Professional Documents
Culture Documents
2
Function of a Cascade Refrigeration System ................................................................... 3
Sanyo Refrigeration System Cutaway.............................................................................. 5
Sanyo Ultra Low Freezer Electrical System Operation..................................................... 6
Electrical and Electronic Component Access ................................................................... 8
Control Panel (MDF U4086S and MDF U5086W) ............................................................ 8
Control Panel (MDF U3086S & MDF U5186S) ................................................................ 9
Main Control Board (MDF U6086S,MDF U50V and MDF U70)V ................................... 11
Function Modes .......................................................................................................... 14
Entering Function Mode.............................................................................................. 14
Initiating a Defrost Cycle ................................................................................................ 15
Control Board Switch Functions and Operation (all other ultra low models)................... 15
Voltage Test Points on the Microboard....................................................................... 16
TEMPERATURE CALIBRATION PROCEDURES...................................................... 16
Thermocouples............................................................................................................... 17
Self Diagnostic Functions............................................................................................... 18
Error codes ................................................................................................................. 18
DEFROST TIMING......................................................................................................... 18
CAPILLARY TUBE HEATER SPECIFICATIONS........................................................... 19
HEAT EXCHANGER TEMPERATURE CONTROL POINTS ......................................... 19
MDF-U4086S ................................................................................................. 20
Sensor Specifications..................................................................................................... 20
PT100Ω Temperature Sensor. ................................................................................... 20
502AT Thermistor Sensor........................................................................................... 20
TROUBLESHOOTING GUIDE....................................................................... 21
PROCEDURE FOR TESTING FOR A REFRIGERANT LEAK ......................23
Leak Suspected in System?........................................................................... 25
TESTING FOR DIFFICULT TO LOCATE LEAKS ON THE LOW STAGE ..................... 26
PARTS REPLACEMENT WHEN A REFRIGERATION REPAIR IS PERFORMED ....... 31
Procedure When All Refrigerant Has Escaped .............................................................. 33
PROPER EVACUATION METHODS............................................................. 33
HIGH STAGE EVACUATION PROCEDURE ................................................................. 33
LOW STAGE EVACUATION PROCEDURE .................................................................. 34
Replacement of Low Stage Compressor........................................................................ 34
CHARGING METHODS................................................................................. 35
WEIGHT CHARGING of Low Pressure Refrigerants ..................................................... 35
Removing Refrigerant from Tanks.................................................................................. 37
Charging with High Pressure Refrigerants (2nd Stage) ................................................... 38
Pressure Charging of High Pressure Refrigerants ......................................................... 38
Weight Charging of High Pressure Refrigerants ............................................................ 40
Pentane Charging Procedure......................................................................................... 43
REFRIGERANT AND PENTANE QUANTITY BY MODEL ............................45
MODEL....................................................................................................................... 45
REFRIGERATION CIRCUIT EQUILLIBRIUM PRESSURES.........................46
Heat Exchanger Access and Replacement .................................................................... 47
REFRIGERATION SYSTEM REPAIR OVERVIEW ........................................................................ 48
Challenges for Low Temperature Refrigeration
The now famous Montreal Protocol for the control of Ozone Depleting substances has effected many of us in
one form or another.
The refrigeration industry has been especially affected, since many of the refrigerants available contain ozone
depleting substances such as chlorofluorocarbons (CFC) and hydrochlorofluorocarbons (HCFC). While
refrigerant manufacturers have been hard at work
producing alternatives for the mainstream
refrigeration systems, low temperature refrigeration has not
received quite the same amount of attention, possibly due to
the much smaller market.
Low temperature refrigeration refers to any
mechanical system which cools to temperatures between
–40 and –160 degrees centigrade. Although there are many
needs for temperatures this low, typical applications include
long term storage of rare tissue and organic
substances used in medical research as well as for product
stress testing.
To address these issues, Sanyo Electric Company in conjunction with ICI Chemical Corportation embarked on
an aggressive program to develop new refrigerants which do not produce harmful effects on the ozone layer,
while still providing long term reliability. To accomplish this many factors needed to be considered which
included the ability of the refrigerants to cool to extremely temperatures and the effect on the components in the
refrigeration system. Compounding this problem is the requirement for any new refrigerants to be used as a
replacement for systems still utilizing the older ozone depleting substances. This factor is especially important
in ultra-low temperature freezers due to the expense of the refrigerants and components involved. If too many
modifications are required to adapt to the new refrigerants, the cost of a change-over or repair could easily
exceed the cost of a new freezer. The result was a new ultra-low temperature refrigerant known as TP5R3,
which received recognition in North America in 1993 and is more commonly known here as R-508. As part of a
cascade refrigeration system, this refrigerant is capable of producing a refrigeration system which will maintain
temperatures below –86 degrees centigrade. R-508 is an HFC refrigerant which is non-flammable, non-toxic
and does not deplete the ozone layer and is expected to be one of the main alternative refrigerants well into the
next century. This refrigerant is currently being used with great success in many commercial products
throughout Canada and has been in use for the last 4 years.
