Professional Documents
Culture Documents
A R T I C LE I N FO A B S T R A C T
Keywords: In this paper, an improved demagnetization control, based on Explicit Model Predictive Control (E-MPC) is
Doubly Fed Induction Generators (DFIG) proposed to improve Low Voltage Ride Through (LVRT) capability of Doubly Fed Induction Generators (DFIGs).
Demagnetization control By injecting an additional rotor current component, the demagnetization control can efficiently eliminate the
Explicit Model Predictive Control (E-MPC) free and negative flux to avoid saturation of the rotor converter. The conventional demagnetization control is
Low Voltage Ride Through (LVRT)
based on fixed scaling factors, whose control performance can’t be guaranteed for different fault conditions. The
proposed E-MPC approach can fully explore the potential of rotor side converter. Besides, the control parameters
of E-MPC are derived offline and very efficient for online control. In addition, the proposed E-MPC structure is
simple and easy to be implemented. The mechanism of proposed E-MPC is presented in detail and verified in
Matlab/Simulink. The results show that the proposed control scheme has a good performance and can improve
the LVRT capability of DFIGs under various fault conditions, especially unbalanced faults.
1. Introduction removed to support reactive power to the grid [10]. Dynamic voltage
restorer is installed between the stator and the grid to compensate the
WITH the increasing penetration of wind power, the integration of drop in the grid voltage by providing reactive power during the fault
wind farms to the grid and their dynamic behavior under grid faults [11,12]. However, the application of hardware in these methods in-
have become an important issue in recent years [1,2]. According to the creases the system cost and control complexity [13].
grid codes, to keep the system stability, the wind turbine should always Many studies have focused on the improvement of converter control
be connected to the grid during and after faults, especially Low Voltage methods to reduce the usage or shorten the activation time of hardware
Ride Through (LVRT). protection devices. Part of the methods improve the dynamic perfor-
The Doubly Fed Induction Generator (DFIG) is widely used in wind mance of DFIG by changing the control parameters. Obviously, the
power generation systems due to its high reliability and low cost [3,4]. rational design of the control parameters is crucial for the control of the
However, it is excessive sensitivity to grid disturbances since the stator DFIG [14]. Appropriate tuning the proportional integral (PI) controllers
is directly connected to the grid. The sudden voltage fault may cause is also shown to affect the DFIG LVRT [15].
problems of DFIG such as rotor side over-current and over-voltage at DC In addition, it is also a mainstream LVRT solution to change the
bus [5]. The situation gets even worse for the unbalanced cases, due to control structure of the rotor side controller. Ref. [16] proposed the
the rotor voltage induced by free and negative sequence flux, which will demagnetization control to eliminate the induced voltage by injecting a
cause activation of protection devices and even disconnection of DFIG rotor current opposite to the free and negative flux. In [17], the mea-
from the grid [6]. It is of highly importance to study the improvement surement of negative sequence and free component flux was improved
of LVRT capability of DFIG [7]. to avoid the delay caused by low pass filter. Ref. [18] proposed a scaled
To protect the DFIG against voltage dips, the primary solution is current tracking control for rotor-side converter to enhance its LVRT
using hardware protection devices, such as crowbar and chopper [8]. capacity without flux observation. In [19], virtual resistance is in-
However, during the activation of crowbar, the DFIG absorbs a large troduced to enlarge the control range, but still can’t adjust the de-
amount of reactive power from the power grid, which can’t help and magnetizing current flexibly. An improved demagnetization control,
even deteriorate the voltage recovery [9]. Crowbar should be timely immune to system parameter variation, is proposed to shorten the
This work was supported by the National Key Research and Development Program of China (2018YFB0904004).
⁎
Corresponding author.
E-mail addresses: jialuo@mail.sdu.edu.cn (J. Luo), hzhao@sdu.edu.cn (H. Zhao), gaosn@mail.sdu.edu.cn (S. Gao), 201714153@mail.sdu.edu.cn (M. Han).
https://doi.org/10.1016/j.ijepes.2019.105783
Received 16 September 2019; Received in revised form 10 December 2019; Accepted 12 December 2019
0142-0615/ © 2020 Elsevier Ltd. All rights reserved.
