Professional Documents
Culture Documents
ABSTRACT: In metropolitan areas and highly populated cities the volume of sludge produced by wastewater
treatment plants is enormously high. Incineration of sludge is a common practice to reduce its volume, through
a burning process that converts it into ash. Still, a considerable amount of ash is produced, which creates
serious disposal problems. Attempts have been made to study the feasibility of using sludge ash as a substitute
for a portion of fine aggregates in concrete. The results indicate that it could be possible to replace up to 30%
by weight of fine aggregate by sludge ash in a concrete mix for normal practice.
Downloaded from ascelibrary.org by University of Southern Queensland on 09/17/17. Copyright ASCE. For personal use only; all rights reserved.
TABLE 3 Analysis of Heavy Metals, Chloride, Phosphate , and Sulfate for Ash Samples
TABLE 5. Mix Design for Concrete Specimens TABLE 8. Differential Scanning Calorimetry Test
Water Cement Sand Ash Stone % Ash" Heat rate U/g)
Ib/cu yd Ib/cu yd Ib/cu yd Ib/cu yd Ib/cu yd (1 ) (2)
Percent ash" (kN/m 3 ) (kN/m 3 ) (kN/m 3 ) (kN/m 3 ) (kN/m 3 ) o 17.25
(1) (2) (3) (4) (5) (6) 25 32.17
0" 250 500 1,380 0 1,900 30 78.73
( 1.4) (2.8) (7.9) (0) (10.9) 35 49.61
10 250 500 1,242 138 1,900 40 60.04
(1.4) (2.8) (7.1) (0.8) (10.9) 30
20 250 500 1.104 276 1.900 (vitrified ash) 18.39
(1.4) (2.8) (6.3) ( 1.6) (10.9) "% of fine aggregates.
30 250 500 966 414 1,900
(1.4) (2.8) (5.5) (2.4) (10.9)
"Percent of sand by weight replaced by ash. TABLE 9. Extraction Procedure (EP) Toxicity Analysis on
"Control sample. Sludge Ash
Composition Quantity EPA standard
TABLE 6. Test Results of Concrete Specimens (1 ) (2) (3) (4)
28-Day Ag mg/L <0.01 5.0
compressive As mg/L 0.160 5.0
strength Split tensile Bond Flexural Sa mg/L <0.2 100.0
Cd mg/L 0.06 1.0
psi strength psi strength psi strength psi
Cr mg/L «Ull 5.0
% Ash" (N/mm 2 ) (N/mm 2 ) (N/mm 2 ) (N/mm 2 )
Hg f.lg/L <0.2 200.0
(1 ) (2) (3) (4) (5) Pb mg/L <0.1 5.0
0" 4,225 467 1,047 645 Se mg/L <0.19 1.0
(28.5) (3.2) (7.2) (4.4) Pesticide
10 3,594 370 905 587 Lindane f.lg/L <0.5 400.0
(24.3) (2.5) (6.2) (4.0) Endrin f.lg/L <0.1 20.0
20 3,188 322 865 518 Methoxychlor f.lg/L <5.0 10,000.0
(21.9) (2.2) (5.9) (3.5) Toxaphene f.lg/L <10.0 500.0
30 3.299 344 817 548 Herbicide
(22.6) (2.3) (5.6) (3.7) 2,4, -D f.l/L <2.0 10,000.0
2,4,5-TP
"Percent of sand by weight replaced by ash.
(Silvex) f.lg/L <0.5 1.000.0
"Control sample.
TABLE 7. Results of Skid Resistance of Test on Concrete Slabs concrete slabs. Each slab had a different percent of sand
Skid Minimum replaced with ash while coarse aggregate, water content, and
Mix % Ash a resistance allowable cement remained unchanged and has the same quantities as
(1 ) (2) (3) (4) indicated in Table 5. The slabs were 0%, 25%. 30%. 35%,
I
and 40% ash replacement. The slabs were subjected to skid
0 60 55
2 25 59 55 resistance (ASTM E303) and differential scanning calo-
3 30 75 55 rimetry (Wendlandt 1986) tests. The results are shown in
4 35 60 55 Tables 7 and 8.
