You are on page 1of 5

Wind Power Plant Voltage Control Optimization with

Embedded Application of Wind Turbines and


STATCOM
Qiuwei Wu, Jose Ignacio Busca Solanas, Haoran Zhao àukasz Hubert Kocewiak
Centre for Electric Power and Energy, Department of DONG Energy Wind Power
Electrical Engineering Gentofte, Denmark
Technical University of Denmark lukko@dongenergy.dk
Kgs. Lyngby, Denmark
qw@elektro.dtu.dk, josetxob@hotmail.com,
hzhao@elektro.dtu.dk
Abstract—Increasing wind power penetration and the size of
Wind Power Plants (WPPs) brings challenges to the operation
and control of power systems. Most of WPPs are located far
from load centers and the short circuit ratio (SCR) at the Point
of Connection (POC) is low, which means that fluctuations of
the wind power can cause voltage variations. An optimal voltage
control scheme for WPPs with STATCOMs is presented in the
paper. It ensures that the voltages within the WPPs and at the
high voltage side of the WPPs are within the limits and
maximizes the dynamic Var reserve of the WPPs. Case studies
were conducted with the simplified Anholt offshore WPP and
the case study results demonstrate the efficacy of the proposed
optimal voltage control scheme.

Index Terms—full scale converter, optimal voltage control,


STATCOM, wind power plant , wind turbine Figure 1. Global cumulative installed capacity of wind power [1].

INTRODUCTION In order to fulfill these requirements, WPPs have a variety


The growth of wind power has been considerably large, of reactive power (Var) or voltage (Volt) regulation devices:
being around 40% annually in the last ten years. By the end of Static Var Compensators (SVCs), Static Var Generators
2015, the total installed capacity of wind power was 432 GW (SVGs), Static Compensator (STATCOM), On Load Tap
as shown in Figure 1 0. The top three countries with the Changing (OLTC) Transformer, static and controllable shunt
highest installed capacity are China, USA and Germany with reactor, etc. Besides, with the development of power
145 GW, 74 GW and 44 GW, respectively. electronics and control technologies, modern WTs equipped
with power electronic converters (Type 3 and Type 4) can
The increasing penetration of wind power and growing control the reactive power, and participate in the voltage
size of WPPs have a big impact on the system operation and control 0.
introduce technical challenges to voltage stability 0. Most
large WPPs are mainly located in areas far from load centers, Several modes of controlling the reactive power of a WPP
the SCR at the POC is low 0, and the grid at the connection have been specified by many grid codes which are defined by
point is weak. The voltage fluctuation caused by fluctuating Transmission System Operators (TSOs) for wind power
power from the WPPs can be quite large. Moreover, grid integration, including power factor control, reactive power
disturbances may cause cascading trip of Wind Turbines control and voltage control 0. For the transmission system, the
(WTs). Therefore, modern WPPs are required to meet more voltage control mode shows superior performance. This paper
stringent technical requirements of voltage support specified focuses on the WPP control under this mode, i.e. the WPP
by system operators. The requirements include reactive power controls the voltage at the POC specified by the system
capability of the WPP, voltage operating range at the POC, operator.
voltage control, high- and low- voltage ride through, and The paper is organized as follows. The optimal voltage
frequency control 0. control of WPPs is presented in Section II. The case studies

978-1-5090-6173- 0/16/$31.00 ©2016 IEEE


are described and discussed in Section III, followed by are the Var regulation vectors of the WTs and STATCOMs;
conclusions in Section IV. Ctw and Cts are the sensitivity matrixes of the WTG terminal
OPTIMAL VOLTAGE CONTROL OF WPP voltage Vwt with respect to ΔQwt and ΔQs ; WT , Ww and
The optimal voltage control of the WPP is to optimize both Ws are weighting factors; Csw and Css are the sensitivity
the voltage levels of all elements and the reactive power matrixes of the STATCOM terminal voltage Vs with respect
distribution within the WPP. The optimal voltage control of to ΔQwt and ΔQs ; Chw and Chs are the sensitivity matrixes
the WPP consists of three modes: corrective voltage control
mode, coordinated voltage control mode and preventive of the WPP voltage at the high voltage side Vwh with respect
voltage control model. The details of the three control modes to ΔQwt and ΔQs ; Vwtmin , Vwtmax , Vsmin , Vsmax , Vwh
min
and
are described below. The diagram of a WPP is shown in max min max
Figure 2. Vwh are the limits of Vwt , Vs and Vwh ; Qwt , Qwt , Qsmin
and Qsmax are the limits of Qwt , and Qs .

