Professional Documents
Culture Documents
THESIS^
STATIC RELAYS FOR THE PROTECTION OF
25 kV SINGLE-PHASE TRACTION OVERHEAD EQUIPMENT
(With Particular Reference to the Indian Railways)
A THESIS
Submitted in fulfilment
of the requirements of the Degree
of
DOCTOR OF PHILOSOPHY
IN
ELECTRICAL ENGINEERING
r"
ia-2'^
By
HAR1SH KUMAR VERMA
CERTIFICATE
-Lx
Roorkee? (T.S.M. Rao)
December /^ ,1976 Professor and Head,
Department of Electrical Engg.,
University of Roorkee,
Roorkee.
-11-
ABSTRACT
LIST OF CONTENT'S
Page
CERTIFICATE
i
ACKNOWLED GEMENTS
ii
ABSTRACT
iii
LIST OF CONTENTS
viii
LIST OF SYMBOLS, SUBSCRIPTS AND ABBREVIATIONS
xiv
CHAPTER I • INTRODUCTION
CHAPTER II _
STATIC RELAYS WITH MODIFIED CHARACTERISTICS FOR
OVERHEAD EQUIPMENT PROTECTION "^^^ *Qh ... 13
2.1 Maloperation of the Existing Relays ...13
2.2 Modification of the Relay Characteristics ... lif
2.2.1 Earth Fault Distance Relay ... 1^
2.2.2 Wrong Phase Coupling Relay ...17
2.2.3 Back-up Overcurrent Relay ...19
2.3 Static Relays versus Electromechanical
Relays
... 20
2.if Static Relay Prototypes for the Indian
Railways
...22
2.if.l D.C. Supply for Relay Circuits ... 23
2.if. 2 Output Device
...23
2.if.3 Operation Indicator ... 25
2.if.if Relay Cabinets
25
2.if.5 Selection of Components 26
-IX-
-• • Page
CHAPTER III - D.C. SUPPLY FOR STATIC RELAYS ...... 29
3.1 D.C. Supply Sources ... 29
3.2 D.C. Supply for Distance and Directional
Relays ..... 32
3.2.1 Available Schemes .... 32
3.2.2 Proposed Method ... 33
3.2.3 Adjustments of Auxiliary V.T. Ratio
and Transactor Impedance ... 37
3.2.if Variations in Source Impedance ... ifl
3.2.5 Test Results ... 1^.2
3.3 D.C. Supply for Other Relays ... if5
3.if Relays without D.C. Supply ... 1^.6
Page
CHAPTER V - QUADRILATERAL DISTANCE RELAY ... 82
5.1 Sampling Technique ... 83
5.2 Relay Principle ttt 36
5.2.1 Reactance Characteristic ... 86
5.2.2 Ohm Characteristic 88
5.2.3 Restricted-Directional Characteristic 90
5.2.if AND-Gating for the Quadrilateral
Characteristic #.. 92
5.2.5 Dual Comparison ... 9^
5.3 Relay Operation on Unfavourable Conditions . ... 96
5.3.1 Operation on Transients ... 96
5.3.2 Operation on Small Current Signal ... 96
5.3.3 Operation on Close-in Faults ... 97
5.if Relay Details ... 97
5.if.l Block Schematic ... 97
5.if. 2 Complete Circuit .... 99
5.if.3 Sampling Unit ...101
5.if.if Memory Circuit ...101*
5.if.5 Temperature and Surge Immunity ...106
5.5 Performance Tests ...106
5.5.1 Steady-State Characteristic ...106
5.5.2 Operating Time ...107
5.5.3 Transient Overreach ...108
5.5.if Accuracy/Range Curves ...110
5.5.5 Effect of Frequency Variation ...112
5.5.6 Simulated-Traction-System Test ...116
5.5.7 Burdens ...119
CHAPTER VI - QUADRILATERAL DISTANCE RELAY APPLYING
OPERATIONAL AMPLIFIERS ...120
6.1 Measuring Principle ...121
6.1.1 Reactance Characteristics ...121
6.1.2 Ohm Characteristic ...122
6.1.3 Restricted-Directional Characteristic ...123
6.1.if AND-Gating for the Quadrilateral
Characteristic ...123
-XI-
Page
Page
REFERENCES 219
APPENDICES
Page
Symbols
A amperes
C capacitance", capacitor
D diode
I current
K a constant
L inductance
P potentiometer
P,Q wrong phase coupling points
Q transistor
R resistance*, resistor
S,T wrong phase coupling points
V voltage*, volts
X reactance' accuracy
Y range
Z impedance
ZD zener diode
a,b constants
e source voltage (instantaneous value)
f frequency
i current (instantaneous value)
J a /.90^ operator
k ratio of auxiliary voltage transformer
n an unspecified number
p,q slopes of straight lines*, scaling factors
r resistance
s seconds
t time
ajpjYjS angles
T) amplitude-to-width conversion factor
9 angle of transactor or replica impedance
X an angle
K radians in 180 degrees
0 angle by which the current lags the voltage in
a protected circuit
t an angle
w frequency in radians/second
Q ohms
V phasor V
|V| rectified value of V
Subscripts
N neutral
R 'red* phase
Y 'yellow' phase
Abbreviatinns
INTRODUCTION
-1-
protective relays.
