iii) 203 Disturbance - HF & DC - Occurrence
Neutral
iv) 204 Disturbance - HF & DC - Restoration
(Clause G-1.1)
Sl No Event ID Descriptions
Sl No Parameter A B C D E F IC
Tamper Logic:
Feeder Meter CAT A
OCC REST.
TAMPERS Occ Condition REST. CONDITIONS TIME(MIN) TIME(MIN)
1 Missing Vx< 5% Vref Vx> 40% Vref
potential Any other phase voltage > 75% of Any other phase 5
Vref voltage > 75% of Vref
I3x> 10 % of Ib I3x> 10 % of Ib
Missing potential tamper detection
will be phase wise
2 Voltage
Unbalance V3x> 75% Vref V3x> 75% Vref
5
Vmax-Vmin> 30% Vref Vmax-Vmin<30% Vref
I3x> 10 % of Ib I3x> 10 % of Ib
3 Low Voltage Vx< 60% Vref V3x> 70% Vref
5
Current Ignored Current Ignored
4 High Voltage Vx>120% Vref V3x< 120% Vref
5
Current Ignored Current Ignored
Voltage Unbalance should not occur
with high voltage event.
5 Power Failure
If power goes off for more than the
persistance time or all phase voltage 5 Immediate
goes less than 30% of Vref
6 Current Open Residual Current >20% Ib
Residual Current<20%
Ib
Ix< 2% Ib Ix Ignored
5
Average line Current :Ignored Average Current >
10% of Ib
V3x>60% Vref V3x> 60% Vref
7 Current Bypass Residual Current >20% Ib Residual Current <20%
Ib
Ix>2% Ib Ix Ignored
5
Average line Current :Ignored Average Current >
10% Ib
Imax- Imin > 30% 0f Imax for that Imax- Imin <27% 0f
period Imax for that period
In> 5% of Ib In Ignore
5
Current Reversal detection will be phase
wise
10 Over Current Ix> 100 % Imax I3x< 100 % Imax 5
12 Cover Open On removal of meter cover the meter will log cover open Immediate. No
Restoration
event along with date and time.
When Voltage or current sequence
13 Invalid Phase is When voltage or No tamper will be logged
Association different. For example: Voltage current sequence is except low pf if satisfied
sequence RYB and Current
sequence same after 5 Mins
is YBR
In case of Low and High Voltage Tamper, no current related tamper will be logged except CT
Reverse Tamper
SCOPE :
This specification covers Design, Engineering, Manufacture, Assembly,
Painting, Inspection, Testing at manufacturer’s works, Delivery to site inclusive
of packing & transportation, Testing and Commissioning assistance of Battery,
Battery Charger & DCDB complete with all accessories.
1 set of 110V D.C. system (Battery, Battery Charger & DCDB) in accordance with
this specification, standards stated herein and Appendices enclosed herewith, shall
comprise of the following:
a) SMF (VRLA) Battery complete with racks & accessories.
b) One No. Float charger.
c) One No. Float cum Boost charger.
d) DCDB
1. GENERAL REQUIREMENTS:
The system requires a reliable and uninterrupted D.C. supply for supplying
D.C. Power to emergency lights, closing and tripping coils of circuit breakers,
relays etc.
2. APPLICATION STANDARD
Unless other wise specified, the equipment shall conform to latest applicable Indian
standard of equivalent IS particular to the following standard
IS:3895/1966 Specification for the rectifier equipment
IS:9224 Specification for HRC fuses.
IS:1248 Indicating instrument.
IS:375/1963 Specification for wiring
IS:4540/1968 Mono crystalline semiconductor rectifier assemblies
IS:2026 Transformers
IS:13947/1993 Air Break Switch/Contactor
IS:5/1978 Colour for ready mix paint
IS:5421/1981 Printed circuit board
IS:8828/1993 Miniature circuit breaker
IS:2147 Degree of protection for cubicle
IS:6619 Safety code for semiconductor rectifier equipment
3.1 AC input:
240 volts +20 % & -25%,50 HZ +/- 5%, single phase supply Input Power factor
0.8 minimum at rated load.
3.2.2 During boost charging, voltage across the battery terminal will go higher at the
order of about 130-152 volts for which suitable automatic solid state transistorized
dropping device shall be provided (maintain 110 V +/- 2 Volts across the terminal.
3.2.3 Battery Charging Equipment shall be fully automatic for Float and Boost charging
facility with suitable indication on front of the panel by means of LED indication. For
this, automatic solid state changeover relay shall be provided. During AC mains fail,
Battery supplies the load and gets discharged. The extent of discharge depends on the
duration of power failure and the current drawn by load. When the mains are restored
after power failure, Battery shall put on automatically on boost mode. During this time,
load voltage shall be maintained by load regulator 110 V +/- 2 volts. It should
automatically switchover to trickle mode & when Battery voltage falls below 110 volts,
the charger should automatically switchover to Boost mode. Soft start feature shall be
provided in the system.
3.2.4 The battery charger shall have one top and one bottom for Manual & Auto
Bridge circuit. The bottom module (Auto mode) shall be so connected to the
top/other modules that if necessary, it can be taken out for repair by simply
disconnecting few links. Each arm of the bridge shall be provided with filter circuit as
well as fuse protection in order to rectify the fault if any, at the earliest opportunity.
3.2.7 Rating : 110 V Dc output, 30 amp auto/ manual dual automatic float cum boost
Battery charger.
a. Type : Thyristor controlled.
b. At Load terminal : During float charging or Boost charging, the load voltage
shall be maintained 110 V + 2 volt. For AC input voltage variation of
+20 & -25 % and load variation of 0 to 100 %. Also system shall
provide 12 Amps continuous current and also momentary current of
40 Amps for one second.
c. At Battery terminal : Trickle charge voltage 118-126 volts (2.16 / 2.25 V
per cell) at 400 mA maximum. Boost charge voltage 130-152 volts
(2.23 V / 2.75 V per cell) at 18 Amps.
d. Ripple : The ripple content in the DC output of DC output of Battery
Chrger shall be limited to 2% RMS.
e. Regulation – +/- 2%
f. Efficiency : More than 70%
g. Method of cooling : Natural air with proper ventilating arrangement.
4.0 DESCRIPTION :
4.1 The charging equipment shall be housed in a free standing, floor mounted
compartmentalized panels having separate compartments for float and float cum boost
charging equipment, battery connection to DC bus, DC distribution equipment,
including incoming feeders and outgoing feeders in different compartments. Panels
shall have provision for bottom entry of cables with removable cable gland plate. (i.e.
separate compartmentalised panels for each float charger, float cum boost charger and
DC distribution).
4.2 The panel shall be of CRCA sheet steel construction and provided with concealed
hinges. Adequate ventilating grills or louvers with fine brass wire mesh shall be provided.
Thickness of sheet steel shall be at least 2.0 mm. Degree of protection provided
by the enclosure to the internals of charger shall be IP-42 as specified in IS : 13947..
4.3 The instruments, switches and indicating lamps shall be flush mounted on the front panel.
4.4 Suitable neoprene rubber gaskets shall be provided all around doors and cover plates,
between two shipping sections, two charger sections, two panel sections, for making
charger construction dust and vermin proof.
4.5 All PCBs used in the charger shall be made of glass epoxy material. Electronic cards
shall be plug in type and shall be mounted on standard racks. Rack shall have PCB guides
which shall allow the insertion of PCBs smoothly without requiring force. Racks shall be
mounted on hinged pivot to enable the rack to be turned for access to back side
terminals. PCBs shall include status indicating LED lights and test connections in the
front to facilitate fault diagnosis. PCBs shall be identified with proper permanent labels
as per approved drawings.
4.6 Dimensions of the Charger : 700 mm (W) X 600 mm (D) X 1300 mm (H)
4.7 Paint shade : Both exterior and Interior – RAL 7032
5.0 COMPONENTS:
5.1 The Battery charger shall comprise of following components but not limited to the same:
a) Double pole AC circuit breaker for AC incoming of the battery charger (MCB) with
auxiliary potential free contact for indication to SCADA MCB ratings shall be for 3 KA
rupturing capacity at 110 V DC..
b) Single phase, full wave half controlled SCR bridge of 40 A rating (Silicon controlled
Rectifier) together with suitable heat sinks and RC suppression network to take care of
momentary high load of 40 Amp. The bidder shall supply the characteristics of the
rectifier used in the construction of the charger indicating the capacity of the
rectifier to suit the temperature conditions. All the electronic components shall be of
high MTBF or heavy duty type and liberally rated.
c. Automatic solid stage voltage / current controller for automatic control of voltage and
current during float / boost charging the batteries complete with manual control
facility.
d. Auto /manual mode selector switch (25 A rating) with Indication lamp/LED for
respective position.
e. Float/Boost indicator lamps/LED.
f. Potentiometers to adjust DC output voltage and current in respective modes.
g. Battery charging current and voltage requirements are to be regulated by using voltage
current feedback loops.
h. Smoothing (filter) circuit comprising of smoothing choke and filter condenser to reduce
ripple content in the DC output of the Battery charger to 2% RMS.
i. DC moving coil Voltmeter of 0-16+0 V rating and 72 sqmm with selection switch and HRC
fuse to measure voltage of charger / Battery and Load.
j. Solid state automatic load voltage regulator to maintain the load voltage of 110 V+/- 2 V
(rating of the regulator shall be 12 A continuous and 40 A for one second) during Float
charging or Boost charging of the Batteries.
k. Double pole DC circuit breaker for Battery protection (MCB) with auxiliary potential
free contact for indication to SCADA.
l. DC contactor to by-pass automatic load voltage regulator in the event of AC mains fails
to allow the full battery across the load. There should not be any discontinuity of DC
supply to the busbar during any transition period and battery power should be available
for tripping circuit, if necessary, even during boost charging.
m. AC analog voltmeter 96x96 sqmm of rating 0 to 300 V.
n. Fuse fail indication lamp / LED for load and Battery fuses.
o. The indicating instruments shall be class 0.5 accuracy.
p. The following provisions conforming to relevant IS shall be made on the front panel:-
(i) Voltmeter to indicate battery/charger DC voltage.
(ii) Voltmeter for Input AC supply voltage.
(iii) Ammeter to indicate Charge/Discharge current of batter.
(iv) Ammeter to indicate load DC current.
5.2 The Charger shall be provided with following LED of reputed make Indication:
5.5 Wiring: Charger cubicle shall be supplied completely wired upto terminal block for
purchasers external connection using solder less crimping type copper lugs. All wiring
shall be carried out with 1.1 KV grades PVC insulated multi-strand copper conductor of
2.5 Sqmm and shall be flame/vermin proof. All wiring shall be neatly bunched without
affecting access to equipment/ components mounted within the cabinet. The Charger
DC output circuit for Battery and load connection separately shall be wired with 6.00
sq.mm PVC insulated cable.
