Professional Documents
Culture Documents
EML Manual (2019 2023)
EML Manual (2019 2023)
Laboratory Manual
Submitted To:
Submitted By:
Name: ___________________________________
Roll No:__________________________________
BS Electrical Engineering
Session (2019-2023)
1
List of Experiments
EXP # EXPERIMENT TITLE
2
EXPERIMENT NO. 1
OBJECTIVES
To measure following parameters at no-load:
(1) Iron or magnetic losses
(2) No-load power factor
(3) No-load current
(4) No-load R, X and Z
APPARATUS
(1) Single phase transformer (1KVA)
(2) Wattmeter
(3) Voltmeter
(4) Ampere meter
(5) Connecting leads
THEORY REFRESHER
From this test we can determine core losses or no -load losses and no-load current (Io) of the
transformer. Low voltage winding is kept open and high voltage winding is supplied by its
normal rated voltage and frequency. A voltmeter, wattmeter and ammeter are connected in high
voltage winding i.e. Primary winding in this case. As the secondary side of the transformer is left
open-circuited, so only a small amount of current will flow only in the primary side i.e.(Io), and
the wattmeter will indicate no-load power (Wo) i.e. Core losses or iron losses. As the value of (Io)
being very small as compared to the rated value of current so Cu. losses being proportional to
2
(I ) will be neglected. No load current is only (2---10%) of rated load current. From the
observations of Io, Wo and voltage, we can find other quantities by calculations as follows:
Wo = V Io Cosφo
Cosφo = Wo / V Io (No -load p.f.)
-1
φo = Cos (Wo / V Io) (angle)
(Iw) Iron loss component of (Io) = Io Cosφo
(Iμ) Magnetizing component of (Io) = Io Sinφo
no-load reactance (Xo) = V/ Iμ
no-load resistance (Ro) = V/ Iw
2 2
and, no-load impedance (Zo) = √ (Ro) + (Xo)
1.6
Hysteresis loss = Ph = K (Bmax) f v (Watts)
2 3
Bmax = maximum flux density (wb/m ), f = frequency (Hz), v = Volume (m )
K = Constant depending on type of transformer and material of the core.
2 2 2
Eddy current loss = Pe=K (Bmax) f t (watts), t = Thickness of core
3
PROCEDURE
1. Arrange the circuit as shown in the Figure-1.
2. Connect a voltmeter, an ammeter and a wattmeter to the primary side as shown in the
Figure-1.
Wattmeter
C.C
P.C
AC Input
50 Hz V V E2 = V2
Auto
transformer
Figure-1
4
TABLE 1
S.No V Wo Io Cos o o Iw Iμ Ro Xo Zo
(V) (W) (A) (A) (A) (Ω) (Ω) (Ω)
5
What do you observe from the graph drawn?
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
6
EXPERIMENT NO. 2
OBJECTIVES
To measure following parameters of a transformer at short-circuit:
(1) Copper losses
(2) Short-circuit power factor
(3) Short-circuit voltage
(4) Equivalent resistance referred to primary side (R01)
(5) Equivalent reactance referred to primary side (X01)
(6) Equivalent impedance referred to primary side (Z01)
APPARATUS
(1) Single phase transformer (1KVA)
(2) Wattmeter
(3) Voltmeter
(4) Ampere meter
(5) Connecting leads
THEORY REFRESHER
From this test we can determine the copper losses of the transformer at desired load.
In the schematic diagram for this test the low voltage winding (secondary side) is short circuited
with the help of an ammeter or by a heavy conductor. Instruments are placed on High Voltage
side (primary side) of the transformer. While performing this test voltage are adjusted from zero
until the ammeter indicates the desired value of load current at which losses are to be measured.
The voltage applied for full load copper losses are only 5 to 10% of the normal rated value. As
the voltage value is very low, so the iron losses being proportional to the voltage can be
neglected, and wattmeter will indicate the copper losses of the transformer at desired value of the
2
load current. Copper losses will be directly proportional to I .
From this method following quantities will be determined:
Wc = Cu. losses
Eq. Impedance of transformer as referred to primary side Z01 = Vs / Is.
7
PROCEDURE
C.C
P.C
AC Input V A
Figure-1
3. Increase input voltage (Vs) gradually from zero volts to V at primary (HV side)
until current Is flows in the ammeters.