>. X
/
1 "1 OLATOR
L5ULM4J&J ULfiJULfiAaJ
132/25 kV TRANSFORMER
nnswsTS^r oatrffwoo)
V A-EARTHING THROUGH TRACK
-25kV BUS
\'Y
FOR FEEDER
& OHE
rao- -G>—VT
PROTECTIONS /- 25KV FEEDER BREAKER
fll~ •C.T.
-^_^L
INSULATED OVERLAP T NEUTRAL SECTION
h— - 50 TO 80 KM.
set for the single-track operation for which the OHE impedance
is the maximum. The polarizing circuit of the relay is tuned
so that 'memory action' is available in it, which assures correct
relay operation on close-up faults. In order to take full
advantage of the memory action, the line voltage-transformer(VT)
is mounted on the transformer side of the feeder circuit breaker.
STATIC RELAYS
WITH
MODIFIED CHARACTERISTICS
FOR
OVERHEAD EQUIPMENT PROTECTION
-13-
coupling on the OHE. Secondly, both the earth fault and WPC
distance relays were observed to operate simultaneously in many
earth faults',
(b) that in some cases the earth fault mho relay also
The above facts reveal that the relays are not completely
selective in their operation. The unwanted relay operations, as
similar voltages,
10 - INSULATED OVERLAP
NS— NEUTRAL SECTION
-*Zo°
EARTH FAULT AREA
\
QUADRILATERAL CHARACTERISTIC
MHO CHARACTERISTIC
\
LOAD LOCUS
RATED LOAD
\
V
\
\
\
\
\
\
V- MAXIMUM PERMISSIBLE LOAD* \
\ WITH MHO RELAY \
t
-16-
The four WPC points Pn, Qn, Sn and Tn represent the impedances
seen by the relay under normal feed conditions for the four poss
ible values of the phase-difference between the coupled voltages.
Similarly, the points Pfi, Qe, SQ and Te correspond to the WPC
under emergency feed conditions. The complete R-X diagram is drawn
to scale on the basis of the impedance values worked out in
Appendix A. Single-track operation and an average value of the
inter-substation spacing are assumed.
A mho relay, with its reach set to cover earth faults upto
the next substation (that is, faults over the entire emergency
feed-section) taking into account the maximum fault resistance as
represented in the earth-fault area, may enclose one or two WC
points within its operating region. The figure represents such a
case where the WPC points Qn and Sn (corresponding to the +120°
phase difference between the coupled voltages under normal feed
conditions) are enclosed by the operating characteristic of the
relay. Therefore, In this case the earth fault relays at both the
substations would operate undesirably on phase-to-phase faults
(WPC) if the phase difference between the feeds happens to be
120 or, else, the connections of the substation transformers
leading to a 120° phase difference should be avoided.
figure. Apparently, all the WPC points are well outside the
tions, are also drawn on the R-X diagram. Either of the two
circles encloses the WPC points Pn and CL corresponding to the
normal feed conditions and P and 0o for the emergency feed
conditions. The relay (of either type) would operate only if the
local voltage lags the voltage of the other substation', otherwise
the impedance seen by the relay is one of the points S , T ,
Sp and T , all of which are outside the relay characteristic.