Suitable two earthing terminal and outgoing terminal shall be supplied to connect
the external supply cables.
Suitable two earthing terminal and outgoing terminal shall be supplied to connect
the external supply cables.
6. SPECIAL FEATURE :
6.1 All printed circuits boards used in the battery charger shall be solder marked, glass, epoxy,
FR 4 grade copper clad material having edge type gold plugging connectors conforming to
latest IS / IEC specifications. All assembled PCB conforming coating on component side &
epoxy varnish on the other side with suitable protective coating for protection against
humidity and corrosion.
6.2 Transformer shall be with class B insulation having a continuous rating atleast 125% of the
rating of the charger. Reactance of the transformer shall be suitable to take care of
regulation and surges. The power transformer rectifier unit of the battery charger shall be
designed for adequate VA rating but in any case it should not be less than 700 VA and
should be rated for 300 V at factor safety of 3. The heat dissipation and power control
system should be designed with a factor of safety of 8. Rating of silicon diode should not
be less than 40 A.
Please note that necessary documentary evidence, showing transformer rating of 700 VA
along with test certificate from manufacturer. It bought out , shall be enclosed, fo
approval of the purchaser.
6.3 Following make of components shall be used in the Battery charging equipment or equivalent
approved by WBSEDCL.
i) Switches Kaycee / Recom
0
ii) Meters AEL/IMP/USHA
0
iii) Contacts/Relay L&T/Siemens/ABB/C&S
0
iv) MCB MOS/ABB/Siemens/L&T
0
v) HRC fuses S&S/Bussman/Siemens/L&T
0
vi) SCR USHA/HIRECT/IR
iI
vii) Diode USHA/KELTRON/IR
0i
viii) Lamps/LED Essen/vaishna/Siemens/L&T/Emco
)
ix) Filter condenser Rescon/Elcon/Kendil
x) Potentiometer Pankaj
xi) VoltmeterA.C. IMP/AE/Rishav/Meco
6.4 The charger cubicle will be indoor type with all associated and auxiliary equipments mounted
therein.
6.5 All fuses shall be HRC cartridge types conforming to IS : 2208 mounted on plug type fuse
bases.
6.6 Electrical indicating instruments shall be flush mounted on panel with only flanges
projecting. Dial shall be white with black number and lettering.
6.7 Control & instrument switches shall be of rotary type.
6.8 Indicating lamps shall be LED type with low watt consumption. The LEDs shall be provided
with series resisters.
6.9 Strip type space heaters of adequate capacity shall be provided inside cabinet to prevent
moisture condensation.
6.10 All door mounted equipmentsas well as equipment mounted inside the cabinet shall be
provided with individual labels with equipment designation engraved on aluminium / plastic
plate (stickers are not acceptable).
6.11 POLARITY MARKING:-
The polarity marking of the terminals shall be marked for identification. The positive
terminal maybe identified by “P” or (+) sign and Red colour mark and the negative
terminal maybe identified by “N” or (-) and Blue colour. Terminal marking shall be
permanent and non-deteriorating.
6.12 Terminals – Battery charger cabinet shall be provided with two separate suitable earthing
terminals. Separate terminals shall be provided for connecting load &
battery leads to the charger. All terminals shall be M12 size. Suitable
copper lugs shall be provided by the bidder for use of the purchaser for
connecting the load wiring. It would be the bidder’s responsibility to prove
the adequacy of the design by submitting all technical particulars and
relevant graphs to show suitability of charger for supplying load on
continuous basis.
6.13 The supplier of battery charger shall be fully coordinate with the supplier of battery in
the event of the purchaser deciding not to place order for both equipments on the same
supplier.
6.14 Method of cooling of the charger equipment shall be specified by the bidder.
6.15 Two earthing studs of MS 50 mm long & 12 mm dia shall be provided for external earth
connections. These should be complete with plain washer, spring washer, nuts etc.
Earthing Bolts must be welded to prevent removal of the same from the box.
AC mains fail √
Load Bus Over Voltage √
Load Bus Under Voltage √
Float Charger fail √
Earth Leakage √
Float Charger On √ √
Float Charger Off √ √
Float Charger on Auto mode √
Float Charger on Manual √
mode
Boost Charger On √ √
Boost Charger Off √ √
Boost Charger On CV mode √ √
Boost Charger On CC mode √ √
Charger on local mode √
Charger on Remote mode √
Battery Voltage √
Boost Voltage √
Float Voltage √
Load Voltage √
Battery Current √
Boost Current √
Float Current √
Load Current √
Battery Room Temperature √
7.1 Type Tests:-The bidder shall have to submit along with their Tender documents, as
pre requisites, the complete Test reports of all tests including Type tests as
stipulated in the relevant IS / IEC, carried out within 5 years from the date of
tender, from CPRI / NABL accrediated / Govt. recognized Test house or Laboratory
on the offered item, failing which their offer may not be technically accepted.
7.1.1 If the bidder fails to produce the said documents on the offered
item during submission of tender, he/she will have to submit the
said type test report after placement of order but before
inspection of 1st lot of material at his own cost.
7.1.2 The following tests shall constitute the type tests as per IS: 3136-
1965, IS:4540-1968(latest amended) and IS 2026 (for short
circuit test) :
a) DC voltage current test.
b) Automatic voltage regulator operation.
c) Efficiency test.
d) Ripple Voltage test.
e) High Voltage test.
f) Temperature rise test.
g) Degree of Protection test.
i) Short circuit test at No Load and full Load at rated voltage for
sustained short circuit.
7.2 List of Routine Tests as follows:-
Physical checking of charger as per approved
drawing.
• Insulation resistance test.
• High voltage test.
• Line regulation test at No Load and full load in test at load in
Float/ boost mode.
• Full load ripple content measurement test at load terminals in
float and boost mode
• Voltage regulation test at load terminal and Battery terminals in
float and boost mode.
• DC short circuit test without blowing HRC fuses and
without tripping MCBs at load terminal and also at Battery
charger output terminals with observation of total current
limit.
• Efficiency measurement test.
• Checking of automatic operation Float to Boost, Boost to
float mode as per Battery condition.
• Checking of Battery voltage, load voltage and Load current
Boost Mode at different charging current.
• Temperature rise test of complete charger at full load
• Checking of battery & Load Terminal voltage in manual Mode
operation at different position of Manual Mode Selector
Switch.
• Checking of automatic connection of Battery to load in case of
“Mains Failure‟ or Charger Trip‟ conditions. Checking of Float
voltage setting range and Boost current setting Range in Automatic
Mode. Any other routine test shall be carried as per IS: 4540 on
the complete battery Charging equipment.
1 Name of manufacturer
2 Type of charger
3 Indicate specification to which the offered charger
conforms
4 Rated Input supply voltage
5 Rated Input current
Input Power Factor
6 Output voltage with range of variation
7 Output current range
8 Output current
a) Max. Battery charging current
b) Max. continuous DC external load current
c) Max. continuous output current
33 Applicable Standards
34 List of accessories to be provided with the
Charger
35 Recommended particulars of matching Battery
1. GENERAL REQUIREMENTS:
The system requires a reliable and uninterrupted D.C. supply for supplying D.C. Power
to emergency lights, closing and tripping coils of circuit breakers, relays etc.
The chargeable batteries shall be Lead acid maintenance free (SMF-VRLA) type.
The end cell voltage after discharge shall be limited to 2.0 volts/cell. Batteries shall not
require any water topping up and shall emit no corrosive fumes or gases under normal
operating conditions.
The batteries shall be supplied along with the necessary mounting racks or sheet steel
enclosure complete with the provision for clamping the cables. Battery racks shall be of steel
frame with epoxy painted/ PVC lined.
2. REQUIRED PARAMETERS :
2.1 The terminals of the battery shall be suitable for receiving cable lugs.
2.2 The device shall be installed in indoor location to provide auxiliary DC Power Supply
for following applications:
a) Emergency lighting
b) Circuit breaker/switchgear/protective relay operations
c) Equipment supervision indication
d) Audio visual annunciation
Under normal conditions, auxiliary DC Power Supply for continuous load will be met from
Battery Charger and storage batteries should be kept under float or boost charging
condition. But in case of Circuit Breaker/Switchgear/Protective Relay operation and/or
in the event of failure of incoming power supply to Battery Charger, required
auxiliary DC Power supply shall be met from Storage Batteries.
2.3 The standard ratings of batteries shall be 110 Volts DC, 125 AH mentioned.
2.4 The nominal voltage of a single cell shall not be less than 2 volts at the beginning of
Charging. The FLOAT charging voltage per cell shall be within 2.15 volts to 2.3 volts.
The BOOST charging voltage per cell shall be 2.35 Vvolts to 2.75 volts. At the end
of the charging, cell shall be floated easily around 2.25 volts without causing adverse
corrosion or loss of water.
2.5 Range of charging current and final cell voltage
• Range of Float charging : 100 mA to 300 mA
• Range of boost charging : i) Starting current – 18 Amp, ii) Finished current – 9 Amp
• After discharging, final voltage shall not be less than 1.85 volts.
3. DESCRIPTION :
All tests shall be carried as per the relevant standard. Test shall comprise of
Routine tests and Acceptance Tests.
4.1 Routine Test :
These are to be performed at manufacture‟s works and shall include
the following test:-
• Verification of constructional requirement.
• Verification of marking.
• Verification of dimensions.
• Test for capacity.
• Test for voltage during discharge.
• Ampere hour and watt – hour efficiency test.
• Test for loss of capacity on storage.
• Endurance test.
Sl Particulars Details
No.
7. Electrolyte details:
i)Applicable standard of electrolyte
ii)Quantity of Electrolyte &
Specific gravity at27◦C for first filling in
each cell
iii)Quantity of Electrolyte required
for15nos.Plante type lead acid cellplus10%
extra
iv)Specific gravity of electrolyte at
27◦C with all cells fully charged
v)Specific gravity of electrolyte at the end of
10 hour of discharge
rate
9. Battery Stand:
1) No. of racks per battery
2) No. of cells per rack
3)Formation of row and tier details
4)Material of stand
5) Particulars of anti-sulphuric paint to be
provided
6) Type and no. of stand insulator to be
provided
1.0 STANDARDS:
Components mounted on the DCDB shall confirm to the latest revisions of the
following standards:
2.0 GENERALTECHNICALPARTICULARS:
2.2.1 Each Distribution Board shall be free standing floor mounted having
compact design. The Board shall be closed, dust protected, weather proof and
shall be made vermin proof with a special type lining e.g. Neoprene gasket, around
the edges of the doors. The distribution board shall comply degree of protection
IP43. MCBs shall be operating vertically upward for ON/OFF operation. The
entire distribution board shall have uniform finish and shall be sturdy. The
distribution boards shall be of modular construction with provision for complete
compartmentalisation of all feeders. It shall be free-standing, dead front type
comprising dust-tight and vermin proof sheet steel cabinets suitable for indoor
installation. The doors of cabinets shall be lockable. Handle shall be made of
reputed make. The DB shall be provided with double door in front having 2 nos.
hinges which should be suitable for movement of 120 degree and 2no. knobs to be
provided on the door corners. All instruments and control devices shall be mounted
on the front of cabinets and fully wired to the terminal blocks. All switches
provided on the distribution board shall be on front side of the cabinets, operable
from outside.
