You are on page 1of 8

J.

Electromagnetic Analysis & Applications, 2010, 2, 467-474


doi:10.4236/jemaa.2010.28062 Published Online August 2010 (http://www.SciRP.org/journal/jemaa)

Voltage Control in Smart Grids: An Approach


Based on Sensitivity Theory
Morris Brenna1, Ettore De Berardinis2, Federica Foiadelli1, Gianluca Sapienza3, Dario Zaninelli1
1
Politecnico di Milano – Department of Energy, Milan, Italy; 2CESI S.p.A., Milan, Italy; 3Politecnico di Milano – Department of
Energy in Collaboration with ENEL Distribuzione S.p.A., Milan, Italy.
Email: gianluca.sapienza@mail.polimi.it

Received March 30th, 2010; revised May 25th, 2010; accepted May 31st, 2010

ABSTRACT
Due to the development of Distributed Generation (DG), which is installed in Medium-Voltage Distribution Networks
(MVDNs) such as generators based on renewable energy (e.g., wind energy or solar energy), voltage control is
currently a very important issue. The voltage is now regulated at the MV busbars acting on the On-Load Tap Changer
of the HV/MV transformer. This method does not guarantee the correct voltage value in the network nodes when the
distributed generators deliver their power. In this paper an approach based on Sensitivity Theory is shown, in order to
control the node voltages regulating the reactive power exchanged between the network and the dispersed generators.
The automatic distributed voltage regulation is a particular topic of the Smart Grids.

Keywords: Voltage Regulation, Reactive Power Injection, Distributed Generation, Smart Grids, Sensitivity Theory,
Renewable Energy

1. Introduction When a generator injects power, the voltage rises in all


network nodes, but some nodes are mainly influenced
Due to the development of Distributed Generation (DG), than others by the power injection. This influence can be
which is installed in Medium-Voltage Distribution Net- obtained using a Sensitivity method.
works (MVDNs) such as generators based on renewable In this paper an approach based on Sensitivity The-
energy (e.g., wind energy or solar energy), voltage con- ory is shown, in order to control the network voltage us-
trol is currently a very important issue. ing the reactive power exchanged between network and
The voltage of MVDNs is now regulated acting only the distributed generators. This approach allows to con-
on the On-Load Tap Changer (OLTC) of the HV/MV tra- trol the voltage in the long term period. Besides, fast-
nsformer [1]. The OLTC control is typically based on the dynamic voltage disturbances are not taken into account
compound technique, and this method does not guarantee [6].
the correct voltage value in the network nodes when the After the theoretical analysis, a numerical example is
generators deliver their power [2,3]. shown, in order to validate the proposed theory.
When a generator injects power in the network, the vo- The proposed method differs from the others used in
ltage tends to rise. In HV networks this phenomenon ha- HV networks analysis, based on the Jacobian Matrix
ppens mainly when reactive power is injected, because [1,2-4] and its application is easy.
the resistance is negligible if compared with the induc- The topological proprieties that results from the th-
tive reactance [4]. Instead in MVDNs the resistance is eoretical analysis imply that the proposed sensitivity me-
not negligible and the result is that an injection of active thod can be easily implemented in automatic voltage
power also increases the voltage. control devices, in order to obtain the distributed voltage
In other words the so-called Pθ - QV decoupling [5], regulation.
which is a typical of HV networks, is inexistent in The automatic voltage regulation in a distributed man-
MVDNs. The P variations are “coupled” with the voltage ner is a typical topic of the Smart Grids context.
variations. The paper is structured in the following way. In Sec-
If no precautions are taken, in particular network con- tion 1, the proposed voltage control method is shown,
ditions the overcome of the maximum admissible voltage and an overview on the voltage profiles with DG, are
can happen in any nodes. given. In Section 3, the proposed Sensitivity approach is

