IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO.

9, SEPTEMBER 2015 4831

Modularized Control Strategy and Performance


Analysis of DFIG System Under Unbalanced
and Harmonic Grid Voltage
Yipeng Song, Student Member, IEEE, and Heng Nian, Member, IEEE

Abstract—The paper presents a modularized control strategy control targets were selected to improve the DFIG operation per-
of doubly fed induction generator (DFIG) system, including the formance under the nonideal grid conditions, for instance, bal-
grid-side converter (GSC) and rotor-side converter (RSC), under anced stator output current, smooth stator output active/reactive
unbalanced and harmonic grid voltage. The sequence decompo-
sition process and complicated control reference calculation can power, smooth electromagnetic torque, etc. In [5], [8], [9], and
be avoided in the proposed control strategy. From the perspec- [12] the coordinated control of both GSC and RSC under the
tive of power grid friendly operation, the control targets of DFIG nonideal grid voltage conditions has been proposed. Generally,
system in this paper are chosen as: 1) smooth active and reactive in the coordinated control, RSC was controlled to obtain the
power injected into the power grid; 2) balanced and sinusoidal smooth DFIG electromagnetic torque and GSC was controlled
current injected into the power grid. The RSC and GSC can work
as two independent modules and the communication between RSC to ensure the overall smooth active power injected by both the
and GSC can be removed. Furthermore, the third harmonic cur- RSC and GSC into the power grid [5], [8], [12]. While Yao
rent component, dc-link voltage fluctuation, and electromagnetic et al. [9] employed the series GSC (SGSC) to the conventional
torque pulsation under the different control targets are theoreti- DFIG system topology, the nonideal grid voltage condition can
cally analyzed. Finally, the availability of the proposed modularized be well compensated by the SGSC and the DFIG can operate
control strategy of DFIG system under unbalanced and distorted
grid voltage is verified by experiment results. under normal grid voltage condition all the time.
However, the previous works also contain certain drawbacks
Index Terms—Balanced and sinusoidal current, doubly fed in- that would be unbeneficial for the practical applications:
duction generator (DFIG) system, modularized control, smooth
active and reactive power, unbalanced and harmonic grid voltage.
1) In order to achieve the specific control targets under the
nonideal grid condition, the fundamental, negative, and
harmonic components of grid voltage have to be extracted
I. INTRODUCTION [5]–[13]. The extraction procedure would employ many
IND power generation based on the doubly fed induc- notch filters and low-pass filters; as a result, the phase
W tion generator (DFIG) has gained increasing popularity
due to its advantages of smaller converters rating around 30%
delay and control error would be inevitable.
2) In order to implement the different control targets by
of the generator rating, variable speed, and four-quadrant ac- employing VOC [5]–[11] or DPC [12]–[13] strategy, the
tive and reactive power operation capabilities. Several control control reference calculation of rotor current in VOC or
strategies have been investigated to improve the power genera- active/reactive power in DPC is always complicated and
tion performance of DFIG under the ideal grid voltage, i.e., the time consuming. Furthermore, DFIG parameters devia-
vector oriented control (VOC) [1], direct power control (DPC) tion, as well as the fundamental, negative, and harmonic
[2], etc. However, the grid voltage may always contain negative component change of grid voltage would also deteriorate
and harmonic component in practical situation [3], [4], and the the reference calculation accuracy and control target im-
DFIG system operation performance would be jeopardized if plementation.
the unbalanced and distorted components in the grid voltage are 3) In order to achieve the smooth active power output of
not taken into consideration. DFIG system to the grid, the conventional control strat-
Up to now, several effective control strategies of the rotor-side egy, similar as [5], would allow the existence of active
converter (RSC) and the grid-side converter (GSC) in DFIG sys- power pulsation in the RSC, while the GSC is controlled
tem under grid voltage unbalance, or harmonically distortion, or to generate the opposite active power pulsation of same
unbalanced and harmonic distortion condition, have been inves- quantity as RSC, so as to maintain the overall smooth ac-
tigated based on VOC [5]–[11] and DPC [12]–[16]. The several tive power output of DFIG system. However, in order to
realize that the GSC needs to communicate all the time
Manuscript received April 24, 2014; revised August 21, 2014; accepted Octo- with the RSC to acquire the accurate information of active
ber 28, 2014. Date of publication October 31, 2014; date of current version April power pulsation in the RSC, this would inevitably increase
15, 2015. Recommended for publication by Associate Editor M. Malinowski.
The authors are with the College of Electrical Engineering, Zhejiang Uni- the DFIG system complexity and reduce the operation re-
versity, Hangzhou 310027, China (e-mail: eedqgcsyp@126.com; nianheng@ liability.
zju.edu.cn). Liu et al. [17] proposed the stator harmonic current elimina-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. tion technique by applying the closed-loop resonant controller
Digital Object Identifier 10.1109/TPEL.2014.2366494 for the stator current in RSC control. Since the stator harmonic

0885-8993 © 2014 IEEE. Translations and content mining are permitted for academic research only. Personal use is also permitted, but republication/redistribution
requires IEEE permission. See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
4832 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO. 9, SEPTEMBER 2015

current is directly regulated by the resonant controller, the com- +ω 1 , −ω 1 , −5ω 1 , and +7ω 1 ; subscripts +, −, 5−, and 7+ rep-
plicated rotor current reference calculation and harmonic com- resent the fundamental, negative, fifth, and seventh harmonic
ponents extraction can be avoided. However, the control target components; θ1 represents the phase angle of grid voltage fun-
of RSC is single and only the sinusoidal stator current can be damental component; and ω 1 represents the angular speed of
implemented, while the voltage unbalance and GSC control are grid voltage fundamental component.
neglected. Similarly, the grid voltage can be presented as
This paper proposes the modularized control strategy of DFIG − −j 2θ 1 −j 6θ 1
system under unbalanced and distorted grid voltage to avoid the U+ +
sdq = U sdq + + U sdq − e + U 5− sdq 5− e + U 7+ sdq 7+ e
j 6θ 1

communication between RSC and GSC, and the grid voltage (2)
fundamental, negative, and harmonic components extraction, as where U is the voltage.
well as complicated reference calculation, can also be avoided. Then, based on (1) and (2), the stator output active and reactive
From the perspective of power grid friendly operation of DFIG power of DFIG can be presented as [5]
system, the control targets of DFIG system are chosen as: 1) 3 − −j 2θ 1 −j 6θ 1
smooth active and reactive power of RSC and GSC into the Ps + jQs = − U + sdq + + U sdq − e + U 5− sdq 5− e
2
power grid; 2) balanced and sinusoidal current of RSC and GSC 
injected into the power grid. Indeed, the DFIG electromagnetic + U 7+
sdq 7+ e
j 6θ 1

torque ripple deserves much attention for the purpose of safe 



and reliable operation of mechanic components. However, it ∗ I+sdq + + I sdq − e
j 2θ 1
+ I 5−sdq 5− e
j 6θ 1