ICTED-DIRECTIONAL CHARACTERISTIC •
MAXIMUM-TORQUE LINE -PLAIN MHO CHARACTERISTIC
FOR MHO RELAYS
OFFSET MHO CHARACTERISTIC
The plain mho relay is thus an ill choice for the WPC
has been employed for two reasons*. Firstly, the relay mainten
19
cabinets . In fact, cabinets similar to those of the existing
D.C. SUPPLY
FOR
STATIC RELAYS
-29-
simpler cases, where the relay can derive its d.c. supply from
CT or VT alone, are also incorporated. In addition, a few measur
ing circuits for instantaneous overcurrent and overvoltage
relays, that require no d.c. supply, are suggested.
the d.c. voltage. As for the various d.c. supply sources, either
a single source can be maintained for the entire protection gear
at a station or each relay can incorporate its own source. In
the former case, the supply is obtained from the station battery
or from an auxiliary battery, usually of 21+ or 1+8 volts2^,
maintained either exclusively for the protection gear or for
serving other installations, such as telemetry, remote control and
remote signalling, as well. Usually the station battery voltage
-30-
is much higher than that required for the relays, which ncess-
I- V Vs ... (3.1)
or vs = kl = kvr+ irzr ... (3.2)
where k = V /E and Z = kZ .
s r s
vab
'1q "Ib 'ic
VaflAAlSLiL/ AUX. \$XT SjLSL^
TRANSACTORS
^nnJlp^-i V-T- j-nnrv. r^rinn, r^nrs
4=/l20
L 120
f f T -# +
D.C.TO
FILTER REGULAT-
RELAY
ING
CIRCUITS
CIRCUIT
• -
RELAY
SOURCE LOCATION
SYSTEM
ON
V,
FORWARD
SIDE OF
RELAY
u
Vr
Vc -• +
REGULAT D.C. TO
FILTER
ING RELAY
CIRCUIT CIRCUITS
• —
E = V + I Z a 3s
a ra ra s ... (3.3)
and thence ~V = kE = kV + I Z fi i ^
s a ra ra r *• • o.«*fJ
where k = V /E . and Z = kZ
s phase *"" r s*
them to get the d.c. supply as shown in figure 3.*+. This scheme
VbwU
h and VO Let
can be produced by mixing three delta-voltages with
the respective delta-currents according to relation (3*6). The
a.c. supply voltages can then be rectified and regulated in a
provisions for setting the ratio of the auxiliary VTs and the
in figure 3.5.
phasors kV and 2L2L are in phase for the correct argument, viz.
arg Zr = arg Z . The correct value of the a.c. supply voltage,
V | is thus given by the scalar sum of the components, that is
resultant would be
|l/2
V
s
=[(k Vr)2 +(lrZr)2+ 2(kVr)(IrZr)cos a]'
Vso" 2(kVr)(lrZr)(l-cos a) 1/2 ... (3.8)
AV,
o S
Va -VSO _
jj.+ cos
j_l+ cos a„l/2
a-1/2
V
so
" V
so
=[ 2 J "2 ••• (3-9)
-i+0-
FROM V rs FROM CTs
v_sa
V_Sb
vsc
MVIARNTXO.(PERCNT) O•i i
FILTER
REGUL
ATING
CIRCUIT
f
D.C. TO
RELAY CIRCUITS
\
>
1 1 1 I
-20 - 10 10 20
DISCREPANCY IN k OR MOD. Zr *
- 10- (percent)
\1
-20-
percent, which is too small when compared with that for the
first part, the constancy of the supply voltages, both a.c. and
phase- to- neutral fault and three-phase fault. Each type of the
fault was created once at the relay location and then at a dis
follows*.
ID
(J
<
O
>
98
The d.c. supply for the relays that have to make measure
a.c. input current a little less than the minimum pick-up setting
REFERENCE OUTPUT
DIODE THYRISTOR
INPUT SIGNAL
¥ f
D.C.TRIP
SUPPLY
I
L
C.B. AUX. SWITCH
-nm^-
TRIP COIL
(<0
INPUT Hi
INPUT
* £
,A • TRIP
[COIL
(C)
FIG.3.9 INSTANTANEOUS O/C AND O/V RELAY CIRCUITS USABLE WITH THYRISTOR
OUTPUT
OUTPUT
REED
i REED
RELAY RELAY
INPUT
^
i
(a) (b)
FIG.3.10 INSTANTANEOUS O/C AND O/V RELAY CIRCUITS USABLE WITH REEDRELAY
CHAPTER IV
presented.
Zn 3> » »' »» N
to enclose the points P and Q obtained for the first case and
P1 and Q' for the second case, the relay would operate on any
WPC condition within the two extreme cases. An appropriate
allowance should be provided at either end of the operating
A 0
E 0
F 0
if degrees more than the catenary impedance angle for the tract
d.c. supply unit for biasing its measuring circuits. The d.c.
figure 3.3 has been used for each d.c. voltage. Additional
changing to any other d.c. supply source. The voltages ic, V and
secondaries.
in series with the output voltage Jea' from the transactor 'B!.
mix MIX
"\
±
Z.C.D Z.CL. I c.c
RECTIFIER RECTIFIER Z.C.D.