5 40 58 55
"% of fine ag![egate. COMMENT ON RESULTS
A review of Table 1 indicates that the particle size distri-
test was conducted on three specimens taken from the same bution of the ash sample resembles an aggregate comprised
batch. The results are shown in Table 6 and represent the approximately 60% sand and 40% silt. Comparing this par-
mean values for three samples derived from the same batch ticle distribution with ASTM C-33 requirements for fine ag-
and tested for the same parameter. gregate reveals that pure ash does not fall within the required
Based on the result of these concrete tests, a 30% replace- range for fine aggregate used in concrete mixes. Blending ash
ment of sand by ash was taken as the median point for the with normal sand and for a maximum of 30% by weight ash
JOURNAL OF ENVIRONMENTAL ENGINEERING / SE!PTEMBER 1995/635
TCLP Pesticides
Lindane fJog/L <10.0 400.0 parameters shown in Tables 3 and 4, sulfate and chloride
Heptachlor fJog/L <0.5 8.0 content of ash are of primary interest because of their po-
Heptachlor-Epoxide fJog/L <0.5 tential impact on the durability of concrete.
Endrin fJog/L <0.5 20.0
The concentration of sulfate in the pure ash barely reached
Methoxychlor fJog/L <100.0 10,000.0
Toxaphene j.Lg/L <10.0 500.0 1.5%. This concentration for an ash-concrete mix with 30%
Chlordane fJog/L <10.0 30.0 ash replacement falls below 0.15%. The impact of sulfates
TCLP Herbicides on concrete may be reduced through the use of Type 2 and
2,4 -D fJog/L <100.0 10,000.0 Type 5 cements in concrete.
2,4,5-TP (Silvex) fJog/L <10.0 1,000.0 Chloride ions have the ability to destroy the passive oxide
TCLP Semivolatiles
film on reinforcing bars, leading to corrosion of the bars. The
1,4-Dichlobenzene fJog/L <10.0 7,500.0
Hexachloroethane fJog/L <100.0 3,000.0
chloride ion concentration in the bulk ash concrete with 30%
1,2-Dichlorobenzene fJog/L <10.0 - ash replacement falls below 0.0015%, which is very small.
Nitrobenzene fJog/L <10.0 2,000.0 An item of interest in the TCLP test results is benzene.
Hexachlorobutadiene fJog/L <10.0 - The amount of benzene was found to be 45 ppb. Benzene
2,4 Dinitrotoluene fJog/L <10.0 130.0 should not be present at this quantity after the incineration
Hexachlorobenzene fJog/L <10.0 130.0 process since it is a volatile substance that should have been
2,4 ,6-Trichlorophenol fJog/L <10.0 2,000.0
Pentachlorophenol fJog/L <5.0 100,000.0
fully volatized or destroyed. The presence of the benzene
2-Methyphenol fJog/L <10.0 - could possibly be a result of contamination after the incin-
2,4,5-Trichlorophenol fJog/L <10.0 - eration process, either during collection or transport.
4-Methylphenol fJog/L <10.0 - As shown in Table 6, the average 28-day compressive strength
3-Methylphenol fJog/L <10.0 - for the control sample (i.e. 0% ash) was 4,225 psi (28.5 N/
Pyridine fJog/L <100.0 5,000.0 mm 2 ). The sample with 10% ash showed a 15% drop in com-
Vinyl Chloride j.Lg/L <10.0 200.0
l,l-Dichloroethene j.Lg/L <10.0 -
pressive strength. However, when the ash content increased
Chloroform j.Lg/L <10.0 6,000.0 from 10% to 30%, further drop in compressive strength was
1,2-Dichloroethene j.Lg/L <10.0 500.0 less than 7%. It is likely that the presence of finer than #200
Carbon Tetrachloride fJog/L <10.0 500.0 size material (which amounts to 38% for ash material alone
Trichloroethene fJog/L <10.0 - and to about 10% for the ash-sand composition in the con-
Benzene fJog/L 45.0 500.0 crete mix with 30% ash replacement) plays a significant role
Tetrachloroethene fJog/L <10.0 -
Chlorobenzene <10.0 100,000.0
in this reduction of strength. It should be noted, however,
fJog/L
2-Butanone (Mek) j.Lg/L <10.0 - that the compressive strengths of all four mixes were still
higher than the minimum design value of 3,000 psi (20 N/
mm 2 ).