has been reported in [10] that the achieving of balanced and 


−j 6θ 1 j −2θ 1
sinusoidal stator current would inevitably cause the electromag- + I 7+
sdq 7+ e + I 3+
sdq 3+ e (3)
netic torque ripple of 100 and 300 Hz, which means these two
control targets are contradictory. In this paper, the authors tend + +
where Î sdq is the conjugated vector of Î sdq , Ps and Qs are
to focus more on the wind power quality, rather than the reliable the stator active and reactive power. When the control target of
operation of mechanic components; therefore, the control tar- smooth active and reactive power is selected, the third harmonic
gets of this paper are chosen as, balanced and sinusoidal stator component would exist in stator current, while the stator current
current, or the smooth active and reactive power. The control negative component would be zero, the detailed explanation can
target of eliminating the DFIG electromagnetic torque ripple be found in Section IV-A.
can be investigated in the future work. It can be found out from (3) that the active and reactive power
This paper is organized as follows: in Section II, the math- under unbalanced and distorted grid voltage would contain dc
ematical model of a DFIG system under negative, fifth, and average component, 100 and 300 Hz pulsation components,
seventh harmonically distorted grids is briefly mentioned. The which are produced by the interaction between fundamental
proposed modularized control strategy is described in detail in and negative harmonic components. Furthermore, the 200 and
Section III. The occurrence of third harmonic current compo- 400 Hz power pulsation components can also be produced by the
nent under control Target I, the dc-link voltage fluctuation, and interaction between negative and harmonic components; they
electromagnetic torque pulsation under both control targets are can be neglected in the control strategy due to the tiny amplitude.
also theoretically analyzed in Section IV. The VPI regulator’s The mathematic model of GSC current, active and reactive
robustness against DFIG parameters deviation is also analyzed power can be similarly expressed as
in Section IV. Finally, in Section V, the experimental system
− −j 2θ 1 −j 6θ 1
on 1 kW laboratory DFIG system is developed to validate the I+ +
g dq = I g dq + + I g dq − e + I 5−
g dq 5− e
availability of the modularized control strategy of DFIG system.
+ I 7+
g dq 7+ e
j 6θ 1
(4)
II. MATHEMATICAL MODEL OF DFIG RSC AND GSC UNDER 3 
− −j 2θ 1 −j 6θ 1
UNBALANCED AND DISTORTED GRID VOLTAGE Pg + jQg = − U + g dq + + U g dq − e + U 5−g dq 5− e
2

Since the fifth and the seventh harmonic components are the
+ U 7+
g dq 7+ e j 6θ 1
major harmonic components in grid voltage [14], only these two
harmonic components are taken into consideration in this paper. 

∗ I+g dq + + I g dq − e
j 2θ 1
+ I 5−g dq 5− e
j 6θ 1
The mathematical model of DFIG system under unbalanced and
harmonic grid voltage has been well established in [5] and is 
−j 6θ 1 −j 2θ 1
described briefly as follows. + I 7+
g dq 7+ e + I 3+
g dq 3+ e (5)
The stator current can be presented as [5]
where the subscript g represents the GSC component.
− −j 2θ 1 −j 6θ 1
I+ +
sdq = I sdq + + I sdq − e + I 5−
sdq 5− e + I 7+
sdq 7+ e
j 6θ 1
It should be noted that the U + +
sdq in (3) and U g dq in (5)
(1) identically represent the grid voltage. When the control target of
where I is the current; subscripts d, q represent components at the smooth active and reactive power is achieved, the third harmonic
d, q axis; subscript s represents stator components of DFIG; su- component would exist in the grid current, while the grid current
perscripts +, −, 5−, and 7+ represent the (dq)+ , (dq)− , (dq)5− , negative component would be zero; the detail explanation can
and (dq)7+ reference frames rotating at the angular speed of be found in Section IV-A.
SONG AND NIAN: MODULARIZED CONTROL STRATEGY AND PERFORMANCE ANALYSIS OF DFIG SYSTEM UNDER UNBALANCED 4833

Fig. 1. Block diagram of the proposed modularized control strategy of DFIG system.

Therefore, based on the aforementioned discussion, it can be employed to directly regulate the negative and harmonic com-
found out that when DFIG system works on the unbalanced and ponents of stator current, or the 100 and 300 Hz pulsation of
distorted grid, the unbalanced and harmonic current, as well as stator output active and reactive power.
output active and reactive power pulsation, will be injected into The output of PI regulator and VPI regulator that are added to-
the power grid, which is detrimental for the wind energy quality gether with the decoupling compensation item [5] would finally

and unfavorable for the stable and reliable operation of power achieve the rotor control voltage reference U + r dq , which would
grid. It is of great importance to improve the injected wind be used as the space vector pulse width modulation (SVPWM)
energy quality in terms of either balanced and sinusoidal three- module input to generate the IGBT switch signal for RSC.
phase current or smooth active and reactive power outputted 2) GSC Control Strategy: In the GSC control strategy, the
from DFIG system. active and reactive power Pg and Qg can be calculated according
to the grid voltage U + +
g dq and current I g dq . The grid voltage
phase angle θ1 can be obtained by the PLL module based on
III. PROPOSED MODULARIZED CONTROL STRATEGY the resonant regulator tuned at 100 and 300 Hz [12]. Since
A. Detailed Description the major function of GSC is to provide stable dc-link voltage
Vdc [5], [8], [12], the closed-loop control of dc-link voltage is
The modularized control strategy and block diagram for RSC implemented based on PI regulator, and the output is considered
and GSC is shown in Fig. 1. As shown in Fig. 1, RSC and GSC as the d-axis current reference I +∗ +∗
g d+ . The I g d+ and the q-axis
can work independently as two separate modules without the +∗
current reference I g d+ (which is normally set 0 to achieve unity
need for communication. The overall control targets for DFIG
power factor operation) would be used as the PI regulator input
system can be defined as:
of current control loop to regulate the fundamental component
1) Target I: Smooth active and reactive power injected into
of grid current.
the power grid.
When the alternative control targets, i.e., smooth GSC ac-
2) Target II: Balanced and sinusoidal current injected into
tive and reactive power output or balanced and sinusoidal GSC
the power grid.
current, are chosen, the closed-loop control with VPI regulator
1) RSC Control Strategy: In the RSC control strategy, the
tuned at 100 and 300 Hz would be employed to directly regulate
stator active and reactive power Ps and Qs of DFIG can be
the GSC current negative and harmonic components, or the 100
calculated according to the stator voltage U + sdq and stator current
and 300 Hz pulsation of GSC output active and reactive power.
I+sdq as shown in (3). The grid voltage phase angle θ1 can be Then, the switch signal implementation process for GSC is the
obtained by the PLL module based on the resonant regulator same as the control of RSC.
tuned at 100 and 300 Hz [12]. The rotor position θr can be
obtained from the encoder. The closed-loop control of rotor
current I + r dq can be implemented based on PI regulator to control
the DFIG average output power, and the rotor current reference B. Advantage of Modularized Control Strategy

I+r dq + can be obtained according to the power reference from Based on the earlier description and control block diagram
the maximum power point track (MPPT) [11]. shown in Fig. 1, it can be found out that, when the DFIG system
When the alternative control targets, i.e., smooth active and operates under the unbalanced and harmonic voltage, the advan-
reactive power output or balanced and sinusoidal stator current, tages of the modularized control strategy over the conventional
are chosen, the closed-loop control with vector proportional coordinated control strategy [5], [8], [12] can be concluded as
integral (VPI) regulator tuned at 100 and 300 Hz would be follows:
4834 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO. 9, SEPTEMBER 2015