Copyright © 2010 SciRes. JEMAA


468 Voltage Control in Smart Grids: An Approach Based On Sensitivity Theory

studied, referring to a MV test network, composed by If the generators are able to control the injected or
four nodes. Finally, in Section 4, a numerical application is absorbed reactive power, the network voltage profiles
presented, in order to validate the proposed theory. can be modified by acting on the reactive powers. It is
clear that each controllable generator needs a Generator
2. The Proposed Criteria to Control the Remote Terminal Unit (GRTU) that is connected to a
Network Voltage with Distributed central control system to set the generator reactive power,
Generation (i.e., to control the exciter of the synchronous generators
[1] or act on the inverter control if the generator is in-
Many methods can be used to control the voltage in ne- verter-based) [10,11]. In this work, the central control is
twork nodes (network voltages). The proposed method called the Generator Control Centre (GCC). In addition,
varies the reactive power exchanged between the gen- we use a hierarchical control structure [12,13].
erators and the network while maintaining the OL-TC in Let us suppose that the voltage is measured only in the
a fixed position for a particular load condition. generator nodes by the GRTUs. This assumption does
Let us suppose that the Automatic Voltage Regulator not affect the generality of the proposed method because
(AVR) that controls the OLTC maintains the MV bus-bar a Measuring Remote Terminal Unit connected to the
voltage at the rated value (1 p.u.), assuming that the GCC can be installed in each node that must be controlled.
transformer taps are adequate. When the voltage in the ith node exceeds Vmax , the GR-
For passive grids, when no generators are connected to TU installed in the same node sends the signal “Voltage
the MVDN, the voltage profile (VP; i.e., the voltage Threshold Overall” (VTO) to the GCC using a commu-
values along a line) decreases monotonically (see profile nication channel. The GCC then selects the generator in
a in Figure 1) due to the load absorptions. When the gen- the jth node that has the maximum influence on the volt-
erators are connected and inject power into the MVDN, age of the ith node, the “Best Generator” (BG), and
the nodal voltages increase and the VP is no longer switches it to the reactive power absorption (RPA) mode.
monotonic, as shown in profile b in Figure 1 (profile b). Therefore, the voltage in the ith node tends to decrease.
This phenomenon also occurs if generators work at unitary The problem is thus to determine the best generator
power factor (i.e., only active power is injected due to the and ensure that the GCC chooses it. In this work, a sensi-
non-negligible network resistance) [7]. tivity-based method is proposed to select the BG.
It is important to note that, in steady-state, the con- Moreover, we suppose that the generators can only be
dition maintained at the MV busbar by the AVR decouples switched in the RPA mode by the GCC by a constant
the MV feeders, and the result is that each feeder works power factor. Therefore, if Pj is the active power inject-
without the influence of the other lines. In other words, ted by the generator connected to the jth node, then it ab-
the loads and generators connected to other feeders do sorbs the reactive power Q j = Pj tan φ j (where cos φ j
not influence the VP of the considered line.
is the minimum power factor of the generator) when it is
Typically, the generators installed in Smart Grids are
switched during RPA. In other words, we assume that no
based on renewable energy; therefore, their power-time
continuous reactive power modulation is possible.
profiles are unknown. Due to the high generated power
An example of the procedure described above is shown
and a possibly low load condition, the voltage in some
in Figure 2. Let us suppose that load Ld suddenly de-
nodes can thus exceed the maximum admissible value
creases its power (for example, due to a trip) and V2
( Vmax ; i.e., the voltage threshold [8]) defined by the
standards. exceed Vmax .
Of course the voltage threshold is strictly related with The GRTUs of G2 send the signal VTO to the GCC
the settings of the voltage relays installed in the network, that must choose the BG using the sensitivity method.
e.g. at the generator nodes [9]. Assuming that the BG is G1, it will be switched by the

V V1 V2 VN
Vn b a
HV / MV
x GRTU GRTU GRTU
G1 G2 GN
~
RPA Ld
G G VTO
AVR Load Generator Signal
VB,ref VB MV feeder
MV busbar
GCC
Figure 1. Voltage profiles in a MV feeder with and without
Distributed Generators Figure 2. Voltage control using GRTU and GCC