- T0-+ •+ TO- -TO + + TO -
DELAY DELAY
FILTER FILTER
<* - e o< - e
r
VOLTAGE
3
VOLTAGE GATE GATE
to
cc
D.C. VOLTAGES O
(I)
v
D.C. SUPPLY CIRCUITS PULSE PULSE
STRETCHING STRETCHING
CIRCUIT CIRCUIT
AND
O
OUTPUT
DEVICE
Z>
"1 a.
TRIP J
FIG. 4.3 BLOCK SCHEMATIC OF THE W.P.C. RELAY
(Z.C-D.-ZERO CROSSING DETECTOR)
-58-
regulators used for the two supplies are of series type and
spike coincidence circuit, for which the input and output wave
small values of the input resistors R-j and Rp. The base current
of Q-, at large input voltages is limited by the zener diode.
rather than the zero value exactly* of VV. This error is consi
derably reduced by using a resistance IU of such a value that
gible (less than 1°) upto 5 percent of the maximum allowable input
voltage and about 5° at 2 percent of the same.
tials.
-V^ approx. The charging time constant (R^+ RD)C, RD being the
forward resistance of D, is taken much smaller than the input
-v,
ZD-
ALzd,
I 1
"=• +V:
(a)
• OUTPUT
INPUT
( b)
V2 = (V±+ V2)il-exp(-T/R^C)}
or T = R, C ln[(V1+ Vg)/^}
time constant.
current signal to the relay becomes too low to cause any problem
very small, the relay has not to operate. It is, therefore, necess
ary to only increase the restraining tendency of the relay when
any input signal is too weak to allow an accurate measurement.
This is ensured by the dual-comparison. The comparators work
with reference to the spikes derived at the zero crossings of the
input signals. On a very small input, the negative-to-positive
and positive-to-negative ZCDs err on opposite sides, that is the
spike from one ZCD is obtained after and that from the other
(a.c.) terminals.
transformer windings.
-70-
of the cables for the a.c. input and control output of the
relay. These measures become more important when the cables are
long:
possible.
the relay fails to operate for any value of che impedance angle.
less than 1.3 A (for the maximum catenary length). The experi
mental curves of figure i+.6 indicate that the constriction in
During the test, the d.c. supplies were given from external
sources because the a.c. voltage and a.c. current signals to the
relay were taken from different circuits. If obtained internally.
the d.c. voltages may become too low when both the a.c. voltage
-72-
(a)
180
(b)
and current are small and too high when both of them are large.
zero, +100 percent and -100 percent, once with a fixed fault
current value (steady state component) of 2 A and second time
with a fixed post-fault voltage of 50 V. The results are shown
at (a) and (b) in figure if.6.
fact that the shifts in the two zero crossings of the current
a) (b)
2 - FAULT CURRENT
3 - OUTPUT OF COMPARATOR-i
4 _ »» *» » -2
(a) (b)
1 - SOURCE VOLTAGE
2 - FAULT CURRENT
3 — RELAY OUTPUT
-77-
perception.
180
51.5 Hz
nary impedances for which the prototype relay had been designed
bench CT, and was tested for two locations — on R-phase and
and for 60° and 120° angles between the source voltages. A
number of random shots was allowed for each system condition and
Y-phase voltage was reversed (thus VRN lagged -VYN by 60°) , and
(ii) when located on Y-phase and the Y-phase voltage was not
impedance.
+•8.7 Burdens
were 1.1 VA and 0.8 VA respectively when the d.c. supply trans
often obtained with one mho relay alongwith two blinder (ohm)
major part of the present work has been devoted to the quadri
lateral relay.
and. i = I sin(wt-0)
v„ - k V sin wt
V m ... (5.2)
and v± = ZrIm sin(u>t-0-*Q)j
J
Zrl
nr
INPUT SIGNALS
|Z r Ir|: RECTIFIED Zr Ir
>M
SAMPLING PULSES
Zr Im Sin 9
o-
SAMPLED AMPLITUDESOF | 2r Ir|
o • AMPLITUDE CONVERTED TO WIDTH
Sin 0
. kVm sine
TlxkV„, Sin 0
INPUT SIGNALS
SAMPLED AMPLITUDES OF . |Z r 1 r|
AMPLITUDE CONVERTED TO WIDTH
— SAMPLING PULSES
"I t -fr"
VVmCos (0 + y)
C 0
'-lf+Y*«|~
L D
p-«H
o! E
i L
0 G 0
the passage of the said spike through the gate would imply the
fulfilment of the operating conditions (5.if) and (5.7).