4. Measure and record current (IS) in Table-1.
5. Measure input power (Wc) with wattmeter. As maximum current flows in secondary side
at very low applied voltage (2-5 % of rated voltage), therefore iron losses which depends
on voltage will be negligible and wattmeter will measure only copper losses.
6. Calculate for the rest of the columns in Table-1.
7. Apply voltage V as given in Table-1 and repeat steps 4, 5 and 6.
8. Apply voltage V and repeat steps 4, 5 and 6.
9. Apply voltage V and repeat steps 4, 5 and 6.
10. Apply voltage V and repeat steps 4, 5 and 6.
11. Plot a graph between current Is and copper losses (Wc).
8
Table-1
Wc
IS
9
What do you observe from the graph drawn?
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
10
EXPERIMENT NO. 3
To Perform Efficiency Test of a single phase transformer
OBJECTIVES
To measure the efficiency of a transformer at RL load.
APPARATUS
11
PROCEDURE
1. Connect the circuit as shown in Figue-1.
2. Connect voltmeter, ammeter and wattmeter to the primary (HV side) and voltmeter,
ammeter and load to the secondary (LV side) as shown in Figure-1 and get the
connection checked from the instructor.
Digital Load
C.C Watt Meter
A A
P.C
V
V W
Transformer
Figure-1
12
Table-1
13
What do you observe from the graph drawn?
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
What is the effect of increasing frequency, voltage and load on the efficiency of
transformer?
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
14
EXPERIMENT NO. 4
OBJECTIVES
To measure voltage regulation up/down of a single phase transformer at resistive loads.
APPARATUS
(1) Single phase transformer (1KVA)
(2) Voltmeters
(3) Ampere meters
(4) Variable resistive load
(5) Connecting leads
THEORY REFRESHER
When the secondary of a transformer is loaded, the secondary terminal voltage falls. This fall in
the voltage increases as p.f. decreases i.e. lagging. This fall in the secondary terminal voltage in
%age is called regulation of the transformer. It is usually expressed as a percentage of the
secondary no-load voltage (Es). The fall in the voltage is due to (1) resistance of the winding and
(2) reactance of the winding. The resistance drop is in phase with the current while reactance
drops lead the current.
For full load condition, voltage regulation is given by,
% age Voltage Regulation = {(Es - Vs) / Es} × 100
Typical values of voltage regulation of transformer at 0.9 p.f. lagging are 3% in small
transformers and (1…1.5%) in 50 KVA or larger transformers.
15
PROCEDURE
C.C
I1 I2
A A
P.C
AC Input
V1 V V2 V LOAD
Figure-1
4. Get your circuit checked from the instructor.
5. Increase input voltage gradually from zero volts up to 220 volts.
6. Put resistive load of 00 A (i.e. no load) on secondary side of the transformer.
7. Measure voltage on secondary side (VS) of the transformer. This voltage is Secondary no
load voltage (Es) as mentioned in Table-1 and would be the same for all loads.
8. Calculate voltage regulation of the transformer and write it down in
9. Table-1.
10. Put a resistive load of 2.25A i.e. increase input voltage gradually until a current of 2.25A
flows through the secondary side ammeter.
11. Note down the secondary no-load voltage as given in Table-1 and calculate the voltage
regulation.
12. Repeat the steps 7 and 8 for different resistive loads of 4.50A, 6.75A and 9.09A and
complete Table-1 accordingly.
13. Plot a graph between different load currents (IS) and voltage regulation.
16
Table-1
S.No Es Is Vs % age Voltage Regulation = {(Es -
(V) (A) (V) Vs) / Es} × 100
VR
IS
________________________________________________________________________
________________________________________________________________________
17
Define efficiency of a transformer?
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
18
EXPERIMENT NO. 5
To Perform Parallel Operation on Two 1-Phase Transformers
OBJECTIVES
To connect two 1-phase transformers in parallel for load sharing.
APPARATUS
(1) Two single phase transformer (1KVA)
(2) Wattmeter
(3) Voltmeter
(4) Ampere meter
(5) Connecting leads
(6) Variable resistive load
THEORY REFRESHER
(1) The voltage ratings (voltage levels of both primary & secondary) should be same.