Copyright © 2010 SciRes. JEMAA


Voltage Control in Smart Grids: An Approach Based On Sensitivity Theory 469

GCC in the RPA mode; therefore, the reactive power After the general treatment, the analysis focuses on a
absorbed by G1 becomes Q1 = P1 tan φ1 . realistic network in which the reactive power can only be
As explained in the following, the GCC must know the controlled in some nodes (generator nodes).
reactive power that each controllable generator can abs- Let us consider the network depicted in Figure 3,
orb in order to choose the BG. We suppose that this in- which is a four-node test MVDN.
formation is acquired by the GCC using a polling tech- The general loads Ld1 …Ld4 are represented using
nique on each GRTU. constant PQ models. Positive P (or Q) corresponds to the
absorbed power by the load. Negative P (or Q) corres-
3. The Proposed Sensitivity Approach ponds to the injected power in the network (i.e., the gene-
3.1 Classical Sensitivity Theory Overview ral load is really a generator). The per-phase equivalent
circuit is shown in Figure 4.
The classical sensitivity theory used in HV network an-
The lines L01…L24 are modeled using the RL-direct
alysis to perform primary and secondary voltage regula-
sequence equivalent circuit [15], but the shunt admittan-
tion [14] is based on the Jacobian Matrix and reveals the ces are neglected. The node 0 represents the MV busbar,
relationships between the nodal voltages (magnitude and
which is regulated at a constant voltage value E0 by the
phase) and the nodal power injections (active and reac-
tive). The relationships mentioned above are represented AVR of the OLTC. This reference voltage coincides with
by the following matrix expression [2]: the rated value E0 = Vn 3 .
−1 Because the busbar is regulated at E0 , we can char-
  ∂P   ∂P  
[ ∆E ]   ∂V   ∂ϑ    [1] [ 0]  ∆P   acterize the generic node i using the difference V0i be-
*

 =  
[1]    ∆Q*  
(1)
[∆ϑ ]   ∂Q   ∂Q   [0]
tween the magnitude of the busbar voltage and the node
   ∂ϑ   voltage Ei . In other words, we can write:
  ∂V   
V0i = E0 − Ei (4)
where [ ∆E ] and [ ∆ϑ ] are, respectively, the nodal
In radial networks, (4) can be calculated as the sum of
voltage magnitudes (rms) and phase variations corre- the voltage differences between adjacent nodes from the
sponding to the nodal active or reactive power injections ith node toward the MV busbar. For example, if i = 3
 ∆P*  and  ∆Q*  ( 1 is the identity matrix).
  (see Figure 4), (4) becomes:
Equation (1) can be rewritten in the following compact V03 = E0 − E3 (5)
form:

[ ∆E ]   ∆P*  
  = [ s ]  
(2) 0 L 1 L12 2 L23 3
[ ∆ ϑ ]    * 

  ∆Q  
01

L24 4
where: HV / MV
−1
Tr . Ld1 Ld2 Ld3
  ∂P   ∂P  
  ∂V   ∂ϑ    [1] Ld4
[ 0 ]
[ s] @     
[1] 
(3)
 ∂Q   ∂Q   [0] Figure 3. The considered four nodes test MVDN
   
  ∂V   ∂ϑ  
is the (injection) sensitivity matrix. The method descries 0 R01 jX 01 1 R12 jX12 2 R23 jX 23 3
above is generally valid, but its computational complexity
is too high for practical voltage analysis in MVDNs. For E0 I S1 IS2 I3
radial networks, only the voltage magnitude is needed to P1 P2 E3 P3
E1 E2
control the nodal voltages. The proposed theory is easier Q1 Q2 R24 Q3
than classical theory, and it is suitable for radial MVDNs.
PS 1 PS 2
3.2 The Proposed Theory jX 24
QS 1 QS 2 E4
In this section, the proposed theory for choosing the BG 4
cos S 1 S1 cos S 2 S2
is outlined. The method is first described in general and I4 P Q
4 4
considers the possibility of reactive power regulation for
all nodes. Figure 4. The per-phase equivalent circuit