are stretched and given to another AND gate for checking the
—In, Zrlm f— i
Sin 0
ue
1 1
hl+H
C (OPERATING INPUT)
r r
D\
—T, kVmSin0
^1
^(blocking inputs)
A\ + ii>
Ht+V-I L
n^kvmcos(0+ip)
180
4- H (releasing input)
j (output)
\_
J
TO + ZERO-CROSSING OF Z r Ir
GATING
SPIKE *
OUTPUT °
OUTPUT
+ vz
(a) (b)
Vi Vr
in
Z.C.D. "»•
(a) (b)
FIG.5.9,MEMORY CIRCUIT
(a) ACTUAL CIRCUIT
(b) EOUIVALENT CIRCUIT
-106-
recomme -nations made with regard to the cable layout for the
WPC relay are applicable In this case equally well (Section if. 7).
'relay output1 was taken from the AND gate that feeds the
output reed-relay. The waveforms of the inputs and output for
each relay operation were recorded on a storage CRO. The
operating times so obtained conformed to the theoretical values
0=6
20-28mS
+ 90 +180
0 > 9
(0-e;
20 - 28rns
+ 90 +180
10 ms 0 < 0
20 - 28 m s
-180 -90 -(e-0) 0 +90 +180
FAULT INCIDENCE ANGLE , DEGREES -
28ms
1.0
/ / / / / I / // / / /
OPERATING ZONE
~r
0.8
-101-
(o)
(b)
4 5 7 10 20 30
RANGE ,Y 1
sistor Q2 gets its base current from +V2 through Rg and conducts
in saturation so that the potential at its collector is about
be very small so that the condenser may charge during the gat
ing period to a large fraction of the instantaneous value v
s
figure 5.8(b) , where the gating period has been exaggerated and
the small saturation voltages neglected for an easy conception.
given by
vs = (kvs+ v1){l-exp(-t/RC)}
rkv_+ V., "I
rkv + V
or t * RC In!.—%
1" J
To have a long output duration for a given value of v ,
factor rj. However, the conversion factors T)' and Tjq have
been kept identical to t). in the design so that the non-
adjustments of X and Z .
o o
-113-
(°)
3 4 5 20 30
RANGE , Y
<
cc
(b)
o
o
<
RANGE ,Y
is
(a)
— 485HZ
(b)
50 Hz
5I.5HZ
relay-test bench as done for testing the V/PC relay (Section if.8.6)
The quadrilateral distance relay prototype was set for a reach
fO
<Tb)
60° apart.
Next, the relay was fed with the voltage of phase Y^to
neutral and current in phase Y and the following abnormalities
were created repeatedly on the system:
(h) as in (f).
(j) as in (g) .
5.5.7 Burdens
employed.
kVmsin0^ZrInsin9
or if Zsin0^< Zrsin9/k ... (6.1)
given by
by Z | such that
angle (-n;/2+l|f) after the current zero and the operating output
-12if-
Zr Zr
NPUT SIGNALS
• ^^\^^--|ZrIr|--RECTIFIEDZr ir
«S^ IkVfl =RECTIFIED kVr
V
OUTPUT OF REACTANCE
COMPARATOR
SAMPLE HELD
OUTPUT OF
OHM COMPARATOR
STRETCHED PULST
FROM REAC. COMP.
OUTPUT OF
AND' GATE
INSTANT
STRETCH (REACTANCE)
COMPARATOR 180°
A
Izi-Irl
M r '•r F.W.R.
GATING
PULSE
INSTANT-
(OHM) (QUADRILATERAL)
COMPARATOR AND - — » TRIP
B
SAMPLE
&
HOLD
DELAY DELAY
rir
Zrl • . ZCD „ .
e
P-*
top and bottom rows are those used independently by the two
comparators working with reference to the negative-to-positve
relay.
uits used for the reactance and ohm characteristics also employ
the circuits of the ZCD and the two comparators, they are dis
driven into saturation for a very small (typically less than 1 mV)
differential, input. The output voltage is at its positive
back consisting of two zener diodes ZD-. and ZDp connected back-
to-back. Thus the oiitput voltage is a square wave that has +V
amplitude when the input V. is negative and -V when V. is
J-il & 111
blocking the negative spikes with the help of diode D,j positive
spikes are obtained at the output terminal V , on positive-to-
negative zero crossings of Vin< Another similar differentiator
preceded by an inverter (the circuit of transistor Q) gives
positive spikes at the terminal V « on the negative-to^positive
zero crossings. The output impedance of the IC operational ampli
|Zflr|« C
•|kVr| • C=3
R2 V0
a V.D3
R|5
^rTrl —
(b)
involved here. Thus, the operating time curves for the three
cases of 0=0, 0< 0 and 0>9 are as shown in figure 6.8. The
minimum and maximum times, when the transactor angle is equal
to the system impedance angle, are 20 ms and 30 ms respectively,
provided there is no delay on account of d.c. transients in the
fault current.