1) In order to achieve the two alternative control targets, both control, and Kir 2 = Kpr 2 Rg /Lg , Kir 6 = Kpr 6 Rg /Lg for GSC
RSC and GSC are able to operate independently and no control [19], [20].
communication is required; thus, the DFIG system control
complexity can be simplified.
2) The negative and harmonic components extraction of grid IV. PERFORMANCE ANALYSIS ON MODULARIZED
voltage, stator current for RSC, or grid current for GSC CONTROL STRATEGY
can be avoided, and the complicated control reference cal- The two control targets can enhance the power quality out-
culation is also avoided. Thus, the RSC and GSC control putted by the overall DFIG system. However, there is still
complexity can be reduced. some detrimental influence on the operation reliability of DFIG
3) The control reference calculation for both RSC and GSC system. The following focuses on the performance analy-
with control Targets I and II is no longer needed in the sis of DFIG system with the proposed modularized control
proposed control strategy, then the DFIG system param- strategy.
eters is not involved in the control reference calculation;
thus, the possibility of DFIG system parameters deviation
to influence the control accuracy can be eliminated. A. Analysis on Third Harmonic Current Under Target I
It was mentioned in [13] that, when the stator active and
C. Limitation of Modularized Control Strategy reactive power 100 Hz pulsation of DFIG are simultaneously
However, there are also limitations of the proposed modular- removed, the third harmonic component in stator current would
ized control strategy: be generated as a consequence. However, only the qualitative
1) when the control Targets I and II are achieved, the elec- analysis on the third harmonic current component was reported.
tromagnetic torque 100 and 300 Hz pulsation would be Considering that the third harmonic current component would
produced, and the DFIG bearing and gear-box would be further pollute the power grid, it is essentially necessary to
damaged as a consequence; quantitatively investigate the third harmonic current component
2) the dc-link voltage 100 and 300 Hz fluctuations would when the control Target I is achieved from the perspective of
be generated when the control Targets I and II are im- the safe and reliable operation of power grid.
plemented; therefore, for the safe operation of RSC and It needs to point out that the third harmonic current component
GSC, the dc-link capacitor needs to be increased; is produced to eliminate the active and reactive power 100 Hz
3) the third harmonic component of stator current and GSC pulsation caused by the grid voltage unbalance and is irrelevant
current would be produced when the control Target I to the grid voltage harmonic distorted components; therefore,
is achieved; this is explained in detail in Section IV-A. the following discussion on the third harmonic current compo-
Therefore, the current injected into the power grid may be nent would involve the negative sequence component of grid
further polluted. voltage only.
In the RSC control, the 100 Hz active and reactive power
pulsations are mainly caused by the interaction between grid
D. VPI Regulator
voltage negative component U − sdq − and the stator current fun-
For the purpose of achieving the alternative control targets damental component I + , as well as the interaction between
sdq +
with the proposed modularized control strategy, it is important to grid voltage fundamental component U + sdq + and the stator
implement the accurate control of 100 and 300 Hz components.
current negative component I − sdq − and third harmonic com-
The VPI regulator [18]–[20], based on pole–zero cancellation
ponents [13]. It should be pointed out that, since VPI regu-
to avoid the unexpected gain peak, can be used to eliminate the
lator tuned at 100 Hz in synchronous frame would generate
DFIG stator current or active and reactive power 100 and 300 Hz
the ±100 Hz ac signals output due to VPI regulation capa-
components control error (GSC three-phase current or active
bility for both +100 and −100 Hz ac error signal, the VPI
and reactive power 100 and 300 Hz) due to the adequate closed-
regulator output would behave as −50 and +150 Hz ac sig-
loop phase margin and accurate ac signal tracking capability
nals in the stationary frame, which would finally result in the
[14], [18]–[20]
negative and third harmonic components in DFIG stator cur-
Kpr 2 s2 + Kir 2 s Kpr 6 s2 + Kir 6 s rent, respectively. Importantly, the third harmonic component
CV P I = 2 + (6) of DFIG stator current or the GSC three-phase current for elim-
s2 + ωc2 s + (2ω1 ) s2 + ωc6 s + (6ω1 )2
inating fluctuations in active/reactive power output is differ-
where ωc2 and ωc6 are the resonant bandwidth of 100 and 300 Hz ent from the commonly known one (which is zero sequence
components to widen the resonant frequency and improve the with the three-phase current having the same phase angle); it
VPI regulator robustness against grid frequency variation; ω1 is the positive sequence of 150 Hz. Thus, the three phases
is the angular speed of grid voltage fundamental component; of the third harmonic current would have the phase angle of
Kpr 2 and Kir 2 , Kpr 6 and Kir 6 are the proportional and inte- 300 πt + 0° for Phase A, 300 πt−120° for Phase B, and 300
gral coefficients of VPI 100 and 300 Hz components, respec- πt−240° for Phase C. As a result, the third harmonic component
tively, and Kir 2 = Kpr 2 Rr /σLr , Kir 6 = Kpr 6 Rr /σLr should of DFIG stator current or the GSC three-phase current is able
be followed based on the rule of pole–zero cancellation for RSC to flow.
SONG AND NIAN: MODULARIZED CONTROL STRATEGY AND PERFORMANCE ANALYSIS OF DFIG SYSTEM UNDER UNBALANCED 4835

According to (3), 100 Hz pulsation component of stator active Based on (8a) and (8b), it can be concluded that, when the
and reactive power can be expressed as control target of smooth active and reactive power is achieved,
3
the stator current third harmonic component would be produced
Ps100 + jQs100 = − U − +
sdq − I sdq + e
−j 2θ 1
and is relevant to the negative voltage component and the fun-
2 damental current component. The grid may be further polluted

− −j 2θ 1
+ U+ I
sdq + sdq − ej 2θ 1
+ U +
I 3+
sdq + sdq 3+ e due to the injection of the third harmonic current into the power
  grid.
3 (k1 + k3 + k5 ) cos 2θ1 + (k2 − k4 + k6 ) sin 2θ1 The third harmonic component I 3+ g dq 3+ of GSC current can
=− be deduced similarly and expressed as
2 +j (k2 +k4 +k6 ) cos 2θ1 + j (k3 − k1 − k5 ) sin 2θ1
− −
Usd− Ig+d+ + Usq +
− Ig q +
(7a)
d3+ = −
Ig3+ +
Usd+
where
− −
− Ig d+ − Usd− Ig q +
+ +
Usq
3 Ig3+
Ps100 cos = − (k1 + k3 + k5 ) q 3+ = + . (9)
2 Usd+
3 Therefore, based on (8a) and (8b) and (9), the overall third
Ps100 sin = − (k2 − k4 + k6 )
2 harmonic current components outputted from DFIG system can
3 be presented as
Qs100 cos = − (k2 + k4 + k6 )
2 3+
Ialld3+ 3+
= Isd3+ + Ig3+ (10a)
d3+
3     
Qs100 sin = − (k3 − k1 − k5 ) (7b) − Usd−− +
Isd+ −
+ Ig+d+ + Usq + +
2 − Isq + + Ig q +
= +
where Usd+
− + − + 3+ 3+ 3+
k1 = Usd− Isd+ + Usq − Isq + Iallq 3+ = Isq 3+ + Ig q 3+
− −
   + 
− Isd+ − Usd− Isq +
+ +
k2 = Usq − −
− Isd+ + Ig d+ − Usd− Isq + + Ig q +
+ + +
Usq
+ − + − = + .
k3 = Usd+ Isd− + Usq + Isq − Usd+
− −
+ Isd− − Usd+ Isq −
+ +
k4 = Usq (10b)
+ 3+ + 3+ It can be seen that, the overall third harmonic current com-
k5 = Usd+ Isd3+ + Usq + Isq 3+
ponent of DFIG system is determined by the unbalanced com-
+ Isd3+ − Usd+ Isq 3+ .
+ 3+ + 3+ −
k6 = Usq (7c) ponent of grid voltage Usdq − , the fundamental component of
+
Thus, based on (7b) and (7c), it can be seen that, in order to grid voltage Usdq + , the fundamental component of DFIG stator
+
achieve smooth stator output active and reactive power, these current Isdq + , and the fundamental component of GSC current
+
equations need to be satisfied, k3 = k4 = 0 k1 + k5 = 0, and Ig dq + . As the grid voltage unbalance condition becomes severe,
k2 + k6 = 0. Thus, the following conclusion can be obtained: the third harmonic current would also be aggravated. Similarly,
1) According to k3 = k4 = 0, it can be deduced that the the increasing of DFIG system active and reactive power would
negative component of stator current is null, i.e., I −
sdq − = also enhance the third harmonic current.
0, which means no stator current negative components
would be injected into the power grid under the control B. DC-Link Voltage Fluctuation Under Target I and Target II
strategy I of smooth active and reactive power.
In the DFIG system, the dc-link voltage is first established by
2) According to k1 + k5 = 0, it can be found out that the
3+ the GSC and then is regarded as the stable dc power supply for
d-axis component Isd3+ of the third harmonic current is
the RSC to implement the safe and reliable operation of DFIG
only related to the unbalanced voltage components and
+ system. Under the control Targets I and II, 100 and 300 Hz
fundamental components of stator current (Usq + should
+ fluctuation of dc-link voltage would occur inevitably. The dc-
be 0 since d is aligned with the fundamental component
link voltage fluctuation will deteriorate the lifetime of dc-link
of grid voltage)
capacitor, and the overlarge dc-link voltage fluctuation would
− + − + cause the danger of IGBT overvoltage and even damage the
Usd− Isd+ + Usq − Isq +
3+
Isd3+ =− + . (8a) entire hardware equipment. Therefore, from the perspective of
Usd+
the safe and reliable operation of DFIG system, it would be
Similarly, according to k2 + k6 = 0, the q-axis component of essentially meaningful to analyze the dc-link voltage fluctuation
third harmonic current can be presented as under unbalanced and distorted grid voltage condition with the
− −
control Targets I and II.
− Isd+ − Usd− Isq +
+ +
3+ Usq According to [5], the dc-link voltage would be influenced by
Isq 3+ = + . (8b)
Usd+ the DFIG electromagnetic power, DFIG stator active power, and
4836 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO. 9, SEPTEMBER 2015