Copyright © 2010 SciRes. JEMAA


470 Voltage Control in Smart Grids: An Approach Based On Sensitivity Theory

By adding and subtracting E1 and E2 in (5), we ob- and:


tain: R12 ( P2 + P3 + P4 ) + X 12 ( Q2 + Q3 + Q4 )
V03 = ( E0 − E1 ) + ( E1 − E2 ) + ( E2 − E3 ) V12 ≅ (14)
(6) En
= V01 + V12 + V23
Finally, the voltage difference V01 is:
where V03 is the sum of the voltage differences V01 ,
R01 PS 1 + X 01QS1
V12 and V23 . V01 = E0 − E1 ≅ (15)
En
V23 can be calculated considering the network para-
where:
meters and the line power flows as follows:
PS 1 ≅ P1 + P2 + P3 + P4 (16)
V23 = E2 − E3
QS 1 ≅ Q1 + Q2 + Q3 + Q4 (17)
= R23 I 3 cos ϕ3 + X 23 I 3 sin ϕ3
R23 E3 I3 cos ϕ3 + X 23 E3 I 3 sin ϕ3 are the powers through section S1 .
= (7)
E3 Using (6) with (15), (9) and (8), we can say that V03
R23 P3 + X 23Q3 is a function of all loads and active and reactive powers,
= i.e., P1…P4 and Q1…Q4. The same observation is valid
E3
for E3 :
where cosϕ3 , P3 and Q3 are the power factor and the
E3 = E0 − V03 = E0 − (V01 + V12 + V23 ) (18)
active and reactive (per-phase) powers of the load Ld3,
respectively. I 3 , R23 and X 23 are the current, resis- because E0 is constant. In other words, we can write:
tance and reactance of the line L3. E3 = f ( P1 ,..., P4 , Q1 ,..., Q4 ) (19)
Normally, the nodal voltages are close to the rated
voltage En . Applying this assumption to (7) leads to: Equation (19) shows that an active/reactive power
variation (in the general j node) that is defined as:
R23 P3 + X 23 Q3
V23 ≅ (8)
En ∆Pj = Pj f − Pj 0 (20)
Similarly, considering nodes 1 and 2, we can write: ∆Q j = Q j f − Q j 0 (21)
V12 = E1 − E2
= R12 I 2 cos ϕ S 2 + X 12 I 2 sin ϕS 2 where Pj f ( Q j f ) and Pj 0 ( Q j 0 ) are the final and ini-
R12 E2 I 2 cos ϕS 2 + X 12 E2 I 2 sin ϕ S 2 tial power values, respectively, produces a voltage varia-
= tion in node 3 that is defined as:
E2
(9) ∆E3 = E3 f − E30 (22)
R P + X 12 QS 2
≅ 12 S 2
En In this treatment, we only consider the reactive power
variations (i.e., ∆Pj = 0 ) because we assume that only
where PS 2 and QS 2 are the active and reactive powers
the reactive power can be used to control the node voltages.
through the section S2 and cos ϕ S 2 is the power factor The variation ∆E3 can be calculated by linearizing
for the same section. For PS 2 and QS 2 , we can write: (19) and considering only the reactive power variations.
PS 2 = P2 + P3 + P4 + PR 23 + PR 24 (10) In particular, we can write:
∂E3 ∂E
QS 2 = Q2 + Q3 + Q4 + QX 23 + QX 24 ∆E3 = ∆Q1 + 3 ∆Q2 +
(11) ∂Q1 ∂Q2
(23)
where PR 23 and PR 24 are the power losses in R23 and ∂E ∂E
+ 3 ∆Q3 + 3 ∆Q4
R24 , while QX 23 and QX 24 are the reactive powers ∂Q3 ∂Q4
absorbed by X 23 and X 24 . These active and reactive The terms ∂Ei ∂Q j in (23) indicate the “gain” from
losses are negligible compared to the load powers. Ap-
plying this assumption to (9), (10) and (11) leads to: the voltage variation ∆Ei in node i when a reactive
PS 2 ≅ P2 + P3 + P4 (12) power variation ∆Q j occurs in node j . In other words,
they are sensitivity terms.
QS 2 ≅ Q2 + Q3 + Q4 (13) According to (18), we can obtain:

Copyright © 2010 SciRes. JEMAA


Voltage Control in Smart Grids: An Approach Based On Sensitivity Theory 471

∂E3 X + X 12 − ( X 01 + X 12 ) En
= − 01
∂Q2 En because the powers delivered by node 2 and node 4 flow
∂E3 X + X 12 + X 23 in branches 01 and 12.
= − 01 (24)
∂Q3 En 3.3 The Choice of the Best Generator
∂E3 X + X 12
= − 01 The BG is the generator that has the greatest influence on
∂Q4 En node i , which is the node where the voltage exceeds the
threshold.
Substituting equation group (24) into (23) has important Thus, after analyzing (25), we can say that the BG is
implications. If we have a reactive injection in any node, the generator that maximizes the following product,
i.e., ∆Q j < 0 (in this case j = 1...4 ), then ∆E3 > 0 in which we call the “sensitivity product”:
node 3 (i.e., the voltage increases). Then, if we were to ∂Ei
∆Q j (28)
reduce the voltage in any node, we must abs- orb reactive ∂Q j
power from the network (i.e., ∆Q j > 0 ) by using, for
For example, if the node with a voltage that exceeds
example, the distributed generators. Vmax is i = 2 and the BG is connected to node j = 4 ,
If the above analysis that focuses on node 3 is extended
the sensitivity product ( ∂E2 ∂Q4 ) ∆Q4 is the highest
to all network nodes, (23) has a general matrix relation-
ship: compared to the other products contained in row 2 of the
sensitivity matrix. In addition, in order to choose the BG,
 ∂E1 ∂E1 ∂E1 ∂E1  it is necessary to evaluate the single products (28) of the
 ∂Q ∂Q2 ∂Q3 ∂Q4  row that represents node i . Thus, the value ∆Q j is
 1 
 ∆E1   ∂E2 ∂E2 ∂E2 ∂E2   ∆Q1  needed and is acquired as the GCC polls the GRTUs, as
 ∆E   ∂Q ∂Q2 ∂Q3

∂Q4   ∆Q2 
stated previously.
 2 =  1 (25) The procedure described above suggests a way of de-
 ∆E3   ∂E3 ∂E3 ∂E3 ∂E3   ∆Q3  fining the “sensitivity table” [TS ] that contains the sin-
    
 ∆E4   ∂Q1 ∂Q2 ∂Q3 ∂Q4   ∆Q4  gle sensitivity products. For the MVDN represented in
 ∂E ∂E4 
 4
∂E4 ∂E4
 Figure 4, [TS ] takes the following form
 ∂Q1 ∂Q2 ∂Q3 ∂Q4 
 ∂E1 ∂E1 ∂E1 ∂E1 
which in a compact form yields:  ∂Q ∆Q1 ∂Q2
∆Q2
∂Q3
∆Q3
∂Q4
∆Q4 
 1 
[ ∆E ] =  sQ  [ ∆Q ] (26)  ∂E2
 ∆Q1
∂E2
∆Q2
∂E2
∆Q3
∂E2 
∆Q4 
 ∂Q1 ∂Q2 ∂Q3 ∂Q4 
where  sQ  is the reactive sensitivity matrix, [ ∆Q ] is  ∂E3 
(29)
∂E3 ∂E3 ∂E3
 ∆Q1 ∆Q2 ∆Q3 ∆Q4 
the reactive power-variations vector and [ ∆E ] is the  ∂Q1 ∂Q2 ∂Q3 ∂Q4 
nodal voltages vector.  ∂E ∂E4 ∂E4 ∂E4 
 4 ∆Q1 ∆Q2 ∆Q3 ∆Q4 
Calculating the partial derivatives contained in  sQ  ,  ∂Q1 ∂Q2 ∂Q3 ∂Q4 
we have Equation (27).
Row i represents the node in which we want to co-
After analyzing this form of (27), we can say that this
matrix can be built using the following inspection rule: ntrol the voltage, and column j represents the nodes in
“The element i , j is the arithmetic sum of the reac- which we can control the reactive power. The BG is the
tance of the branches in which both the powers absorbed generator connected to node j that has the maximum
by node i and node j flow multiplied by −1 En ”. absolute value of the sensitivity product in position i , j .
For example, in (27), the element 2, 4 is By finding the maximum sensitivity product in row i ,

