Wind Power Plant Voltage Control Optimization with
Embedded Application of Wind Turbines and
STATCOM Qiuwei Wu, Jose Ignacio Busca Solanas, Haoran Zhao àukasz Hubert Kocewiak Centre for Electric Power and Energy, Department of DONG Energy Wind Power Electrical Engineering Gentofte, Denmark Technical University of Denmark lukko@dongenergy.dk Kgs. Lyngby, Denmark qw@elektro.dtu.dk, josetxob@hotmail.com, hzhao@elektro.dtu.dk Abstract—Increasing wind power penetration and the size of Wind Power Plants (WPPs) brings challenges to the operation and control of power systems. Most of WPPs are located far from load centers and the short circuit ratio (SCR) at the Point of Connection (POC) is low, which means that fluctuations of the wind power can cause voltage variations. An optimal voltage control scheme for WPPs with STATCOMs is presented in the paper. It ensures that the voltages within the WPPs and at the high voltage side of the WPPs are within the limits and maximizes the dynamic Var reserve of the WPPs. Case studies were conducted with the simplified Anholt offshore WPP and the case study results demonstrate the efficacy of the proposed optimal voltage control scheme.
Index Terms—full scale converter, optimal voltage control,
STATCOM, wind power plant , wind turbine Figure 1. Global cumulative installed capacity of wind power [1].
INTRODUCTION In order to fulfill these requirements, WPPs have a variety
The growth of wind power has been considerably large, of reactive power (Var) or voltage (Volt) regulation devices: being around 40% annually in the last ten years. By the end of Static Var Compensators (SVCs), Static Var Generators 2015, the total installed capacity of wind power was 432 GW (SVGs), Static Compensator (STATCOM), On Load Tap as shown in Figure 1 0. The top three countries with the Changing (OLTC) Transformer, static and controllable shunt highest installed capacity are China, USA and Germany with reactor, etc. Besides, with the development of power 145 GW, 74 GW and 44 GW, respectively. electronics and control technologies, modern WTs equipped with power electronic converters (Type 3 and Type 4) can The increasing penetration of wind power and growing control the reactive power, and participate in the voltage size of WPPs have a big impact on the system operation and control 0. introduce technical challenges to voltage stability 0. Most large WPPs are mainly located in areas far from load centers, Several modes of controlling the reactive power of a WPP the SCR at the POC is low 0, and the grid at the connection have been specified by many grid codes which are defined by point is weak. The voltage fluctuation caused by fluctuating Transmission System Operators (TSOs) for wind power power from the WPPs can be quite large. Moreover, grid integration, including power factor control, reactive power disturbances may cause cascading trip of Wind Turbines control and voltage control 0. For the transmission system, the (WTs). Therefore, modern WPPs are required to meet more voltage control mode shows superior performance. This paper stringent technical requirements of voltage support specified focuses on the WPP control under this mode, i.e. the WPP by system operators. The requirements include reactive power controls the voltage at the POC specified by the system capability of the WPP, voltage operating range at the POC, operator. voltage control, high- and low- voltage ride through, and The paper is organized as follows. The optimal voltage frequency control 0. control of WPPs is presented in Section II. The case studies
are described and discussed in Section III, followed by are the Var regulation vectors of the WTs and STATCOMs; conclusions in Section IV. Ctw and Cts are the sensitivity matrixes of the WTG terminal OPTIMAL VOLTAGE CONTROL OF WPP voltage Vwt with respect to ΔQwt and ΔQs ; WT , Ww and The optimal voltage control of the WPP is to optimize both Ws are weighting factors; Csw and Css are the sensitivity the voltage levels of all elements and the reactive power matrixes of the STATCOM terminal voltage Vs with respect distribution within the WPP. The optimal voltage control of to ΔQwt and ΔQs ; Chw and Chs are the sensitivity matrixes the WPP consists of three modes: corrective voltage control mode, coordinated voltage control mode and preventive of the WPP voltage at the high voltage side Vwh with respect voltage control model. The details of the three control modes to ΔQwt and ΔQs ; Vwtmin , Vwtmax , Vsmin , Vsmax , Vwh min and are described below. The diagram of a WPP is shown in max min max Figure 2. Vwh are the limits of Vwt , Vs and Vwh ; Qwt , Qwt , Qsmin and Qsmax are the limits of Qwt , and Qs .