(2) While connecting two or more transformers in parallel it is essential that
their terminals of similar polarities are connected together. There are some
additional definite conditions which should be satisfied in order to avoid any
local circulating current.
(3) The %age Z should be equal in magnitude and should have same X/R ratio.
(4) If transformers have different KVA ratings then their equivalent impedances
should be inversely proportional to the individual KVA rating.
Condition # 2 i.e. polarities should be same is absolutely essential otherwise
parallel operation with incorrect polarities will result in a dead short circuit.
PROCEDURE
1. Connect the two single phase transformers in parallel as shown in the Figure-1.
2. Connect the load as shown in the Figure-1.
3. While connecting in parallel, it should be kept in mind that the voltage
rating of both the transformers should be same.
19
4. Their terminals of same polarities must be connected together.
Figure-1
5. Connect ammeters on the secondary sides of both the transformers.
6. Vary the load and record the load current as well as individual secondary
current contributions from both the transformers and write them down in
Table-1.
7. Write down the conclusion of this experiment based on your observation.
Table-1
________________________________________________________________________
________________________________________________________________________
20
EXPERIMENT NO. 6
To Find & Plot Load – Speed Characteristics of a Shunt DC Motor
OBJECTIVES
To find load –speed characteristics, Back EMF and efficiency of a dc shunt motor.
APPARATUS
(1) D.C. shunt motor
(2.1 KW, 220 V, IA = 13 A, RF = 0.95 Ω A, RA = 1.8 Ω , 3500 r.p.m.)
(2) Voltmeter
(3) Ammeters
(4) Speed indicator
(5) Variable load
(6) Connecting leads
THEORY REFRESHER
A shunt motor is connected to power supply as shown below. The field windings are connected
in parallel (shunt) with the armature windings. The circuit for a shunt motor is shown in figure.
Once you adjust the speed of a dc shunt motor, the speed remains relatively constant even under
changing load conditions. One reason for this is that the field flux remains constant. A constant
voltage across the field makes the field independent of variations in the armature circuit. If the
load on the motor is increased, the motor tends to slow down.
The performance of a dc motor is judged from its characteristics or curves.
Speed – load characteristic is the curve between speed and armature current of a d.c. motor.
The speed of a d.c. motor is given by,
NαEb/Ф
N α (V – I a R a) / Ф
As flux is constant, therefore N α (V – I a R a)
As I a ↑, then I a Ra ↑, then (V-I a Ra) ↓, then N ↓ and hence N α 1/ I a
21
PROCEDURE
1. Arrange the circuit as shown in Figure-1.
Figure-1
2. Connect voltmeter and ammeter and load as shown in Figure-1 and get checked form
instructor.
3. Armature shafts of both the sets (dc motor and generator) are already connected by
coupling as shown in Figure-1.
4. Excite motor field first and then gradually increase motor armature voltage up to 220 V.
5. Now generator is mechanical load on the motor and motor will draw current from line.
6. Excite generator field gradually and it will generate voltage. Now increase resistive
load on generator such that the armature current of the motor is as mentioned in Table-
1. The generator will draw current. Note that generator’s load will be actually on the dc
motor. DO NOT increase current on generator beyond the rated current of dc motor.
7. The reading for no-load is already provided in Table-1. Calculate only the back e.m.f
and percentage efficiency of the motor.
8. For the next reading, increase the armature current to the value as given in Table-1.
9. Measure and record armature voltage (VA) and speed (N) of the motor for different
values of motor armature current (IA) by varying the load.
10. Calculate back e.m.f (Eb) and percentage efficiency of the motor in each case.
11. Plot the load characteristics of DC shunt motor.
22
Table-1
Sr # Va Vf Ia If N Eb=V-IaRa Pi Po η
Eb
Ia
________________________________________________________________________
________________________________________________________________________
23
What is back emf?
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
____________________________________________________________________________
___________________________________________________________________________
24
EXPERIMENT NO. 7
OBJECTIVES
To carry out speed control of DC Shunt Motor.
APPARATUS
(1) D.C. shunt motor
(2.1 KW, 220 V, IA = 13 A, RF = 0.95 Ω A, RA = 1.8 Ω, 3500 r.p.m.)