GSC active power


7+
−Usd5−
5− +
Isd+ − Usq
5− +
5− Isq +
Isd7+ = +
dVdc Usd+
C Vdc = Pe + Ps + Pg (11)
dt
5− Isd+ − Usd5− Isq +
5− + 5− +
7+
Usq
where Vdc represents the dc-link voltage, C is dc-link capacitor, Isq 7+ = + . (16)
Usd+
Pe , Ps , and Pg are the electromagnetic power, DFIG stator active
power, and GSC active power, respectively. Then, (15) can be rewritten as
 
It should also be noted that the instantaneous active power 3 ωr  6 6
pulsation in the GSC inductance Lg is not null, but due to
I
Pe6 = − A3 − A5 cos 6θ1
2 ω1 5 7
its significant small value compared with the Pe , Ps , and Pg  
6 6 
in (11), the following discussion would ignore the instantaneous + − A4 + A6 sin 6θ1 (17a)
active power pulsation in the GSC inductance Lg . 5 7
The power positive direction in this discussion is defined 5− + 5− +
A3 = Usd5− Isd+ + Usq 5− Isq +
as flowing from power grid to the DFIG system; therefore,
5− Isd+ − Usd5− Isq +
in (11), Pe is always positive due to the electromagnetic power 5− + 5− +
A4 = Usq
from wind turbine to the DFIG, Ps is always negative due to the 7+ + 7+ +
generator characteristic of DFIG, and Pg is positive under sub- A5 = Usd7+ Isd+ + Usq 7+ Isq +
synchronous state, or negative under supersynchronous state.
7+ Isd+ − Usd7+ Isq + .
7+ + 7+ +
A6 = Usq (17b)
Based on (11), it can be seen that the dc-link voltage is deter-
mined by the three active power components, thus these active As can be observed from (14a) and (14b) and (17a) and
power pulsation needs to be investigated first. (17b), when the control Target I is achieved, the electromagnetic
I
1) Active Power Pulsation Under Control Target I: As de- power would contain 100 and 300 Hz pulsation components Pe2
I
scribed in Section IV-A, when control Target I is achieved, no and Pe6 , while the DFIG stator power and GSC power Ps and
stator and grid current negative components would be produced. Pg would both be smooth without pulsation, i.e., Ps2 = Ps6 =
Therefore, the 100 Hz electromagnetic power pulsation can be Pg 2 = Pg 6 = 0; thus, according to (11), the 100 and 300 Hz
presented as [17] fluctuation of dc-link voltage under control Target I can be
3   3+ +
 expressed as
− −j 2θ 1
I
Pe2 = ωr Re j ψ + Î
sdq + sdq 3+ + ψ Î
sdq − sdq + e I
dVdc2 dV I
2 C I
Vdc2 I
= Pe2 ; C dc6 Vdc6 I
= Pe6 I
. (18)
(12) dt dt
where ωr is rotor electric angular speed, Ψ is flux, which can be 2) Power Pulsation Under Control Target II: When control
presented as Target II is achieved, the balanced and sinusoidal stator and
1  +  grid current would be ensured in the DFIG stator winding and
ψ+
sdq + = Usq + − jUsd+
+
GSC. Thus, the 100 Hz electromagnetic power pulsation can be
ω1
  presented as
1
ψ−
sdq − = −
−Usq −
− + jUsd− . (13) 3   
ω1 Pe2II
= ωr Re j ψ − I +
sdq − sdq + e−j 2θ 1
2
Based on (8a) and (8b) and (13), (12) can be rewritten as
3ωr
3ωr = (−A1 cos 2θ1 − A2 sin 2θ1 ) (19)
I
Pe2 = (−A1 cos 2θ1 − A2 sin 2θ1 ) (14a) 2ω1
ω1 where A1 and A2 can be found in (14b).
− − − −
− Isd+ − Usd− Isq + .
+ + + +
A1 = Usd− Isd+ + Usq − Isq + ; A2 = Usq According to [8], the DFIG stator active power and GSC
active power would also contain the 100 Hz pulsation
(14b)
3
Similarly, the 300 Hz electromagnetic power pulsation can
II
Ps2 = − (A1 cos 2θ1 + A2 sin 2θ1 ) (20)
2
be presented as ⎡   ⎤
− + − +
⎡⎛ ⎞⎤ 3 ⎣ Usd− Ig d+ + Usq − Ig q + cos 
2θ1
⎦ . (21)
ψ +

5−
ej 6θ 1
+ψ 7+
I +
e j 6θ 1 P II
g 2 = − − −
I 3
Pe6 = ωr Re j ⎣ ⎝
sdq + sdq 5− sdq 7+ sdq +
⎠⎦.
2 + Usq − I
g
+
d+ − U sd− Ig
+
q + sin 2θ 1
2 7+ −j 6θ 1 + −j 6θ 1
+ψ +sdq + Î sdq 7+ e +ψ 5−sdq 5− Î sdq + e Based on the 100 Hz electromagnetic power pulsation in (19),
(15) 100 Hz DFIG stator power pulsation in (20), 100 Hz GSC power
The fifth and seventh harmonic components of stator current pulsation in (21), it can be found out that
under control Target I can be expressed as [10]
3 (ωr + ω1 )
II
Pe2 + Ps2 II
+ PgI2I = − (A1 cos 2θ1 + A2 sin 2θ1 )
5−
−Usd7+ Isd+ − Usq 7+ Isq +
7+ + 7+ +
2ω1
Isd5− =
Usd++
3  − + −