If Vwtreal − Vwtnom ≥ Vwtth , the WPP voltage control will
operate in the corrective voltage control mode. Vwtth is the threshold value and is usually set as 0.1 pu. In order to make sure that the WT bus voltage values do not exceed the boundaries, Vwtth is set as 0.07 pu and the voltage limits are [0.93 pu, 1.07 pu]. B. Coordinated voltage control mode The coordinated voltage control mode is to track the voltage reference at the POC of the WPP from the system operator and mitigate the voltage fluctuations considering all Figure 2. Single line diagram of a generic WPP with array cable system, necessary operation constraints. If all the WT and STATCOM dynamic reactive power compensation and stepup transformer connecting to terminal voltages are within limits, and the voltage deviation the grid.. at the HV side of the WPP is larger than the threshold value, the WPP voltage control will operate in the coordinated A. Corrective voltage control mode voltage control mode. The threshold of the HV side voltage of th The corrective voltage control mode is to ensure that all the WPP, Vwh , is set as 0.05 pu. the WT bus voltages are within limits. If the WT bus voltage exceeds the limits, the WPP voltage controller will determine The coordinated voltage control can be formulated as the the optimal solutions of reactive power regulation of wind optimization below. turbine generators and STATCOMs in order to keep the WT 2 real ref bus voltages within the limits. min WH Vwh − Vwh + Chw ΔQwt + Chs ΔQs ΔQwt , ΔQs The corrective voltage control can be formulated as the 2 2 optimization problem below. +Ww ΔQwt + Ws ΔQs (7) 2 min WT Vwtreal − Vwtnom + Ctw ΔQwt + Cts ΔQs subject to constraints (2)-(6). ΔQwt , ΔQs C. Preventive voltage control mode 2 2 +Ww ΔQwt + Ws ΔQs (1) The preventive voltage control is to maximize the dynamic Var reserve of STATCOMs and replace the Var output from subject to STATCOMs with the one from WTs. It is realized by driving the Var output of STATCOMs to the middle. As such, there Vwtmin ≤ Vwtreal + Ctw ΔQwt + Cts ΔQs ≤ Vwtmax (2) will be both upward and downward regulation capability. Vsmin ≤ Vsreal + C sw ΔQwt + Css ΔQs ≤ Vsmax (3) The preventive voltage control can be formulated as the following optimization. min real max Vwh ≤ Vwh + Chw ΔQwt + Chs ΔQs ≤ Vwh (4) 2 1 2 min real max min Ws' Qs + ΔQs − (Qsmax − Qsmin ) + Ww' ΔQwt (8) Qwt ≤ Qwt + ΔQwt ≤ Qwt (5) ΔQwt 2
Qsmin ≤ Qsreal + ΔQs ≤ Qsmax (6) subject to constraints (2)-(6) and
Css ΔQs + Csw ΔQwt = 0 (9) where Vwtreal is the actual WT terminal voltage; Vwtnom is the nominal WT terminal voltage and is 1.0 pu; ΔQwt and ΔQs
In the corrective and coordinated control modes, the For testing the proposed WPP optimal voltage control, as STATCOMs work with the constant-Q mode. The set-point to long as the system layout is kept, it will not be necessary to the STATCOM is Qsref = Qs + ΔQs and the terminal voltage include all the details of the Anholt WPP. Therefore, the Anholt WPP is simplified. The simplified WPP consists of 10 is bounded by (3). In the preventive control mode, the WTs and two STATCOMs. The rest of the system is the same STATCOMs work in the constant V mode. The voltage as the Anholt WPP. The simplified and modified WPP is reference of the ith STATCOM is [ Vsmin min ,i − ξ , Vs ,i + ξ ] where shown in Figure 4. Bus 1 is the bus of the external grid. Bus ξ is a small deviation. 12 is the HV side of the WPP main transformer. The POC is defined at Bus 14. CASE STUDY In order to test the efficiency of the proposed WPP voltage control method, case studies were conducted using the simplified and modified electrical infrastructure of Anholt offshore WPP. D. Test System The Anholt offshore WPP in Denmark is situated 15 km from the shore. The installed capacity is 400 MW and it consists of 111 Siemens SWT-3.6-120 WTs. The WTs are connected to an offshore substation and divided into three Figure 4. Simplified and modified electrical infrastructure of Anholt groups. Each of them has 37 WTs which are radially Offshore WPP. connected