Professional Documents
Culture Documents
Experiment 10
Aim:
1) To find the polarities of primary and secondary windings of a single-phase transformer by conducting
the polarity test.
2) To determine the rated iron loss, rated full load copper loss, and the equivalent circuit parameters of a
single-phase transformer by performing the Open-Circuit (OC) test and Short-Circuit (SC) test.
Procedure:
1) Connect the circuit as shown in Fig. 10.1.
2) Apply the rated voltage (i.e., V1 = 115 V) across primary winding of the transformer by varying the
output voltage of Variac and note down the readings of the three voltmeters.
If V3 = V1 + V2 then the transformer will have additive polarity, therefore mark P1 & S2 or P2 & S1 as dot
(•) polarities and if V3 = V1 ~ V2 then the transformer will have subtractive polarity, therefore mark P1 &
S1 or P2 & S2 as dot (•) polarities.
3) Reduce the variac output voltage to zero volts and then switch-off the supply.
Observation :
V1 = 114.5v
V2 = 229.2v
V3 = 343v
V1 + V2 = 343v
Result:
Transformer will have additive polarity, therefore we will mark P1 & S2 or P2 & S1 as dot ( •) polarities on
transformer.
2. Connect the circuit as per the circuit diagram shown in Fig. 10.2. (Note that all the measuring
instruments have to be connected on the LV side i.e., 115V side and HV side terminals are opened, and also
note that the loose connections in the circuit should be avoided).
3. Set the autotransformer at zero output voltage position and switch on the supply. Gradually increase
the autotransformer output to the rated voltage i.e., 115 V across the LV winding and note down the
readings of voltmeter (Voc), ammeter (Ioc), and wattmeter (Poc). Reduce the autotransformer output to
zero volts and switch off the supply.
Observation:
Voc Ioc = I(A) Poc(W)
115 0.58 30
Calculations:
Rated core-loss in the transformer Poc = 30W
1. The short circuit test can be conducted on either side of the transformer, but if the short circuit test is
conducted on HV side then low range meters will be sufficient. In this test, voltmeter (0-50 V, MI),
Ammeter (0-5A, MI), and wattmeter (150V, 5A, UPF) are required to measure the voltage, current, and
power.
2. Connect the circuit as per the circuit diagram shown in Fig. 10.3. (Note that all the measuring
instruments have to be connected on the HV side i.e., at 230V side, and LV terminals are shorted, and also
note that the loose connections in the circuit should be avoided).
3. Set the autotransformer at zero output voltage position and switch on the supply. Gradually increase the
autotransformer output to the rated current i.e., 4.35A to be flown through the HV winding, and note
down the readings of voltmeter (VSC), ammeter (ISC), and wattmeter (PSC). Reduce the autotransformer
output to zero volts and switch off the supply.
4. Find the full load copper loss (=PSC) and power factor when LV terminals are shorted
.
The effective resistance ReHV = PSC/I2SC , the effective impedance ZeHV = VSC/ISC and the effective leakage
reactance XeHV= Z2eHV - R2eLV can be determined with respect to HV side.
5. For a good designed transformer, RHV = ReHV/2 and XHV = XeHV/2 . By using these two relations, We can
determine the RHV , RLV , XHV and XLV.
Observation:
VSC = 16.2v
ISC = 4.35A
PSC = 60W
Calculations:
Rated copper loss or rated ohmic loss in transformer. PSC = 60W
Power factor at short circuit condition, cosѲsc = Psc / Vsc * Isc = 0.8514 lagging
The equivalent resistance of the transformer, ReHV = Psc /I2HV = 50/4.352 = 3.17Ω
Therefore,
RHV = 1.585Ω
XHV = 0.997Ω
RLV = 0.39635Ω
XLV = 0.24425Ω
Result:
The supply voltage required to follow the rated current in both HV and LV windings when the LV side
terminals are short-circuited is 7.04% of the rated terminal voltage.