2.2.2 Distribution Board shall be made out of atleast 2.0 mm thick cold rolled
steel sheet, suitably reinforced to provide flat level surface. Size 1000(H) x
750(W) x 300(D) mm. Gland plate shall be 3.0 mm thick. No welds, rivets, hinges
or bolts shall be visible from outside. The doors shall be fitted with double leaf
neoprene rubber gaskets.
2.2.3 All cables shall enter and leave from bottom. Suitable cable terminal blocks
with cable lugs shall be provided inside each cabinet for the incoming and outgoing
cables. The terminals shall be serially numbered to facilitate installation and
maintenance. Main busbars shall be accommodated in busbar chambers and cable
alleys arranged by their side. Compression type cable glands shall be provided to
hold the cables to avoid any pressure or tension on the terminal block connections.
The terminal blocks shall be easily accessible for inspection and checking. Panels
shall have cable supports and metallic clips for supporting power and control cables
for internal wiring of the panels.
2.2.4 DCDB should have 2 sets of Bus Bars in Two separate compartments
to facilitate termination of Incomers from Battery and Chargers. One Change
over switch should be provided to facilitate DC supply to outgoing load
circuit in the event of failure of anyone of the battery/ Charger. The
change over switch should be 2 way 2 position for changing over of both
incomer individually.
Each Busbar shall consist of tinned electrolytic copper of cross-sectional area of a
minimum of2 5mmx3mm, suitable for carrying rated continuous current without
temperature exceeding 85° C. The busbars shall be continuous throughout each
section. The busbars shall have current rating to suit the requirements
corresponding to the loads incident there on under the various operating
conditions and shall withstand the applicable voltage and maximum short circuit
stress. The busbars shall be insulated from supporting structure by means of
durable non-hygroscopic, non-combustible and non-tracking polyester fibre glass
material or porcelain. Busbars shall be encased separately in heat- shrunk sleeves
of insulating material which shall be suitable for the operating temperature of
busbar during normal service. The busbars joints shall be provided with removable
thermosetting plastic shrouds.
The busbars shall be housed in totally separated enclosed busbar chambers.
The incoming connections from the busbars to the various feeders shall be so
designed as not to disturb cable connections and to ensure safety to the operating
and maintenance personnel and to facilitate working outside any outgoing module
without the need for switching off in-feed to the adjacent modules, as far as
possible. The busbars shall be of high conductivity, adequate uniform cross-
section and current density shall be there.
A cable alley preferably 230 mm wide shall be provided in each vertical section for
taking cables in to the compartments.
2.2.6 Danger board (Caution Plate) shall be fitted suitably on inner door of the
DB. Danger board shall be of 100 x 100mm size with details as per
WBSEDCL standard format.
2.2.7 The DC boards shall be provided with the following equipments wherever
applicable:
i. Single bus arrangement with provision for one set of +ve and –ve
connected to Charger. Busbar shall consist of tinned electrolytic
copper.
ii. Terminal arrangement with necessary equipment for connecting the
incoming supply.
iii. Voltage and current measurement in the incomer feeder.
iv. Outgoing modules with switch/MCB units of adequate capacity for the
outgoing feeders and 20% spare feeder units of each rating.
v. Necessary cable glands and terminal blocks.
vi. Adequate number of spare terminals on terminal blocks for receiving
connections for external connections.
vii. The number of outgoing feeders from DC boards shall be such that
each substation equipment is fed by separate feeder with 20% as spare.
2.2.8 The ventilating louvers should be covered from inside by a perforated
sheet.
2.2.9 All sheet metal used for DB shall undergo seven tank mechanical/ chemical
cleaning process & painting shall be done using powder coating process.
Colour of the Paint shall be RAL 7032type.
3.1 Incoming cables for DCDB shall be terminated on terminal connectors provided at the
bottom. Connection between incomer terminals and MCBs shall be with 50 sq. mm copper
cable. Outgoing shall be connected with 35 sq.mm copper cable.
All MCBs, cable used in the DB shall be of reputed make and ISI marked.
DCDB should have 1 set of Bus Bar in a compartments to facilitate termination of
Incomers from of Battery and Charger.
3.2 Incoming circuit:
Two double pole MCBs of 63 Amp s capacity shall act as Incoming breaker of load bus.
Changeover switch of 63 Amps DP is to be provided.
3.3.2 All MCB outgoing terminals shall be terminated on terminal connectors of 10 mm. stud
type provided at the bottom.
3.3.3 The enclosure shall be provided with proper earthing
3.3.4 PVC cable glands of adequate size shall be provided for all incoming and outgoing
cables.
3.3.5 The moving contacts of all poles of multi-pole circuit breakers hall be so mechanically
coupled that all poles, except the switched neutral, if any, make and break
substantially together. Whether operated manually or automatically even if an
overload occurs on one protected pole only.
Both side terminal should be suitable for direct cabling as well as bus bar connection
and should take wire up to cross-section area of 25 sq.mm.
Emergency lighting circuit shall be provided such that the lights normally burn on AC
240Volts, 50 Hz but in case of failure of AC supply, these come upon DC supply with the
help of automatic changeover contactors and again changeover to AC supply with the
restoration of AC supply. There shall be two number double pole ON/OFF switches with
HRC fuses one each for AC and DC supply.
3.4.4 MARKING
Each compartment shall be provided with legible and indelibly marked/engraved
nameplate. Name plates shall be white with black engraved letters. On top of each
module, name plates with bold letters shall be provided for feeder designation. Each
device shall also suitably marked for identification inside the panels. Name- plates with
full and clear inscriptions shall be provided inside the panels for all isolating switches,
links, fuse blocks, test blocks and cable terminals. Every switch shall be provided with
a name plate giving its function clearly. Switches shall also have clear inscriptions for
each position indication e.g. ‘ON’ ‘OFF’ etc.
DCDB shall be furnished completely factory wired up to terminal blocks ready for
external connections.
All wires shall consist of 1100V grade PVC insulated flexible stranded copper
wires with a cross-section of 2.5 sq. Mm suitable for switchboard wiring and complying
with the requirement of relevant IS. Each wire shall bear an identifying ferrule or tag at
each end or connecting point.
Control cables for external connections shall consist of stranded copper wire with
4.0sq. Mm or higher cross-sectional areas and shall enter the bottom.
All interconnecting/outgoing control wiring shall terminate on stud type terminals on
terminal blocks. The terminals shall be marked with identification numbers to facilitate
connections.
The terminal blocks shall be made of moulded, non-inflammable, plastic material and
arranged to provided maximum accessibility for inspection and maintenance. All terminal
block shall have transparent plastic cover.
The terminals shall be made of hard brass and diameter of not less than 6mm.
The studs shall be securely locked within the mounting base to prevent turning. The terminal
blocks shall be provided with twenty(20) percent spare terminals. The terminals shall be
suitable for connections through tinned copper crimped lugs.
Wiring shall be complete in all respect to ensure proper functioning of the
control, protection and monitoring scheme.
Each wire shall be identified at both ends with permanent markers bearing
wire numbers as per wiring diagram.
MCBs & other components used in DCDB shall be fully type tested as per
relevant IS and this specification.
All the Type Tests shall be carried out from laboratories which are accredited
by the National Board of Testing and Calibration Laboratories (NABL) of Government of
India such as CPRI Bangalore/Bhopal, ERDA Baroda, to prove that the MCBs & other
components used in DCDB meet requirements of the specification.
11 All MCBs are type tested and having short circuit rating of Y/N
Min. 6KA at 0.7 pf lag
12 Ammeter is having range of 0-75A And accuracy class1.0 Y/N
13 Make and type of Ammeter Y/N
14 Voltmeter is having range of 0-130V And accuracy class 1.0 Y/N
15 Make and type of voltmeter Y/N
16 Indicating lamps are of LED type with 22.5 mm dia. Y/N
17 Wiring between MCBs and terminal connectors is with Y/N
specified stranded copper wire as per specification
18 Terminal connectors are of bolted type provided as per Y/N
specification
1(i). Scope : The specification covers the design, manufacture, testing at the
State Electricity Distribution Company Limited of Lead Acid Battery set suitable for
Auto and Manual Float cum Boost Battery Charger with 30 V DC Output. Supervision
APPLICATION:
The system requires a reliable and uninterrupted D.C. supply for supplying
D.C. Power to emergency lights, closing and tripping coils of circuit breakers, relays,
semaphores etc.
Indian standard of equivalent IEC, British or USA standard and in particular to the
The tenderer shall clearly state the standard to which the equipment offered by
him conforms.
IS:
1652/
1991 Specification for stationary lead acid Plante Cell battery
1.1 Low maintenance type of Lead Acid stationary Batteries incorporating of pure Lead
Lamellar type with “Plante” formation positive plates assembled in 2 Volt containers
voltage of 1.85 V per Cell having Electrical performance as per IS: 1652/1991
1.2 The terminals of the battery shall be suitable for receiving cable lugs. 15
Nos. of 2 volts 100 AH Cell connected in series shall form one set of 30 volts 100
AH.
2.0 Application : The device shall be installed in indoor location within the battery Room
a) Emergency lighting
Under normal conditions, auxiliary DC Power Supply for continuous load will be met from
Battery Charger and storage batteries should be kept under float or boost charging condition.
failure of incoming power supply to Battery Charger, required auxiliary DC Power supply
4.0 Cell Voltage : The nominal voltage of a single cell shall not be less than 2
volts at the beginning of Charging.
The trickle charging voltage per cell shall be within 2.25 volts to 2.3 volts. The boost
charging voltage per cell shall be upto 2.75 volts.
At the end of the charging, cell shall be floated easily around 2.25 volts without
causing adverse corrosion or loss of water.
6.0 The expected life span of the batteries shall be minimum 10 years.
7.1 Type: The storage batteries shall consist of 15 nos. Plante type
Lead Acid Cells of Voltage not less than 2 volts per cell at the beginning of initial
charging.
The positive plates of cell shall be constructed from pure lead consisting of laminations.
