You are on page 1of 4

CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005

CO-ORDINATED VOLTAGE REGULATION IN DISTRIBUTION NETWORKS


WITH EMBEDDED GENERATION

Roberto CALDON (*), Silvano SPELTA (**), Valter PRANDONI (**), Roberto TURRI (*)
(*) University of Padova Italy, (**) CESI Italy,
caldon@die.unipd.it, turri@die.unipd.it prandoni@cesi.it, spelta@cesi.it,

INTRODUCTION variations, and relies on the fact that the voltage profile
decreases along the feeders.
The growing diffusion of Distributed Generation in the MV This control action may be further enhanced by providing a
networks is the result of several concurrent factors. line drop compensator which dynamically modifies the
All these factors are changing the way energy is being reference voltage set point of the OLTC (typically switching
generated and consumed and the traditionally passive between two set points, for maximum and minimum loading
distribution networks are starting to become active by the respectively). The values of the set points are usually
integration of distributed generation. determined off-line on the basis of preliminary analysis of the
MV distribution networks are characterised by feeders (aerial two extreme loading conditions, verifying that all network
or buried) with an almost unitary resistance/reactance ratio node voltages are maintained within the permitted range.
which results in relatively high voltage drops and power The presence of DG, with the injection of active and reactive
losses. In the absence of DG, voltage control actions are power, alters the original passive nature of the distribution
traditionally performed by the HV/MV substation OLTC network thus affecting the network voltage profile particularly
transformer, possibly provided by a regulator for line drop in the neighbouring of the DG connections and this calls for a
compensation, and by shunt compensators suitably located radical revision of the control strategies adopted so far [1].
within the network. Particularly stringent is the fact that in each network feeder
The uncontrolled power injection throughout the distribution power may flow in both directions, the voltage profile is no
network provided by the DG, even though it may have a longer decreasing and thus each feeder has different
beneficial effect in terms of power losses and voltage drop regulation voltage requirements. In addition, the variability of
reductions, makes it hard to perform the voltage regulation operation of the independent distributed generators make any
with the traditional control strategies. regulation procedure based on constant (i.e. time
Assuming, as it is normally the case, that it is not possible to independent) voltage settings inadequate to ensure an
control and/or limit the active power production of the effective voltage control [2,3].
distributed independent generators, in this work a co- In fact, with the present reactive regulation practice imposed
ordinated voltage/reactive power control scheme is proposed to a DG (with no certainty that such service is provided by the
which enables the dispersed generator to participate, DG), the System Operator is bound to limit the network
together with the HV/MV substation OLTC transformer, to voltage regulation range by an amount which is constrained
the node voltage regulation of the feeder they are connected by the generator itself. This reduces the available regulation
to, thus ensuring a better voltage profile along the range for new user connections since it is not possible to
distribution feeders. define a fixed power factor which allows to compensate such
The performance of the proposed control scheme has been voltage variations for any load conditions.
tested by dynamics simulations on a case study network
embedding distributed generation of various nature and
size. MT active power MT
HV/MV
OLTC
Cos set point
voltage driver
CO-ORDINATED VOLTAGE CONTROL STRATEGY control
P, Q, V feeder 1 P, Q, V feeder 3
Feeder 1
Traditional distribution systems are characterised, in radial P, Q, V feeder 1 Def. reactive
configurations, by unidirectional power flows, i.e. the entire Cos transit V
Cos set point control Cos DG
active and reactive power demand of the various loads is feeder 3 DG
V
provided by the MV grid which is supplied by the HV P, Q, V feeder 3
Feeder 3

network through the Primary Substation transformer. Def. reactive


transit
Cos DG DG
Cos set point Cos
The voltage regulation relies chiefly on the action of the feeder 1 control

primary substation On-Load Tap-Changer transformer which Feeder n


suitably adjusts its ratio in order to compensate the voltage
drop due to the active and reactive power flowing through it.
OLTC control is based on a local measurement of the MV
bus-bar voltage, which is aimed to be kept almost constant
Figure 1 Principle of operation of the co-ordinated voltage control.
(equal to a desired reference voltage) for a wide range of load