0 90 180
FAULT INCIDENCE ANGLE , DEGREES-
0 = 0
(0-0)
20TT1S
-180
The relay was tested with the same values of the imped
ance angles and the d.c. transient in signals as those in
•t
///// / / \ / Jf /] OPERATING
/
ZONE
/
'
1/
7" 7 / ' '
\26ttis
1
0.8
/
X 0.6
(a)
<
cc
8 0,4 /
'/,
<
/
0.2 '/
'//.
/
RANGE,Y
—. 1
HRESH OLD
61-ms
0.8
^i&
x
0.6
>-
o (b)
<
cc
§ 0.4
<
•
0.2 i
f 4f»
^^^^.61-ms
2 3 4 5 7 10 20 30 40 50
RANGE , Y «-
supply system. The relay settings used and the system condi
5.5.6^ except for the difference that the fault at the relay
terminals (item (c)) was created in the present case through a
very small (and not zero) resistance giving about 0.1V at the
relay terminals. The relay operated on the internal earth
faults (item (c) and (d)) only, and thus exhibited a complete
selectivity.
6.3. 7 Burdens
found to be as follows*.
included.
Z
5 Hz
Ca)
50 Hz
51.5 Hz
(b)
thus occur if
where K • KpsinX/K-,
'range1.
OVERCURRENT RELAYS
-11*9-
AUX.CT. TRANSACTOR
FILTER FILTER
PRE-REGULATOR LIMITER
VOLTAGE REGULATOR
FAULT DETECTOR
D.C.
SUPPLY, CONTROL CIRCUIT
V
CHARGING CIRCUIT
VARIABLE-LEVEL
LEVEL- DETECTOR
AMPLIFIER
OUTPUT DEVICE
TRIP
•v -V
D.C.SUPPLY CIRCUITS MEASURING CIRCUITS
TIME-MULTIPLIER
/ SETTING
RF. AC
rvr: i
(OUTPUT DEVICE) g -Y-D2 '15 •14 <I3 R|0
ZD5 U y
R 17
rfr r^I D|
*>~
Qi
>- 1I2
= Q7
c7 r4
a6>J
*IB «16
the reset and overshoot times much smaller than without it.
than the pickup setting, the voltage output from the fault
ing.
Their saturation currents are made much higher than the leakage
thus ensured.
-157-
is not much serious with this relay because of the time delay
essentially present in its operation. Suppression of these
CS of 5A and TMSs of 1.0 and 0.5, which are shown in figure 7.3.
In the figure are also shown, for comparison, the points
specified by the above standard. Discrepancies at these points
are noted to be well within the permissible limits.
28 30
(c) Overshoot
(a) (b)
(f) Burden
timing circuit for this relay is much simpler than that for the
and the circuitry in figure 7.7. The d.c. supply circuits arc
the timing condenser is charged here from the fixed d.c. voltage V,
are similar.
the same lines as on the IDMT relay (Section 7.1.6). The time-
CURRENT SIGNAL FRON1 MAIN C T
TRANSACTOR
[ c so;
CIRCUITS
BRIDGE RECTi'
FILTER
LIMITER
,y\
FAULT "OR
i /
CONTROL ClRCtllT
'
CHARGING CIRCUIT
1
FIXED -LEVEL
LEVEL- ±TECTOR
,
1
AMPLIFIER
'
OUTPU' DEVi.'
JVrip
MEASURING
-V
D.C. SUPPLY
3
3 CIRCUITS
Al IX
<
• CURRENT SETTING -V
/TIME-DELAY
SETTING
REED DELAY
(OUTPUT DEVICE)
r&
>
2 0-
o l0 **•>> « •—•-
o
m
us
UJ
5:
^ 05|-
<
cc
UJ
a
cr
(a) (b)
I - RELAY CURRENT
2- VOLTAGE ACROSS TIMING CONDENSER
(Z - MODULATION AT 100 Hz)
CURRENT SETTING
REED RELAY
P(OUTPUT DEVICE)
ZENER
(REFEREE
^ P DIG
*n
<c
RECTIFIER LIMITER LEVEL-DETECTOR AMPLIFIER
TRANSACTOR
current obtained from the zener diode that acts as the reference
or a level detector. A reed relay is excited by the transistor
collector current. A capacitance C (10 uE) is placed across the
reed relay coil to avoid contact-chattering on the relaying
currents just above the pickup value.