Advancements to refrigeration technology has resulted in Sanyo being awarded the 1995 Stratospheric Ozone
Protection Award from the United States’ Environmental Protection Agency. Although HFC refrigerants are
today considered the solution to our current environmental concerns, more work needs to be done on the new
generation of refrigerants. Although HFC’s do not harm the ozone layer, they do contribute to global warming if
released into the atmosphere. Currently Sanyo is working on new technologies which utilize newly developed
hydrogen absorbing alloys which allow hydrogen to be used as a refrigerant. By continually developing new
techniques for refrigeration instead of depending on the old methods, we can help to protect our planet for
future generations.
The cascade refrigeration system is a unit consisting of two independent refrigeration circuits connected
through a heat exchanger. Following is a schematic diagram of a basic cascade system.
The system, where the heat exchanger serves as an evaporator, is called the high stage refrigeration system.
The other side, where the heat exchanger serves as a condenser is called the low stage refrigeration system.
In the operation of this system, the low stage is the refrigeration system that actually removes the heat
energy from the freezer chamber. This heat energy is transferred through the heat exchanger to the high
stage. It is then transferred to the ambient through the hi-stage condenser along with the other heat loads
created by friction and the heat of compression for both stages.
A cascade refrigeration system is required because the compression ratio required to allow the low stage
refrigerants to evaporate at very low temperatures and re condense at near ambient temperatures would
require a compressor which would not be practical.
By allowing the refrigerants in the low stage to condense at temperatures well below zero degrees through
the heat exchanger, the compression ratio created is well within the capable range of Sanyo's compressors
designed for ultra-low applications.
Capillary tubes are chosen as metering devices for their reliability at very low temperatures. The oil separator
is used on the low stage to remove as much oil as possible from the refrigerant before it is exposed to the low
temperature portion of the system. This is done to reduce the risk of blocking the metering device at the
extremely low temperatures at which these systems operate.
Sanyo Refrigeration System Cutaway
Component Layout – Chest Freezers
Sanyo Ultra Low Freezer Electrical System Operation
Most Sanyo ultra-low freezers are operated by one main control board. Currently , there are two main
board in use in existing freezers which are described later in this chapter. Although the boards are
vastly different in their designs, they both perform the same function of controlling the refrigeration
system to keep the freezer at set temperature.
The control board is designed to cycle the low stage compressor on demand for cooling. Before it can
do this however, the heat exchanger temperature (evaporator of the high stage) must be at the proper
temperature to avoid undue stress on the low stage compressor. All boards also incorporate a so
called ‘defrost’ feature to ensure that the freezer has an off cycle where the capillary tubes are heated
to remove any possible restrictions that may have built up over time.
When the heat exchanger cools down below -34 degrees centigrade, the temperature control board will apply
voltage to the temperature control relay. This will in turn apply power to the low stage compressor. The low stage
compressor will not start until the heat exchanger temperature drops below -34 degrees. This will protect the low
stage compressor from damage should the high stage system fail to cool for any reason. See page 44 and 45 for
specifics on monitoring and adjusting the heat exchanger temperature if required.
Electrical and Electronic Component Access
Access to refrigeration starting and electrical components is accessed by removing the four screws on the left
side panel on the compressor compartment.
To remove the front grill to access the condenser filter, remove the 2 thumb screws on the right side of the
front panel.
The micro control board is located behind the left control panel cover. To access the screws holding this panel,
the right front grill panel must be removed first.
Buzzer Key
When pressed, this switch will silence the audible alarm for several minutes, if the abnormality which caused
the alarm to sound has not been corrected, the audible alarm will automatically sound again.
Entry Key
Pressing this switch momentarily after the desired set point temperature has been set will store
the point in memory. This point will be maintained even in the event of a power failure.
Function of Keys
Buzzer Key (BUZZER) To stop the alarm from sounding, press this key. Should a further
abnormality occur, the buzzer will sound automatically.
Alarm Test Key (ALARM TEST) Check that the alarm lamp and the buzzer functional when the
deep freezer is operating well.
AIarm Set Key (ALARM SET) A key for setting alarm temperature. Pressing this key leads the
setting mode for high and low temperature alarm. Set a desired temperature by
using the shift key, and then press the set key. (see page 12)
Set Key (SET) Temperature setting mode will be led by pressing this key. The changeable digit
will be flashed. Press this key again after setting desired temperature, and temperature
setting will be stored.
Digit Shift Key ( H ) Pressing this key in the setting mode will cause the changeable digits to
move. Key lock will be caused by pressing this key when in the temperature
display mode. As for details, see page 11 "Key lock Function'
Numerical Value Shift Key Pressing this key in the setting mode will cause the numerical value
to move. ONOFF" of key lock can be selected by pressing this key
when in the Key Lock mode
Digital Temperature Indicator (TEMPERATURE (°C)) This indicator shows the present
temperature or setting temperature.