The negative plates shall be pasted type consisting of sturdy lead alloy grid filled
The plug of the plates of like polarity shall be connected to terminal post for
external connections. Suitable plastic buffer, moulded bottom plate support shall be used
7.2.4 Separator
The separators shall be constructed from highly micro-porous and rigid material of
appropriate shape. Separators shall be inert chemically and shall prevent internal
The positive and negative terminal posts shall be clearly and indelibly marked for easy
identification. The terminal posts shall be sealed properly with the lid by rubber
grommets or other suitable device. The terminal posts shall have provision for inter-
7.2.6 Container
Transparent styrene acryl nitrile (SAN) container for each cell shall be made of
Cell lid for covering cell container shall be made from high quality non-corrosive plastic
A vent plug of suitable design shall be provided on each cell lid. The vent plug shall
which will prevent escape of acid fume/spreading of acid fume but will allow free exit
7.2.9 Electrolyte
The electrolyte for the cell shall be battery grade sulphuric acid conforming to
IS:266-1977 or its latest version amended upto date and diluted with distilled water to
specific gravity 1.2 at 27 Deg C. The lead acid cell batteries shall be supplied in dry and
uncharged condition. Diluted sulphuric acid of approved quality and required quantity
shall be supplied in separate non-returnable porcelain or any other acid and corrosive
Cell Pillars and connectors shall be made from highly conductive material of lead allow
having generous cross section ideally suited for high current duties.
Bolts, nuts, washers etc. for connecting the cells and connectors
The stand for supporting battery cells shall be provided. The stand for battery cell
shall be of Mild Steel finished with at least three coats of anti-sulphuric paints of
approved shade. The racks shall be free standing type. Suitable porcelain/plastic
insulators shall be provided between the stand and the battery room floor. Number
plate to designate each cell of battery shall be provided and shall be attached on the
rack. Provision shall be made for clamping outgoing cable on the rack. The cell shall be
supported on the rack in suitable row and tier formation with adequate clearance
The polarity marking of the terminals shall be marked for identification. The positive
terminal may be identified by “P” or (+) sign or red colour mark and the negative
terminal may be identified by “N” or (-) or blue colour. Terminal marking shall be
7.3.4 Life
The Bidder shall quote in his offer the guaranteed life of the battery when operating
7.3.5 Battery shall be transported in dry, uncharged condition. The electrolyte shall be
i) Loss of capacity on storage of a fully charged battery for 28 days shall not be more
than 3%.
iii) Distilled water addition once in 6 months should be sufficient to maintain the
electrolyte level.
iv) The battery should withstand conditions of under-floating and over- floating.
vi) The Bidder should furnish sufficient evidence of his capability to manufacture the
low maintenance batteries.
These are to be performed at manufacture‟s works and shall include the following
test:-
from the sample selected from the lot offered for supply.
performance durability and shall not buckle during different service condition i.e.
high rate of discharge and rapid fluctuation of load. The container should have
7.3.11 Accessories
Following accessories in addition to battery shall have to be supplied in each set of
equipment:
The Bidder must clearly indicate what testing facilities are available in the works of
manufacturer and whether the facilities are adequate to carry out all Routine,
deputed to carry out or witness the tests in the manufacturer‟s works. If any of the
tests can not be carried out in the manufacturer‟s works, Bidder shall have to
arrange for such testing at any NABL Accredited/Govt. Test house or Laboratory at his
own cost.
9.0 Inspection :
manufacturer and the WBSEDCL. The manufacturer shall provide the WBSEDCL all
reasonable facilities, without charge to satisfy him that the material is being supplied in
10.0 Tests:-
General: The equipment including all components and accessories shall be subjected to
all type of tests including Routine and acceptance tests in accordance with provision
10.1 Type Test: The Bidder shall have to submit along with their Tender
as stipulated in the relevant IS/IEC, carried out within 5 years from the due date of
offered Item, failing which their offer may not be technically acceptable.
10.2 Routine and acceptance Tests: Routine &acceptance tests shall have to be carried out
Manufacturer.
manuals, literatures for approval to the office of the Chief Engineer (P & E)
the equipment, 6(six) copies of drawings, manuals and literature shall be submitted to
In addition to above, every crate of complete set of equipment shall also contain in
Particulars‟ and the statement such as “as per drawing enclosed”, “as per
WBSEDCL requirement”, “as per IS”, “as per specification” etc. shall be
14.0 Schedules:
The Bidder shall fill in the following schedules, which is part and parcel
of the tender specification and offer. If the schedules are not submitted
duly filled in with the offer, the offer shall be liable for rejection.
2. Application standards
6. Cell details
ii)Negativeplate
h) Rated current of each positive
plate:
j) Container details:
i) Material of container
: Length
: Width
: Height
a) Without Acid
b) With acid
m) Clearance in mm between:
i) Material
ii) Type
iii) Feature
7. Electrolyte details:
i) Applicable standard of
electrolyte
ii) Quantity of Electrolyte
& Specific gravity at 27◦C
for first filling in each cell
i) Material
ii) Type
iii)Dimension details in mm
9. Battery Stand:
4) Material of stand
5) Particulars of anti-sulphuric
paint to be provided
1) Current in amps
2) Voltage in volts
3) Total minimum input during
initial charging in AH
Name:
APPLICATION:
The system requires a reliable and uninterrupted D.C. supply for supplying
D.C. Power to emergency lights, closing and tripping coils of circuit breakers, relays etc.
2. Service conditions:
The tenderer shall clearly state the standard to which the equipment offered by
him conforms.
4.1 SUPPLY: AC input: 240 volts +20 % & - 25%, 50 HZ +/- 5%, Single phase supply.
Input power factor 0.7 minimum at rated load.
4.2.2 During boost charging, voltage across the battery terminal will go higher at the
order of about 42 volts for which suitable Automatic solid state transistorized
dropping device shall be provided (maintain 30 Volts +2/- 0V volts across the load
terminal).
4.2.3 Battery Charging Equipment shall be fully automatic for Float and Boost charging
facility with suitable indication on front of the panel by means of LED
indication. For this, automatic solid state changeover relay shall be provided. During AC mains
fail, Battery supplies the load and gets discharged. The extent of discharge depends on the
duration of power failure and the current drawn by load. When the mains are restored
after power failure, Battery shall put on automatically on boost mode. During this time,
load voltage shall be maintained by load regulator 30 V ± 2 Volt. After the Battery
gets fully charged i.e. its voltage reaches 42 Volts, it should automatically switch over to
trickle mode & when Battery voltage falls below 27 volts, the charger should
automatically switch over to Boost mode. Soft start feature shall be provided in the system.
4.2.4. The manual mode should be fully independent so that no element of electronic
controller comes into its operation. This shall also include an independent full wave
bridge rectifier of suitable rating, output of which will be connected to load and
battery by means of a contactor controlled switch on the front panel. Output of the
charger in manual mode shall be maintained below 35 volts by means of selector
switch connecting the suitable tap on the secondary side of power transformer
by the operator. Facility should be provided to prevent the excessive in-rush
current into the battery, when the discharged battery suddenly comes across the
float charger after an emergency period.
4.2.5 The battery charger shall have one top and one bottom for Manual & Auto Bridge
circuit. The bottom module (Auto mode) shall be so connected to the top/other modules that if
necessary, it can be taken out for repair by simply disconnecting few links. Each arm
of the bridge shall be provided with filter circuit as well as fuse protection in order to
rectify the fault if any, at the earliest opportunity.
4.2.6 There shall be 4(four) nos. Feeder specific outgoing MCBs to cater DC load as and when
needed. Out of 4(four) nos., 3 nos. shall be provided with 32 Amp. MCB for protection
circuit and one number with 6 Amp MCB for emergency light without changeover. The
above MCBs considered excluding Battery circuit.
4.3 RATING: 30V DC output, 35 Amp Auto & Manual dual automatic float cum boost Battery
Charger.
During Float charging or Boost charging, the load voltage shall be maintained
30 V ± 2 Volt for AC input voltage variation of +20% & - 25 % and load
variation of 0 to 100 %. Also system shall provide 35
Amps continuous current and also momentary current of 40 Amps for one
second.
c) At Battery Terminal:
Trickle charge voltage 34.50 volts (2.3V per cell) at 400 mA maximum. Boost
charge voltage 42 volts (2.75 V per cell) at 14 amps.
d) RIPPLE:
e) Regulation: +/- 2%
5.1 COMPONENTS:
5.1.1 The Battery charger shall comprise of following components but not limited to the
same:
c) Single phase, full wave half controlled SCR bridge of 40A rating (Silicon
controlled rectifier) together with suitable heat sinks and RC suppression network
to take care of momentary high load of 40
Amp. All the electronic components shall be of high MTBF or heavy duty type
and liberally rated.
j) DC moving coil Ammeter of 0-25A rating and 72 sq. mm. for load and 0 to 50 A
battery current.
k) DC moving coil Voltmeter of 0-50 V rating and 72 sq. mm. with selector
switch and HRC fuse to measure voltage of Charger/ Battery and Load.
l) Solid state automatic load voltage regulator to maintain the load voltage of 30
V ± 2 V (rating of the regulator shall be 20 A continuous and 40 A for
one second) during Float charging or Boost charging of the Batteries.
m) Double pole DC circuit breaker for Battery protection (MCB) with auxiliary
potential free contact for indication to SCADA.
p) Fuse fail indication lamp/ LED for load and Battery fuses.
5.2 a. Wiring: Charger cubicle shall be supplied completely wired upto terminal block
for purchaser‟s external connection using solder less crimping type copper lugs. All
wiring shall be carried out with 750 V
grades PVC insulated multi-strand copper conductor of 2.5 Sq mm and shall be flame/
vermin proof. All wiring shall be neatly bunched without affecting access to
equipment/ components mounted within the cabinet. The Charger DC output
circuit for Battery and load connection separately shall be wired with 6.00 sq.mm PVC
insulated cable.
c. Termination:
The input, battery and load terminals shall be located in easy accessible
positions. The terminals shall be properly labelled for easy identification of
Input (Ph &Neutral), Battery (positive & negative), Load (Positive
&negative) and Emergency Lamp (Positive & negative).
The terminals shall be rated at 25 Amps or more depending on scheme
requirement.
The Input terminals shall be connected to a 3 core PVC insulated
multi-stranded copper conductor cable (minimum 2 mtr. length) with a 16
Amp 3 pin plug socket at the other end. The earth conductor of the
cable shall be provided on the charger body.
The charger shall incorporate terminals and fuse of 4 Amp rating
for connecting wires from outside to bring emergency light into battery
circuit in the event of mains failure.
All control cables should run through the bottom side of the
Charger cubicle with proper gland arrangement.
a) All printed circuits boards used in the Battery charger shall be solder marked,
glass, epoxy, FR 4 grade copper clad material having edge type gold plugging
connectors conforming to latest IS-IEC specifications. All assembled PCB conforming
coating on component side & epoxy varnish on the other side with suitable protective
coating for protection against humidity and corrosion.
f) a) The charger cubicle will be indoor type with all associated and auxiliary
equipments mounted therein.
b) The charger cabinet shall be 2 mm. thick sheet steel for Non – Load
bearing members & 3 mm for Load bearing members enclosed and shall be
dust and vermin proof. The maximum overall dimension of the charger
shall be height-1500 mm. Width – 700 mm. and depth - 600 mm.
c)The cabinet shall be free standing floor mounting type with a provision for
proper ventilation. Backside Cover will be double door type. Necessary
arrangement on front, back & top side shall be provided for easy
access to different components for repair/maintenance etc. The
enclosures of the cabinet shall provide at least degree of protection IP-42 as
specified in IS: 13947.
d) All doors, removable covers and plates shall be provided with neoprene
gasket all around. Louvers, when provided shall have screens and filters.
