RET670 DIFFERENTIAL RELAY

GBASVAL:1 GBASVAL:2
Sbase 90 MVA Sbase 90 MVA
Ubase 220 kV Ubase 33 kV
Ibase 236.18204 A Ibase 1574.5469 A
Side1 CTR 800 A Side2 CTR 2000 A

Side1 FLC Pri 236.18204 A Side2 FLC Pri 0.2952275 A


Side1 FLC Sec 1574.5469 A Side2 FLC Sec 0.7872735 A

IdMin 0.3 %IB


EndSection1 1.25 %IB
EndSection1 3 %IB
SlopeSection2 40 %
SlopeSection3 80 %
IdUnre 10 %IB

IdMin Pickup Values


Side 1 If Dela Winding Side 2 if Star Winding
1-Phase 0.1534091 A 1-Phase 0.3542731 A
2-Phase 0.0767045 A 2-Phase 0.236182 A
3-Phase 0.0885683 A 3-Phase 0.236182 A

IdUnres Pickup Values


Side 1 If Dela Winding Side 2 if Star Winding
1-Phase 5.1136364 A 1-Phase 11.809102 A
2-Phase 2.5568182 A 2-Phase 7.8727346 A
3-Phase 2.9522755 A 3-Phase 7.8727346 A
Y=MX+C
Note: Please Enter Values In Yellow Box only M 0.4
X 1.75
C 0.3
Y 1

Y=MX+C
Y 10
IBias IDiff M 0.8
0,0 0 0.3 C 1
1,1 1.25 0.3 2.4
2,2 3 1 1
3,3 14.25 10 11.4
X 14.25
Idifferential/IBias
12

10

8
I Differential

0
0 2 4 6 8 10 12 14 16
I Bias
1000000 P=1.7321*V*I
1000 I=P/1.7321*V

1.7321 HV S 90000000
0.86605 LV S 90000000
1.5 HV V 220000
0 LV V 33000
100
S1 0.4 MLF HV 3.3872178
S2 0.8 MLF LV 1.2702067