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783
dynamic process [20], but only applied to balanced faults. In [21], the ωs ψsq ωr ψrq
isd Rs − + Lls Llr + − Rr ird
rotor flux linkage is controlled to track a reduced fraction of the
changing stator flux linkage. However, the reactive power required by + + + +
grid code is not involved. The cooperation of the crowbar and the de- usd dψsd
dt
Lm dψrd
dt
urd
magnetization are studied in the article [22]. However, the control − − − −
parameters of the aforementioned control strategies are fixed, which
can’t be adjusted flexibly for different grid conditions. Thus, their
control performance can’t be guaranteed. ωs ψsd ωr ψrd
isq Rs + − Lls Llr − + Rr irq
To overcome this problem, a demagnetization control based on
Explicit Model Predictive Control (E-MPC) is proposed. Model + + + +
Predictive Control (MPC) can predict future output over a specific usq dψsq
Lm dψrq urq
dt dt
prediction horizon based on the system model [23,24]. The main ad-
− − − −
vantage of using MPC is computing the optimal control action while
considering system constraints [25]. However, during LVRT, the fault
Fig. 2. Model of DFIG in dq frame.
time is very short and MPC is difficult to handle the fast online calcu-
lation [26]. In this study, E-MPC is applied to calculate the optimization
problem offline and suitable for online calculation [27]. where usd , usq , i sd , i sq , ψsd , ψsq are stator voltage, current and flux
The main contributions of this paper are twofold. Firstly, the de- linkage vector in dq reference frame, respectively.
magnetizing current can be optimally derived for various fault condi- urd , urq , i rd , i rq , ψrd , ψrq represent rotor voltage, current and flux linkage
tions to fully explore the capacity of the rotor side converter. Secondly, vector in dq reference frame, respectively. Rs and Ls are stator re-
a simple E-MPC control structure without additional measurement re- sistance and self inductance. Rr and Lr are rotor resistance and self
quirements is designed and described in detail. inductance, respectively. L m indicates the mutual inductance, ωs and ωr
This paper is organized as follows. Section 2 describes the dynamic are grid synchronous angular frequency and the electrical angular fre-
model of DFIG. Section 3 analyzes the dynamical performance of DFIG quency of rotor respectively.
under unbalanced conditions. In Section 4, the working principle of By substituting (2) into (1), the rotor voltages urd and urq can be
conventional demagnetization control is elaborated. The proposed de- calculated by,
magnetization control based on E-MPC is designed and presented in dird Lm dψ L
urd = Rr i rd − ωr σLr i rq + σLr + sd
− ωr Lm ψsq
detail in Section 5. To verify the proposed strategy, the simulation are dt Ls dt
s
erd
carried out in Section 6. The conclusion is drawn in Section 7. dirq dψsq ,
L L
urq = Rr i rq + ωr σLr i rd + σLr dt
+ ωr Lm ψsd + Lm dt
s s
erq (3)
2. Dynamical model of DFIG
L2
Lr − m
Ls
The basic structure of DFIG with crowbar and chopper is shown in where σ ≜ Lr
is the leakage inductance coefficient. The induced
Fig. 1. rotor voltage caused by the stator flux linkage in dq reference frame are
The mathematical modelling of DFIG under synchronous rotating denoted by erd and erq , respectively.
reference frame (dq) can be expressed as follows. The equivalent cir-
cuits are shown in Fig. 2. 3. Dynamical performance of DFIG under unbalanced conditions
dψsd
usd = Rs i sd + dt
− ωs ψsq Due to the direct connection to the grid, it can be considered that
→s
dψsq the stator voltage V s is determined by the grid [28]. By ignoring the
usq = Rs i sq + dt
+ ωs ψsd →s
, stator resistance Rs , V s can be written as the sum of the positive se-
dψrd
urd = Rr i rd + dt
− ωr ψrq quence and the negative sequence in stator reference frame without
dψrq considering the zero sequence component,
urq = Rr i rq + dt
+ ωr ψrd (1)
→s
V s = V1 e jωs t + V2 e−jωs t , (4)
where the flux linkages for stator and rotor are derived by,
where V1 and V2 denote the amplitudes of the positive and negative
ψsd = Ls i sd + L m i rd sequence of the stator voltage. To be noticed, the superscript “s” in
ψsq = Ls i sq + L m i rq variables represents the stator reference frame.