Filter Check Lamp (FILTER) This lamp lights when the condenser filter is clogged. Clean the
condenser filter.
Alarm Lamp (ALARM) This lamp will be flashed when the internal temperature will be
exceeded the alarm setting temperature, or at the time of power failure.
Battery,6VDC
VR1
VR2 VR1
VR2 Used to adjust the duration of the defrost ‘ON’ cycle. During defrost the
low stage compressor will be off and the capillary heaters will energize.
VR3 Used to adjust the temperature cut-in point where the low
stage compressor will start. Not adjusted under normal circumstances.
1
National Institute of Standards and Technology
13
Function Modes
The control boards used on the MDF-U6086S, MDF U70V, MDF U71V and the MDF U50V
can be calibrated and adjusted utilizing function modes. Function modes are adjusted via
the front panel and provide other useful purposes such as testing for proper operation and
making adjustments.
1.Press the ‘SET’ key on the front panel to get into set mode.
2. Press and hold the ‘ALARM SET’ key for about 5 seconds
3. ‘FO’ should appear in the display
4. use the ‘UP” key to get into the function mode required.
F2- used to change the status of the capillary heater during defrost
O=normal position, cap tube heaters come on during defrost
1= default position. Cap tube heaters will not come on.
F3- used to set the duration of time that the cap heaters will come on during
defrost. The range is between 0 and 10. The minimum duration is 6 minutes (0).
The maximum is 16 minutes (10). Each increment from zero represents 1 extra
minute. (i.e. A setting of 5 is a defrost of 11 minutes, 6+5=11). The adjustment is
made by adjusting pot VR2 on the control board while watching the display.
F4- zero adjustment of the display temperature. The range is between 00 and 60.
00 means that 3º will be added to the displayed temperature
60 means 3º will be subtracted from the display temperature
The preset value is 30 (neutral), set at the factory. The adjustment is made by
adjusting pot VR1 on the control board while watching the display.
i.e. The displayed temperature is –80º. The actual temperature is –82º. Make the
indicator read 50 while in F4 mode to add 2 degrees to the calibration.
F6- Displays chambers temperature in 1/10 of a degree. Used for fine calibration.
VR3 – used to adjust the temperature span when the freezer is at set temperature
14
Initiating a Defrost Cycle
A defrost cycle can be used to clear a possible restriction in a capillary tube. This should
be done before any refrigeration gauges are connected to the system.
2. Go to Function mode 2 (F2) , This mode is used to change the state of the capillary
heater. When you initially go into this mode, the display should read ‘0’, indicating a
normal defrost will take place. Change this to zero by using the ‘up arrow’ key on
the control panel. Then press ‘set’. You will have disabled the capillary tube cycle.
3. Go back into function mode ‘F2’, but this time change the ‘1’ back to a ‘0’and press
‘set’. When you do this, you will be setting the capillary heater back to default mode.
When this happens, the freezer should automatically go into a defrost cycle
immediately.
Control Board Switch Functions and Operation (all other ultra low models)
SW2- Press this switch to display the present temperature of the cascade condenser. 1. (This is
required when making adjustments using VR-3 described on the following page).
SW4- Press this switch to display chamber temperature in 0.1 degree increments on the front
panel L.E.D. temperature display.
SW5- Toggle this switch 'on' and then 'off' again to force the freezer into a defrost cycle. LED 1
will light indicating that the capillary tube heaters have been activated, and the low stage
compressor will turn off. Each time this switch is toggled, the defrost cycle will be extended
the equivalent of one defrost cycle time period.
SW6- Used for factory inspection, drives freezer to its coldest point. This
switch MUST be off under normal circumstances.
SW7- Model and Mode Setting Switch. This switch is used to allow the control board to adjust to
different models of freezers.
The switch is also used to tell the freezer whether there is
liquid CO2 back-up system connected to the freezer.
Important Note
Switch number 3 on SW7 MUST be switched to the on position if a
back-up system is installed on freezers using this type of control
board. Failure to do this will prevent the back-up system from
operating when it is called upon.
15
Voltage Test Points on the Microboard
This microboard has 5 different test points. When diagnosing problems with the microboard, use these test
points to aid in diagnosis of discrete component failure. All voltages are in DC values.
16
Refer to the circuit board layout diagram on the previous page for location of the trim pots
refereed to in the following chart.
Adjustments are only required when there is a difference between the actual measured
temperature in the chamber and the temperature displayed on the unit's control panel.
Temperature readings for calibration purposes should be taken using a N.I.S.T. traceable
thermometer, and should be taken from the center of the freezer chamber. The
temperature inside the freezer must be allowed to stabilize before adjustments can be
made accurately.
Thermocouples
Sanyo upright and chest freezers contain thermocouples to aid in diagnosis of refrigeration
problems.