− Usd− Ig d+ + Usq +
− g q + cos 2θ1
I
2
5−
U 7+
I +
sq 7+ sd+ − U 7+
I
sd7+ sq +
+
  
Isq 5− = − −
− Ig d+ − Usd− Ig q + sin 2θ1 .(22)
+ +
+
Usd+ + Usq
SONG AND NIAN: MODULARIZED CONTROL STRATEGY AND PERFORMANCE ANALYSIS OF DFIG SYSTEM UNDER UNBALANCED 4837

The 300 Hz electromagnetic power pulsation under control Target II in (22) can be transformed into the same as the active
Target II can be presented as power pulsation of 100 Hz under Target I in (14a) and (14b).
3    +  Similarly, the active power pulsation of 300 Hz under Target II
−j 6θ 1
II
Pe6 = ωr Re j ψ 5− sdq 5− e + ψ 7+
sdq 7+ e
j 6θ 1
Î sdq + in (26) can also be transformed into the same as the active power
2
pulsation of 300 Hz under Target I in (17a) and (17b).
3ωr  1 1 1 3) DC-Link Voltage Fluctuation Analysis: Undoubtedly, the
= A5 cos 6θ1 − A6 sin 6θ1 − A3 cos 6θ1
2ω1 7 7 5 active power pulsation of 100 and 300 Hz under Targets I and
1  II would both result in the dc-link voltage fluctuation, and for
− A4 sin 6θ1 . (23) the sake of discussion simplicity, only the case of special cir-
5
+ +
The 300 Hz DFIG stator active power pulsation can be ex- cumstance (i.e., Isq + = 0, Ig q + = 0) would be analyzed here,

pressed as [10] where both the 100 and 300 Hz power pulsation under control
Targets I and II are the same; thus, the corresponding 100 and
3 300 Hz dc-link voltage fluctuation would be the same no matter
II
Ps6 = − (A5 cos 6θ1 −A6 sin 6θ1 +A3 cos 6θ1 +A4 sin 6θ1 ) .
2 which control target is selected under this special circumstance.
(24) The dc-link voltage can be expressed including the dc com-
Similarly, the 300 Hz GSC active power pulsation can be ponent, 100 and 300 Hz fluctuation components as follows:
expressed as
⎡ ⎤ Vdc = Vdc0 + Vdc2 cos cos 2θ1 + Vdc2 sin sin 2θ1
5−
Usd5− Ig+d+ + Usq 5− + 7+ +
5− Ig q + + Usd7+ Ig d+
⎢  ⎥ +Vdc6 cos cos 6θ1 + Vdc6 sin sin 6θ1
⎢ + U 7+ I + ⎥

3 ⎢  g q + cos 6θ1 ⎥
Pg 6 = − 2 ⎢
II sq 7+
⎥. = Vdc0 + Vdc2m sin (2θ1 + ϕ2 ) + Vdc6m sin (6θ1 + ϕ6 )
+ ⎥
⎢ + Usq 5− Ig d+ − Usd5− Ig q + − Usq 7+ Ig d+ ⎥
5− + 5− + 7+
⎣  ⎦ (28a)
7+
+ Usd7+ Ig+q + sin 6θ1
(25) where Vdc0 represents the dc component, Vdc2cos , Vdc2sin repre-
Based on (23), (24), and (25), the 300 Hz power pulsation sents the 100 Hz cosine and sine fluctuation component, Vdc6cos ,
under control Target II can be expressed as Vdc6sin represents the 300 Hz cosine and sine fluctuation com-
ponent, Vdc2m , Vdc6m represents the overall 100 and 300 Hz
II II
Pe6 + Ps6 + PgI6I fluctuation component, which can be calculated according to
⎡    ⎤ the trigonometric function as
ωr ωr
− 1 A5 cos 6θ1 − − 1 A6 sin 6θ1 
3 ⎢ 7ω1 7ω1 ⎥
= ⎢     ⎥
(Vdc2 cos )2 + (Vdc2 sin )2
2⎣ ωr ωr ⎦ Vdc2m =
− + 1 A3 cos 6θ1 − + 1 A4 sin 6θ1 
5ω1 5ω1
Vdc6m = (Vdc6 cos )2 + (Vdc6 sin )2 . (28b)
⎡ ⎤
5−
(Usd5− Ig+d+ + Usq
5− + 7+ +
5− Ig q + + Usd7+ Ig d+
⎢ ⎥ Based on (28a) and (28b), the dc-link voltage fluctuation in
⎢ +U 7+ I + ) cos 6θ ⎥ (11) can be rewritten as
3 ⎢ sq 7+ g q + 1 ⎥
− ⎢ ⎥.
2 ⎢ +(U 5− I + − U 5− I + − U 7+ I + ⎥

⎥ dVdc 
⎣ sq 5− g d+ sd5− g q + sq 7+ g d+ ⎦ C Vdc = C 2ω1 Vdc2m cos (2θ1 + ϕ2 )
dt
7+ +
+Usd7+ Ig q + ) sin 6θ1 
+ 6ω1 Vdc6m cos (6θ1 + ϕ6 )
(26)

Therefore, it can be found out that the power pulsation of ∗ Vdc0 + Vdc2m sin (2θ1 + ϕ2 )
100 Hz under Target I in (14a) and (14b) and under Target II 
in (22) is different, while the power pulsation of 300 Hz under + Vdc6m sin (6θ1 + ϕ6 ) . (29)
Target I in (17a) and (17b) and under Target II in (26) is also
According to the 100 Hz power pulsation under control Tar-
different.
gets I and II as given in (14a) and (14b) and (22), the 100 Hz
However, it is reported in [1] that GSC provides the slip rate
dc-link voltage fluctuation in (29) can be presented as
(s = (ω1 − ωr )/ω1 ) percentage of DFIG output active power
2ω1 CVdc0 Vdc2m sin (2θ1 + ϕ2 )
g d+ = −sl I sd+
I+ +
(27)

3ωr
where sl is the slip rate, and the “−” indicates that the GSC = A21 + A22 sin (2θ1 + ϕ3 ) . (30)
power flows from grid to DFIG system under subsynchronous ω1
state (sl > 0), or from DFIG system to grid under supersyn- Thus, the 100 Hz dc-link voltage fluctuation can be obtained
chronous state (sl < 0). as
Then, under the special circumstance that both the RSC and 
+
GSC output zero reactive power, i.e., Isq +
+ = 0, Ig q + = 0, and
3ωr A21 + A22
Vdc2m = . (31a)
according to (27), the active power pulsation of 100 Hz under 2 (ω1 )2 CVdc0
4838 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO. 9, SEPTEMBER 2015

The 300 Hz dc-link voltage fluctuation can be deduced simi-


larly on the basis of (17a) and (17b) and (26) and shown as

Vdc6m
 Fig. 2. Closed-loop control scheme using VPI regulator with control
Target II.
ωr (−(6/5)A3 − (6/7)A5 )2 + (−(6/5)A4 + (6/7)A6 )2
= .
4 (ω1 )2 CVdc0  
3  6 6
(31b)
I
Te6 = − A3 − A5 cos 6θ1
2pω1 5 7
  