CIRED2005

Session No 3
CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005

DG could, and in the authors opinion should, positively substation transformer and a number of Secondary
contribute to voltage regulation. However, given the Controllers (one for each feeder) for determining the
uncertainties of location, size, characteristics and reference control signals to be communicated to the
dispatching of DG, it is quite challenging, with the present Distributed Generators.
network structure and operational modes, to implement
efficient control strategies [4,5]. Primary Controller
It should be noted that many of the generators used in DG The block diagram of the Primary Controller is shown in fig.
systems have little or no regulation capacities on their own 2 below.
and can only operate in parallel to the network, being unable
to sustain the voltage by themselves. However, for technical PMV
and economic reasons the majority of medium-small sized Cos-set I* + V +
generators are provided of power factor controllers. Vref -
To this issue in the following a control strategy is proposed Iset
+
Vref
which consists of a co-ordinated regulation between a
centralised control, located in the primary substation, and a
distributed reactive power regulation action performed by the Vset
DGs (see fig. 1). The novelty lies in the controller, all the + 1 1 V tr
regulating actions being performed by the existing devices, sTovp 1+sTa
i.e. the OLTC at the primary substation and the power factor -

controllers of the DGs.


VMV
The control principle is based on the fact that in radial passive
Figure 2 - Primary Controller for HV/MV OLTC Transformer
distribution networks, with known load demand and location,
the mean network voltage (i.e. the average value of the main
The controller performs a regulating action for compensating
network nodes) is strictly related to the amount of P and Q (or
the network voltage variations due to the actual MV network
P and cos) flowing through the primary substation
loading deviation with respect to the transformer maximum
transformer. Considering that different feeders have different
loading (represented in terms of current Iset in the control
voltage (and thus power factor) regulation requirements, the
scheme of fig. 2 and it is normally taken as 70% of the
strategy adopted for regulating the voltage distribution
transformer rated current). The network loading (I*) is
throughout the distribution system is based on a power factor
estimated on the basis of the measured active power transit
control of the network power flows.
through the transformer (PMT), the system operator defined
The basic idea is to delegate to the primary substation OLTC,
besides the regulation of the MV bus-bar voltage, the task of reference power factor (Cos-set) and reference voltage level
modulating the reactive power transit through the transformer of the transformer secondary windings (Vref).
in order to maintain a desired power factor (cos-set) and A correction voltage signal (V) equal to
thus to contain the level of the transit current required to
VMAX + VMIN
satisfy the network active load demand. As a result of this V = (I * I set ) + V (1)
action, the primary substation MV bus-bar voltage is I MAX + I MIN
modulated around the desired reference voltage by an amount
proportional to the transformer loading degree. is then generated to be added to Vref. The value V depends
The reactive power regulation is subsequently assigned to the upon the distribution network structure and
DGs, which are forced by their local regulators to inject generation/loading characteristics and represents the voltage
power with a given reference power factor (cos set point) correction to be applied to Vref when the transformer transit
whose value is automatically determined, for each feeder, by current is Iset.
the centralised controller on the basis of the mean voltage This regulation chain enables to perform a sort of voltage
feeder nodes. compounding by setting the reference voltage of the OLTC
In this way each generator, when in operation, would transformer controller (lower part of the regulation chain of
participate to the voltage profile regulation of the feeder fig.2) equal to a voltage level (Vset) proportional to the net
where it is connected to. It should be noted that passive distribution network loading degree. The actual tap-changer
feeders (feeders with temporary or permanent no generation) variation (VTR) is thus determined by comparing the
would also intrinsically benefit by the co-ordinated control, reference (Vset) with the voltage measured at the secondary
since their active and reactive load demand contribute in transformer windings.
determining the transformer loading and, in turn, the reference
cos set points. Secondary Controllers
The block diagram of a feeder Secondary Controller is shown
REGULATION SCHEMES in fig. 3. The function of this controller, one for each feeder
and located in the primary substation, is to elaborate a
The coordinated reactive/voltage controller comprises a suitable reference power factor set point (cosDG-lin) to be
Primary Controller for driving the OLTC of the primary communicated to all DGs connected to that specific feeder.
CIRED2005