If Vwtreal − Vwtnom ≥ Vwtth , the WPP voltage control will


operate in the corrective voltage control mode. Vwtth is the
threshold value and is usually set as 0.1 pu. In order to make
sure that the WT bus voltage values do not exceed the
boundaries, Vwtth is set as 0.07 pu and the voltage limits are
[0.93 pu, 1.07 pu].
B. Coordinated voltage control mode
The coordinated voltage control mode is to track the
voltage reference at the POC of the WPP from the system
operator and mitigate the voltage fluctuations considering all
Figure 2. Single line diagram of a generic WPP with array cable system,
necessary operation constraints. If all the WT and STATCOM
dynamic reactive power compensation and stepup transformer connecting to terminal voltages are within limits, and the voltage deviation
the grid.. at the HV side of the WPP is larger than the threshold value,
the WPP voltage control will operate in the coordinated
A. Corrective voltage control mode voltage control mode. The threshold of the HV side voltage of
th
The corrective voltage control mode is to ensure that all the WPP, Vwh , is set as 0.05 pu.
the WT bus voltages are within limits. If the WT bus voltage
exceeds the limits, the WPP voltage controller will determine The coordinated voltage control can be formulated as the
the optimal solutions of reactive power regulation of wind optimization below.
turbine generators and STATCOMs in order to keep the WT 2
real ref
bus voltages within the limits. min WH Vwh − Vwh + Chw ΔQwt + Chs ΔQs
ΔQwt , ΔQs
The corrective voltage control can be formulated as the
2 2
optimization problem below. +Ww ΔQwt + Ws ΔQs (7)
2
min WT Vwtreal − Vwtnom + Ctw ΔQwt + Cts ΔQs subject to constraints (2)-(6).
ΔQwt , ΔQs
C. Preventive voltage control mode
2 2
+Ww ΔQwt + Ws ΔQs (1) The preventive voltage control is to maximize the dynamic
Var reserve of STATCOMs and replace the Var output from
subject to STATCOMs with the one from WTs. It is realized by driving
the Var output of STATCOMs to the middle. As such, there
Vwtmin ≤ Vwtreal + Ctw ΔQwt + Cts ΔQs ≤ Vwtmax (2) will be both upward and downward regulation capability.
Vsmin ≤ Vsreal + C sw ΔQwt + Css ΔQs ≤ Vsmax (3) The preventive voltage control can be formulated as the
following optimization.
min real max
Vwh ≤ Vwh + Chw ΔQwt + Chs ΔQs ≤ Vwh (4) 2
1 2
min real max min Ws' Qs + ΔQs − (Qsmax − Qsmin ) + Ww' ΔQwt (8)
Qwt ≤ Qwt + ΔQwt ≤ Qwt (5) ΔQwt 2

Qsmin ≤ Qsreal + ΔQs ≤ Qsmax (6) subject to constraints (2)-(6) and


Css ΔQs + Csw ΔQwt = 0 (9)
where Vwtreal is the actual WT terminal voltage; Vwtnom is the
nominal WT terminal voltage and is 1.0 pu; ΔQwt and ΔQs