Finally, (31a) and (31b) give out the 100 and 300 Hz dc-link 6 6
+ − A4 + A6 sin 6θ1 . (33b)
voltage fluctuation under the special circumstance using the 5 7
modularized control strategy. It can be concluded from (31a)
Similarly, based on (19), (23), and (32), 100 and 300 Hz
and (31b) that:
pulsation of the electromagnetic torque under control Target II
1) DC-link voltage fluctuation would become more severe
can be expressed as
when the rotor speed ωr accelerates from subsynchronous
state to the supersynchronous state. 3
II
Te2 = (−A1 cos 2θ1 − A2 sin 2θ1 ) (34a)
2) DC component Vdc0 in dc-link voltage would also influ- 2pω1
 
ence the 100 and 300 Hz fluctuation component, and larger 3  1 1
Vdc0 would be helpful in reducing the voltage fluctuation.
II
Te6 = − A3 + A5 cos 6θ1
2pω1 5 7
3) The 100 Hz fluctuation caused by grid voltage unbalance  
1 1 
would be comparatively larger than the 300 Hz fluctua-
+ − A4 − A6 sin 6θ1 . (34b)
tion; therefore, the grid voltage unbalance rather than the 5 7
harmonic distortion should deserve more attention in the
According to the electromagnetic torque pulsation expres-
practical situation.
sion shown in (33) and (34), the following conclusion can be
4) When the grid voltage negative component U − sdq − , har-
7+
obtained:
monic components U 5− sdq 5− and U sdq 7+ , and the stator 1) Based on A1 –A6 shown in (14b) and (17b), as the grid
current fundamental component I + sdq + increase, the corre- voltage unbalance and distortion become severe, the larger
sponding dc-link voltage fluctuation would also increase. electromagnetic torque pulsation will occur.
5) According to (31a) and (31b), a proper dc-link capacitor 2) It can be found out that the 100 Hz electromagnetic torque
can be designed to satisfy the dc-link voltage fluctuation pulsation under control Target II is half as that under con-
criterion for the reliable operation of DFIG system under trol Target I. Moreover, the 300 Hz electromagnetic torque
the nonideal grid voltage condition. pulsation under control Target II is also much smaller than
that under control Target I; therefore, it can be verified that
C. Electromagnetic Torque Pulsation Under Target I the overall electromagnetic torque pulsation under control
and Target II Target II would be much smaller than that under control
Target I.
When DFIG operates under the unbalanced and harmonic
voltage, the smooth electromagnetic torque is usually set as the
D. VPI Regulator’s Robustness Against DFIG
important control target for the reliable working of the mechanic
Parameter Deviation
parts, i.e., the gear-box and DFIG rotor shaft and bearing. Since
the balanced and sinusoidal current, or smooth output power, is In the practical application, the DFIG parameter deviation
achieved for DFIG in this paper, 100 and 300 Hz fluctuation of may occur due to the temperature changing, skin effect or
electromagnetic torque will occur inevitably. flux saturation, thus discussing the VPI regulator’s robustness
As deduced in Section IV-B, the 100 and 300 Hz fluctuation against DFIG parameter deviation would be essential, and for
of electromagnetic power under control Targets I and II has been the sake of simplicity, the control Target II of balanced and
given in (14a) and (14b), (17a) and (17b), (19), and (23). And sinusoidal stator current is taken as an example.
the electromagnetic torque can be presented as When the control Target II of balanced and sinusoidal stator
current is implemented, the closed-loop control scheme can be
Pe
Te = (32) shown in Fig. 2.
pωr The transfer function of control subject DFIG from VPI reg-
where T is electromagnetic torque and p is the DFIG pole pairs. ulator output to stator current can be presented as
e
Therefore, based on (14a) and (14b), (17a) and (17b), and Lm 1
Gplan t (s) = (35)
(32), 100 and 300 Hz pulsation of the electromagnetic torque Ls Rr + sσLr
under control Target I can be expressed as
where Rr is DFIG rotor resistance, σ = 1–L2m/Ls Lr is
3 DFIG leakage inductance efficient, and Lr is the DFIG rotor
I
Te2 = (−A1 cos 2θ1 − A2 sin 2θ1 ) (33a) inductance.
pω1
SONG AND NIAN: MODULARIZED CONTROL STRATEGY AND PERFORMANCE ANALYSIS OF DFIG SYSTEM UNDER UNBALANCED 4839

Then, the closed-loop control transfer function can be pre-


sented as (36), shown at the bottom of the page.
Preliminarily, it should be noted that the leakage inductance
efficient σ is calculated as

L2m
σ =1− (37)
Ls Lr

where Ls is the stator inductance, Lr is the rotor inductance,


and Lm is the mutual inductance.
The stator inductance and rotor inductance can be, respec-
tively, presented as

Ls = Lm + Lσs ; Lr = Lm + Lσ r (38)

where Lσs is the stator leakage inductance and Lσr is the rotor
leakage inductance; Lσs and Lσr are almost equal.
Thus, based on the transfer function of control subject DFIG,
the rotor resistance Rr , mutual inductance Lm , and leakage in-
ductance Lσ (designating both Lσ s and Lσ r ) would be involved
in the discussion of VPI regulator’s robustness against DFIG
parameter deviation. Typically, the variation range of mutual
inductance Lm , leakage inductance Lσ , and rotor resistance
Rr is chosen, respectively, as ±20%, ±60%, and ±50% [21].
The corresponding bode diagram of closed-loop control trans-
fer function with the different parameter deviation is shown in
Fig. 3.
As can be observed from Fig. 3(a), once the mutual inductance
Lm deviates to 0.8 times or 1.2 times of the normal value,
both the closed-loop magnitude response and phase response
within 50–350 Hz would remain almost unchanged, and more
importantly, the magnitude response at 100 and 300 Hz would
maintain 0 dB, and the phase response at 100 and 300 Hz would
remain 0°. As shown in Fig. 3(b), when the leakage inductance
Lσ deviation of ±60% occurs, the slight changing of magnitude
response and phase response within 50–350 Hz can be observed,
while the magnitude and phase response at the control frequency
of 100 and 300 Hz would remain 0 dB and 0°. When the rotor
resistance Rr deviation of ±50% happens, as given in Fig. 3(c),
the magnitude and phase response can keep almost same, and
the magnitude and phase response of 0 dB and 0° at the control
frequency 100 and 300 Hz can be ensured. Therefore, based
on the analysis result shown in Fig. 3, it can be found out Fig. 3. Bode diagram of closed-loop control transfer function with DFIG
parameter deviation (a) mutual inductance L m deviation of ±20%; (b) leak-
that the effective working capability of VPI regulator under the age inductance L σ deviation of ±60%; (b) rotor resistance R r deviation of
circumstance of DFIG parameters deviation can be guaranteed, ±50% (VPI regulator parameters of ω c 6 = ω c 6 = 2 rad/s, K p r 2 = K p r 6 = 1,
and the achievement of the control targets can be obtained. K i r 2 = K i r 6 = 150).

CV P I (s)Gplan t (s)
Ccl (s) =
 1 + CV P I (s)Gplan t (s) 
(Kpr 2 s2 + Kir 2 s)/(s2 + ωc2 s + (2ω1 )2 ) + (Kpr 6 s2 + Kir 6 s)/(s2 + ωc6 s + (6ω1 )2 ) (Lm /Ls ) (1/(Rr + sσLr ))
=  
1 + (Kpr 2 s2 + Kir 2 s)/(s2 + ωc2 s + (2ω1 )2 ) + (Kpr 6 s2 + Kir 6 s)/(s2 + ωc6 s + (6ω1 )2 ) (Lm /Ls ) (1/(Rr + sσLr ))
(36)
4840 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO. 9, SEPTEMBER 2015

Fig. 4. Block diagram of experiment system.