Session No 3
CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005

AT/MT
132 / 20
Vn 40 MVA
+ N1
Q SET V V1 +
PLIN 1 - Vmset
1+sTp Q L3 L2 L1
+ N5
+
Cos-set lin N7
Q LIN 1
N2
1+sTq

Vn + Vlim
VmDG1 +
select V2 N6
VmDG2 MAX 1 - 1
DG1
1+sTf sT ~ 3.6 MVA
N9
N3
N8
compute
mean
- Cos-set-DG
1 + Kpfi + 1 +
feeder
VMV voltage 1+sTf sTfi +
1 ~ N4
DG3
1.25 MVA
N12
Figura 3 Secondary Controller for cos control of Feeder transit power

In order to do so, the controller firstly elaborates a reference N11


N10
value of the mean voltage of the feeder nodes (Vmset)
required for maintaining at a desired power factor ( cos-set
lin) the active power transit Plin through the feeder sending ~
DG2
6.25 MVA
end; this can be referred to as the reactive power transit ~ DG4
7.37 MVA

regulator chain, represented by the upper part of the block


diagram of fig. 3. Figure 4 Case study network
In the case of any of the DG bus-bar voltages exceeding the
TABLE I. Main system data
maximum allowed +5% limit, the regulator performs a
Feeder Length Rated Load Rated Gen
decrement of Vmset by a quantity V2 proportional to the 1 24 km 16.2 MW 9.2 Mvar 9.85 MVA
maximum measured DG bus-bar voltage excess. As a result, 2 15 km 10 MW 5 Mvar 0 MVA
the DGs are called to reduce their reactive production (cos- 3 24 km 6.9 MW 2.6 Mvar 8.62 MVA
set-DG is increased). This regulation chain thus actuates a
reactive feedback control action on the system with a As an example, in fig. 5 a selection of simulation results are
stabilising effect. reported considering, for the same sequence of events, the action
The reference power factor set point (cos-set-DG) to be of the OLTC only (left hand side column) and the action of the
assigned to the regulators of the DGs connected to the feeder co-ordinated voltage/reactive control (right hand side column).
is then evaluated by a P+I regulator on the basis of the mean The sequence of events is summarised in Table II.
voltage level measured at all DGs nodes, including substation
TABLE II. Sequence of events
MV bus-bar, compared to the reference voltage (Vmset) Time (sec) Event description
determined by the reactive power transit regulator chain. 0400 sec Initial state with full rated load and DG 1-2-3 at rated
Il should be noted that each secondary controller regulates a power (cos=0.9). HV/MV Transf. loading =75%
mean feeder voltage computed as a weighted average of the 400 sec Intervention of OLTC to increase network voltage
voltage measured at DG terminals and substation busbar. This 600 sec Activation of co-ordinated control (latter simulation only)
800 sec Insertion of DG4 at rated power (cos=0.9).
is only possible provided a suitable continuous information HV/MV Transf. loading =56%
exchange between DGs and primary substation is established.
From fig. 5 it may be seen that the reactive power injection of
CASE STUDY NETWORK DG4 at 800 sec. produces unacceptable increases of Feeder 3 bus
bar voltages (with a negligible effect on Feeder 1 voltages) which
The performance of the proposed control scheme has been cannot be compensated by the OLTC only, whereas with the co-
tested on the case study network reported in fig. 4, ordinated voltage/reactive control all Feeder 3 node voltages are
representing a portion of MV distribution network with four maintained within the permitted range. It is worth noting that such
embedded synchronous generators (5th order models) regulating action is performed primarily by the generators
participating to the network voltage/reactive regulation by connected to Feeder 3 (DG3 and DG4).
means of their own reactive power control systems. The main The network has been modelled on the LegoPC software
system data are listed in Table I. environment (a CESI proprietary dynamic modular code),
On this system both static and dynamic simulations have been while the control schemes are implemented in MATLAB-
carried out covering a wide range of load/generation operating Simulink. Transient simulations have been carried out with
regimes. In all cases the co-ordinated control has demonstrated its LegoSim, a software environment which provides a run-time
capability of regulating the voltage profile along the different link between LegoPC and MATLAB-Simulink.
feeders with excellent stability features.