17
Using a temperature meter that does not read t-type thermocouple probes will cause
erroneous reading which could lead to misdiagnosis of a potential problem.
L EVA OUT – indicates the outlet temperature of the low stage evaporator.
The following table provides test data on a typical freezer in a 30ºC ambient with no load
in the freezer.
Error codes
Error codes are in indication of a probe failure and will cause a freezer alarm. The
temperature display will indicate the error code which has occurred.
DEFROST TIMING
The following information specifies the timing for each model's 'defrost' cycle.
18
ON TIME- means that the freezer has entered a defrost cycle. During this cycle, the low
stage compressor will turn off and power will be supplied to the capillary tube
heaters.
OFF TIME- means that the freezer is allowed to operate under normal control.
All timing functions are electronic and located on the main temperature control board.
The capillary tube heater is used to heat the end of the low stage capillary tube during the 'defrost'
cycle. It can only be accessed by removing the heat exchanger access panel at the rear of the
freezer. If it is found necessary to test the operation of the heaters, the electrical leads to the
heaters can be accessed from the control board for testing resistance and operation. Individual
specifications are given for each heater on the table below, but in most cases, two or more heaters
are used connected in parallel. Therefore composite or total vales are also given for the purposes
of testing the circuit from the control board. Keep in mind that heater resistance with respect to
ground should always be approaching infinite for a properly operating heater.
For all freezer models, the composite resistance of each heater is 833Ω. The total
resistance where the capillary heaters plug into the control board is 416.5Ω due to the fact
that the heaters are connected in parallel.
When the temperature controller calls for cooling, the low stage compressor is not permitted to come on unless the heat
exchanger temperature is within a set temperature range. Initially, the low stage compressor will not start until the 'ON
POINT' temperature is reached. Once the low stage compressor is running, it will continue to remain on unless the 'OFF
POINT' temperature is reached, or the temperature controller shuts down the compressor indicating that setpoint
temperature has been reached.
19
MDF-U4086S -34 degrees centigrade -12 degrees centigrade
MDF-U5086W -34 degrees centigrade -12 degrees centigrade
MDF-U5186S -34 degrees centigrade -12 degrees centigrade
Sensor Specifications
This sensor is used as the main chamber temperature sensor in most sanyou Ultra-Low
freezers
ºC Ω ºC Ω ºC Ω ºC Ω
-160 35. 79 -110 56. 19 -60 76. 33 -10 96. 09
-150 39. 82 -100 60. 25 -50 80. 31 0 100. 0
-140 43. 87 -90 64. 30 -40 84. 27 10 103. 9
-130 48. 00 -80 68. 33 -30 88. 22 20 107. 8
-120 52. 11 -70 72. 33 -20 92. 16 30 116. 7
This sensor is used as the main heat exchanger sensor connected to the main control
board. It is also used as the high stage condenser sensor which is also connected to the
control board and is used to control the ‘ Check Filter’ light on the main display.
The check filter light is designed to illuminate at about 48ºC.
ºC KΩ ºC KΩ ºC KΩ ºC KΩ
-50 154. 5 -36 71. 80 -22 3S. 65 0 13. 29
-49 145. 9 -35 68. 15 -21 33. 99 5 10. 80
-48 137. 8 -34 64. 71 -20 32. 43 10 8. 84
-47 130. 2 -33 61. 48 -19 30. 92 15 7. 20
20
-46 123. 1 -32 58. 43 -18 29. S0 20 6. 0 1
-45 116. 5 -31 55. 55 -17 28. 14 25 S. 00
-44 110. 2 -30 52. 84 -16 26. 87 30 4. 17
-43 104. 4 -29 50. 23 -15 25. 65 35 3. S0
-42 98. 87 -28 47. 77 -14 24. 51 40 2. 96
-41 93. 70 -27 45. 45 -13 23. 42 45 2. 51
-40 88. 85 -26 43. 26 -12 22. 39 50 2. 13
-39 84. 18 -25 41. 19 -11 21. 41 SS 1. 82
-38 79. 80 -24 39. 24 -10 20. 48 60 1. 56
-37 75. 67 -23 37. 39 -5 16. 43 65 1. 35
Troubleshooting Guide
Possible Cause: -Dirty condenser filter or other obstruction of air flow through
compressor area. Clean filter or remove obstruction.
-Too much warm product has been put in the freezer at one time.
-Chamber door has been open for an extended period of time, or door s
not sealing properly against the gasket.
-Temperature controller requires calibration. See pages 43 to 46.
-Chamber Access Stopper is missing (located on side of freezer).
-Refrigeration System is malfunctioning. (See troubleshooting problems
11 & 121.
-Oil Logging due to overload. (see troubleshooting problem 11 &12).
CHAMBER NOT COOLING DOWN. BOTH HIGH AND LOW STAGE COMPRESSORS ARE RUNNING.