(2) Voltmeter
(3) Ammeters
(4) Speed indicator
(5) Connecting leads
THEORY REFRESHER
Armature Voltage Control:
In this exercise the field winding current is kept constant. The voltage applied is changed but the field
winding current also changes so to make it constant the Shunt Regulator resistance is changed to keep
it constant.
Field Winding Current Control:
For field winding control method, the field current is changed by varying the Shunt Regulator
added in series with the field winding and the milli ampere meter. The field current is changed
from 0 A to the some value where the speed changes with respect the current values.
PROCEDURE
Figure-1
25
1. Connect the circuit of a shunt motor as shown in Figure 1.
2. Increase the applied voltage so that speed is nearly 1400 rpm.
3. Start increasing the applied voltage from the PSU (power supply unit) which will increase the
applied armature voltage but will also increase the field current, so to make it constant change
the shunt regulator.
4. Take at least five readings at appropriate interval until the speed has nearly reached 3000 rpm.
5. Draw the graph with applied voltage on the x-axis and the speed on the y- axis.
6. In field winding control, adjust the applied voltage to the motor and then changes the field
current for varying the speed of the motor.
7. Take at least five readings with appropriate intervals.
Table-1
Armature Voltage Control
Sr No. Armature voltage Field Voltage Speed
Table-2
Field Voltage Control
Sr No. Armature voltage Field Voltage Speed
26
GRAPH BETWEEN SPEED & APPLIED VOLTAGE (For Armature Voltage Control)
GRAPH BETWEEN SPEED & APPLIED VOLTAGE (For Field Voltage Control)
27
What do you observe from the graph drawn?
____________________________________________________________________________
____________________________________________________________________________
___________________________________________________________________________
____________________________________________________________________________
___________________________________________________________________________
28
EXPERIMENT NO. 8
To find and plot Torque speed characteristics of a DC Series Motor
OBJECTIVES
APPARATUS
(1) D.C. series motor
(2) Voltmeter
(3) Ammeters
(4) Speed indicator
(5) Connecting leads
THEORY REFRESHER
The circuitry of this motor includes as armature in series with an inductive field winding. The
relationship between speed and torque for a dc series motor can be given
This relationship shows that a high torque is obtained at low speed and a low torque is obtained
at high speed. This is special characteristic feature of DC Series Motor. Due to this feature DC
Series Motor are used in such applications where large starting torque is required. It is also
notable in this motor that
This means that the toque in the motor is proportional to the square of its armature current. DC
Series Motor produces unidirectional torque both for AC and DC supply. Thus it is a universal
motor which can be operated both on DC as well as AC Supply. DC Series Motor has a
dangerously high starting current if it is directly connected to the DC Power Supply because of
very low emf at start. The starting current is limited either by inserting a resistance or by using a
low DC Terminal Voltage at start.
DC Series Motor has a very poor speed control as it is very slow for heavy load and fast for
lighter loads. If no load is applied, the motor may over speed and destroy itself. This feature
makes this motor unsafe for using with belts for a brake in belt may cause motor to be destroyed.
PROCEDURE
1. Connect the circuit as shown in the Figure-1
29
Figure-1
2. Set the applied DC voltage to a constant value from 80 to 220 V.
3. Varying the applied voltages and note the values of armature current and
speed. In this way at least observe the six readings.
4. Calculate the torque in N.M using the formula.
5. Draw the graph between speed and torque where speed will be on y-axis and
torque will be on x-axis.
Table 1
30
GRAPH BETWEEN TORQUE & SPEED
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
31
EXPERIMENT NO. 9
To find and plot magnetic Characteristics of a DC Shunt Generator
OBJECTIVES
To find magnetic characteristic of a dc shunt generator
APPARATUS
(1) D.C. shunt generator
(2) Voltmeter
(3) Ammeters
(4) Speed indicator
(5) Separate D.C. variable power supply unit
(6) Variable load
(7) Connecting leads
THEORY REFRESHER
A shunt generator is also called self excited generator as field is connected across the armature so
that armature voltage can supply the field current. Some residual magnetism must exist in the
magnetic circuit of the generator. Because of this residual magnetism small voltage appears
across the armature terminal even when the field current is disconnected.