The screen shall be of fine wire mesh made of G.I. wire.
e) All sheet steel work shall be degreased, pickled phosphate and then applied with
two coats of Zinc primer and two coats of finishing epoxy powder coating or
polyethylene protective coating of light gray as per IS : 631, both inside and outside.
The cabinet legs shall be of adequate height and strength and should provide minimum
clearance of 500 mm from ground.
f) All fuses shall be of HRC cartridge types conforming to IS: 2208 mounted on
plug type fuse bases.
i) Indicating lamps shall be LED type with low watt consumption. The
LEDs shall be provided with series resistors.
j) Strip type space heaters of adequate capacity shall be provided inside cabinet to
prevent moisture condensation.
k) All door mounted equipments as well as equipment mounted inside the cabinet
shall be provided with individual labels with equipment designation engraved on
aluminium/plastic plate (stickers are not acceptable).
l) POLARITY MARKING:-
The polarity marking of the terminals shall be marked for identification. The
positive terminal may be identified by “P” or (+) sign or Red colour mark and the
negative terminal may be identified by “N” or (-) or Blue colour. Terminal marking
shall be permanent and non-deteriorating.
m) TERMINALS
Battery charger cabinet shall be provided with two separate suitable earthing
terminals. Separate terminals shall be provided for connecting load and battery leads
to the charger. All terminals shall be of M12 size. Suitable copper lugs shall be
provided by the supplier for use of the purchaser for connecting the load
wiring. It would be the bidder’s responsibility to prove the adequacy of its
design by submitting all technical particulars and relevant graphs to show
suitability of charger for supplying load on continuous basis.
n) All Deviations from this specification shall be set out by the bidder and should be
brought out clearly in the Deviation sheet.
6.0 Technical Particulars of Matching Lead Acid Cell Battery for 30 V, 100
AH
15 nos. 2 volts, 100AH at 27 Deg C when discharged at 10 hours with final cell voltage not
less than 1.85 Volts.
9.1 For acceptance of lot all above routine tests shall be carried out on selected
2 samples.
11.0 Inspection :
All tests and inspection shall be made at the place of
manufacturer unless otherwise specially agreed upon by the
manufacturer and WBSEDCL. The manufacturer shall provide the WBSEDCL all
reasonable facilities, without charge to satisfy him that the material is being supplied in
accordance with this specification.
12.0 Tests:-
General: The equipment including all components and accessories shall be subjected to
all type of tests including Routine and acceptance tests in accordance with provision
contained in relevant standard.
12.1 Type Test: The Bidder shall have to submit along with their Tender documents,
as pre-requisites, the complete Type test Reports as stipulated
as per Clause No.8.0 of the specification, carried out within
5 years from the due date of Tender, from CPRI/NABL accredited/Govt. recognised
Test House or Laboratory on the offered Item, failing which
their offer may not be technically acceptable. However, in case of failure to
submit the same, submission of type test report on 20.5 Amp Auto & Manual Float-
cum-Boost Charger during submission of Tender is
essential.
If the Tenderer fails to produce the said type test report on the offered item
during submission of tender, he will have to submit the said type test report before
opening of price bid at his own cost.
12.2 Routine and acceptance Tests: Routine &acceptance tests shall have to be carried out
in compliance with provision contained in the relevant standard and / or to
ascertain satisfactory performance of the offered
device at the works of the Manufacturer.
The acceptance tests shall have to be conducted in the presence of authorised
representative of the WBSEDCL before effecting delivery.
13.0 Drawings:
The successful bidder shall have to submit the 6(six) copies of drawings, manuals,
literatures for approval to the office of the Chief Engineer (P & E) for approval before
starting manufacture of the equipment. It is desired that the complete schematic of
the charger is provided on a permanently laminated/engraved plate of suitable
thickness which has to be bolted/riveted at the four corners on the inside
face of rear door. In addition, one more plate of similar type and dimension shall
be provided on the outside of the rear door providing guidelines and instructions for
operation of the charger. The guidelines and schematic to be provided on the plates
shall be as per approved drawings.
Before despatch of the equipment, 6(six) copies of drawings, manual and literature
shall be submitted to WBSEDCL for distribution to different offices of the
Company.
In addition to above, every crate of complete set of equipment shall also contain in
waterproof folder, 2(two) sets of drawing, manuals and literature for
commissioning, operation and maintenance at site.
The bidder should fill up the details in schedule A – „Guaranteed Technical Particulars‟
and the statement such as “as per drawing enclosed”, “as per WBSEDCL requirement”, “as
per IS”, “as per specification” etc. shall be considered as details not furnished and such
17.1. Immediately on receipt of this order you shall have to submit a “Quality
Assurance Plan” indicating the specific quality control procedure and practices adopted
in the major activities of production to ensure its standard.
17.2 The successful Bidder shall within 30 days of placement of order, submit following
information to the purchasers.
(i) List of raw material as well as bought out accessories and the names of sub suppliers
selected from those furnished alongwith offer.
(ii)Type test certificates of the raw material and bought out accessories. (iii)Quality Assurance Plan
17.3 The successful Bidder shall submit the routine test certificates of bought out
accessories and central excise passes for raw material at the time of routine testing of the
fully assembled equipment.
Schedule „A‟
11 Efficiency
12 Method of Cooling
13 Painting details
1.0 SCOPE:
This specification covers the design, manufacturing, testing at works and supply of
Indoor type A.C. Distribution Boards for power supply to yard lighting, Battery charger,
33 kV substation equipments, compressors etc. The system shall be AC 3 Phase, 4 Wire,
433 Volts, 50 HZ with effectively grounded neutral.
3.0 STANDARDS:
3.1 Components mounted on the ACDB shall confirm to the latest revisions of the
following standards:
Degree of protection provided for enclosure for low
A IS: 13947 voltage control gear and switchgear & MCCB
B IS 5 Painting
C IS: 13947/1993 Part-III Switch Fuse Disconnector unit amended
up to date
D IS 2705 amended up to
date
E IS 8828/1996 amended MCB
upto date
F IS 1248 Indicating instruments
G IS 375 Wiring
IS: 13703/1993 Part-I & II
H HRC Fuses
Rated voltage for the Distribution Board and its constituent items like Switch Fuse
Disconnector unit, MCBs, busways etc. shall be 3 phase 4 wire A.C. 433 volts, 50 Hz with solidly
grounded neutral. The supply voltage may vary by ± 10% of rated voltage. All the
equipments used in the Board shall operate satisfactorily at this voltage variation.
4.2.1 Each Distribution Board shall be free standing floor mounted having
compact design. The Board shall be closed, dust protected, weather proof and shall be
made vermin proof with a special type lining e.g. Neoprene gasket, around the
edges of the doors. The distribution board shall comply degree of protection IP 43.
MCBs shall be operating vertically upward for ON/OFF operation. The entire distribution
board shall have uniform finish and shall be sturdy. The distribution boards shall be of
modular construction with provision for complete compartmentalisation of all feeders. It
shall be of dead front type comprising dust-tight and vermin proof sheet steel cabinets
suitable for indoor installation. The doors of cabinets shall be lockable. Handle shall be
made of reputed make. The DB shall be provided with double door in front having 2 nos.
hinges (for each door) which should be suitable for movement of 120 degree and 2 no. knobs
to be provided on the door corners. All instruments and control devices shall be
mounted on the front of cabinets and fully wired to the terminal blocks. All switches
provided on the distribution board shall be on front side of the cabinets, operable from
outside.
4.2.2 Each Distribution Board shall be made out of at least 2.0 mm thick cold
rolled steel sheet, suitably reinforced to provide flat level surface. Size 1000(H) x
750(W) x 300(D) mm. Gland plate shall be 3.0mm thick. No welds, rivets, hinges or
bolts shall be visible from outside. The doors shall be fitted with double leaf
neoprene rubber gaskets.
4.2.3 All cables shall enter and leave from bottom. Suitable cable terminal
blocks with cable lugs, for a minimum of 22 nos., (to be finalised during detailed
engineering as per requirement) shall be provided inside each cabinet for the
incoming and outgoing cables. The terminals shall be serially numbered to facilitate
installation and maintenance. Main busbars shall be accommodated in busbar
chambers and cable alleys arranged by their side. Compression type cable glands
shall be provided to hold the cables to avoid any pressure or tension on the
terminal block connections. The terminal blocks shall be easily accessible for
inspection and checking. Panels shall have cable supports and metallic clips for
supporting power and control cables for internal wiring of the panels.
4.2.4 The busbars shall consist of tinned electrolytic copper of cross- sectional
area of a minimum of 30mm x 5mm, suitable for carrying their rated continuous
current without their temperature exceeding 85 deg C. The busbars shall be
continuous throughout each section. The busbars shall have current rating to suit
the requirements corresponding to the loads incident thereon under the various
operating conditions and shall withstand the applicable voltage and maximum short
circuit stress. The busbars shall be insulated from supporting structure by means
of durable non-hygroscopic, non-combustible and non-tracking polyester fibreglass
material or porcelain. Busbars shall be encased in heat-shrunk sleeves of insulating
material which shall be suitable for the operating temperature of busbars during normal
service. The busbar joints shall be provided with removable thermosetting plastic
shrouds.
The busbars shall be housed in totally enclosed busbar chambers. The incoming
connections from the busbar to the various feeders shall be so designed as not to
disturb cable connections and to ensure safety to the operating and maintenance
personnel and to facilitate working outside any outgoing module without the need for
switching off in-feed to the adjacent modules, as far as possible. The phase and
neutral busbar shall be of high conductivity, adequate uniform cross section and
current density shall not be more than 1.6 Amp/sq. mm.
A cable alley preferably 230 mm wide shall be provided in each vertical section
for taking cables into the compartments.
4.2.7 The AC boards shall be provided with the following equipments wherever
applicable:
ii. Terminal arrangement with necessary equipment for connecting the incoming
supply.
4.2.9 All sheet metal used for DB shall undergo seven tank mechanical/ chemical cleaning
process & painting shall be done using powder coating process. Colour of the Paint shall
be admiral gray as per shade no. 632 of IS 5 on exterior and white from interior sides.
5.0 MAJOR COMPONENTS:
5.1 Incoming cable for ACDB shall be terminated on terminal connectors provided at
the bottom. Connection between incomer terminals and Switch Fuse Disconnector
unit shall be with 50 sq. mm copper cable. Outgoing shall be connected with 35 sq. mm
copper cable.