, ⎯→
⎯ s ⎯→
⎯ s
ψrd = L m i sd + Lr i rd The corresponding generated flux linkages ψ s1 and ψ s2 can be
ψrq = L m i sq + Lr i rq (2) written as,
⎯→
⎯ s V ⎯→
⎯ s V2 −jωs t
ψ s1 = 1 e jωs t , ψ s2 = e .
jωs −jωs (5)
2
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783
R s + Rr σLr irrf
+
s1
| s1 | | s2 | + errf r
vrf
−
s
s s2 −
sf
axis
(10)
The control structure of proposed E-MPC based demagnetization
control is shown in the Fig. 8. To be noticed, the following variables are
Considering that (ωr + ωs) is approximately equal to 2, the all in the rotor reference frame. Therefore the superscript “r” is ignored
equivalent circuit of negative sequence can be obtained and shown in
Fig. 4.
⎯→
⎯ r
According to (3), the rotor voltage →
r
v induced by ψ is rf sf
s1
⎡ 2 ⎤ →r →r
→ r L ⎯→
⎯ s L d i rf
v rf = − m jωr ψ f e−jωr t + ⎢Rr + ⎛ m ⎞ Rs ωr ⎥ i rf + σLr
⎜ ⎟
Ls →
⎢ ⎝ Ls ⎠ ⎥ dt
erf ⎣ ⎦ (11) s
s s2
Considering that ωr is approximately equal to 1, the equivalent
circuit of free component can be obtained and shown in Fig. 5. sf
axis
→r →r def
According to (10) and (11), the induced voltage v r2 and v rf can be
+ err2 r
vr2
−
−
axis
Fig. 4. Rotor equivalent circuit of negative sequence. Fig. 6. Flux linkage with demagnetizing current.
3
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783
By substituting (2) into (1), the state space model can be derived as,
dψsd Rs Lm Rs
⎧ dt
= usd − ψ
Ls sd
+ Ls rd
i + ωs ψsq
.
⎨ dψsq = usq −
Rs
ψ +
Lm Rs
i − ωs ψsd
⎩ dt Ls sq Ls rq (16)
∗ ∗
Fig. 7. Control diagram of conventional demagnetization control. The control input references i rd and i rq are composed by,
∗ ∗ ∗ ∗
⎧i rd = i r1d + i r2d + i rfd
∗ .
⎨ i∗ = ∗
i r1q + ∗
i r2q + i rfq (17)
⎩ rq
where are used to suppress free flux component and
∗
i rfd ∗
, i rfq are ∗
i r2d ∗
, i r2q
used to suppress negative flux component.
According to the symmetrical component method, the negative and
free components of (16) can be expressed separately,
dψs2d Rs Lm Rs
⎧ dt
= us2d− ψ
Ls s2d
+ i
Ls r2d
+ ωs ψs2q
,
⎨ dψs2q = us2q−
Rs
ψ +
Lm Rs
i − ωs ψs2d
⎩ dt Ls s2q Ls r2q (18)
dψsfd Rs Lm Rs
⎧ dt
=− ψ
Ls sfd
+ i
Ls rfd
+ ωs ψsfq
.
⎨ dψsfq = − Rs
ψ +
Lm Rs
i − ωs ψsfd
⎩ dt Ls sfq Ls rfq (19)
It should be noted that the stator voltage usd , usq does not contain a free
component.
Fig. 8. Control diagram of E-MPC based demagnetization control.
By introducing incremental variables (labelled by Δ ), (18) and (19)
can be transformed into,
for simplicity.
dΔψs2d R Lm Rs
⎧ dt
= − L s Δψs2d + Ls
Δi r2d + ωs Δψs2q
s
5.1. Free and negative flux measurement ,
⎨ dΔψs2q =
R
− L s Δψs2q +
Lm Rs
Δi r2q − ωs Δψs2d
⎩ dt s Ls (20)
It is key to accurately measure free flux (ψsfd , ψsfq ) and negative flux
dΔψsfd R Lm Rs
(ψs2d , ψs2q ) in proposed method. The low pass filter can cause amplitude ⎧ dt
= − L s Δψsfd + Ls
Δi rfd + ωs Δψsfq
s
and phase errors during LVRT. In this study, the low pass filter is only dΔψsfq
.
⎨ R
= − L s Δψsfq +
Lm Rs
Δi rfq − ωs Δψsfd
used for ψsf . ⎩ dt s Ls (21)
The measurement method adopted in this paper is shown in Fig. 9.
The total stator flux is obtained by The state space form of the Linear Time-Invariant (LTI) system can
be finally written as,
ψs = ∫ ⎛vs − Rs is⎞ dt.
⎜ ⎟ x ̇ = Ax + Bu
⎝ ⎠ (14) y = I4 × 4 x
The ψsf can be extracted through the low-pass filter. A linear combi- x ≜ [Δψs2d , Δψs2q , Δψsfd , Δψsfq]T
nation of these two quantities ψsf + 2ψs2 can be directly estimated by u ≜ [Δi r2d , Δi r2q , Δi rfd , Δi rfq]T . (22)
stator current i s and stator voltage vs .
By applying the sampling time Ts , according to the discretization
1 dψs 1 d ⎛ ⎞ method described in [29]. The LTI system (22) can be transformed into
ψs − = ψs1 + ψs2 + ψsf − ⎜ψs1 + ψs2 + ψsf ⎟
jωs dt jωs dt a discrete-time form,
⎝ ⎠
.
= ψs1 + ψs2 + ψsf −
1 ⎛
⎜jψs1 − jψs2⎞⎟ ⎧ x (k + 1) = Ad x (k ) + Bd u (k ) ,
jωs ⎨ y (k ) = Cd x (k )
⎝ ⎠ ⎩ (23)
= 2ψs2 + ψsf (15) where Ad , Bd , Cd are the discrete forms of A, B, I4 × 4 in (22), respec-
In order to get their respective values, ψsf is measured by a low pass tively.
∗ ∗
The rotor current references i rd and i rq are limited by the capacity of
the rotor side converter,
∗2 ∗2
Fig. 9. Measurement structure of flux. i rd + i rq ⩽ ilim , (24)
4
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783
Δψs2d (k ) = S1 y (k ), S1 = [1, 0, 0, 0]
Δψs2q (k ) = S2 y (k ), S2 = [0, 1, 0, 0]
,
Δψsfd (k ) = S3 y (k ), S3 = [0, 0, 1, 0]
Δψsfq (k ) = S4 y (k ), S4 = [0, 0, 0, 1] (30)
In this part, the control rule of E-MPC is derived. The partitions that
Fig. 10. Constraints of rotor current references. are calculated offline are highly correlated with the prediction horizon
n p and sampling time Ts . Too many partitions will increase the time for
∗ ∗ online search and slow down the calculation. Under the premise of
⎧i rd = i r1d + i r2d + i rfd + Δi r2d + Δi rfd . guaranteeing the effect, n p is chosen as 3 and Ts is set to 0.0005 s. The
∗ ∗
⎨ i = i r1q + i r2q + i rfq + Δi r2q + Δi rfq (25)
⎩ rq state partition map and the corresponding optimal control algorithm
The nonlinear constraint (24) can be considered as a circle with i rd are obtained by offline calculation. In this paper, 29 regions are di-
and i rq as the horizontal and vertical axis. The radius of the circle is ilim . vided. The partition map of E-MPC is shown in Fig. 11. Each different
In order to be implemented in E-MPC, Eq. (24) can be approximately color region represents an optimized control algorithm. In online cal-
represented by a series of linear constraints. In this study, 8 linear culation, the corresponding optimal control algorithm can be found by
constraints surrounding the circle is used, as shown in Fig. 10. finding the partition in which the current state variable of the system is
located. Thereby E-MPC greatly reduce the solution time and meet the
∗ ∗
⎧ − 2 ilim ⩽ i rd + i rq ⩽ 2 ilim calculation requirements of the transient period.
