2020 International Conference on Power Electronics & IoT Applications in Renewable Energy and its Control (PARC)

GLA University, Mathura, UP, India. Feb 28-29, 2020

Development of Intelligent Automatic Electronic


MCB and ELCB Using Fault Diagnosis Technique
2020 International Conference on Power Electronics & IoT Applications in Renewable Energy and its Control (PARC) 978-1-7281-6575-2/20/$31.00 ©2020 IEEE 10.1109/PARC49193.2020.236623

Mihir Rameshkumar Vasavada Vishwa S. Patel Jay R. Prajapati


Electrical Engineering, Electrical Engineering, Electrical Engineering, L.D. College of
L.D. College of Engineering L.D. College of Engineering Engineering
Gujarat Technological University Gujarat Technological University Gujarat Technological University
Ahmedabad, India Ahmedabad, India Ahmedabad, India
mihir75@gmail.com, patelvishwa.ee@gmail.com, prajapatijayr98@gmail.com

Abstract— Protection system and continuous power supply so that even a normal person can be able to understand as to
are important for residential and commercial areas. To ensure what has happened with the circuit breaker [7]. The new
enhanced protection, automatically operated intelligent energy management system or smart-grid was introduced
miniature circuit breaker (MCB) and earth leakage circuit into the power system. The management system of
breaker (ELCB) is developed using advanced current generation, transmission and demand side were controlled
measurement and fault diagnosis technique. Whenever short under the concept of bidirectional power and bidirectional
circuit or earth fault occurs the system will trip and power communication system. The smart protection device is also
supply is if it is temporary fault system will restore power integrated into smart-grid for improving the novel power
supply using advanced fault diagnosis technique and if it is
system protection [4].
permanent fault it will remain off. Thus, the aim of this paper
is to develop an intelligent protection system to overcome In domestic premises, there are two major faults
problems of electromechanical circuit breakers. The automatic occurring short circuits and earth fault. Short circuit fault
system is able to detect, diagnose, interrupt and reclose the occurs due to a tremendous increase in line current, while
circuit breaker in order to ensure power supply continuity earth leakage fault occurs due to leakage current from a line
along with safety. to earth directly or indirectly. Existing MCB works on the
principle of heating and bending of Bi-metallic strip which
Keywords— Hall-effect transducer; Earth leakage circuit
releases mechanical latch and ELCB works on detection of
breaker(ELCB); Miniature circuit breaker(MCB); Solid-state
relay; Fault diagnosis system; Auto-recloser system
current between line and neutral wire using a current
transformer. Both of existing systems have the manual
I. INTRODUCTION operation and use of the electromechanical system, while
intelligent electronic circuit breaker works on the principle of
The uninterruptible power supply is essential in electrical hall-effect transducer and advanced fault diagnosis-technique
distribution system at domestic residential areas, corporate [11].
buildings, hospitals, labs and all kinds of emergency
services. For protection from short circuit fault and earth II. WORKING PRINCIPLE
faults, these miniature circuit breaker (MCB) and earth
leakage circuit breaker (ELCB) are used respectively. Due to Existing Circuit Breakers are electromechanical circuit
short circuit equipment failure and fire hazard takes place breakers while Intelligent Protection System consists of
and earth fault cause shock hazard to human life. In India electronic circuit breaker. Electronic circuit breaker makes
installation of earth leakage circuit breaker has been use of current sensors, microcontroller, solid state relay,
mandatory under section 61 A of the Indian Electricity voltage transformer, BJTs and rectifier. Electronic circuit
Rules, 1956 for all new connections of 5KW, but awareness breaker detects over current and leakage current using hall-
of earth leakage circuit breaker(ELCB) is still less, that cause effect transducers, Fault detection and diagnosis works on
a shock hazard. Workplace accidents report nearly 13 small supply injection technique, tripping and reclosing
electrocution deaths on an average per day India. This is the mechanism works on solid state technology. Automatic
highest in the world. The annual average electric related intelligent protection system works as per user requirements.
deaths in the United Kingdom and the United States are 8 If the current difference in line and neutral exceeds 30mA for
and 82 respectively [9]. Delhi(424), Mumbai(418) and domestic application and 100milliamperes for industrial
Ahmedabad(260) are recorded the highest number of a short application circuit interruption takes place [1]. If the
circuit in India during a decade [10]. response of the fault diagnosis system is the occurrence of a
temporary fault, then the circuit will get automatically
The existing system do not protect against the reclose as soon as temporary fault removed. The system will
overheating which occurs due to improper screwing of not reclose the circuit if it detects permanent fault using a
conductors into their terminals. This can also be avoided by small supply injection technique. Microcontroller fetches
using thermal sensors integrated onto the electronic circuit data from current sensors continuously, process the data,
breaker. Also, the conventional mechanical MCB and ELCB sends signals to relaying mechanism and take decisions as
boards can be fitted with sensors through which we can per given instruction sets. The block diagram in Fig.1 shows
individually monitor the conditions in each part of the house data flow and working of overall system.
Aarambh Cell, LDCE, Student Startup and Innovation Policy,
Educational Department, Government of Gujarat.