TABLE I
PARAMETERS OF EXPERIMENT DFIG SYSTEM
Fig. 5. Experimental result of DFIG system performance under unbalanced
and distorted grid voltage condition when VPI regulator is disabled.
Rated Power 1 kW Frequency 50 Hz

Grid voltage 110 V DFIG pole pairs 3


Stator/rotor turns ratio 0.33 DC-link voltage V d c 200 V TABLE II
Stator resistance R s 1.01 Ω DC-link capacitor C d c 2200 μF EXPERIMENT RESULT ANALYSIS
Rotor resistance R r 0.88 Ω GSC line inductance L g 4 mH
DFIG mutual inductance 90.1 mH GSC line resistance R g 0.02 Ω
Lm Without VPI Control Control Target I Control Target II
DFIG stator leakage 3.0 mH DFIG rotor leakage 3.0 mH
inductance L σ s inductance L σ r U g negative 2.90% 2.90% 2.90%
U g fifth order 2.36% 2.36% 2.36%
U g seventh order 1.17% 1.17% 1.17%
I g negative 13.82% 1.22% 1.62%
V. EXPERIMENTAL VALIDATION I g third order 1.62% 4.70% 1.18%
I g fifth order 14.49% 6.02% 2.31%
A. Experiment Setup I g seventh order 13.39% 2.88% 1.84%
P g 100 Hz ±84 W ±10 W ±27 W
Experiment system was built on a laboratory prototype of Q g 100 Hz ±18 Var ±9 Var ±15 Var
P g 300 Hz ±36 W ±5 W ±30 W
1 kW DFIG system as shown in Fig. 4, the DFIG is driven by Q g 300 Hz ±30 Var ±4 Var ±24 Var
a 1.5 kW squirrel cage induction machine as the wind turbine. I s negative 17.42% 1.56% 1.69%
The induction machine is driven by a general converter. The I s third order 0.45% 5.41% 0.31%
I s fifth order 4.37% 2.79% 1.85%
Chroma 61704 is employed to simulate the practical unbalanced I s seventh order 1.87% 2.01% 0.92%
and harmonically distorted power grid. In the experiment, grid P s 100 Hz ±84 W ±18 W ±45 W
voltage negative, fifth, and seventh-order harmonic components Q s 100 Hz ±75 Var ±25 Var ±45 Var
P s 300 Hz ±36 W ±12 W ±30 W
are set 2.90%, 2.36%, and 1.17%, respectively. The parameters Q s 300 Hz ±24 Var ±10 Var ±21 Var
of the DFIG system are listed in Table I.
In the control of DFIG RSC, the rotor speed is initially set to
800 r/min (the synchronous speed is 1000 r/min). The dc-link
voltage is provided by the GSC to be 200 V. Both the RSC and
GSC control strategies are implemented on the two separate
DSP TMS320F28335, and the driver for IGBT is SEMIKRON
SKHI61. The sampling frequency is 10 kHz, and the IGBT
switching frequency is 5 kHz.

B. Experiment Results
Fig. 5 shows the experimental result of DFIG system under
unbalanced and distorted grid voltage condition when VPI regu-
lator is disabled. It can be found out that the heavily unbalanced
and distorted current in GSC and DFIG will occur; moreover,
100 and 300 Hz pulsation of the GSC and DFIG stator power
would be produced; the detailed experiment result analysis can
be found in Table II.
Fig. 6 shows the experimental result of DFIG system under Fig. 6. Experimental result of DFIG system under unbalanced and distorted
unbalanced and distorted grid voltage condition with control grid voltage condition with control Target I.
SONG AND NIAN: MODULARIZED CONTROL STRATEGY AND PERFORMANCE ANALYSIS OF DFIG SYSTEM UNDER UNBALANCED 4841

Fig. 7. Experimental result of DFIG system under unbalanced and distorted Fig. 8. Experimental result of DFIG stator output active power stepping under
grid voltage condition with control Target II. unbalanced and distorted grid voltage condition with control Target II: balanced
and sinusoidal GSC three-phase current and DFIG stator current.

Target I, i.e., the smooth GSC output power and smooth DFIG
stator output power is achieved. As can be seen, the GSC power
and DFIG stator power would all become much smoother com-
pared with the results in Figs. 5 and 7. It can also be seen from
Table II that, in order to eliminate the 100 Hz GSC power and
DFIG stator power pulsation, both the GSC current and DFIG
stator current would contain nonnegligible amount of the third
harmonic component. Similarly, for the purpose of removing
the 300 Hz power pulsation, the GSC current and DFIG sta-
tor current would contain the severe fifth and seventh harmonic
components compared with the result shown in Fig. 7. The de-
tailed experiment result analysis is also available in Table II.
Fig. 7 shows the experimental result of DFIG system under
unbalanced and distorted grid voltage condition with control
Target II, i.e., the balanced and sinusoidal GSC current and
DFIG stator current is achieved. In comparison with Fig. 5, both
Fig. 9. Experimental result of DFIG speeding up from 800 r/min (0.8 p.u.)
the GSC three-phase current and DFIG stator current would be to 1200 r/min (1.2 p.u.) under unbalanced and distorted grid voltage condition
significantly improved with negligible harmonic distortion and with control Target II: balanced and sinusoidal GSC three-phase current and
tiny unbalance; this is quite helpful for the safe and reliable DFIG stator current.
operation of the power grid. Besides, the pulsation of GSC power
and DFIG stator output power would also be larger than that
under control Target I. The detailed experiment result analysis II, and the GSC active power would correspondingly step from
is available in Table II. 50 to 100 W. It can be seen that the DFIG stator active power
By analyzing the experiment results, it can be found out in stepping takes the transient response time of around 100 ms,
Table II that compared with the control without VPI regulator, which proves the excellent dynamic regulation capability of
the unbalanced and distorted current, as well as power pul- the rotor current fundamental component. Moreover, it can be
sation can be significantly improved whatever control target observed that the GSC current and DFIG stator current is able
is implemented. Moreover, the pulsation of DFIG stator output to maintain balanced and sinusoidal both before and after the
active/reactive power and GSC active/reactive power under con- stepping moment; this result validates the proposed modularized
trol Target I is much smaller than that under control Target II. control strategy by applying the VPI closed-loop control.
Instead, the heavily distorted DFIG stator current and GSC cur- Fig. 9 shows the experimental result of DFIG speeding up
rent, containing third, fifth, and seventh harmonic components, from 800 r/min (0.8 p.u.) to 1200 r/min (1.2 p.u.) under unbal-
would be generated under Target I as a consequence. It should anced and distorted grid voltage condition with control Target
be noted that no negative component of DFIG stator current II: balanced and sinusoidal GSC three-phase current and DFIG
or GSC current would occur under both control targets, which stator current. As can be seen from Fig. 9, when the rotor speed
verifies the theoretical analysis in Section IV-A. acceleration happened, the GSC current would first decrease
Fig. 8 shows the experimental result of DFIG stator output to 0, then the direction of GSC current would become oppo-
active power stepping from 250 to 500 W with control Target site, indicating that the GSC would operate as an inverter under
4842 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 30, NO. 9, SEPTEMBER 2015