21
Possible Cause: - Low stage malfunction. See problem number 12.
CHAMBER NOT COOLING. LOW STAGE COMPRESSOR NOT RUNNING. COMPRESS ISWARM.
COMPRESSOR RECEIVING POWER.
FREEZER IS NOISY
Possible Cause: -Temperature sensor or cascade sensor are open or short circuit.
22
Possible Cause: -Refrigerant charge either too high or too low.
-Moisture is present in the refrigeration system.
-There is a refrigerant leak in the system. Without the low stage
operating, the cascade condenser should drop below -35 degrees
centigrade.
-Capillary tube is blocked or plugged, can be caused by low charge.
-High stage compressor or starting components are defective.
-Non-condensable gases (air, nitrogen etc..) are present in the refrigeration
system.
-The air cooled condenser is dirty.
Possible Cause: -Refrigerant or Pentane charge is either too high or too low.
-Moisture is present in the refrigeration system.
-Capillary tube is blocked or plugged. This can be caused by low
refrigerant charge.
-Defective oil separator or capillary tube heater open circuit or not
receiving power from control board.
-Non-condensable (air, nitrogen etc..) are present in the refrigeration
system.
-High stage refrigeration system is not functioning. See problem 11 .
HIGH STAGE
The high stage system is charged with either R-412A or R-407D. The usual symptoms for a loss of
refrigerant in the high stage include the inability of the heat exchanger to remove heat from the second
stage system. If symptoms indicate a loss of refrigerant, look for signs of oil around the accessible
refrigerant tubing. A large refrigerant leak will sometimes leave refrigerant oil residue at the location
where the leak occurred. Recover any remaining refrigerant from the high stage system, and
pressurize the system using an inert gas such as dry nitrogen. Do not allow the pressure to exceed
285 psi.
After pressurizing the system, remove the refrigeration gauges. Often a leak can occur at the service
valve access port, and connecting refrigeration gauges will eliminate the source of the leak. Use soap
bubbles to locate the source of the leak. It may be necessary to remove the heat exchanger cover and
insulation from the back of the freezer to access the remaining components if the leak cannot be easily
found. Use a mirror to check any points in the system which is not easily visible.
After the leak is repaired, it will be necessary to test for leaks again. You cannot assume that there will be
only one leak in the system.
LOW STAGE
The low stage system is charged with R-508. This refrigerant will not be picked up easily with an
electronic leak detector. If the symptoms indicate a leak, it will be necessary to recover the existing
23
refrigerant and pressurize the refrigeration system with dry nitrogen. Do not allow the pressure to
exceed 285 psi.
After pressurizing the system, remove the refrigeration gauges. Often a leak can occur at the service valve
access port, and connecting refrigeration gauges will eliminate the source of the leak. Use soap bubbles to
locate the source of the leak. It may be necessary to remove the heat exchanger cover and insulation from
the back of the freezer to access the remaining components if the leak cannot be easily found. Use a mirror
to check any points in the system which is not easily visible.
If the leak cannot be found, it will be necessary to divide the refrigeration piping into 4 parts, then
connecting a pressure gauge to each part, and pressurizing with dry nitrogen after pulling a vacuum on
each section. (Details follow later in this section).
After the leak is repaired, it will be necessary to test for leaks again. You cannot assume that there will be
only one leak in the system.
24
Leak Suspected in System?
Replace Replace
Capillary tube Capillary heater
25
TESTING FOR DIFFICULT TO LOCATE LEAKS ON THE LOW STAGE
1. If it has been determined that a gas leak is present and leak test procedures laid out
on the previous have been followed and leak cannot be located, recover the
remaining refrigerant.
2. Divide the refrigeration into three parts. Refer to figures 1 to 4 on the following pages
on where to make the cuts. Perform the tests one section at a time to avoid
unnecessary work.
4. Pull a vacuum on each section to remove any gas that could cause errors in the
following procedures. Some gases under pressure will mix with refrigerant oil and
cause the appearance of a leak when in fact, none exists.
5. Put a pressure gauge on each section, and pressurize with dry nitrogen to a pressure
not to exceed 285 psi. If using refrigeration gauges, it is recommended that the
standard colored hoses not be used. Many of these hoses will leak through the walls
of the hose under high pressure. On a small refrigeration system, this could cause the
appearance of a leak, where none exists. Special high pressure hoses, copper or
braided stainless hoses are recommended for this procedure.
6. Disconnect supply of nitrogen and note the pressure indicated on the gauge.
Leave for 1 day, and note if there is a pressure drop on the gauges. If a drop is noted,
re-test this section of the refrigeration system for signs of leakage.
NOTES:
- do not make cuts at existing braze joints. Make cuts at portions where rebrazing after
a repair will be easiest.
- After leak has been located, repeat leakage test before reconnecting the system. After
refrigeration system has been reconnected, the entire system must be leak tested
again to insure integrity.