978-1-7281-6575-2/20/$31.00 ©2020 IEEE 346

Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on May 16,2020 at 02:39:52 UTC from IEEE Xplore. Restrictions apply.
minimum 5 milliamperes accuracy. Hence, external ADC is
used in the circuit. ADS1115 has a 16-bit resolution that
means it can measure 65535th part of 5 V that is 0.125
millivolts. Hence, it can measure 1.89 milliamperes current
precisely.
The output of ACS 724 is pure sinusoidal in nature hence
no harmonics are present. 65.76 millivolts RMS or 92.95
millivolts peak output can be obtained when there is 1 A
RMS supply current is flowing. This can be also seen in Fig.
Fig. 1. Functional Block Diagram 3 along with Fig. 4

III. SYSTEM OPERATION B. Condition Monitoring


Automatic Intelligent Protection System consists of four Measured data of current is continuously fed to micro-
major subsystems as following: controller endurance arduino nano ATMEGA328. This
provides better running characteristics, low power
A) Current Measurement System consumption, RISC architecture, fully static operation at 16
megahertz. It contains volatile memory segment, internally
B) Condition Monitoring System calibrated oscillator and having high endurance. Device
C) Fault Detection and Diagnosis System condition and control can be accessible by a user directly
through IOT. Condition is to be monitored by a user via
D) Tripping and Auto-reclosing System GSM Module/ Bluetooth Module/ Wifi Networks. Alert
A. Current Measurement System message is sent to the user on the occurrence of the fault and
response of the system is available to the user. In case of any
Current measurement can be done by using a current
hazard, the user can also directly control the device to
transformer, series resistor, hall-effect transducer, mirror
prevent further damages. IOT technology makes device more
matched transistors. Out of this hall-effect transducer gives
user friendly for future smart homes. [5]. Data flow in
best results suitable for electronic circuit breaker application.
overall system is shown in flowchart in Fig.5.
Two ACS 724 are used to an accurate and precise
measurement of current in phase and neutral. ACS 724
provides low primary conductor resistance, low power loss.
No shielding is required because sensor rejects common
mode field successfully [12]. This can be used for
measurement of AC and DC current in industrial,
automotive, commercial and domestic application
economically. This IC sense current differentially using hall-
effect transducer in order to reject the common-mode field
and improve accuracy in a noisy environment. It can measure
precisely up to 1.9 milliamperes and can operate within 4
milliseconds. For domestic applications module of 30 A is to
be used. For getting the accurate results from hall-effect
transducer filter pin of the sensor must be connected with the
capacitors in the configuration as shown in Fig. 2.
Fig. 3. The waveform of ACS 724

Fig. 2. IC ACS 724 Configuration

Arduino has inbuilt 10-bit ADC that means it can


measure 1023rd part of 5 Volt i.e. 4.9 millivolts ACS 724 30
A has a sensitivity of 66 millivolts per ampere so that it can
measure only 74 milliamperes current precisely. This is not Fig. 4. Cursor values of Fig. 3.
sufficient for accurate measurement. Hence it cannot be
implemented in earth leakage circuit breaker that requires

347

Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on May 16,2020 at 02:39:52 UTC from IEEE Xplore. Restrictions apply.
Fig. 5. Flowchart of signals