For 125 A MCB, 50 sq. mm. stranded cable shall be used. For all
32 A rated MCBs, 16 sq. mm. stranded cable; and, for all 16A rated
MCBs, 10 sq. mm. cable shall be used.
All MCBs, cable used in the DB shall be of reputed make and ISI marked.
Incoming circuit shall have one no. 3 phase, 433 volt Switch Fuse
Disconnector unit of nominal current rating of 200Amps conforming to IS:
13947/1993 amended up to date and fitted with HRC fuses and 3 No. LT resin cast
CTs having CT ratio of 200/5 A with burden 10VA & accuracy class 1. Switch Fuse
Disconnector unit shall be of reputed make.
To receive incoming cable, one no. 4 way bolted type connector of suitable size shall be
provided. Provision for one kWH meter (3 ph, 4 wire) of flush mounted type with complete
wiring and connected CTs shall be made in the panel.
Incoming cable for incomer LT XLPE, 4 C, 120 sq. mm shall be provided by WBSEDCL.
5.3 Outgoing circuits:
Sr. Feeder Cable size Purpose
No. Rating
1 TPN 125 A 4 core 50 sq. a. Filtration/ Miscellaneous
MCB mm. LT PVC
cable
2 TPN 32 A 4 core 16 sq. mm a. Water supply
MCBs LT PVC cable b. Outdoor lights
c. Yard light
4 core 10 sq. mm d. Spare (1 nos.)
3 TPN 16 A LT PVC cable a. OLTC for Power
MCBs 2 core 16 sq. mm Transformers (3 nos.)
LT PVC cable b. Spare (1 no.)
4 DP 32 A a. Indoor lights
MCBs 2 core 10 sq. mm b. Battery Charger1
LT PVC cable c. battery Charger 2
d. Spare (1 no.)
5 DP 16 A a. 33 kV Panel AC supply (1 nos.)
MCBs b. 11 kV panel AC supply (1 nos.)
c. Supply for RTU
d. Supply for UPS
e. RTCC (3nos.)
f. Spare (1 nos.)
5.3.1 Total 22 Nos. Outgoing circuits shall be provided as per the details given below.
a) Rated voltage & freq. shall be 230V & 50 Hz respectively for DP MCBs.
b) Rated current shall be 125A/ 32A/16 A as mentioned above.
5.3.4 PVC cable glands of adequate size shall be provided for all incoming and outgoing
cables.
5.3.5 The moving contacts of all poles of multipole circuit breaker shall be so
mechanically coupled that all poles, except the switched neutral, if any, make and
break substantially together, whether operated manually or automatically,
even if an overload occurs on one protected pole only.
A switched neutral pole shall open after and close before the protected pole(s). The
mechanism should be quick make, quick break with trip free mechanism.
Both side terminal should be suitable for direct cabling as well as bus bar connection and
should take wire up to cross section area of 25 sq. mm.
Detailed specification is tabulated below:-
5.4.1 Ammeter:
Ammeter Selector switch shall be a four-position rotary type with R, Y, B and 'OFF'
positions marked clearly on 48 x 48 mm brushed aluminum plate with black handle. The
Switch should be screw mounting type with finger touch proof terminals. Terminal wire
should be inserted from the side of the switch terminal. Terminal screw must be captive to
avoid misplace during maintenance. The switch shall be of 12 A rating with insulation level of 1100
V.
Voltmeter Selector switch shall be a seven-position rotary type ( 6 way & off) with 3 phase
to phase & 3 phase to neutral position marked clearly on 48 x 48 mm brushed aluminium plate with
black handle. The Switch should be screw mounting type with finger touch proof terminals.
Terminal wire should be inserted from the side of the switch terminal. Terminal screw must
be captive to avoid misplace during maintenance. The switch shall be of 12 A rating with
insulation level of 1100 V.
Indicating lamps, for indicating voltage presence in three phases, shall be panel mounting
type 23 mm with rear terminal connections having low wattage LEDs cluster type. Lamps shall
have translucent lamp covers to diffuse lights, coloured red, yellow, green or blue as
specified. The lamp cover shall be preferably of screw-on type, unbreakable and moulded
from heat resisting fast coloured material. Conventional bulbs are not acceptable. The intensity of
light should be minimum 100 milli cd at 20 mA. Indication lamp should be suitable to operate on 230
V AC.
Necessary wiring shall be provided accordingly.
5.4.6 MARKING
Two nos. Earthing studs of galvanized M.S. 25 X 6 mm shall be provided for external earth
connections at the bottom. These should be complete with plain washer, spring washer,
nuts etc. Earthing Bolts must be welded to prevent removal of the same from the cabinet.
Flexible stranded copper connector (braided conductor) should be connected of
copper equivalent 10 sq. Mm size between door and box enclosure. This flexible
braided cable should be terminated using gland and proper size nut/bolts at both ends.
The CTs box, ACDB box are to manufacture with suitable mounting arrangement on
wall/steel support by means of 4 nos. 25X6 mm size clamps having hole dia. 14mm, fixed over the
body as per drawing.
The removable gland plate should be provided in the lower portion of the box to
accommodate all brass glands (according to requirement) for incoming and outgoing cables.
Aluminium sheet 2 mm engraved with details should be provided duly refitted over
front door.
a. ACDB
b. P.O No.
c. ‘Property of WBSEDCL’
d. Name of the Manufacturer
Each ACDB shall be furnished completely factory wired upto terminal blocks ready for
external connections.
All wires shall consist of 1100V grade PVC insulated flexible stranded copper wires with a
cross-section of 2.5 sq. mm suitable for switchboard wiring and
complying with the requirement of relevant IS. Each wire shall bear an identifying
ferrule or tag at each end or connecting point.
Control cables for external connections shall consist of stranded copper wire with
1.5, 2.5, 4.0 sq. mm or higher cross-sectional areas and shall enter from the bottom.
All interconnecting/outgoing control wiring shall terminate on stud type terminals on
terminal blocks. The terminals shall be marked with identification numbers to facilitate connections.
The terminal blocks shall be made of moulded, non-inflammable, plastic material and
arranged to provided maximum accessibility for inspection and maintenance. All terminal block
shall have transparent plastic cover.
The terminals shall be made of hard brass and diameter of not less than
6 mm. The studs shall be securely locked within the mounting base to prevent turning. The terminal
blocks shall be provided with twenty(20) percent spare terminals. The terminals shall be
suitable for connections through tinned copper crimped lugs.
Wiring shall be complete in all respect to ensure proper functioning of
the control, protection and monitoring scheme.
Each wire shall be identified at both ends with permanent markers bearing wire numbers as
per wiring diagram.
MCBs & other components used in ACDB shall be fully type tested as per relevant IS and
this specification. The successful Bidder shall furnish detailed type test reports before
commencement of supply.
All the Type Tests shall be carried out from laboratories which are accredited by the
National Board of Testing and Calibration Laboratories (NABL) of Government of India
such as CPRI Bangalore/ Bhopal, ERDA Baroda, to prove that the MCBs & other components
used in ACDB meet requirements of the specification.
8.0 DRAWINGS:
Successful bidder shall submit the detailed drawings along with component details/makes etc.
for necessary approval.
9.0 INSPECTION:
All tests and inspection shall be made at the place of manufacturer. The manufacturer
shall provide reasonable testing and inspection facilities and co- operation without any charge
to satisfy him that the material is being supplied is in accordance with this specification. The
proto of ACDB shall be inspected
& checked by Ordering Authority or his representative for approval before commencement of
supply.
10.0 SCHEDULES:
The tenderer shall fill in the following schedules, which form part of the tender specification and
order. If the schedules are not submitted duly filled in with the offer, the offer shall be
liable for rejection.
11.0 Deviations
Deviation from this specification, if any, shall be clearly bought out in the offer. Unless
owner explicitly accepts such deviations, it shall be constructed that the offer fully
complies with the specification.
SCHEDULE
‘A’
1. ACDB Panel
Make Havells
Type TPN Switch Fuse Unit with HRC Fuse Link
Current Rating 200A
4. TPN MCB
Make Havells/ C&S
Current rating 125A, 32A, 16A
Voltage rating 433 Volt
5. DP MCB
Make Havells/ C&S
Current rating 32A, 16A
Voltage rating 230 V
6. Low Voltage Terminal connector
Make Elmex / Connectwel / Phonix
Type Locking Stud
Size Suitable for 4.0 sq. mm control wire.
7. Low Voltage CT
Make KAPPA
Type Ring Type
Voltage level 600 volt
Ratio 200/5 Amps
Class 1.0
Burden 10 VA
8. Ammeter
Make AE
Type Analog
CTR 200/5 Amps
Accuracy Class 1.0
Size 96 mm X 96 mm
Mounting Flush mounting
9. Ammeter Selector Switch
Make KAYCEE
Type 4 Position ( R Y B and Off )
Current rating 16 Amps
10. Volt meter AE
Type Analog
Accuracy Class 1.0
Size 96 mm X 96 mm
11. Voltmeter Selector Switch
Make KAYCEE
Type 4 Position ( RN -YN-BN-Off)
Current rating 10 Amps
12. Energy meter
Type 3 Phase 4 Wire, CT operated
CTR 200/ 5 Amps
Accuracy Class 1.0
Voltage 433 V
13. Control wire
Make KEI/Relicab/Polycab/RR Cable
Voltage grade 750V
Size 2.5 sq.mm
Colour Red Phase : Red,
Yellow Phase : Yellow
Blue Phase : Blue
Neutral : Black.
Earth circuit : Green.
14. Earthing Terminal
Material Copper
Shape Rectangular
Size 25 mm x 6 mm
Provision To be provided on both sides of the panel
15. Painting details
1.0 SCOPE:
This specification covers the design, manufacturing, testing at works and supply of
Indoor type D.C. Distribution Boards for protection system of the 33 kV substation. The
system shall be DC, 30 V.
3.0 STANDARDS:
3.1 Components mounted on the ACDB shall confirm to the latest revisions of the
following standards:
B IS 5 Painting
C IS: 13947/1993 Part-III Switch Fuse Disconnector unit
amended up to date
D IS 2705 amended up to date CTs
E IS 8828/1996 amended MCB
upto date
F IS 1248 Indicating instruments
G IS 375 Wiring
H IS: 13703/1993 Part-I & II HRC Fuses
4.0 GENERAL TECHNICAL PARTICULARS:
Rated voltage for the Distribution Board and its constituent items like Switch Fuse
Disconnector unit, MCBs, busways etc. shall be single phase 2 wire D.C. 30 volts. The supply
voltage may vary by ± 10% of rated voltage. All the equipments used in the Board shall
operate satisfactorily at this voltage variation.