26
Figure 1
27
Figure 2
28
Figure 3
29
Figure 4
30
PARTS REPLACEMENT WHEN A REFRIGERATION REPAIR IS
PERFORMED
The following chart will provide an indication of which parts should be repaired dependant upon the
diagnosis of the problem with the refrigeration system.
Both an acid test and an oil color test of the refrigerant oil should be performed whenever there is a
failure of the compressor for whatever reason. Acid test kits are available from your refrigeration
wholesaler. After taking a sample of the oil, compare it to the color chart on the following page to
determine its acceptance before proceeding to the acid test mixing procedure. A positive indication
on either test requires that the refrigeration system be flushed.
31
32
Procedure When All Refrigerant Has Escaped
A leak in the suction side of the refrigeration system where the gas has completely escaped can
allow ambient air and moisture to enter the refrigeration system. This will have a detrimental effect on
the refrigerant oil and the long term reliability on the refrigeration system. It is therefore
recommended that all components containing refrigerant oil as well as the filter/drier be replaced
whenever this condition occurs.
When all repairs have been completed and the refrigeration system has been recharged, the system
should be started up and operated for 24 hours to ensure that the freezer reaches setpoint
temperature. At this point the freezer should be turned off and allowed to warm up to room
temperature. The freezer should be restarted once again and tested to ensure that it reaches setpoint
temperature. Ideally this procedure should be repeated for a period of one week.
The following procedure outlines the proper method of performing a vacuum evacuation on
the components for the high stage and low stage refrigeration systems. Failure to follow this
procedure may lead to equipment failure due to the fact that non-condensable and moisture
may be left in the system following repair.
IMPORTANT NOTE: Vacuum must be pulled on the high stage refrigeration system for a
period of no less than three (3) hours regardless of the vacuum level. This will ensure the
effective removal of non condensables.
33
LOW STAGE EVACUATION PROCEDURE
Vacuum must be pulled on the low stage refrigeration system for a period of no less
than three (3) hours regardless of the Vacuum level. This will ensure the effective
removal of non-condensibles.
• Model MDF U3086S employs a sealed in-line expansion tank which does not require a
separate evacuation point.
When replacing the low stage compressor, it is important to note that the refrigerant from
both the high and low stages must be removed. This is due to the fact that the high stage
refrigerant loops through the oil cooling loop in the low stage compressor.
34
Failure to remove the low stage refrigerant when removing the low stage compressor can
result in future high stage system failure.
CHARGING METHODS
This method of charging works best with small charging tanks. An example of the charging tank is
pictured below. Although freezers can be charged directly from the main refrigerant cylinders, the
difference between the weight of the tank and the weight of the refrigerant charge required is often
large dependant upon the size of the supply tank. Therefore, measuring the charge accurately with
standard refrigeration scales is often difficult and can cause an over or under charge in the system.
The system pictured below utilizes two shut off valves with standard refrigeration access valves on
the end.
1. Connect a vacuum pump on VS2 of the small charging tank, connect VS1 to the
refrigerant cylinder containing the refrigerant you will be charging with. Ensuring that
all connections are air tight, open VS1 and VS2 and pull a vacuum for a minimum of
5 minutes, and close VS2.
2. Weigh the empty small charging tank on the refrigeration scales. Use scales which are
capable of accurately measuring to +/- 1.0g.
3. Weigh the refrigerant into the small charging tank at the specified weight of the unit
35
to be charged, +/- 5 g. ( example: if the small tank weighs 5OOg and the charge
required on the unit to be repaired is 490g, charge the cylinder to 990 g). Charge by
opening the valve on the main tank, when the desired amount of refrigerant has been
metered into the small tank, close the main tank valve and then close VS1.
4. Connect the small charging tank to the manifold gauge (see fig. 1)
36
6. Close MV1 and open VS2 on the small charging tank and slowly charge refrigerant to
the high stage refrigeration system by opening MV4 and charging through the suction
side.
Caution: Do not open VS1.
7. When no more refrigerant will flow into the system, run the high stage compressor to
pull in the rest of the remaining refrigerant. It may be necessary to heat up the small
charging tank to force out the rest of the remaining refrigerant.
8. When all of the refrigerant has entered the system, close MV4, MV2 and VS2.
9. Weigh the small charging cylinder again, if the weight is not the same as the cylinder
weighed when it was empty, some refrigerant remains in the tank. Reconnect the tank
to the manifold, evacuate the hoses and manifold with the vacuum pump and charge
the remaining refrigerant.
10. Pinch off the process stubs and braze shut, or close the access valves, whichever
applies. Always test for leaks on the process stubs or valves after closing.
R-412A
37
Charging with High Pressure Refrigerants (2nd Stage)
There are two methods of charging the low or 2nd stage refrigeration system. The system can
be charged by weight or pressure. When charging by pressure, it is important that the ambient
room temperature in the location where the freezer is being repaired is stable. Either method
will produce satisfactory results.