 X 01 X 01 X 01 X 01 
 X 01 + X 12 X 01 + X 12 X 01 + X 12 
1 X
 sQ  = −  01 (27)
En  X 01 X 01 + X 12 X 01 + X 12 + X 23 X 01 + X 12 
 
 X 01 X 01 + X 12 X 01 + X 12 X 01 + X 12 + X 24 

Copyright © 2010 SciRes. JEMAA


472 Voltage Control in Smart Grids: An Approach Based On Sensitivity Theory

we automatically choose the BG because the location cl ml


corresponds to column j of the maximum sensitivity pr- bl c m nl
2 d
n
oduct.
b dl G6 p
It is clear that, for a general network with N nodes, the 6 l
0 a e 3 h 5 i q 8 pl
sensitivity table takes the following form: 1 o
f 7
g G5 G7
 ∂E1 ∂E1 ∂E1  ol
 ∂Q ∆Q1 ∂Q2
∆Q2 ...
∂QN
∆QN  VB ,ref VB G4
4 gl
 1 
 ∂E2 
 ∆Q1 ... ... ...  Figure 5. The network considered in the numerical applica-
 ∂Q1  (30) tion
 ... ... ... ... 
  Table 1. Loads characteristics
 ∂E N ∆Q ... ...
∂E N
∆QN 
 ∂Q 1
∂QN
 1  Load S [MVA] cos P [MW] Q [MVAR]

It is important to note that, if it is not possible to bl, nl 2 0.95 1.9 0.62


regulate the reactive power (e.g., if in that node there is a cl 7 0.92 6.44 2.74
load or a non-controllable generator) in a node j , then dl 3 0.92 2.76 1.18
∆Q j = 0 and, consequently, the sensitivity product in gl 2.08 0.95 1.99 0.62
the position i , j of the sensitivity table is 0. ml 2.58 0.93 2.4 0.94
Comparing (29) with (25), we can say that each ele- ol 1.98 0.96 1.9 0.57
ment i , j of [TS ] represents the line-to-ground voltage pl 1.5 0.92 1.38 0.59

variation in node i when a reactive power variation


occurs in node j . Table 2. Generators characteristics
In the following section, a numerical example of the Generator P [MW]
sensitivity method application is shown.
G4 6
4. Application of the Proposed Method G5 1.75

The network considered in this numerical application is G6 4.5


represented in Figure 5. G7 3.75
During normal network operation, we have four ge-
nerators and eight loads. The generator and load charac- Table 3. Lines parameters
teristics are summarized in Table 1 (S is the apparent
power) and Table 2, respectively (three-phase powers Line Name L [km] X [Ω]
are represented in these tables). a, l, q 2 0.34
We suppose that the generators normally operate with b, f, g, i, m, n 1 0.17
a unitary power factor (i.e., no reactive power is injected c, d, o, p 0.5 0.085
in the nodes).
e 15 2.55
The per-kilometer reactance of the cable lines is x =
h 5 0.85
0.17 Ω km , which is a typical value for Italian MVDNs.
The line lengths and parameters are summarized in Ta-
ble 3. If line b trips (e.g., due to a fault), loads bl, cl and dl
Let us suppose that each generator is connected to its are cut off from the supply, which causes the voltage to
GRTU that measures the nodal voltage and communicates increase in the network. In particular, if the load-flow is
with the GCC. Moreover, let us suppose that G5 cannot re-computed to take into account the new network con-
regulate the reactive power because it is not designed for figuration, we obtain the results shown in Figure 6
this purpose. The MV busbar is regulated at the rated (Tripped Line).
voltage (1 p.u.), which is 20 kV (line-to-line). In this It is important to note that, if the voltage exceeds the
example, the voltage threshold Vmax is 1.05 p.u. maximum threshold Vmax in node 5, the GRTU con-
Using load-flow software, we calculated the voltage E nected to G5 sends the VTO signal to the GCC that must
in the generator nodes (nodes 4, 5, 6, and 7) for normal choose the BG using the sensitivity table.
network operation. The results are shown in Figure 6 We suppose that the three-phase reactive powers ab-
(Normal Operation). sorbable by each generator that were collected from the