C. Fault detection and diagnosis system The microcontroller sends signals to relays as per system
condition. On the occurrence of the fault immediately relay
Electronic Circuit Breaker detect overcurrent and earth operates and trip the circuit. Ultra fast relay works in very
fault very fast. This will trip the circuit if a fault is detected. less time to isolate a faulty part of the system and avoid any
For reclosing application it uses small supply injection damages. From the results of fault diagnosis system
technique to check whether the fault is removed or not. From microcontroller sends a signal to relay to remain permanently
the input side of this module step down transformer is off in case of a permanent fault. If the response of a fault
connected for lower voltage injection in the system. If still diagnosis system is an identification of temporary fault then
there is a difference of current between line and neutral, the the signal is sent to the reclosing system and lines are closed
system is in a faulty condition. Hence, it remains off. But if to ensure the reliability of power supply. The typical
there is no difference between line and neutral current, sequence for auto-recloser operation of a large power circuit
System is in healthy condition and it will on the breaker. breaker is shown in Fig. 7. [8]. Similar system works for
The calculation for current during small supply injection domestic auto-recloser.
is performed in an experimental case for 230 V system. At Use of these relays makes system very effective,
the time of earth fault, 30 milliamperes leakage current is economical, fast dynamic response, less operation time, high
measured then there is virtual resistance of 7.6 kiloohms. For voltage and current withstand capability. Calculation of
small supply, 12 V injection 1.8 milliamperes current is to be tripping time is performed for the proposed system. ACS 724
tripped if detected. works at 120 kHz frequency, it means that it works in 8
Faults due to overcurrent and insulation failure are a microseconds. Arduino nano works at 16 megahertz that it
permanent fault. In such cases, the breaker will trip works in 0.0625 microseconds and solid-state relay work in
permanently. Transient faults are temporary fault due to 7.5 milliseconds. Hence overall system is ultra fast acting
which nuisance tripping occurs. whose time response is 8 milliseconds. It also can withstand
high di/dt and dv/dt. There are no contact failures, No arc
The system can identify such faults successfully and it noise, very little noise generation during operation [2],[6].
will make system on automatically once it is removed.
The solid-state relay consists of triac, optocoupler,
D. Tripping and Reclosing Mechanism snubber circuit. All movable mechanical parts are absent.
For opening and closing of lines, solid-state relays are The optocoupler is used for firing triac at the desired instant
used as a switch. Solid-state relay consist of various circuit of time.
elements which are connected to each other as shown in Fig.
6.

Fig. 6. Schematic of the solid-state relay Fig. 7. Operation of auto-recloser

348

Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on May 16,2020 at 02:39:52 UTC from IEEE Xplore. Restrictions apply.
IV. CIRCUIT DESCRIPTION TABLE II. COMPARISON BETWEEN MECHANICAL CIRCUIT BREAKER
AND ELECTRONIC CIRCUIT BREAKER
The circuit is operated at single phase 230 V supply.
Features Mechanical circuit Electronic circuit
Circuit diagram consists of two solid state relays, ACS 724, breaker breaker
step down transformer 230V/12 V , Diode bridge Rectifier Auto-reclosing Not Available Available
for 12 V AC to 12V DC, Voltage regulator of 5 V. Arduino Life span 2-3 years 4-5 years
ATMEGA328 are used as a mircrocontroller in the circuit. Nuisance tripping Yes No
Lamp Load of 100 W is connected as a load for simulation of IOT compatible No Yes
the circuit. During actual set up various other loads are to be Trip unit Technology Thermal-Magnetic Solid state technology
connected to check the performance of the system under Fault Diagnosis Not possible Possible
Size of device Bulky Compact
different cases. According to the used circuit element this
Arcing Present Absent
intelligent protection system can be used for the system Operation noise High Low
parameters that are specified in table I. Hardware kit is Maintenance Regularly Very less
shown in Fig. 8. The circuit diagram and modelling of Requirement
Intelligent Protection system is shown in Fig. 9.

TABLE I. SYSTEM PARAMETERS


System Quantities Values
Voltage Level 250 V
Load 5000 W
Short Circuit Current >25 A
Earth Leakage Current >30 milliamperes

Table II shows the comparison between the existing


system and proposed system. It is clear that ultra fast-acting
Intelligent Protection System have better performance than
the existing system [6].