X
o
0 0
<
UJ
cc
cc
UJ
>
o
l- •0.1
z
UJ
in
<
-0.2' 1
180 120 - 60 0 60 120 180
LEVEL OF
DETECTION
o
< NPUT
UJ SIGNAL
a.
O
180
(a)
10
f
LEVEL OF
UJ
DETECTION
o
NPUT
z 3.3
SIGNAL
cc
UJ
CL
O I
180 -150 0 30 150 180 180
(to
(e) Burden
A NEW TECHNIQUE
FOR
INVERSE-TIME OVERCURRENT RELAYS
-178-
that the principle can yield Is 'I.t= constant1, with the level
of the level-detector made constant. Steeper curves can be
teristic.
8.1.1 Principle
and given by
t = V C/I
o c
V c
o
, E,^E<E. ..
Icj+M.(E-E.) J J+1 \ ... (8.2)
A^
E-B
(say) ,.E.<E,<Ej+1
t = I-N, , ir<uiJ+1
j - 0 to (n-1) ... (8.3)
1=0
o
8.1.2 Circuitry
/
/
/^-—-"""'
/' / ^ti+t2
/ y'
y
/ //
/ /£*
/
+
/ yS
Ly^
z
y
y^
LU
,y
iX
to / y
y
o E| E2\ E3 E4^N E5
\ s
\
\ \
\
\
\
\
\i2 \ t4
X
Jc = °> 0^E<;E1
= ±1 = E(l/R1)-E1/R1 , E^WEg
- ^+±2 • E(l/Rl - l/^)-^/^ - E2/R2),E^EN<E3*, etc.
LEVEL
DETECTOR
(v0)
i
-187-
E5 E6 E—
20 oo X SETTING
VALUE
•1-5
T.M.S.= I.O
EXPERIMENTAL CURVE
2 4 6 8 10 12 14 Iff 20 22 24 26 28 30
OPERATING CURRENT , MULTIPLES OF THE SETTING -
A WJJ APPROACH
TO
DISTANCE PROTECTION
•19V-
9.1 PRINCIPLE
the top part of figure 9.1. The fault area is shown alongwith
the trip area of the relay. The trip area (operating zone) is
bound by the four straight lines a, b, c and d. These
constituent straight-line characteristics are shown in the
figure separately alongwith their operating zones. Mathemat
ically, the latter are represented by
L >- 0
L <I1
L < pR ... (9.k)
/ / '
TRIP (L < L|)
trip(l >o)
JL.L / / / ///////// y
R
i-
TRIP
(L +L2>qR)'
trip(l <pr)
I
DIFEERENTIAT0R
di/dt
II u
ZCD ZCD ac QC
di/dl
G PC
SG
R(A)
G PC SG
L(A)
DELAY
L|(Wl L?(W)
AND-3
TRIP
obtained from AND-1 if L<L, and L<pR and that from /ID-2
if L>0 and (L+L2) > qR. Coincidence of their outputs is checked
in a third gate AND-3, which gives a trip-signal if the coinci
dence takes place. The trip signal is thus obtained only
when all the four conditions, viz. L<L*9 L<pR, L >0 and
(L+L2) ^qR? are satisfied simultaneously. This corresponds to
a relay operation only for the R-L combinations falling within
the quadrilateral trip area shown in figure 9.1.
given above.
is bettered.
circuit used for the purpose is similar to the one used in the
ZCD
QC QC
ZCD
\r/(di/d t) v/i
l=o d t/d t = o
SAMPLE
SAMPLE-AND-
RESET HOLD
DELAY CIRCUIT
j INPUT LT
.-INPUT
WINDOW WINDOW
GATE GATE^
COMPARATOR COMPARATOR
UT B
A
OUTPUT • OUTPUT
1_I
AND
1
TRIP
V , = V+
ol = 7omaxJ if Vin/Rl> vi/tl2 3i*e* if vin> avi
Vol = ^max* if Vin/Rl< Vl/R2 >1-e' ±f vm< avi
Vo2 " VomaxJ if vln/Yi3>V2/\ 5 i*e* if vin> bv2
7o2 s rmaxJ if Vin/R3 <v2Aik s i,G* if vin<bv;
Further, in the absence of the gating pulse*.