4.2.1 Each Distribution Board shall be free standing floor mounted having
compact design. The Board shall be closed, dust protected, weather proof and shall be
made vermin proof with a special type lining e.g. Neoprene gasket, around the
edges of the doors. The distribution board shall comply degree of protection IP 43.
MCBs shall be operating vertically upward for ON/OFF operation. The entire distribution
board shall have uniform finish and shall be sturdy. The distribution boards shall be of
modular construction with provision for complete compartmentalisation of all feeders. It
shall be free-standing, dead front type comprising dust-tight and vermin proof sheet
steel cabinets suitable for indoor installation. The doors of cabinets shall be lockable.
Handle shall be made of reputed make. The DB shall be provided with double door in front
having 2 nos. hinges which should be suitable for movement of 120 degree and 2 no. knobs to
be provided on the door corners. All instruments and control devices shall be mounted on
the front of cabinets and fully wired to the terminal blocks. All switches provided on the
distribution board shall be on front side of the cabinets, operable from outside.
4.2.2 Each Distribution Board shall be made out of at least 2.0 mm thick cold rolled
steel sheet, suitably reinforced to provide flat level surface. Size 1000(H) x 750(W) x
300(D) mm. Gland plate shall be 3.0mm thick. No welds, rivets, hinges or bolts shall be
visible from outside. The doors shall be fitted with double leaf neoprene rubber gaskets.
4.2.3 All cables shall enter and leave from bottom. Suitable cable terminal
blocks with cable lugs shall be provided inside each cabinet for the incoming and outgoing
cables. The terminals shall be serially numbered to facilitate installation and
maintenance. Main busbars shall be
accommodated in busbar chambers and cable alleys arranged by their side. Compression type
cable glands shall be provided to hold the cables to avoid any pressure or tension on the
terminal block connections. The terminal blocks shall be easily accessible for inspection
and checking. Panels shall have cable supports and metallic clips for supporting power
and control cables for internal wiring of the panels.
4.2.4 The DC Distribution Board shall have double bus arrangement with change over
switch. The Distribution Board shall have provision for one set of +ve and –ve connected to
Charger-1 and another set of +ve and – ve connected to Charger-2. Each busbars shall consist
of tinned electrolytic copper of cross-sectional area of a minimum of 25mm x 3mm,
suitable for carrying their rated continuous current without their temperature
exceeding 85 deg C. The busbars shall be continuous throughout each section. The
busbars shall have current rating to suit the requirements corresponding to the loads
incident thereon under the various operating conditions and shall withstand the applicable
voltage and maximum short circuit stress. The busbars shall be insulated from supporting
structure by means of durable non-hygroscopic, non-combustible and non-tracking
polyester fibreglass material or porcelain. Busbars shall be encased in heat- shrunk sleeves
of insulating material which shall be suitable for the operating temperature of
busbars during normal service. The busbar joints shall be provided with removable
thermosetting plastic shrouds.
The busbars shall be housed in totally enclosed busbar chambers. The incoming
connections from the busbar to the various feeders shall be so designed as not to
disturb cable connections and to ensure safety to the operating and maintenance
personnel and to facilitate working outside any outgoing module without the need for
switching off in-feed to the adjacent modules, as far as possible. The busbars shall be
of high conductivity, adequate uniform cross section and current density shall not be more
than
1.6 Amp/sq. Mm.
A cable alley preferably 230 mm wide shall be provided in each vertical section for
taking cables into the compartments.
4.2.6 Danger board (Caution Plate) shall be fitted suitably on inner door of the DB.
Danger board shall be of 100x100 mm size with details as per WBSEDCL standard
format.
4.2.7 The DC boards shall be provided with the following equipments wherever
applicable:
i. Double bus arrangement with change over switch with provision for one set of
+ve and –ve connected to Charger-1 and another set of +ve and –ve connected to
Charger-2. Each busbars shall consist of tinned electrolytic copper of cross-
sectional area of a minimum of 25mm x 3mm.
ii. Terminal arrangement with necessary equipment for connecting the incoming
supply.
vii. The number of outgoing feeders from DC boards shall be such that each
substation equipment is fed by separate feeder with 20% as spare.
4.2.9 All sheet metal used for DB shall undergo seven tank mechanical/ chemical cleaning
process & painting shall be done using powder coating process. Colour of the Paint shall
be admiral gray as per shade no. 632 of IS 5 on exterior and white from interior sides.
5.1 Incoming cables for DCDB shall be terminated on terminal connectors provided at the
bottom. Connection between incomer terminals and MCBs shall be with 50 sq. mm copper
cable. Outgoing shall be connected with
35 sq. mm copper cable.
For all 32 A rated MCBs, 16 sq. mm. stranded cable shall be used. For all 16A rated MCBs, 10
sq. mm. stranded cable shall be used.
All MCBs, cable used in the DB shall be of reputed make and ISI marked.
DCDB should have 2 sets of Bus Bars in Two separate compartments to facilitate
termination of Incomers from two sets of Battery and Chargers. One Change over
switch should be provided to facilitate DC supply to outgoing load circuit in the event
of failure of anyone of the battery/ Charger. The change over switch should be 2 way
2 position for changing over of both incomer individually.
Two double pole MCBs of 63 Amps capacity shall act as Incoming breaker of load bus. Change
over switch of 63 Amps DP is to be provided.
Incoming cable for incomer LT XLPE, 2 C, 120 sq. mm shall be provided by WBSEDCL.
5.3.1 Total 24 Nos. outgoing circuits shall be provided as per the details given below.
a) Rated voltage & freq. shall be 240V & 50 Hz respectively for DP MCBs.
b) Rated current shall be 32A/16 A as mentioned above.
5.3.3 The enclosure shall be provided with proper earthing arrangement. Earthing
arrangement shall consist of 2 G.I. Bolts of 12 mm x 50mm (min.) with 2 spring/ plain washers and
2 check nuts.
5.3.4 PVC cable glands of adequate size shall be provided for all incoming and
out going cables.
5.3.5 The moving contacts of all poles of multi-pole circuit breaker shall be so
mechanically coupled that all poles, except the switched neutral, if any, make and break
substantially together. Whether operated manually or automatically even if an overload
occurs on one protected pole only.
Both side terminal should be suitable for direct cabling as well as bus bar
connection and should take wire up to cross section area of 25 sq.mm.
Emergency lighting circuit shall be provided by the Bidder such that the lights normally
burn on AC 240 Volts, 50 Hz but in case of failure of AC supply, these come up on DC
supply with the help of automatic change over contactors and again change over to AC
supply with the restoration of AC supply. There shall be two number double pole ON/OFF
switches with HRC fuses one each for AC and DC supply.
Indicating lamps shall be panel mounting type 23 mm with rear terminal connections having
low wattage LEDs cluster type. Lamps shall have translucent lamp covers to diffuse
lights, coloured red for ‘DC ON’ condition. The lamp cover shall be preferably of screw-on type,
unbreakable and moulded from heat resisting fast coloured material. Conventional bulbs
are not acceptable. The intensity of light should be minimum 100 milli cd at 20 mA.
Indication lamp should be suitable to operate on 30 V DC.
Necessary wiring shall be provided accordingly.
5.4.6 MARKING
Each compartment shall be provided with legible and indelibly marked/
engraved name plate.
Name plates shall be white with black engraved letters. On top of each module, name plates with
bold letters shall be provided for feeder designation. Each device shall also suitably marked
for identification inside the panels. Name- plates with full and clear inscriptions shall be
provided inside the panels for all isolating switches, links, fuse blocks, test blocks and cable
terminals. Every switch shall be provided with a nameplate giving its function clearly.
Switches shall also have clear inscriptions for each position indication e.g. ‘ON’ ‘OFF’ etc.
Two nos. Earthing studs of galvanized M.S. 25 X 6 mm shall be provided for external earth
connections at the bottom. These should be complete with plain washer, spring washer,
nuts etc. Earthing Bolts must be welded to prevent removal of the same from the cabinet.
Flexible stranded copper connector (braided conductor) should be connected of
copper equivalent 10 sq. mm. size between door and box enclosure. This flexible
braided cable should be terminated using gland and proper size nut/bolts at both ends.
The DCDB box are to manufacture with suitable mounting arrangement on wall/steel
support by means of 4 nos. 25X6 mm size clamps having hole dia. 14mm, fixed over the body as
per drawing.
The removable gland plate should be provided in the lower portion of the box to
accommodate all brass glands (according to requirement) for incoming and outgoing cables.
5.4.10 Name Plate:
Aluminium sheet 2 mm engraved with details should be provided duly refitted over
front door.
a. DC Distribution Box
b. P.O No.
c. ‘Property of WBSEDCL’
Each DCDB shall be furnished completely factory wired up to terminal blocks ready
for external connections.
All wires shall consist of 1100V grade PVC insulated flexible stranded copper
wires with a cross-section of 2.5 sq. Mm suitable for switchboard wiring and complying
with the requirement of relevant IS. Each wire shall bear an identifying ferrule or tag
at each end or connecting point.
Control cables for external connections shall consist of stranded copper wire with
1.5, 2.5, 4.0 sq. Mm or higher cross-sectional areas and shall enter the bottom.
All interconnecting/outgoing control wiring shall terminate on stud type terminals on
terminal blocks. The terminals shall be marked with identification numbers to facilitate
connections.
The terminal blocks shall be made of moulded, non-inflammable, plastic material and
arranged to provided maximum accessibility for inspection and maintenance. All terminal block
shall have transparent plastic cover.
The terminals shall be made of hard brass and diameter of not less than
6 mm. The studs shall be securely locked within the mounting base to prevent turning. The
terminal blocks shall be provided with twenty(20) percent spare terminals. The terminals
shall be suitable for connections through tinned copper crimped lugs.
Wiring shall be complete in all respect to ensure proper functioning of the control,
protection and monitoring scheme.
Each wire shall be identified at both ends with permanent markers bearing wire numbers as
per wiring diagram.
MCBs & other components used in DCDB shall be fully type tested as per relevant IS and
this specification. The successful Bidder shall furnish detailed type test reports before
commencement of supply.
All the Type Tests shall be carried out from laboratories which are accredited by the
National Board of Testing and Calibration Laboratories (NABL) of Government of India
such as CPRI Bangalore/ Bhopal, ERDA Baroda, to prove that the MCBs & other components
used in DCDB meet requirements of the specification.
8.0 DRAWINGS:
Successful bidder shall submit the detailed drawings along with component details/makes etc.
for necessary approval.
9.0 INSPECTION:
All tests and inspection shall be made at the place of manufacturer. The
manufacturer shall provide reasonable testing and inspection facilities and co- operation
without any charge to satisfy him that the material is being supplied is in accordance with this
specification. The proto of DCDB shall be inspected
& checked by Ordering Authority or his representative for approval before commencement of
supply.
10.0 SCHEDULES:
The tenderer shall fill in the following schedules, which form part of the tender specification and
order. If the schedules are not submitted duly filled in with the offer, the offer shall be
liable for rejection.
