Calculation According To en 13384-1, Chimney With Negative Pressure
Calculation According To en 13384-1, Chimney With Negative Pressure
Project: GST
No. Document: 001
Date: 17/09/2017
ENVIRONMENT DATA
Altitude: m 50
Maximum ambient
ºC 15
temperature:
Minimum temperature at the
ºC 0
chimney outlet:
Inside
Installation
building
Wind velocity pressure: NO
CHIMNEY DATA
PRESSURE REQUIREMENTS
Flow safety coefficient SE 1.2
Nominal Minimum
+ Thermal draught in the connection point: PH 19.91 14.02 Pa
- Chimney pressure losses: PR 15.25 1.53 Pa
- Wind velocity pressure: PL 0 0 Pa
Available draught in the connection point: PZ 4.66 12.49 Pa
Fulfills
First pressure requirement: PZ ≥ PZe requireme
nts
At nominal heat output: 4.66 > -3.6 YES
At minimum heat output: 12.49 > -2.96 YES
Fulfills
Second pressure requirement: PZ ≥ PB requireme
nts
At nominal heat output: 4.66 > 0 YES
At minimum heat output: 12.49 > 0 YES
Draught in the installation: PZ - PZe
At nominal heat output: 8.26 Pa
At minimum heat output: 15.45 Pa
Fulfills
First temperature requirement: Tiob ≥ Tg requireme
nts
At nominal heat output: 104.1 > 0 YES
At minimum heat output: 41.2 > 0 YES
SIZING
Nom Min
Average flue gas velocity: m/s 4.9 1.4
Average flue gas temperature: ºC 178 118
Average outer wall temperature: ºC 127 62
CHIMNEY
Chimney system: Dinak SW
Inner diameter: mm 350
Outer diameter: mm ---
Designation according to EN 1856-1: T600 N1 W V2 G
Nom Min
Average flue gas velocity: m/s 4.8 1.4
Average flue gas temperature: ºC 168 108
Average outer wall temperature: ºC 113 53
CHIMNEY OUTLET
Nom
Flue gas velocity: m/s 4.7
Flue gas temperature: ºC 161
Outer wall temperature: ºC 110