⎪
⎪ − ∗ ∗
2 ilim ⩽ i rd − i rq ⩽ 2 ilim
. 6. Cases study
⎨ ∗
− ilim ⩽ i rd ⩽ ilim
⎪ ∗
⎪ − ilim ⩽ i rq ⩽ ilim (26)
⎩ A 1.5-MW DFIG-based system is built in MATLAB/ Simulink to
verify the proposed control strategy. The DFIG parameters are shown in
5.4. Design of cost function Table 1. To show the control performance, simulation is carried out
under both balanced and unbalanced faults with three controllers:
The goal of E-MPC is to minimize ψs2d , ψs2q , ψsfd and ψsfq . The ob- without demagnetization (labelled by “Control 1”), conventional de-
jective function can be written as follows, magnetization control (labelled by “Control 2”) and E-MPC.
Lm ⎡ ⎛
→ Ls ⎢
⎜ωr + ωs⎟⎞ V2 e−j (ωr + ωs) t ⎤
er2 ⎥
= ⎣⎝ ⎠ ⎦,
→
e rf Lm ⎛ ⎯→
⎯ s −jωr t ⎞
⎜ − jωr ψ f e ⎟
Ls
⎝ ⎠ (28)
where ωr = 1 − s, ωs = 1, and s ∈ [−0.3, 0.3]. Accordingly, Eq. (28) can
be approximated as,
→ ⎯→
⎯ ⎯→
⎯
er2 (ωr + ωs) ψs2 2 ψs2
→ ≈ ⎯→
⎯ ≈ ⎯ .
⎯→
esr ωr ψsf ψsf (29)
According to (29), it is obvious that the induced voltage caused by
⎯→
⎯ ⎯→
⎯
ψs2 is twice than that caused by ψsf . For the perspective of the induced
voltage minimization, the optimal weighting factor ratio of Q T and QF
can be set as 4:1.
Fig. 11. Reduced partition for E-MPC for ψs2d and ψs2q (other variables are set to
The prediction horizon is n p and k indicates the prediction index. By
defining, 0).
5
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783
Table 1
Parameters of 1.5-MW DFIG.
Rated power 1.5 MW
Stator voltage 575 V
Mutual inductance 2.9 p.u.
Stator leakage inductance 0.18 p.u.
Rotor leakage inductance 0.16 p.u.
Stator resistance 0.023 p.u.
Rotor resistance 0.016 p.u.
Fig. 13. Single phase fault to 0.8 p.u. (a) Stator active power. (b) Stator reactive
power. (c) Electromagnetic torque. (d) Amplitude of rotor current. (e) DC bus
voltage.
6
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783
Fig. 14. Single phase fault to 0.6 p.u.. (a) Amplitude of rotor current. (b) DC Fig. 15. Single phase fault to 0.4 p.u. (a) Amplitude of rotor current. (b) DC bus
bus voltage. voltage.
always be offset by the demagnetizing current, and it can not send more
reactive power during the fault. The oscillation of the electromagnetic
torque under the proposed control method is much smaller as shown in
Fig. 13(c). The magnitude of the oscillation is reduced by about 40
percent. Among all these controllers, the damping speed of the rotor
current Ir is the fastest as shown in Fig. 13(d). In comparison, it has
better demagnetization effect than Control 2. Similarly, E-MPC can best
suppress the oscillation of DC bus voltage compared with Control 1 and
Control 2 in Fig. 13(e). The Ir can always be limited within 1 p.u. while
VDC does not exceed 1170 V. In the following, due to space limitations,
only the rotor current and DC bus voltage values will be displayed
under different fault levels.
