Professional Documents
Culture Documents
1) IR test
2) Turns Ratio
3) Vector Group
1) 1U2N + 2N1V =1U1V, 30.05+389.1=409.6
2) 1W2V>1W2W , 403.9>379.0
3) 1V2V=1V2W, 382.0=380.5
1
5) Winding Resistance test (ohm)
a)(HV side)
Tap-5
Tap-17
2
Magnetising current LV side
R- phase
3
2 0.135 0.215 0.179 0.179
5 0.338 0.215 0.171 0.171
10 0.675 0.215 0.168 0.168
b) Transformer Winding
1. HV/LV (UST)
4. LV/HV (UST)
4
Transformer -2
Transformer -1
2) IR test
3) Turns Ratio
5
14 17.615 -0.136 17.615 -0.163 17.615 -0.163
15 17.363 -0.186 17.362 -0.191 17.363 -0.186
16 17.111 -0.209 17.112 -0.203 17.113 -0.197
17 16.861 -0.221 16.862 -0.215 16.863 -0.209
4) Vector Group
4) 1U2N + 2N1V =1U1V, 30.05+389.1=409.6
5) 1W2V>1W2W , 403.9>379.0
6) 1V2V=1V2W, 382.0=380.5
Tap-5
6
1V-1W 411 6.1 71.9
1W-1V 409 6.1 71.9
Tap-17
R- phase
7
Vtg(kV) Leakage crt(mA) Capacitance(nF) tandelta pf
2 0.13472 0.213 0.266 0.26
5 0.335 0.213 0.241 0.24
10 0.669 0.213 0.254 0.25
Y-phase
d) Transformer Winding
7. HV/LV (UST)
8
Vtg(kV) Leakage crt(mA) Capacitance(nF) tandelta pf
2 8.24 13.25 0.289 0.289
5 20.92 13.23 0.285 0.285
10 42.32 13.46 0.287 0.287