in four feeders to a step-up transformer. The POC is at the Low Voltage (LV) side of the offshore transformer. In E. WT Model the offshore substation, there are three 140 MVA transformers The WTs used in the Anholt offshore WPP are the and each transformer is connected to a group of 37 WTs. The Siemens SWT-3.6-120 ones. The nominal active power output transformers step up the voltage from 33 kV to 220 kV 0. is 3.6 MW and the diameter is 120 m. The cut-in speed is 3-5 m/s, the nominal power output is reached with a speed of 12- The offshore substation is connected to an onshore 13 m/s and the cut out wind speed is 25 m/s 0. substation through a 24.5 km submarine cable. In the onshore substation, a 120 MVAr STATCOM is placed. Originally at The PQ chart of the Siemens 3.6 MW WTs is not available Anholt offshore WPP a shunt reactor is provided in order to from the manufacturer. Therefore, a standard PQ chart of a assure static reactive power compensation. However to full-scale converter (FSC) WT was used for the case studies. demonstrate the concept of proposed optimized voltage The standard PQ chart is shown in Figure 5. In order to control a STATCOM was introduced instead. The onshore simplify the PQ capability, the squared area is used as the substation is connected to another substation through a 58 km operating range of the reactive power Q with respect to the underground cable which is connected to the 400 kV external active power P. For 1.0 pu active power, the boundaries of the grid. In this substation, there are two 450 MVA transformers reactive power is ±0.44 pu, meaning that the maximum and 4 shunt reactors of 60 MVAr each. Similarly here, 4 reactive power output is ±1.58 MVAr. STATCOMs are introduced instead of the shunt reactors to incorporate them in the optimized system level voltage control strategy. The single line diagram of the Anholt offshore WPP is shown in Figure 3. Each WT represents one feeder.
Figure 5. FSC WTG Standard PQ Chart
F. Case Study Reulsts
Three case studies were conducted including WT terminal voltages out of the boundary, HV side voltage of the WPP step-up transformer out of the boundary, and STATCOM Var output close to the full capacity. The results of the three Figure 3. Single line diagram of the simplified and modified Anholt control modes are presented in the following subsections. offshore WPP.
The three case study scenarios are designed in order to 3) Preventive voltage control create voltage conditions in which the effectiveness of the The preventive voltage control is to maximize the dynamic three control modes can be illustrated. Var reserves and maintain the voltages in the WPP and the external buses. The idea is to replace the Var outputs from the 1) Corrective voltage control STATCOM by the Var output from slower reactive power For testing the corrective voltage control mode, a case with compensation equipment, i.e. mechanically switched static WT terminal voltages out of limits was created. In this reactive power compensation plants. It is a good option to condition, the WTs were delivering very low active power and have a combined compensation solution. The STATCOM absorbing reactive power. This scenario was designed to sizes can be reduced and the dynamic response can still meet create a condition in which the WT terminal voltages were the requirements. violated. In real operation, it might not happen. The bus voltages and Var outputs of STATCOMs are The bus voltages with and without the corrective voltage shown in Figure 8 and Table I. It is shown that the bus control are shown in Figure 6. The WT buses are Bus 2 - Bus voltages are almost the same. The Var outputs of the 11. Without the corrective voltage control, the WT terminal STATCOMs are reduced. voltages are below the specified voltage limit, 0.95 pu. With the corrective voltage control, the Var output of WTs is adjusted, and the WT terminal voltages are brought back within the limits with the corrective voltage control.
Figure 8. Bus voltages with and without preventive voltage control.