If vol = ^max5 Dl Gonducts, hence v = 0
T +
If vQl = Vomaxt Qj conducts in saturation, hence v - 0
If vin<
•w* avlJ. ^thus vin^
m hvo2 too) ?»tne*i vol,«V"omax5, vo2„ =V~oomax3
D-, conducts, hence v = 0.
x o
CONCLUSIONS,
FIELD TESTING
AND
SUGGESTIONS FOR FURTHER WORK
-207-
10.1 CONCLUSIONS
(Q) (b)
V.
(C)
The third, and the final, phase of the field testing will be
with the static relays alone tripping the breaker.
35. INGOLE, V.T.#, SANT, M.T. and PAITHANKAR, Y.G. «New technique for
quadrilateral distance relay', Proceedings IEE, Vol.121,
No.6, June 197if, pp.if6if-if66.
1*2. SONNEMAN, W.K. , "A. new time overcurrent relay with adjust
able characteristic', Transactions AIEE, Vol.72, Part 3,
1953, pp.360-365.
APPENDIX A
Traction transformer
Traction load
0.1(25)2/12.5 0
i.e. 5.0 Q
5.625/85° ohms,
and that referred to the secondary sides is
For the complete range of 500 to 1 500 MVA of the short circuit
level, the range of the source impedance at 25 kV bus is accord
ingly 5.3 to 5.9 £2 referred to the primary side and 2.35 to
2.60 Q referred to the secondary side.
-227-
110 V / 5 A
i.e.22.0 Q
65 x 0.229 £2
i.e. 11*.88 g
Table A-l
Fault ;R
Fault impedance Icurrent Rarc for
distance Representation i j jlinear
km ! variation
Q A Q I Q
0 Fault at relaying
point 0 if 1*60 0.10 0.10
The earth fault area on the R-X diagram may be drawn taking
a ground resistance of 5 £2 and the arc resistances indicated in
the last column of the table. Accordingly, the fault resistance
to be plotted for an earth fault taking place at zero distance
(relaying point) is
(5.0 + 0.1) x 0.1*1* Q
i.e. 2.25 £2
Z = V /I
r r
Z E
a on m
I - I
zn »• • (A-l*)
m n
- - Z5. _
z = z —— - z
nm A - i m
1+ /6
= Z _ z
^ lo -Z,6 **
v 2 "*Tn ' " «* ~2~ col; 2 "* (•"•-?)
APPENDIX B
tance from the substation where the relay is located, the next
substation should not be nearer than 30 km (talcing the worst
conditions of normal feed and double-track operation with OHE
impedance of 0.32 Q/km) and the next substation in operation
APPENDIX C
Zm S Zm Ai E %+ J"Lm.
zn • zn Z®n = Rn+ JwLn, and so on.
If the instantaneous values are denoted by the lower case
letters and \ be the angle after zero of the voltage E (taken
as the reference) at which the fault (WPC) occurs, then the
source-voltage values at a time t after the fault inception can
be written as follows:
en s *W sin(wt + M .. (C-l)
em =*\max sin(u)t+\+6) (
The relaying current Ir on the fault is given by
dlr
Lmn dt + Rnm \ a eEren = emn ••• ^c~2)
Since the substations are connected to the same grid, the source
voltages at them are fairly equal. Thus, for simplicity the
voltage magnitudes |eJ and |sj may be taken equal. Solution
of equation (C-2) on the basis of this assumption yields,
-236-
E E c
!. _- _mnmax_„eirM++>4.^
— cos(wt+\+2i - 0Q n) +, zmnmax /? , 82 - 0^ n
cosU+
1 nnn mn
exP( -Vt) mn
... (0-3)
dir
vr s en + Hn dT + Rfn xr
Thence
LuLLl
vv - k vr •
Z /»
+k Ennri
mnmax cosU+ 4
2 - ©nn)
mn s*1
Z^ ( f?
L^n - T*
L^ ) exp( - JB
Lim t)
... (c-5)
dir
311(1 vi = Lr dt + Vr
-237-
condition of feeding.
AUTHOR'S
PAPERS AND PATENT
FROM
THE REPORTED WORK
-21*0-
P/iPERS
1*. 'D.C.supply for static relays from CTs and PTs', Journal IE(l) ,
publication awaited*, Presented at the Paper Meeting of IE (I) ,
Bangalore, April 1976.
'ATENT
fast operation have only been partially successful. All the appro
aches suggested hitherto for distance protection, measure impedance,
required.
utilize the P.T. and CT. outputs inefficiently and need d.c.
quantities and from all the three phases combined are given.
are presented.
ing.
-21*8-
in the relay.