11.0 Deviations
Deviation from this specification, if any, shall be clearly bought out in the offer. Unless
owner explicitly accepts such deviations, it shall be constructed that the offer fully
complies with the specification.
SCHEDULE ‘ A’
Y/N
7. No. of 1 ph 36 A DP MCBs provided Y/N
The Remote Terminal Unit (RTU) shall be installed to acquire data for control of Substation
devices and different parameters. The supplied RTUs shall be interfaced with the substation
equipment, communication equipment, power supply distribution boards by providing all the interface
cables, TBs, wires, lugs, glands etc.
The RTUs need to be installed in separate panel. The RTU panel also must house the SMPS
based DCPS and the Batteries, Modems/Routers and other accessories to be supplied by the
Bidder. All necessary requirements for such arrangement within the panel must be made.
• The RTUs shall have following communication ports to communicate with master station,
MFTs and configuration & maintenance terminal.
• RTU shall have at least two TCP/IP Ethernet port for communication with Master
station(s) using IEC 60870-5-104 protocol.
• RTU shall have minimum 2(two) number of RS 485 ports for communication with MFTs to
be connected in daisy chain using MODBUS protocol. Minimum 15 analog values
(including 4 energy values) to be considered per energy meter. The RTU shall be
designed to connect maximum 5 MFT per port. Further, bidder to demonstrate during
testing that all analog values updated within 2 Sec.
• RTU shall have one Ethernet/USB 2.0port for maintenance
• The RTU shall support the use of a different communication data exchange rate (bits per
second) and scanning cycle on each port & different database for each master station.
• RTU shall use IEC 60870-5-104 communication protocol for communicating to master
station. The RTU communication protocol shall be configured to report analog (except
energy values) & status changes by exception to master stations. However, RTU shall
support periodic reporting of analog data and periodicity shall be configurable from 2
sec to 1 hour. Digital status data shall have higher priority than the Analog data. The
dead-band for reporting Analog value by exception shall be initially set to 1% (in %) of the
full scale value. In addition, analog values shall also be reported to Master station by
exception on violation of a defined threshold limit. All the analog values and status data
shall also be assigned to scan groups for integrity check by Master stations at every 10
minutes configurable up to 60 minutes RTU wise.
• RTU shall report energy values to master station periodically. The periodicity shall be
configurable from 5 minutes to 24 hours (initially set for 15 minutes)
• The RTU shall acquire data from the MFTs using the MODBUS protocol.
• The real time values like Active power, Reactive Power, Apparent power, three phase
Current & Voltage and frequency, and power factor & accumulated values of import
/export energy values will be acquired RTU from the following in the given manner:
• All status inputs shall be scanned by the RTU from the field at 1 millisecond
periodicity.
• The RTU shall make provision to stop transmission when a Transmission Disable
command is received from Control Centre. This is to suppress spurious recurring
indications/ alarms.
• Local indication for healthiness of Card shall be provided.
• The RTU shall maintain a clock and shall time-stamp the digital status data. Any
digital status input data point in the RTU shall be assignable as an SOE point. Each
time a SOE status indication point changes the state, the RTU shall time-tag the
change and store in SOE buffer within the RTU. A minimum of 4000 events can
be stored in the SOE buffer. SOE shall be transferred to Master Station as
per IEC60870-5-104 protocol. SOE buffer shall be maintained by FRTU on power
supply interruption.
The RTU shall include the following security and safety features as a minimum for
control outputs:
A manual Local/Remote selector switch shall be provided for each RTU to disable all
control outputs by breaking the power supply connection to the control outputs. When
in the "Local" position, the Local/Remote switch shall allow testing of all the control
outputs of RTU without activating the control outputs to field devices. A status input
indication shall be provided for the Local/Remote switch to allow the SCADA system to
monitor the position of the switch. RTU with inbuilt local remote selector switch also will be
acceptable.
It shall provide a latching relay to be used to simulate and test supervisory control from
the Master station. The latching relay shall accept the control signals from the RTU to
open and close, and shall provide the correct indication response through a single point
status input.
The relays shall be DC operated self reset type. The relay shall be able to operate for
+/-20% variation from nominal voltage.
The relay shall have a minimum of two change over contacts, out of which one
shall be used for telemetry purposes. The contacts shall be rated to carry minimum
current capacity of 5A.
The internal RTU time base shall have a stability of 10 ppm. The RTU shall be
synchronised through synchronisation message from master station at every 5 minutes
(configurable from 5 minutes to 60 minutes) over IEC 60870-5-104/NTP/SNTP.
15.0 Diagnostic Software
All RTU modules, shall have light emitting diodes (LEDs) to indicate errors or
operating modes. The application/configuration data shall be stored on SD Cards which
makes it possible to exchange modules without new configuration download. The
functional operation of the RTU shall be guaranteed by a comprehensive monitoring
concept. The hardware and software shall be continuously monitored from the I/O
modules throughout the entire RTU. The hardware and software monitoring shall be
carried out by active checks at several levels. The RTU shall report its system and error
states to the Control Centre by means of System Events. The RTU shall provide remote
diagnostics capabilities. It shall be possible to connect to the RTU from a remote
computer in order to analyze the system and error status, check-up of the configuration or
signal values of the RTU remotely, e.g. by means of a Web-Server via LAN/WAN.
Remote access via Intranet shall be combined with authority privileges for the user
for following activities:
The RTU shall comply the advanced cyber security standard i.e ISO 27002 2005
(previously known as ISO IEC 17799 2005), NERC CIP-009-1, and ISA-99.02.01[5]–[7],
IEEE 1686 standard and should have following features:
User level configuration
User wise authentication like system admin, configuration admin, control, operator.
Disabling the DNS
Disabling, enabling & configuration of the TCP and UDP ports.
Door lock alarm integration with RTU.
Local and remote access connection shall be secured for maintenance (locally and
remotely) with HTTPS, IPSEC protocols
Role Based User Account Management (UAM) integrated in the Web Server
User Activity Log (UAL) on the SD card or internal memory of the CPU
Password Complexity enforcement based on at least one
upper/lower/number/ non- alphanumeric character options
Security Event Logging and viewing of the same through the web browser. It
shall also be possible to upload this log into .CSV files.
The FRTU shall be hardened - Closing of unused TCP/IP ports and services
Enabling/disabling of Web Server use
Secured HTTPS connection to the RTU through Web Browser shall be supported
RTU should conform any of the following security standards in respect
of above functionalities and to be tested as per following standard:
a. NERC/CIP - North American Electric Reliability Corporation - Critical
Infrastructure Protection NERC CIP-009-1, and ISA-99.02.01[5]–[7]
b. IEC 62351-5:2013,IEC 62351-3- Power systems management and associated
information interchange - Data and communications security
c. IEEE 1686 - Standard for Substation Intelligent Electronic Devices (IED)
Cyber Security capabilities.
19.0 Archives:
RTU Events shall be archived in logs in CPU internal memory or external SD card.
RTU Events shall be stored in the archive logs with a time resolution of 1ms, and a
discrimination of 10ms.The capacity of the logs shall be more than 30,000 events and
measurement. All the logs shall be available from a maintenance tool connected to the
RTU or sent on request to the SCADA. The content of the logs shall be configurable and the
name of the logs sent to the SCADA shall be configurable. It shall be formatted as a .csv
file.
At least 50% of the space inside each enclosure shall be unused (spare) space that
shall be reserved for future use. RTU panel dimension should be around 650mm (W), 450mm
(D), 1200mm (H). Panel with lesser dimension is preferred. The Contractor shall provide
required panels conforming to IEC 529 for housing the RTU modules/racks, relays etc.
and other required hardware. No IO module shall be placed outside the RTU panel. The
panels shall meet the following requirements:
(a) Shall be pole/ floor mounted compact size cabinet. The size shall be sufficient to
accommodate the RTUs and associated equipment required for telemetry and
control and shall be designed according to the site requirement/locations at the
time of design/ engineering. All doors and removable panels shall be fitted with
long life rubber beading. All non load bearing panels/doors shall be
fabricated from minimum 1.6 mm thickness steel sheet and all load bearing
panels, frames, top & bottom panels shall be fabricated from minimum 2.0 mm
thickness steel sheet
(b) Shall have maintenance access to the hardware and wiring through lockable
doors.
(c) Shall have the provisions for bottom cable entry
(d) The safety ground shall be isolated from the signal ground and shall be
connected to the ground network. Safety ground shall be a copper bus bar. The
contractor shall connect the panel’s safety ground to the owner’s grounding
network. Signal ground shall be connected to the communication
equipment signal ground.
(e) All panels shall be supplied with 230 Vac, 50 Hz, single-phase switch and
15/5A duplex socket arrangement for maintenance.
(f) All panels shall be provided with an internal maintenance lamp and gaskets.
(g) Panel shall be indoor, dust proof with rodent protection and meet IP 41
(h)There shall be no sharp corners or edges. All edges shall be rounded to
prevent injury.
(j) All materials used in the enclosures including cable insulation or sheathing,
wire troughs, terminal blocks, and enclosure trim shall be made of flame
retardant material and shall not produce toxic gasses under fire conditions.
(k) Panels shall have padlocking arrangement.
All wires that carry low-level signals shall be adequately protected and
separated as far as possible from power wiring. All wires shall be identified either by
using ferrules or by colour coding. In addition, cables shall be provided with cable
numbers at both ends, attached to the cable itself at the floor plate where it enters the
cubicles.
Shielded cables shall be used for external Cabling from the RTU panels. The
external cables (except communication cables) shall have the following characteristics:
All terminal blocks shall be suitably arranged for easy identification of its
usages such as CT circuits, PT circuits, analog inputs, status inputs, control outputs,
auxiliary power supply circuits, communication signals etc. TBs for CT circuits shall
have feature for CT shorting (on CT side) & disconnection (from load side) to
facilitate testing by current injection. Similarly, TBs for PT circuit shall have
feature for disconnection to facilitate voltage injection for testing.
RTU including Transducers shall conform to the type tests listed in the relevant
table. Type test reports of tests conducted in NABL accredited Labs or
internationally accredited labs within last 5 years from the date of bid opening
may be submitted. Bidder shall offer only Type tested Product. A complete integrated
unit shall be tested to assure full compliance with the functional and technical
requirements of the Specification. The testing sample shall include one of each type of
cards/modules and devices. For other items also such as MFT, sensor etc the
requirements are mentioned in the respective sub sections of specification. However,
the type tests shall be only be limited to the specification of that item only. Type Test
reports shall be in the name of the Bidder for RTU.
After field testing, RTU shall exhibit a 99% availability during test period
(15 days). Availability tests shall be performed along with Master station.
The RTU shall be considered available only when all its functionality and
hardware is operational. The non-available period due to external factors such as
failure of communication link etc., shall be treated as hold-time & availability test
duration shall be extended by such hold time.