CIRED2005

Session No 3
CIRED 18th International Conference on Electricity Distribution Turin, 6-9 June 2005

With OLTC regulation only With co-ordinated voltage/reactive regulation


Feeder 1 Node Voltages (kV) Feeder 1 Node Voltages (kV)
22.0 22.0

21.5 21.5
+5% +5%
21.0 21.0

20.5 20.5
N1 N1
20.0 20.0
N11 (DG2) N11 (DG2)
19.5 N2 (DG1) 19.5 N2 (DG1)
-5% -5%
19.0 19.0
18.5 18.5
18.0 18.0
200 400 600 800 1000 1200 1400 200 400 600 800 1000 1200 1400
Time (sec) Time (sec)
Feeder 3 Node Voltages (kV) Feeder 3 Node Voltages (kV)
22.0 22.0
21.5 21.5
+5% +5%
21.0 21.0

20.5 20.5
N1 N1
20.0 20.0
19.5 19.5
N9 (DG3) -5% N9 (DG3) -5%
19.0 19.0
18.5 N10 (DG4) 18.5 N10 (DG4)

18.0 18.0
200 400 600 800 1000 1200 1400 200 400 600 800 1000 1200 1400
Time (sec) Time (sec)
DG Reactive power (MVar) DG Reactive power (MVar)
3.5 3.5

3.0 3.0
2.5 DG2 2.5 DG2

2.0 2.0
DG1 DG1
1.5 1.5
1.0 1.0
DG3 DG3
0.5 0.5
DG4 DG4
0.0 0.0
-0.5 -0.5
200 400 600 800 1000 1200 1400 200 400 600 800 1000 1200 1400
Time (sec) Time (sec)

Fig. 5 Dynamic simulations results: comparison between OLTC regulation and co-ordinated voltage/reactive regulation

CONCLUSIONS This work has been developed in the frame of the research on the
Italian Electrical System Ricerca di Sistema Ministerial Decrees
In this work a novel co-ordinated voltage/reactive power of January 26 - 2000, and April 17 - 2001.
control scheme is presented which enables embedded
generators to participate to the regulation of the distribution REFERENCES
network voltage. An interesting feature of the system is the [1] R.Caldon, V. Prandoni, S. Spelta, R. Turri, 2004, "Control Issues in MV
Distribution Systems with Large-scale Integration of Distributed
capability of satisfying the diverse voltage regulation
Generation", IREP Bulk Power System Dynamics and Control - VI, 22-
requirements of different feeders connected to the primary 27August 2004, Cortina dAmpezzo, Italy
substation. [2] E.Carpaneto, G.Chicco, M.De Donno, R.Napoli, 2004, "Voltage
It is important to remark that the primary and the secondary Controllability of Distribution Systems with Local Generation Sources",
controllers regulate quasi-independent variables (active IREP Bulk Power System Dynamics and Control - VI, 22-27August
power MV network load and reactive power feeders transit) 2004, Cortina dAmpezzo, Italy
acting on the voltage level of the substation MV bus-bar and [3] Leite H., Li H.Y., Jenkins N., 2003, Real-Time Voltage Regulation of
Distribution Networks with Distributed Generation, Proc. of the CIRED
DGs reactive power production respectively. Besides, the 2003, Barcelona, Spain, 12-15 May, 2003.
feeder reactive power control is actuated using a common [4] F.Jiang, S.K.Salman, V.Elaveeti, R.Gupta, 2001, Improvement of
power factor reference for all the DGs connected to the Automatic Voltage Control of On-Load Tap-Changer Transformer in a
feeder. For these features the proposed co-ordinated control Distribution System with Embedded Generators, Proc. 36th Universities
strategy can ensure the dynamic stability of the grid reactive Power Engineering Conference (UPEC2001), Swansea, UK, 12-14
sept., 2001.
power and voltage regulation.
[5] E.F. Mogos, X.Guillaud, 2004, A Voltage Regulation System for
Distributed Generation, IEEE PES Power Systems Conference &
ACKNOWLEDGEMENTS Exibition (PSCE04), New York, US, 10-13 oct., 2004.

CIRED2005

Session No 3

You might also like