supersynchronous state, and the GSC power would flow from [8] J. Hu, Y. He, L. Xu, and B. W. Williams, “Improved control of DFIG
the dc-link capacitor to the power grid. Importantly, it should systems during network unbalance using PI–R current regulators,” IEEE
Trans. Ind. Electron., vol. 56, no. 2, pp. 439–451, Feb. 2009.
be noted that since the several losses (copper loss, magnetizing [9] J. Yao, H. Li, Z. Chen, X. Xia, X. Chen, Q. Li, and Y. Liao, “Enhanced
loss) in the experiment inevitably exists; therefore, the mag- control of a DFIG-based wind-power generation system with series grid-
nitude of GSC current under subsynchronous state would be side converter under unbalanced grid voltage conditions,” IEEE Trans.
Power Electron., vol. 28, no. 7, pp. 3167–3181, Jul. 2013.
smaller than that under supersynchronous state (Pg = 100 to [10] J. Hu, H. Nian, H. Xu, and Y. He, “Dynamic modeling and improved
−40 W) due to these losses. Moreover, the stator current is able control of DFIG under distorted grid voltage conditions,” IEEE Trans.
to maintain constant within the DFIG speeding moment, and Energy Convers., vol. 26, no. 1, pp. 163–175, Mar. 2011.
[11] H. Xu, J. Hu, and Y. He, “Operation of wind-turbine-driven DFIG sys-
the stator output power can also remain constant as a result. tems under distorted grid voltage conditions: Analysis and experimental
The rotor current, which is relevant to the DFIG rotor speed, validations,” IEEE Trans. Power Electron., vol. 27, no. 5, pp. 2354–2366,
would change according to the speeding variation with very May 2012.
[12] P. Zhou, Y. He, and D. Sun, “Improved direct power control of a DFIG-
smooth transient response, and no overcurrent or overshoot can based wind turbine during network unbalance,” IEEE Trans. Power Elec-
be observed. Thus, it can be concluded that the proposed con- tron., vol. 24, no. 11, pp. 2465–2474, Nov. 2009.
trol strategy is able to maintain effective under the circumstance [13] H. Nian, Y. Song, P. Zhou, and Y. He, “Improved direct power control
of a wind turbine driven doubly fed induction generator during transient
of DFIG speed variation, thus making the strategy applicable grid voltage unbalance,” IEEE Trans. Energy Convers., vol. 26, no. 3,
in the practical situation where DFIG speed variation happens pp. 976–986, Sep. 2011.
frequently. [14] H. Nian and Y. Song, “Direct power control of doubly fed induction
generator under distorted grid voltage,” IEEE Trans. Power Electron.,
vol. 29, no. 2, pp. 894–905, Feb. 2014.
VI. CONCLUSION [15] J. Hu, J. Zhu, Y. Zhang, G. Platt, Q. Ma, and D. G. Dorrell, “Predictive
direct virtual torque and power control of doubly fed induction generators
The paper presented a modularized control strategy of the for fast and smooth grid synchronization and flexible power regulation,”
DFIG system under unbalanced and distorted grid voltage, with IEEE Trans. Power Electron., vol. 28, no. 7, pp. 3182–3194, Jul. 2013.
[16] Y. Zhang, J. Hu, and J. Zhu. “Three-vectors-based predictive direct power
the control targets of smooth active and reactive power of RSC control of the doubly fed induction generator for wind energy appli-
and GSC, or balanced and sinusoidal current for both RSC and cations,” IEEE Trans. Power Electron., vol. 29, no. 7, pp. 3485–3500,
GSC. Several advantages over the conventional control strat- Jul. 2014.
[17] C. Liu, F. Blaabjerg, W. Chen, and D. Xu, “Stator current harmonic control
egy have been validated: 1) avoids the negative and harmonic with resonant controller for doubly fed induction generator,” IEEE Trans.
component extraction in GSC and RSC; 2) removes the com- Power Electron., vol. 27, no. 7, pp. 3207–3220, Jul. 2012.
plicated and time-consuming current reference calculation; and [18] Y. Song and H. Nian, “Comparison of resonant current regulators for
DFIG during grid voltage distortion,” J. Zhejiang Univ-Sci C (Comput &
3) is able to cancel the communication between RSC and GSC. Electron), vol. 14, no. 12, pp. 953–965, Dec. 2013.
It has been proved that when the smooth active and reactive [19] C. Lascu, L. Asiminoaei, I. Boldea, and F. Blaabjerg, “High performance
power is achieved, no negative component of current would be current controller for selective harmonic compensation in active power
filters,” IEEE Trans. Power Electron., vol. 22, no. 5, pp. 1826–1835,
generated, but only third harmonic current component occurs, Sep. 2007.
which would unfortunately further pollute the power grid. How- [20] C. Lascu, L. Asiminoaei, I. Boldea, and F. Blaabjerg, “Frequency re-
ever, the 100 and 300 Hz dc-link voltage fluctuation would be sponse analysis of current controllers for selective harmonic compensa-
tion in active power filters,” IEEE Trans. Ind. Electron., vol. 56, no. 2,
generated when control Targets I and II are achieved; the electro- pp. 337–347, Feb. 2009.
magnetic torque 100 and 300 Hz pulsation under control Targets [21] H. M. Jabr and N. C. Kar. “Effects of main and leakage flux saturation on
I and II have also been theoretically analyzed. Besides, it has the transient performances of doubly-fed wind driven induction genera-
tor,” Electric Power Syst. Res., vol. 77, no. 8, pp 1019–1027, Jun. 2007.
also been proved that the VPI regulator has strong robustness
against DFIG parameters deviation.
Yipeng Song (S’14) was born in Hangzhou, China.
He received the B.Sc. degree in July 2010 from the
REFERENCES College of Electrical Engineering, Zhejiang Univer-
sity, Hangzhou, China, where he is currently working
[1] S. Muller, M. Deicke, and R. W. De Doncker, “Doubly fed induction toward the Ph.D. degree.
generator systems for wind turbines,” IEEE Ind. Appl. Mag., vol. 8, no. 3, His current research interests include motor con-
pp. 26–33, May/Jun. 2002. trol with power electronics devices in renewable-
[2] D. Zhi and L. Xu, “Direct power control of DFIG with constant switch- energy conversion, particularly the control and op-
ing frequency and improved transient performance,” IEEE Trans. Energy eration of doubly fed induction generators for wind
Convers., vol. 22, no. 2, pp. 110–118, Mar. 2007. power generation under adverse grid condition.
[3] National Grid Transco, Appendix 1. (Feb. 2004). Extracts from the
grid code—Connection conditions [Online]. Available: http://www.
nationalgrid.com Heng Nian (M’09) received the B.Eng. degree and
[4] IEEE Recommended Practices and Requirements for Harmonic Control the M.Eng. degree from Hefei University of Tech-
in Electrical Power Systems, IEEE Standard 519-1992, 1993. nology, Hefei, China, in 1999 and 2002, respec-
[5] J. Hu, H. Xu, and Y. He, “Coordinated control of DFIG’s RSC and GSC tively, and the Ph.D. degree from Zhejiang University,
under generalized unbalanced and distorted grid voltage conditions,” IEEE Hangzhou, China, in 2005, all in electrical engineer-
Trans. Ind. Electron., vol. 60, no. 7, pp. 2808–2819, Jul. 2013. ing.
[6] H. Xu, J. Hu, and Y. He, “Integrated modeling and enhanced control From 2005 to 2007, he was as a Postdoctoral
of DFIG under unbalanced and distorted grid voltage conditions,” IEEE Fellow with the College of Electrical Engineering,
Trans. Energy Convers., vol. 27, no. 3, pp. 725–736, Sep. 2012. Zhejiang University, China, where he has been an
[7] C. Liu, D. Xu, N. Zhu, F. Blaabjerg, and M. Chen, “DC-voltage fluctuation Associate Professor at the College of Electrical En-
elimination through a DC-capacitor current control for DFIG converters gineering since 2007. His current research interests
under unbalanced grid voltage conditions,” IEEE Trans. Power Electron., include the optimal design and operation control for wind power generation
vol. 28, no. 7, pp. 3206–3218, Jul. 2013. system.