A single phase voltage drop at the grid side is set to 0.6 p.u. at
t = 1 s , and the simulation results are shown in Fig. 14. The Ir of
Control 1 oscillates at 1.5 p.u.. Control 2 has a little demagnetization
effect, but still can not meet the current value requirements. Compared
with the other two controls, the oscillations of rotor current Ir based on
E-MPC is damped rapidly and significantly. After t = 1.1 s, Ir can be
limited within 1 p.u.. The proposed control can reduce the time of ac-
tivation of the crowbar, thereby providing reactive power and sup-
porting grid voltage recovery. As shown in Fig. 14(b), the same phe-
nomenon which E-MPC has the best control effect can also be observed. Fig. 16. Phase to phase fault to 0.8 p.u.. (a) Amplitude of rotor current. (b) DC
Among three controllers, the oscillation amplitude of VDC using E-MPC bus voltage.
is the minimum.
A single phase voltage drop at the grid side is set to 0.4 p.u. at shown in Fig. 16(b). E-MPC enables the DFIG to have better dynamics
t = 1 s , and the simulation results are shown in Fig. 15. Ir of Control 1 behaviours during unbalanced faults.
is the largest, and Ir of E-MPC is slightly lower than Control 2 as shown A phase to phase voltage drop at the grid side is set to 0.6 p.u. at
in Fig. 15(a). Compared with other controllers, E-MPC can better sup- t = 1 s , and the simulation results are shown in Fig. 17. Compared with
press VDC oscillation as shown in Fig. 15(b). In addition to the moment Control 1 and Control 2, E-MPC has the best effect which can limit Ir to
the fault begins, VDC can be limited within 1200 V. However, the less than 1 p.u. after t = 1.1 s as shown in Fig. 17(a). Capability of the
magnitude of the current of all controllers have exceeded the limit of rotor-side converter can be fully explored to achieve LVRT. And the
the rotor side converter. It is indicated that the limit of the capacity of oscillation of VDC can be significantly suppressed as shown in Fig. 17(b).
the rotor side converter has been reached at this time, and crowbar Under this circumstance, crowbar will not be activated so that the rotor
need be put into use to achieve LVRT. side converter will not lose control and the DFIG is able to provide
reactive power during the fault.
A phase to phase voltage drop at the grid side is set to 0.4 p.u. at
6.3. Phase to phase faults
t = 1 s , and the simulation results are shown in Fig. 18. E-MPC can
better suppress Ir compared to Control 1 and Control 2 as shown in
A phase to phase voltage drop at the grid side is set to 0.8 p.u. at
Fig.18(a). However, Ir of the three controllers all exceed the limit
t = 1 s , and the simulation results are shown in Fig. 16. Comparably, the
value, which means that at such a fault depth, it is not possible to rely
damping speed of Ir based on E-MPC is the fastest, as shown in
solely on the rotor converter to complete the LVRT. Hardware
Fig. 16(a). The oscillation of VDC can be significantly suppressed as
7
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783
and reduce the activation time of the crowbar and the chopper.
7. Conclusion
References
[1] Degeilh Y, Singh C. A quantitative approach to wind farm diversification and re-
liability. Int J Electr Power Energy Syst 2011;33(2):303–14.
[2] Dash P, Patnaik R, Mishra S. Adaptive fractional integral terminal sliding mode
power control of UPFC in DFIG wind farm penetrated multimachine power system.
Prot Control Mod Power Syst 2018;3(1).
[3] Tohidi S, Behnam MI. A comprehensive review of low voltage ride through of
doubly fed induction wind generators. Renew Sustain Energy Rev 2016;57:412–9.
[4] Kenan M, Arsoy A. Transient modeling and analysis of a DFIG based wind farm with
supercapacitor energy storage. Int J Electr Power Energy Syst 2016;78:414–21.
[5] Noureldeen O, Hamdan I. A novel controllable crowbar based on fault type pro-
tection technique for DFIG wind energy conversion system using adaptive neuro-
fuzzy inference system. Prot Control Mod Power Syst 2018;3(1).
[6] Amer Saeed M, Mehroz Khan H, Ashraf A, Aftab Qureshi S. Analyzing effectiveness
of LVRT techniques for DFIG wind turbine system and implementation of hybrid
combination with control schemes. Renew Sustain Energy Rev
2018;81(7):2487–501.