Copyright © 2010 SciRes. JEMAA


Voltage Control in Smart Grids: An Approach Based On Sensitivity Theory 473

last poll are those summarized in Table 4, which also 1


contains the corresponding power factors cosφ. To cal- t S 5,6 = − ( X a + X e + X h ) ΔQ6
En (34)
culate the sensitivity table, we need the single-phase
powers. Therefore, the reactive powers shown in Table 4 = −98.65 V
have to be divided by three. It is important to note that 1
the reactive powers calculated this way correspond to t S 5,7 = − ( X a + X e + X h ) ΔQ7
En (35)
∆Q j because Q j 0 is zero (see (21)). The ∆Q j values
= −133.07 V
are shown in Table 5.
The voltage exceeds the threshold in node 5. Thus, we The maximum sensitivity product (in absolute value)
only consider the fifth row of the sensitivity table. corresponds to generator 4, (i.e., j = 4 ). Thus, the BG is
According to the inspection rule mentioned above, this G4.
row is as follows: Equation (32) provides important information. If G4
 0 0 0 tS 5,4 tS 5,5 t S 5,6 t S 5,7 0 (31) performs the considered reactive power variation, the
line-to-ground voltage variation in node 5 is:
where the single sensitivity products t S i , j are: ΔE5 = −164.53 V → − 0.0142 p.u. (36)
1 Then, considering (22) (rewritten for node 5), and
t S 5,4 = − ( X a + X e ) ΔQ4 = −164.53 V (32)
En E50 = 1.0502 p.u. from Figure 6, we can say that the
1 voltage value after the reactive power variation is:
t S 5,5 = − ( X a + X e + X h ) ΔQ5 = 0 V (33)
E5 f = E50 + ΔE5 = 1.036 p.u. (37)
En
which is less than the voltage threshold Vmax .
Normal Operation Tripped Line Equation (37) shows the theoretical result obtained
1,055
1,0502 1,0496 1,0498
using the proposed method. We checked this value using
1,05 1,0479 load-flow software:
Node Voltage E [p.u.]

1,045
1,04 E5 f load flow = 1.034 p.u. (38)
1,035
1,03 1,0275
1,0298 1,0292 1,0295 The percentage error between (38) and (37) is:
1,025
E5 f load flow − E5 f
1,02 ε% = ⋅100 = −0.19 % (39)
1,015 E5 f load flow
4 5 6 7
Node Number
which is negligible and demonstrates the validity of the
proposed approach.
Figure 6. Load-Flow results with the Network Normal Op-
eration 5. Conclusions
The proposed sensitivity method allows the voltage wi-
Table 4. Reactive powers absorbable by the generators thin network acting on single generators to be regulated
by choosing the most effective generator on the contr-
Generator Q [MVAR] cosφ olled node (i.e., the Best Generator). This is a very im-
G4 1.97 0.95 portant feature in grids that have distributed generation
G5 0.00 1 (e.g., in a Smart Grid context).
G6 0.91 0.98
The proposed method uses a topological approach. Mo-
reover, the sensitivity table can be constructed automati-
G7 1.23 0.95
cally.
In addition to the BG choice, the proposed method al-
Table 5. Reactive Power Variations in the Generator Nodes so evaluates the voltage in all network nodes after a reac-
tive power variation.
Generator ∆Qj [MVAR] After choosing the BG, but before its commutation du-
G4 0.66 ring RPA, it is possible to verify that the voltage var-
G5 0.00 iation in the other nodes is tolerable for the connected lo-
G6 0.30 ads. Moreover, it is necessary to verify that the threshold
G7 0.41 settings of the voltage relay installed in the same nodes.