978-1-5090-6173- 0/16/$31.00 ©2016 IEEE


In the corrective and coordinated control modes, the For testing the proposed WPP optimal voltage control, as
STATCOMs work with the constant-Q mode. The set-point to long as the system layout is kept, it will not be necessary to
the STATCOM is Qsref = Qs + ΔQs and the terminal voltage include all the details of the Anholt WPP. Therefore, the
Anholt WPP is simplified. The simplified WPP consists of 10
is bounded by (3). In the preventive control mode, the
WTs and two STATCOMs. The rest of the system is the same
STATCOMs work in the constant V mode. The voltage
as the Anholt WPP. The simplified and modified WPP is
reference of the ith STATCOM is [ Vsmin min
,i − ξ , Vs ,i + ξ ] where shown in Figure 4. Bus 1 is the bus of the external grid. Bus
ξ is a small deviation. 12 is the HV side of the WPP main transformer. The POC is
defined at Bus 14.
CASE STUDY
In order to test the efficiency of the proposed WPP voltage
control method, case studies were conducted using the
simplified and modified electrical infrastructure of Anholt
offshore WPP.
D. Test System
The Anholt offshore WPP in Denmark is situated 15 km
from the shore. The installed capacity is 400 MW and it
consists of 111 Siemens SWT-3.6-120 WTs. The WTs are
connected to an offshore substation and divided into three Figure 4. Simplified and modified electrical infrastructure of Anholt
groups. Each of them has 37 WTs which are radially Offshore WPP.
connected in four feeders to a step-up transformer. The POC is
at the Low Voltage (LV) side of the offshore transformer. In E. WT Model
the offshore substation, there are three 140 MVA transformers The WTs used in the Anholt offshore WPP are the
and each transformer is connected to a group of 37 WTs. The Siemens SWT-3.6-120 ones. The nominal active power output
transformers step up the voltage from 33 kV to 220 kV 0. is 3.6 MW and the diameter is 120 m. The cut-in speed is 3-5
m/s, the nominal power output is reached with a speed of 12-
The offshore substation is connected to an onshore 13 m/s and the cut out wind speed is 25 m/s 0.
substation through a 24.5 km submarine cable. In the onshore
substation, a 120 MVAr STATCOM is placed. Originally at The PQ chart of the Siemens 3.6 MW WTs is not available
Anholt offshore WPP a shunt reactor is provided in order to from the manufacturer. Therefore, a standard PQ chart of a
assure static reactive power compensation. However to full-scale converter (FSC) WT was used for the case studies.
demonstrate the concept of proposed optimized voltage The standard PQ chart is shown in Figure 5. In order to
control a STATCOM was introduced instead. The onshore simplify the PQ capability, the squared area is used as the
substation is connected to another substation through a 58 km operating range of the reactive power Q with respect to the
underground cable which is connected to the 400 kV external active power P. For 1.0 pu active power, the boundaries of the
grid. In this substation, there are two 450 MVA transformers reactive power is ±0.44 pu, meaning that the maximum
and 4 shunt reactors of 60 MVAr each. Similarly here, 4 reactive power output is ±1.58 MVAr.
STATCOMs are introduced instead of the shunt reactors to
incorporate them in the optimized system level voltage control
strategy.
The single line diagram of the Anholt offshore WPP is
shown in Figure 3. Each WT represents one feeder.

Figure 5. FSC WTG Standard PQ Chart

F. Case Study Reulsts


Three case studies were conducted including WT terminal
voltages out of the boundary, HV side voltage of the WPP
step-up transformer out of the boundary, and STATCOM Var
output close to the full capacity. The results of the three
Figure 3. Single line diagram of the simplified and modified Anholt control modes are presented in the following subsections.
offshore WPP.

978-1-5090-6173- 0/16/$31.00 ©2016 IEEE


The three case study scenarios are designed in order to 3) Preventive voltage control
create voltage conditions in which the effectiveness of the The preventive voltage control is to maximize the dynamic
three control modes can be illustrated. Var reserves and maintain the voltages in the WPP and the
external buses. The idea is to replace the Var outputs from the
1) Corrective voltage control
STATCOM by the Var output from slower reactive power
For testing the corrective voltage control mode, a case with compensation equipment, i.e. mechanically switched static
WT terminal voltages out of limits was created. In this reactive power compensation plants. It is a good option to
condition, the WTs were delivering very low active power and have a combined compensation solution. The STATCOM
absorbing reactive power. This scenario was designed to sizes can be reduced and the dynamic response can still meet
create a condition in which the WT terminal voltages were the requirements.
violated. In real operation, it might not happen.
The bus voltages and Var outputs of STATCOMs are
The bus voltages with and without the corrective voltage shown in Figure 8 and Table I. It is shown that the bus
control are shown in Figure 6. The WT buses are Bus 2 - Bus voltages are almost the same. The Var outputs of the
11. Without the corrective voltage control, the WT terminal STATCOMs are reduced.
voltages are below the specified voltage limit, 0.95 pu. With
the corrective voltage control, the Var output of WTs is
adjusted, and the WT terminal voltages are brought back
within the limits with the corrective voltage control.

Figure 8. Bus voltages with and without preventive voltage control.