Fig. 8. Hardware Image of Intelligent Portection System

Fig. 9. Modelled Circuit Diagram of Intelligent Protection system

349

Authorized licensed use limited to: Univ of Calif Santa Barbara. Downloaded on May 16,2020 at 02:39:52 UTC from IEEE Xplore. Restrictions apply.
V. CONCLUSION insulated gate bipolar transistor for distribution system protection”,
International Electrical Engineering Congress 2014(IEECON).
Intelligent Protection System consisting of Electronic [3] J. Rajaram; N. M. Nor; T. Ibrahim; H. Daud; P. H. Shaikh, “A novel
Circuit Breaker and auto-reclosing system considered as a supervisory control for residential building protection system”, IEEE
novel solution for domestic protection system for smart 8th International Power Engineering and Optimization Conference
2014 (PEOCO2014).
home. This system removes drawbacks of mechanically [4] Supawat Kamtip ; Krischonme Bhumkittipich, “Comparison between
operated circuit breakers. Development of auto reclosing mechanical circuit breaker and solid state circuit breaker under
electronic MCBs and ELCBs enhances the performance and abnormal conditions for low voltage systems”, 18th International
reliability of the protection system.From experimental Conference on Electrical Machines and Systems 2015 (ICEMS).
results it can be concluded that proposed system is robust, [5] D. Pavithra. Ranjith Balakrishnan, “IoT based monitoring and control
system for home automation”, Global Conference on Communication
having ultra fast tripping mechanism, stable operating point, Technologies (GCCT). Optimization Conference 2015 (PEOCO).
low power consumption, accurate, automatic operation, [6] Tushar V. Deokar; Onkar Y. Salunkhe; Ganesh J. Ankalgi; Vishal D.
longer life and economy that can be used for smart home in Kare, “Ultra fast acting Electronic Circuit Breaker for overload
the future. protection.”, Third International Conference on Advances in
Electrical, Electronics, Information, Communication and Bio-
ACKNOWLEDGMENT Informatics 2017 (AEE-ICB).
[7] C. V. Chiranthan; M. Krishna Prasad; R. Y. Shreyas, “Digital MCB",
This research is supported by Aarambh Cell, L.D. International Conference On Smart Technologies For Smart Nation
College of Engineering, Student Startup and Innovation 2017 (SmartTechCon).
Policy, Educational Department, Government of Gujarat. We [8] Hamid Bentarzi; Abderrah-mane Ouadi; Abdelkader Abdelmoumene,
are thankful to our colleagues from Department of Electrical “A new framework of smart auto-recloser”, IEEE 12th International
Engineering, L.D. College of Engineering who provided Conference on Compatibility, Power Electronics and Power
Engineering 2018 (CPE-POWERENG 2018).
insight and expertise that greatly assisted the research.
[9] “Mumbai ranks 2nd in short circuit fires, with 418 deaths in 10 years:
We are thankful to Mitul Patel, Assistant Professor, L.D. NCRB”, The Times Of India, (Jan 8, 2018) Retrieved from:
College of Engineering for assistance with technical support https://timesofindia.indiatimes.com/city/mumbai/city-ranks-2nd-in-
short-circuit-fires-with-418-deaths-in-10-years-
in hardware building and continuous mentoring. We are also ncrb/articleshow/62406828.cms .
thankful to Prof. Adhwaryu Vaishali Apurva and Prof. Hiral
[10] “Why safe wiring is a must”, The Hindu, (Feb 21, 2019) Retrieved
Raval, Assistant Professors, L.D. College of Engineering for from: https://www.thehindu.com/life-and-style/homes-and-
comments on an earlier version of manuscript that greatly gardens/why-safe-wiring-is-a-must/article26330183.ece .
improved the manuscript. [11] Analysis on failure modes of miniature circuit breaker Yang Xue ;
Penghe Zhang ; Yinghui Xu ; Dezhi Xiong ; Yangchun Cheng ; Fuli
REFERENCES Yang ; Zhengzhou Du 2016 IEEE International Conference on Power
System Technology (POWERCON)
[1] A.Z.H. Abd Azzis; Nursyarizal Mohd Nor; Taib Ibrahim, “Automated
Electrical Protection System for domestic application”, IEEE 7th [12] Optimization Design of Anti-Strong Magnetic Interference for
International Power Engineering and Optimization Conference 2013 Intelligent Miniature Circuit Breaker Dezhi Xiong ; Xiaoping Liu ;
(PEOCO). Xiangqun Chen 2018 2nd IEEE Conference on Energy Internet and
Energy System Integration (EI2).
[2] Wanida Pusorn; Warunee Srisongkram; Kittiwat Chiangchin;
Krischonme Bhumkittipich, “Solid State Circuit Breaker using