R-508
This method of charging is used to charge the low stage refrigeration system using R-508. The
diagram below assumes that the refrigerant will be metered into the refrigeration system using a
pressure method. To perform this procedure properly, the unit being repaired must be at a stable
ambient temperature.
Following the diagram pictured below, connect the components needed to evacuate and charge the
low stage refrigeration system. The pentane cylinder must be charged in advance with n-pentane with
the volume specific to the system being recharged. As mentioned previously, the Sanyo low stage
refrigeration systems require 3-point evacuation.
The connection points are:
1- Process tube on low stage compressor. (suction side).
2- Service valve on the expansion tank. (suction side).
3- Process tube on outlet pipe of the oil separator. (discharge side). Install a brazed access
valve at this point. The high pressures reached when the compressor is running during
testing are too high for a process tube adapter.
38
Vacuum Procedure
1. Open all valves on the 4-way refrigeration manifold fully and evacuate the refrigeration
system to 200 millitorres. Ensure that the vacuum will hold at 200 millitorres by closing
the shut off valve to the vacuum pump. Once the proper vacuum has been obtained,
close MV3.
Charging Procedure
2. Charge the system with n-pentane first by opening valve VS2 on the pentane cylinder.
Once the pentane has been pulled into the refrigeration system, close VS2.
NOTES: It is important to charge with pentane first since pressures created by the
refrigerant would make it difficult to allow the pentane to flow into the refrigeration
system.
It is important that the hose connecting the pentane cylinder to the t-connection not
form a u-trap which could trap some of the pentane.
3. Determine the charging pressure for the R-508 by referring to the table: 'CONVERSION
TABLE FOR TEMPERATURE-PRESSURE OF R-508'
This table provides specific charging information by model number at different ambient
temperatures. Please note that it is very important that the freezer temperature be at
ambient for proper charging to occur.
4. Open MV2 and slowly charge the refrigeration system from the R-508 supply through
MV4. As the proper charge pressure is approached, close MV2 and watch the pressures
39
on the gauges GL and GH. When the pressures on both gauges equalize, slowly meter
refrigerant into the system in small amounts by opening MV2. Allow to equalize, and
continue to perform this process until proper charge pressure has been obtained. Allow
system pressures to stabilize for a minimum of 5 minutes before proceeding.
5. Start up the freezer to pull in any refrigerants remaining in the lines. Monitor temperatures
and pressures to ensure that the freezer operates to proper pressure and temperature
specifications.
6. Once proper operation of the freezer has been assured, pinch off and cut process tube
connections. Braze the ends dosed as well. Close service valve to the expansion tank.
Ensure that the valve and the process stubs are leak free.
R-508
This method of charging is used to charge the low stage refrigeration system using R-508. The
diagram below assumes that the refrigerant will be metered to a smaller tank that is refillable and is
certified to withstand pressures above 1150psi. Barring this, the main cylinder can be weighed and the
refrigerant can be charged into the system directly.
1. As in the procedure for charging the high stage, pull a vacuum on the small pressure
vessel, for at least 5 minutes.
2. Charge the R-508 into the smaller cylinder to the specified weight for the unit being
repaired +/- 5 grams. The refrigerant should be weighed in as per FIG. 2. Connect the
two tanks using a looped capillary tube fixed to a stand so that movements will not
affect the weight registered on the digital scale.
40
3. Ensuring that there is no air in the capillary tube, open the valve on the main R-508
cylinder and adjust the pressure regulator to a secondary pressure of 30 to 40 psi.
4. Open the valve on the smaller tank, and slowly charge it to the desired volume. Adjust
the pressure gauge secondary pressure to obtain the desired weight in the secondary
tank. Once the weight has been achieved, close the main valve on both tanks, starting
with the main tank.
5. Connect the small charging tank to the manifold gauge (see fig. 3).
7. Close MV 1 and charge the system first with n-pentane first by opening valve VP on the
pentane cylinder and opening MV4 to charge through the suction side. Once the
pentane has been pulled into the refrigeration system, close VP.
NOTE: It is important to charge with the pentane first since pressures created by the
refrigerant would make it difficult to allow the pentane to flow into the refrigeration
system. It is also important that the hose connecting the pentane cylinder to the t
connector not form a u-trap which could trap some of the refrigerant.
41
8. Open the valve on the small charging tank and slowly charge refrigerant to the low
stage refrigeration system through the suction side.( A pressure regulator should be
used here as well to charge the system.
9. When no more refrigerant will flow into the system, run the low stage compressor to
pull in the rest of the remaining refrigerant. It may be necessary to heat up the small
charging tank to force out the rest of the remaining refrigerant.
10. When all the refrigerant has entered the system, close MV4, MV2 and the tank valve.
11. Weigh the small charging cylinder again, if the weight is not the same as the cylinder weighed
when it was empty, some refrigerant remains in the tank. Reconnect the tank to the manifold,
evacuate the hoses and manifold with the vacuum pump and charge the remaining refrigerant.