TABLE I. VAR OUTPUTS OF THE STATCOMS WITH AND WITHOUT


Figure 6. Bus voltages with and without corrective voltage control. PREVENTIVE VOLTAGE CONTROL

2) Coordinated voltage control Var Output without Var Output with


STATCOM Preventive Control Preventive Control
For the coordinated voltage control, the WT terminal (MVar) (MVar)
voltages are within the limits. However, the HV side of the STATCOM 1 12 11.4
WPP main transformer (Bus 1 in Figure 4) is out of the limits. STATCOM 2 20 17.64
In this case study, the voltages of the WT buses are close to
the lower bound. Because the main step-up transformer
absorbs reactive power, the HV side of the main step-up CONCLUSIONS AND DISCUSSION
transformer is below 0.95 pu which is the specified limit. An optimal voltage control scheme is proposed in this
paper for WPPs with STATCOMs. The voltage control is to
The results with and without the coordinated control is
ensure that the voltages within the WPP and at the HV side of
shown in Figure 7. With the coordinated voltage control, the
the WPP main transformer are within limits and the dynamic
reactive power absorption of WTs is reduced and the HV side
Var reserve is maximized. Case studies results show that the
voltage of the WPP main step-up transformer is within the
proposed voltage control can determine the optimal Var set-
limits.
points of WTs and STATCOMs to bring the WT terminal
voltages and the HV side voltages of the WPP main
transformer back into the limits if there is a voltage violation.
When the voltages within the WPP and at the HV side of the
WPP main transformer are within limits, the Var outputs of
STATCOMs can be reduced to maximize the dynamic Var
reserves of the WPP by coordinating with slower reactive
power compensation equipment.
Such control implementation requires measurements at the
busbars of interest and fast communication channels. This of
course should be taken into consideration while designing and
implementing such centralized/optimized control strategy on a
system level.
Figure 7. Bus voltages with and without cordinated voltage control

978-1-5090-6173- 0/16/$31.00 ©2016 IEEE


Furthermore it should be noted that voltage control REFERENCES
optimization should be combined together with loss Global wind energy council, “Global wind statistics 2015”, Brussels,
optimization to make the proposed solutions feasible and Belgium, Feb. 2016. Available: http://www.gwec.net/wp-
applicable in the industry. However more sophisticated content/uploads/vip/GWEC-PRstats-2015_LR.pdf
voltage control provides more flexibility in overall electrical M. J. Hossain, H. R. Pota, M. A. Mahmud, and R. Ramos, “Investigation of
infrastructure optimization in contrary to e.g. fixed voltage the impacts of large-scale wind power penetration on the angle and
voltage stability of power systems,” IEEE Syst. Journal, vol. 6, no. 1,
setpoints for all WTs causing potential simultaneous reactive pp. 76–84, 2012.
power import and export from different WTs within the same T. Neumann, C. Feltes, and I. Erlich, “Response of DFG-based wind farms
string. operating on weak grids to voltage sags,” in Proc. Power Eng. Soc.
Gen. Meeting, 2011, pp. 1–6.
In order to avoid a number of STATCOMs connected Q. Wu, Z. Xu, and J. Østergaard, “Grid integration issues for large scale
within the system, which might not be feasible from cost- wind power plants,” in Proc. Power Eng. Soc. Gen. Meeting, 2010, pp.
benefit analysis perspective, the proposed method can be 1–6.
further optimized exclusively for WPP offshore electrical Z. Chen, J. M. Guerrero, and F. Blaabjerg, “A review of the state of the art of
power electronics for wind turbines,” IEEE Trans. Power Electron.,,
infrastructure. This would allow reactive power balancing vol. 24, no. 8, pp. 1859–1875, 2009.
within the offshore array cable system and optimization of the J. Fortmann, M. Wilch, F. W. Koch, and I. Erlich, “A novel centralized wind
voltage level at the HV side of the offshore transformer to farm controller utilising voltage control capability of wind turbines,” in
maximize the active power transfer via long HVAC cables. PSCC Power Syst. Comput. Conf., 2008.
à. H. Kocewiak, B. L. Øhlenschlæger Kramer, O. Holmstrøm, K. H. Jensen,
ACKNOWLEDGMENT L. Shuai, “Active Filtering Application in Large Offshore Wind
Farms,” in Proc. The 13th International Workshop on Large-Scale
The authors would like to express their appreciation to Integration of Wind Power into Power Systems as well as Transmission
Troels Stybe Sørensen from DONG Energy Wind Power for Networks for Offshore Wind Farms, Energynautics GmbH, 11-13
the valuable feedback. November 2014, Berlin, Germany.
Renewable Energy Division Siemens AG Energy Sector. “Siemens Wind
Turbine SWT-3.6-120”. 2011

978-1-5090-6173- 0/16/$31.00 ©2016 IEEE

You might also like