[7] Shahbabaei K, Radmehr M, Firouzi M. LVRT capability enhancement of DFIG-based
wind farms by using capacitive DC reactor-type fault current limiter. Int J Electr
Power Energy Syst 2018;102(3):287–95.
[8] Vidal J, Abad G, Arza J, Aurtenechea S. Single-phase DC crowbar topologies for low
voltage ride through fulfillment of high-power doubly fed induction generator-
based wind turbines. IEEE Trans Energy Convers 2013;28(3):768–81.
[9] Lu H, Yuan Z, Wei L, Kerkman RJ, Lukaszewski RA, Ahmed AS. LVRT performance
limit of DFIG with traditional AC crowbar and DC-link brake approach. In: IEEE Int
Symp Ind Electron; 2012. p. 692–9.
Fig. 18. Phase to phase fault to 0.4 p.u.. (a) Amplitude of rotor current. (b) DC [10] Yang S, Zhou T, Sun D, Xie Z, Zhang X. A SCR crowbar commutated with power
converter for DFIG-based wind turbines. Int J Electr Power Energy Syst
bus voltage. 2016;81:87–103.
[11] Wang Y, Wu Q, Gong W, Gryning MPS. Robust current control for DFIG-based wind
turbine subject to grid voltage distortions. IEEE Trans Sustain Energy
protection such as crowbar must be activated. The similar phenomenon 2017;8(2):816–25.
can also be observed in Fig. 18(b). E-MPC shows the best performance. [12] Hosani K, Nguyen T, Sayari N. An improved control strategy of 3P4W DVR systems
The oscillation of VDC is damped rapidly. under unbalanced and distorted voltage conditions. Int J Electr Power Energy Syst
2018;98(12):233–42.
[13] Ayyarao T. Modified vector controlled DFIG wind energy system based on barrier
function adaptive sliding mode control. Prot Control Mod Power Syst 2019;4(1).
6.4. Discussion
[14] Vieira J, Nunes M, Bezerra U, Do Nascimento A. Designing optimal controllers for
doubly fed induction generators using a genetic algorithm. IET Gener Transm
As shown above, under symmetrical faults, the proposed control Distrib 2009;3(5):472–84.
scheme can significantly suppress the oscillation of the electromagnetic [15] Justo J, Mwasilu F, Jung J. Enhanced crowbarless FRT strategy for DFIG based wind
turbines under three-phase voltage dip. Electr Power Syst Res 2017;142:215–26.
torque DC bus voltage and suppress the amplitude of the rotor current. [16] Xiang D, Ran L, Tavner PJ, Yang S. Control of a doubly fed induction generator in a
Under asymmetrical faults, simulation experiments were performed to wind turbine during grid fault ride-through. IEEE Trans Energy Convers
verify the reliability of E-MPC at different depths. Obviously, under the 2006;21(3):652–62.
[17] Lopez J, Gubia E, Olea E, Ruiz J, Marroyo L. Ride through of wind turbines with
three fault depths, the E-MPC can effectively reduce the amplitude of doubly fed induction generator under symmetrical voltage dips. IEEE Trans Ind
the rotor current and suppress the oscillation of the DC bus voltage. Electron 2009;56(10):4246–54.
However, when the fault level reaches 0.4, although the E-MPC can [18] Huang Q, Zou X, Zhu D, Kang Y. Scaled current tracking control for doubly fed
induction generator to ride-through serious grid faults. IEEE Trans Power Electron
play a demagnetizing effect, the rotor current and DC bus voltage still 2016;31(3):2150–65.
exceed 1p.u. and 1200 V. Therefore, the proposed E-MPC can improve [19] Hu S, Lin X, Kang Y, Zou X. An improved low-voltage ride-through control strategy
the demagnetization effect within the limit of the converter capacity of doubly fed induction generator during grid faults. IEEE Trans Power Electron
8
J. Luo, et al. Electrical Power and Energy Systems 119 (2020) 105783