On the connecting field, armature voltage increases which in turn increases the field current
which again builds up the voltage, so this process continues until a specific voltage is reached. In
actual cases, this build up follows approximately the magnetization curve. Field circuit resistance
is important for voltage stabilization. If the resistance slope coincides with somewhat linear
portion of the magnetization curve it results in unstable voltage situation. If resistance is greater
than this, build up is insignificant and for lower values of resistance, generator will build up
higher voltages. Shunt generator uses a field having suitable impedance across the armature such
that the armature voltage supplies the necessary field current, although in some cases, separate
external voltage may also be applied.
32
Thus speed varies inversely with field current. Speed also varies inversely with load and for load
T we have the following relation.
i.e
PROCEDURE
Figure-1
33
Table 1
Table 2
34
GRAPH BETWEEN GENERATED VOLATGE VS FIELD CURRENT
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
35
EXPERIMENT NO. 10
To find and plot the Load Characteristics of a DC Series Generator
OBJECTIVES
To find load characteristic of a dc series generator
APPARATUS
(1) D.C. series generator
(RSE=1Ω, RF = 0.95 Ω A, RA = 1.8 Ω)
(2) Voltmeter
(3) Ammeters
(4) Speed indicator
(5) Separate D.C. variable power supply unit
(6) Connecting leads
THEORY REFRESHER
In series generator, the field winding provides the flux in the machine when armature current
flows through it. Load characteristics are also termed as performance characteristics. It gives
relation between terminal voltage and the load current. This curve lie below the internal
characteristics curve because it takes into account the voltage drop over the armature circuit
resistance. The values of V are obtained by subtracting IaRa from corresponding values. This
characteristic is of great importance in judging suitability of a generator for a particular purpose.
It may be obtained by making simultaneous measurements with a suitable voltmeter and
ammeter on a loaded generator. This gives the relation between induced emf E. Actually induced
in the armature and the armature current Ia. DC series generator has rising voltage characteristics
i.e with increase in load its voltage is also increased. But at high loads, the voltage starts
decreasing due to extensive demagnetization of armature due to armature reaction. In fact
terminal voltage start decreasing as load current is increased.
36
PROCEDURE
Figure-1
Table 1
Sr. No. Load current Terminal voltage Induced Emf
IL Vt
1
2
3
4
5
6
37
GRAPH BETWEEN TERMINAL VOLATGE VS LOAD CURRENT
________________________________________________________________________
________________________________________________________________________
38
EXPERIMENT NO. 11
To Control the speed of Induction Motor by changing frequency
OBJECTIVES
APPARATUS
(1) Induction Motor (3 Hp,50 Hz,1430 rpm,4.9A,400/440v)
(2) Voltmeter
(3) Ammeters
(4) Speed indicator
(5) Connecting leads
THEORY REFRESHER
Having known the torque speed characteristic of the motor, its speed can be controlled in three
ways
1. Changing the number of poles
2. Varying the input voltage at fixed frequency
3. Varying both the input voltage and frequency accordingly
When a balanced set of three phase sinusoidal voltages is applied to the stator of an induction
motor, a constant amplitude flux is produced in the air gap which rotates with a constant speed
called the synchronous speed. For a p pole machine, the synchronous speed is given as
If we vary the supply frequency, we can change the speed of an induction motor.
Procedure
39
Table No.1
Frequency
Speed
________________________________________________________________________
________________________________________________________________________
40
What are the ways by which the speed of induction motor can be controlled?
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
41
EXPERIMENT NO. 12
To find and plot the characteristics of Synchronous Generator
OBJECTIVES
APPARATUS
THEORY REFRESHER
Synchronous generators are the majority source of commercial electrical energy. They are
commonly used to convert the mechanical power output of steam turbines, gas turbines,
reciprocating engines, hydro turbines and wind turbines into electrical power for the grid. They
are known as synchronous generators because f, the frequency of the induced voltage in the
stator (armature conductors) conventionally measured in hertz, is directly proportional to RPM,
the rotation rate of the rotor usually given in revolution per minute.
If the rotor windings are arranged in such a way as to produce the effect of more than two
magnetic poles, then each physical revolution of the rotor results in more magnetic poles moving
past the armature windings. Each passing of a North and South Pole corresponds to a complete
cycle of magnet field oscillation.
Procedure
42
Table 1
________________________________________________________________________
________________________________________________________________________
43