TABLE I. VAR OUTPUTS OF THE STATCOMS WITH AND WITHOUT
Figure 6. Bus voltages with and without corrective voltage control. PREVENTIVE VOLTAGE CONTROL
2) Coordinated voltage control Var Output without Var Output with
STATCOM Preventive Control Preventive Control For the coordinated voltage control, the WT terminal (MVar) (MVar) voltages are within the limits. However, the HV side of the STATCOM 1 12 11.4 WPP main transformer (Bus 1 in Figure 4) is out of the limits. STATCOM 2 20 17.64 In this case study, the voltages of the WT buses are close to the lower bound. Because the main step-up transformer absorbs reactive power, the HV side of the main step-up CONCLUSIONS AND DISCUSSION transformer is below 0.95 pu which is the specified limit. An optimal voltage control scheme is proposed in this paper for WPPs with STATCOMs. The voltage control is to The results with and without the coordinated control is ensure that the voltages within the WPP and at the HV side of shown in Figure 7. With the coordinated voltage control, the the WPP main transformer are within limits and the dynamic reactive power absorption of WTs is reduced and the HV side Var reserve is maximized. Case studies results show that the voltage of the WPP main step-up transformer is within the proposed voltage control can determine the optimal Var set- limits. points of WTs and STATCOMs to bring the WT terminal voltages and the HV side voltages of the WPP main transformer back into the limits if there is a voltage violation. When the voltages within the WPP and at the HV side of the WPP main transformer are within limits, the Var outputs of STATCOMs can be reduced to maximize the dynamic Var reserves of the WPP by coordinating with slower reactive power compensation equipment. Such control implementation requires measurements at the busbars of interest and fast communication channels. This of course should be taken into consideration while designing and implementing such centralized/optimized control strategy on a system level. Figure 7. Bus voltages with and without cordinated voltage control
Furthermore it should be noted that voltage control REFERENCES optimization should be combined together with loss Global wind energy council, “Global wind statistics 2015”, Brussels, optimization to make the proposed solutions feasible and Belgium, Feb. 2016. Available: http://www.gwec.net/wp- applicable in the industry. However more sophisticated content/uploads/vip/GWEC-PRstats-2015_LR.pdf voltage control provides more flexibility in overall electrical M. J. Hossain, H. R. Pota, M. A. Mahmud, and R. Ramos, “Investigation of infrastructure optimization in contrary to e.g. fixed voltage the impacts of large-scale wind power penetration on the angle and voltage stability of power systems,” IEEE Syst. Journal, vol. 6, no. 1, setpoints for all WTs causing potential simultaneous reactive pp. 76–84, 2012. power import and export from different WTs within the same T. Neumann, C. Feltes, and I. Erlich, “Response of DFG-based wind farms string. operating on weak grids to voltage sags,” in Proc. Power Eng. Soc. Gen. Meeting, 2011, pp. 1–6. In order to avoid a number of STATCOMs connected Q. Wu, Z. Xu, and J. Østergaard, “Grid integration issues for large scale within the system, which might not be feasible from cost- wind power plants,” in Proc. Power Eng. Soc. Gen. Meeting, 2010, pp. benefit analysis perspective, the proposed method can be 1–6. further optimized exclusively for WPP offshore electrical Z. Chen, J. M. Guerrero, and F. Blaabjerg, “A review of the state of the art of power electronics for wind turbines,” IEEE Trans. Power Electron.,, infrastructure. This would allow reactive power balancing vol. 24, no. 8, pp. 1859–1875, 2009. within the offshore array cable system and optimization of the J. Fortmann, M. Wilch, F. W. Koch, and I. Erlich, “A novel centralized wind voltage level at the HV side of the offshore transformer to farm controller utilising voltage control capability of wind turbines,” in maximize the active power transfer via long HVAC cables. PSCC Power Syst. Comput. Conf., 2008. à. H. Kocewiak, B. L. Øhlenschlæger Kramer, O. Holmstrøm, K. H. Jensen, ACKNOWLEDGMENT L. Shuai, “Active Filtering Application in Large Offshore Wind Farms,” in Proc. The 13th International Workshop on Large-Scale The authors would like to express their appreciation to Integration of Wind Power into Power Systems as well as Transmission Troels Stybe Sørensen from DONG Energy Wind Power for Networks for Offshore Wind Farms, Energynautics GmbH, 11-13 the valuable feedback. November 2014, Berlin, Germany. Renewable Energy Division Siemens AG Energy Sector. “Siemens Wind Turbine SWT-3.6-120”. 2011
The Complete HVAC BIBLE for Beginners: The Most Practical & Updated Guide to Heating, Ventilation, and Air Conditioning Systems | Installation, Troubleshooting and Repair | Residential & Commercial
Power of Habit: The Ultimate Guide to Forming Positive Daily Habits, Learn How to Effectively Break Your Bad Habits For Good and Start Creating Good Ones