Professional Documents
Culture Documents
Apparatus required
Digital multi meter-----------------------------------2
Digital/Analog wattmeter--------------------------- 1
Single phase transformer --------------------------- 1
Variable ac power supply----------------------------1
DC power supply-------------------------------------1
Name Plate Details
H.V. side L.V. side
1. KVA : ______________ _____________
2. Voltage : ______________ _____________
3. Current : ______________ ______________
4. Frequency : ______________ ______________
Theoretical hints
The physical basis of the transformer is mutual induction between two circuits linked by a common
magnetic field. Transformer is required to pass electrical energy from one circuit to another, via the
medium of the pulsating magnetic field, as efficiently and economically as possible. This could be
achieved using either iron or steel which serves as a good permeable path for the mutual magnetic flux.
1
The practical transformer has coils of finite resistance. Also, all the flux produce by the primary current
cannot be confined into a desired path completely as an electric current. Though a greater proportion
links both the coils (mutual flux), a small proportion called the leakage flux links one or other winding,
but not both. It does not contribute to the transfer of energy from primary to secondary. On account of
the leakage flux, both the windings have a voltage drop which is due to ‘leakage reactance’.
To predict the performance of a transformer, the equivalent circuit shown can be used; and therefore all
the circuit parameters must be known. The equivalent circuit parameters are determined by performing
OC and SC tests.
Experiment – 1
Open circuit test – By performing the open circuit test, shunt branch parameters Xo and Ro can be
determined.
Procedure
1. Connect the circuit as shown in fig 2.1and see that vaiac is in minimum position.
2. Apply rated voltage to the LV winding by varying the variac.
3. Note down the readings of voltmeter (V1), ammeter (Io) and wattmeter (W) in table 2.1.
4. Disassemble the circuit and return everything to its previous posit
50
60
70
2
80
𝑉
No load loss component resistance, 𝑅𝑜 = 𝐼 1
𝑤
Experiment – 2
Short circuit test – By performing the short circuit test, load loss (copper loss) winding resistance and
leakage reactance are determined.
Procedure
1. Connect the circuit as shown in fig. 3. and keep the variac in minimum position.
2. Adjust the variac voltage such that rated current flows through the HV windings.
3. Note down the readings of voltmeter (Vsc) ammeter(I1sc and I2sc) and wattmeter (Wsc) in table 2.
4. Disassemble the circuit and return everything to its previous position.
𝑉
Total impedance referred to the H.V. side, 𝑍02 = 𝐼 𝑆𝐶
1𝑆𝐶
3
𝑃
Total resistance referred to the H.V. side,𝑅02 = 𝐼2𝑆𝐶
1𝑆𝐶
2 2
Total reactance referred to the HV side, 𝑋02 = √𝑍02 − 𝑅02
𝑅02 𝑋02
Therefore, total resistance and reactance referred to L.V. side (Primary side) 𝑅01 = 𝑎𝑛𝑑 𝑋01 =
𝐾2 𝐾2
𝑉
Where ‘k’ is transformation ratio and is given by 𝑉2 .
1
Questions to be answered
4
1. Which winding (LV or HV) should be kept open while conducting OC test? Justify your answer.
2. Assume that the transformer has the following name plate ratings: 40 kVA, 440 V/ 11 kV, 50 Hz.
what do these numbers imply?
3. Assume that you have been given a transformer manufactured for the supply voltage and
frequency 110 V and 60 Hz respectively. What voltage will you apply if this transformer is
to be used in this country? Justify your answer.
Results and conclusion: