You are on page 1of 4

FORMS INDEX

LIST OF ATTACHED FORMS

No. Form No. Rev. Description


1. ITP - 931 2 GENERATOR CIRCUIT BREAKER

LIST OF REFERENCED FORMS

No. Form No. Doc. Ref. Description


STANDARD INSPECTION AND TEST PLAN Document No:
47400320T97503
ITP No: 931 Date:13.01.2009
GENERATOR CIRCUIT BREAKER Rev.No:2
Page: 2
PROJECT NAME: ZWITINA POWER PLANT PROJECT NO:740032 DRAWING NO/ISO NO: OTHER REFERENCES:

MAIN ACTIVITY NAME: EQUIPMENT NO: UNIQUE ID:

Activity Activity Inspection/Test Reference Document Inspection and Acceptance Initials/Stamp and Date Report
No. Description Requirements ENKA TEKNİK QC. Client GECOL/ACES Co. Rep. Reference No.:
931-1 Visual and Dimensional Check - Paint Control • Outline Drawings * W W
- Name plate data check • IEEE C37.013 Section 6
- Accessories and quantities
- Proper location of
instrumentation control
- Verify compliance to
specification
- Dimensional Inspection

931-2 SF6 gas receiver test • IEEE C37.013 Section 6 * W W

931-3 Pressure tests • IEEE C37.013 Section 6 * W W

931- 4 Control and secondary wiring check tests • IEEE C37.013 Section 6 * W W

931- 5 Mechanical operation tests • IEEE C37.013 Section 6 * W W

931- 6 Timing tests • IEEE C37.013 Section 6 * W W

931- 7 Stored energy system tests • IEEE C37.013 Section 6 * W W

931- 8 Power-frequency withstand voltage tests on major • IEEE C37.013 Section 6 * W W


insulation components

931- 9 Power-frequency withstand voltage tests on • IEEE C37.013 Section 6 * W W


control&secondary wiring

Sub -contractor QC Date & Signature /Stamp No. Enka Teknik QC Date & Signature /Stamp No. Client GECOL/ACES Co. Rep. Date & Signature / Stamp No.
STANDARD INSPECTION AND TEST PLAN Document No:
47400320T97503
ITP No: 931 Date:13.01.2009
GENERATOR CIRCUIT BREAKER Rev.No:2
Page: 3
931- 10 Leakage test • IEEE C37.013 Section 6 * W W

931- 11 Electrical resistance of current path tests • IEEE C37.013 Section 6 W W

931- 12 Resistor, heater and coil check test • IEEE C37.013 Section 6 W W

931- 13 Clearence and mechanical adjustment check tets • IEEE C37.013 Section 6 W W

931- 14 TYPE TESTS - Rated continuous current • IEEE C37.013 Section 6 * R R


carrying test
- Rated dielectric strength
- Out-of-phase switching
current tests
- Noise Level
- Transient Recovery
Voltage(TRV) test
- Short circuit current
rating
- Short circuit current with
delayed current zero
- Load current switch test
- EMC Test
- Mechanical endurance
Life Test

Note : Above mentioned tests shall be carried out by manufacturer.


Legend : S - Surveillance Inspection W - Witness Inspection Point H - Mandatory Hold Point For Inspection R - Record Review
* Report or Certificate to be provided.

Sub -contractor QC Date & Signature /Stamp No. Enka Teknik QC Date & Signature /Stamp No. Client GECOL/ACES Co. Rep. Date & Signature / Stamp No.