Time Inverse Overcurrent Relay

Model CONS
Con Value Con Description
2 THR, current threshold (pu sbase)
0.15 T0, zero current reset time (sec.)
3.57 CUR1, lowest operating current (multiple of pickup)
1 T1, time to close relay (sec.)
0 CUR2, second current point (multiple of pickup)
0 T2, time to close relay (sec.)
0 CUR3, third current point (multiple of pickup)
0 T3, time to close relay (sec.)
0 CUR4, fourth current point (multiple of pickup)
0 T4, time to close relay (sec.)
0 CUR5, largest (saturation) current (multiple of pickup)
0 T5, time to close relay (sec.)
0 TB, breaker time (sec.)
0 FRAC, fraction of load to shed

IBUS, ’TIOCR1’, JBUS, ID, RS, ICON(M) to ICON(M


vercurrent Relay

Model ICONS
ICon Value ICon Description
0 FLAG, monitor/trip flag (0=monitor only,1=monitor & trip)
0 LBUS, bus number for load shedding
'0' LDID, load id for load shedding
220141 IBUS1, first transfer trip: from bus number
220137 JBUS1, first transfer trip: to bus number
'1' CKT1, first transfer trip: circuit id
220141 IBUS2, second transfer trip: from bus number
220138 JBUS2, second transfer trip: to bus number
'1' CKT2, second transfer trip: circuit id
220141 IBUS3, third transfer trip: from bus number
220139 JBUS3, third transfer trip: to bus number
'1' CKT3, third transfer trip: circuit id

, ID, RS, ICON(M) to ICON(M+11), CON(J) to CON(J+13) /


Enter New Values
Con Value Con Description
here
0.8 V1, first voltage-based load shed point (pu volt) 0.8
1 TV1, first voltage-based point pickup time (sec) 1.5
0.2 FV1, first fraction of voltage-based load shed 1
0.8 V2, second voltage-based load shed point (pu volt) 0
1.5 TV2, second voltage-based point pickup time (sec) 0
0.2 FV2, second fraction of voltage-based load shed 0
0.8 V3, third voltage-based load shed point (pu volt) 0
2 TV3, third voltage-based point pickup time (sec) 0
0.2 FV3, third fraction of voltage-based load shed 0
0.1 TVB, voltage-based breaker time (sec.) 0.06
48.4 F1, first frequency-based load shed point (Hz) 49
0.2 TF1, first frequency-based point pickup time (sec.) 0.15
0.96 FF1, first fraction of frequency-based load shed 0.242
0 F2, second frequency-based load shed point (Hz) 0
0 TF2, second frequency-based point pickup time (sec.) 0
0 FF2, second fraction of frequency-based load shed 0
0 F3, third frequency-based load shed point (Hz) 0
0 TF2, third frequency-based point pickup time (sec.) 0
0 FF2, third fraction of frequency-based load shed 0
0.1 TFB, frequency-based breaker time (sec.) 0.06
Script in dyr file:
Example:
240277 'USRLOD' * 'UVUFBLU1' 13 1 1 20 0 7 18 24027
0.80000 1.0000 0.20000 0.80000 1.5000
0.20000 0.80000 2.0000 0.20000 0.10000
48.400 0.20000 0.96000 0.0000 0.0000
0.0000 0.0000 0.0000 0.0000 0.10000 /

Input Data:
Enter Bus Number: 103001
Bus to be Monitored 10301

Code:
103001 'USRLOD' * 'UVUFBLU1' 13 1 1 20 0 7 18 10301
0.8 1.5 1 0 0
0 0 0 0 0.06
49 0.15 0.242 0 0
0 0 0 0 0.06 /