12. Pinch off the process stubs and braze shut, or close the access valves,
whichever applies. Always test for leaks on the process stubs or valves after closing.
42
CONVERSION TABLE FOR TEMPERATURE VS. PRESSURE FOR R-508
MDF-292
76 MDF-392
MDF-492
71 MDF-592
PRESSURE (psia)
MDF-792
66
MDF-U3086S
MDF-U4086S
61
MDF-U5086W
56 MDF-U5186S
MDF-U6086S
51 MDF-U70v
46
0 5 10 15 20 25 30 35
M D F-292 54 56.1 58.4 60.4 62.5 64.6 66.7 69
58 59.9 62 64.1 66.2 68.3 70.4 72.5 TEMP. (C)
M D F-392
M D F-492 55.3 57.9 60.5 63.1 65.5 68.2 70.7 73.1
M D F-592 57.5 60.1 62.7 65.3 67.9 70.5 73.1 75.7
M D F-792 58.5 61.1 63.7 66.3 68.9 71.5 74.1 76.4
M D F-U 3086S 54.8 56.8 58.9 60.9 63 65.1 67.2 69.3
M D F-U 4086S 50.5 53 55.5 58 60.5 63 65.5 68
M D F-U 5086W 49.7 52.6 55.5 58.4 61.3 64.4 67.3 69.8
M D F-U 5186S 47.7 49.5 51.1 53 54.7 56.5 58.3 60
This method of charging works best with a medium sized mist infuser so that it can be used several times
without purging or recharging, yet is small enough to allow for accurate charging. An example of the mist
infuser used as a charging cylinder is pictured below.
The system pictured below utilizes two shut off valves with standard refrigeration access fittings on the VS2
and VS1 valves.
1. Referring to the diagram pictured below. Connect a vacuum pump on VS2 of the small charging
cylinder through a refrigeration manifold. Connect VS1 to a fresh dryer. Ensure that all connections
are air tight.
43
When charging with pentane, keep exposure to the atmosphere as short as possible. Any moisture
that has been absorbed by the pentane must be removed with a dryer during the charging process.
PENTANE IS FLAMMABLE AND VOLATILE. DO NOT HANDLE AT TEMPERATURES ABOVE
30 DEGREES CENTIGRADE. USE IN A WELL VENTILATED AREA NOT NEAR OPEN
FLAMES.
1. Make sure that the mist infuser is held in the upright position and that the line
connected to the vacuum pump is connected to the top of the mist infuser to avoid
pulling liquid pentane into the vacuum pump.
2. Note the amount of pentane required for the unit being recharged on the chart on page
72.
3. Insert the flexible hose into the bottle of n-Pentane. Start the vacuum pump and open
MV3,MV4,VS1 and VS2 in this order. The pentane will begin being pulled into the mist
infuser through the drier. Regulate the flow of pentane using VS1 and VS2 until the
proper level has been obtained in the mist infuser. Close VS2,VS1,MV4 and MV3 and
shut off the vacuum pump.
4. Follow the Low Stage Charging procedure to meter the pentane into the refrigeration
system.
44
REFRIGERANT AND PENTANE QUANTITY BY MODEL
2
Recommend HPLC Grade of Pentane
3
1cc is equivalent to 1ml of measure
4
This column is used if the Sanyo Custom Charging Cylinder is used which is available from Sanyo Scientific.
5
Some older designs may show 508g on the serial number plate, correct charge for this model is 545g.
45
REFRIGERATION CIRCUIT EQUILLIBRIUM PRESSURES
46
Heat Exchanger Access and Replacement
Procedure:
47
10. Remove all traces of the old silicone seal from around the panel and back of the
freezer.
11. Replace the access panel with screws and seal with RTV silicone. Ensure that the
seal is complete and air tight. Any leaks can cause a reduction of performance
and eventual failure.
3. Replace gas in system with dry nitrogen. This will help prevent a layer of oxidation from
building up in the refrigeration piping, as well as the carbonization of refrigerant oil
caused by heating during the brazing process.
6. Vacuum evacuation. Perform 3 point evacuation. One point on discharge and two
points on suction side of the refrigeration system. (for most models)
7. Charge with refrigerant and sweeping agent where necessary through the suction side.
B. Pinch off and braze closed process tubes. Check for leaks.
OR
Close access valves and seal. Check for leaks. Which ever is applicable.
48
Substitute Refrigerant
for
Sanyo would like to announce that the following solutions may help in cases where the
SANYO standard refrigerants is not readily available.
49
2. For ICI R-407D Refrigerant Used in High Stage.
Note-2 : Sanyo standard ICI R-407D is produced under license of Matsushita Electric
Industrial Co., Ltd.. Therefore, the approval of Matsushita Electric Co., Ltd. is
required before blending this refrigerant.
50