The results of other tests are also tabulated in Table 6. For
replacement, however, can result in a product that falls within
the ASTM allowable range. This is shown in Fig. 1. each of these tests the ratio of the strength (for a particular
The other physical properties of ash, as tabulated in Table test) to its compressive strength remained fairly constant for
2, are as follows: all samples, including the control sample. These ratios are
Ash is an inorganic material. This is a result that was ex- 16% for flexural strength, 25% for bond strength, and 10%
pected because of the incineration process, which tends to for splitting tensile strength. The tensile strength of concrete
burn out all organic matters present in sludge cake. is relatively low, and it ranges between 0.1[: and 0.2t:·. It is
The fine material test covers determination of the amount more difficult to measure tensile strength than compressive
of material finer than a #200 (75 IJ-m) mesh by washing. Clay strength because of the gripping problems with testing ma-
particles and other aggregate particles that are dispersed by chines. For concrete members subjected to bending, the value
the wash water will be removed from the aggregate during of flexural strength rather than tensile splitting strength is
the test. There is no chance for ash with 40% fine material used in design. The flexural strength has a higher value than
as shown in Table 2 to be considered as a fine aggregate by the tensile splitting strength. The ACI specifies a minimum
itself. Blending it with sand, to an extent that reduces the value of 7.5 (f:.)1l5 for the flexural strength of normal-weight
fine material of the overall sand-ash composition to below concrete. A review of Table 5 indicates that the flexural strength
the standard limit, however, may give a suitable fine aggre- for all samples exceeds the minimum ACI requirement. Bond
gate for concrete. stress is primarily the result of the shear interlock between
The clay-lumps test covers the approximate determination the reinforcing bar and the adjacent concrete. It is described
of friable particles in aggregate. For usual aggregates the as a local shearing stress per unit area of the bar surface. This
value of this test directly indicates the amount of clay particles direct stress is transferred from the concrete to the bar in-
present. Our study shows that even though the ash material terface so as to change the tensile stress in the reinforcement
is free of organiz matter, it contains 44% clay lumps. The bar along its length.
presence of clay lumps will adversely affect the strength of A comparison of the results of the concrete containing 30%
636 / JOURNAL OF ENVIRONMENTAL ENGINEERING / SEPTEMBER 1995
0.05
t
I
~
If
0.00
".05
! 0.1 !
".10
Downloaded from ascelibrary.org by University of Southern Queensland on 09/17/17. Copyright ASCE. For personal use only; all rights reserved.
120.33°C
0.0 ...15
50 100 150 ZOO 250 300 0 50 100 150 ZOO 250 300
T-....-n(°C) Ttmperature (OC)
FIG. 2. DSC Test Result for No-Ash Concrete FIG. 5. DSC Test Result for 35% Ash Replacement Concrete
0.3
".1
".15 0.2
t ...20 IE
I
M.16°C
! 0.1
6O.04J/,
f ".25 I
! ! 0.0
".30
121.71°C
".1
".35 50 100 150 200 250 300
0 50 zoo 250
Ttmpentur'e (0C)
FIG. 3. DSC Test Result for 25% Ash Replacement Concrete FIG. 6. DSC Test Result for 40% Ash Replacement Concrete
0.18
0.1
0.16
0.0 91.3O°C
78.'73 J/I 0.14
I I 86.52°C
18.39 J/I
1.. 1 I O.U
r! f 0.10
!
! ".2
cc
0.08
129.29°C
0.06 0
50 150 ZOO 250 300
...3
0 50 100 150 200 250 300
Tempenture (0C)
FIG. 7. DSC Test Result for 30% Vltrlfled·Ash Replacement Con-
FIG. 4. DSC Test Result for 30% Ash Replacement Concrete crete
ash replacement with those of the control sample indicates tablished for this test, pavements that exhibit a skid-resistance
that the tensile, bond, and flexural strengths were reduced value above 55 are generally considered to be satisfactory.
to 74%, 78%, and 85% of the values for the control sample, Values of skid resistance above 65 are considered desirable,
respectively. fulfilling the requirements even of fast traffic and making it
The skid-resistance property of a pavement is of major most unlikely that the road will be the scene of repeated
concern for driver safety. The skid resistance tests were per- skidding accidents.
formed on 4 ft 0 in. x 4 ft 0 in. x 4 in. (1.2 m x 1.2 m x The results of the skid-resistance tests (Table 7) show an
10 cm) concrete slabs. The tests were conducted using a port- improvement in skid resistance for the sample with 30% ash
able British pendulum tester. According to the standards es- replacement compared to the control sample. All samples
JOURNAL OF ENVIRONMENTAL ENGINEERING / SEPTEMBER 1995/637
enclosed by the curve peaks can be related to heats of re- impact on ash concrete.
action, transition, polymerization, fusion, and so on. The type There is also no evidence of significant toxic leachate for
of phenomena happening to a sample under DSC testing may sludge ash and its concrete product. Various tests have been
be inferred by investigating the origins of the endothermic or carried out on fresh and hardened concrete. In all of these
exothermic curve peaks. DSC can be used as a control for tests it was found that the sludge ash was environmentally
comparing similar but not identical materials. In this study inert and could be used in concrete mix.