Copyright © 2010 SciRes. JEMAA


474 Voltage Control in Smart Grids: An Approach Based On Sensitivity Theory

When a generator is switched during RPA, it works wi- tage Rise Mitigation in Distribution Networks,” IEEE
th a non-unitary power factor; the reactive power flow in- Transactions on Power Systems, Vol. 23, No. 2, 2008, pp.
creases along the lines and increases the power loss [16]. 766-772.
This phenomenon is negligible in HV networks beca- [8] P. N. Vovos, A. E. Kiprakis, A. R. Wallace and G. P.
use the line resistance is typically smaller than the line Harrison, “Centralized and Distributed Voltage Control:
reactance, but is important to consider in MV networks. Impact on Distributed Generation Penetration,” IEEE
Transactions on Power Systems, Vol. 22, No. 1, 2007, pp.
Therefore, if network analysis reveals that the RPA- 476-483.
switching produces high losses, voltage control using the
[9] P. M. Anderson, “Power System Protection,” IEEE Press,
reactive power variation must only be used for temporary Piscataway, 1999.
voltage variation mitigation (i.e., during emergency con-
[10] N. Mohan, T. M. Undeland and W. P. Robbins, “Power
ditions).
Electronics: Converters, Applications, and Design”,
The possible future develops of this work could be fo- Wiley, 1995.
cused on the optimization of the forecasted power-time
[11] M. H. Rashid, “Power Electronics Handbook”, Academic
profiles of the loads and generators applying both the se Press-Elsevier, 2007.
nsitivity approach and distributed voltage measurement.
[12] L. L. Grigsby, “Electric Power Generation, Transmission
and Distribution,” CRC Press-Taylor & Francis Group,
REFERENCES Boca Raton, 2006.
[1] R. Marconato, “Electric Power Systems,” Vol. 2, CEI, [13] F. A. Viawan and D. Karlsson, “Coordinated Voltage and
Milano, 2008. Reactive Power Control in the Presence of Distributed
[2] P. Kundur, “Power System Stability and Control,” McGraw- Generation,” PES General Meeting - Conversion and De-
Hill, New York, 1994. livery of Electrical Energy in the 21st Century, IEEE,
Pittsburgh, 2008, pp. 1-6.
[3] Y. Rosales Hernandez and T. Hiyama, “Distance Measure
Based Rules for Voltage Regulation with Loss Reduc- [14] S. Corsi, “Wide Area Voltage Regulation & Protection”
tion”, Journal of Electromagnetic Analysis and Applica- 2009 IEEE Bucharest Power Tech Conference, Bucharest,
tions (JEMAA), Vol. 1, No. 2, June 2009, pp. 85-91. June 28 -July 2, Bucharest, pp. 1-7.

[4] F. Saccomanno, “Electric Power Systems” [15] A. Gandelli, S. Leva and A. P. Morando, “Topological
Wiley-Interscience IEEE Press, Piscataway, 2003. Considerations on the Symmetrical Components Trans-
formation”, IEEE Transactions on Circuits and Systems I:
[5] G. Andersson, “Modeling and Analysis of Electric Power Fundamental Theory and Applications, Vol. 47, No. 8,
Systems” Lecture 227-0526-00, ITET ETH Zürich, Zürich, August 2000, pp. 1202-1211.
2008.
[16] H. M. Ayres, L. C. P. da Silva, W. Freitas, M. C. de Alm-
[6] Y. Abdel-Rady, I. Mohamed and E. F. El-Saadany “A eida and V. F. da Costa, “Evaluation of the Impact of
Control Scheme for PWM Voltage-Source Distributed- Distributed Generation on Power Losses by Using a Sen-
Generation Inverters for Fast Load-Voltage Regulation sitivity-Based Method,” IEEE Power & Energy Society
and Effective Mitigation of Unbalanced Voltage Distur- General Meeting, Calgary, 2009, pp. 1-6.
bances” IEEE Transactions on Industrial Electronics, Vol.
[17] A. Kishore and E. F. Hill, “Static optimization of Reac-
55, No. 5, May 2008, pp. 2072-2084.
tive Power Sources by use of Sensitivity Parameters”,
[7] P. M. S. Carvalho, P. F. Correia and L. A. F. M. Ferreira, IEEE Transactions on Power Apparatus and Systems,
“Distributed Reactive Power Generation Control for Vol- Vol. PAS-90, No. 3, 1971, pp. 1166-1173.

Copyright © 2010 SciRes. JEMAA

You might also like