the DSC test was used to study the role of sludge ash in the At the present time it seems that legal impediments and
microstructure of concrete and its potential impact on the concerns over liability issues pose a far greater barrier to use
durability of the product. of ash residue as a construction material than any failure on
Figs. 2 - 7 and Table 8 show the results of DSC tests ana- the part of the engineering society to devise the technologies
lyzing the durability of the concrete samples. It can be seen needed to make utilization of ash and its secondary products
that the rate of heat [in terms of joules per gram (jIg)] that environmentally acceptable. This is a rapidly evolving tech-
is absorbed by the ash-containing samples is higher than the nology that neither the regulatory structure nor public per-
rate of heat absorbed by the control no-ash sample. All tran- ception has yet caught up with. To a considerable degree,
sitions occurred at a temperature less than lOO°C, implying acceptance of this technology depends, and will depend, on
that transitions were not in the form of structural deforma- local and national attitudes toward interest and investment
tion. One explanation could be that transitions occurred due in testing and development of our knowledge of ash, as well
to a change of phase of the water entrapped in the ash skel- as on the presence of clear federal guidance and comprehen-
eton. The water content of ash prior to mixing was found to sive regulatory measures.
be 28%. As determined through physical analysis, the high
water content of the fine ash grains may lead one to the ACKNOWLEDGMENTS
conclusion that the ash concrete still contains some of the This study was funded by the Suffolk County Department of Public
original ash moisture, which did not yet get a chance to con- Works and the State Energy Research and Development Authority in
tact and react directly with cement. cooperation with the Research Foundation of the City University of New
In an attempt to eliminate the entrapped pore water, a York under grant No. 776167.
concrete mix similar to the one with 30% ash replacement
was prepared using vitrified ash. The DSC result for this APPENDIX. REFERENCES
sample containing vitrified ash, however, remained almost Breslin. V. T., Roethel, F. J., and Schaeperkoetter. V. P. (1988). "Phys-
the same as the one for the control no-ash sample, supporting ical and chemical interactions of stabilized incineration residue with
the idea that the excess absorbed heat rate in the DSC test the marine environment." Marine Pollution Bull.• 19(11B), 628-632.
for ash mixed samples could have been exerted for a phase Duedall. I. W.• and Woodhead. P. J. M. (1983). "Coal waste artificial
reef program: Conscience Bay studies." Rep.• EPRI. Palo Alto. Calif.
change of the pore water entrapped in the ash-concrete, which Koppelman. L. E .. and Tanenbaum, E. G. (1993). "A summary of the
originated from the relatively high original water content of findings. conclusions and recommendations of phase I of the Long
ash prior to mixing. The entrapped water in the pores will Island ash management study." Rep.. Long Island Regional Ping.
adversely affect the durability and strength of concrete. Board. Hauppauge, N.Y.
Schubel. J. R .• and Neal. H. A. (1985). "Results and conclusions of the
municipal solid waste policy forum." Rep.. SUNY at Stony Brook,
CONCLUSION N.Y.
Shieh. C. S" and Roethel. F. J. (1989). "Physical and chemical behaviour
The 28-day compressive strength of concrete decreases as of stabilized sewage sludge blocks in seawater." Envir. Sci. & Technol.,
the percentage of sludge ash in the mix increases. However, Vol. 23. 122 - 125.
the design strength is still attainable for up to 30% (by weight) Tay. J. H. (1987). "Sludge ash as filler for portland cement concrete."
ash replacement. Under this condition, although the strength J. En vir. Engrg.• ASCE. 113(2). 345 - 351.
of concrete is found to drop 20% when compared to the Tay. J. H .• and Yip. W. K. (1989). "Sludge ash as lightweight concrete
material." J. Envir. Engrg., ASCE. 115( 1). 56 - 64.
control no-ash mix, the ash-concrete still satisfies the ACI Wendlandt, W. W. (1986). Thermal analysis, 3rd Ed .• Wiley Intersci-
design requirements. The presence of clay lumps in ash may ence. New York. N.Y.
have contributed to the reduction in compressive strength. Woodhead, P. J. M.. and Parker. J. H. (1985). "Biological colonization
Ash is a water-absorbent material but, unlike plastic soils, it of a coal-ash artificial reef." Wastes in the Oc.• Vol. 4.